construction of proposed up police bhawan at gomti … · ,bounadry wall and gate hoseses...
TRANSCRIPT
in figures in words
1
CIVIL WORKS INCLUDING LOOSE
FURNITURE ,EXTERNAL DEVELOPMENT
,BOUNADRY WALL AND GATE HOSESES
5108247004.24
2
PLUMBING WATER SUPPLY ,SEWERGADE
SYSTE INCLUDING SEWAGE TREATMENT
PLANT AND FIRE FIGHTING WORKS
220,921,779.58
3 ELECTRICAL WORKS 617838825.74
4 TELECOMMUNICATION SYSTEM 19357800.00
5 HVAC SYTEM 371566500.38
6CENTRAL CONTROL STATIONS FOR BAS &
FAS SYSTEM17206954.00
7
AUDITORIUM-ACOUSTIC,STAGE LIGHTING
PROJECTION AND SOUND SYSTEM SPECIAL
SERVICES
54314905.00
TOTAL ESTIMATED COST 6409453768.94
SIGNATURE OF BIDDER WITH STAMPSIGNATURE OF UPRNN.LTD (WITH STAMP)
% above/ belowTOTAL AMOUNT
AMOUNT ABOVE OR
BELOW (+) OR (-)
CONSTRUCTION OF PROPOSED UP POLICE BHAWAN AT GOMTI NAGAR EXTENSION AT LUCKNOW.UP
S.NO. PARTICULARSESTIMATED COST
IN INR
BIDDER'S PRICE
Stup Consultants P.Ltd 1 of 234
1 EARTH WORK 126634150.81
2 CONCRETE WORK 370120860.10
3 REINFORCED CONCRETE WORK 2204537864.07
4 BLOCK MASONRY WORK 54635302.20
5 STONE WORK 74345.00
6 MARBLE WORK 30296843.10
7 WOOD WORK AND PVC WORK 250629109.22
8 STEEL WORKS 48002175.10
9 FLOORING 231927017.05
10 ROOFING 251825580.01
11 FINISHING 201638483.05
12 PILING WORK 239246046.70
13 ALUMINIUM WORK 53553795.55
14 WATER PROOFING OF MAIN BUILDINGS AND WATER TANKS 222655835.34
15 GLAZINGAND CURTAIN WALLS WORK 333639870.85
16 STAINLESS STEEL RAILINGS AND OTHER WORKS 191284332.00
17 LOOSE FURNITURE 234175962.00
18 EXTERNAL DEVELOPMENT WORKS, LAND SCAPING AND WATER FEATURES, 33888502.98
19 BOUNDARY WALL AND GATE HOUSES 29480929.11
5108247004.24
CONSTRUCTION OF PROPOSED UP POLICE BHAWAN AT GOMTI NAGAR
EXTENSION AT LUCKNOW.UP
Total Cost of Civil Work
S.No. Name of Sub - Head
A SUMMARY OF COST OF CIVIL WORKS
RATES IN INR
Stup Consultants P.Ltd 2 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
1.0 EARTH WORK
1.1 Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5
m in width as well as 10 sqm on plan including disposal of excavated earth upto 50
m and lift upto 1.5 m, disposed soil to be levelled and neatly dressed :
( Note : Excavated earth have to be preserved , for re use in horticulture works , at
the locations as directed by the Engineer In Charge )
1.1.1 All kinds of soil 100
sqm
50 5044.15 2522.075
1.2 Earth work in excavation by mechanical means (Hydraulic excavator) / manual
means over areas (exceeding 30cm in depth. 1.5m in width as well as 10 sqm on
plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5m,
disposed earth to be levelled and neatly dressed.
1.2.1 All kinds of soil cum 320918 92.00 29524456.00
1.2.1.1 Extra for every additional lift of 1.5m cum 55683 46.25 2575338.75
1.2.1.2 Extra for every additional lift of 3.0m to 4.5 m cum 55683 92.50 5150677.50
12.1.3 Extra for every additional lift of 4.5m to 6.0m cum 55683 138.75 7726016.25
1.2.1.4 Extra for every additional lift of 6.0m to 7.50m cum 55683 185.00 10301355.00
1.2.1.5 Extra for every additional lift of 7.5m to 9.0m cum 29698 231.25 6867662.50
1.3 Earth work in excavation by mechanical means (Hydraulic excavator) / manual
means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on
plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including
getting out the excavated soil and disposal of surplus excavated soil as directed,
within a lead of 50 m.
1.3.1 All kinds of soil cum 1070 157.50 168525.00
1.4 Excavating trenches of required width for pipes, cables, etc including excavation
for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m,
including getting out the excavated soil, and then returning the soil as required, in
layers not exceeding 20 cm in depth, including consolidating each deposited layer
by ramming, watering, etc. and disposing of surplus excavated soil as directed,
within a lead of 50 m :
1.4.1 All kinds of soil
1.4.1.1 Pipes, cables etc. exceeding 300 mm dia but not
exceeding 600 mm
metre 200 325.20 65040.00
1.5 Filling available excavated earth (excluding rock) in trenches, plinth, sides of
foundations etc. in layers not exceeding 20cm in depth, consolidating each
deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
cum 775 112.40 87110.00
1.6 Supplying and filling in plinth with Jamuna sand under floors,empty bores ,
including watering, ramming, consolidating and dressing complete.
cum 9011 910.25 8202262.75
1.7 Surface dressing of the ground & excavated bottom including removing vegetation
and inequalities not exceeding 15 cm deep and disposal of rubbish, lead upto 50 m
and lift upto 1.5 m.
1.7.1 All kinds of soil 100sq 4020 1245.75 5007915.00
1.8 Supplying & filling approved earth (excluding rock) brought from outside in
trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth,
consolidating each deposited layer by ramming and watering, lead upto 50 m and
lift upto 1.5 m.
Cum 2775 324.00 899100.00
CONSTRUCTION OF PROPOSED UP POLICE BHAWAN AT GOMTI NAGAR EXTENSION AT
LUCKNOW.UP
BILL OF QUANTITIES FOR CIVIL WORKS
(A) If in any of the item described below contains a product / catalogue number of a particular brand then it is merely an indication of the specification
/design of the particular relevant item and the bidder may be asked to provide /use any of the brand mentioned in the list of approved makes attached
with the technical specifications and he should get the same approved from the Engineer In charge and Consultant Architect before placing the order.
( B ) The work shall be executed by an approved agency and It will be responsibility of the contractor on board to get approved Samples of the
materials to be used & shop drawings from the consultant Architect.
( C ) Rates quoted shall be for all heights and levels unless other vise specified . Flat area in horizontal / vertical plane will be measured for payment
of plastering and painting etc. deductions for openings shall be made as per the IS 1200 /CPWD Specifications 2009 with up to date correction slips
.No additional payment will be made for ,attending of broken edges ,corners or patches of plastered surface , grooves /patterns , cornices, moldings ,
preparing the base surface for painting and polishing,staging,scaffolding,vatta, 'shuttering of edges of slabs ,breaks in floors and walls', 'treating of
construction joints in RCC ,opening for sleeves and holes of tie roads with cementetious grout or any other specified item being used for the same
location 'etc. cost of the same deem to be included in the quoted rates .BOQ,Special conditions of contract ,Technical specifications and tender
drawings are complimentary to each other and should be referred together ,no claim in this regard shall be admissible.
GENERAL NOTES FOR CIVIL WORKS ,GATE HOUSE ,BOUNDARY WALL ,ROAD $EXTERNAL DEVELOPMENT
WORK AND ACOUSTICS ETC :-
Stup Consultants P.Ltd 3 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
Providing pre-constructional Anti-termite treatment by treating bottom surface
and sides of excavation, fill in immediate contact with foundation / raft slabs
/ pile caps / retaining wall (at the rate of 5 litres of an emulsion concentrate of
1.0 percent of Chlorpyrifos 20EC or equivalent approved chemical per square
meter of surface area), treatment to the soil along with external perimeter of the building,
retaining wall etc. by punching holes of 12 to 15 mm diameter about 300 to 600
mm deep at 150 mm centre to centre as close to the wall as possible and inject
1.0%
Chloropyrifos at the rate of 7.5 litres emulsion concentrate per hole and sealing
the same with proper filling etc. complete through approved manufacturers with 10
years guarantee bond and as per specifications complete (IS 6313 part II)
Sqm. 3613 250.00 903250.00
Note : 1) The horizontal area of the basement raft for all the above activities shall
be measured for payment
2) The contractor shall furnish a guarantee for a minimum period of ten years to
maintain the treated area / structure free from termite.
1.9.1 Disposal of excavated earth/excavated rock by mechanical transport including
loading , unloading and stacking( Rate shall be applicable for net quantity after
deduction of prescribed rate of voids )
1.9.1.2 Earth upto 5 KM cum 321114 153.07 49152919.98
SUB TOTAL (EARTHWORK) 126634150.8
2 CONCRETE WORK
2.1 Providing and laying in position cement concrete of specified grade excluding the
cost of centering and shuttering - All work up to plinth level :2.1.1 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size). cum 50 3790.00 189500.00
2.2 Centering and shuttering including strutting, propping etc. and removal of form for :
2.2.1 Foundations, footings, bases for columns sqm 1602 196.45 314712.90
2.3 Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1
cement : 2 coarse sand : 4 graded stone aggregate 12.5mm nominal size).
sqm 20 257.8 5156.00
2.4 Applying a coat of residual petroleum bitumen of grade of VG-10 of approved
quality using 1.7kg per square metre on damp proof course after cleaning the
surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil.
sqm 20 132 2640.00
2.5 Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement :3 coarse
sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry
brick ballast 40 mm nominal size, well rammed and consolidated and grouted with
fine sand including finishing the top smooth
sqm 850 419.3 356405.00
2.6 Providing and laying in position ready mixed plain cement concrete, using fly ash
and cement content as per approved design mix and manufactured in fully
automatic batching plant and transported to site of work in transit mixer for all
leads, having continuous agitated mixer, manufactured as per mix design of
specified grade for plain cement concrete work, including pumping of R.M.C. from
transit mixer to site of laying and curing, excluding the cost of centering, shuttering
and finishing, including cost of curing, admixtures in recommended proportions as
per IS : 9103 to accelerate/ retard setting of concrete, improve workability without
impairing strength
and durability as per direction of the Engineer - in - charge.
Note : (1) Excess/less cement used than specified in this item is payable/
recoverable separately. (2) Fly ash conforming to grade I of IS 3812 (Part- 1) only
be used as part replacement of OPC as per IS : 456. Uniform blending with cement
is to be ensured in accordance with clauses 5.2 and 5.2.1 of IS: 456 -2000 in the
items of BMC and RMC.
2.6.1 All works upto plinth level
2.6.1.1 M-15 grade plain cement concrete (cement content considered @ 240 kg/cum). Cum 3582 5872.90 21036727.80
1.9
Stup Consultants P.Ltd 4 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
2.7 Providing and laying in position and compaction as specified machine mixed plain
cement concrete using well graded sand and coarse aggregate with embedding 30%
hard stone plums of 130 to 230mm size including all necessary dewatering, form
work, casting in panels of any size and thickness wherever necessary, in 1: 3: 6 (1
part cement: 3 part sand: 6 part Stone aggregate) mix concrete to shape and depth
as specified curing, etc., complete as directed by the Engineer.
Cum 81086 4294.40 348215718.40
SUB TOTAL (CONCRETE WORK)370120860.1
3 REINFORCED CEMENT CONCRETE WORK
3.1 Providing and laying in position specified grade of reinforced cement concrete
excluding the cost of centering, shuttering, finishing and reinforcement - All work up
to plinth level :
3.1.1 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cum 10 5725.90 57259.00
3.2 Reinforced cement concrete work in walls (any thickness), including attached
pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers,
abutments, posts and struts etc. up to floor five level excluding cost of centering,
shuttering, finishing and reinforcement :
3.2.1 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal
size)
cum 10 7074.3 70743.00
3.3 Providing and laying up to floor five level reinforced cement concrete in kerbs,
steps and the like excluding the cost of centering, shuttering, finishing and
reinforcement with 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20
mm nominal size).
cum 10 6362.85 63628.50
3.4 Reinforced cement concrete work in arches, archribs, domes, vaults, shells, folded
plate and roofs having slope more than 15° up to floor five level, excluding the cost
of centering, shuttering, finishing and reinforcement, with 1:2:4 (1 cement : 2
coarse sand : 4 graded stone aggregate 20 mm nominal size).
cum 10 7,047.25 70472.50
3.5 Reinforced cement concrete work in vertical and horizontal fins individually or
forming box louvers, facias and eaves boards up to floor five level excluding the
cost of centering, shuttering, finishing and reinforcement with 1:1½:3 (1 cement :
1½ coarse sand : 3 graded stone aggregate 20mm nominal size).
Cum 10 6690.80 66908.00
3.6 Centering and shuttering including strutting, propping etc. and removal of form for :
3.6.1 Foundations, footings, bases of columns, etc. for mass concrete. sqm 11096 196.45 2179809.20
3.6.2 Walls (any thickness) including attached pilasters, butteresses, plinth and string
courses etc.
sqm 56074 360.8 20231499.20
3.6.3 Suspended floors,drop papans , roofs, landings, balconies and access platform. sqm 144617 401.65 58085418.05
3.6.4 Shelves (Cast in situ) sqm 401.65
3.6.5 Lintels, beams, plinth beams, girders, bressumers and cantilevers. sqm 45432 332.15 15090238.80
3.6.6 Columns, Pillars, Piers, Abutments, Posts and Struts. sqm 27092 453.35 12282158.20
3.6.7 Stairs, (excluding landings) except spiral-staircases. sqm 8425 395.65 3333351.25
3.6.10 Vertical and horizontal fins individually or forming box louvers band, facias and
eaves boards
sqm 400 587.35 234940.00
3.6.11 Extra for shuttering in circular work (20% of respective centering and shuttering
items)
3.6.11.1 For Columns sqm 27092 90.67 2456431.64
3.6.11.2 For beams sqm 20 66.43 1328.60
3.6.12 Small lintels not exceeding 1.5m clear span, moulding as in cornices, window sills,
string courses, bands, copings, bed plates, anchor blocks and the like.
sqm 1020 196.45 200379.00
3.6.13 Edges of slabs and breaks in floors and walls
3.6.13.1 Under 20 cm wide metre 200 116.40 23280.00
3.6.13.2 Above 20 cm wide sqm 50 508.55 25427.50
3.6.15 Small surfaces such as cantilever ends, brackets and ends of steps, caps and
bases to pilasters and columns and the like
sqm 50 483.70 24185.00
3.6.16 Weather shade, Chajjas, corbels etc., including edges. sqm 225 492.35 110778.75
3.7 Extra for additional height in centering, shuttering where ever required with
adequate bracing, propping etc. including cost of de-shuttering and decentering at
all levels, over a height of 3.5 m, for every additional height of 1 metre or part
thereof (Plan area to be measured)
(Item shall be operated for payment of staging/access plateforms for
shuttring of more than 3.5M height only)
3.7.1 Suspended floors, roofs, landing, beams and balconies (Plan area to be
measured).
sqm 296419 159.05 47145441.95
3.8 Providing, hoisting and fixing up to floor five level precast reinforced cement
concrete work in string courses, bands, copings, bed plates, anchor blocks, plain
window sills and the like including the cost of required centering, shuttering but
excluding cost of reinforcement, with 1:2:4 (1 cement: 2 coarse sand: 4 graded
stone aggregate 20mm nominal size).
cum 50 6447.95 322397.50
Stup Consultants P.Ltd 5 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
3.9 Providing, hoisting and fixing up to floor five level precast reinforced cement
concrete in small lintels not exceeding 1.5m clear span up to floor five level
including the cost of required centering, shuttering but excluding the cost of
reinforcement, with 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate
20mm nominal size).
cum 50 8797.80 439890.00
3.10 Providing, hoisting and fixing precast reinforced cement concrete in cover slabs,
gratings, lintels, beams and bressumers, including setting in cement mortar 1:3 (1
cement : 3 coarse sand), cost of required centering and shuttering but excluding the
cost of reinforcement, with 1:2:4 (1 cement:2 coarse sand : 4 graded stone
aggregate 20 mm nominal size).
3.10.1 Up to floor five level cum 30 8953.65 268609.50
3.11 Steel reinforcement for R.C.C. work including straightening, cutting, bending,
placing in position and binding all complete upto plinth level.
3.11.1 Thermo-Mechanically Treated bars kg 9824000 68.10 669014400.00
3.12 Steel reinforcement for R.C.C. work including straightening, cutting, bending,
placing in position and binding all complete above plinth level.
3.12.1 Thermo-Mechanically Treated bars kg 5718000 68.10 389395800.00
3.13 Providing and fixing in position to exact profile high tensile prestressing steel
(12T13 ) confirming to low relaxation pre stressing steel strands – Cl. II as per IS
14268 of specified ultimate strength, including cutting, forming cables etc. and
further including laying bright metal / HDPE sheathing of specified dia, anchorages
stage wise stressing,, grouting and all enabling work including staging / scaffolding
/ necessary working platform for pre tensioning / post tensioning of steel etc.
complete as directed by engineer and conforming to specification Section 1800 of
MoRTH
MT 912 104724.00 95508288.00
3.14 Extra for laying reinforced cement concrete in or under water and/ or liquid mud,
including cost of pumping or bailing out water and removing slush etc., complete.
Note For BOQ Item No. 3.18:- The quantity will be calculated by multiplying the
depth measured from the subsoil water level up to the centre of gravity of the
R.C.C. under subsoil water with the quantity of R.C.C. in cubic metre executed
under subsoil water. The depth of centre of gravity shall be reckoned correct to 0.1
m. 0.05 m or more shall be taken as 0.1 m and less than 0.05 m ignored. No extra
payment shall be made for placing reinforcement or centering & shuttering under
sub - soil water conditions.
(This item shall be operated for special conditions only and with written instructions
of Engineer Incharge only.)
Cum 23001 426.15 9801876.15
3.15 Extra for providing richer mixes at all floor levels.
Note:- Excess/less cement over the specified cement content used is payable
/recoverable separately.
3.15.1 Providing M-30 grade concrete instead of M-25 grade BMC/RMC. (Note:- Cement
content considered in M-30 is @ 340 kg/cum).
cum 110107 76.50 8423185.50
3.15.2 Providing M-35 grade concrete instead of M-25 grade BMC/RMC. (Note : Cement
content considered in M-35 is @ 350 kg/cum).
cum 50 152.95 7647.50
3.15.3 Providing M-40 grade concrete instead of M-25 grade BMC/RMC.(Note : Cement
content considered in M-40 is @ 360 kg/cum).
cum 50 299.45 14972.50
3.16 Add for using extra cement in the items of design mix over and above the specified
cement content therein.
quintal 33451.5 742.75 24846101.63
3.17 Extra for R.C.C./ B.M.C/ R.M.C. work above floor V level for each four floors or part
thereof
cum 26755 174.20 4660721.00
Stup Consultants P.Ltd 6 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
3.18 Providing and laying in position ready mixed M-25 grade concrete for reinforced
cement concrete work, using fly ash and cement content as per approved design
mix, and manufactured in fully automatic batching plant and transported to site of
work in transit mixer for all leads, having continuous agitated mixer, manufactured
as per mix design of specified grade for reinforced cement concrete work, including
pumping of R.M.C. from transit mixer to site of laying, excluding the cost of
centering, shuttering, finishing and reinforcement, including cost of admixtures in
recommended proportions as per IS : 9103 to accelerate / retard setting of
concrete, improve workability without impairing strength and durability as per
direction of the Engineer - in - charge.
NOTE- (1) Cement content considered in this item is @ 330 kg/cum. Excess/ less
cement used as per design mix is payable/ recoverable separately.
(2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part
replacement of OPC as per IS : 456. Uniform blending with cement to be ensured
in accordance with clauses 5.2 and 5.2.1 of IS:456 -2000 in the items of BMC and
RMC.
3.18.1 All works up to Plinth level
(foundations ,walls,pedistals,slabs and stairs etc.)
cum 76039 6561.20 498907086.80
3.18.2 All works above plinth & up to floor V leve cum 36180 7279.60 263375928.00
3.19 Supplying and applying pre tested and approved water based concrete curing
compound to concrete/ masonry surface, all as per manufacturer’s specification
and direction of Engineer-in-charge.
3.19.1 Pigmented wet curing compound Sqmt 353210 120.70 42632447.00
3.20 Providing and fixing tapered / parallel threaded couplers conforming to IS code on
"Reinforcement Couplers for Mechanical Splices of Bars for Concrete
Reinforcement – Specification", to reinforcement bars including threading,
enlargement at connection by forging, protecting the prepared reinforcement bars
and related operations as required to complete the works per direction of Engineer-
in-Charge . (The length of the bars in which coupler is to be provided should not be
less than 4 metre, no deduction for labour and binding wire saved for not providing
lap length shall be made).
3.20.1 Coupler for 16 mm diameter reinforcement bar each 50 122.35 6117.50
3.20.2 Coupler for 20 mm diameter reinforcement bar each 125 166.45 20806.25
3.20.3 Coupler for 25 mm diameter reinforcement bar each 150 230.20 34530.00
3.20.4 Coupler for 28 mm diameter reinforcement bar each 125 316.90 39612.50
3.20.5 Coupler for 32 mm diameter reinforcement bar each 175 367.65 64338.75
3.21 Expansion Joint
3.21.1 Providing and fixing of expansion joint system related with floor location as per
drawings and direction of Engineer-In-Charge. The joints system will be of
extruded aluminum base members, self aligning / self centering arrangement and
support plates etc. as per ASTM B221-02. The system shall be such that it provides
floor to floor /floor to wall expansion control system for various vertical localtion in
load application areas that accommodates multi directional seismic movement
without stress to it’s components. System shall consist of metal profiles with a
universal aluminum base member designed to accommodate various project
conditions and finish floor treatments. The cover plate shall be designed of width
and thickness required to satisfy projects movement and loading requirements and
secured to base members by utilizing manufacturer’s pre-engineered self-centering
arrangement that freely rotates / moves in all directions. The Self – centering
arrangement shall exhibit circular sphere ends that lock and slide inside the
corresponding aluminum extrusion cavity to allow freedom of movement and
flexure in all directions including vertical displacement. Provision of Moisture
Barrier Membrane in the Joint System to have watertight joint is mandatory
requirement all as per the manufactures design and as approved by Engineer -in-
Charge . (Material shall confirm to ASTM 6063.)
3.21.1.1 Floor Joint of 150 mm gap metre 4016 6982.85 28043125.60
Stup Consultants P.Ltd 7 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
3.21.2 Providing and fixing of expansion joint system related with wall joint (internal/
external) location as per drawings and direction of Engineer-In- Charge. The joints
shall be of extruded aluminum base members, self aligning / centering arrangement
and support plates as per ASTM B221- 02. The material shall be such that it
provides an Expansion Joints System suitable for vertical wall to wall/ wall to
corner application, both new and existing construction in office Buildings &
complexes with no slipping down tendency amongst the components of the Joint
System. The Joint System shall utilize light weight aluminum profiles exhibiting
minimal exposed aluminum surfaces mechanically snap locking the multicellular to
facilitate movement.
(Material shall confirm to ASTM 6063.)
3.21.2.1 Wall Joint of 150 mm gap Metre 1144 5472.90 6260997.60
3.21.3 Providing and fixing of expansion joint system of approved make and manufactures
for various roof locations as per approved drawings and direction of Engineer-In-
Charge. The joints shall be of extruded aluminum base members with, self aligning
and self centering arragement support plates asper ASTM B221-02. The system
shall be such that it provides watertight roof to roof/roof to corner joint cover
expansion control system that is capable of accommodating multidirectional
seismic movement without stress to its components. System shall consist of metal
profile that incorporates a universal aluminum base member designed to
accommodate various project conditions and roof treatments. The cover plate shall
be designed of width and thickness required to satisfy movement and loading
requirements and secured to base members by utilizing manufacturer’s pre-
engineered self-centering arrangement that freely rotates / moves in all directions.
The Self centering arrangement shall exhibit circular sphere ends that lock and slide
inside the corresponding aluminum extrusion cavity to allow freedom of movement
and flexure in all directions including vertical displacement. The Joint System shall
resists damage or deterioration from the impact of falling ice, exposure to UV, 3.21.3.1 Roof Joint of 150 mm gap Metre 103 6750.55 695306.65
SUB TOTAL (REINFORCED CEMENT CONCRETE WORK) 2204537864.07
4 BRICK / BLOCK MASONRY WORK
A BRICK MASONRY
4.1 Brick work with common burnt clay F.P.S. (non modular) bricks of class
designation 7.5 in foundation and plinth in:4.1.1 Cement mortar 1:6 (1 cement : 6 coarse sand) cum 20 4,677.25 93545.00
4.2 Brick work with common burnt clay F.P.S. (non modular) bricks of class
designation 7.5 in superstructure above plinth level up to floor V level in all shapes
and sizes in :
4.2.1 Cement mortar 1:6 (1 cement : 6 coarse sand) cum 20 5,426.15 108523.00
4.3 Brick work 7 cm thick with common burnt clay F.P.S. (non modular) brick of class
designation 7.5 in cement mortar 1:3 (1 cement : 3 coarse sand) in superstructure
above plinth level and upto floor five level.
sqm 50 517.60 25880.00
4.4 Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class
designation 7.5 in foundations and plinth in.
4.4.1 Cement mortar 1:4 (1 cement :4 coarse sand) sqm 50 584.75 29237.50
4.5 Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class
designation 7.5 in superstructure above plinth level up to floor V level
4.5.1 Cement mortar 1:4 (1 cement :4 coarse sand) sqm 50 665.80 33290.00
4.6 Extra for half brick masonry in superstructure, above floor V level for every four
floors or part thereof by mechanical means.
sqm 105 25.60 2688.00
4.7 Extra for providing and placing in position 2 Nos. 6mm dia. M.S. bars at every third
course of half brick masonry.
sqm 150 69.50 10425.00
4.8 Brick work with non modular fly ash bricks conforming to IS:12894, class
designation 10 average compressive strength in super structure above plinth level
up to floor V level in :
4.8.1 Cement mortar 1:6 (1 cement : 6 Coarse sand) Cum 9026 6006.20 54211961.20
4.9 Providing and laying Gypsum panel partitions 100 mm thick with water proof
Gypsum panels of size 666x500x100 mm, made of calcite phosphor Gypsum fixed
with tongue and groove, jointed with bonding plaster as per manufacturer’s
specifications in superstructure above plinth level up to floor V level. Gypsum
blocks will have a minimum compressive strength of 9.3 kg/cm2
sqm 50 783.50 39175.00
4.10 Extra for Gypsum panel Partitions in superstructure above floor V level for every
four floors or part thereof.
sqm 25 66.10 1652.50
4.11 Brick edging 7cm wide 11.4cm. deep to plinth protection with common burnt clay
F.P.S. (non modular) bricks of class designation 7.5 including grouting with cement
mortar 1:4 (1 cement : 4 fine sand).
metre 100 38.15 3815.00
4.12 Half brick masonry with non modular fly ash bricks of class designation 10,
conforming to IS : 12894, in super structure above plinth and upto floor V level
Stup Consultants P.Ltd 8 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
4.12.1 Cement mortar 1 : 4 (1 cement : 4 coarse sand sqm 100 751.10 75110.00
SUB TOTAL (BRICK WORK) 54635302.2
5.0 STONE WORK
5.1 Stone tile work for wall lining upto 10 m height with special adhesive over 12mm
thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) including pointing in
white cement with an admixture of pigment to match the stone shade.
5.1.1 8mm thick (mirror polished and machine cut edge)
5.1.1.1 Granite stone of any colour and shade sqm 50 1486.90 74345.00
SUB TOTAL (STONE WORK) 74345.00
6 MARBLE WORK
6.1 Providing and fixing 18mm thick gang saw cut mirror polished premoulded and
prepolished) machine cut for kitchen platforms, vanity counters, window sills ,
facias and similar locations of required size of approved shade, colour and texture
laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with
joints treated with white cement, mixed with matching pigment, epoxy touch ups,
including rubbing, curing, moulding and polishing to edges to give high gloss finish
etc. complete at all levels.
6.1.1 Granite of any colour and shade
6.1.1.1 Area of slab over 0.50 sqm sqm 325 3907.40 1269905.00
6.2 Providing edge moulding to 18mm thick marble stone counters, Vanities etc.
including machine polishing to edge to give high gloss finish etc. complete as per
design approved by Engineer-in-Charge.
6.2.1 Granite work metre 813 230.55 187437.15
6.3 Extra for fixing marble /granite stone over and above corresponding basic item, in
facia and drops of width upto 150 mm with epoxy resin based adhesive including
cleaning etc. complete.
metre 813 247.40 201136.20
6.4 Extra for providing opening of required size & shape for wash basins/ kitchen sink
in kitchen platform, vanity counters and similar location in marble/Granite/stone
work including necessary holes for pillar taps etc. including moulding, rubbing and
polishing of cut edges etc. complete.
each 850 386.60 328610.00
6.5 Mirror polishing on marble work/Granite work/stone work where ever required to
give high gloss finish complete
sqm 325 212.85 69176.25
6.6 Providing and fixing machine cut, mirror / eggshell polished , Marble stone
work for wall lining (veneer work) including dado, skirting, risers of steps
etc., in required design and pattern wherever required, stones of different
finished surface texture, on 12 mm (average) thick cement mortar 1:3 (1
cement : 3 oarse sand) laid and jointed with white cement slurry @ 3.3
kg/sqm including pointing with white cement slurry admixed with pigment
of matching shade, including rubbing, curing, polishing etc. all complete
as per Architectural drawings, and as directed by the Engineer-in-Charge.
a. 18 mm thick Italian Marble stone slab,Perlato, Rosso verona, Fire Red
or Dark Emperadore etc
sqm 325 7022.6 2282345.00
6.7 Providing and laying flamed finish Granite stone flooring in required design and
patterns, in linear as well as curvilinear portions of the building all complete as per
the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick
base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement
slurry and pointing with white cement slurry admixed with pigment of matching
shade including rubbing, curing and polishing etc. all complete as specified and as
directed by the Engineerin- Charge :
6.7.1 Flamed finish granite stone slab Jet Black, Cherry Red, Elite
Brown, Cat Eye or equivalent.
sqm 50 3244.35 162217.50
6.8 Flamed finish Granite slab flooring in treads of steps and risers using single length
upto 2.00 metre over 20mm (average) thick base laid over and jointed with grey
cement slurry mixed with pigment to match the shade of the slab inlcuding rubbing
and polishing complete with base of 1:4 (1 cement : 4 coarse sand)
(Basic rate:- 185.80- per sft)
6.8.1 18 mm thick approved of approved quality and colour Sqmt 6792 3798.00 25796016.00
SUB TOTAL (MARBLE WORK) 30296843.10
7 WOOD WORK & PVC WORK
Note :- Wood work items may be substituted with available species of wood
as per direction of Engineer-in-charge for which rates shall be derived from
the relevant items.
Stup Consultants P.Ltd 9 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
7.1 Providing wood work in frames of doors, windows, clerestory windows and other
frames, wrought framed and fixed in position with hold fast lugs or with dash
fasteners of required dia & length ( hold fast lugs or dash fastener shall be paid for
separately).
7.1.1 Second class teak wood cum 86 91496.90 7868733.40
7.2 Providing and fixing panelled or panelled and glazed shutters for doors, windows
and clerestory windows including ISI marked M.S. pressed butt hinges bright
finished of required size with necessary screws excluding, panelling which will be
paid for separately, all complete as per direction of Engineer-in-charge.
7.2.1 Second class teak wood
7.2.1.1 35 mm thick shutters sqm 10 2689.05 26890.50
7.3 Providing and fixing glazed shutters for doors, windows and clerestory windows
using 4 mm thick float glass panes including ISI marked M.S. pressed butt hinges
bright finished of required size with necessary screws.
7.3.1 Second class teak wood
7.3.1.1 35 mm thick sqm 30 3262.90 97887.00
7.4 Providing and fixing ISI marked flush door shutters conforming to IS: 2202 (Part I)
non-decorative type, core of block board construction with frame of 1st class hard
wood and well matched commercial 3 ply veneering with vertical grains or cross
bands and face veneers on both faces of shutters :
7.4.1 35 mm thick including ISI marked stainless steel butt hinges with necessary
screws.
sqm 25 1909.55 47738.75
7.5 Providing and fixing ISI marked flush door shutters conforming to IS: 2202
(Part I) non-decorative type, core of block board construction with frame of
1st class hard wood and well matched commercial 3 ply veneering with
vertical grains or cross bands, teak wood lipping and face veneers on both
faces of shutters :
7.5.1 40 mm thick including including edge lipping,equivelent to Kich DH 235S
Stainless Steel butt hinges with necessarycross head screws.
sqm 3318 5367.30 17808701.40
7.6 42 mm thick including including edge lipping,equivelent to Kich DH 235S
Stainless Steel butt hinges with necessarycross head screws.
sqm 50 5473.50 273675.00
7.7 Extra over abve referred item Nos. 7.6&7.7or providing and fixing Double
leaf Flush door instead of single leaf flush door shutters
sqm 50 203.30 10165.00
7.8 Providing & Installing openable double leaf double swing doors in required
sizes in glazed partitions using 12mm thick toughened clear float glass,
including fixing necessary imported stainless steel satin finished hardware
fittings like handles(PHC 3824 of Kich), patch fitting ,hinges, floor springs
with cast iron body size-4 upto 120 Kg.(NFS 990), door patch to suit floor
spring , top door patch to suit 15 mm pivot floor , locking arrangements
which are BMS compatible, keys etc. all as approved shop drawings and
specification.
sqm 25 10680.00 267000.00
7.9 Providing and fixing expandable fasteners of specified size with necessary plastic
sleeves and galvanised M.S. screws including drilling holes in masonry work /CC/
R.C.C. and making good etc. complete.
7.9.1 40 mm long each 500 21.65 10825.00
7.10 Providing and fixing plywood 4 mm thick one side decorative veneer
conforming to IS: 1328 (type-1) for plain lining / cladding with necessary
screws, priming coat on unexposed surface with:
7.10.1 Decorative veneer facings of approved manufacture sqm 157 1156.2 181523.40
7.11 Providing and fixing wooden moulded beading to door and window frames with iron
screws, plugs and priming coat on unexposed surface etc. complete :
7.11.1 2nd class teak wood
7.11.1.1 50x12 mm metre 100 117.95 11795.00
7.12 Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10
mm diameter bolts, nuts and wooden plugs and embedding in cement concrete
block 30x10x15cm 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate
20mm nominal size)
each 16632 117.35 1951765.20
Stup Consultants P.Ltd 10 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
7.13 Providing and fixing partition upto ceiling height consisting of G.I. frame and
required board including providing and fixing of frame work made of special section
power pressed/ roll form G.I. sheet with zinc coating of 120 gms/sqm(both side
inclusive), consisting of floor and ceiling channel 50mm wide having equal flanges
of 32 mm and 0.50 mm thick, fixed to the floor and ceiling at the spacing of 610
mm centre to centre with dash fastener of 12.5 mm dia meter 50 mm length or
suitable anchor fastener or metal screws with nylon plugs and the studs 48 mm
wide having one flange of 34 mm and other flange 36 mm and 0.50 mm thick fixed
vertically within flanges of floor and ceiling channel and placed at a spacing of
610mm centre to centre by 6 mm dia bolts and nuts, including fixing of studs along
both ends of partition fixed flush to wall with suitable anchor fastener or metal
screws with nylon plugs at spacing of 450 mm centre to centre, and fixing of boards
to both side of frame work by 25 mm long dry wall screws on studs, floor and
ceiling channels at the spacing of 300 mm centre to centre. The boards are to be
fixed to the frame work with joints staggered to avoid through cracks, M.S. fixing
channel of 99 mm width (0.9 mm thick having two flanges of 9.5 mm each) to be
provided at the horizontal joints of two boards, fixed to the studs using metal to
metal flat head screws, including jointing and finishing to a flush finish with
recommended jointing compound, jointing tape, angle beads at corner (25 mm x 25
mm x 0.5 mm), joint finisher and two coats of primer suitable for board as per
manufacture's specification and direction of engineer in charge all complete.
7.13.1 66mm overall thickness Partition with 8mm thick double skin Calcium Silicate
Board made with Calcareous & Siliceous materials reinforced with cellulose fiber
manufactured through autoclaving process with Compressive Strength 225
kg/sq.cm, Bending Strength 100 kg./ sq.cm.
sqm 70648 1325.65 93654521.20
7.14 Supply and fixing of 12.5 mm thick double skin fire rated Gypsum board
conforming to IS: 2095: part I ,on the existing framing /on the existing board
partition as described above in BOQ item No.7.13.1 of this sub head ,including the
coast of all required accessories ,POP,Glue,Joint tape ,primer ,Round head
G.S.Bolts with slots etc.complete to the satisfaction of engineer incharge
sqm 70490 419.90 29598751.00
7.15 Supply and fixing of 8 mm thick double skin Calcium Silicate Board made with
Calcareous & Siliceous materials reinforced with cellulose fiber manufactured
through autoclaving process with Compressive Strength 225 kg/sq cm, Bending
Strength 100 kg/ sq cm ,on the existing framing /on the existing board partition as
described in as described above in BOQ item No.7.13.1 of this sub head ,including
the coast of all required accessories ,POP,Glue,Joint tape ,primer ,Round head
G.S.Bolts with slots etc.complete to the satisfaction of engineer incharge
sqm 30 1319.90 39597.00
7.16 Providing and fixing wooden moulded corner beading of triangular shape to the
junction of panelling etc. with iron screws, plugs and priming coat on unexposed
surface etc. complete 2nd class teak wood.
