Your Reliable Guide for Power Solutions Information Sheet # 12 Concrete Platforms and Mounting Arrangements for Generator Systems 1.0 Introducon This informaon sheet is a guide to the locaon and mounng of engine driven generator set systems. In an ideal situaon the generator set should be mounted on a concrete pad on firm ground, however the designer of a system is frequently challenged with less than ideal mounng situaons, as such this informaon covers the crical criteria that must be followed for any arrangement. Correctly mounted staonary generator systems will give years of dependable service. This informaon sheet gives suitable guidelines and details the applicable codes governing generator set installaons. 2.0 Locaon consideraons If the generator set cannot be located on the ground the building engineer has to confirm if the structure is able to support the weight of the generator set. In locang the generator set the following have to be considered: Load bearing requirements: In addion to the generator set the weight of accessories such as fuel tanks, baeries, radiators, mounng pads and any other equipment has to be known and calculated. An outside installaon will likely have all the accessories already mounted but the all up weight should be known. (See diagram one) Fire codes: Local authories have strict codes controlling the standard of generator set installaon with applicable fire codes. Water protecon: Ensure the locaon is not prone to ground water flooding or water from any other source such as the rain. An indoor installaon should be a structure not suscepble to flooding from ground water or problems with water ingress due to the weather. Equipment has to be protected from corrosion and for safety no electrical components should be allowed to get wet or be adjacent to wet surfaces. Any out door installaon should be fied with the appropriate weather protecve enclosure and on a plaorm that sits above known flood levels. Check the local code requirements. (connued over) 4 3 5 7 8 6 Diagram 1 Key issues to note with outside installations Consult a licensed installation contractor before installing any generator set. Consult local and NEC codes. 1) When mounted on a sub-base tank, access should be provided to operate and service controls. Consult local codes for platform and stairs access. 2) Stub-up for electrical conduits has to be provided and access allowed through sub-base tank. See manufacturer drawings for location. 3) Access steps to controls for operation and service are required due to sub base tank height. 4) Concrete pad should meet local codes and allow full service access around the generator set. 5) Sub-base tank has to meet required UL and any local codes and be rated to carry the generator set weight. 6) Housing should provide adequate weather protection to generator equipment plus ventilation for cooling. 7) Exhaust muffler should meet local sound ordinance codes and safely vent to atmosphere. 8) The location of the mounting pad and generator set should provide proper maintenance, testing, flow of exhaust gases and cooling air flows. Particular attention must be made to radiator placement for obstructions to air flow and prevailing wind considerations (dirt, debris and snow contamination). Sub-base fuel tanks can greatly increase the height of an installation and provision should be made to read and service controls 1 2 The installation information provided in this information sheet is informational in nature only, and should not be considered the advice of a properly licensed and qualified electrician or used in place of a detailed review of the applicable National Electric Codes and local codes. Specific questions about how this information may affect any particular situation should be addressed to a licensed and qualified electrician. To fulfill our commitment to be the leading supplier and preferred service provider in the Power Generation Industry, the Central Power Systems & Services team maintains up-to-date technology and information standards on Power Industry changes, regulations and trends. As a service, our Information Sheets are circulated on a regular basis, to existing and potential Power Customers to maintain awareness of changes and developments in engineering standards, electrical codes, and technology impacting the Power Generation Industry.

Upload: phamminh

Post on 03-Jul-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Concrete Platforms and Mounting Arrangements for Generator ...cpower.com/PDF/InfoSheets/12.pdf · Concrete Platforms and Mounting Arrangements for Generator Systems ... Before deciding

Your Reliable Guide for Power Solutions

Information Sheet # 12

Concrete Platforms and Mounting Arrangements for Generator Systems

1.0 IntroductionThis information sheet is a guide to the location and mounting of engine driven generator set systems. In an ideal situation the generator set should be mounted on a concrete pad on firm ground, however the designer of a system is frequently challenged with less than ideal mounting situations, as such this information covers the critical criteria that must be followed for any arrangement.Correctly mounted stationary generator systems will give years of dependable service. This information sheet gives suitable guidelines and details the applicable codes governing generator set installations.2.0 Location considerationsIf the generator set cannot be located on the ground the building engineer has to confirm if the structure is able to support the weight of the generator set. In locating the generator set the following have to be considered:

Load bearing requirements: In addition to the generator set the weight of accessories such as fuel tanks, batteries, radiators, mounting pads and any other equipment has to be known and calculated. An outside installation will likely have all the accessories already mounted but the all up weight should be known. (See diagram one)Fire codes: Local authorities have strict codes controlling the standard of generator set installation with applicable fire codes.Water protection: Ensure the location is not prone to ground water flooding or water from any other source such as the rain. An indoor installation should be a structure not susceptible to flooding from ground water or problems with water ingress due to the weather. Equipment has to be protected from corrosion and for safety no electrical components should be allowed to get wet or be adjacent to wet surfaces. Any out door installation should be fitted with the appropriate weather protective enclosure and on a platform that sits above known flood levels. Check the local code requirements. (continued over)

4

3

5

78

6

Diagram 1 Key issues to note with outside installations

Consult a licensed installation contractor before installingany generator set. Consult local and NEC codes.

1) When mounted on a sub-base tank, access should be provided to operate and service controls. Consult local codes for platform and stairs access.2) Stub-up for electrical conduits has to be provided and access allowed through sub-base tank. See manufacturer drawings for location.3) Access steps to controls for operation and service are required due to sub base tank height.4) Concrete pad should meet local codes and allow full service access around the generator set.5) Sub-base tank has to meet required UL and any local codes and be rated to carry the generator set weight.6) Housing should provide adequate weather protection to generator equipment plus ventilation for cooling.7) Exhaust muffler should meet local sound ordinance codes and safely vent to atmosphere.8) The location of the mounting pad and generator set should provide proper maintenance, testing, flow of exhaust gases and cooling air flows. Particular attention must be made to radiator placement for obstructions to air flow and prevailing wind considerations (dirt, debris and snow contamination).

Sub-base fuel tanks can greatly increase the height of an installation and provision should be made to read and service controls

1

2

The installation information provided in this information sheet is informational in nature only, and should not be considered the advice of a properly licensed and qualified electrician or used in place of a detailed review of the applicable National Electric Codes and local codes. Specific questions about how this information may affect any particular situation should be addressed to a licensed and qualified electrician.

To fulfill our commitment to be the leading supplier and preferred service provider in the Power Generation Industry, the Central Power Systems & Services team maintains up-to-date technology and information standards on Power Industry changes, regulations and trends. As a service, our Information Sheets are circulated on a regular basis, to existing and potential Power Customers to maintain awareness of changes and developments in engineering standards, electrical codes, and technology impacting the Power Generation Industry.

Page 2: Concrete Platforms and Mounting Arrangements for Generator ...cpower.com/PDF/InfoSheets/12.pdf · Concrete Platforms and Mounting Arrangements for Generator Systems ... Before deciding

CPSS-INFO#12 2013 PLC Enterprises, LLC

Colby, KS Branch1920 Thielen Ave.KS 67701785.462.8211 Ph785.462.8286 Fax

Liberty - Corporate Office9200 Liberty DriveLiberty, MO 64068816.781.8070 Ph816.781.2207 Fax

Woodward, OK Branch127 NW Hwy. 270OK 73801580.256.6014 Ph580.256.0314 Fax

Springfield, MO Branch3100 E. KearneyMO 65803417.865.0505 Ph417.865.4304 Fax

www.cpower.com

Wichita, KS Branch4501 W. IrvingKS 67209316.943.1231 Ph316.943.4560 Fax

Great Bend, KS Branch625 E. 10th St.KS 67530620.792.1361 Ph620.792.1364 Fax

Liberty, MO Branch1900 Plumbers WayLiberty, MO 64038816.415.6700 Ph816.415.6767 Fax