7.16.1 50x50mm (base and height). metre 100 199.85 19985.00
7.17 Providing & Fixing decorative high pressure laminated sheet of plain / wood grain
in gloss / matt / suede finish with high density protective surface layer and reverse
side of adhesive bonding quality conforming to IS : 2046 Type S including cost of
adhesive of approved quality
7.17.1 1.5 mm thick. sqm 6636 829.7 5505889.20
7.18 Providing and fixing, in position concealed G.I. section for wall paneling using
board of required thickness fixed on the 'W' profile (0.55mm thick ) having a
knurled web of 51.55mm and two flanges of 26mm each with lips of 10.55 mm,
placed @ 610mm C/C in perimeter channel having one flange of 20mm and
another flange of 30mm with thickness of 0.55mm and web of length 27mm.
Perimeter channel is fixed on the floor and the ceiling with the nylon sleeves @
610mm C/C with fully threaded self-tapping dry wall screws. Board is fixed to the
'W' profile with 25 mm countersunk ribbed head screws @ 200mm C/C., all
complete as per the drawing & directions of engineer-in-charge the joints of the
boards are finished with specially formulated jointing compound and 48mm wide
jointing tape to provide seamless finish.
Stup Consultants P.Ltd 11 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
7.18.1 Tapered edge calcium silicate board made with calcareous & siliceous materials
reinforced with cellulose fiber manufactured through autoclaving process to give
stable crystalline structure with compressive strength 225 kg/sq.cm, Bending
strength 100 kg/sq.cm.
7.18.1.1 10mm thick. sqm 20 1002.15 20043.00
7.19 Supply and applying of Film from 3 M on glass at the locations shown in the
drawings
Sqmt 16312 500.00 8156000.00
7.20 Providing and fixing, in position concealed G.I. section for wall paneling using
board of required thickness fixed on the ‘W’ profile (0.55 mm thick ) having a
knurled web of 51.55 mm and two flanges of 26 mm each with lips of 10.55 mm,
placed @ 610 mm C/C in perimeter channel having one flange of 20 mm and
another flange of 30 mm with thickness of 0.55 mm and web of length 27 mm.
Perimeter channel is fixed on the floor and the ceiling with the nylon sleeves @ 610
mm C/C with fully threaded self-tapping dry wall screws. Board is fixed to the ‘W’
profile with 25 mm countersunk ribbed head screws @ 200 mm C/C., all complete
as per the drawing & directions of engineer-incharge, the joints of the boards are
finished with specially formulated jointing compound and 48 mm wide jointing tape
to provide seamless finish.
Framing only
Sqmt 50 302.60 15130.00
7.21 Providing and fixing, in position 12.5 mm thick Gypsum board conforming to IS:
2095 Part - I in the existing framing of concealed G.I. section for wall paneling
using board of required thickness fixed on the ‘W’ profile (0.55 mm thick ) having a
knurled web of 51.55 mm and two flanges of 26 mm each with lips of 10.55 mm,
placed @ 610 mm C/C in perimeter channel having one flange of 20 mm and
another flange of 30 mm with thickness of 0.55 mm and web of length 27 mm.
Perimeter channel is fixed on the floor and the ceiling with the nylon sleeves @ 610
mm C/C with fully threaded self-tapping dry wall screws. Board is fixed to the ‘W’
profile with 25 mm countersunk ribbed head screws @ 200 mm C/C., all complete
as per the drawing & directions of engineer-incharge, the joints of the boards are
finished with specially formulated jointing compound and 48 mm wide jointing tape
to provide seamless finish.
(Excluding the cost of framing which shall be measured and paid for seperately)
Sqmt 50 437.60 21880.00
7.22 Providing and fixing, in position ,10 mm thickTapered edge calcium silicate board
made with calcareous & siliceous materials reinforced with cellulose fiber
manufactured through autoclaving process to give stable crystalline structure with
compressive strength 225 kg/sqcm, Bending strength 100 kg/sqcm, in the existing
framing of concealed G.I. section for wall paneling using board of required
thickness fixed on the ‘W’ profile (0.55 mm thick ) having a knurled web of 51.55
mm and two flanges of 26 mm each with lips of 10.55 mm, placed @ 610 mm C/C
in perimeter channel having one flange of 20 mm and another flange of 30 mm with
thickness of 0.55 mm and web of length 27 mm. Perimeter channel is fixed on the
floor and the ceiling with the nylon sleeves @ 610 mm C/C with fully threaded self-
tapping dry wall screws. Board is fixed to the ‘W’ profile with 25 mm countersunk
ribbed head screws @ 200 mm C/C., all complete as per the drawing & directions
of engineer-incharge, the joints of the boards are finished with specially formulated
jointing compound and 48 mm wide jointing tape to provide seamless finish.
(Excluding the cost of framing which shall be measured and paid for seperately)
Sqmt 50 699.60 34980.00
7.23 Providing and fixing fully glazed partitions made out of 12mm thick clear
toughened full height glass panels as shown in the drawings, transparent
silicon sealants of approved make at glass joints and corners / junctions as
shown, all visible edges of glass to be machine polished, including fixing
arrangements at top in concealed Aluminium frame and bottom in metal
skirting, accessories etc. complete all as per drawings, as per approved shop
drawings and as directed by the Engineer.
7.23.1 Using 12mm thick clear toughened glass
7.23.1.1 Partitions in straight profile / curved segmented profile Sqmt 1000 3647.35 3647350.00
7.24 Not Used
Stup Consultants P.Ltd 12 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
7.25 Providing and fixing Laqured glass of approved colour for wall panels (as specified
below) with approved fixing system,of approved size and make, with transparent
sealed joints, including 9mm thick commercial plywood backing and hard wood
framework, (teak wood beading frame work on outer edges with melamine
polishing to exposed wood if required) , all visible edges of glass to be machine
polished, (backing ply & wooden frame to be chemically treated with preservative &
anti-termite treatment and painted) etc., complete all as per drawing and as
directed by the Engineer.
Sqmt 1200 12350.80 14820960.00
7.26 Providing and fixing vision panels of approx. size 1200 x 150 x 6mm clear
annealed float Glass of approved make and quality etc. complete with
necessary frame work all as directed by the Engineer.
Each 20 1336.00 26720.00
7.27 BUILDING HARDWARE :Supplying and fixing of following stainless steel
hardwares at the locations shown in the drawings.Complete with cross headed
stainless steel screw and other accessories required complete as per the
instructions and satisfaction of Engineer Incharge.
a Supplying and fixing Stainless Steel AISI 316 grade satin finished door hinge with
four bearings of sizw 127x76x3 and SS self tapping philips cross head screws
,equivelent to Kich DH 235S
Each 10643 995.40 10594042.20
b Supplying and fixing Stainless Steel AISI 316 grade satin finished Pull Handles of
Code No. "PHC2524" manufactured by KICH or approved equivalent, with
necessary long stud, SS screws, all accessories etc. complete.
Set 1572 5025.72 7900431.84
c Supplying and fixing Stainless Steel AISI 316 grade satin finished Pull Handles of
Code No. "PHC3824" manufactured by KICH or approved equivalent, with
necessary long stud, SS screws, all accessories etc. complete.
Set 10 12851.00 128510.00
d Satin finished Mortice Handles of Code No. "MH2221S" manufactured by KICH Set 307 4610.00 1415270.00
e Dead bolt of (Code No.MDBS) including Stainless Steel Main Plate & Strike Plate,
S.S. Escutcheons (EEP50) ,locking arrangement with Master Key upto 25
Cylinders (Code No. PCKNS70) manufactured by KICH
Set 1572 2584.28 4062488.16
f Concealed type hydraulic door closer (Item Code No. : DCC 611S) manufactured
by Kich Set 1878 4192.00 7872576.00
g Heavy duty automatic double action hydraulic floor springs (Item Code No : NFS
990) manufactured by Neki
(Suitable for door Size- 2200mm X 1100mm) Door Weight capacity 80 -120 Kg.
[Finish:Satin]
Set 106 5359.52 568108.62
h Floor / wall mounted Stainless Steel AISI 316 grade half moon door stopper (Code
No. DSTHMS) manufactured by KICH
Each 106 568.00 60208.00
i Stainless Steel AISI 316 grade half moon door stopper (Code No. DSTRS)
manufactured by KICH
Each 1572 531.00 834732.00
j Stainless Steel tower bolt with extension rod (Code No.ATBS 12S) manufactured
by KICH
Each 315 440.67 138812.03
k Indicator Bolt (Item Code No. IB106S) manufactured by KICH Each 307 631.40 193840.73
l 16 SWG stainless steel pictograms / signages of 170mm x 170mm x 2mm size
manufactured by KICH
Each 307 991.80 304482.60
m 16 SWG stainless steel pictograms / signages of 300mm x 75mm x 2mm size
manufactured by KICH
Each 1772 1395.30 2472471.60
7.28 FIRE RATED DOORS AND HARDWARES /ACCESSORIES
7.28.1 55MM THICK NON-METALLIC WOODEN FIRE PROOF DOORS OF
120 MINUTES FIRE RATING:
Stup Consultants P.Ltd 13 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
7.28.1.1 Supply and fixing of Sukri/Shaktimet/Godrej 2hours Fire Rated Wooden Door
system duly tested for Stability, Integrity and Insulation criteria clause 9.4 as per IS
3614 Part – 2 and BS 476 Part 22 for single and double leaf Doors from CBRI
Roorkee with Ivory Coast Teak Wood Door Frame of section 145mm x 70mm with
heat activated intumescent fire seal strip of size 20mm x 4mm (Astroflame U.K./
Abesco) and one coat of anti-termite fire retardant Primer alongwith 55mm thick
asbestos free composite fire / smoke check wooden shutters of 120 minute fire
rating comprising of two 9mm thick Starpan Calcium Silicate boards, a 100%
without Asbestos, Brucite and Meerschaum, having density not more than 1150
Kg/M3 and thermal conductive 0.14 W/m*K sandwiching 31mm thick fire
resistance insulation filler coated with FR silicon sealant and faced with 3mm thick
Century Plyboards India Ltd(IGBC) Teak Veneer with Melamine Polish on both
sides or 3mm thick commercial ply on both side with 1mm lamination on both faces
with heat activated intumescent fire seal strip of size 20mm x 4mm (Astroflame
U.K/ Abesco) mounted in the grooves of teakwood lipping on all sides except
bottom.The internal framing of the Wooden fire door of size 100X31mm(perimeter
stile) and the wooden door frame shall be manufactured from the wood IS
CERTIFIED FOR FOREST STEWARDSHIP COUNCIL CHAIN-OF-CUSTODY
AND CONTROLLED WOOD. The door shall have a vision panel of a minimum size
of 300X500mm the manufacturer should have tested the glass from CBRI Roorkee
along with the Single / Double Leaf fire rated door for 2hrs. fire rating for stability,
integrity and insulation criteria prior to manufacturing.
a Single leaf door Sqmt 1138 11511.90 13100542.20
b Double leaf door Sqmt 285 12886.00 3672510.00
7.30 FIRE RATED HARDWARES
a Supply and fixing of stainless steel 304 grade ball bearing hinges of size 102 x
76mm x 3mm thick from I.R / Dorma/ Marshall
Each 20 474.00 9480.00
b Supply and fixing of 2 hrs. Fire rated Door Closers having rack and pinion
mechanism, with standard arm, dual speed control, CE certifier, having 10 years
mechanical warranty from I.R Briton 121 / Dorma TS 72 / Marshall MH DC- S-
14003
Each 20 3385.80 67716.00
c Supply and fixing of 2 hrs. fire rated stainless steel Panic Bars tested as per IS
3614 Part –II / BS 476 from I.R Briton 378 series / Dorma PHA series / Marshall
MH- PB series
d Single Leaf Each 572 10157.50 5810090.00
e Double Leaf Each 29 20315.10 589137.90
7.31 Supply and fixing of stainless still 304 grade Outside Access Device (Trim)
compatible with Single and Double leaf Panic Bars from Briton/ Dorma/Marshall
Each 601 6771.70 4069791.70
7.32 Supply and fixing of 2hrs. fire rated Mortice Dead Lock with 80mm cylinder having
one side key and one side thumb turn operation from I.R Briton EL 2020 series /
Dorma 278 series / Marshall MH – L- ENT- 13001 SSS series
Each 601 3385.85 2034895.85
7.33 Supply and fixing of stainless steel D-Type Handle of size 22mm dia and 300mm
long from Dorma TGDI series / Briton / Marshall make TGDI
Each 601 1015.75 610465.75
SUB TOTAL (WOOD AND PVC WORK) 250629109.2
8 STEEL WORK
Supplying, fabricating, assembling, hoisting / erecting and fixing in position at
locations specified below, structural steel works of MS rolled single / built-up
sections conforming to IS 2062, including joist, channel, angle, tee, plates (plain or
chequered) etc. all as per structural drawings and as per detailed specifications (for
materials & workmanship) including necessary scaffolding / staging, applying a
priming coat of approved steel primer etc. complete in the situations described
hereinafter and comprising of :
i) Profile Cutting of components to required lengths/widths and shapes/profiles
ii) Smooth grinding / machining of edges / faces / all welding joints.
iii) Preparing the surface to ensure complete removal of mill scale by using wire
brushes & sand papering
iv) Necessary welding (electric arc welding) for required weld lengths and sizes
Note: The contractor shall submit fabrication drawings for work involved based on
construction drawings (that may be issued during construction period) for approval
by the Engineer.
The fabrication work shall start only after approval of the fabrication drawings. Any
change required in the fabrication drawings shall be carried out at no extra cost.
Fabrication shall be in a perfect Architectural workmanship manner and as
provided in Section V & VI of IS 800 & IS 7215.
Welding shall be carried out by professional / certified welders.
8.1
Stup Consultants P.Ltd 14 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
Electrodes for welding, the procedure, selection, test and inspection shall confirm
to provisions in IS 816, IS 818, IS 822, & IS 833.
Erection / hoisting shall commence only after approval of fabricated parts by the
Engineer.
8.1.1 Structural steel work in single section fixed with or without connecting plate
including cutting, hoisting, fixing in position and applying a priming coat of
approved steel primer all complete.(Also For waller beams and other locations as
shown in drawings)
kg 45000 67.70 3046500.00
8.1.2 Structural steel work riveted, bolted or welded in built up sections, trusses and
framed work, including cutting, hoisting, fixing in position and applying a priming
coat of approved steel primer all complete:
kg 39000 73.95 2884050.00
8.2 Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6mm angle
iron and 3mm M.S. gusset plates at the junctions and corners, all necessary fittings
complete, including applying a priming coat of approved steel primer
8.2.1 Using flats 30x6mm for diagonal braces and central cross piece. Sqm 10 2906.65 29066.50
8.3 Supplying and fixing rolling shutters of approved make, made of required size M.S.
laths, interlocked together through their entire length and jointed together at the
end by end locks, mounted on specially designed pipe shaft with brackets, side
guides and arrangements for inside and outside locking with push and pull
operation complete, including the cost of providing and fixing necessary 27.5 cm
long wire springs manufactured from high tensile steel wire of adequate strength
conforming to IS: 4454 – part 1 and M.S. top cover of required thickness for rolling
shutters.
8.3.1 80x1.25mm M.S. laths with 1.25 mm thick top cover. Sqm 30 2142.1 64263.00
8.4 Providing and fixing ball bearing for rolling shutters each 6 438.95 2633.70
8.5 Extra for providing mechanical device chain and crank operation for operating
rolling shutters.
8.5.1 Exceeding 10.00 sqm and upto 16.80 sqm in the area each 2 724.85 1449.70
8.6 Extra for providing grilled rolling shutters manufactured out of 8 mm dia. M.S. bar
instead of laths as per design approved by Engineer-in-charge.(area of grill to be
measured).
sqm 10 313.6 3136.00
8.7 Steel work in built up tubular ( round, square or rectangular hollow tubes etc.)
trusses etc. including cutting, hoisting, fixing in position and applying a priming coat
of approved steel primer, including welding and bolted with special shaped
washers etc. complete.
8.7.1 Hot finished welded type tubes kg 33000 102.90 3395700.00
8.7.2 Hot finished seamless type tubes kg 320000 115.10 36832000.00
8.8 Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan
clamp of internal dia 140mm, 73mm height, top lid of 1.5mm thick M.S. sheet with
its top surface hacked for proper bonding, top lid shall be screwed into the cast
iron/ M.S. sheet box by means of 3.3mm dia. round headed screws, one lock at the
corners. Clamp shall be made of 12mm dia M.S. bar bent to shape as per standard
drawing.
each 2636 142.95 376816.20
8.9 Steel work welded in built up sections/ framed work including cutting, hoisting,
fixing in position and applying a priming coat of approved steel primer using
structural steel etc. as required.
8.9.1 In stringers, treads, landings etc. of stair cases including use of chequered plate
wherever required, all complete.
kg 200 75.30 15060.00
8.9.2 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. kg 15000 90.10 1351500.00
SUB TOTAL (STEEL WORK) 48002175.1
9 FLOORING
9.1 Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate) finished with a floating coat of neat cement including cement slurry, but
excluding the cost of nosing of steps etc. complete.
9.1.1 40mm thick with 20mm nominal size stone aggregate. sqm 425 353.35 150173.75
9.2 52 mm thick cement concrete flooring with concrete hardener topping, under layer
40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener
consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm
nominal size) by volume, .hardening compound mixed @ 2 litre per 50kg of cement
or as per manufacturers specifications. This includes cost of cement slurry, but
excluding the cost of nosing of steps etc. complete.
sqm 69756 535.25 37336899.00
9.3 Cement plaster skirting (up to 30 cm height) with cement mortar 1:3 (1 cement : 3
coarse sand) finished with a floating coat of neat cement.
9.3.1 18mm thick sqm 76 377.25 28671.00
9.4 Cement concrete pavement with 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size) including finishing complete.
Cum 20 5759.20 115184.00
9.5 Providing and fixing glass strips in joints of terrazo/ cement concrete floors.
9.5.1 40 mm wide and 4 mm thick. metre 50 50.05 2502.50
9.6 Extra for pre finished nosing to treads of steps of marble stone. metre 6453 274.90 1773929.70
9.7 Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with
grey cement slurry mixed with pigment to match the shade of the slab including
rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4
coarse sand) :
Stup Consultants P.Ltd 15 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
9.7.1 25 mm thick. sqm 592 1141.40 675708.80
9.8 Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12
mm (average) thick cement mortar 1:3 (1 cement 3 coarse sand) and jointed with
grey cement slurry mixed with pigment to match the shade of the slabs, including
rubbing and polishing complete.
sqm 1191.25
9.9 Providing and fixing Glass mossaic tiles at finished plain wall surface of size 20
mm x 20 mm x 4 mm in all colour, design , fixing in customize design as per
direction of Engineer-in- Charge. The glass mosaic tiles to be fixed on the wall
surface with the help of approved adhesive applied at the rate of 2.5 kg per sqm
and grouting of the same. The rate is inclusive of all operation, material and
required pattern approved by Engineer-in- Charge
sqm 5065 1752.60 8876919.00
Providing and fixing removable raised/false access flooring with system and its
components of approved make for different plenum height with possible height
adjustment upto 50 mm, comprising of modular load bearing floor panels supported
on G.I. rectangular stinger frame work and G.I. Pedestal etc. all complete, as per
the architectural drawings, as specified and as directed by Engineer-in-charge
consisting of :
a) P roviding at required spacing to form modular framework, pedestals made out
of GI tube of thickness minimum 2 mm and 25 mm outer diameter, fully welded on
to the G.I. Base plate of size 100mm x 100mm x 3mm at the bottom of the pedestal
tube, G.I. pedestal head of size 75mmx75mmx3.5 mm welded with GI fully
threaded stud 16mm outer
diameter with two GI Check nuts screwed on the stud for level adjustment upto
50mm, locking and stabilizing the pedestal head in position at the required level.
The pedestals shall be fixed to the subfloor (base) through base plate using epoxy
based adhesive of approved make or the machine screw with rawl plug.
b) S tringers system in all steel construction hot dipped galvanized of rectangular
size 570x20x30x0.80mm thick having holes at both ends for securing the stringers
on to the pedestal head using fully threaded screws ensuring maximum lateral
stability in all directions, the grid formed by the pedestal and stringer assembly
shall receive the floor panel, this system shall provide adequate solid, rigid support
for access floor panel, the system shall provide a minimum clear uninterrupted
clearance between the bottom of the floor for electrical conduits and wiring etc. all
complete as per the architectural drawings, as specified and as directed by the
Engineer-incharge.
c) P r oviding and fixing Access Floor panel of 600x600x32 mm medium grade
Filled Steel anti static high pressure Lamination of 800H grade (FS800H). Access
Floor panel shall be steel welded construction with an enclosed bottom pan with
uniform pattern of 64 hemispherical cones. The top and bottom plates of Steel
Gauges: top 0.6 mm and bottom 0.7 mm fused spot welded together (minimum 64
welds in each dome and 20 welds along each flange). The panel should be
Corroresist epoxy coated for lifetime rust protection and cavity formed by the top
and bottom plate is filled with Pyrogrip noncombustible Portland cementitious core
mixed with lightweight foaming compound. The access floor shall be factory
finished with Anti-static High Pressure laminate with Non Warp technology upto
1mm thickness for superior adhesion and Surface flatness within 0.75mm.The
panel is to withstand a Concentrated Load of 363 kgs applied on area 25mm x
25mm without collapse in the centre of the panel which is placed on four steel
blocks. The panel will withstand and Uniformly Distributed Load (UDL) minimum
1250 kg/sqm and an impact load of 50kg all complete as per the approved
manufacturers specification and as per the direction of Engineer-in-charge. All
specification must be printed on the side of the panel to ensure the quality of the
product.
9.10.1 450 mm Finished Floor Height (FFH). Sqmt 1150 3983.85 4581427.50
9.11 Providing and fixing Ist quality Digital high definition ceramic glazed wall tiles of
300 X 600 mm in size and conforming to IS : 15622 (thickness to be specified by
the manufacturer ) of approved make in all colours, shades as approved by
Engineer-in-Charge in skirting, risers of steps and dados over 12 mm thick bed of
cement Mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry
@ 3.3kg per sqm including pointing in white cement mixed with pigment of
matching shade complete.
Basic Rate of tiles Rs.50/ Sqft
Sqmt 10353 950.00 9835350.00
9.10
Stup Consultants P.Ltd 16 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
9.12 Providing and laying 1st quality digital Glazed plain or non skid full body vitrified
floor tiles in different sizes (thickness to be specified by the manufacturer) with
water absorption's less than 0.08% and conforming to IS:15622 of approved make
in all colours and shades, laid on 20mm thick cement mortar 1:4 ( 1 cement : 4
coarse sand) including the grouting the joints with white cement and matching
pigments etc., complete.
Basic Rate of tiles Rs.125/ Sqft
Sqmt 58593 1350.00 79100550.00
9.13 Providing and laying 1st quality digital Glazed plain or non skid full body vitrified
floor tiles in different sizes (thickness to be specified by the manufacturer) with
water absorption's less than 0.08% and conforming to IS:15622 of approved make
in all colours and shades, laid on 20mm thick cement mortar 1:4 ( 1 cement : 4
coarse sand) including the grouting the joints with white cement and matching
pigments etc., complete.
Basic Rate of tiles Rs.100/ Sqft
Sqmt 7866 1300.00 10225800.00
9.14 Providing and fixing 1st quality digital Glazed plain or non skid full body vitrified
floor tiles in different sizes conforming to IS : 15622 (thickness to be specified by
the manufacture of approved make in all colours, shades in skirting, risers of steps
and dados over 12 mm thick bed of cement Mortar 1:3 (1cement: 3 coarse sand)
and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white
cement mixed with pigment of matching shade complete.
Basic Rate of tiles Rs.125/ Sqft
Sqmt 1345 1450.00 1950250.00
9.15 Granite slab flooring over 20mm (average) thick base laid over and jointed with
grey cement slurry mixed with pigment to match the shade of the slab inlcuding
rubbing and polishing complete with base of 1:4 (1 cement : 4 coarse sand)
(Basic rate:- 175/- per sft)
Sqmt 2892 2676.00 7738992.00
9.16. Granite slab flooring in treads of steps and risers using single length upto 2.00
metre over 20mm (average) thick base laid over and jointed with grey cement
slurry mixed with pigment to match the shade of the slab inlcuding rubbing and
polishing complete with base of 1:4 (1 cement : 4 coarse sand)
(Basic rate:- 175/- per sft)
9.16.1 18 mm thick approved of approved quality and colour Sqmt 1049 3110.20 3262599.80
9.17 Providing and fixing of Granite slab in skirting , wall cladding / lining or on pillers
over 12mm (average) thick base of cement mortar of 1:4 (1 cement : 4 coarse
sand) cement slurry @ 3.3 kg/sqm including pointing in white cement mixed with
pigment to match the shade of the slab inlcuding rubbing and polishing complete.
(Basic rate:- 175/- per sft)
9.17.1 18 mm thick approved of approved quality and colour Sqmt 745 3247.80 2419611.00
9.18 Providing and laying 1st quality 15 mm thick ceramic tiles from Pavit Ceramic Pvt.
Ltd or equivelent approved with pavit earthen ,Exotic and Decor series in required
precentage and size to make the pattenr in the required colours and shades, laid
on 20mm thick cement mortar 1:4 ( 1 cement : 4 coarse sand) including the
grouting the joints with white cement and matching pigments etc., complete as per
the instruction of the Engineer Incharge
Basic Rate of tiles Rs.685/ Sqmt
Sqmt 50 1171.50 58575.00
Providing and doing MYK Deck Coat a three components system comprising of
colour resin & Hardener The components shall be mixed mechanically using a
slow speed stirrer to get a homogeneous mix. While mixing, add MYK Indufibre @
0.60% - 0.70% by weight. Addition of MYK Indufibre depends on the nature of
texture required. Apply the mixed MYK Deck Coat @ 0.75 kg/ m2 by using English
trowel or suitable roller to obtain even coverage & finally use texture roller to get
even texture finish..System shall be laid as per the manufacturers specifications in
the below mentioned steps for drive way and ramps area :
Drive Way and Parking Bay Floor
9.19
Stup Consultants P.Ltd 17 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
1)Prepare the dry concrete surface using proper grinding equipment to remove any
loose material, contaminations and laitance to provide a sound, gripping surface.
In case of broom finished surface a flowable repair mortar is made using MYK
Indufloor 1290(I) @ 0.50 and quartz dust mixed at a dosage which is appropriate
as per the nature of repair at site.
Clean the entire floor area using a powerful industrial vacuum cleaner.
2)Application of Epoxy based primer for concrete floor : Providing and applying a
coat of epoxy resin based primer for concrete surface with MYK Indufloor 1290(I)
@ 0.30 kg/sqm or Sikafloor®-93a
3)Application of Textured Epoxy topping: Providing and applying chemical and
abrasion resistant thixotropic epoxy resin textured antiskid topping (Non Broadcast)
MYK Deck Coat having a mixed density of 1.70 kg/ltr (or SikafloorCarDeckThixo@
1 Coats of 0.8 kg/sqm) and admixed with MYK Indufibre @ 0.60 to 0.70% by
weight. Total consumption @ 0.90kg/sqm to bring out even crested finish having a
thickness of aprox 2-2.5 mm from crest. The material has to be applied with the
appropriate textured roller.
4)Application of Line Marking: Providing and applying abrasion resistant
thixotropic epoxy resin topping (Non Broadcast) MYK Deck Coat @ 0.40 kgs. m2 in
white or yellow colour
Sqmt 69572 755.00 52526860.00
Ramps areas
1)Prime the surface using MYK Indufloor 1290(I) @ 0.35 kg/m2
2)Application of Base Coat: Apply MYK Deck Coat @ 0.40 kg/m2 evenly using an
English trowel and subsequently, if required, use a short piled lamb’s roller to
smoother all the trowel edge marks.
3)Spreading of Silica Quartz : Immediately after application of MYK Deck Coat,
while it is still wet, BROADCAST silica quartz having mesh size of 0.7 to 1.0 @ 2.0
2.5 kg/m2
4)Application of Sealer Coat: Evenly apply MYK Deck Coat @ 0.60 kg/m2 using a
lamb’s wool short piled roller. Ensure excess material does smoothen the
broadcast surface.
5)Application of Line Marking: Providing and applying abrasion resistant
thixotropic epoxy resin topping (Non Broadcast) MYK Deck Coat @ 0.80 kg/m2
admixed with 0.60% MYK Indufibre in white or yellow colour
Providing and laying approved Anti-static machine tuffed pattern loop nylon Pattern
Loomed pile carpet, made out pile yarn of face weight 881.55 gm/sqm, of
type 100 % Permacolour polypropylene, SRS Strain resistance system,
Solution Dyed, Flammability ASTM E-648 flooring Radiant Panel - Class I,
NBS Smoke Chamber Test -less than 450 (flaming), static property 3.5 KV
or less (tested as per AATCC-134),of density 242.69 kg/m3, with 11 stitches per inch, carpet thickness approx. 6 to
8mm, in available widtth installed strictly as per manufacturer's recommendations
with approved adhesive SR-998, making cut outs for junction boxes, providing &
fixing approved, fire resistant, acoustic underlayer etc. complete as directed by the
Engineer. Location of joints to be decided with prior approval of the Engineer and
actual net area of carpet laid shall be measured for payment.
Note : A warranty shall be submitted by the Contractor for a period of ten years
from the certified date of completion for the satisfactory performance of the entire
carpet flooring system.
9.20.1 In pattern loop pile carpet (Style Name : Space, Style Number : 50911)
manufactured. by Shaw Industries Inc., USA or approved equivalent.
Sqmt 1000 9787.03 9787030.00
9.21 Supplying and filling in sunken portions with brick aggregate of 40mm nominal size
and fine sand @ 8%by volume of brick aggregate at all floors including, watering,
ramming consolidating and dressing complete.
Cum 1404 970.00 1361880.00
9.22 Providing and laying on the locations as shown in the drawings Spectra laminated
wooden flooring in approved shade with 8mm thick planks of AC-5 grade , each
plank having size of 1210 mm (Length) x 193mm having proloc joints, tongue and
groove, the edges duly pre impregneted, laid overover 3mm thick mosture resistant
barier made of 1mm thick polythene and 2 mm thick foam of approved quality .
Flooring shall be laid over IPS flooring including all required accessories complete
as per the drawings and manufacturer's specifications .( Base flooring course of
IPS shall be paid seperately in the respective item of BOQ)
Sqmt 74 1596.00 118104.00
SUB TOTAL (FLOORING) 231927017.05
10 ROOFING
10.1 Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4
stone aggregate 10mm and down gauge) including finishing with cement mortar
1:3 (1 cement : 3 fine sand) as per standard design :
9.20.
Stup Consultants P.Ltd 18 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
10.1.1 In 75x75mm deep chase metre 200 143.1 28620.00
10.2 Making khurras 45x45 cm with average minimum thickness of 5 cm cement
concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm
nominal size) over P.V.C. sheet 1mx1mx400micron, finished with 12mm cement
plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the
edges and making and finishing the outlet complete
each 77 186.65 14372.05
10.3 Providing and fixing false ceiling at all height including providing and fixing of frame
work made of special sections, power pressed from M.S. sheets and galvanized
with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and
consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm
and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash
fastener 12.5 mm dia x 50mm long with 6mm dia bolts other flange of cleat fixed to
the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of
required size and other end of angle hanger fixed with intermediate G.I. channels
45x15x0.9 mm running at the rate of 1200 mm centre to centre to which the ceiling
section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each
having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction
perpendicular to G.I. intermediate channel with
10.3.1 connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every
junction, including fixing perimeter channels 0.5 mm thick 27 mm high having
flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition
with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @
230 mm interval, including fixing of gypsum board to ceiling section and perimeter
channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c,
including jointing and finishing to a flush finish of tapered and square edges of the
board with recommended jointing compound , jointing tapes , finishing with jointing
compound in 3 layers covering upto 150 mm or both sides of joint and two coats of
primer suitable for board, all as per manufacturer’s specification and also including
the cost of making openings for light fittings, grills, diffusers, cutouts made with
frame of perimeter channels suitably fixed, all complete as per drawings,
specification and direction of the Engineer in Charge but excluding the cost of
painting with :
10.3.1..1 12.5 mm thick tapered edge gypsum fire resistant board conforming to IS: 2095-
Part I.
sqm 65448 1022.95 66950031.60
10.4 Extra for providing Access door panals in gypsum /calcium silicate board false
ceiling including the cost of extra framing and other accessories required complete
at the locations shown in the drawings or as directed by the Engneer Incharge
sqm 1261 580.00 731380.00
10.5 Providing and fixing tiled false ceiling of approved materials of size 595x595 mm in
true horizontal level suspended on inter locking metal grid of hot dipped galvanized
steel sections ( galvanized @ 120 gsm/sqm, both side inclusive) consisting of main
"T" runner with suitably spaced joints to get required length and of size 24x38mm
made from 0.30mm thick (minimum) sheet, spaced at 1200mm center to center
and cross "T" of size 24x25mm made of 0.30mm thick (minimum) sheet, 1200mm
long spaced between main "T" at 600mm center to center to form a grid of
1200x600 mm and secondary cross "T" of length 600mm and size 24x25mm made
of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600mm
panel to form grids of 600x600mm and wall angle of size 24x24x0.3 mm and laying
false ceiling tiles of approved texture in the grid including, wherever, required,
cutting/making, opening for services like diffusers, grills, light fittings, fixtures,
smoke detectors etc. Main "T" runners to be suspended from ceiling using GI
slotted cleats of size 27 x 37 x 25 x1.6 x mm fixed to ceiling with 12.5 mm dia and
50 mm long dash fasteners, 4mm GI adjustable rods with galvanised butterfly level
clips of size 85 x 30 x 0.8 mm spaced at 1200mm center to center along main T,
bottom exposed width of 24 mm of all T-sections shall be pre-painted with
polyester paint, all complete at all heights as per specifications drawings and as
directed by Engineer-in-charge.
10.5.1 12.5mm thick square edge PVC Laminated Gypsum Tile of size 595x595mm,
made of Gypsum plasterboard; manufactured from natural gypsum as per IS 2095
part I and laminated with white 0.16mm thick fire retardant PVC film on the face
side and 12micron metalized polyester on the back side with all edges sealed with
the face side PVC film which goes around and wraps the edges and is bonded to
the edges and the back side metalized polyester film so as to make the tile a
completely sealed unit.
sqm 5428 1136.90 6171093.20
Stup Consultants P.Ltd 19 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
10.5.2 Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight
calcium silicate false ceiling tiles of approved texture spintone/cosmos / Hexa or
equivalent of size 595 x 595 mm in true horizontal level suspended on inter locking
metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per
sqm including both side) consisting of main 'T' runner suitably spaced at joints to
get required length and of size 24x38mm made from 0.33 mm thick (minimum)
sheet, spaced 1200mm centre to centre, and cross "T" of size 24x28mm made out
of 0.33mm (Minimum) sheet, 1200mm long spaced between main'T' at 600mm
centre to centre to form a grid of 1200x600mm and secondary cross 'T' of length
600mm and size 24 x28mm made of 0.33mm thick (Minimum) sheet to be inter
locked at middle of the 1200x 600mm panel to from grid of size 600x600mm,
resting on periphery walls /partitions on a Perimeter wall angle pre-coated steel of
size(24x24X3000 mm made of 0.40 mm thick (minimum) sheet with the help of rawl
plugs at 450mm centre to centre with 25mm long dry wall screws @ 230mm
interval and laying 15mm thick densified edges calicum silicate ceiling tiles of
approved texture (Spintone / Cosmos/hexa) in the grid including, cutting/ making
opening for services like diffusers, grills,light fittings, fixtures, smoke detectors etc.,
whereever required, Main 'T' runners to be suspended from ceiling using G.I.
slotted cleats of size 25x35x1.6mm fixed to ceiling with 12.5 mm dia and 50mm
sqm 18956 1649.15 31261287.40
10.6 Providing and fixing thermal insulation with Resin Bonded Fibre glass wool
conforming to IS: 8183 having density 24 kg/m3, 50 mm thick,wrapped in 200G
Virgin Polythene Bags fixed to wall with screw, rawel plug & washers and held in
position by criss crossing GI wire etc. complete as per directions of Engineer-in-
Charge.
sqm 70648 319.90 22600295.20
10.7 Providing and fixing at all height false ceiling with 6mm thick BWP fire retardent
plywood (Confirming to IS-710) screwed to the metal grid and covered with
approved quality 4mm thick decorative vineer pasted with approved quality glue /
adhesive including providing and fixing of frame work made of special sections
power pressed from M.S. sheet and galvanised in accordance with zinc coating of
grade 350 as per IS : 277 and consisting of angle cleats of size 25mm wide x
1.6mm thick with flanges of 22mm and 37mm at 1200mm centre to centre one
flange fixed to the ceiling with dash fastener 12.5mm diax40mm long with 6mm
dia bolts to the angle hangers of 25x25x0.55mm of required length, and other end
of angle hanger being fixed with nut and bolts to G.I. channels 45x15x0.9mm
running at the rate of 1200mm centre to centre to which the ceiling section 0.5mm
thick button wedge of 80mm with tapered flanges of 26mm each having clips of
10.5mm at 450mm centre to centre shall be fixed in a direction perpendicular to
G.I. channel with connecting clips made out of 2.64mm diax230mm long G.I. wire
at every junction .
Sqmt 50 1948.00 97400.00
10.8 Providing and fixing Ecophon FOCUS Ds 20 mm thickness and completely
concealed edge , easily demountable tiles of 600x 600 / 1200x 600/ 1200x 1200
false ceiling with, Gypsteel pre coated (Exposed portion only) GI T Grid system
in 600x600mm module which includes providing and fixing wall
angle(24x24x0.40x3000) along the perimeter of the room with help of self-
tapping screws((3.5x35) at 300mm centers. Then suspending the main
T(40x15x0.30x3600) from the soffit with help of soffit cleat(27x37x25x1.6), rawl
plugs(38x12 dia) and wire rod of dia 4mm with Leveling spring
clip(85x30x0.8mm) at 1200mm c/cwe have to fix space bar in direction
perpendicular to the main T to make a grid of 600x1200mm.Finally the space bar
(2 meter long) get interlock in the main T at every 600 mm and screws to be put
inside the main T and space Bar to lock and give strength to the system .
The glass wool core of the tiles should be tested and classified as non-combustible
according to prEN ISO 1182 . The system should have Sound Absorption NRC
value of 0.9 (according to EN ISO 11654). Tiles should withstand a permanent
ambient RH upto 95% at 30 * C without sagging , warping or delaminating (ISO
4611). The light reflectance of the tiles should not be less than 84%. CAC value for
sound insulation should be 25 db according to ASTM E 1414 and evaluation
according to ASTM E 413.
work to be complete in all respects as per specifications,drawings and directions of
Engineer-in-charge.
Sqmt 600 4655.00 2793000.00
10.9 Providing and laying roof insulation with 50 mm thick impervious sprayed, closed
cell free Rigid Polyurethane foam over deck insulation conforming to IS - 12432 Pt.
III (density of foam being 40-45 kg/ cum), over a coat of polyurethane primer
applied @ 6-8 sqm per litre, laying 400 G polythene sheet over PUF spray over a
course of average thickness 50 mm thick cement screed 1: 2 : 4 (1 cement : 2
coarse sand : 4 stone aggregate 20 mm nominal size) and sealing the joints with
Bonding agent /polymerized mastic, all complete as per direction of Engineer-in-
Charge.
Sqmt 5018 1230.88 6176564.56
Stup Consultants P.Ltd 20 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
10.10 Supply of 0.50mm Thick TCT double skin insulated metal profiled sheet cladding
for external faced at various elevations with troughed Zinc aluminium alloy coated
(both side) sheet of yeild stress 550 Mpa confirming to AS1397/IS 513/ IS 277/IS
14246/ASTM A446 grade E to be used on external face (outer face) of cladding
system. Metalic coating thickness to be minimum 150gms/ sq.m. on both side. The
outer side (expose face) to be permanently colour coated with Zinc Alluminiun of
Dry film thickness 20microns over a 5 micron primer. Inner side of external sheet to
be provided with suitable pre coating of minimum 7 microns thick over coat of 5
micron primer coat. Galvanized M.S. sheet to be used as inner liner (internal face)
of the cladding system. The expose face to be permanently colour coated
confirning to IS:14246 and confirm to class 3 for the durability. With
Galvalume(PPGL) of Dry Film thickness 20 microns over primer. Inner face of
external sheet to be provided with suitable pre coating of minimum 7 microns. The
Rate of galvanization not to be less than 150gm/ sq.m.with Z spacers made of at
least 2mm thick galvanized steel sheet of grade 375 as per IS:277 to maintain
1.50m centre to centre hold the insulation and external sheeting. Rate quoted shall
Sqmt 1169 2744.00 3207736.00
10.11 Providing and fixing 10 mm thick multicell Thermo clear solar control
polycarbonate panals from M/S Coxwell or Danpolan of approved colour & quality,
fire retardant confirming to IS 14443-1987 with specially designed duly natural
anodized with approved leak proof system confirming to IS-733-1987 ,Alloy 6063
T6 including EPDM Rubber gaskets ,GE Silicon Sealant , Gold forged fasteners
etc. complete as per the drawings on existing R.C.C OR M.S. structure.( Steel
structure will be paid separately )
Note :- Febrication /Shop drawing shall be preapered by the contractor and same
will be got approved from the Consultant before starting the execution of the work
and procurement of the materials.
Sqmt 600 2973.00 1783800.00
Tensile Roof Membrain :Providing ,designig and installing / erection in
locations as shown in the drawings or directed by the engineer incharge
outdoor tensile membrane fabric sun shading device / system of
approved colour , grade and quality comprising of the PTFE Fabric
including cutting, welding and cables, plates and necessary hardware for
fixing the fabric. As per approved shape. The fabric should be 100%
recyclable at the end of its lifespan, with a undertaking from the
manufacturer that it has the facilities for recycling the membrane. Warranty
on fabric should be 10 years manufacturers standard warranty. Scope of
work will be inclusive of :Development of the Membrane’s initial shape & form ,details of all connections
between Membrane & Structure ,details of seams on the Membrane ,details of
tensioning & clamping of the Membrane ,details of the fabrication of structural
members..Patterning, cutting, welding of the Membrane for the approved
shape.Structural steel elements
Stainless steel tensile cable with Stainless Steel turn buckle, Stainless Steel rings,
locking arrangement, accessories etc. The Stainless Steel cable shall be fixed to
pergola by using PU painted MS brackets & SS hooks welded to pergola structure.
The post tensioned Stainless Steel cable shall be passed through the seam
stitching of the fabric.
Central prismatic feature / splice made out of Stainless Steel plate with connecting
stainless steel connecting spheres at both ends including Stainless Steel
ornamental features etc. complete.
All Stainless Steel components shall be of non magnetic type, grade 316
conforming to American Iron & Steel institute and the surface shall be satin finish.
The whole assembly shall be fabricated and fixed taut to the pergola as shown in
the drawing including
Rates shall also includes all necessary materials, fabrication / assembly,
machining, installation in required position, tensioning the system, buffing,
polishing, stitching, scaffolding, staging ,electricity ,storage and water etc.complete
all as per manufacturer's guidelines and as approved by the Engineer in Charge.
Sqmt 3000 36670.00 110010000.00
SUB TOTAL (ROOFING) 251825580
FINISHING
Note :- Rates for external plaster are for height upto 10m. from ground level
unless otherwise stated.11.1 12mm cement plaster of mix
11.1.1 1:6 (1 cement: 6 find sand) sqm 44128.5 109.00 4810006.50
11.2 15mm cement plaster on the rough side of single or half brick wall of mix:
11.2.1 1:6 (1 cement: 6 find sand) sqm 44128.5 172.80 7625404.80
11
10.12
Stup Consultants P.Ltd 21 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
11.3 18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1
cement: 5 coarse sand) finished with a top layer 6mm thick cement plaster 1:6 (1
cement: 6 fine sand).
(Water proofing compound shall also be added in this item however ut shall be
measured and paid for in the respective head)
sqm 240.55
11.4 6mm cement plaster of mix
11.4.1 1:3 (1 cement: 3 fine sand) sqm 161866 134.70 21803350.20
11.5 Extra for providing and mixing water proofing material in cement plaster work in
proportion recommended by the manufacturers
Per
bag of
50 kg
cemen
t used
1000 50.65 50650.00
11.6 Extra for plastering exterior walls of height more than 10 m from ground level for
every additional height of 3 m or part thereof.
sqm 10000 37.95 379500.00
11.7 Extra for plastering on circular work not exceeding 6 m in radius:
11.7.1 In one coat sqm 50 18.80 940.00
11.8 Providing and applying plaster of paris putty of 2 mm thickness over plastered
surface to prepare the surface even and smooth complete.
sqm 29102 110.95 3228866.90
11.9 White washing with lime to give an even shade:
11.9.1 New work (three or more coats) sqm 67310 16.2 1090422.00
11.10 Distempering with oil bound washable distemper of approved brand and
manufacture to give an even shade
11.10.1 New work (two or more coats) over and including water thinnable priming coat with
cement primer.
sqm 695 89.70 62341.50
11.11 Distempering with 1st quality acrylic distemper (ready mixed) of approved
manufacturer, of required shade and colour complete, as per
manufacturer’s specificati
11.11.1 Two or more coats on new work sqm 82871 50.65 4197416.15
11.12 Finishing walls with water proofing cement paint of required shade
11.12.1 New work (Two or more coats applied @ 3.84 kg/10 sqm) sqm 461 57.85 26668.85
11.13 Painting with oil type wood preservative of approved brand and manufacture: sqm
11.13.1 New work (two or more coats) sqm 1322 31.90 42171.80
11.14 Providing and applying two coats of fire retardant paint on cleaned wood/ply
surface @ 3.5 sqm per litre per coat including preparation of base surface as per
recommendations of manufacturer to make the surface fire retardant.
sqm 50 247.65 12382.50
11.15 Wall painting with acrylic emulsion paint of approved brand and manufacture to
give an even shade:
11.15.1 Two or more coats on new work sqm 147286 80.5 11856523.00
11.16 Painting with synthetic enamel paint of approved brand and manufacture of
required colour to give an even shade:
11.16.1 Two or more coats on new work over an under coat of suitable shade with ordinary
paint of approved brand and manufacture
sqm 2467 106.25 262118.75
Providing and fixing of FAVETON BERSAL (or equivalent) Extruded Hollow Clay/
Ceramic Ventilated Rainscreen Facade Tiles of dimensions 300/400mm (c/c) x
max 1000mm (c/c) x 16mm thickness in horizontal direction on the building facade.
The facade tiles shall be rigid and of adequate strength and shall satisfy all the
performance parameters. The tiles shall have a total thickness of 16 mm (±10%)
and shall be installed using the ventilated rainscreen principle, with provision for
uninterrupted natural ventilation of the space between the cladding panels and the
structural wall from top to bottom. The tiles shall be fixed to an extruded aluminium
support framework consisting of vertical aluminium tubular sections measuring
40x40mm spaced at maximum 1200mm c/c intervals, fixed to the wall using
aluminium L-brackets spaced at maximum 1500mm distance vertically.
11.17
Stup Consultants P.Ltd 22 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
Each aluminium bracket to be fixed to the brickwork/ RCC structure using stainless
steel anchor fasteners for brickwork/ RCC as applicable, and to be fixed to the
vertical aluminium tubes using two stainless steel self-drilling screws of dimensions
23x5.5mm. Horizontal aluminium C-sections measuring 56x25mm to be fixed to the
40x40mm vertical aluminimum tubes using stainless steel self-drilling screws at
maximum 1200mm intervals horizontally and at maximum 400mm c/c intervals
vertically matching to the tile-grid. The tiles to be fixed to the horizontal aluminium
C-sections using approved sealent adhesive. The vertical joint between adjacent
tiles to be a 6mm open groove. The wall top and window sills to be protected using
an aluminium-composite-panel flashing/ coping. External square angles between
two vertical tile pieces to be a mitred corner formed by the two tiles, complete all to
the satisfaction of the Engineer-in-charge.
Colour : Light & Terracotta Colours Sqm 15337 8687.30 133237120.10
11.18 Finishing with Epoxy paint (two or more coats) at all locations prepared and applied
as per manufacturer's specifications including appropriate priming coat,
preparation of surface, necessary scaffolding / staging etc.
11.18.1 Preparing the surface to ensure complete removal of mill scale by grit blasting
confirming to SA 2.5 to achieve rust free surface.
MT 250 2206.90 551725.00
11.20 Providing and applying "Intergard-251" manufactured by Akzonobel or approved
equivalent two component epoxy anti-corrosive primer to minimum dry film
thickness of 50 microns over structural steel sections
MT 250 1569.40 392350.00
11.23 Providing and applying "Interchar-963" manufactured by Akzonobel or approved
equivalent Intumescent fire protection coating to achieve the fire rating level of 60
minutes in accordance with BS: 476 Part 20 & 21, and conforming to National
Building Code No. 3.33 to minimum dry film thickness of 50 microns over
structural steel sections.
MT 250 42776.70 10694175.00
11.24 Providing and applying "Interthane-900" manufactured by Akzonobel or approved
equivalent toap coating tcomplete as per the manufacturers specifications
MT 250 4325.00 1081250.00
11.25 Painting over structural steel sections with approved synthetic enamel paint of
approved brand and manufacturre to give an even shade over a coat of ready
mixed red oxide zinc chromate primer including necessary scaffolding / staging,
surface preparation etc.
11.25.1 Two or more coats on new work MT 100 2331.00 233100.00
SUB TOTAL (FINISHING) 201638483.1
12 PILING WORK
12.1 Boring, providing and installation bored cast-in-situ reinforced cement concrete
piles of grade M-25 of specified diameter and length below pile cap, to carry a safe
working load not less than specified, excluding the cost of steel reinforcement but
including the cost of boring with bentonite solution and temporary casing of
appropriate length for setting out and removal of same and the length of the pile to
be embedded in the pile cap etc. by Crawler mounted, telescopic boom hydraulic
pilling Rig all complete, including removal of excavated earth with all its lifts and
leads (length of pile for payment shall be measured up to bottom of pile cap).
12.1 Note: Truck Mounted rotary/TMR/Tube well boring machine shall not be used.
11.1.1 600 mm dia. Shore piles Metre 18900 2,671.00 50481900.00
12.2 Boring, providing and installation bored cast-in-situ reinforced cement concrete
piles of grade M-25 of specified diameter and length below pile cap, to carry a safe
working load not less than specified, excluding the cost of steel reinforcement but
including the cost of boring with bentonite solution and temporary casing of
appropriate length for setting out and removal of same and the length of the pile to
be embedded in the pile cap etc. by Crawler mounted, telescopic boom hydraulic
pilling Rig all complete, including removal of excavated earth with all its lifts and
leads (length of pile for payment shall be measured up to bottom of pile cap).
12.2.1 750 mm dia. piles Metre 21215 4,962.65 105282619.75
12.2.2 1000 mm dia. piles Metre 300 8,201.40 2460420.00
12.2.3 1200 mm dia. piles Metre 200 11,334.45 2266890.00
12.3 Same as above but for empty boring only (excluding concrete work) upto specified
depths as directed by the Engineer
(upto 1200 mm dia piles)
Metre 12022 3311.00 39804842.00
Stup Consultants P.Ltd 23 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
12.4 Vertical load testing of piles in accordance with IS 2911 (Part IV) including
installation of loading platform and preparation of pile head or construction of test
cap and dismantling of test cap after test etc. complete as per specification & the
direction of Engineer in-charge.
12.4.1 Single pile above 250 tonne and upto 300 tonne capacity
12.4.1.1 Initial test (Test Load 2.5 times the Safe capacity) Per 3 46,808.45 140425.35
12.4.1.2 Routine test (Test Load 1.5 times the Safe capacity) Per 7 26,714.50 187001.50
12.50 Lateral load testing of single pile in accordance with IS Code of practice IS : 2911
(Part IV) for determining safe allowable lateral load on pile :
12.5.1 Upto 50 tonne capacity pile Per 40 17,422.50 696900.00
12.6 Integrity testing of Pile using Low Strain/ Sonic Integrity Test/ Sonic Echo Test
method in accordance with IS 14893 including surface preparation of pile top by
removing soil, mud, dust & chipping lean concrete lumps etc. and use of
computerised equipment and high skill trained personal for conducting the test &
submission of results, all complete as per direction of Engineer-in-charge.
Per
test
768 74.5 57216.00
Designing, providing and installing at specified inclination as approved and
directed by Engineer, testing stressing and locking inclined soil anchors of the
specified capacity for the shore piling to control earth pressure and prevent
over turning/sliding of shore piling / capping beam including providing and
fixing GI casing pipe of 150 mm dia at required inclination in the
reinforcement cage held in position by providing required spacer bars etc. as specified, boring hole of specified diameter through soil and to the length
required for design capacity, providing guide shoe of size and shape, bulb etc., as
required including drilling and grouting wherever necessary stabilizing the bore
with full depth sacrificial casing pipe of required diameter for drilling in the soil /
rock as specified providing 7 ply low relaxation
class II strands conforming to IS 14268 of required size (diameter), strength and
numbers, providing corrosion protection to the free and fixed length of anchor as
specified, preparing cement grout using ordinary Portland cement as specified, and
grouting fixed length of strand of anchor with cement grout as specified after
providing required packers, spacers and centralizers.
Providing flexible plain HDPE sheathing as specified, to the free length of anchor
assembly, pre-stressing the anchors and locking to the bearing plate, anchor
assembly, end protection treatment to anchor assembly, necessary bursting zone
reinforcement behind anchor assembly including testing of anchors as specified
and as per IS 10270, sealing / treating / plugging the Rock Anchor head using
clamp rings, swellable water stops, grouting with Nitoseal MS 50 including
cleaning, curing etc.complete as per approved design and as directed by the
Engineer.
The Contractor shall be responsible for meeting the test acceptance criteria.
Design factor of safety shall be minimum 2.0 for tension in strands and 3.0 for bond
stress between the cement grout and surrounding soil. The rate includes cost of
designing anchors, cost of all operation and all inputs of labour material and T & P
etc. involved in the work and all other incidental expenditure for completing the job
as per the directions of the Engineer. However for purpose of payment only the
number of anchors provided, installed, and tested to the satisfaction of the
Engineer shall be measured.
Note : The Soil Anchoring System including post-tensioning works shall be
executed through a specialised agency approved by the Engineer.
12.7.1 33 T net design capacity Nos 567 66786.30 37867832.10
SUB TOTAL PILING 239246046.7
13 ALUMINIUM WORK
12.7
Stup Consultants P.Ltd 24 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
13.1 Providing and fixing aluminium work for doors, windows, ventilators and partitions
with extruded built up standard tubular sections/ appropriate Z sections and other
sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash
fasteners of required dia and size, including necessary filling up the gaps at
junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene
gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and
jointed mechanically wherever required including cleat angle, Aluminium snap
beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as
per architectural drawings and the directions of Engineer-in-charge. (Glazing,
paneling and dash fasteners to be paid for separately) :
13.1.1 For fixed portion
13.1.1.1 Polyester powder coated aluminium (minimum thickness of polyester powder
coating 50 micron)
Kg 100 385.10 38510.00
13.1.2 For shutters of doors, windows & ventilators including providing and fixing hinges/
pivots and making provision for fixing of fittings wherever required including the
cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for
separately).
13.1.2.1 Polyester powder coated aluminium (minimum thickness of polyester powder
coating 50 micron)
Kg 100 443.20 44320.00
13.2 Providing and fixing glazing in aluminium door, window, ventilator shutters and
partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the
architectural drawings and the directions of engineer-in-charge . (Cost of
aluminium snap beading shall be paid in basic item):
13.2.1 With float glass panes of 4.0mm thickness Sqmt 20 828.75 16575.00
13.3 Providing and fixing double action hydraulic floor spring of approved brand and
manufacture conforming to IS : 6315, having brand logo embossed on the body /
plate with double spring mechanism and door weight upto 125 kg., for doors,
including cost of cutting floors , embedding in floors as required and making good
the same matching to the existing floor finishing and cover plates with brass pivot
and single piece M.S. sheet outer box with slide plate etc. complete as per the
direction of Engineer-in-charge.
13.3.1 With stainless steel cover plate Each 4 2,039.00 8156.00
13.4 Filling the gap in between aluminium frame & adjacent RCC/ Brick/ Stone work by
providing weather silicon sealant over backer rod of approved quality as per
architectural drawings and direction of Engineer-in-charge complete
13.4.1 Upto 5mm depth and 5mm width Metre 20 88.75 1775.00
13.5 Providing and fixing double glazed hermetically sealed glazing in aluminium
windows, ventilators and partition etc. with 6 mm thick clear float glass both side,
having 12 mm air gap, including providing EPDM gasket, perforated aluminium
spacers, desiccants, sealant (Both primary and secondary sealant) etc. as per
specifications, drawings and direction of Engineer-in-charge complete
Sqmt 15312 3487.10 53394475.20
13.6 Providing and fixing stainless steel (SS 304 grade) adjustable friction windows
stays of approved quality with necessary stainless steel screws etc. to the side
hung windows as per direction of Engineer-in-charge complete.
13.6.1 205 X 19 mm Each 6 288.75 1732.50
13.6.2 710 X 19 mm Each 6 1088.30 6529.80
13.7 Providing and fixing 100mm brass locks (best make of approved quality) for
aluminium doors including necessary cutting and making good etc. complete.
Each 2 418.65 837.30
13.8 Providing and fixing anodised aluminium (anodised transparent or dyed to required
shade according to IS: 1868. Minimum anodic coating of grade AC 15) sub frame
work for windows and ventilators with extruded built up standard tubular sections
of approved make conforming to IS: 733 and IS: 1285, fixed with dash fastener of
required dia and size (Dash fastener to be paid for separately).
Kg 50 312.20 15610.00
13.9 Providing and fixing aluminium casement windows fastener of required length for
aluminium windows with necessary screws etc. complete.
13.9.1 Polyester powder coated minimum thickness 50 micron aluminium. Each 20 54.00 1080.00
13.10 Providing and fixing aluminium round shape handle of outer dia 100mm with SS
screws etc. complete as per direction of Engineer-in-charge
13.10.1 Polyester powder coated minimum thickness 50 micron aluminium. Each 6 77.25 463.50
Stup Consultants P.Ltd 25 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
13.11 Providing and fixing 12 mm thick frameless toughened glass door shutter of
approved brand and manufacture, including providing and fixing top & bottom pivot
& spring type fixing arrangement and making necessary holes etc. for fixing
required door fittings, all complete as per direction of Engineer-in-charge (Door
handle, lock and stopper etc.to be paid separately).
Sqmt 5 4746.25 23731.25
SUB TOTAL (ALUMINIUM WORK) 53553795.55
14 WATER PROOFING OF MAIN BUILDINGS AND WATER TANKS
14.1 Grading roof for water proofing treatment with
14.1.1 Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20
mm nominal size)
Cum 589 5,570.25 3280877.25
14.2 Horizontal Surfaces on Blinding Concrete (for Raft Slab and Piled foundation Slab)
14.2.1 Waterproofing of Raft: Supplying and installing positive side waterproofing
treatment for “Raft Slab” by using “Preprufe 300R,MYK Power Prufe,Fosroc
Proofex Rngage or Sika Proof A”, 1.2mm thick fully bonded HDPE sheet
membrane ( manufactured by Grace Construction Products ,MYK Schomburg
,Fosroc chemicals India Pvt.Ltd or Sika India Pvt.Ltd ) before casting of the base
RCC slab. The pre-applied, fully bonded HDPE sheet membrane to get bonded to
the underneath of the poured concrete used as base/ raft slab. ‘’ No protection
screed, enabling faster construction’’ The fully bonded HDPE sheet membrane
shall consist of a thick HDPE film, a highly aggressive pressure sensitive adhesive
and weather resisting coating which bonds integrally to poured concrete of base
slab. The membrane shall conform to basement waterproofing protection to grades
2, 3 as defined in BS 8102:2009. The fully bonded HDPE sheet waterproofing
membrane shall have following minimum properties : 1) Resist hydrostatic
pressure of up to 70 m head of water as per ASTM D 5385 modified 2) Puncture
Resistance of 990 N 3) Adhesion to concrete of 2.88 N/mm 4) Shear strength of
joints of 9.52 N/mm The fully bonded HDPE sheet membrane,shall be installed
with standard 75mm selvedge laps and 75mm end laps taped with PrePrufe Tape
HC, a double side coated adhesive tape over the entire area and turned up on to a
vertical timber. The membrane shall be laid over the concrete blinding having
smooth dried surface including necessary removal of release liner while applying
Sqmt 37114 2190.00 81279660.00
14.3 RCC Wall (Unconfined areas : Post Application)
14.3.1 Waterproofing of un-confined Retaining Wall:Supplying and Installing 'Bituthene
8000 ,MYK self Stick 3000 or Proofex GP' (manufactured by Grace Construction
Products , Fosroc chemicals India Pvt.Ltd or Ardex endura India Pvt.Ltd ), a self
adhesive, cold applied , flexible 1.5mm thick waterproofing membrane comprising
of a self adhesive rubberized asphalt with cross laminated HDPE film with a unique
solar reflective film on top surface . The membrane shall have pre-marked overlaps
of 50mm and shall be applied on the uniform surface of the Vertical RCC Wall after
application of single component solvent based bituminous primer approved &
installed as per manufacturer’s recommendation. The self adhesive membrane
shall conform to BS 8102:2009 and shall have following minimum properties : (i)
Puncture resistance of 280N (ii) Resistance to Hydrostatic head of 70m (ASTM D
5385) (iii) Should be resistant to Sulphates, Nitrates and salt in soil.
Sqmt 9521 1326.19 12626654.99
14.4 Membrane Protection:
14.4.1 Supply & spot bonding 25mm thick expanded polystyrene board onto the Bituthene
8000 membrane with liquid mastic. The expanded polystyrene shall have minimum
density of 24 kg/cum (or as decided by engineer–in–charge) and shall be applied
prior to backfilling. The backfilling shall be done within 2-3 days of fixing protection
board.
Sqmt 9521 232.10 2209824.10
14.5 Membrane Termination:
14.5.1 Membrane Termination: Where the Bituthene 8000 or Proofex GP is required to be
terminated on retaining wall, a chase should be provided of dimensions (20 x 20)
mm at a distance of 300 mm from ground level or 150 mm from podium/roof slab
level for membrane termination. The Bituthene 8000 or Proofex GP should be
dressed into the chase and pointed with Bituthene LM/ mortar or as approved by
Grace prior to backfilling. Rates include 3rd quality brickwork for membrane
protection. All systems to be installed as per manufacturer's recommendations, etc.
complete with all lead and lift for all materials and labour and as directed by
Engineer in-charge
Sqmt 515 927.00 477405.00
14.6 Construction Joint Treatment:
Stup Consultants P.Ltd 26 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
14.6.1 Waterproofing treatment to Construction joints: Supply and installing Supercast
SW20 with adhesive Supercast Adhesive,Water bar RS 800 or ADCOR 500S, a
hydrophilic, rubber based construction joint of 25mm x 20mm fixed with ADCOR
MS Adhesive and ADCOR Mastic (manufactured by Grace Construction Products
, Fosroc chemicals India Pvt.Ltd or Ardex endura India Pvt.Ltd ) at required
locations such as (i) Junction of raft/retaining wall & (ii) at all other locations as
mentioned in drawings All systems to be installed as per manufacturer's
recommendations, etc. complete with all lead and lift for all materials and labour
and as directed by Engineer in-charge. (Refer drawing: STD-INDIA-PP-002)
Metre 10370 996.00 10328520.00
14.7 Basement and other Roofs (With Land Scaping) treatment :
14.7.1 Providing and applying solvent free two component Polyurethane spray applied
waterproofing system (manufactured by BASF India Ltd or equivelent product from
Fosroc chemicals India Pvt.Ltd MYK Schomborg or Ardex endura India Pvt.Ltd )
on Landscape on horizontal and verticle face at 2mm total thickness . I/c applying
moisture insensitive epoxy primer broadcasted with sand after necessary surface
preparation followed by applying waterproofing membrane using specialized 2
component spray machine as per manufactures specifications .
The mixed product should have 100% solid content as per DIN 53213, density of
0.9-1.0g/cm3, tensile strength of 8-10 Mpa as per DIN 53504, fast setting less than
1 min and green certified
14.7.1.1 For area coverd by land scaping Sqmt 28248 2294.00 64800912.00
14.7.1.2 For exposed area of walls(U.V. STABLE TOP COAT)
The top sealer for use on exposed areas shall be a pigmented, single component,
moisture curing, UV and weather resistant, protective top sealer. It is based on
high quality aliphatic polyurethane prepolymers. It should be should be stirred well
and applied evenly by roller, brush or by spray
Sqmt 4148 795.60 3300148.80
14.8 For terraces over pre layed PUF insulation
14.8.1 For the area covered by interlocking tiles
14.8.1.1 Providing and applying solvent free two component Polyurethane spray applied
waterproofing system (manufactured by BASF India Ltd or equivelent product from
Fosroc chemicals India Pvt.Ltd MYK Schomborg or Ardex endura India Pvt.Ltd )
over insulation horizontal and verticle face at 1.8mm averagethickness using
specialized 2 component spray machine as per manufactures specifications BASF
or equivalent. The mixed product should have 100% solid content as per DIN
53213, density of 0.9-1.0g/cm3, tensile strength of 8-10 Mpa as per DIN 53504,
fast setting less than 1 min and green certified.
Consumption : 2.2-2.4 Sqmt
Sqmt 5018 1974.00 9905532.00
14.9 Providing and laying factory made coloured chamfered edge Cement Concrete
paver blocks of required strength, thickness & size/shape, made by table vibratory
method using PU mould, laid in required colour & pattern over average 50mm thick
compacted bed of cement mortar 1:12 (1cement :12 fine sand ), compacting and
proper embedding/laying of inter locking paver blocks into the sand bedding layer
through vibratory compaction by using plate vibrator, filling the joints with jamuna
sand and cutting of paver blocks as per required size and pattern, finishing and
sweeping extra sand in basement roof and terraces of main buildin (after PUF anf
water proofing) etc. complete as per manufacturer’s specifications & direction of
Engineerin-Charge. 60mm thick C.C. paver block of M-35 grade with approved
colour, design & pattern.
Each 5018 823.00 4129814.00
14.10 For Under Ground water Tanks
14.10.1 The cleaning and preparation of the substrate on which the waterproofing coating
is applied must be carried out thoroughly by water jetting or grit blasting to leave a
sound base for the application. Any laitance present on the surface must be
removed mechanically. Release oil and other contaminants which may impair
adhesion must be removed prior to the application. Surface moisture shall be
below 4% prior to commencing application of this modified polyurethane waterproof
membrane system
14.10.2 External wall and floor Waterproofing
Stup Consultants P.Ltd 27 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
14.10.3 Application Of Waterproofing Coating:
Providing and applying a Liquid, cold-applied elastomeric waterproofing
membrane system such as, MasterSeal HLM 5000 (manufactured by BASF India
Ltd or equivelent product from Fosroc chemicals India Pvt.Ltd MYK Schomborg
or Ardex endura India Pvt.Ltd )strictly to the written application guidelines of the
manufacturer. The elastomeric, seamless waterproof membrane shall exhibit the
following key performanceproperties.
Applied in 2 coats to a DFT of 1.5mm thick
Having an elongation capacity over 600% , Tensile Strength: 150 psi (1.0 MPa),
ASTM D412. with solid content more than 85% applied on the RCC surface, As per
specification. And complying to ASTM C 836
Coverage – 2.5 Kg / Sqmt.
Sqmt 1316 1277.70 1681453.20
INTERNAL WATERPROOFING (Walls and floors)
Providing and applying MasterSeal 551 (manufactured by BASF India Ltd or
equivelent product from Fosroc chemicals India Pvt.Ltd MYK Schomborg or Ardex
endura India Pvt.Ltd )system as follows, Surface preparation, prewetting the
surface and applying el
Sqmt 11580 813.10 9415698.00
14.10.5 PROTECTIVE COATING
Providing and applying Masterprotect 1818 (manufactured by BASF India Ltd or
equivelent product from Fosroc chemicals India Pvt.Ltd MYK Schomborg or Ardex
endura India Pvt.Ltd )a non-toxic, high build epoxy coating, solvent-less, taint free
potable grade, protective coating. The product shall exhibit excellent bond strength
with the substrate at least exceeding 1.5 MPa, when tested as per ASTM D4541.
The product shall be formulated to have high build thickness exceeding 200
microns per coat on average and shall be applied to achieve overall thickness of
400 microns in two coats. The product must be approved by reputed institute such
as CFTRI for use in contact with potable water.
Sqmt 1316 522.70 687873.20
14.11 Anti Root Barrier:
Providing and laying anti root barrier membrane of M/s. E.I. Dupont (India) Pvt.
Ltd.or equivelent approved to the locations as shown in the drawings or as
directed complete all as per manufactures specifications. Root Barrier shall be
consisting of green colored Elvalloy polymer layer of approx. 25 GSM, fused onto
Typar non woven polypropylene geotextile layer of 300 GSM, so that the total
weight of the membrane is approx. 325 GSM with nominal thickness of 0.8 mm.
The membrane shall be loosely laid over the surfaces with an overlap of 50 mm
between the adjoining rolls.
Sqmt 28248 432.00 12203136.00
14.12 Construction Joint Treatment and Sealing of side faces of Pile Caps for 600mm to
1200 mm dia piles as described below:
14.12.1 A)Re-Profiling of Pile Surface: The compression pile surface will be re-profiled
using non-shrink cementitious grout, PrePrufe Grout CEM 100 in minimum 15mm
thickness, all as per manufacturers recommendations/ drawings. Refer Pile Head
Treatment Drawing
b)Sealing of side faces of Pile Cap: The 1000 mm dia pile caps penetrations will be
sealed all around on the PrePrufe membrane with a 2 component liquid membrane,
Bituthene LM, as per drawing.
Each 1258 5000.00 6290000.00
14.13 Providing orange colour safety foot rest of minimum 6 mm thick plastic
encapsulated as per IS : 10910 on 12mm dia steel bar conforming to IS : 1786
having minimum cross section as 23 mmx25mm and over all minimum length 263
mm and width as 165mm with minimum 112 mm space between protruded legs
having 2 mm tread on top surface by ribbing or chequering besides necessary and
adequate anchoring projections on tail length on 138 mm as per standard drawing
and suitable to with stand the bend test and chemical resistance test as per
specifications and having manufacture's permanent identification mark to be visible
even after fixing, including fixing in manholes with 30x20x15 cm cement concrete
block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal
size) complete
Each 123 311.60 38326.80
SUB TOTAL (WATER PROOFING) 222655835.3
15.00 STRUCTURAL GLAZING AND ALUMINIUM COMPOSITE PANEL
15.1 Providing and supplying aluminium extruded tubular and other aluminium sections
as per the architectural drawings and approved shop drawings, the aluminium
quality as per grade 6063 T5 or T6 as per BS 1474,including super durable powder
coating of 60-80 microns conforming to AAMA 2604 of required colour and shade
as approved by the Engineer-in-Charge.
(The item includes cost of material such as cleats, sleeves, screws etc. necessary
for fabrication of extruded aluminium frame work. Nothing extra shall be paid on
this account).
Kg 256008 338.25 86594706.00
14.10.4
Stup Consultants P.Ltd 28 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
15.2 Designing, fabricating, testing, protection, installing and fixing in position semi
(grid) unitized system of structural glazing (with open joints) for linear as well as
curvilinear portions of the building for all heights and all levels,
including
a) Structural analysis & design and preparation of shop drawings for the specified
design loads conforming to IS 875 part III (the system must passed the proof test at
1.5 times design wind pressure without any failure), including functional design of
the aluminum sections for fixing glazing panels of various thicknesses, aluminium
cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps
etc., structural and weather silicone sealants, flashings, fire stop (barrier)- cum-
smoke seals, microwave cured EPDM gaskets for water tightness, pressure
equalisation & drainage and protection against fire hazard including
b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of
6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3
Dimentional movement for achieving perfect verticality and fixing structural glazing
system rigidly to the RCC/ masonry/structural steel framework of building structure
using stainless
steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with
nuts and washers etc. of stainless steel grade 316, of the required capacity and in
required numbers.
c) Providing and filling, two part pump filled, structural silicone sealant and one part
weather silicone sealant compatible with the structural silicone sealant of required
bite size in a clean and controlled factory / work shop environment , including
double sided spacer tape, setting blocks and backer rod, all of approved grade,
brand and manufacture, as per the approved sealant design, within and all around
the perimeter for holding glass.
Sqmt 32001 2,556.15 81799356.15
d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick
and of sizes, shapes and profiles, as required as per the site conditions, to seal the
gap between the building structure and all its interfaces with curtain glazing to
make it watertight.
e) Making provision for drainage of moisture/ water that enters the curtain glazing
system to make it watertight, by incorporating principles of pressure equalization,
providing suitable gutter profiles at bottom (if required), making necessary holes of
required sizes and of required numbers etc. complete. This item includes cost of all
inputs of designing, labour for fabricating and installation of aluminium grid,
installation of glazed units, T&P, scaffolding and other incidental charges including
wastages etc., enabling temporary structures and services, cranes or cradles etc.
as described above and as specified. The item includes the cost of getting all the
structural and functional design including shop drawings checked by a structural
designer, dully approved by Engineer-in-charge. The item also includes the cost of
all mock ups at site, cost of all samples of the individual components for testing in
an approved laboratory, field tests on the assembled working structural glazing as
specified, cleaning and protection till the handing over of the building for
occupation. In the end, the Contractor shall provide a water tight structural glazing
having all the performance characteristics etc. all complete as required, as per the
Architectural drawings, as per item description, as specified, as per the approved
shop drawings and as directed by the Engineerin-Charge.
15.3 Providing, assembling and supplying vision glass panels (IGUs) comprising of
hermetically-sealed 6-12- 6 mm insulated glass (double glazed) vision panel units
of size and shape as required and specified, comprising of an outer heat
strengthened float glass 6mm thick, of approved colour and shade with reflective
soft coating on surface # 2 of approved colour and shade, an inner Heat
strengthned clear float glass 6mm thick, spacer tube 12mm wide, dessicants,
including primary seal and secondary seal
(structural silicone sealant) etc. all complete for the required performances, as per
the Architectural drawings, as per the approved shop drawings, as specified and as
directed by the Engineer-in-Charge. The IGUs shall be assembled in the factory/
workshop of the glass processor. (Payment for fixing of IGU Panels in the curtain
glazing is included in cost of item No.15.2 of this sub head)
For payment, only the actual area of glass on face # 1 of the glass panels
(excluding the areas of the grooves and weather silicone sealant) provided and
fixed in position, shall be measured in sqm.
(i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on
face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make
having properties as visible Light transmittance (VLT) of 25
to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %,
shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The
properties of performance glass shall be decided by technical sanctioning authority
as per the site requirement
Sqmt 32001 4,090.95 130914490.95
Stup Consultants P.Ltd 29 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
15.4 Additional cost for using Saint Gobain make Envision SKN 465 glass (6mm thick
toughened glass + 12mm airgap + 6mm clear float glass ) having properties as
visible Light transmittance (VLT) of 50 %, Light reflection internal 16%, light
reflection external 13 % and U value of 1.5 W/m2 degree K,Solar factor 0.27 in
place of Coloured tinted float glass 6mm thick substrate with reflective soft coating
on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved
make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light
reflection internal 10 to 15%, light reflection external 10 to 20 %, shading
coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc as specified in
BOQ item No.15.3 of S.H.15.