Liberal, KS Branch1150 E. Hwy. 54KS 67901620.624.7274 Ph620.624.7277 Fax

Salina, KS Branch1944B N. 9th St.KS 67401785.825.8291 Ph785.825.8282 Fax (Continued from page-one)

Positioning: Before deciding on the position ensure the generator is not located near combustible material, a porous surface susceptible to fuel, coolant, battery acid and oil. (if so containment should be designed into the system to meet local codes)Access: Ensure there is easy access to the generator set to carry out checks, routine service and overhaul.Access for fuel tank mounted installation: When the generator set is mounted on a sub-base fuel tanks that significantly increases the overall height of the unit, the system designer has the responsibility to ensure controls and other equipment can be easily accessed for operation and service. If access can only be achieved by means of a ladder or access platform the designer has to ensure the design of the installation meets local codes. Ventilation: The unit should have sufficient ventilation for combustion and coolant air. If the natural ambient airflow is not sufficient then the designer will have to design ducts for adequately ventilating inlet and exhaust air flow.Exhaust: Ensure there is adequate expulsion of the exhaust to prevent the build up of dangerous exhaust gases.Fuel systems: The location of the fuel tank should allow for the vertical lift specification of the fuel pump and any auxiliary pumps within the system. Frequently even with a remote bulk storage of fuel a day tank will be adjacent to the generator set.Security: For safety and protection of vital standby power the installation should minimize public/ unauthorized accessOutside installations: In addition to providing all round access for operation and service the design should specify in accordance with codes an installation that is not hindered in access or operation by vegetation or other structures.

3.0 Mounting Surface:All mounting surfaces should be level and firm enough to bear the load of the generator set and accessories.There are various mounting configurations as follows. (Diagram two details typical arrangement points)

Single-pad mounting: This is the most common mounting arrangement. A single level concrete pad (diagram three) provides for a firm level surface that supports the weight of the generator set and prevents any distortion of the base. With this method it may be necessary to provide an oil drain pump or raise the generator set above the pad to allow clearance for draining. Mounting pad weight: Recommendations are that the single mounting pad or combined weight of two and four mounting pads should be at least the total weight of the generator set and its mounted accessories.Guide to determining pad weight: The volume of the pad(s) in cubic feet (length x width x height) multiplied by 150 lbs gives weight of the pad. The designer should determine if this weight comes within the load bearing limits of the location.Mounting pad specifications: The composition of the mounting pad should follow standard practice for required loadings. The specification with 2500-3000 psi is for concrete reinforced with eight-gauge wire mesh of #6 reinforcing bars on 12” centers.Concrete mixture: The recommended mixture by volume is given as 1:2:3 parts of cement, sand and aggregate, respectively. The generator set should be anchored to the pad using bolts set in the concrete. (Expansion anchors should not be used)

4.0 Conduit entry:When the generator set is mounted on the concrete pad provision should be made to receive the electrical conduit. The area where the cables come up through the pad is called the “stub-up.” The system designer has to ensure the stub-up location is optimally placed to the generator set’s load and control terminal connections. Also, when the generator set is mounted on a sub-base fuel tank the designer has to ensure the electrical conduit entry of the sub tank is optimally located to the generator set terminals.(See diagram one for details of an outdoor installation, sub-base fuel tank and stub-up location)

3

5

7

6

1

2

4

3

3

Mounting surface - diagram two

1. Engine end

2. Generator set skid

3. Concrete should extend 6” outside skid

4. Battery rack (Outside installation will have set inside base frame)

5. Allow at least 18” access around the set

to assist service

6. Alternator end

7. Mounting pad (concrete surface)

1. Exhaust thimble 2. Silencer 3. Supports 4. Flexible section 5. Duct work for cooling air outlet 6. Mounting base7. Controller8. Electrical conduit9. Water trap with drain10. Fresh air intake

6

7

8

4

1

9

2

5

Sample stationary generator set inside installation - diagram three

3

Single pad arrangement