Sqmt 10078 1471.00 14824738.00
15.5 Extra for openable side / top hung vision glass panels (IGUs) including providing
and supplying at site all accessories and hardwares for the openable panels as
specified and of the approved make such as heavy duty stainless steel friction
hinges, min 4 -point cremone locking sets with stainless steel plates, handles,
buffers etc. including necessary stainless steel screws/ fasteners, nuts, bolts,
washers etc. all complete as per the Architectural drawings, as per the approved
shop drawings, as specified and as directed by the Engineerin- Charge.
Sqmt 3200 3,062.25 9799200.00
15.6 Providing, fabricating and supplying shadow box of required size and shape, for
fixing in the spandrel portion of the structural glazing, in linear as well as curvilinear
portions of the building by providing semi -rigid, inorganic, non-combustible fibre
glass wool insulation 50 mm thick, conforming to IS: 8183 and BS: 3958 Part 5.
The insulation layer shall have facing (factory bonded on surface # 1of the fibre
glass insulation layer), of black nonwoven fibre glass tissue of nominal thickness
0.5 mm and nominal mass not less than 60 gm / sqm, made of randomly oriented
glass fibres distributed in a binder by a wet-lay process including fixing 1.5 mm
thick solid aluminum sheet backing using, 6 mm thick cement board including SS
rivets, nuts, bolts, washers etc complete
Sqmt 25 1634.5 40862.50
15.7 Providing and supplying Spandrel Glass Panels comprising of 6 mm thick heat
strengthened monolithic float glass of approved colour and shade with reflective
soft coating on surface # 2 of approved colour and shade so as to match the colour
and shade of the IGUs in the vision panels etc. ,all complete for the required
performances as specified, as per the Architectural drawings, as per the approved
shop drawings, as specified, and as directed by the Engineer- in-Charge. For
payment, only the actual area of glass on face # 1 of the glass panels (but
excluding the area of grooves and weather silicone sealant) provided and fixed in
position, shall be measured in sqm.(Payment for fixing of Spandrel Glass Panels in
the curtain glazing is included in cost of relevent Item*).
(i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on
face # 2, having properties as visible Light transmittance (VLT) of 25 to 35%, Light
reflection internal 10 to 15%, light reflection external 10 to 20%, shading coefficient
(0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of
performance glass shall be decided by technical sanctioning authority as per the
site requirement.
Sqmt 25 2997.25 74931.25
Designing, fabricating, testing, installing and fixing in position Curtain Wall with
Aluminium Composite Panel Cladding, with open grooves for linear as well as
curvilinear portions of the building, for all heights and all levels etc.
including:
a) Structural analysis & design and preparation of shop drawings for pressure
equalisation or rain screen principle as required, proper drainage of water to make
it watertight including checking of all the structural and functional
design.
b) Providing, fabricating and supplying and fixing panels of aluminium composite
panel cladding in pan shape in metalic colour of approved shades made out of
4mm thick aluminium composite panel material consisting of
3mm thick FR grade mineral core sandwiched between two Aluminium sheets
(each 0.5mm thick). The aluminium composite panel cladding sheet shall be coil
coated, with Kynar 500 based PVDF / Lumiflon based fluoropolymer resin coating
of approved colour and shade on face # 1 and polymer (Service) coating on face #
2 as specified using stainless steel screws, nuts, bolts, washers, cleats, weather
silicone sealant, backer rods etc
Sqmt 25 3775.3 94382.5015.8
Stup Consultants P.Ltd 30 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
c) The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip
Galvanised with serrations and serrated washers to arrest the wind load
movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS 316,
Nylon separators to prevent bi-metallic contacts all complete required to perform as
per specification and drawing The item includes cost of all material & labour
component, the cost of all mock ups at site, cost of all samples of the individual
components for testing in an approved laboratory, field tests on the assembled
working curtain wall with aluminium composite panel cladding, cleaning and
protection of the curtain wall wit aluminium composite panel cladding till the
handing over of the building for occupation. Base frame work for ACP cladding is
payable under the relevant aluminium item.s The Contractor shall provide curtain
wall with aluminium composite panel cladding, having all the performance
characteristics all complete , as per the Architectural drawings, as per item
description, as specified, as per the approved shop drawings and as directed by
the Engineer-in-Charge. However, for the purpose of payment, only the actual area
Conducting performance testing in structural glazing system as per criteria
specified in clause - 24.1 to 24.7 of Technical Specification for Structural
Glazing and Cladding System including cost of conveyance to the System
Principal's or any other approved independent specialised facade testing
laboratory for witnessing the test by one representatives each from the
Employer, Architect and Engineer-in-charge, preparation and submission of
final test report in the approved proforma etc. complete all as directed by the
Engineer-in-charge.
One
Job
1 1306000.00 1306000.00
The Bidder to indicate the location & name of the laboratory seperately in the Bid,
where he proposes to carry-out the above performance testing
15.10Extra over and above BOQ item NO. 13.1 of S.H.13 and 15.1 of S.H.15
for doing 35 micron PVDF coating instead of 50 micron polyester powder cating
Sqmt 256008 29.00 7424232.00
15.11 Providing and installing in positions at the locations as shown in the drawings
S.S.316 grade fish hooks having capacity to carry 250 Kg safe working load for
Façade cleaning operations of Admin Block including ,Hilti Metalic fastners ,grout
,S.S.Sockets, HDU's . light weight Call complete as per approved shop drawings
and as directed by the Engineer-in-Charge
Each 207 3484.50 721291.50
15.12 Supplying & fixing high tensile bolts with hexagonal nuts, grade 8.8 or 10.9
and conforming to IS : 4000, IS : 1367 of approved make (Unbrako,GKW,
TVS or approved equivalent) and in required diameter, length etc. for
connection of structural members including plain / spring washers all
complete as directed by the Engineer.
Kg 400 114.20 45680.00
SUB TOTAL 333639870.9
16 STAINLESS STEEL RAILINGS AND OTHER MISCELLANEOUS WORKS
Supply and installation of AISI 316 Grade Stainless Steel Knock Down ( Welding
free) Welding free railing system (kich ,D line,Kelco or Fitwell technologies)
comprising of 50mm Ø , 2mm wall thickness Handrail containing high grade
Stainless Steel Bushings at every Bend / Joint of Railing to provide extra strength
fixed by T- Bracket (Matt Finish) on 40 x40mm ,1.5mm wall thickness square tube
of Stainless Steel baluster of AISI 316 grade , with the help of M8 x 12 mm
Handrail Clamping Screws. The balusters shall be fixed with investment casted
base plate of 100x100x10mm thick shall be covered by glossy finished cover caps
of required size .Base plates shall be secured by Anchor Fasteners (extra strength
Bolt with Zinc coating of M12x70 size & Anchor sleeves of Brass M12 x 45mm) on
Concrete Surface/ Floor and concealed with AISI 316 grade cover Cap (Glossy
Finish) to conceal the mounting anchor fasteners. Baluster to be placed at
maximum 900mm to 1200 mm c/c (as shown in the drawing)along with 3 Nos. 16
mmØ of 1.5mm wall thickness mid rails connected at the side of baluster and
strengthened with high quality brass bushes and bolted with high precision
Investment casted T-bracket (Combi. Finish).
15.9
16.1
Stup Consultants P.Ltd 31 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
Handrail, Baluster and In-fill members should be of Matt Finish of 320 grit done
with minimum 3 times finishing process in automatic polishing machine to achieve
smooth and long lasting hairline finish. If any welding to be done that will be only at
factory by automatic welding machine in Tig welding process with accurate
precision so as no welding marks, burrs are visible on products.Wall thickness of
all Pipes/tubes shall be taken as 1.5mm along with all visible components
developed in High Grade S.S. Railing height to be taken @ 915 or 450mm from
floor level or as shown in the relevent Architectural drawings. Complete Handrail
and Baluster system shall be made in factory using advance machineries to
achieve best quality and finishing and installed at site by highly technical
installation team with utmost care and precision to avoid any damage at site. In No
case, any Welding, cutting, bending, Finishing or any kind of fabrication work shall
be allowed at site. On completion of installation, Handrail shall be completely
covered with plastic wrapping to protect from any damages of nearby site work.
16.1.1 Floor mounted for staicase waste slabs and landings height of railing 915 mm Metre 1316 20944.60 27563093.60
16.1.2 Floor mounted for staicase to be fixed on top of existing walls height of railing
350mm
Metre 5263 10506.30 55294656.90
16.2 Supply and installation of satin finish stainless steel AISI 316 SS wall mounted
system having 50mm dia tube rail with 1.5mm wall thickness connected with
approved unified stem keys in bead blast finish complete with all necessary bends,
termination, metallic fasteners, chemical grouts, staging / scaffolding etc. to the
satisfaction of engineer in charge.
16.2.1 Two point Handrail system: Metre 3189 7381.00 23538009.00
16.3 Supply & fixing of SWR pipes (R/R) Type A confirming to IS 13592:1992 of
specified length and diameter in RCC / brick work for laying service lines etc. as
directed by Engr Incharge.
16.3.1 Dia 75mm SWR pipe Type A sleeve Metre 800 292.00 233600.00
16.3.2 Dia 110 mm SWR pipe Type A sleeve Metre 1600 480.00 768000.00
16.3.3 Dia 160 mm SWR Type A pipe sleeve Metre 500 480.00 240000.00
Supply and install modular toilet cubicles of -BESCO make 'TITAN Ceiling Hung '
series as per manufaturer's std specifications.All intermediate panels shall be of 12
mm thickness and pilasters, doors shall be made up of Solid Compact Laminate
18 mm thickness (Phenolic Core Board) as per IS 2046 based on thermosetting
resins, homogeneously reinforced with cellulose fibers making cubicles impervious
to Water, resistant to Fire, etc. Compact laminate should be Greenguard and IGBC
certified.
Item shall be inclusive of the following hard ware and accessories
Hardware and Fixing
All accessories shall be of SS 304 grade including all hardware/fittings except
heavey duty aluminium top rail.The pilaster are fixed to the overhead top rail and all
doors are hung on these pilasters. All the fittings are concealed using SS shoe box
at the top
Accessories
Standard accessories include SS Hinges, SS Door knob, SS thumb turn indicator,
SS coat hook, SS shoe box and SS channels (All in SS 304 grade) and heavy duty
aluminium top rail.
16.4.1 Titan Ceiling Hung Series Cubicles: Std Sizes
(W x D x H)- 900 mm x 1550 mm x 2400 mm, (Height is including 100 mm gap
from bottom) Door Size- 600 mm
Set 448 67243.00 30124864.00
16.4.2 Toilet Cubicle I-Shape (Front Partition) with standard dimension of 2400mm Height
x 1000mm Width which includes 600mm door size width).
Set 5 64105.30 320526.50
16.4.3 L-Safety Support Bar for Handicaped Toilet Cubicle Set 40 8218.60 328744.00
16.4.4 Horizontal / Vertical Support Bar having 300mm size for Handicaped Toilet
Cubicle
Set 40 5095.60 203824.00
16.4.5 Urinlal partitions od Size of Partition : 500mm x 1200mm with standard
Accessories of Stainless Steel (Grade - 304)
Set for
each
100 5259.90 525990.00
16.4
Stup Consultants P.Ltd 32 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY RATE (INR) AMOUNT IN INR
BILL OF QUANTITIES FOR CIVIL WORKS
16.6 Design, supplying and installing PVDF coated aluminium louvered panel in
approved colour minimum 2mm thick and with ample rigidity within
extruded shape and with concealed stiffener supports in approved
spacing with an assumed efficiency of 50%, including all aluminium
brackets, sub-frames, silicon sealant, approved fixing arrangement to
main structure etc. complete as per approved shop drawings and
specifications.
( Flat area of the surface covered with louvers shall be measured
and payed for.)
Sqmt 1440 9147.00 13171680.00
16.7 PVDF coated Aluminium sheetcladding with 2mm thick Aluminium sheet
supported on deep zink galvanized M.S..supporting structure along with all the
required accessories ,stagging and scaffolding complete
Sqmt 7032 5542.00 38971344.00
SUB TOTAL �(STAINLESS STEEL RAILINGS AND OTHER WORKS) 191284332
Stup Consultants P.Ltd 33 of 234
S.NO PARTICULARS BASIC
RATES IN
INR
MODEL
as per godrej
DESI
GN
UNIT NOS. RATE IN INR AMOUNT IN
INR
17
A TABLES
A.1 DG 213080 ARRIVE T1 Each 1 245042 245042
A.2 ADG 85802 MAESTRO T2 Each 21 98672 2072112
A.3 IG/DIG 80806 NUMERO UNO T3 Each 46 92927 4274642
A.4 DSP/SP/ASP 45234 IMPRESS T4 Each 132 52019 6866508
A.6 CA 14857 FINNESSE T6 Each 249 17085 4254165
A.7 ACA 8111 FINNESSE T7 Each 546 9328 5093088
A.9 CONFERENCE 3960 ENCARTA T9 Each 137 4554 623898
A.10 RECEPTION 62889 RECEPTION
TABLE
T10 Each 40 72322 2892880
B.1 CHAIRS
B.1 DG 40016 HALO (VERY
HIGH BACK)
C1 Each 1 46018 46018
B.2 ADG 39228 HALO ( HIGH
BACK)
C2 Each 24 45112 1082688
B.3 IG/DIG 34043 SEDNA (VERY
HIGH BACK)
C3 Each 242 39150 9474300
B.4 DSP/SP/ASP 22370 MONARCH C4 Each 207 25725 5325075
B.5 WORKSTATION 5717 VENTILLO C5 Each 1597 6575 10500275
B.6 CA 6820 SPYDER C6 Each 337 7843 2643091
B.7 CONFERENCE 3568 STAR C7 Each 504 4103 2067912
B.10 RECEPTION/DG
P
8856 PULSE C10 Each 73 10184 743432
C VISITOR'S
CHAIRSC.1 DG 20083 HALO
VISITOR
VC1 Each 10 23096 230960
C.2 ADG 21435 HALO
VISITOR
VC2 Each 274 24650 6754100
C.3 IG/DIG 21435 SEDNA
VISITOR
VC3 Each 560 24650 13804000
C.4 DSP/SP/ASP 17897 MONARCH
VISITOR
VC4 Each 264 20581 5433384
C.4 INTEROGATION
ROOM
6263 BREEZE VC5 Each 15 7202 108030
C.5 CA 2586 CLASSIC VC6 Each 524 2974 1558376
D SOFA
D.1 DG 16632 S-1.1 Each 1 19127 19127
23323 S-1.2 Each 9 26822 241398
28284 S-1.3 Each 1 32527 32527
D.2 ADG 17974 S-2.1 Each 1 20670 20670
22143 S-2.2 Each 84 25465 2139060
26903 S-2.3 Each 42 30939 1299438
D.3 IG/DIG 13599 S-3.1 Each 22 15639 344058
18327 S-3.2 Each 149 21076 3140324
22996 S-3.3 Each 2 26445 52890
D.4 DSP/SP/ASP 10962 S-4.1 Each 8 12606 100848
15648 S-4.2 Each 231 17995 4156845
18657 S-4.3 Each 80 21456 1716480
CONSTRUCTION OF PROPOSED UP POLICE BHAVAN AT GOMTI NAGAR EXTENSION AT LUCKNOW.UP
BOQ FURNITURE
MILAN
JINERIO
D-ALPINA
VIDA
LOOSE FURNITURE
Supplying and placing the following furniture items at the places as shown in the drawings. Basic rates given are
inclusive of all taxes ,cartage ,loading, unloading and placing in position at the locations shown in the drawings or
as directed by the Engineer incharge.For the selection of the product only 15% shall be added in the basic rates
for profit and over heads of the contractor. Irrespective of the percentage quoted basic rates shall remain same,
Decision for selection of brand and module shall be done by the committee formed by Client ,UPRNN.LTD and
consultant Architect. All product shall be factory made and no fabrication work shall be done at site.Original
invices of the purchase shall be produced by the contractor and same shall be defaced by the client or his
authorised representative.
Approved Makes -Godrej ,Feather Lite ,B.P.Ergo,Eurotech Indo office Solutions,Amardeep ,Geeken or as
speciofied in approved list of makes
Stup Consultants P.Ltd 34 of 234
S.NO PARTICULARS BASIC
RATES IN
INR
MODEL
as per godrej
DESI
GN
UNIT NOS. RATE IN INR AMOUNT IN
INR
BOQ FURNITURE
D.5 WAITING 6135 S-5.1 Each 1 7055 7055
12447 S-5.2 Each 177 14314 2533578
9236 S-5.3 Each 110 10621 1168310
D.6 CA 6135 S-6.1 Each 64 7055 451520
12447 S-6.2 Each 225 14314 3220650
9236 S-6.3 Each 71 10621 754091
D.7 CENTRAL
WAITING HALL
23643 S-8.1 Each 16 27190 435040
40410 S-8.2 Each 16 46471 743536
E COFFEE
TABLESE.1 DG 9905 GAYLE CT-1 Each 3 11391 34173
E.2 ADG 9637 ALLICE CT-2 Each 42 11083 465486
E.3 IG/DIG 7344 ACCURA CT-3 Each 67 8446 565882
E.4 DSP/SP/ASP 6763 CRYSTALLINE CT-4 Each 112 7777 871024
E.5 WAITING 6266 GLAZE CT-5 Each 32 7206 230592
E.6 CA 6266 GLAZE CT-6 Each 96 7206 691776
E.7 CENTRAL
WAITING HALL
6757 DUAL CT-8 Each 8 7771 62168
F SIDE TABLES
F.1 DG 4380 VEGAS ST-1 Each 7 5037 35259
F.2 ADG 2381 GLIDE
CORNER
ST-2 Each 84 2738 229992
F.3 IG/DIG 8398 BLOOM ST-3 Each 97 9658 936826
F.4 DSP/SP/ASP 5441 CRYSTALLINE
CORNER
ST-4 Each 204 6257 1276428
F.5 WAITING 4690 GLAZE
CORNER
ST-5 Each 33 5393 177969
F.6 CA 4690 GLAZE
CORNER
ST-6 Each 252 5393 1359036
H BOOK STACK
H.1 DG 22830 ARRIVE
BOOK STACK
SC-1 Each 2 26255 52510
H.2 ADG 45790 MAESTRO
BOOK STACK
SC-2 Each 63 52659 3317517
H.3 IG/DIG 57301 NUMERO
UNO BOOK
SC-3 Each 110 65896 7248560
H.4 DSP/SP/ASP 49345 IMPRESS
BOOK UNIT
SC-4 Each 315 56747 17875305
H.5 CA 9984 GAIN SC-6 Each 765 11482 8783730
I WORK STATION
I.1 SECTION STAFF 32691 GAIN L-
SHA
Each 1392 37595 52332240
I.2 NOC 7520 GAIN SING
LEWI
Each 98 8648 847504
K.5 RECORD ROOM 18763 GLASS DOOR
STORWEL
SC-5 Each 1035 21577 22332195
L DISPLAY UNIT
K.6 MUSEUM 17755 4 DOOR
BOOKCASE
DU-1 Each 36 20418 735048
M DESK FURNITURE
M.1 PENSION
DINING
9580 TIME OUT CF4 Each 4 11017 44068
M.2 PENSION
DINING
14001 TIME OUT CF6 Each 6 16101 96606
M.3 CAFETRIA 18422 TIME OUT CF8 Each 68 21185 1440580
M.4 LIBRARY 5743 LECTURA
TABLE
LS4 Each 10 6605 66050
N CONFERENCE
N.1 DG 107147 TALK
VENEER
MT11 Each 1 123219 123219
N.2 ADG 50450 TALK
UNITISED
MT2 Each 21 58018 1218378
N.3 MEETING
ROOMS
6688 SENATE MT3 Each 16 7691 123056
O CLASS ROOM
O.1 TRAINNING
ROOM
15618 UNLEARN DC2 Each 20 17961 359220
O.2 TRAINNING
ROOM
23861 UNLEARN DC3 Each 33 27440 905520
O.2 CLASS ROOM 5176 SCHOLAR FC2 Each 112 5952 666624
TOTAL 234175962
ORLEANS
URBAN SOFA
UPHOLSTERY
IN FABRIC
QUILTURBAN SOFA
UPHOLSTERY
IN FABRIC
QUILT
Stup Consultants P.Ltd 35 of 234
18
A ROAD, PARKING AND PAVEMENT WORK
1 Providing and laying in position cement concrete of specified
grade excluding the cost of centering and shuttering - All work
up to plinth level :
1.1 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40
mm nominal size).cum 3310.00 4301.15 14236806.50
2 Preparation and consolidation of sub grade with power road
roller of 8 to 12 tonne capacity after excavating earth to an
average of 22.5 cm. depth, dressing to camber and
consolidating with road roller including making good the
undulations etc. and re-rolling the sub grade and disposal of
surplus earth with lead upto 50 metres.
sq.m 2011.00 81.29 163474.19
3 Extra for compaction of earth work in embankment under
optimum moisture conditions to give at least 95% of the
maximum dry density (proctor density).
cum 1005.50 10.15 10205.83
3.1 Supplying and stacking at the site.
3.2 90mm to 45mm size stone aggregate. cum 250.37 1310.45 328096.71
3.3 63mm to 45mm cum 188.03 1348.20 253500.02
3.4 53mm to 22.4mm cum 94.01 1354.00 127295.29
3.5 Stone screening 13.2 mm nominal size (Type A). cum 57.31 1558.15 89303.03
3.6 Stone screening 11.2 mm nominal size (Type B). cum 27.15 1,471.00 39935.44
3.7 Moorum. cum 44.24 646.35 28595.82
4 Laying, spreading and compacting stone aggregate of specified
sizes to WBM specifications in uniform thickness, hand picking,
rolling with 3 wheeled road / vibratory roller 8-10 tonne capacity
in stages to proper grade and camber, applying and brooming
requisite type of screening / binding material to fill up interstices
of coarse aggregate, watering and compacting to the required
density .
cum 616.87 425.05 262202.40
5 Supplying, stacking and Spreading 6 mm thick red bajri,
watering and rolling complete including preparation of the
surface and rolling. ( For two layers)
5.1 With road roller / hand roller sqm 2011.00 14.9 29963.90
6 Scarifying metalled (water-bound) road surface including
disposal of rubbish, lead upto 50m and consolidation of the
aggregate received from scarifying with power road roller of 8 to
10tonne capacity.
sqm 2011.00 13.75 27651.25
7 Providing and laying 60mm thick factory made cement
concrete interlocking paver block of M -30 grade made by
block making machine with strong vibratory compaction,
of approved size, design & shape, laid in required colour
and pattern over and including 50mm thick compacted
bed of fine sand, filling the joints with fine sand etc. all
complete as per the direction of Engineer-in-charge.
sqm 2436.00 602.20 1466959.20
CONSTRUCTION OF PROPOSED UP POLICE BHAVAN AT GOMTI NAGAR
EXTENSION AT LUCKNOW.UP
S.NO. DESCRIPTION OF ITEMS UNIT
EXTERNAL DEVELOPMENT WORKS, LAND SCAPING AND WATER FEATURES,
Qty. RATE (INR) AMOUNT (INR)
Stup Consultants P.Ltd 36 of 234
18
S.NO. DESCRIPTION OF ITEMS UNIT
EXTERNAL DEVELOPMENT WORKS, LAND SCAPING AND WATER FEATURES,
Qty. RATE (INR) AMOUNT (INR)
8 Providing and laying design mix cement concrete of M-30
grade, in roads/ taxi tracks/ runways, using cement
content as per design mix, using coarse sand and graded
stone aggregate of 40 mm nominal size in appropriate
proportions as per approved & specified design criteria,
providing dowel bars with sleeve/ tie bars wherever
required, laying at site, spreading and compacting,
mechanically by using needle and surface vibrators,
levelling to required slope/ camber, finishing with
required texture, including steel form work with sturdy
M.S. channel sections, curing, making provision for
contraction/ expansion, construction & longitudinal joints
( 10 mm wide x 50 mm deep) by groove cutting machine,
providing and filling joints with approved joint filler and
sealants, complete all as per direction of Engineer-in-
charge (Item of joint fillers, sealants, dowel bars with
sleeve/ tie bars to be paid separately)
Note:- Cement content considered in M-30 is @ 340
kg/cum. Excess/ less cement used as per design mix is
payable/ recoverable separately.
9 Cement concrete manufactured in automatic batching
plant (RMC plant) i/c transportation to site in transit
mixer.
Cum 300.00 7143.45 2143035.00
10 Providing and fixing in position pre-moulded joint filler
in expansion joints.
Per cm
depth
per cm
width
per m
length
1000.00 2.45 2450.00
11 Providing and laying in position bitumen hot sealing
compound for expansion joints etc.
12 Using grade ‘A’ sealing compound. Per cm
depth
per cm
width
per m
length
1000.00 2.05 2050.00
Stup Consultants P.Ltd 37 of 234
18
S.NO. DESCRIPTION OF ITEMS UNIT
EXTERNAL DEVELOPMENT WORKS, LAND SCAPING AND WATER FEATURES,
Qty. RATE (INR) AMOUNT (INR)
12.1 Providing and laying at or near ground level factory made
kerb stone of M-25 grade cement concrete in position to
the required line, level and curvature, jointed with cement
mortar 1:3 (1 cement: 3 coarse sand) including making
joints with or without grooves (thickness of joints except
at sharp curve shall not to more than 5mm), including
making drainage opening wherever required complete
etc. as per direction of Engineer-in-charge (length of
finished kerb edging shall be measured for payment).
(Precast C.C. kerb stone shall be approved by Engineer-in-
charge).
cum 290.00 5,295.90 1535811.00
13 Construction of granular sub-base by providing close
graded Material conforming to specifications, mixing in a
mechanical mix plant at OMC, carriage of mixed material
by tippers to work site, for all leads & lifts, spreading in
uniform layers of specified thickness with motor grader
on prepared surface and compacting with vibratory
power roller to achieve the desired density, complete as
per specifications and directions of Engineer-in-Charge.
13.1 With material conforming to Grade-I (size range 75 mm to
0.075 mm ) having CBR Value-30.
Cum 3519.00 2119.90 7459928.10
C WATER BODIES
Water Body 1 & 2 : Providing, fixing, testing &
commissioning of Geyser Jet With Overflow Fountain
Remarks. : (i) Piping & wiring distance from water body to
plantroom/panel taken as 15m. as per standard,
incase of change beyond 10% cost of Piping & wiring
would change on pro-rata basis
Water Body 3: Providing, fixing, testing & commissioning
of Geyser Jet With Overflow Fountain
Remarks. : (i) Piping & Wiring distance from water body to
plantroom/panel taken as 15m. as per standard,
incase of change beyond 10% cost of Piping & wiring
would change on pro-rata basis
1.00 1953595.0 1953595.00
15 HORTICULTURE & LANDSCAPING
15.1 Trenching in ordinary soil up to a depth of 60cm including
removal and stacking of serviceable materials and then
disposing of by spreading and neatly levelling with in a lead of
50m and making up the trenched area to proper levels by filling
with earth or earth mixed with sludge or/and manure before and
after flooding trench with water (excluding cost of imported
earth, sludge or manure).
Cum 10.00 16.95 169.50
15.2 Supplying and stacking of good earth at site including royalty
and carriage up to 1 km ( earth measured in stacks will be
reduced by 20 % for payment)
cum 50.00 144.05 7202.50
15.3 Supplying and stacking sludge at site including royalty and
carriage up to 1 km (sludge measured in stacks will be reduced
by 8% for payment).
cum 10.00 136.85 1368.50
15.4 Supplying and stacking at site dump manure from approved
source, including carriage upto 1km (manure measured in
stacks will be reduced by 8% for payment)
1
ONE
LOT
FOR
ALL
THE
THREE
WATER
BODIES
Stup Consultants P.Ltd 38 of 234
18
S.NO. DESCRIPTION OF ITEMS UNIT
EXTERNAL DEVELOPMENT WORKS, LAND SCAPING AND WATER FEATURES,
Qty. RATE (INR) AMOUNT (INR)
15.4.1 Screened through sieve of I.S. Designation 4.75mm cum 10.00 97.05 970.50
15.5 Uprooting weeds from the trenched area after 10 to 15 days of
its flooding with water including disposal of uprooted vegetation
100sqm 10.00 106.85 1068.50
15.6 Fine dressing the ground 100sqm 10.00 80.20 802.00
15.7 Spreading of sludge, dump manure or/and good earth in
required thickness (Cost of sludge,dump manure or/ and good
earth to be paid separately)
cum 70.00 11.60 812.00
15.8 Mixing earth and sludge or manure in proportion specified or
directed.cum 80.00 7.85 628.00
15.9 Grassing with "Doob" grass including watering and maintenance
of the lawn for 30 days or more till the grass forms a thick lawn
free from weeds and fit for mowing including supplying good
earth if needed(the good earth shall be paid for separately)
15.9.1 In rows 5 cm apart in either direction 100sqm 500.00 384.85 192425.00
B HORTICULTURE & LANDSCAPING
1 Trenching in ordinary soil up to a depth of 60cm including
removal and stacking of serviceable materials and then
disposing of surplus soil, by spreading and neatly leveling
within a lead of 50m and making up the trenched area to
proper levels by filling with earth or earth mixed with
sludge or/and manure before and after flooding trench
with water (excluding cost of imported earth, sludge or
manure).
cum 2086.00 37.1 77390.6
2 Supplying and stacking of good earth at site including royalty
and carriage up to 1 km (earth measured in stacks will be
reduced by 20% for payment
cum 5214.00 308.35 1607736.9
3 Supplying and stacking sludge at site including royalty and
carriage up to 1 km (sludge measured in stacks will be reduced
by 8% for payment).
cum 521.00 239.2 124623.2
4 Supplying and stacking at site dump manure from approved
source, including carriage up to 1 km (manure measured in
stacks will be reduced by 8% for payment) :
5 Screened through sieve of I.S. designation 16mm cum 521.00 184.85 96306.85
6 Rough dressing the trenched ground including breaking clods 100sqm 35.00 71.8 2513
7 Uprooting weeds from the trenched area after 10 to 15 days of
its flooding with water including disposal of uprooted vegetation.
100sqm 35.00 233.05 8156.75
8 Fine dressing of the ground 100sqm 35.00 175.3 6135.5
9 Spreading of sludge, dump manure and / or good earth in
required thickness as per direction of Officer-in-charge (Cost of
sludge, dump manure and / or good earth to be paid separately)
cum 6256.00 25.15 157338.4
10 Grassing with selection No.1 grass including watering and
maintenance of the lawn for 30 days or more till the grass forms
a thick lawn, free from weeds and fit for mowing including
supplying good earth, if needed (the good earth shall be paid for
separately).
10.1 In rows 5 cm apart in both directions 100sqm 20.00 841.25 16825
Stup Consultants P.Ltd 39 of 234
18
S.NO. DESCRIPTION OF ITEMS UNIT
EXTERNAL DEVELOPMENT WORKS, LAND SCAPING AND WATER FEATURES,
Qty. RATE (INR) AMOUNT (INR)
11 Preparation of beds for hedging and shrubbery by excavating
60cm deep and trenching the excavated base to a further depth
of 30cm, refilling the excavated earth after breaking clods and
mixing with sludge or manure in the ratio of 8:1 (8 parts of
stacked volume of earth after reduction by 20% : one part of
stacked volume of sludge or manure after reduction by 8%),
flooding with water, filling with earth if necessary, watering and
finally fine dressing, leveling etc. including stacking and disposal
of materials declared unserviceable and surplus earth by
spreading and leveling as directed, within a lead of 50 m, lift up
to 1.5 m complete (cost of sludge, manure or extra earth to be
paid for separately).
Cum 469.00 105.2 49338.8
12 Digging holes in ordinary soil and refilling the same with the
excavated earth mixed with manure or sludge in the ratio of 2:1
by volume (2 parts of stacked volume of earth after reduction by
20% : 1 part of stacked volume of manure after reduction by 8%)
flooding with water, dressing including removal of rubbish and
surplus earth, if any, with all leads and lifts (cost of manure,
sludge or extra good earth if needed to be paid for separately)
12.1 Holes 1.2 m dia and 1.2 m deep each 25.00 211.9 5297.5
12.2 Holes 90 cm dia, and 90 cm deep each 25.00 90.9 2272.5
12.3 Holes 60 cm dia, and 60 cm deep. each 100.00 28 2800
12.4 Holes 45 cm dia, and 45 cm deep. each 50.00 12.15 607.5
13 Flooding the ground with water including making kiaries and
dismantling the same.
100sqm 35.00 129.5 4532.5
14 Providing and fixing M. S. tree guard 50 cm square in plan,
height 1.40 metre above ground level and 0.50 metre below
ground level. The vertical members shall consist of four nos. of
angle iron of size 25x25x5 mm 1.9 long, one at each corner and
8 nos. flat iron of size 25x5 mm 1.4 long. The vertical members
shall be welded to 4 nos. 25x6 mm M. S. flats placed horizontally
around the vertical member of the cage. One name plate of 1
mm thick M.S. sheet of size 250x100 mm shall be welded to the
tree guard near the middle height and lettered CPWD / PWD/
any other approved name. The tree guard shall be fixed to the
ground by making suitable holes and by embedding four corners
leg in the ground , including refilling the earth , compaction etc.
complete. The tree guard shall be painted with two coats of paint
of approved brand and manufacture over a coat of primer,
complete in all respect.
each 200 2,689.95 537990
15 Preparation of mounds of various size and shape by available
excavated / supplied earth in layers not exceeding 20 cm in
depth, breaking clods, watering of each layer, dressing etc., lead
upto 50 meter and lift upto 1.5 m complete as per direction of
Officer-in-charge.
Cum 313 215.6 67482.8
16 TREES
The rate of the following items include for transportation at site,
Filling excavated pits with prepared manure soil (ratio 1:3,one
part sludge plus two parts good earth by volume ) supply,
transportation & mixing of soil improvement nutrients including
manure as required and inside coat of Aldrin in all pits, flooding
with water,dressing including removal of rubbish & surplus earth
if any with all leads and lifts, planting and stacking in full & final
location including all locations specified .Maintainance of plants
for 12 months replacement of any dead& sickly plants in this
period,supply&spraying of insecticides as required .
16.1 AEGLE MARMELOS
BAEL
Minimum 2.0/2.5m overall height
Stup Consultants P.Ltd 40 of 234
18
S.NO. DESCRIPTION OF ITEMS UNIT
EXTERNAL DEVELOPMENT WORKS, LAND SCAPING AND WATER FEATURES,
Qty. RATE (INR) AMOUNT (INR)
Minimum 40mm caliper
Multibranching at 2.5m from collar each 15 5000 75000.00
16.2 CASURINA ESQUISTIFOLIA
SARU
Minimum 2.0/2.5m overall height
Minimum 40mm caliper
Multibranching at 2.0m from collar each 15 11250 168750.00
16.3 EMBLICA OFFICINALIS
AMLA
Minimum 2.0/2.5m overall height
Minimum 40mm caliper
Multibranching at 2.0m from collar each 15 10500 157500.00
16.4 EUGINIA JAMBOLANA
MALE JAMUN
Minimum 2.0/2.5m overall height
Minimum 40mm caliper
Multibranching at 2.0m from collar each 15 4500 67500.00
16.5 Alstonia Scholaris
Minimum 2.0/2.5m overall height
Minimum 40mm caliper
Multibranching at 2.0m from collar each 25 250 6250.00
16.6 Azadirachta Indica
Minimum 2.0/2.5m overall height
Minimum 40mm caliper
Multibranching at 2.0m from collar each 25 350 8750.00
16.7 Bauhinia Purpurea
Minimum 2.0/2.5m overall height
Minimum 40mm caliper
Multibranching at 2.0m from collar each 25 350 8750.00
16.8 Delonix Regia
Minimum 2.0/2.5m overall height
Minimum 40mm caliper
Multibranching at 2.0m from collar each 25 300 7500.00
16.9 Legestromia Flosregina
Minimum 2.0/2.5m overall height
Minimum 40mm caliper
Multibranching at 2.0m from collar each 25 250 6250.00
17 SHRUBS
17.1 Cledendron Inerme ,Duranta Plumerie,Ficus Panda
,Golden Callistemon,Hamelia Patens
(42+427+77+141+132+330+52+169+443+107+205+195+
166)
each 2486 100 248600.00
TOTAL 33888503
Stup Consultants P.Ltd 41 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITYRATE
(INR)
AMOUNT
(INR)
19 GATE HOUSES AND BOUNDARY WALL
A GATE HOUSE
1.0 EARTH WORK
1.1 Supplying and filling in plinth with Jamuna sand under floors, including watering, ramming,
consolidating and dressing complete.
cum 56 910.25 50974
Providing pre-constructional Anti-termite treatment by treating bottom surface
and sides of excavation, fill in immediate contact with foundation / raft slabs / pile
caps / retaining wall (at the rate of 5 litres of an emulsion concentrate of 1.0 percent
of Chlorpyrifos 20EC or equivalent approved chemical per square meter
2 CONCRETE WORK
2.1 Providing and laying in position cement concrete of specified grade excluding the cost of
centering and shuttering - All work up to plinth level :
2.1.1 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size). cum 42 4301.15 180648.3
2.2 Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement :3 coarse sand : 6
graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40
mm nominal size, well rammed and consolidated and grouted with fine sand including
finishing the top smooth
sqm 93 419.3 38994.9
3 REINFORCED CEMENT CONCRETE WORK
3.1 Centering and shuttering including strutting, propping etc. and removal of form for :
3.1.1 Foundations, footings, bases of columns, etc. for mass concrete. sqm 82 196.45 16108.9
3.1.2 Suspended floors, roofs, landings, balconies and access platform. sqm 103 401.65 41369.95
3.1.3 Lintels, beams, plinth beams, girders, bressumers and cantilevers. sqm 632 332.15 209918.8
3.1.4 Columns, Pillars, Piers, Abutments, Posts and Struts. sqm 137 453.35 62108.95
3.1.5 Stairs, (excluding landings) except spiral-staircases. sqm 20 395.65 7913
3.1.6 Arches, domes, vaults up to 6 m span sqm 564 1066.30 601393.2
3.1.7 Extra for arches, domes, vaults exceeding 6 m span sqm 564 446.65 251910.6
3.1.8 Vertical and horizontal fins individually or forming box louvers band, facias and eaves
boards
sqm 10 587.35 5873.5
3.1.9 Extra for shuttering in circular work (20% of respective centering and shuttering items)
3.1.9.
1
For Columns sqm 8 90.67 725.36
3.1.10 Edges of slabs and breaks in floors and walls
3.1.10
.1
Under 20 cm wide metre 10 116.40 1164
3.2 Extra for additional height in centering, shuttering where ever required with adequate
bracing, propping etc. including cost of de-shuttering and decentering at all levels, over a
height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be
measured)
3.2.1 Suspended floors, roofs, landing, beams and balconies (Plan area to be measured). sqm 1291 159.05 205333.55
3.3 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in
position and binding all complete upto plinth level.
3.3.1 Thermo-Mechanically Treated bars kg 17554 68.10 1195427.4
3.4 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in
position and binding all complete above plinth level.
3.4.1 Thermo-Mechanically Treated bars kg 30370 68.10 2068197
CONSTRUCTION OF PROPOSED UP POLICE BHAVAN AT GOMTI NAGAR EXTENSION AT
LUCKNOW.UP
BILL OF QUANTITIES GATE HOUSE AND BOUNDARY WALL (CIVIL WORKS)
1.2
Stup Consultants P.Ltd 42 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITYRATE
(INR)
AMOUNT
(INR)
BILL OF QUANTITIES GATE HOUSE AND BOUNDARY WALL (CIVIL WORKS)
3.5
Providing and laying in position ready mixed M-25 grade concrete for reinforced cement
concrete work, using fly ash and cement content as per approved design mix, and
manufactured in fully automatic batching plant and transported to site of work in transit
mixer for all leads, having continuous agitated mixer, manufactured as per mix design of
specified grade for reinforced cement concrete work, including pumping of R.M.C. from
transit mixer to site of laying, excluding the cost of centering, shuttering, finishing and
reinforcement, including cost of admixtures in recommended proportions as per IS : 9103 to
accelerate / retard setting of concrete, improve workability without impairing strength and
durability as per direction of the Engineer - in - charge.
NOTE- (1) Cement content considered in this item is @ 330 kg/cum. Excess/ less cement
used as per design mix is payable/ recoverable separately.
(2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of
OPC as per IS : 456. Uniform blending with cement to be ensured in accordance with
clauses 5.2 and 5.2.1 of IS:456 -2000 in the items of BMC and RMC.
3.5.1 All works up to Plinth level cum 195 6561.20 1279434
3.5.2 All works above plinth & up to floor V leve cum 180 7279.60 1310328
4 BRICK / BLOCK MASONRY WORK
A BRICK MASONRY
4.1 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in
foundation and plinth in:
4.1.1 Cement mortar 1:6 (1 cement : 6 coarse sand) cum 61 4,677.25 285312.25
4.2 Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class
designation 7.5 in foundations and plinth in.
4.2.1 Cement mortar 1:4 (1 cement :4 coarse sand) sqm 35 584.75 20466.25
4.3 Extra for providing and placing in position 2 Nos. 6mm dia. M.S. bars at every third course
of half brick masonry.
sqm 35 69.50 2432.5
4.4 Brick work with non modular fly ash bricks conforming to IS:12894, class designation 10
average compressive strength in super structure above plinth level up to floor V level in :
4.4.1 Cement mortar 1:6 (1 cement : 6 Coarse sand) Cum 123 6006.20 738762.6
5 WOOD WORK & PVC WORK
Note :- Wood work items may be substituted with available species of wood as per
direction of Engineer-in-charge for which rates shall be derived from the relevant
items.
5.1 Providing wood work in frames of doors, windows, clerestory windows and other frames,
wrought framed and fixed in position with hold fast lugs or with dash fasteners of required
dia & length ( hold fast lugs or dash fastener shall be paid for separately).
5.1.1 Second class teak wood cum 1.10 91496.90 100646.59
5.2 Providing and fixing ISI marked flush door shutters conforming to IS: 2202 (Part I) non-
decorative type, core of block board construction with frame of 1st class hard wood and well
matched commercial 3 ply veneering with vertical grains or cross bands, teak wood lipping
and face veneers on both faces of shutters :
5.2.1 40 mm thick including including edge lipping,equivelent to Kich DH 235S Stainless Steel
butt hinges with necessarycross head screws.
Sqmt 20 5367.30 107346
5.3 Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm
diameter bolts, nuts and wooden plugs and embedding in cement concrete block
30x10x15cm 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm
nominal size)
each 60.00 117.35 7041
Stup Consultants P.Ltd 43 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITYRATE
(INR)
AMOUNT
(INR)
BILL OF QUANTITIES GATE HOUSE AND BOUNDARY WALL (CIVIL WORKS)
5.4 Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss /
matt / suede finish with high density protective surface layer and reverse side of adhesive
bonding quality conforming to IS : 2046 Type S including cost of adhesive of approved
quality
5.4.1 1.5 mm thick. sqm 40.00 829.7 33188
5.5 BUILDING HARDWARE :Supplying and fixing of following stainless steel hardwares at the
locations shown in the drawings.Complete with cross headed stainless steel screw and
other accessories required complete as per the instructions and satisfaction of Engineer
Incharge.
a Supplying and fixing Stainless Steel AISI 316 grade satin finished door hinge with four
bearings of sizw 127x76x3 and SS self tapping philips cross head screws ,equivelent to
Kich DH 235S
Each 40.00 1103.40 44136
b Supplying and fixing Stainless Steel AISI 316 grade satin finished Pull Handles of Code No.
"PHC2524" manufactured by KICH or approved equivalent, with necessary long stud, SS
screws, all accessories etc. complete.
Set 20.00 5409.00 108180
c Supplying and fixing Stainless Steel AISI 316 grade satin finished Pull Handles of Code No.
"PHC3824" manufactured by KICH or approved equivalent, with necessary long stud, SS
screws, all accessories etc. complete.
Set 2 12851.00 25702
d Satin finished Mortice Handles of Code No. "MH2221S" manufactured by KICH Set 5 4610.00 23050
e Dead bolt of (Code No.MDBS) including Stainless Steel Main Plate & Strike Plate, S.S.
Escutcheons (EEP50) ,locking arrangement with Master Key upto 25 Cylinders (Code No.
PCKNS70) manufactured by KICH
Set 10.00 2584.28 25842.8
f Concealed type hydraulic door closer (Item Code No. : DCC 611S) manufactured by Kich Set 10.00 4648.00 46480
g Floor / wall mounted Stainless Steel AISI 316 grade half moon door stopper (Code No.
DSTHMS) manufactured by KICH Each 5 568.00 2840
h Stainless Steel AISI 316 grade half moon door stopper (Code No. DSTRS) manufactured
by KICH Each 10.00 531.00 5310
i Stainless Steel tower bolt with extension rod (Code No.ATBS 12S) manufactured by KICH Each 10.00 440.67 4406.731
j Indicator Bolt (Item Code No. IB106S) manufactured by KICH Each 10.00 631.40 6314.03015
k 16 SWG stainless steel pictograms / signages of 170mm x 170mm x 2mm size
manufactured by KICHEach 10.00 991.80 9918
l 16 SWG stainless steel pictograms / signages of 300mm x 75mm x 2mm size
manufactured by KICHEach 10.00 1395.30 13953
6 STEEL WORK
Supplying, fabricating, assembling, hoisting / erecting and fixing in position at locations
specified below, structural steel works of MS rolled single / built-up sections conforming to
IS 2062, including joist, channel, angle, tee, plates (plain or chequered) etc. all as per
structural drawings and as per detailed specifications (for materials & workmanship)
including necessary scaffolding / staging, applying a priming coat of approved steel primer
etc. complete in the situations described hereinafter and comprising of :
i) Profile Cutting of components to required lengths/widths and shapes/profiles
ii) Smooth grinding / machining of edges / faces / all welding joints.
iii) Preparing the surface to ensure complete removal of mill scale by using wire brushes &
sand papering
iv) Necessary welding (electric arc welding) for required weld lengths and sizes
Note: The contractor shall submit fabrication drawings for work involved based on
construction drawings (that may be issued during construction period) for approval by the
Engineer.
The fabrication work shall start only after approval of the fabrication drawings. Any change
required in the fabrication drawings shall be carried out at no extra cost.
Fabrication shall be in a perfect Architectural workmanship manner and as provided in
Section V & VI of IS 800 & IS 7215.
Welding shall be carried out by professional / certified welders.
Electrodes for welding, the procedure, selection, test and inspection shall confirm to
provisions in IS 816, IS 818, IS 822, & IS 833.
Erection / hoisting shall commence only after approval of fabricated parts by the Engineer.
6.1
Stup Consultants P.Ltd 44 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITYRATE
(INR)
AMOUNT
(INR)
BILL OF QUANTITIES GATE HOUSE AND BOUNDARY WALL (CIVIL WORKS)
6.1.1 Steel work in built up tubular ( round, square or rectangular hollow tubes etc.) trusses etc.
including cutting, hoisting, fixing in position and applying a priming coat of approved steel
primer, including welding and bolted with special shaped washers etc. complete.
6.1.1.
1
Hot finished welded type tubes kg 9000.00 102.90 926100
6.2 Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp of
internal dia 140mm, 73mm height, top lid of 1.5mm thick M.S. sheet with its top surface
hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by
means of 3.3mm dia. round headed screws, one lock at the corners. Clamp shall be made
of 12mm dia M.S. bar bent to shape as per standard drawing.
each 25 142.95 3573.75
6.3 Steel work welded in built up sections/ framed work including cutting, hoisting, fixing in
position and applying a priming coat of approved steel primer using structural steel etc. as
required.
6.3.1 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. kg 1863 90.10 167856.3
6.4 Grouting below base plates of columns, equipments, around the foundation bolts, or
locations as specified using pre-packed cementetious non-shrink grout "Conbextra GP2" of
Fosroc or approved equivalent including cleaning the base by water / compressed air, pre-
socking, necessary shuttering/ form work, mixing,placing,curing etc.complete all as per
manufacturers guidelines and as directed by Engineer in charge.
Note: The pre-packed dry grout material consumed in the work shall be measured for
payment.
kg 100 25.40 2540
7 FLOORING
7.1 Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey
cement slurry mixed with pigment to match the shade of the slab including rubbing and
polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) :
7.1.1 25 mm thick. sqm 136 1141.40 155230.4
7.2 Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm
(average) thick cement mortar 1:3 (1 cement 3 coarse sand) and jointed with grey cement
slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing
complete.
sqm 27 1191.25 32163.75
7.3 Providing and fixing Glass mossaic tiles at finished plain wall surface of size 20 mm x 20
mm x 4 mm in all colour, design , fixing in customize design as per direction of Engineer-in-
Charge. The glass mosaic tiles to be fixed on the wall surface with the help of approved
adhesive applied at the rate of 2.5 kg per sqm and grouting of the same. The rate is
inclusive of all operation, material and required pattern approved by Engineer-in- Charge
sqm 970 1752.60 1700022
7.4 Providing and fixing Ist quality Digital high definition ceramic glazed wall tiles of 300 X 600
mm in size and conforming to IS : 15622 (thickness to be specified by the manufacturer ) of
approved make in all colours, shades as approved by Engineer-in-Charge in skirting, risers
of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement : 3 coarse sand)
and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement
mixed with pigment of matching shade complete.
Basic Rate of tiles Rs.50/ Sqft
Sqmt 28 1095.70 30679.6
7.5 Providing and laying 1st quality digital Glazed plain or non skid full body vitrified floor tiles
in different sizes (thickness to be specified by the manufacturer) with water absorption's
less than 0.08% and conforming to IS:15622 of approved make in all colours and shades,
laid on 20mm thick cement mortar 1:4 ( 1 cement : 4 coarse sand) including the grouting
the joints with white cement and matching pigments etc., complete.
Basic Rate of tiles Rs.125/ Sqft
Sqmt 196 1509.30 295822.8
Stup Consultants P.Ltd 45 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITYRATE
(INR)
AMOUNT
(INR)
BILL OF QUANTITIES GATE HOUSE AND BOUNDARY WALL (CIVIL WORKS)
7.6 Providing and laying 1st quality digital Glazed plain or non skid full body vitrified floor tiles
in different sizes (thickness to be specified by the manufacturer) with water absorption's
less than 0.08% and conforming to IS:15622 of approved make in all colours and shades,
laid on 20mm thick cement mortar 1:4 ( 1 cement : 4 coarse sand) including the grouting
the joints with white cement and matching pigments etc., complete.
Basic Rate of tiles Rs.100/ Sqft
Sqmt 7 1445.20 10116.4
7.7 Providing and fixing 1st quality digital Glazed plain or non skid full body vitrified floor tiles in
different sizes conforming to IS : 15622 (thickness to be specified by the manufacture of
approved make in all colours, shades in skirting, risers of steps and dados over 12 mm
thick bed of cement Mortar 1:3 (1cement: 3 coarse sand) and jointing with grey cement
slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching
shade complete.
Basic Rate of tiles Rs.100/ Sqft
Sqmt 21 1544.20 32428.2
8 ROOFING 0
8.1 Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4
(1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C.
sheet 1mx1mx400micron, finished with 12mm cement plaster 1:3 (1 cement : 3 coarse
sand) and a coat of neat cement, rounding the edges and making and finishing the outlet
complete
each 10 186.65 1866.5
FINISHING
Note :- Rates for external plaster are for height upto 10m. from ground level unless
otherwise stated.9.1 12mm cement plaster of mix
9.1.1 1:6 (1 cement: 6 find sand) sqm 649 149.45 96993.05
9.2 15mm cement plaster on the rough side of single or half brick wall of mix:
9.2.1 1:6 (1 cement: 6 find sand) sqm 649 172.80 112147.2
9.3 6mm cement plaster of mix
9.3.1 1:3 (1 cement: 3 fine sand) sqm 1157 134.70 155847.9
9.4 Finishing walls with textured exterior paint of required shade :
9.4.1 New work (Two or more coats applied @ 3.28 ltr/10 sqm) over
and including priming coat of exterior primer applied @ 2.20kg/
10 sqm
sqm 970 146.45 142056.5
9.5 Painting with oil type wood preservative of approved brand and manufacture:
9.5.1 New work (two or more coats) sqm 9.00 31.90 287.1
9.6 Wall painting with acrylic emulsion paint of approved brand and manufacture to give an
even shade:
9.6.1 Two or more coats on new work sqm 656 80.5 52808
9.7 Painting with synthetic enamel paint of approved brand and manufacture of required colour
to give an even shade:
9.7.1 Two or more coats on new work over an under coat of suitable shade with ordinary paint of
approved brand and manufacture
sqm 13.00 106.25 1381.25
9.8 Providing & fixing G.I. Hexagonal chicken wire mesh of size 12mm x 22 gauge at the
junction of dissimilar surfaces of brick / block masonry wall and RCC column / beams and
the like including necessary "U" nails / screws with cleats for fixing, overlapping etc.
complete all as per specification and as directed by the Engineer for all height and all
locations.
Sqm 389 68.00 26452
9.9 Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per
manufacturer's specifications including appropriate priming coat, preparation of surface,
necessary scaffolding / staging etc.
9.9.1 Two or more coats on new work MT. 9.00 2331.00 20979
10 WATER PROOFING OF MAIN BUILDINGS AND WATER TANKS
10.1 Grading roof for water proofing treatment with
10.1.1 Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm
nominal size)
cum 50 5,570.25 278512.5
9
Stup Consultants P.Ltd 46 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITYRATE
(INR)
AMOUNT
(INR)
BILL OF QUANTITIES GATE HOUSE AND BOUNDARY WALL (CIVIL WORKS)
11.00 STRUCTURAL GLAZING AND ALUMINIUM COMPOSITE PANEL
11.1 Providing and supplying aluminium extruded tubular and other aluminium sections as per
the architectural drawings and approved shop drawings, the aluminium quality as per grade
6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-80 microns
conforming to AAMA 2604 of required colour and shade as approved by the Engineer-in-
Charge.
(The item includes cost of material such as cleats, sleeves, screws etc. necessary for
fabrication of extruded aluminium frame work. Nothing extra shall be paid on this account).
kg 472.00 338.25 159654
11.2 Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized
system of structural glazing (with open joints) for linear as well as curvilinear portions of the
building for all heights and all levels,
including
a) Structural analysis & design and preparation of shop drawings for the specified design
loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times
design wind pressure without any failure), including functional design of the aluminum
sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and
splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather
silicone sealants, flashings, fire stop (barrier)- cum-smoke seals, microwave cured EPDM
gaskets for water tightness, pressure equalisation & drainage and protection against fire
hazard including
b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5
brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional
movement for achieving perfect verticality and fixing structural glazing system rigidly to the
RCC/ masonry/structural steel framework of building structure using stainless
steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with nuts and
sqm 59.00 2,556.15 150812.85
d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of
sizes, shapes and profiles, as required as per the site conditions, to seal the gap between
the building structure and all its interfaces with curtain glazing to make it watertight.
e) Making provision for drainage of moisture/ water that enters the curtain glazing system to
make it watertight, by incorporating principles of pressure equalization, providing suitable
gutter profiles at bottom (if required), making necessary holes of required sizes and of
required numbers etc. complete. This item includes cost of all inputs of designing, labour for
fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding
and other incidental charges including wastages etc., enabling temporary structures and
services, cranes or cradles etc. as described above and as specified. The item includes the
cost of getting all the structural and functional design including shop drawings checked by a
structural designer, dully approved by Engineer-in-charge. The item also includes the cost
of all mock ups at site, cost of all samples of the individual components for testing in an
approved laboratory, field tests on the assembled working structural glazing as specified,
11.3 Providing, assembling and supplying vision glass panels (IGUs) comprising of hermetically-
sealed 6-12- 6 mm insulated glass (double glazed) vision panel units of size and shape as
required and specified, comprising of an outer heat strengthened float glass 6mm thick, of
approved colour and shade with reflective soft coating on surface # 2 of approved colour
and shade, an inner Heat strengthned clear float glass 6mm thick, spacer tube 12mm wide,
dessicants, including primary seal and secondary seal
(structural silicone sealant) etc. all complete for the required performances, as per the
Architectural drawings, as per the approved shop drawings, as specified and as directed by
the Engineer-in-Charge. The IGUs shall be assembled in the factory/ workshop of the glass
processor. (Payment for fixing of IGU Panels in the curtain glazing is included in cost of
item No.26.2)
For payment, only the actual area of glass on face # 1 of the glass panels (excluding the
areas of the grooves and weather silicone sealant) provided and fixed in position, shall be
measured in sqm.
(i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, +
12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties
as visible Light transmittance (VLT) of 25
sqm 59.00 4,090.95 241366.05
Stup Consultants P.Ltd 47 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITYRATE
(INR)
AMOUNT
(INR)
BILL OF QUANTITIES GATE HOUSE AND BOUNDARY WALL (CIVIL WORKS)
11.4 Additional cost for using Saint Gobain make Envision SKN 465 glass (6mm thick
toughened glass + 12mm airgap + 6mm clear float glass ) having properties as visible Light
transmittance (VLT) of 50 %, Light reflection internal 16%, light reflection external 13 % and
U value of 1.5 W/m2 degree K,Solar factor 0.27 in place of Coloured tinted float glass
6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat
Strengthened clear Glass of approved make having properties as visible Light
transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection
external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree
K etc as specified in item NO.11.4 above of this sub head.
Sqmt 59.00 1539.00 90801
11.5 Extra for openable side / top hung vision glass panels (IGUs) including providing and
supplying at site all accessories and hardwares for the openable panels as specified and of
the approved make such as heavy duty stainless steel friction hinges, min 4 -point cremone
locking sets with stainless steel plates, handles, buffers etc. including necessary stainless
steel screws/ fasteners, nuts, bolts, washers etc. all complete as per the Architectural
drawings, as per the approved shop drawings, as specified and as directed by the
Engineerin- Charge.
sqm 9 3,062.25 27560.25
11.6 Providing, fabricating and supplying shadow box of required size and shape, for fixing in the
spandrel portion of the structural glazing, in linear as well as curvilinear portions of the
building by providing semi -rigid, inorganic, non-combustible fibre glass wool insulation 50
mm thick, conforming to IS: 8183 and BS: 3958 Part 5. The insulation layer shall have
facing (factory bonded on surface # 1of the fibre glass insulation layer), of black nonwoven
fibre glass tissue of nominal thickness 0.5 mm and nominal mass not less than 60 gm /
sqm, made of randomly oriented glass fibres distributed in a binder by a wet-lay process
including fixing 1.5 mm thick solid aluminum sheet backing using, 6 mm thick cement board
including SS rivets, nuts, bolts, washers etc complete
sqm 12 1634.5 19614
11.7 Providing and supplying Spandrel Glass Panels comprising of 6 mm thick heat
strengthened monolithic float glass of approved colour and shade with reflective soft
coating on surface # 2 of approved colour and shade so as to match the colour and shade
of the IGUs in the vision panels etc. ,all complete for the required performances as
specified, as per the Architectural drawings, as per the approved shop drawings, as
specified, and as directed by the Engineer- in-Charge. For payment, only the actual area of
glass on face # 1 of the glass panels (but excluding the area of grooves and weather
silicone sealant) provided and fixed in position, shall be measured in sqm.(Payment for
fixing of Spandrel Glass Panels in the curtain glazing is included in cost of relevent Item*).
(i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2,
having properties as visible Light transmittance (VLT) of 25 to 35%, Light reflection internal
10 to 15%, light reflection external 10 to 20%, shading coefficient (0.25- 0.28) and U value
of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by
technical sanctioning authority as per the site requirement.
sqm 12 2997.25 35967
B BOUNDARY WALL
1.0 EARTH WORK
1.1 Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over
areas (exceeding 30cm in depth. 1.5m in width as well as 10 sqm on plan) including
disposal of excavated earth, lead upto 50m and lift upto 1.5m, disposed earth to be levelled
and neatly dressed.
1.1.1 All kinds of soil cum 3443 155.6 535730.8
2 CONCRETE WORK
2.1 Providing and laying in position cement concrete of specified grade excluding the cost of
centering and shuttering - All work up to plinth level :
2.1.1 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size). cum 266 4301.15 1144105.9
3 STEEL WORK
Supplying, fabricating, assembling, hoisting / erecting and fixing in position at locations
specified below, structural steel works of MS rolled single / built-up sections conforming to
IS 2062, including joist, channel, angle, tee, plates (plain or chequered) etc. all as per
structural drawings and as per detailed specifications (for materials & workmanship)
including necessary scaffolding / staging, applying a priming coat of approved steel primer
etc. complete in the situations described hereinafter and comprising of :
i) Profile Cutting of components to required lengths/widths and shapes/profiles
ii) Smooth grinding / machining of edges / faces / all welding joints.
iii) Preparing the surface to ensure complete removal of mill scale by using wire brushes &
sand papering
3.1
Stup Consultants P.Ltd 48 of 234
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITYRATE
(INR)
AMOUNT
(INR)
BILL OF QUANTITIES GATE HOUSE AND BOUNDARY WALL (CIVIL WORKS)
iv) Necessary welding (electric arc welding) for required weld lengths and sizes
Note: The contractor shall submit fabrication drawings for work involved based on
construction drawings (that may be issued during construction period) for approval by the
Engineer.
The fabrication work shall start only after approval of the fabrication drawings. Any change
required in the fabrication drawings shall be carried out at no extra cost.
Fabrication shall be in a perfect Architectural workmanship manner and as provided in
Section V & VI of IS 800 & IS 7215.
Welding shall be carried out by professional / certified welders.
Electrodes for welding, the procedure, selection, test and inspection shall confirm to
provisions in IS 816, IS 818, IS 822, & IS 833.
Erection / hoisting shall commence only after approval of fabricated parts by the Engineer.
3.2 Steel work welded in built up sections/ framed work including cutting, hoisting, fixing in
position and applying a priming coat of approved steel primer using structural steel etc. as
required.
3.2.1 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. kg 150919 90.10 13597801.9
TOTAL GATE HOUSE AND BOUNDARY WALL 29480929.11
Stup Consultants P.Ltd 49 of 234
SCHEDULE OF QUANTITIES
GENERAL NOTES PLUMBING WORKS:
1
2
3
4
a All materials, fixing materials, accessories, appliances tools, plants, equipment,
transport, labour and incidentals required in preparation for and in the full and
entire execution, testing, balancing, commissioning and completion of work
called for in the item and as per Specifications and Drawings.
b Wastage on materials and labour.
c Loading, transporting, unloading, handling/double handling, hoisting to all
levels, setting, fitting and fixing in position, protecting, disposal of debris and all
other labour necessary in and for the full and entire execution and for the job in
accordance with the contract documents, good practice and recognize
principles.
d Liabilities, obligations and risks arising out of Conditions of Contract.
e All requirements of Specifications, whether such requirements are mentioned
in the item or not. The Specifications and Drawings where available, are to be
read as complimentary to and part of the Schedule of Quantities and any work
called for in one shall be taken as required for all.
f In the event of conflict between Schedule of Quantities and other documents
including the Specifications, the most stringent shall apply. The interpretation
of the Consultant/Project Manager shall be final and binding.
g Tenderer has to include the rate of all items/ operations as mentioned in the
Technical Specifications as applicable and for all Heights and levels as
required to complete the system at site
5
6
CONSTRUCTION OF PROPOSED UP POLICE BHAVAN AT GOMTI NAGAR EXTENSION AT
LUCKNOW.UP
All items of work under this Contract shall be executed strictly to fulfill the requirements
laid down under “Basis of Design” in the specifications. Type of equipment, material
specification, methods of installation and testing and type of control shall be in accordance
with the specifications, approved shop drawings and the relevant Indian Standards,
however capacity of each component and their quantities shall be such as to fulfill the
above mentioned requirement.
The unit rate for all equipment or materials shall include cost in INDIAN RUPEES (INR) for
equipment and materials including all taxes and duties and also including forwarding,
freight, insurance and transport into Contractor’s store at site, storage, installation, testing,
balancing, commissioning and other works required.
For all imported items Owners shall arrange EPCG licence and open L/C in the name of
principals. Rates for all imported items shall be quoted in US Dollars. During award of work
Owner shall be at liberty to ask for proforma invoice in any convertible foreign currency.
All relevant document for import shall be taken care by the contractor. Port charges /
octroi / inland transportation etc. upto site shall be paid on actuals subject to ceiling of
quoted amount.
The rate for each item of work included in the Schedule of Quantities shall, unless
expressly stated otherwise, include cost of :
The Contractor shall procure and bring Materials/Equipment to the site only on the basis of
drawings approved for construction and shop drawings and not on the basis of Bill of
Quantities which are approximate only. This also applies to the Contractor’s requisition for
Owner supplied materials.
The work shall be carried out in conformity with the drawings and within the requirements
of architectural, HVAC, Fire Fighting, Electrical, Structural and other specialized services
drawings.
Stup Consultants P.Ltd 50 of 234
SCHEDULE OF QUANTITIES
GENERAL NOTES PLUMBING WORKS:
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
The contractor shall , from time to time, clear away all debris and excess materials
accumulated at the site failing which the same shall be done by Project Manager at
contractor’s risk and cost and cost of clean up shall be deducted from the contractors
prorata bill.
After the fixtures, equipment and appliances have been installed and commissioned,
contractor shall cleanup the same and remove all plaster, paints, stains, stickers and other
foreign matter or discoloration leaving the same in a ready to use condition.
Shop drawings are detailed working drawings coordinated with other trading work, which
incorporate the contractor’s details for execution of the work and incorporate equipment
manufacturer’s details and dimensions to ensure that the same can be installed in the
space provided.
All shop drawings should detail pipe routing and levels, showing location of other services
at crossings etc., cable runs, route cable trays etc. and all allied works and must be fully
coordinated with other services, before execution of the works.
All shop drawings will be made on AutoCAD and colored prints has to be produced for site
work.
The contractor shall cooperate with all trades and agencies working on the site. He shall
make provision for hangers, sleeves, structural openings and other requirements well in
advance to prevent hold up of progress of the construction schedule. All supports to the
civil structure shall be provided with anchor fasteners.
On award of the work, contractor shall submit a schedule of construction in the form of a
PERT chart or BAR chart for approval of the Project Manager.
On award of the work the contractor shall be issued set of consultant’s drawings. The
drawings shall be the basis of contractor’s shop drawings.
Any pipe crossing fire rated wall as per fire compartmentation will be provide with higher
size of GI sleeve. All floor crossing pipes will be provided with higher size GI sleeve.
This Schedule shall be fully priced and the extensions and totals duly checked. The rates
for all items shall be filled in INK including NIL items.
No alteration whatsoever is to be made to the text or quantities of this Schedule unless
such alteration is authorised in writing by Consultant. Any such alterations, notes or
additions shall, unless authorized in writing, be disregarded when tender documents are
considered.
In the event of an error occurring in the amount of the Schedule, as a result of wrong
extension of the unit rate and quantity, the unit rate quoted by the tenderer shall be
regarded as firm and the extensions shall be amended on the basis of rates.
Any error in totaling in the amount column and in carrying forward total shall be corrected.
Any error, in description or in quantity, omission of items from this Schedule shall not
vitiate this Contract but shall be corrected and deemed to be variation required by the
Consultant/Project Manager.
Rates have been called for a number of items of works, as alternatives which, for the
present do not form part of the total value of tender. However the rates for these items
shall be quoted, with due care so that in the event of choice of an alternative item of work,
said rate shall form part of the contract and shall not violate the contract any way.
On completion of all works, contractor shall demolish all stores, remove all surplus
materials and leave the site in a broom clean condition, failing which the same shall be
done by the Project Manager at the Contractor'’ risk and cost. Cost of the cleanup shall be
deducted from the contractor’s bills on pro-rata basis in proportion to his contact value.
Stup Consultants P.Ltd 51 of 234
S. No. DESCRIPTION AMOUNT
1 RAIN WATER PIPES 4,563,844
2 INTERNAL / EXTERNAL WATER SUPPLY 3,349,530
3 EXTERNAL SEWAGE SYSTEM 2,981,120
4 SANITARY FIXTURES 45,718,782
5 MISCELLANEOUS ITEMS 40,902
6 WATER SUPPLY PUMP ITEMS 7,102,215
7 WATER TREATMENT PLANT 2,684,675
8 HYDROPNEUMATIC SYSTEM 1,427,091
9 SOLAR WATER HEATERS 540,788
10 ELECTRICAL INSTALLATION FOR PLUMBING SYSTEM 652,814
11 WATER COOLERS WITH R.O. MACHINE 8,519,360
12 LPG GAS SYSTEM 1,105,644
TOTAL CARRIED TO SUMMARY 78,686,764
SUMMARY OF COSTS
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW IN U.P.
Stup Consultants P.Ltd 52 of 234
RATE (INR) AMOUNT (INR)
GENERAL NOTES :-
A. SCHEDULED ITEMS
1 RAIN WATER PIPES
1.1 Providing and fixing on wall face unplasticised-Rigid PVC rain water
pipes conforming to IS:13592 Type A including jointing with leaving
10 mm gap for thermal expansion single socketed pipes along with all
required fittings like tees, bends, junctions, cowls, offsets, cleanout
plugs, access pieces, crosses with or without access doors jointed with
approved solvent cement as per manufacturer's recommendations, fixed
to walls and ceilings with clamps complete including cutting and
making good the floors and walls where required complete of outer
diameter as per direction of Engineer in Charge.
(A) If in any of the item described below contains a product / catalogue number of a particular brand then it is merely an indication of the
specification /design of the particular relevant item and the bidder may be asked to provide /use any of the brand mentioned in the list of
approved makes attached with the technical specifications and he should get the same approved from the Engineer In charge and
Consultant / Architect before placing the order.
( B ) The work shall be executed by an approved agency and It will be responsibility of the contractor on board to to get approved the
Samples of the materials to be used & shop drawings from the consultant/ Architect.
Bill of Quantities- Plumbing & Sewerage Work
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW IN U.P.
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
diameter as per direction of Engineer in Charge.
1.1.1 110 mm outer dia RM 1.00 232 232
1.1.2 160 mm outer dia RM 2400 505 1,213,004
1.2 Providing and laying Double Flanged (Screwed / Welded) Centrifugally
(Spun) Ductile Iron Pipes of Class K - 9 conforming to IS : 8329 along
with all required fittings like tees, bends, junctions, cowls, offsets,
cleanout plugs, Flexible joints at building junction, access pieces,
crosses with or without access doors:
1.2.1 150 mm dia Ductile Iron Double Flanged RM 110 4,115 452,601
1.2.2 250 mm dia Ductile Iron Double Flanged RM 710 4,070 2,889,807
1.2.3 300 mm dia Ductile Iron Double Flanged RM 1.00 8,202 8,202
TOTAL CARRIED TO SUMMARY 4,563,844
2 INTERNAL / EXTERNAL WATER SUPPLY
2.1 Providing and fixing chlorinated Polyvinyl chloride (CPVC) pipes,
having thermal stability for hot & cold water supply including all CPVC
plain & brass threaded fittings i/c fixing the pipe with clamps at 1.0m
spacing. This includes jointing of pipes & fittings with one step CPVC
solvent cement and the cost of cutting chases and making good the
same including testing of joints complete as per direction of Engineer in
Charge.
Concealed work including cutting chases and making good
the walls etc.2.1.1 15 mm nominal outer dia pipes RM 400 270 108,000
2.1.2 20 mm nominal outer dia pipes RM 4000 296 1,185,600
Stup Consultants P.Ltd 53 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
2.2 Providing and fixing chlorinated Polyvinyl chloride (CPVC) pipes,
having thermal stability for hot & cold water supply including all CPVC
plain & brass threaded fittings i/c fixing the pipe with clamps at 1.0m
spacing. This includes jointing of pipes & fittings with one step CPVC
solvent cement and the cost of cutting chases and making good the
same including testing of joints complete as per direction of Engineer in
Charge.
Internal work- Exposed on wall and shafts
2.2.1 20 mm nominal outer dia pipes RM 1 191 191
2.2.2 25 mm nominal outer dia pipes RM 1 231 231
2.2.3 32 mm nominal outer dia pipes RM 1 297 297
2.2.4 40 mm nominal outer dia pipes RM 2000 408 815,800
2.2.5 50 mm nominal outer dia pipes RM 1575 582 915,941
2.4 External work- Suspended from Slab / Trenching
2.4.1 75 mm nominal outer dia pipes RM 100 2,359 235,894
2.4.2 100 mm nominal outer dia pipes RM 1 3,260 3,260
2.4.3 150 mm nominal outer dia pipes RM 1 3,940 3,940
2.5 Providing and fixing gun metal gate valve with CI wheel of approved
quality (screwed end).
2.5.1 20mm nominal bore Nos. 40 342 13,690
2.5.2 25mm nominal bore Nos. 1 428 428
2.5.3 32mm nominal bore Nos. 1 500 500
2.5.4 40mm nominal bore Nos. 24 584 14,021
2.5.5 50mm nominal bore Nos. 42 749 31,475
2.6 Constructing masonary Chamber 60x60x75 cm, inside with 75 class
designation brick work in cement mortar 1:4 (1 cement : 4 coarse sand)
for sluice valve with C. I. surface box 100 mm top diameter, 160 mm
bottom diameter and 180 mm deep (inside) with chained lid and RCC
top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate
20mm nominal size) necessary excavation foundation concrete1:5:10 (1
cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size)
and inside plastering with cement mortar 1:3 (1 cement:3 coarse sand)
12mm thick finished with a floating coat of neat cement complete as per
standard design :
2.6.1 With F.P.S bricks Each 3 6,754 20,263
TOTAL CARRIED TO SUMMARY 3,349,530
Stup Consultants P.Ltd 54 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
3 EXTERNAL SEWERAGE SYSTEM
3.1 Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement :
4 coarse sand ) R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand
: 4 graded stone aggregate 20 mm nominal size), foundation concrete
1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40mm
nominal size) inside plastering 12mm thick with cement mortar 1:3 (1
cement : 3 coarse sand) finished with floating coat of neat cement and
making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4
graded stone aggregate 20mm nominal size) finished with a floating
coat of neat cement complete as per standard design :
3.2 Inside size 90x80 cm and 45 cm deep including C.I. cover with frame
(light duty) 455x610 mm internal dimensions total weight of cover and
frame to be not less than 38 kg (weight of cover 23 kg and weight of
frame 15 kg) OR including Precast RCC cover with 2 Inch Dia Holes
with precast RCC Frames. :
3.2.1 With Sewer bricks conforming to IS : 4885 each 30 8,691 260,738
3.3 Extra for depth for manholes :
3.3.1 Size 90x80 cm3.3.1 Size 90x80 cm
3.3.1.1 With Sewer bricks conforming to IS : 4885 meter 20 6,175 123,493
3.4 Providing orange colour safety foot rest of minimum 6mm thick plastic
encapsulated as per IS: 10910 on 12 mm dia steel bar conforming to IS :
1786 having minimum cross section as 23 mmx25 mm and over all
minimum length 263 mm and width as 165 mm with minimum 112 mm
space between protruded legs having 2 mm tread on top surface by
ribbing or chequering besides necessary and adequate anchoring
protections on tail lenght on 138 mm as per standard drawing and
suitable to with stand the bend test and chemical resistance test as per
specification & having manufacture's permanent identification mark to
be visible even after fixing, including fixing in manhole with 30x20x15
cm cement concrete block 1:3:6 (1 cement: 3 coarse sand : 6 graded
stone aggregate 20 mm nominal size) complete as per design.
each 300 312 93,480
3.5 Constructing brick masonary road gully chamber ( or catch Basin)
50x45x60 cm with bricks of class designation 75 in cement morter 1:4
(1 cement : 4 coarse sand) including 500x450 mm precast RCC
horizontal grating and Precast RCC Frame complete as per standard
design.
3.5.1 With F.P.S bricks Each 14 3,958 55,406
Stup Consultants P.Ltd 55 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
3.6 Providing and fixing square-mouth S.W. gully trap grade 'A'’ complete
with C.I. grating brick masonry chamber with water tight C.I. cover
with frame of 300 x300 mm size (inside) the weight of cover to be not
less than 4.50 kg and frame to be not less than 2.70 kg as per standard
design :
3.6.1 100x100 mm size P type
3.6.2 With F.P.S. Bricks class designation 75 Each 32 1,571 50,280
3.7 Providing and laying non pressure NP2 class (light duty) R.C.C. pipes
with collars jointed with stiff mixture of cement mortar in the
proportion of 1:2 (1 cement :2 fine sand) including testing of joints etc.
complete :
3.7.1 150 mm dia R.C.C. pipe Metre 165 348 57,470
3.7.2 250 mm dia R.C.C. pipe Metre 1 469 469
3.7.3 300 mm dia. R.C.C. pipe Metre 260 506 131,651
3.8 Providing and laying Non Pressure NP-4 class (Heavy duty) R.C.C.
pipes including collars/spigot jointed with stiff mixture of cement
mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing
of joints etc. complete
3.8.1 450 mm dia. R.C.C. pipe Metre 280 2,196 614,810
3.9 Providing and laying cement concrete 1:5:10 (1 cement :5 coarse sand:
10 graded stone aggregate 40 mm nominal size) upto haunches of S.W/
RCC. pipes including bed concrete as per standard design :
3.9.1 150 mm diameter S.W. / RCC Pipe Metre 165 456 75,314
3.9.2 300 mm diameter S.W. / RCC pipe Metre 260 721 187,382
3.9.3 450 mm diameter S.W./ RCC pipe Metre 280 1,513 423,772
3.10 Earth work in excavation by mechanical means (Hydraulic excavator) /
manual means in foundation trenches or drains (not exceeding 1.5 m in
width or 10 sqm on plan), including dressing of sides and ramming of
bottoms, lift upto 1.5 m, including getting out the excavated soil and
disposal of surplus excavated soil as directed, within a lead of 50m.
3.10.1 All kinds of soil. cum 50 158 7,875
3.11 Excavating trenches of required width for pipes, cables, etc including
excavation for sockets, and dressing of sides, ramming of bottoms,
depth upto 1.5 m, including getting out the excavated soil, and then
returning the soil as required, in layers not exceeding 20 cm in depth,
including consolidating each deposited layer by ramming, watering, etc.
and disposing of surplus excavated soil as directed, within a lead of 50
m :
3.11.1 All kinds of soil.
Stup Consultants P.Ltd 56 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
3.11.2 Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia
meter 200 208 41,660
3.11.3 Pipes, cables etc. exceeding 300 mm dia but not exceeding 600 mm meter 200 325 65,040
3.12 Making Khurra 45x45 cm with average minimum thickness of 5cm
cement concrete 1:4 (1 cement: 2coarse sand: 4 graded stone aggregate
of 20mm nominal size) over PVC Sheet 1m x 1m x 400 micron,
finished with 12mm cement plaster 1: 3 (1 cement: 3coarse sand) and a
coat of neat cement, rounding the edge and making and finishing the
outlet complete.Nos. 56 187 10,452
3.13 Slotted cowl (terminal guard) 100mm/ 150 Dia Nos. 40 285 11,400
3.14 Providing, fixing, jointing, testing & commissioning in position the
following heavy class GI pipes conforming to IS:1239 cut to required
lengths including all necessary fittings (conforming to IS:1879) and
specials such as bends, tees, unions, reducers, flanges & plugs etc.
fixing at wall/ceiling level supported by clamps, hangers etc, (to be
galvanized after fabrication) cutting hole in wall/floor/slab and making
good the same good with cement concrete 1:2:4 / fire sealent complete
as required.
3.14.1 50 mm dia RM 440 400 175,780
3.14.2 80 mm dia RM 535 637 340,822 3.14.2 80 mm dia RM 535 637 340,822
3.14.3 100 mm dia RM 100 995 99,539
3.15 Providing and application of two coats of Synthetic enamel paint of
approved shade on pipes and supports as per pipe colour code over a
coat of primer. Including painting of legends with direction arrow as per
the approval of the Consultants / Project Manager.
3.15.1 80 mm dia RM 440 51 22,651
3.15.2 100 mm dia RM 100 74 7,425
3.16 Supply, installing, testing and commissioning of BUTTERFLY VALVE
(MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16
pressure rating as specified with counter flanges, nuts & bolts and
gasket to suit pressure rating.
3.16.1 65 mm dia Nos. 1 2,921 2,921
3.16.2 80 mm dia Nos. 7 3,256 22,792
3.16.3 100 mm dia Nos. 10 4,615 46,150
3.16.4 150 mm dia Nos. 1 5,845 5,845
3.17 Supply, installing, testing and commissioning of CI wafer type check
valve tested to a pressure of 15 Kg/sqcm. Including rubber gasket,
flanges, union, nuts, bolts, washers & painting complete as required.
3.17.1 65 mm dia Nos. 1 2,011 2,011
3.17.2 80 mm dia Nos. 3 2,345 7,035
3.17.3 100 mm dia Nos. 3 3,257 9,771
3.17.4 150 mm dia Nos. 1 5,705 5,705
Stup Consultants P.Ltd 57 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
3.18 Providing and fixing enclosed type water meter (bulk type) conforming
to IS : 2373 and tested by Municipal Board complete with bolts, nuts,
rubber insertions etc.
3.18.1 80 mm dia No. 1 3,115 3,115
3.18.2 100 mm dia No. 1 4,654 4,654
3.18.3 150 mm dia No. 1 6,814 6,814
3.18.4 200 mm dia No. 1 7,398 7,398
TOTAL CARRIED TO SUMMARY 2,981,120
B. NON- SCHEDULED ITEMS
1 SANITARY FIXTURES, WATER SUPPLY AND DRAINAGE
1.1 Providing and Fixing, testing and commissioning of white vitreous
china wall mounting cascade type water closet Kohler Cat No. (K-
17647T-S-O)/ American Standards TF-3116/ Roca RS346467460 +
RA80N462001 with CP bolts, nuts, CI chair hanging arrangements,
seat & soft close seat cover with CP hinges & rubber buffers, CP brass
screw, washer, P/S trap/bend, bracket, connection to main pipe on shaft
with all accessories, connectors with rubber lip / buffer and side gapwith all accessories, connectors with rubber lip / buffer and side gap
filled with silicon sealant wherever required with concealed type dual
flush cistern Kohler Cat No (6286IN-NA & 6283T-CP)/ American
Standards K-301+K-5034-CH/ Roca RA890031410+
RA8900450C0 & GROHE (model no. 38987000) comprising of
actuator button facia assembly including brass / SS screws , fastner,and
washer complete, cutting and making good the walls floors wherever
required . The water discharge shall be as per GRIHA noms.
Each 340 17,821 6,059,140
1.2Providing and fixing water closet squatting pan (Indian/ Orissa type
W.C. pan ) with 100 mm sand cast Iron P or S trap,
with concealed type dual flush cistern Kohler Cat No (6286IN-NA &
6283T-CP)/ American Standards K-301+K-5034-CH/ Roca
RA890031410+ RA8900450C0 & GROHE (model no. 38987000)
comprising of actuator button facia assembly including brass / SS
screws , fastner,and washer complete, cutting and making good the
walls floors wherever required . The water discharge shall be as per
GRIHA noms. with all fittings and fixtures complete, including cutting
and making good the walls and floors wherever required: 17.1.1 White
Vitreous china Orissa pattern W.C. pan of size 580x440 mm with
integral type foot rest Each 200 10,000 2,000,000
Stup Consultants P.Ltd 58 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
1.3 Providing and Fixing, testing and commissioning of vitreous china
white oval over counter wash basin of Kohler (K-2075IN))/
American Standards 470LM-WT/ Roca RS322307460, 32 mm dia
C.P. brass bottle trap Kohler (16407IN-CP)/ American Standards
ART-PW323/ Roca RF9066A1 & GROHE ( model no. 28920000)
with CP brass waste Kohler (9031 IN-A-CP)/ American Standards
A-8006/ Roca assembly, wall flanges and rubber adapters for waste
connection complete including CI/MS brackets duly painted, nuts,
washers, cutting and making good the walls floors wherever required. .
Each 535 5,500 2,942,500
1.4 Providing and Fixing, testing and commissioning of CP brass Central
single hole /Single lever basin mixer of Kohler (8620IN-ND-CP)/
American Standards WF-3101.101.50/ Roca RT5A3125CA1 &
GROHE (model no. 32851000) without pop up waste with 450mm
long braided hose complete including cutting and making good the
walls where required. The water discharge shall be as per GRIHA
noms.
Each 120 4,950 594,000
1.5 Providing and fixing Kohler (17526T-CP)/ American Standards WF-
6581.908.50/ Roca RA816050001 & GROHE (model no. 40461000)
robe hook fixed to PVC rawl plug with CP brass screws as per
direction of Engineer in Charge. direction of Engineer in Charge.
Each 380 760 288,800
1.6 Providing and Fixing, testing and commissioning of hand spray
(Health faucet) of Kohler 12925IN-CP/ American Standards A4700-
A-CH/ Roca RFR9061A1 with flexiable hose connection, regulator
with flexible pipe 1.5 m long, wall hooked complete as required.
Each 340 1,460 496,400
1.7 Providing and fixing 15mm dia. C.P. brass Short body bib cock of
(Kohler-1161635-A-CP/ Roca-RT5A7825 CAI ) Flow Rate 1.89 LPM
at 3 bar including cutting and making good the walls wherever required
complete as per directions of Engineer incharge.
Each 200 2,830 566,000
1.8 Providing and fixing in position of approved quality high pressure rated
Brass Float Valve with ball float and brass rods of required length
suitable for test pressure of not less than 15 Kg/sqcm of the following
sizes:
1.8.1 32 mm dia. Nominal bore Each 6 2,997 17,982
1.8.2 50 mm dia. Nominal bore Each 6 5,585 33,510
1.9 Providing and fixing C.P brass toilet paper holder of Kohler (5633IN-
CP)/ American Standards/ Roca RA816057001 & GROHE (model
no. 40457000/40367000) including cutting and making good the walls
wherever required complete as per directions of Engineer incharge.
Each 340 1,873 636,820
Stup Consultants P.Ltd 59 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
1.10 Providing and fixing of towel ring of Kohler 17528T-CP/
American Standards WF-6590.908.50/ Roca Ra816052001 &
GROHE (model no. 40460000) complete in all respects including
cutting and making good the walls required. Only attached Toilets
Each 120 1,693 203,160
1.11 Providing and fixing, jointing and testing of 15mm dia C.P. brass
angle valve of Kohler (11568IN-7-CP)/ American Standards A-
4400/ Roca RF525159700 & GROHE (model no. 2201600M) with
C.P. brass wall flange with any other items complete including
cutting and making good the walls wherever required as per direction of
Engineer-Incharge.The water discharge shall be as per GRIHA noms.Each 1200 821 985,200
1.12 Providing and fixing 35 mm dia powder coated steel grab bar (Kohler-
37349IN-CP/ Roca-RA816671001)
Each 40 5,050 202,000
1.13 Providing and Fixing, testing and commissioning of CP Braided hoses
connection Kohler/American standards/ Roca 450 mm long
including nuts and washers and making connection to fixtures and
fittings complete as required. Each 1200 989 1,186,800
1.14a Providing and fixing white vitreous china battery based infrared sensor
operated urinal of approx size 610x390x370 mm having pre & postoperated urinal of approx size 610x390x370 mm having pre & post
flushing with water (250ml &500ml consumption ), having water inlet
from back side including fixing to wall with suitable brackets all as per
manufacturers specification and direction of brackets all as per
manufacturers specification and direction of engineer-in -charge.
Each 1 16,725 16,725
1.14b Providing and fixing vitreous china flat back urinal basin with
Kohler Cat No. ( K-18842D )/ American Standards WP-6401/ Roca
RS35945J000 C.I. Hangers, C.P. spreader with short bent, electronic
flushing system comprising of electronic & electrical items including
infrared photo cells eyes, electronically operated solenoid valve,
step down equipment, electric operated,concealed copper piping
etc.with P-trap siphon and concealed urinal sensor of Kohler Cat
No ( E6807-NF)/ American Standards WF-8604.000.50/ Roca
RT5X9215e00 & connection kit for urinal and any other item required
to provide satisfactory functioning, waste and jali to prevent napthelene
balls from going inside the pipe and connecting pipe to wall with C.P.
flange complete including cutting and making good the walls and floors
where required. The water discharge shall be as per GRIHA noms.
Each 210 26,050 5,470,500
Stup Consultants P.Ltd 60 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
1.15 Providing, jointing, testing and fixing UPVC Soil, Waste & Vent
system conforming to IS : 13592 - Type B and UPVC fittings
(moulded as well as fabricated) like bends, tees, Y-tees, crosses, boss
connections, access pieces, saddle pieces, cleanouts, adaptors for
connections to other materials, plugs, reducers, cowls, offSet and other
specials. Jointing shall be done with pushfit EPDM ring jointing
technique in general. Solvent cement joints may be provided for fittings
and specials which are not manufactured with pushfit rubber joints.
Pipes may be laid / fixed in sunken floors, under slung from ceiling. The
pipes laid in sunken floor shall be encased with 75 mm thick cement
concrete (1:2:4) all around. The installation shall be complete in all
respects including cutting chases / holes in walls, slabs and making
good the same as per specifications.
1.15.1 110 mm dia RM 5000 581 2,903,704
1.15.2 160 mm dia RM 1 1,025 1,025
1.15b Providing and laying Double Flanged (Screwed / Welded) Centrifugally
(Spun) Ductile Iron Pipes of Class K - 9 conforming to IS : 8329 along
with all required fittings like tees, bends, junctions, cowls, offsets,
cleanout plugs, access pieces, crosses with or without access doors:
1.15.3 100 mm dia Ductile Iron Double Flanged RM 50 2,565 128,238
1.15.4 150 mm dia Ductile Iron Double Flanged RM 900 4,115 3,703,095
1.15.5 200 mm dia Ductile Iron Double Flanged RM 750 4,842 3,631,388
1.15.6 250 mm dia Ductile Iron Double Flanged RM 165 4,070 671,575
1.15.7 300 mm dia Ductile Iron Double Flanged RM 1.00 8,202 8,202
1.16 Providing, fixing, jointing and testing UPVC soil, waste, vent
pipework comprising UPVC pipe conforming to IS :4985-1983 and
of required class as specified below and fittings (moulded as well as
fabricated) like elbows, bends, reducers, threaded tail pieces, caps,
suitable elbow with suitable extension piece for drain point and other
specials jointing with cement solvent, chasing, cutting and making good
the walls & floors, pipes laid in floors shall be encased with 40 mm
thick concrete all around, complete in all respects including testing of
complete installation.
1.16.1 40 mm dia 6 kg/cm2 (Class III )
RM 1000 147 146,555
1.16.2 75 mm dia 6 kg/cm2 (Class III ) RM 1420 260 369,625
Stup Consultants P.Ltd 61 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
1.17 Fixing, testing & commissioning of floor Drain (Make-Viega model
no.-4935.1) Article Code-557119 Flat model with Sealing flange,with
removable trap (Storage water height-Seal- 30mm) (Drain Capacity 0,6
l/s) with height adjustable and Rotatable top 100 X 100mm and
Stainless Steel grate 94x94mm,with protection plug, with plastic frame
and Stainless Steel Grate.Loading capacity class K=300kg, with supply
DN40, with horizontal drain socket, adjustable due to ball joint with
outlet 50 mm.With Height Adjustment Piece Model No.:-4947
Article Code:- 111496(Body made of environmentally friendly PP
(poly propylene). Item to include all required chasing, cutting and
making good the floors, complete in all respects.
No. 100 480 48,000
1.18 Providing, of floor Drain (Make-Viega model no.-4935.1) Article
Code-557119 Flat model with Sealing flange,with removable trap
(Storage water height-Seal- 30mm) (Drain Capacity 0,6 l/s) with height
adjustable and Rotatable top 100 X 100mm and Stainless Steel grate
94x94mm,with protection plug, with plastic frame and Stainless Steel
Grate.Loading capacity class K=300kg, with supply DN40, with
horizontal drain socket, adjustable due to ball joint with outlet 50
mm.With Height Adjustment Piece Model No.:-4947 Article Code:-
111496(Body made of environmentally friendly PP (poly
propylene) No. 100 2,430 243,000
1.19 Fixing, testing & commissioning of floor trap (Make-Viega model no.-1.19 Fixing, testing & commissioning of floor trap (Make-Viega model no.-
4942.7IN) Article Code-707002 with Sealing flange,with removable
trap,(Storage Water Height 50 mm-Water Seal),with protection
plug, with Three rotable supply DN50, with horizontal drain
socket,with outlet 70/ 100 mm. WITH height adjustable and rotratable
TOP FRAME (Height adjustment piece) 150x 150 (suitable for
143x143 GRATE) WITH BACK PRESSURE SEAL.WITH
STAINLESS STEEL GRATE(143x143).With Height Adjustment
Piece Model No.:-4996 Article Code:- 112707 LOADING
CAPACITY CLASS K=300KG Quality controlled in accordance with
DIN EN -1253(Body and Top Frame made of environmentall friendly
PP (poly propylene). Item to include all required chasing, cutting and
making good the floors, complete in all respects.
No. 700 480 336,000
1.20 Providing of floor trap (Make-Viega model no.-4942.7IN) Article
Code-707002 with Sealing flange,with removable trap,(Storage Water
Height 50 mm-Water Seal),with protection plug, with Three rotable
supply DN50, with horizontal drain socket,with outlet 70/ 100 mm.
WITH height adjustable and rotratable TOP FRAME (Height
adjustment piece) 150x 150 (suitable for 143x143 GRATE) WITH
BACK PRESSURE SEAL.WITH STAINLESS STEEL
GRATE(143x143).With Height Adjustment Piece Model No.:-4996
Article Code:- 112707 LOADING CAPACITY CLASS K=300KG
Quality controlled in accordance with DIN EN -1253(Body and Top
Frame made of environmentall friendly PP (poly propylene)
No. 700 5,980 4,186,000
Stup Consultants P.Ltd 62 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
1.21 Fixing, testing & commissioning of Terrace Drain (Make-Viega
model no.-4946.2 / Article Code- 626990) with Dirt Trap, with
Vertical Drain Socket, DN 100,Without Trap, loading capacity class
H=150 kg,quality controlled in accordance with DIN EN 1253,(Body
and Top Frame made of environmentall friendly PP (poly propylene) .
Item to include all required chasing, cutting and making good the floors,
complete in all respects.
No. 36 480 17,280
1.22 Providing of Terrace Drain (Make-Viega model no.-4946.2 / Article
Code- 626990) with Dirt Trap, with Vertical Drain Socket, DN
100,Without Trap, loading capacity class H=150 kg,quality controlled
in accordance with DIN EN 1253,(Body and Top Frame made of
environmentall friendly PP (poly propylene)
No. 36 4,520 162,720
1.23 Providing and fixing (if demanded extra) Floor / clean out plug with
opening arrangements for soil / waste pipe and other necessary fittings
inlcuding jointing, all complete as per standard detail.
1.23.1 For 110 mm dia UPVC pipe No. 150 325 48,750
1.23.2 For 150 mm dia DI pipe No. 80 1,030 82,400
1.23.3 For 200 mm dia DI pipe1.23.3 For 200 mm dia DI pipe No. 20 1,557 31,134
1.23.4 For 250 mm dia DI pipe No. 6 2,720 16,318
1.24
Providing and fixing S.S finish Countertop Manually operated liquid
soap dispenser with glass bottle Jaquar Code : AKP-35735P or
approved equivalent make complete to the satisfaction of Engineer in
charge.Each 380 2,125 807,500
1.25
Providing and fixing fully automatic hand drier of approved make
suitable to operate on 220 volts, single phase 50 hz, A.C. power supply.
Each 330 6,744 2,225,520
1.26
Providing and fixing horizontal storage type hot water heater fixed to
wall with anchor bolts & nuts, 15mm CP brass angle stop cock and
15mm CP brass non-return valve complete including making
connections with 15mm dia CP connecting pipes on inlet and outlet,
suitable length of power cable and 15 amps plug .(Venus or equivalent)
1.26.1 (a) Capacity 15 Litres Only attached Toilets Each 150 10,900 1,635,000
1.27
Providing and fixing HPL Board (Merino or Equivalent) urinal partition
Magnum/Large with expandable anchor fasteners with C.P. brass bolts
and washers complete, including cutting and making good the walls
where required.
Each 190 613 116,470
1.28
Providing and fixing 6mm thick bevelled edge plate glass mirror of
approved quality with 6mm thick marine ply backing fixed to wooden
cleats with CP brass screws and washers.(Including s/s studs for fixing
the glass)Including inclined angles for Handicapped.
Sqm 50 4,600 230,000
Stup Consultants P.Ltd 63 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
1.29 Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per
IS: 13983 with C.I. brackets and stainless steel plug 40 mm, including
painting of fittings and brackets, cutting and making good the walls
wherever required : Kitchen sink with drain board
1.29.1 510x1040 mm bowl depth 250 m Each 40 7,052 282,086
1.30 Providing and Fixing, testing and commissioning of CP auto push cock
as approved by Engineer in Charge and Consultant/ Architect. (Make :
Jaquar or as per Equivalent make.) Each 450 1,865 839,250
1.31 Providing and Fixing, testing and commissioning of CP brass sink
mixer wall mounted with nut and rubber washer complete including
cutting and making good the walls where required. (Make :
Jaquar " Clarion" -COT-23309B or as per Equivalent make.)
Each 40 4,185 167,400
1.32 Supply, installation, testing and commissioning of tanker inlet
connection complete with 80 mm dia GI inlet piping, hose inlet
connection, MS cabinet enclosure (epoxy painted after fabriction), pad
locking arrangement, inlet flexible hose complete with all necessary
arrangement.No. 1 8,000 8,000
1.33 Providing, Fixing, Testing & Commissioning of Air Release valve for1.33 Providing, Fixing, Testing & Commissioning of Air Release valve for
cold water supply risers, suitable for pressure not less than 10
Kg/Sq.cm.
1.33.1 15 mm dia No. 44 2,658 116,952
1.34 Providing, fixing, testing & commissioning of pressure reducing valve
for cold water supply . The complete system is tested to a pressure not
less than 15 Kg/Sq.cm and shall be suitable to reduce the pressure upto
1 Kg/Sq.cm)
1.34.1 20 mm dia No. 275 2,910 800,250
1.35 Fixing, testing and commissioning of bathing facucets including
necessary wall chases and making good.
1.35.1 Bib Cock and Concealed Stop Cock with complete accessories
(Cat.No.FLR-5047N+ ARI39089 Make:- Jaquar or equivalent).
No. 10 2,229 22,290
1.35.2 S.S Overhead shower with arm and wall flange(Cat.No.OHS-
1709+SHA-485 Make:- Jaquar or equivalent).
No. 10 3,352 33,520
TOTAL CARRIED TO SUMMARY 45,718,782
2 MISCELLANEOUS ITEMS
Stup Consultants P.Ltd 64 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
2Providing and fixing M.S. puddle flanges fabricated of 750 mm long
pipe pieces to R.C.C. water tanks wall / slab. The entire fitting shall be
hot dipped galvanised (Flanges shall confirm to BS10 Table E) .
2.1.1 32 mm dia (Screwed ends MS plate 6 mm thick; 100 mm x 100 mm
plus dia of pipe). No. 11 616 6,776
2.1.2 50 mm dia (Screwed ends MS plate 6 mm thick; 100 mm x 100 mm
plus dia of pipe). No. 9 984 8,856
2.1.3 80 mm dia (Flanged ends MS plate 6 mm thick; 100 mm x 100 mm plus
dia of pipe). No. 7 1,450 10,150
2.1.4 100 mm dia (Flanged ends MS plate 6 mm thick; 250 mm x 250 mm
plus dia of pipe). No. 7 2,160 15,120
Note: Contractor shall ensure that the quoted rates are inclusive of
providing and installing puddle flange in Finished retaining wall as
required including water proofing and making good.
TOTAL CARRIED TO SUMMARY 40,902
3 WATER SUPPLY PUMP ITEMS
3.1 Supplying, installing, testing and commissioning of SS horizontal
centrifugal pump. Each pump shall have TEFC 2900 RPM three phase
electric motor. The pump shall have cast iron head, base plate SS Shaft /
Impeller / Intermediate chamber along with motor, pressure gauge with
isolation cock, Isolation valve, NRV on delivery line. Isolation valve,
stainer (with by-pass) at suction. Pump shall be provided with
mechanical seal, suitable vibration elimination pads of approved design,
drain pipe with valve (25 dia). The pump shall be suitable for auto/
manual operation. The installation shall be complete with all necessary
ancillaries, starter panel / control panel & accessories including base
plate complete as required.
Domestic transfer pump
Location:- Plant room
Flow rate : 3.0 LPS each
Head : 70 Mts
Required for : filling to over head Tank Set 1 292,133 292,133
(2 working + 1 standby)
Stup Consultants P.Ltd 65 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
3.2 Submersiable Centrifugal Non-clog Drainage Pump - Supply,
installation, testing and commissioning of continuous duty submersible
centrifugal non-clogging drainage pumps complete with 3 phase motor
with all necessary protection and mechanical seal etc. complete with all
ancillaries including float type level controllers, electrical control panels
fabricatd from 14 gauge CRCA sheet volt meter ammeter with selector
switch, TPMCB, 5 VA CL : CTs, phase indicating lamps protected by 2
amp SP MCB, DOL starter, necessary wiring, cable alleys, earthing,
interlocking, starter with Automatic float type level controller,
providion of high level alarm, sequence timer, potential free contact to
starter for connection to BAS, both pumps may run simultaneously at
pre determind level. (Both Working)
3.2.1 Vendor to submit proposed pump model with duty curve.
3.2.1.1 Flow rate : 10 LPS (Both Working, 2nd Pump to start at High
Level Set Point)
Head : 15 Mts
Solid Handling : 12 - 15 MM
Location : Basement
Purpose : Drainage
MOC : CI Impeller & Shaft Sets 30 212,562 6,376,873
3.2.1.2 Flow rate : 5 LPS3.2.1.2 Flow rate : 5 LPS
Head : 16 Mts
Solid Handling : 15 MM
Location : Plant room drainage
MOC : CI Impeller & Shaft Sets 2 216,604 433,209
TOTAL CARRIED TO SUMMARY 7,102,215
4 WATER TREATMENT PLANT
4.1 Supplying, installing, testing and commissioning of SS vertical
centrifugal pump. Each pump shall have TEFC 2900 RPM three phase
electric motor. The pump shall have cast iron head, base plate SS Shaft /
Impeller / Intermediate chamber. Pump shall be provided with
mechanical seal. The pump shall be suitable for auto/ manual operation.
The installation shall be complete with all necessary ancillaries &
accessories including base plate complete as required.
4.1.1 Flow rate : 4.5 LPS each (2 Working + 1 Standby)
Head : 30 Mts
Required for : Filter Feed Pump Set 1 367,425 367,425
4.2 Providing, fixing, testing & commissioning of vertical FRP filter with
adequate dirt holding capacity. The filter shall be complete having PVC
frontal piping with 50 mm multiport valve including all supporting
structure with initial charge filter media. The filter shall be provided with
set of internals for raw water inlet and bottom collecting system. Velocity
in frontal piping and valves shall be 1.50 m/sec.
4.2.1 Filter for Domestic Water services.
Filteration Rate 20000L/Sqm/Hr
Working pressure 3 Kg/Sq.cm
Capacity : 9 LPS Set 1 287,500 287,500
Stup Consultants P.Ltd 66 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
4.2.2 Activated Carbon Filter
Filteration Rate 14000L/Sqm/Hr
Working pressure 3 Kg/Sq.cm
Capacity : 9 LPS Set 1 316,250 316,250
4.3 Providing, fixing, testing & commissioning of FRP water softening
plant (suitable for 3 Kg/Sqcm working pressure) complete with initial
charge with T-40 NA Resin, multiport valve with built in ejector for
controlling all operations), regeneration system and HDPE tank, pressure
gauge at inlet, outlet and back wash (each with isolation cock), valves,
fittings and water hardness testing kit & associated works. Velocity in
frontal piping and valves shall be 1.50 m/sec. Softener shall be suitable
for the following duty.
4.3.1 Raw water hardness 650 Mg/L
Treated water harness 100 Mg/L
Regeneration Period 12 Hrs.
Capacity : 9 LPS Set 1 1,012,000 1,012,000
4.4 Supplying, installing, testing and commissioning of chlorine dosing
system (for domestic water treatment plant) consisting of one HDPE
tank of 100 litres capacity with a positive displacement diphragm
dosing pump having variable flowrate of 0-6 lph. The motor shall be
suitable for operation at 240 V/Single phase/50 Hz. Supply. The pump
shall be supplied complete with necessary polypropylene piping, valves,
strainers, low level switch and injection fittings. The pump shall be
speed & stroke control.. speed & stroke control..
Set 1 28,750 28,750
4.5 Supply, installing, testing and commissioning of annunciation and
indication panel with interlocking arrangement complete in
accordance to specification with level controller (In Raw Water,
Treated Water and Soft Water Tank : High / Low Level Controller) etc
with control cabling from field to MCC as required.
Lot 1 103,500 103,500
4.6 Providing, fixing, testing & commissioning pressure switch for water
pumps to start/stop the pump at set pressure. Including wiring, cabling
from pump to panel & all other accessories as required to operate the
system automatically.
No. 3 17,250 51,750
4.7 Supply, installing, testing and commissioning of level controllers for
water pumps to start/stop the pump at set level. Including wiring,
cabling from pump to panel & all other accessories as required to
operate the system automatically.
No. 15 23,000 345,000
4.8 Supply, installing, testing and commissioning of Electric control panel
to open/close the solenoid valve at low/ high water level through level
controller in soft water tanks. Including wiring, level controller probes
& other accessories as required to operate the system automatically.
No 1 172,500 172,500
TOTAL CARRIED TO SUMMARY2,684,675
5 Hydropneumatic System:
Stup Consultants P.Ltd 67 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
Supply, Installation, Testing And Commissioning of Compact Self
Contained Skid Mounted Hydropneumatic System As Follows:
a. In-Line, Multisage, centrifugal pumps with SS-304 casing and
impeller and SS-316 shaft, CI base & head TEFC motor (with
mechanical seal)
(Vendor to submit performance curves and technical catalog of
the proposed model for review & information)
The pump shall be selected for performance at best efficiency
point. However, the pump selection shall be suitable for
performance with set point @ + 20% of the rated head.
Nos. of Pumps : 2 Working (2nd Pump to start at Higher Set
Point)+1 Standby
Water Flow Rate : 8 LPS
Head : 80 M
b. External Pump mounted or wall mounted microprocessor PID
controller and frequency inverter (VFD) integrated in a single
body or as separate components with pressure sensor
transmitter minimum two lined LCD display, diodes to indicatetransmitter minimum two lined LCD display, diodes to indicate
pump ready, pump running and fault and capable to
communicate with other controllers following MODBUS-RTU or
BACNET Class-2 protocall through RS485 port. System should
be capable to compensate for frictional losses at lower flows. All
alarms should be displayed in the controller. System should be
equiped with dry running protection
Quantity : Complete Set for (a).
c. Complete (Skid mounted wall mounted / floor mounted) electrical
control panel comprising of all accessories such as PLCs,
pressure switches, pressure transducers, control wiring and any
other necessary imports etc. (list to be provided by the vendor)
d. Precharged diaphram pressure vessel of suitable capacity with
food grade membrane, charging connection, connected to outlet
header with necessary flanges, gaskets, isolating valves,
nuts/bolts etc complete.
e. Set of accessories such as pressure switches, pressure
transducers, inter connecting power and control cabling etc.
complete
f. Accessories like NRVs, isolating valves, SS-304 (non-Magnetic)
suction and delivery header, pressure gauge, MS base frame
(Synthetic enamel painted over a coat of primer)
Hydropneumatic System as described aboveSet 1 1,427,091 1,427,091
TOTAL CARRIED TO SUMMARY1,427,091
Stup Consultants P.Ltd 68 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
6
Solar Water Heating System of 500 Litres/ Hr Capacity with
Combined Heat Pump Technology or 2000 LPD
Conventional Package solar water heating system based on a
closed circuit indirect heat transfer system and capable of
producing specified quantity of water at 60 deg C during peak
winters. The system shall essentially consist of insulated storage
tank, collector panels, insulated interconnecting pipe work, electric
booster, supporting structure, electrical back up all complete.
Set 1 540,788 540,788
TOTAL CARRIED TO SUMMARY540,788
7 ELECTRICAL INSTALLATION FOR PLUMBING SYSTEM
Design, fabrication, assembling, wiring, supply, installation, testing and
commissioning of motor control centre shall be fabricated out of 14
gauge CRCA sheet steel in form in 3b formation with reinforcement of
suitable size angle iron, channel ‘T’ sections irons and/or flats wherever
necessary. Cable gland plates shall be provided on top as well as at the
bottom of the panels. Panels shall be treated with all anticorrosive
process before painting as per specifications with 2 coats of red oxide
primer and final approved shade of powder coated paint. 2 Nos.
earthing terminals shall be provided for 3 phase, 4 wire, 50 Hz supply
system. Lifting hooks shall also be provided in case of large panels.
Approval shall be taken for each panel before fabrication. CadmiumApproval shall be taken for each panel before fabrication. Cadmium
Plated hardware shall be used in fabrication of panels. Quoted rates
shall inclusive of cables (in accordance to specification)
with earthing from panel to each motor / equipment.
1 MCC –1 for Plumbing system
Incoming
150 amps TPN MCCB with the following accessories:
a. 0-500 volts 96 x 96 mm square voltmeter with selector switch
protected by 2 amps TP MCB. 1 Set
b. Phase indicating lamps protected by 2 amp SP MCB 3 Sets
Bus Bar
200 amps TPN aluminium bus bar with heat shrinkable insulation
sleeves.
Outgoings
a. 3 No. suitable rating MPCB for 7.5 KW DOL starter and outgoing
feeder to Filter feed pump (including 1 No. as standby). Each
compartment shall contain auto / manual selector swtich and indicating
/ pushbutton lamps with MCB for ON / OFF / TRIP of motor.
b. 1No. 160 amps TPN MCCB outgoing feeder to 1No. Domestic Water
Hydro-pneumatic system.
Stup Consultants P.Ltd 69 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
c. f. 2 No. suitable rating MPCB for 5 KW DOL starter and outgoing
feeder to sump pumps in plant room. Each compartment shall contain
auto / manual selector swtich and indicating / pushbutton lamps with
MCB for ON / OFF / TRIP of motor.
Spare MCP's & MPCB’s of following capacities:
i. 25 amps TPN MCB’s 4 No.
ii. 40 amps TPN MPCB’s 4 No.
iii. 63 amps TPN MPCB’s 2 No.
Necessary cabling, cable alleys, internal wiring, and interlocking,
earthing for all equipment shall also be included.
Notes :
a. All MPCBs shall be of 25 KA breaking capacity and suitable for
motor duty application.
b. Provision shall be made for providing potential free contacts to all
pumps starters for connection to BAS
c. Provision shall be made to ensure system protection from dry
running of the pumprunning of the pump
MCC - 1 For Plumbing System as described above. Set 1 652,814 652,814
TOTAL CARRIED TO SUMMARY652,814
8 WATER COOLERS with R.O.
Supplying,Installation Testing & commisioning of floor mounted storage
water cooler of undermentioned capacity with R.O. made of Stainless
steel body with PUF insulation, SS storage tank and extra large SS
tray to prevent splashing of water to ensure quick drainage. The
complete unit shall be compact, eco- friendly with externally mounted
thermostat for easy setting of temperature complete as required. the
system shall be factory assembeled and tested. The cost of suitable
RO Plant shall also be included.
Rated Condition -60 LPH
Storage Capacity 80 Ltr
Faucet-2 Nos. 80 106,492 8,519,360
TOTAL CARRIED TO SUMMARY
9 LPG GAS SYSTEM
A. Gas Bank
1.1 Cylinder manifold suitable for 1X 26 nos of LPG cylinders of 19kg.capacity
fabricated from of Seamless Sc-40 Pipe of 25mmdia and as per (IS: 6044
Part-1 of 1971 specifications)
Set 02
13,536 27,072
1.2 Adjustable pressure regulator (R-2301 Gas flow rate is 100Nm3/hr and out let
pressure is adjustable from 0.5 to 10 kg/cm2' 1" BSP-INT) like wit fittings. One
set of two reducers inlet side, out let side , flanges, welding at 4 points and
fitment of regul
Nos 02
17,422 34,844
1.3 H.P Brass Non Return Valves Nos. 52 786 40,870
1.4 Compact Valve Adaptors for cylinders, SierraType Nos 52 1,004 52,222
1.5 H.P.Flexible Cylinder Pigtails with hydraulic crimping ends, 3ft long Nos. 521,004 52,222
Stup Consultants P.Ltd 70 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- Plumbing & Sewerage Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
1.6 Pressure Gauge 4" dial, range (0-10kg/sq.cm) with suitable isolation valves on
the cylinder manifold
Nos. 02
4,279 8,558
1.7 Pressue Gauge 4" dial, range (0-4kg/sq.cm) with suitable isolation valves after
the PRS-1
Nos. 01
4,279 4,279
1.8 Isolation Ball Valves.size:25mm Ball Valve -(L3RBTC) Nos 06 4,541 27,246
1.9 Supply and Installation 9 kg DCP type fire extinguishers{As per IS-15683 and
with anti corrosive coating thickness min.0.050mm}
Nos 04
13,099 52,397
1.1 Sand Buckets & Water Buckets,4nos each With Stand Nos 04 1,310 5,240
1.12 Supply and installation of LPG Gas Bank of MS construction size: 7L x 1W x
2.5H ) or ( 3.5 L x3 W x 2.5H) in mtrs.
Nos 01
253,252 253,252
1.13 Providing and Fixing "C" class ERW Pipe 25 mm dia duly welded with all
Fittings likeshort bends,Tees & Sockets,clamps etc.
Mtrs. 10
917 9,169
B Sprinkler System
2.1 Provinding and Fixing MS "C" Class ERW Pipe 50mm duly welded with all
Fittings like Elbow, Tee & Socket etc.
Mtrs 10
1,528 15,282
2.2 Provinding and Fixing MS "C" Class ERW Pipe 25mm duly welded with all
Fittings like Elbow, Tee & Socket etc.
Mtrs 07
917 6,419
2.3 M.V.Water Spry Nozzle(15mm) K-Factor- 30 Nos. 07 611 4,279
2.4 Isolation Ball Valves,size:50mm Nos. 01 7,860 7,860
C Pipe & valve
3.1 Providing and Fixing "C" class ERW Pipe dia duly welded with all Fittings like
short bends,Tees & socket clamps etc.size:50mm
Mtrs. 144
1,528 220,067
3.2 Wrapping Coating of of 50NB pipe with 2mmthick wrapping coating tape Mtrs. 144 279 40,241
3.3 50mm Ball Valve - Fire Proof - (L3RSWCF) Nos 05 12,226 61,130
3.4 Providing & laying of the 6" Hume Pipe for Covering 50mm Pipe Mtrs. 25 2,620 65,496 2,620 65,496
D Kitchen
4.1 Isolation Ball Valves,size:15mm Nos 05 2,795 13,973
4.2 High Pressure Adjustable Regulator (0- 20Psi) Nos 01 1,703 1,703
4.3 High pressure preset Regulator 15 Psi Nos 01 4,104 4,104
4.4 High pressure preset Regulator 10 Psi Nos 01 4,104 4,104
4.5 High pressure preset Regulator 5 Psi Nos 01 4,104 4,104
4.6 High Pressure Preset Regulator 7 Psi {Before meter }
(G-16)
Nos 01
4,104 4,104
4.7 Flexible Burner Pigtails 4 ft.Long for equipments.with hydraulic crimpings ends Nos 04
1,004 4,017
4.8 Brass Stop Nuts/ Dead Plugs of 3/8" Nos 01 262 262
4.9 Pressue Gauge 4" dial, range (0-2kg/sq.cm) with suitable isolation valves Nos 01 4,279 4,279
4.1 Gas Filter for Commercial Meter,size:25mmdia Nos 01 8,733 8,733
4.11 Commercial Meter Diaphargm Type G-16 {Load Q Min.m3/h-0.16, Max.m3/h-
25. Pressure Stage P. max - 0.5 Bar
Nos 01
68,116 68,116
TOTAL CARRIED TO SUMMARY 1,105,644
Stup Consultants P.Ltd 71 of 234
SCHEDULE OF QUANTITIES
PREAMBLE STP:
1 All items of work under this Contract shall be executed strictly to fulfill the requirements laid down under
“Basis of Design” in the specifications. Type of equipment, material specification, methods of installation and
testing and type of control shall be in accordance with the specifications, approved shop drawings and the
relevant Indian Standards, however capacity of each component and their quantities shall be such as to fulfill
the above mentioned requirement.
2 The unit rate for all equipment or materials shall include cost in INDIAN RUPEES (INR) for equipment and
materials including all taxes and duties and also including forwarding, freight, insurance and transport into
Contractor’s store at site, storage, installation, testing, balancing, commissioning and other works required.
3 The rate for each item of work included in the Schedule of Quantities shall, unless expressly stated
otherwise, include cost of:
a All materials, fixing materials, accessories, appliances tools, plants, equipment, transport, labour and
incidentals required in preparation for and in the full and entire execution, testing, balancing, commissioning
and completion of work called for in the item and as per Specifications and Drawings.
b Wastage on materials and labour.
c Loading, transporting, unloading, handling/double handling, hoisting to all levels, setting, fitting and fixing in
position, protecting, disposal of debris and all other labour necessary in and for the full and entire execution
and for the job in accordance with the contract documents, good practice and recognized principles.
d Liabilities, obligations and risks arising out of Conditions of Contract.
e All requirements of Specifications, whether such requirements are mentioned in the item or not. The
Specifications and Drawings where available, are to be read as complimentary to and part of the Bill of
Quantities and any work called for in one shall be taken as required for all.
f In the event of conflict between Bill of Quantities and other documents including the Specifications, the most
stringent shall apply. The interpretation of the Architect / Consultant /Project Manager shall be final and
binding.
4 The Contractor shall procure and bring Materials/Equipment to the site only on the basis of drawings
approved for construction and shop drawings and not on the basis of Bill of Quantities which are approximate
only. This also applies to the Contractor’s requisition for Owner supplied materials.
5 The contractor shall include for making all the opening in slabs, beams, walls etc. as required for his work.
However, the contractor can coordinate with civil work to provide necessary sleeves. All openings shall be
closed using water proofing compound or as specified by Project Manager.
6 The work shall be carried out in conformity with the plumbing drawings and within the requirements of
architectural, HVAC, electrical structural and other specialized services drawings.
7 The contractor shall cooperate with all trades and agencies working on the site. He shall make provision for
hangers, sleeves, structural openings and other requirements well in advance to prevent hold up of progress
of the construction schedule. All supports to the civil structure shall be provided with anchor fastners.
8 On award of the work, contractor shall submit a schedule of construction in the form of a PERT chart or BAR
chart for approval of the Project Manager.
9 On award of the work the contractor shall be issued two (2) sets of consultant’s drawings. The drawings
shall be the basis of contractor’s shop drawings.
10 Shop drawings are detailed working drawings coordinated with other trading work, which incorporate the
contractor’s details for execution of the work and incorporate equipment manufacturer’s details and
dimensions to ensure that the same can be installed in the space provided.
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR
,LUCKNOW IN U.P.
Stup Consultants P.Ltd 72 of 234
PREAMBLE STP:
11 All shop drawings should detail pipe routing and levels, showing location of other services at crossings etc.,
cable runs, route cable trays and all allied works and must be fully coordinated with other services, before
execution of the works.
12 All shop drawings will be made on Autocad and coloured prints has to be produced for site work.
13 All rates quoted are inclusive of cutting holes and chases in walls and floors and making good the same with
cement mortar / concrete / water proofing of appropriate mix and strength as directed by the Project
Manager. Contractor shall provide holes, sleeves, recesses in the concrete and masonry work as the work
proceeds. All hot and cold water supply pipes crossing masonry walls of toilets shall be provided with GI pipe
sleeves. The annular space between the pipe and sleeve shall be filled up with glass wool in between and
fire proof sealent on either end after testing.
14 Any pipe crossing fire rated wall as per fire compartmentation will be provide with higher size of GI sleeve.
All floor crossing pipes will be provided with higher size GI sleeve.
15 The contractor shall, from time to time, clear away all debris and excess materials accumulated at the site
failing which the same shall be done by Project Manager at contractor’s risk and cost and cost of clean up
shall be deducted from the contractors prorata bill.
16 After the fixtures, equipment and appliances have been installed and commissioned, contractor shall cleanup
the same and remove all plaster, paints, stains, stickers and other foreign matter or discoloration leaving the
same in a ready to use condition.
17 On completion of all works, contractor shall demolish all stores, remove all surplus materials and leave the
site in a broom clean condition, failing which the same shall be done by the Project Manager at the
Contractor'’ risk and cost. Cost of the cleanup shall be deducted from the contractor’s bills on pro-rata basis
in proportion to his contact value.
Stup Consultants P.Ltd 73 of 234
A SEWAGE TREATMENT PLANT 4381138
B CONTROL PANEL FOR SEWAGE TREATMENT PLANT 529227
TOTAL : 4910365
Bill of Quantities- STP
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW, U.P.
SUMMARY OF COSTS
Sr.No. Description TOTAL COST IN INR
Stup Consultants P.Ltd 74 of 234
RATE
(INR)AMOUNT (INR)
A. SEWAGE TREATMENT PLANT
( Extended Aeration/ Rotating Media Bio Reactor )
1 Design, supplying, installing, testing & commissioning of
Sewage Treatment Plant (excluding excavation, back filling
& disposal of surplus earth Civil construction work) for the
following duty:
Nature of effluent - Domestic Sewage from Room toilets,
Public toilets, Kitchen cum/day)
(Kitchen effluent app.10.0 cum.day)
Daily average flow - 225 Cum / Day
pH - 6.5 – 8.5
BOD5 - 250 – 400 Mg/L
S. Solids - 200 – 450 Mg/L
COD - 600 – 800 Mg/L
Oil & Grease - 75 Mg / L
Effluent discharge standard after treatment
pH - 6.0 – 8.0
BOD5 - Less than 20 Mg/L
S. Solids - Less than 10 Mg/L
COD - Less than 60 Mg/L
Oil & Grease - Less than 5 Mg/L
Coliform Count - Nil
Total Hardness (as CaCO3)- 10 Mg/L
Quantity of Treated water for Cooling Tower Make Up-
Approx. 200 Cum/ Day
Sewage treatment plant shall include the following items:
Screen Chamber
Sewage equalization tank/sump
Aeration tank / RMBR Inbuilt Tank
Clarifier tank
Sludge holding tank/ Hydrophobic sludge Bags
Air Blowers (if reqd), Pumps & equipment
Screw Pump & Filter Press (Reqd in Extended Aeration)
Piping, valves etc
Electrical Panel & Cabling
Flushing / Irrigation water storage tank
Soft water tank
Common plant room adjacent to STP.
Pre-treatment for Kitchen effluents (if required)
1.1 Supply, installation, testing & commissioning of 2 Nos
Stainless Steel Perforated, Corrugated Bar Screen with
suitable lifting arrangement Set 1 47790 47790
1.2 Supply of MS hot dip galvanized puddle flanges in accordance
to BS:10 table D as required to be provided (in the structural
slab and wall) of various diameters. Puddle flanges shall be
provided for all the structural component of the STP. The
installation of the puddle flanges shall be carried out by the
Civil contractor in accordance to the Civil GA drawing (to be
prepared by the STP contractor) at the required levels &
position; under the supervision of the STP contractorL/S 1 107527 107527
Bill of Quantities- STP Work
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW IN U.P.
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
Stup Consultants P.Ltd 75 of 234
RATE
(INR)AMOUNT (INR)
Bill of Quantities- STP Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
1.3 Supply of plastic manhole step/foot rest (@ 300 mm c/C) with
polypropelene compound injection molded around 12 mm dia
(Fe-415) steel reinforcing bar. Provision of the foot rest is
envisaged in various tanks/ components of the STP for the
purpose of accessability. The installation of the foot rest shall
be done by the civil contractor as per civil GA drawingL/S 1 35842 35842
1.4 Supply, installation, testing & commissioning of CI medium
duty rectangular manhole cover with frame for the feasibility of
access in the tank L/S 1 35842 35842
Size : 600 x 900 (175 kg)
1.5 Supply of vent pipes of 100 mm dia with mosquito proof
grating suitable for the ventilation purpose of the various tanksL/S 1 23895 23895
1.6 Supply, installation, testing & commissioning of electronic type
level indicator and controller for automatic operation of the
system with high/low level alarm complete with auxillary
NO/NC contacts. Set 1 47790 47790
1.7 Supply, installation, testing & commissioning of sight tube (of
3.5 to 4.5 m length) with isolation valve at top/bottom,
demarcation on tube & for making the installation completeL/S 1 23895 23895
Contractor shall ensure submission of detailed GA
drawings (Plan & Section), P & I diagram, schematic
diagram for the above mentioned component and
additional component if so required for the complete
working of the STP and got it approved by the Owner’s
Architect / Project Manager / Consultants. .
1.8 Supply, installation, testing & commissioning of non clogging
type pumps capable of handling solids upto 38 mm having CI
casing & impeller complete with all accessories, motor of
required capacity. Delivery header with isolation valve,
pressure gauge on delivery line with isolation cock, level
controller (with wiring) to control the level of sump
automatically. Pumps shall have following duty:
1.8.1 Submersible Sump Pumps
Flow rate (each) = Suitable capacity
Head = Suitable L/S 1 35842 35842
1.8.2 Plant room sump pump with CI body & CI impeller pump
Flow rate (each) = Suitable capacity
Head = Suitable L/S 1 47790 47790
(Solid handling size for this pump shall be 15 mm).
Cost shall be inclusive of PVC flexible Hose pipe ( for piping
submeged in effluent) with M S epoxy piping (for piping non-
submerged in effluent)
Provision of guide ropes to guide submersible pump from
upper level to operational level in sump basin with channels /
angle section shall be made by the STP contractor.
Stup Consultants P.Ltd 76 of 234
RATE
(INR)AMOUNT (INR)
Bill of Quantities- STP Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
Contractor is requested to submit quote rate for above pumps
with CI Casing & SS impeller, material of construction.
1.9 Air diffusion system shall include the following:
1.9.1 Twin lobe rotary air blowers capable of delivering suitable
amount of free air at suitable pressure driven through “V” belt
or directly coupled through flexible coupling to a TEFCmotor of
suitable HP Suitable for 415 ± 10% volts, 3 phase, 50 cycles
A/C supply. L/S 1 101554 101554
1.9.2 Air piping shall comprise of pipes droppers/ laterals with M S
(epoxy coated) Header complete with all fittings such as tees,
crosses, plugs, sockets, elbows, reducers, supports & clamps,
puddle flanges etc cutting chases & making good. Contactor to
submit detailed P & I indicating their proposal.Lot 1 119475 119475
1.9.3 Non clog type air dispersion system capable of handling 3-5
cfm of air with oxygen transfer efficiency of 3-4% per/meter
water depth. Air dispersion grid shall be assembled in modular
form so that they can be replaced / repaired easily from plat
form at the top. (Imported fine bubble membrane diffusers)Lot 1 119475 119475
1.9.4 Bronze Ball valve and air dispersion grid as required for STP
as described above. Lot 1 53764 53764
Note :
Air dispersion system shall be provided for Sewage Sump,
Aerobic digester cum Thickner & Aeration Tank.
1.10 Providing and fixing all piping (as described below) and
isolation control valves for making the system complete.
SS 304 : Submerged air piping
MS Epoxy : Air piping
PVC Piping : Pumped effluent & tank overflow pipe line
GI Heavy : Interconnecting pipe line after delivery
header of pump/ filter Job 1 238949 238949
2 Supplying, installing, testing & commissioning of vertical
centrifugal filter feed water pumps CI Head & Base,
SS304 Impeller along with motor, pressure gauge with
isolation cock, Isolation valve, NRV on delivery line. Isolation
valve, stainer at suction. Mechanical seal, suitable vibration
elimination pads of approved design, drain pipe with valve
(25 dia) for the pump. The pump shall be suitable for
415±10% volts 3 phase AC supply (solid handling size for this
pump shall be – 5 mm)
Capacity : Suitable Capacity
Head : Suitable L/S 1 102748 102748
Stup Consultants P.Ltd 77 of 234
RATE
(INR)AMOUNT (INR)
Bill of Quantities- STP Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
3 Supplying, installing, testing and commissioning of centrifugal
vertical water supply pump C.I Body, Bronze Impeller with
mechanical seal along with motor. Pressure gauge with
isolation cock, NRV, Isolation valve on delivery line. Isolation
valve, stainer at suction. Suction &delivery header (sized at
velocity of 1.5m/sec). Suitable vibration elimination pads of
approved design for the pump. The pump shall be suitable
for 415±10% volts 3 phase AC. Supply.
3.1 Capacity : ___ LPS
Head : ___ M
Purpose : Set 1 59737 59737
(1 Working + 1 Standby)
Note
Operation of pump shall be based on level controller proposed
to be installed in tank as per site location. The contractor to
recheck the Head required for pumps as per site conditions
and provide accordingly.
4 Supplying, installation, testing and commissioning of ----- Nos.
centrifugal horizontal / vertical soft water booster pump (Flow
Rate -----.0 lps) to cooling tower of CI Head & Base, SS 304
Impeller along with motor, pressure gauge with isolation cock,
NRV, Isolation valve on delivery line. Isolation valve, stainer
(with by-pass) at suction. Mechanical seal suitable vibration
elimination pads of approved design, drain pipe with valve
(25 dia) for the pump. The pump shall be suitable for
415±10% volts 3 phase AC Supply.
Pump shall be supplied with two nos pressure vessel of 50
liters actual water capacity (at specified cut-in /cut- out ) with
pressure switch and wiring for ON / OFF Function of
the pump.
Cost shall be inclusive of G.I piping Suction/ Delivery Header
with hot dip galvanizing. Set 1 181602 181602
4.1 Capacity : 5.2 LPS
Head : 26 M
Purpose : AC Cooling Tower Makeup Set 1 179212 179212
(1 Working + 1 Standby)
4.2 Capacity : 1.4 LPS
Head : 26 M
Purpose : DG Cooling Tower Makeup Set 1 34648 34648
(1 Working + 1 Standby)
5 Supplying, installing, testing and commissioning of composite
FRP vessel filter with PVC frontal piping. Filter shall be
suitable for working pressure of ____ kg / cm2 and shall
include media, standard fittings like pressure gauges,
sampling cock, backwash, rinse drain, vacuum breaker,
including multiport valve, & 1 No water flow meter at outlet
(flow meter shall be approved by dept. of weights & measures
).
5.1 Multigrade pressure sand filter Nos. 2 268818 537636
Flow rate : 215 KLD
Filtration velocity 1500 Cum./ Hr./ Sq.cm.
Filter diameter Suitable.
5.2 Activated Carbon Filter Nos. 2 298687 597374
Stup Consultants P.Ltd 78 of 234
RATE
(INR)AMOUNT (INR)
Bill of Quantities- STP Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
Flow rate : 215 KLD
Filtration velocity 1500 Cum./ Hr./ Sq.cm.
Filter diameter _________ meter.
6 Supply, installation, testing & commissioning of water
softening plant (FRP) for make-up water for cooling towers
comprising of face piping with butterfly valve with brine ejector
and plastic piping complete with brine tank with fittings and
brine filtering media and complete charge of cation exchange
resin as per speciftication for the capacity as given below:
Water Flow : 215 KLD
(Incoming hardness _____450 PPM (Approx))
Working pressure 3.5 Kg / Sq.cm.)
Outgoing hardness less than 20 ppm
Water Softening plant as described above
OBR - 168 Cum/ Hr Nos. 1 573479 573479
7 Supply, installation, testing & commissioning of High Flow UV
system for tertiary water treatment. The UV chamber shall be
internally & externally electro polished with double side flange,
drain part & probe bar. The unit shall use quartz glass
technology for superior UV transmission and specialized high
intensity UV lamp rated for 16000 hour operation. The UV
dosage shall be greater than 60,000 uW-Sec / sq.cm
Unit flow : 215 cu-m / Day No. 1 238949 238949
8 Supply, installation, testing & commissioning of poly electro
type dosing system comprising of 100 ltrs HDPE/FRP tank
with 0-6 lph electronic metering type pump and SS agitator
complete with motor. Set 1 47790 47790
9 Supply, installation, testing & commissioning of single screw
double stage, flanged end, CI body alloy steel screw and
rotateing parts, pump to filter press of Suitable capacity &
suitable head. ( 1 Working + 1 Standby) No. 2 25090 50179
10 Supply, installation, testing & commissioning of automatic,
hydraulic closing mechanism filter press comprising of CI body
grade FG 20, polypropylene plate with sludge cake holding
capacity of 650 ltrs. No. 1 179212 179212
11 Providing and laying G.I. pipes (heavy class) of approved
make complete with G.I. fittings such as tees, crosses,
plugs, sockets, elbows, reducers, unions, flanges, sleeve
pieces, check nuts etc in including cutting and making good
the walls, floors, RCC work etc cutting chases & filling the
same with cement concrete 1:3:6 (1 cement : 3 coarse sand
:6 graded stone aggregate 20 mm nominal size) or cement
mortar 1:4 (1 cement : 4 coarse sand) as required, including
painting the exposed pipes with desired shade of enamel
paint over a coat of primer.
11.1 50 mm dia LOT 1 17921 17921
11.2 80 mm dia LOT 1 29869 29869
Stup Consultants P.Ltd 79 of 234
RATE
(INR)AMOUNT (INR)
Bill of Quantities- STP Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
12 Providing, fixing, jointing and testing in position the following U-
PVC pressure Pipes as per ASTM D 1785 and conforming to
IS:554. Cut to required lengths including all necessary fittings
and specials such as bends, tees, unions, reducers, flanges
and plugs etc. The pipes & fittings shall be tested to a
pressure of ___ Kg/Sq.cm. Fixing at wall/ ceiling level
supported by clamps, hangers etc. as per specification.
Cutting hole in wall / floor / slab and making good the same
with cement concrete 1:2:4 complete as required (upto 2" dia
UPVC moulded fittings and above 2" dia powder coated fittings
shall be used). G.I. heavy class pipe sleeve of larger diameter
shall be provided wherever the pipes crossing the walls/floor
slab and sealing the sleeves as per consultants
requirement. Threading, jointing & making proper
connections.
12.1 50 mm dia LOT 1 9558 9558
12.2 80 mm dia LOT 1 11947 11947
13 Providing and fixing cast iron butterfly valves (for treated
water) tested to 15 kg/ Sqcm pressure (Including flanges).
13.1 50 mm dia LOT 1 35842 35842
13.2 80 mm dia LOT 1 59737 59737
14 Providing and fixing horizontal flap type non-return valve
tested to 15 kg/Sqcm pressure of approved make (including
flanges)
14.1 50 mm dia LOT 1 35842 35842
14.2 80 mm dia LOT 1 59737 59737
15 Providing, fixing, testing and commissioning water meter with
direct reading dial in KL with all integral parts of gun metal or
brass with necessary fitting such as threaded pieces, unions
pressure gauge and isolation cock, flanges piece for future
removal, flanges / unions complete with all necessary testing
charges and obtaining test certificates from municipal
authorities, on following size pipe lines (1 no. strainer & 2 nos.
pressure gauges shall be provided at inlet & outlet and cost
shall be inclusive for the same).
15.1 65 mm dia LOT 1 119475 119475
16 Approval from pollution board at initial & various other
stages of works including preparation of report / drawings as
per pollution board requirement, arrangement of raw sewage
for testing & commissioning. Contractor shall include the cost
of all chemicals (consumed during testing & commissioning
and the cost of such items of works which are not explicitly
mentioned above, but are mendatory to have pollution board
approval. Job 1 179212 179212
TOTAL "A" 4381138.20
B ELECTRICAL INSTALLATION FOR STP
Stup Consultants P.Ltd 80 of 234
RATE
(INR)AMOUNT (INR)
Bill of Quantities- STP Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
1 Design, fabrication, assembling, wiring, supply, installation,
testing and commissioning of motor control centre shall be
fabricated out of 14 gauge CRCA sheet steel in form in 3
formation with reinforcement of suitable size angle iron,
channel ‘T’ sections irons and/or flats wherever necessary.
Cable gland plates shall be provided on top as well as at the
bottom of the panels. Panels shall be treated with all
anticorrosive process before painting as per specifications with
2 coats of red oxide primer and final approved shade of
powder coated paint. 2 Nos. earthing terminals shall be
provided for 3 phase, 4 wire, 50 Hz supply system. Lifting
hooks shall also be provided in case of large panels. Approval
shall be taken for each panel before fabrication. Galvanised
hardware with zinc passivation shall be used in fabrication of
panels.
MCC-1 (STP Motor Control Centre)
Incoming
200 amps TPN MCCB with the following accessories:
a. 0-500 volts 96 x 96 mm square digital electronic voltmeter with
selector switch shall be protected by 2 amps TP MCB. 1 Set
b. 0-200 amps 96 x 96 mm square digital electronic ammeter
with selector switch and 200/5 amps 15 VA CL: 1 CTs. 1 Set
c. Phase indicating lamps shall be protected by 2 amp SP MCB 3
Sets
Bus Bar
300 amps TPN (35 KA) copper bus bar with heat shrinkable
insulation sleeves.
Outgoing
a. Suitable capacity 4 Pole MPCB for Suitable capacity/ HP
direct on line starter and out going feeders to submersible
pumps. Each compartment shall contain direct operated
digital electronic ammeter 0-32 amps range with auto/manual
selector switch and indicating lamp with MCB’s and
‘ON/OFF/TRIP’ status of motor.
b. Suitable capacity TPN MPCB for Suitable capacity/ HP star
delta starter and outgoing feeder to air roots (__ working + __
standby) blowers pump. Each compartment shall contain CT
operated digital electronic ammeter of 0-63 amps range with
auto/manual selector switch and indicating lamps with MCB’s
and ‘ON/OFF/TRIP’ status of motor
c. Suitable capacity TPN MPCB for Suitable capacity/ HP direct
on line starter and outgoing feeders to ____ Nos. of (__
working + __ standby) filter feed pump. Each compartment
shall contain direct operated digital ammeter of 0-40 amps
range, auto/manual selector switch and indicating lamps with
MCB and ‘ON/OFF/TRIP’ status of motor
Stup Consultants P.Ltd 81 of 234
RATE
(INR)AMOUNT (INR)
Bill of Quantities- STP Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
d. Suitable capacity TPN MPCB for Suitable capacity/ HP direct
on line starter and outgoing feeder to (__ working + __
standby) soft water pumps. Each compartment shall contain
direct operated 0-40amps range digital ammeter with selector
switch, auto/ manual selector switch and indicating lamps with
MCB’s and ON/OFF/TRIP status of motor.
e. Suitable capacity TPN MPCB for Suitable capacity/ HP direct
on line starter and outgoing feeders to (__ working + __
standby) plant room sump pump. Each compartment shall
contain direct operated digital ammeter of 0-32 amps range,
auto/manual selector switch and indicating lamps with MCB’s
and ‘ON/OFF/TRIP’ status of motor
f. Suitable capacity TPN MPCB forSuitable capacity/ HP direct
on line starter (__ working + __ standby) and outgoing feeders
to irrigation pump. Each compartment shall contain C T
operated 0-40 amps range digital ammeter with selector
switch, auto/manual selector switch and indicating lamps with
MCB’s and ‘ON/OFF/TRIP’ status of motor.
h. Suitable capacity TPN MPCB for Suitable capacity/ HP direct n
line start (including ____ No standby) and outgoing feeders to
screw pumps. Each compartment shall contain direct operated
digital ammeter of 0-50 amps range, auto/manual selector
switch and indicating lamps with MCB and ‘ON/OFF/TRIP’
status of motor
j. Spare Feeders of suitable capacities:
k. Necessary cable alleys, internal wiring, and interlocking,
earthing for all equipment shall also included
Notes:
a. All MCCBs shall be of 35 KA breaking capacity and suitable for
motor duty application.
b. All motor starter shall be provided with Automatic level
controller.
c. Provision shall be made for providing potential free contacts to
all pumps starters for connection to BAS
MCC-1 for STP as described above No. 1 268818 268818
2 CABLE & CABLE TRAYS
2.1 Supplying & laying of following 1100 volt grade PVC
sheathed aluminum copper conductor armoured cables as
per specification in existing trenches, cable trays, ducts over
bed of sand, clamped to wall with suitable clamps, saddles
fixing bolts including connecting testing and commissioning.
a. 4 core 16 sq.mm copper cable LOT 1 17921 17921
b. 4 core 10 sq. mm copper cable LOT 1 14337 14337
c. 4 core 6 sq. mm copper cable LOT 1 11947 11947
Stup Consultants P.Ltd 82 of 234
RATE
(INR)AMOUNT (INR)
Bill of Quantities- STP Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
d. 3 core 4 sq. mm LOT 1 8961 8961
2.2 Supplying & laying of following 1100 volt grade PVC insulated
copper conductor armoured cables as per specification in
existing trenches, cable trays ducts over bed of sand, clamped
to wall with suitable clamps, saddles fixing bolts including
connecting testing and commissioning.
a. 2 core 2.5 sq.mm control cable LOT 1 35842 35842
b. 4 core 2.5 sq.mm control cable LOT 1 23895 23895
2.3 Cable end termination of the following copper conductor
armoured cables of 1100 volt grade including supplying and
fixing of bimettalic crimping lugs, double compression glands
with earthing facility and cable sockets etc. complete as
required.
a. 3 core 16 sq. mm. LOT 1
b. 3 core 10 sq. mm. LOT 1
c. 3 core 6sq. mm LOT 1
d. 3 core 4 sq.mm LOT 1
e. 2 core 2.5 sq.mm control cable LOT 1
f. 4 core 2.5 sq.mm control cable LOT 1
2.4 Supply and fixing of perforated type GI cable trays with
supports, hangers, fastners of the following sizes as per
specification.
a. 200 mm x 40 x 40 x 2 mm thick LOT 1
b. 150 mm x 25 x 25 x 2 mm thick LOT 1
3 EARTHING
Supply and fixing of following bare GI tapes / wires including
all necessary fixing accessories and effecting connections
as per specifications.
a. 25 x 6 mm thick GI strip. LOT 1 11947 11947
b. 8 SWG GI wire LOT 1 9558 9558
TOTAL "B" 529227
85000
41000
Stup Consultants P.Ltd 83 of 234
A ELECTRICAL WORK
I INTERNAL ELECTRICAL 428605261.68
II SUB STATION AND DG SYCHRONIZING PANEL 177801564.07
III EXTERNAL ELECTRICAL WORKS AND LIGHTING 11432000.00
SUB TOTAL ELECTRICAL WORK 617838825.74
B TELECOMMUNICATION SYSTEM
COST OF TELECOMMUNICATION AS PER BOQ 19357800.00
TOTAL COST OF ELECTRICAL AND TELECOMMUNICATION
SYSTEM 637196625.74
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW IN U.P.
SUMMARY SHEET FOR ELECTRICAL AND TELECOMMUNICATION SYSTEM
SUB-
HEADSH. DESCRIPTION TOTAL COST AS PER BOQ
Stup Consultants P.Ltd 84 of 234
I. DISTRIBUTION BOARDS 46,343,926.54
II. SUB MAIN CABLES 31,242,510.00
III. POINT WIRING 91,652,882.00
IV. LIGHT FIXTURES, SENSORS & FANS 39,707,072.00
V. TELEPHONE SYSTEM 10,151,040.00
VI. DATA NETWORKING SYSTEM (PASSIVE COMPONENTS) 7,939,164.00
VII. INTELLIGENT ADDRESSABLE FDA SYSTEM 41,127,799.76
VIII CCTV SYSTEM 11,444,951.39
IX SMATV NIFRA-STRUCTURE 816,380.00
X LIGHTNING PROTECTION SYSTEM 701,840.00
XI EARTHING SYSTEM 3,379,194.00
XII UPS & BATTERIES 16,204,000.00
XIII ACCESS CONTROL SYSTEM 8,097,651.25
XIV QUEUE MANAGEMENT SYSTEM 6,000,000.00
XV ELECTRONIC DISPLAY SYSTEM 222,080.00
XVI CALL BELL SYSTEM 463,750.00
XVII VIDEO PROJECTION & CONFERENCE SYSTEM 5,522,856.00
XVIII SECURITY SYSTEM 2,907,950.00
XIX LIFT 101,400,000.00
XX SOLAR SYSTEM 3,280,214.74
TOTAL 428,605,262
XXI ADVANCED TELECOMMUNICATION SYSTEM 19,357,800.00
TOTAL 19,357,800
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW , U.P.
BILL OF QUANTITY -INTERNAL ELECTRICAL WORKS
SUMMARY OF COST- INTERNAL ELECTRICAL
SUB-HEAD SH. DESCRIPTION
Stup Consultants P.Ltd 85 of 234
RATE (INR) AMOUNT (INR)
I. DISTRIBUTION BOARDS
1.0 MAIN DISTRIBUTION BOARDS & SUB DISTRIBUTION BOARDS
Supply, installation, testing & commissioning of cubicle type totally enclosed free
standing type moisture, dust and vermin proof Main Distribution Boards (MDB) &
Sub Distribuiton Boards (SDB) made out of 2 mm thick CRCA sheet steel
complete with following switchgears and equipments, including ammeter, ammeter
selector switch, voltmeter, voltmeter selector switch, indicating lamps, CT's, internal
wiring with suitable size wires/ cable, interconnection, painting etc as required.
1.1 VENTLATION PANEL -1 , TYPICAL FOR VENTILATION PANEL -2
(TOTAL OF A TO D) 2 Set 1,084,755 2,169,509.40
(A) INCOMER BREAKERS
● 1 No. 1000 Amp FP Manaually Draw out type Air Circuit Breaker of 50KA (Ics
Value) with microprocessor release for O/L, S/C, E/F protection with RS485
Communication port.
(B) INSTRUMENTS
● 1 No. 0 to 500 Volt digital voltmeter (96mm square) with selector switch.
● 1 No. 0 to 1000 Amp digital ammeter (96mm square) with selector switch & CT's.
● 1 Set of multifuction meter with basic parameters like frequency, KW, KVA,
KVAR, Power Factor, harmonics analyser etc. shall be with RS 485 port for
communication and BMS compatible MODBUS output protocol.
● 1 Set of phase indicating lights (RYB) with protection mcb.
● 1 Sets breaker 'ON' & 'OFF' indicating lamps.
(C) BUSBARS
● 1250 Amp TPN busbars of aluminium alloy.
(D) OUTGOING
● 30 Nos. 40-63 Amp FP moulded case circuit breaker 25KA (Ics Value).
1.2 TERRACE PRE VENT PANEL -1 , TYPICAL FOR TERRACE PRE VENT
PANEL -2 (TOTAL OF A TO D)2 Set 246,577 493,153.20
(A) INCOMER BREAKERS
● 1 No. 630 Amp FP Moulded Case Circuit Breaker of 35KA (Ics Value) with
microprocessor release for O/L, S/C, E/F protection with RS485 Communication
port.
(B) INSTRUMENTS
● 1 No. 0 to 500 Volt digital voltmeter (96mm square) with selector switch.
● 1 No. 0 to 630 Amp digital ammeter (96mm square) with selector switch & CT's.
Bill of Quantities- INTERNAL ELECTRICAL Work
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW IN U.P.
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
Stup Consultants P.Ltd 86 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
● 1 Set of multifuction meter with basic parameters like frequency, KW, KVA,
KVAR, Power Factor, harmonics analyser etc. shall be with RS 485 port for
communication and BMS compatible MODBUS output protocol.
● 1 Set of phase indicating lights (RYB) with protection mcb.
● 1 Sets breaker 'ON' & 'OFF' indicating lamps.
(C) BUSBARS
● 800 Amp TPN busbars of aluminium alloy.
(D) OUTGOING
● 1 Nos. 20 Amp FP moulded case circuit breaker 25KA (Ics Value).
● 3 Nos. 32 Amp FP moulded case circuit breaker 25KA (Ics Value).
● 2 Nos. 40 Amp FP moulded case circuit breaker 25KA (Ics Value).
1.3 KITCHEN VENTILATION PANEL (TOTAL OF A TO D)
1 Set 244,873 244,872.90
(A) INCOMING
● 1 No. 250 Amp FP moulded case circuit breaker of (35KA Ics Value) with
Microprocessor release for O/L, S/C & E/F protection.
(B) INSTRUMENTS
● 1 No. 0 -500 Volt voltmeter with selector switch.
● 1 No. 250 Amp Ammeter with selector switch and CT's.
● 1 Set of multifuction meter with basic parameters like frequency, KW, KVA,
KVAR, Power Factor, harmonics analyser etc. shall be with RS 485 port for
communication and BMS compatible MODBUS output protocol.
● 1 Set of phase indicating lights (RYB) with protection mcb.
● 1 Set of Breaker 'ON' & 'OFF' indicating lamp.
(C) BUSBARS
● 300Amp TPN busbars of aluminium alloy.
(D) OUTGOING
● 5 Nos. 160Amp FP moulded case circuit breaker 35KA (Ics Value) .
1.4 L+P SDB- 1 (WING- EAST ) , TYPICAL FOR L+P SDB ( WING-EAST ) -
2,3,4,5,6,7,8,9 & 10 (TOTAL OF A TO D) 40 Set 381,598 15,263,928.00
TYPICAL FOR L+P SDB ( WING -WEST ) 1,2,3,4,5,6,7,8,9 & 10
TYPICAL FOR L+P SDB ( WING -NORTH ) 1,2,3,4,5,6,7,8,9 & 10
TYPICAL FOR L+P SDB ( WING -SOUTH ) 1,2,3,4,5,6,7,8,9 & 10
(A) INCOMING
● 2 No. 160Amp FP moulded case circuit breaker of (35KA Ics Value) with T/M
release for O/L, S/C & E/F protection including electrically & mechanically
interlocking arrangement complete in all respect.
(B) INSTRUMENTS
● 2 No. 0 -500 Volt voltmeter with selector switch.
● 2 No. 160Amp Ammeter with selector switch and CT's.
Stup Consultants P.Ltd 87 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
● 2 No. 96 x 96 square mm digital kilowatt hour meter with RS 485 port for
communication and BMS compatible MODBUS output protocol.
Stup Consultants P.Ltd 88 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
● 2 Set of phase indicating lights (RYB) with protection mcb.
● 2 Set of Breaker 'ON' & 'OFF' indicating lamp.
(C) BUSBARS
● 200 Amp TPN busbars of aluminium alloy.
(D) OUTGOING
● 11 Nos. 40-63Amp FP moulded case circuit breaker 25KA (Ics Value).
1.5 MDB- SERVER INPUT PANEL (TOTAL OF A TO D) 1 Set 1,242,455 1,242,454.50
(A) INCOMING
● 2 Nos. 800Amp FP Manually draw out type Air circuit breaker of (50KA Ics
Value) with microprocessor release for O/L, S/C, E/F protection including
intrlocking arrangemgent complete in all respect.
(B) INSTRUMENTS
● 2 No. 0 -500 Volt voltmeter with selector switch.
● 2 No. 100 Amp Ammeter with selector switch and CT's.
● 2 Set of phase indicating lights (RYB) with protection mcb.
● 2 Set of Breaker 'ON' & 'OFF' indicating lamps.
(C) BUSBARS
● 1250 Amp TPN busbars of copper.
(D) OUTGOING
● 3 No. 630 Amp FP moulded case circuit breaker (35KA Ics Value) with "ON" &
"OFF" indicating lamps.
1.6 MDB- SERVER OUTPUT PANEL (TOTAL OF A TO D)1 Set 490,794 490,794.30
(A) INCOMING
● 3 No. 630 Amp FP moulded case circuit breaker of (35KA Ics Value) with
microprocessor release for O/L, S/C, E/F protection with RS 485 communication
port.
(B) INSTRUMENTS
● 3 No. 0 -500 Volt voltmeter with selector switch.
● 3 No. 300Amp Ammeter with selector switch and CT's.
● 3 No. 96 x 96 square mm digital kilowatt hour meter with RS 485 port for
communication and BMS compatible MODBUS output protocol.
● 3 Set of phase indicating lights (RYB) with protection mcb.
● 3 Set of Breaker 'ON' & 'OFF' indicating lamps.
(C) BUSBARS
● 800 Amp TPN busbars of copper.
(D) OUTGOING
● 4 Nos. 150 Amp FP moulded case circuit breaker (25KA Ics Value).
1.7 MDB- UPS FOR POWER INPUT PANEL (TOTAL OF A TO D)
1 Set 1,398,449 1,398,448.80
(A) INCOMING
Stup Consultants P.Ltd 89 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
● 2 Nos. 800Amp FP Manually draw out type Air circuit breaker of (50KA Ics
Value) with microprocessor release for O/L, S/C, E/F protection including
intrlocking arrangemgent complete in all respect.
Stup Consultants P.Ltd 90 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
(B) INSTRUMENTS
● 2 No. 0 -500 Volt voltmeter with selector switch.
● 2 No. 100 Amp Ammeter with selector switch and CT's.
● 2 No. 96 x 96 square mm digital kilowatt hour meter with RS 485 port for
communication, BMS compatible MODBUS output protocol.
● 2 Set of phase indicating lights (RYB) with protection mcb.
● 2 Set of Breaker 'ON' & 'OFF' indicating lamps.
(C) BUSBARS
● 1250 Amp TPN busbars of copper.
(D) OUTGOING
● 5 Nos. 400 Amp FP moulded case circuit breaker (35KA Ics Value).
1.8 MDB- UPS FOR POWER OUTPUT PANEL (TOTAL OF A TO D)
1 Set 848,403 848,403.00
(A) INCOMING
● 4 Nos. 400Amp FP moulded case circuit breaker of (35KA Ics Value) with
Microprocesor release O/L, S/C, E/F protection.
(B) INSTRUMENTS
● 4 No. 0 -500 Volt voltmeter with selector switch.
● 4 No. 400Amp Ammeter with selector switch and CT's.
● 4 No. 96 x 96 square mm digital kilowatt hour meter with RS 485 port for
communication, BMS compatible MODBUS output protocol.
● 4 Set of phase indicating lights (RYB) with protection mcb.
● 4 Set of Breaker 'ON' & 'OFF' indicating lamps.
(C) BUSBARS
● 800 Amp TPN busbars of copper.
(D) OUTGOING
● 5 Nos. 400 Amp FP moulded case circuit breaker (35KA Ics Value).
1.9 MDB-UPS ( WING - EAST ) TYPICAL FOR MDB-UPS ( WING- WEST,
NORTH & SOUTH ) (TOTAL OF A TO D) 4 Set 418,040 1,672,160.40
(A) INCOMING
● 1 No. 400Amp FP moulded case circuit breaker of (35KA Ics Value) with
Microprocessor release for O/L, S/C, E/F protection.
(B) INSTRUMENTS
● 1 No. 0 -500 Volt voltmeter with selector switch.
● 1 No. 400Amp Ammeter with selector switch and CT's.
● 1 No. 96 x 96 square mm digital kilowatt hour meter with RS 485 port for
communication, BMS compatible MODBUS output protocol.
● 1 Set of phase indicating lights (RYB) with protection mcb.
● 1 Set of Breaker 'ON' & 'OFF' indicating lamps.
(C) BUSBARS
● 500 Amp TPN busbars of copper.
Stup Consultants P.Ltd 91 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
Stup Consultants P.Ltd 92 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
(D) OUTGOING
● 13 Nos. 40 Amp FP moulded case circuit breaker (25KA Ics Value).
1.10 USDB-GF (WING - EAST ) TYPICAL FOR USDB- 1F,2F,3F,4F,5F,6F,7F,8F
& 9F (TOTAL OF A TO D) 40 Set 148,261 5,930,424.00
TYPICAL FOR USDB ( WING -WEST ) - GF, 1F,2F,3F,4F,5F,6F,7F,8F & 9F
TYPICAL FOR USDB ( WING -NORTH ) - GF, 1F,2F,3F,4F,5F,6F,7F,8F &
9F
TYPICAL FOR USDB ( WING -SOUTH ) - GF, 1F,2F,3F,4F,5F,6F,7F,8F &
9F
(A) INCOMING
● 1 No. 40 Amp FP moulded case circuit breaker of (25KA Ics Value) with T/M
release for O/L, S/C, E/F protection.
(B) INSTRUMENTS
● 1 No. 0 -500 Volt voltmeter with selector switch.
● 1 No. 40Amp Ammeter with selector switch and CT's.
● 1 No. 96 x 96 square mm digital kilowatt hour meter with RS 485 port for
communication, BMS compatible MODBUS output protocol.
● 1 Set of phase indicating lights (RYB) with protection mcb.
● 1 Set of Breaker 'ON' & 'OFF' indicating lamps.
(C) BUSBARS
● 100Amp TPN busbars of Copper.
(D) OUTGOING
● 6 Nos. 32 Amp FP moulded case circuit breaker (25KA Ics Value).
1.11 SDB - LOWER BASEMENT ( TYPICAL FOR UPPER BASEMENT )
2 Set 148,261 296,521.20
(A) INCOMING
● 1 No. 63 Amp FP moulded case circuit breaker of (25KA Ics Value) with T/M
release for O/L, S/C, E/F protection.
(B) INSTRUMENTS
● 1 No. 0 -500 Volt voltmeter with selector switch.
● 1 No. 63Amp Ammeter with selector switch and CT's.
● 1 No. 96 x 96 square mm digital kilowatt hour meter with RS 485 port for
communication, BMS compatible MODBUS output protocol.
● 1 Set of phase indicating lights (RYB) with protection mcb.
● 1 Set of Breaker 'ON' & 'OFF' indicating lamps.
Stup Consultants P.Ltd 93 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
(C) BUSBARS
Stup Consultants P.Ltd 94 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
● 100Amp TPN busbars of AL alloy.
(D) OUTGOING
● 6 Nos. 32 Amp FP moulded case circuit breaker (25KA Ics Value).
1.12 SERVICE LIFT PANEL , TYPICAL FOR PASSENGER LIFT PANEL -1 &
2 (TOTAL OF A TO D) 3 Set 282,758 848,272.50
(A) INCOMING
● 2 Nos. 160 Amp FP moulded case circuit breaker of (35KA Ics Value) with T/M
release for O/L, S/C, E/F protection.
● 2 No. 160Amp FP (AC -3 ) Power Contactor with interlocking arrangement
complete in all respect..
(B) INSTRUMENTS
● 2 No. 0 -500 Volt voltmeter with selector switch.
● 2 No. 160Amp Ammeter with selector switch and CT's.
● 1 No. 96 x 96 square mm digital kilowatt hour meter with RS 485 port for
communication, BMS compatible MODBUS output protocol.
● 2 Set of phase indicating lights (RYB) with protection mcb.
● 2 Set of Breaker 'ON' & 'OFF' indicating lamps.
(C) BUSBARS
● 2 Nos 200 Amp TPN busbars of aluminium alloy.
(D) BUS COUPLER
● 1 No. 160Amp FP moulded case circuit breaker of 35KA (Ics Value) with
interlocking arrangement between incomers & bus coupler breaker.
(E) OUTGOING
● 8Nos. 63 Amp TP moulded case circuit breaker of 25KA (Ics Value) with neutral
link
2.0 MOULDED CASE CIRCUIT BREAKER IN SS ENCLOSURE
Supply installation, testing and commissioning of Moulded Case Circuit Breaker in
sheet steel enclosure made out of 2mm thick, suitable for 3 phase 4 wire 50 Hz AC
supply complete with incoming/outgoing terminations, internal connections/ links
etc as required.
(i) 63Amp Four Pole 4 No. 16,780 67,118.40
3.0 Supplying, installing on wall, testing and commissioning of following capacity Air
Insulated Compact Type Rising Mains for use on 3 phase 4 wire 415 volts, 50Hz
A.C. supply with enclosure made of 1.6mm thick steel sheet duly powder coated in
convenient sections complete with 4 Nos aluminium bus bars, necessary joints &
expansion joints, fire barrier at each floor, provision of tapping at every metre,
continuous earthing with 2 Nos aluminium strip of suitable size (one on each side)
including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to
earthing system etc. as required.
(i) 800 amps 50KA SC for 1 sec 400 M. 12,072 4,828,800.00
Stup Consultants P.Ltd 95 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
Stup Consultants P.Ltd 96 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
4.0 Supplying, installing, connecting to existing Air Insulated Compact Type bus
trunking/ rising mains, testing and commissioning of following capacity Plug In/
Tap Off Box for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with 1.6mm
thick steel sheet enclosure duly powder coated with provision of MCCB (but
without MCCB) complete etc. as required.
(i) 125 amps 15KA SC for 1 sec 4 No. 4,611 18,444.00
(ii) 250 amps 30KA SC for 1 sec 80 No. 7,518 601,440.00
5.0 Supplying, installing, connecting to existing Air Insulated Compact Type bus
trunking/ rising mains, testing and commissioning of following capacity End Feed
Unit for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick
steel sheet enclosure duly powder coated with provision of MCCB/ACB (but
without MCCB/ACB) complete with necessary joints including clamping brackets,
angle iron bracket, steel fasteners, connecting to earthing system etc. as required.
(i) 800 amps 50KA SC for 1 sec 8 No. 8,457 67,656.00
6.0 Supply & fixing of following rating four pole MCCB in the existing Tap OFF &
End Feed Unit box complete with commissioning of testing and common as
required. connection
(i) 800 Amps FP MCCB (50 KA) with energy analyser shall be with RS485 port for
communication and BMS compatible MODBUS output protocol. 8 No. 174,930 1,399,440.00
(ii) 125 Amps FP MCCB (25 KA) 4 No. 27,820 111,280.00
(iii) 160 Amps FP MCCB (35 KA) 80 No. 27,820 2,225,600.00
7.0 DISTRIBUTION BOARDS
7.1 Supplying and fixing following way, single pole and neutral, sheet steel, MCB
distribution board, 240 volts, on surface/ recess, complete with tinned copper bus
bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including
earthing etc. as required. (But without MCB/RCCB/Isolator)
(i) 2 + 12 way, Double door 44 No. 1,344 59,136.00
(ii) 2 + 8 way, Double door 2 No. 1,132 2,264.00
7.2 Supplying and fixing following way, horizontal type TP&N MCB distribution board
of steel sheet for 415 volts on surface/ recess complete with tinned copper bus bar,
neutral link, earth bar, din bar, interconnections, powder painted including earthing
etc. as required. (But without MCB/ RCCB/ Isolator)
(i) 12 way (4 + 36), Double door 48 No. 5,313 255,024.00
(ii) 8 way (4 + 24), Double door240 No. 3,148 755,520.00
(iii) 6 way (4 + 18), Double door 200 No. 2,636 527,200.00
Stup Consultants P.Ltd 97 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
7.3 Supplying and fixing of following ways surface/ recess mounting, vertical type, 415
volts, TPN MCB distribution board of sheet steel, dust protected, duly powder
painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth
bar, din bar for mounting MCB’s (but without MCB’s and incomer) as required.
(Note :- Vertical type MCB TPDB is normally used where 3 phase outlets are
required.)
(i) 4 way (4 + 12), Double door 4 Set 4,478 17,912.00
7.4 Providing and fixing following rating and breaking capacity and pole MCCB in
existing cubicle panel board including drilling holes in cubicle panel, making
connections, etc. as required.
(i) 100Amp, 30KA, FP MCCB 4 No. 5,347 21,388.00
7.5 Supplying and fixing following rating, double pole, (single phase and neutral), 240
volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300
milliamperes in the existing MCB DB complete with connections, testing and
commissioning etc. as required.
(i) 40 Amp 1366 No. 1,714 2,341,324.00
(ii) 63 Amp 144 No. 2,237 322,128.00
7.6 Supplying and fixing following rating, four pole, (three phase and neutral), 415
volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300
milliamperes in the existing MCB DB complete with connections, testing and
commissioning etc. as required.
(i) 63 Amp 2 No. 2,294 4,588.00
(ii) 40 Amp 2 No. 2,123 4,246.00
7.7 Supplying and fixing following rating, four pole, 415 volts, isolator in the existing
MCB DB complete with connections, testing and commissioning etc. as required.
(i) 40 Amps 440 No. 659 289,960.00
(ii) 63 Amps 48 No. 670 32,160.00
7.8 Supplying and fixing following rating, double pole, 240 volts, isolator in the existing
MCB DB complete with connections, testing and commissioning etc. as required.
(i) 40 Amps 46 No. 218 10,028.00
7.9 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, “C” curve, miniature
circuit breaker suitable for inductive load of following poles in the existing MCB
DB complete with connections, testing and commissioning etc. as required.
(i) Single pole 8076 No. 169 1,364,844.00
(ii) Triple pole 16 No. 696 11,136.00
7.10 Supplying and fixing single pole blanking plate in the existing
MCB DB complete etc. as required. 2452 No. 6 14,712.00
Stup Consultants P.Ltd 98 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
7.11 Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand )
R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm
nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone
aggregate 40mm nominal size) inside plastering 12mm thick with cement mortar 1:3 (1
cement : 3 coarse sand) finished with floating coat of neat cement and making channels in
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal
size) finished with a floating coat of neat cement complete as per standard design :
Inside size 1200x90 cm and 90cm deep including C.I. cover with frame (medium duty) 500
mm internal diameter total weight of cover and frame to be not less than 116 kg (weight of
cover 58 kg and weight of frame 58 kg)
i With Sewer bricks conforming to IS : 48852 No 18,808 37,616.00
ii Extra for depth for manholes : 300 mm2 No 2,218 4,435.80
Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610
mm internal dimensions total weight of cover and frame to be not less than 38 kg (weight
of cover 23 kg and weight of frame 15 kg)
iii With Sewer bricks conforming to IS : 48854 No 8,691 34,765.00
iv Extra for depth for manholes : 750 mm2 No 4,631 9,261.96
v Extra for depth for manholes : 450 mm2 No 2,779 5,557.18
TOTAL FOR MAIN DISTRIBUTION BOARDS, SUB DISTRIBUTION
BOARD & DISTRIBUTION BOARDS CARRIED OVER TO SUMMARY
46,343,926.54
II. SUB MAIN CABLES
1.0 Wiring for circuit/ submain wiring along with earth wire with the following sizes of
FRLS PVC insulated copper conductor, single core cable in surface/ recessed
medium class PVC conduit as required.
i) 2 X 10 sq. mm + 1 X 10 sq. mm earth wire 10 M 327 3,270.00
ii) 2 X 6 sq. mm + 1 X 6 sq. mm earth wire 10 M 221 2,210.00
iii) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire 10 M 162 1,620.00
iv) 4 X 6 sq. mm + 2 X 6 sq. mm earth wire 25 M 389 9,725.00
v) 4 x 10 sq.mm + 2 x 10 sq.mm earth wire. 25 M 597 14,925.00
vi) 4 x 16 sq.mm + 2 x 16 sq.mm earth wire. 25 M 883 22,075.00
Stup Consultants P.Ltd 99 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
2.0 Supply of following size of 1.1KV grade multicore copper conductor XLPE
insulated & PVC sheathed armoured cable as per IS: 7098 (Part-1) 1988 complete
as required.
i) 4 core, 400 Sq.mm. 720 M 18,251 13,140,720.00
ii) 1 core, 240 Sq.mm. ( Flexible ) 240 M 2,594 622,560.00
iii) 1 core, 185 Sq.mm. ( Flexible ) 480 M 2,012 965,760.00
iv) 4 core, 25 Sq.mm. 3000 M 1,183 3,549,000.00
v) 4 core, 16 Sq.mm. 2300 M 763 1,754,900.00
vi) 4 core, 10 Sq.mm. 3540 M 529 1,872,660.00
vii) 4 core, 6 Sq.mm. 14280 M 339 4,840,920.00
viii) 2 core, 10 Sq.mm. 200 M 301 60,200.00
ix) 2 core, 6 Sq.mm. 200 M 199 39,800.00
3.0 Supply of following size of 1.1KV grade multicore aluminium conductor XLPE
insulated & PVC sheathed armoured cable as per IS: 7098 (Part-1) 1988 complete
as required.
i) 3.5 core, 95 Sq.mm. 1200 M 498 597,600.00
4.0 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power
cable of 1.1 KV grade of following size on Cable Tray as required.
i) Upto 35 sq. mm (clamped with 1mm thick saddle) 24270 M 20 485,400.00
ii) Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
1200 M 48 57,600.00
iii) Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
480 M 59 28,320.00
iv) Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
960 M 91 87,360.00
5.0 Suppling and making indoor end termination with brass compression gland and
aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE
aluminium conductor cable of 1.1 KV grade as required.
i) 3.5 core, 95 Sq.mm. 160 Set 324 51,840.00
6.0 Suppling and making indoor end termination with brass compression gland and
copper lugs for following size of PVC insulated and PVC sheathed / XLPE copper
conductor cable of 1.1 KV grade as required.
i) 4 core, 400 Sq.mm. 16 Set 5,650 90,400.00
ii) 4 core, 25 Sq.mm. 40 Set 300 12,000.00
iii) 4 core, 16 Sq.mm. 56 Set 280 15,680.00
iv) 4 core, 10 Sq.mm. 228 Set 220 50,160.00
v) 4 core, 6 Sq.mm. 440 Set 220 96,800.00
vi) 2 core, 10 Sq.mm. 4 Set 210 840.00
vii) 2 core, 6 Sq.mm. 4 Set 210 840.00
Stup Consultants P.Ltd 100 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
7.0 Suppling and making indoor end termination with PVC gland and copper lugs for
following size of PVC insulated and PVC sheathed / XLPE copper conductor cable
of 1.1 KV grade as required.
i) 1 core, 240 Sq.mm. 48 Set 750 36,000.00
ii) 1 core, 185 Sq.mm. 96 Set 600 57,600.00
8.0 Supply and installing following size of perforated Pre- Painted M.S. cable trays
with perforation not more than 17.5% in convenient sections, joints with connectors
suspended from the ceiling with M.S. suspenders and including bolts & nuts,
painting suspenders etc. as required.
i) 100 mm width X 50 mm depth X 1.6 mm thickness 250 M 461 115,250.00
i) 150 mm width X 50 mm depth X 1.6 mm thickness 500 M 520 260,000.00
ii) 300 mm width X 50 mm depth X 1.6 mm thickness 250 M 789 197,250.00
i) 450 mm width X 50 mm depth X 2 mm thickness 200 M 1,117 223,400.00
ii) 600 mm width X 50 mm depth X 2 mm thickness100 M 1,386 138,600.00
ii) 900 mm width X 75 mm depth X 2 mm thickness50 M 2,038 101,900.00
9.0 Supply and installing following size of perforated Galvanised cable trays with
perforation not more than 17.5% in convenient sections, joints with connectors
suspended from the ceiling with suspenders and including bolts & nuts, painting
suspenders etc. as required.
i) 100 mm width X 50 mm depth X 1.6 mm thickness 500 M 576 288,000.00
i) 150 mm width X 50 mm depth X 1.6 mm thickness 500 M 650 325,000.00
ii) 300 mm width X 50 mm depth X 1.6 mm thickness 250 M 986 246,500.00
i) 450 mm width X 50 mm depth X 2 mm thickness 250 M 1,396 349,000.00
ii) 600 mm width X 50 mm depth X 2 mm thickness 100 M 1,732 173,200.00
ii) 900 mm width X 75 mm depth X 2 mm thickness 50 M 2,547 127,350.00
10.0 Supply , installation balancing & commissioning of fabricated at site GSS sheet
metal rectangular/ round ducting complete with neoprene rubber gasket , elbows ,
spillter damper , vans , hanger , support etc as per approved drawing & speification
of following sheet thickness complete as required .
i) Thickness 0.63 mm sheet 25 Sqmtr 605 15,125.00
i) Thickness 0.8 mm sheet 25 Sqmtr 728 18,200.00
i) Thickness 1.0 mm sheet 50 Sqmtr 949 47,450.00
11.0 Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in
ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2
fine sand) including trenching (75 cm deep) and refilling etc as required.
i) 150 mm dia 50 M 384 19,200.00
Stup Consultants P.Ltd 101 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
ii) 300 mm dia 50 M 566 28,300.00
Stup Consultants P.Ltd 102 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
TOTAL OF SUB MAIN CABLES CARRIED OVER TO SUMMARY. 31,242,510.00
III. POINT WIRING
1.0 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm
FRLS PVC insulated copper conductor single core cable in surface / recessed
medium class PVC conduit, with modular switch, modular plate, suitable GI box
and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor
single core cable etc as required.
(i) Group-C 12614 Pt. 718 9,056,852.00
2.0 Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper
conductor single core cable in surface / recessed medium class PVC conduit, 2 way
modular switch, modular plate, suitable GI box and earthing the point with 1.5
sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.
86 Pt. 770 66,220.00
3.0 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of
FRLS PVC insulated copper conductor, single core cable in surface/ recessed
medium class PVC conduit as required0
(i) 2 x 1.5 Sq.mm. + 1 x 1.5Sq.mm earth wire 75950 M. 106 8,050,700.000
(ii) 4 x 1.5 Sq.mm. + 2 x 1.5Sq.mm earth wire 34050 M. 166 5,635,275.000
4.0 Supply and wiring of following MCB control light point with 2.5 sq.mm PVC
insulated multistranded single core copper conductor cable (FRLS type) in PVC
conduit recessed and/or on surface including chasing of wall, filling of chases with
cement mortar 1:3 mix and providing 24 SWG G.I. chicken wire mesh & fixing with
nails etc. and/or fixing conduit on surface of wall/ceiling/purpose made MS support
channel including PVC insulated copper earth wire, PVC connector, tee cover,
surface or deep tee etc. complete as required. (Cost of MCB paid under DB item)
i) Single / First Point 110 1,000 110,000.00
ii) Looping Point (Average length 8 Mtrs. Approx.) 974 800 779,200.00
5.0 Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper
conductor single core cable in surface/ recessed medium class PVC conduit
alongwith 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cable
for loop earthing as required.
165540 M. 162 26,817,480.00
6.0 Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper
conductor single core cable in surface/ recessed medium class PVC conduit
alongwith 2 Nos 4 sq. mm FRLS PVC insulated copper conductor single core cable
for loop earthing as required. 112560 M. 275 30,954,000.00
7.0 Supplying and fixing suitable size GI box with modular plate and cover in front on
surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket
outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to
be used in non residential buildings).
5912 No. 303 1,791,336.00
Stup Consultants P.Ltd 103 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
8.0 Supplying and fixing suitable size GI box with modular plate and cover in front on
surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular
socket outlet and 15/16 amps modular switch, connection etc. as required.
1954 No. 395 771,830.00
9.0 Supply, installation, testing & commissioning of under floor cross over box of size
250mm x 250mm x 60-75mm one trap 3 compartment with metal lid and suitable
for 225mm / 75mm x 25mm depth three/ single compartment metal ducting /
trunking / raceway made out of high pressure die- cast zinc alloy complete with all
accessories such as top cover base support frame, base support stud etc. complete as
required.
80 No. 2,850 228,000.00
10.0 Supply, installation, testing & commissioning of following size of Access Outlet
Box made out of high pressure die cast material with Trap lid made of galvanised
iron (GIE). Trap frame openable by pulling stainless steel hinged type with leveling
secrews & trap door made of 2.5mm thick pre galvanised steel plate with 8mm
recess. The Access Outlet Box epoxy coated & suitable for mounting of modular
type light & power accessories & for connecting to three compartment PVC Wall
trunking v ia PVC Conduit under floor raceway complete as required.
300mm x 300mm x 60 mm-75mm. (1 Trap 3 Compartment) - (Metal Lid) 80 No. 3,200 256,000.00
11.0 Supply and fixing of following sizes single/triple compartment under floor/ Vertical
trunking made out of 1.6mm thick hot dip galvanised sheet steel complete with all
accessories and fixing accessories as per site requirement all as required &
specified.
i) 225mm x 38mm x 1.6mm (3 compartment) 400 M 1,840 736,000.00
ii) 225mm x 25mm x 1.6mm (3 compartment) 600 M 1,770 1,062,000.00
iii) 75mm x 38mm x 1.6mm (single compartment) 2000 M 760 1,520,000.00
12.0 Supply, Installation, Testing & Commissioning of 3 compartment PVC wall cable
management system complete with main carrier, strraight cover, armed cover, and
all accessories to make the system complete as required (similar/ Equivalent to to
MK - Prestige 3D System).
1500 M 500 750,000.00
Note :- The Cable Management System shall be laid on linear basis & linear
Length paid shall deemed to include cost of tees, bends, joints etc. complete as
required.
13.0 Supplying and fixing following size/ modules, GI box along with modular base &
cover plate for modular switches in recess etc as required.
(i) 1 or 2 Module (75 mmX75mm) 5960 No. 166 989,360.00
(ii) 3 Module (100mmX75mm) 2870 No. 175 502,250.00
(iii) 4 Module (125mmX75mm) 200 No. 195 39,000.00
(iv) 6 Module (200 mmX75mm) 2910 No. 248 721,680.00
(iv) 8 Module (125mmX125mm) 100 No. 287 28,700.00
(v) 12 Module (200mmX150mm) 50 No. 334 16,700.00
Stup Consultants P.Ltd 104 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
14.0 Supplying and fixing stepped type electronic fan regulator on the existing modular
plate switch box including connections but excluding modular plate etc. as required.
2636 No 284 748,624.00
15.0Supplying and fixing modular blanking plate on the existing modular plate & switch
box excluding modular plate as required. 100 No 23 2,300.00
16.0
Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2
pole and earth, metal enclosed plug top along with 20 amps \"C\" curve, SP, MCB,
in sheet steel enclosure, on surface or in recess, with chained metal cover for the
socket out let and complete with connections, testing and commissioning etc. as
required. 10 No 954 9,540.00
17.0
Supply and fixing 20 amps, 415 volts, TPN industrial type socket outlet with 4 pin
and earth metal enclosed plug top alongwith 20Amps 'C' curve TP MCB in sheet
steel enclosure on surface or in recessed with chained metal cover for the socket
outlet and complete with connection, testing commissioning as required.
5 No 1,967 9,835.00
TOTAL FOR POINT WIRING CARRIED OVER TO SUMMARY 91,652,882.00
IV. LIGHT FIXTURES, SENSORS & FANS
1.0 Supply of 4 x 14 W T5 recess mounted fluorescent light fixture complete with
lamps, electronic driver & all accessories as required of Wipro Cata. Ref. WVF
14414SGW or approved equivalent.
4675 No. 4,750 22,206,250.00
2.0 Supply of 6W LED recess mounted light fixture complete with lamps, electronic
driver & all accessories as required of Wipro Cata. Ref. LD 71 -151 or approved
equivalent. 3577 No. 2,150 7,690,120.00
3.0 Supply of 2 x 28 W T5 type suface / wall mounted fluorescent light fixture
complete with lamp, electronic ballast & all accessories as required of Wipro Cata.
Ref. WIF 20228 or approved equivalent.
469 No. 1,600 750,720.00
4.0 Supply of 1 x 28 W T5 type suface / wall mounted fluorescent light fixture
complete with lamp, electronic ballast & all accessories as required of Wipro Cata.
Ref. WIF 20128 or approved equivalent.
938 No. 1,240 1,163,616.00
5.0 Supply, installation, testing and commissioning of 1x18 watt CFL wall recessed step
light fixture complete with lamps mounting box with electronics ballast and all
accessories as required of WIPRO Cat Ref. FSP 42118 (Fantasy step light) or
approved equivalent.
102 No. 2,040 208,080.00
6.0 Light band complete with all accessories as required Equiv to Phillips- model
Trugroove OR Pharox 31 Mtr. 7,500 0.00
7.0
Recessed Ceiling lights complete with all accessories as required Equiv to Thorn
Archiline 6 No. 8,000 0.00
8.0
Suspended Ceiling lights (Cafe area) complete with all accessories as required
Equiv to Phillips/ Wipro as approved by Architect/ Engineer In Charge 22 No. 9,000 0.00
9.0 Supply, Installation, Testing & Commissioning of 1 x 14 watt T5 balten light fixture
with diffuser and decorative end caps complete with all accessories as required of
Havells Cata. Ref. E-LITE Maglev DLX.337 No. 570 191,862.00
Stup Consultants P.Ltd 105 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
10.0 Supply, Installation, Testing & Commissioning of 1 x 8 watt CFL surface mounted
bulkhead light fixture complete with all accessories complete as required of Havells
Cata. Ref. RUGBY or approved equivalent.
238 No. 540 128,520.00
11.0 Supplying, erection, testing and commissioning of Aviation obstruction lights with
LED lamp with flasher 170mm suitable for 230V AC complete with fitting
including photochromatic switch for automatic ON/OFF of Aviation lights complete
as per Bajaj Cata. No. BGAV 302 LED with Neon Lamp or approved equivalent.
2 No 7,000 14,000.00
12.0 Wiring for Aviation light with 3 core 2.5 sq.mm PVC insulated PVC sheathed
copper conductor armoured cable from Ground Floor DB to Aviation light as
required. 128 M 150 19,125.00
13.0 Supply of following sizes of energy saver ceiling fan without regulator complete
with double ball bearing, motor, blades, downrod, canopy, capacitor etc. complete
as required.
(i) Sweep 900 mm 2210 No. 2,170 4,795,700.00
(ii) Sweep 1200 mm 36 No. 2,180 78,480.00
14.0 Supply of following sizes of heavy duty exhaust fan complete suitable for operation
on 220V, 50Hz, single Phase AC Supply with all accessories such as, motor, blade,
MS Powder Coated louvre shutter, capacitor etc. including all fixing accessories as
required.
(i) 300mm dia, 1400 RPM.14 No. 3,370 47,180.00
15.0 Installation, testing and commissioning of pre-wired, fluorescent fitting / compact
fluorescent fitting of all types, complete with all accessories and tube etc. directly on
ceiling/ wall, including connection with 1.5 sq. mm FRLS PVC insulated, copper
conductor, single core cable and earthing etc. as required.
1044 No. 91 94,985.80
16.0 Installation, testing and commissioning of pre-wired, fluorescent fitting / compact
fluorescent fitting of all types, complete with all accessories and tube etc. including
supply & fixing ball & socket arrangement, 2 Nos down rod of 20mm dia X 1.6
mm thick steel conduit up to 30 cm length , painting & wiring the down rods &
connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core
cable and earthing etc. as required.938 No. 233 218,647.20
17.0 Providing & fixing extra conduit down rod of 20 mm dia 2 X 10 cm length wiring
with 2x 1.5 sq mm FRLS PVC insulated copper conductor single core cable
including painting etc as required. ( NOTE : More than 5 cm length shall be rounded
to the 10 cm & 5 cm or less shall be ignored.)
938 No. 31 29,090.40
18.0 Installation, testing and commissioning of pre-wired, fluorescent fitting / compact
fluorescent / LED fitting of all types, complete with all accessories and tube etc. in
recess including connection with 1.5 sq.mm FR PVC insulated, copper conductor,
single core cable and earthing etc. as required.
7749 No. 113 875,591.80
19.0 Installation testing and commissioning of ceiling fan including wiring the down
rods of standards length ( up to 30 cm ) with 1.5 sq.mm FRLS PVC insulated
copper conductor single core cable etc as required.
2241 No 95 212,857.00
Stup Consultants P.Ltd 106 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
20.0 Supplying and fixing extra down rod of 10 cm length G.I. pipe ,15 mm dia, heavy
gauge including painting etc. as required. (Note : More than 5 cm length shall be
rounded to the nearest 10 cm and 5 cm or less shall be ignored).
85 Each 23 1,955.00
21.0 Installation of exhaust fan in the existing opening, including making good the
damage, connection, testing, commissioning etc. as required.
(i) Upto 450 mm sweep 14 Each 204 2,856.00
22.0 Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all
sizes. 14 Each 90 1,260.00
23.0 Supply & fixing of call bell/buzzer suitable for single phase 230 volts complete as
required. 40 Each 61 2,440.00
24.0 Numbering of ceiling fan / exhaust fan / flouresent fitting as required,
11983 Each 26 311,565.80
25.0 Supplying, installation, testing & commissioning of the factory built Inverter system
of following rating suitable for 230 volts single phase 50Hz. 4 wire A.C. supply
input and also 230 volts single phase 50Hz 4 wire A.C. Supply output, capable of
continuously delivering the 100% rated power, with proper LCD display Indication
panel. The output power factor shall not be less than 0.8 The system shall be
complete with 150AH lead acid maintenance free batteries suitable for 1 Hours
back up and all connections/ inter-connections etc. complete as required.
(i) 1.0 KVA 4 No 18,290 73,160.00
26.0 LIGHTING CONTROLS
Supply,Installation, testing and commissioning of Scene Select control system
complete with the following items / accessories :-
4 No 115,000 460,000.00
Scene Select wall Unit (Panle) of MK cata Ref. MLS 2000 SSP
Cover Plate White of MK cata Ref. MSS PWHT
Hand hold programmable unit 2 way commuinication of MK cata Ref. K4053
Hand held remote unit 10 Button control of MK cata Ref. K4052
MLS Universal bus trans receiver MK cata Ref. K4640
27.0 Supplying, installation, testing and commissioning of Passive Infrared (PIR)
technology based occupancy sensor having high performance, non regulating
programmable type, suitable for connected load upto 10Amp , for mounting height
up to 2.8 mtr and for 5 m diameter coverage area along with necessary fixing
arrangements i/c programming at site etc. complete as required.
10 No. 3,173 31,730.00
Stup Consultants P.Ltd 107 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
28.0 Supplying, installation, testing and commissioning of Microwave technology based
occupancy sensor having high preformance, non regulating programmable type,
suitable for connected load upto 10Amp, for mounting height up to 2.6 mtr and for
5m X 20m coverage area along with necessary fixing arrangements i/c programming
at site etc. complete as required.
16 No. 6,080 97,280.00
TOTAL OF LIGHT FIXTURES & FANS CARRIED OVER TO
SUMMARY. 39,707,072.00
V. TELEPHONE SYSTEM
1.0 Supplying and fixing of following sizes of medium class PVC conduit along with
accessories in surface/recess including cutting the wall and making good the same in
case of recessed conduit as required.
i) 20mm dia 25000 M. 53 1,325,000.00
ii) 25mm dia 15000 M. 65 975,000.00
2.0 Supplying and fixing of following modular switch / socket on the existing modular
plate & switch box including connections but excluding modular plate etc. as
required.
i) Telephone socket outlet 2890 No. 95 274,550.00
3.0 Supplying and fixing following size / modules, GI box alongwith modular base &
cover plate for modular switches in recess etc. as required.
i) 1 or 2 Module (75mm x 75mm) 2890 No. 166 479,740.00
4.0 Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed
copper conductor, unarmored telephone cable in the existing surface/ recessed steel/
PVC conduit as required.
i) 2 Pair 13180 M. 18 237,240.00
ii) 4 Pair 69770 M. 27 1,883,790.00
5.0 Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed
copper conductor, armored telephone cable in the existing surface/ recessed steel/
PVC conduit as required.
i) 10 Pair 200 M. 140 28,000.00
ii) 30 Pair 150 M. 360 54,000.00
iii) 50 Pair 200 M. 450 90,000.00
iv) 100 Pair 2400 M. 820 1,968,000.00
v) 150 Pair 100 M. 1,270 127,000.00
vi) 500 Pair 200 M. 3,500 700,000.00
vii) 1000 Pair 200 M. 6,500 1,300,000.00
6.0 Supply installation and testing and commissioning of follwing size of Telephone
distribution board in a M.S. box with hinged cover/ door complete with krone type
tag block with double jumpering facility mounted on a bakelite sheet etc. including
terminations of cable as required.
i) 10 Pair telephone distribution board 6 No. 1,220 7,320.00
ii) 30 Pair telephone distribution board 2 No. 3,460 6,920.00
iii) 50 Pair telephone distribution board 2 No. 4,410 8,820.00
Stup Consultants P.Ltd 108 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
iv) 100 Pair telephone distribution board 1 No. 10,060 10,060.00
Stup Consultants P.Ltd 109 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
v) 150 Pair telephone distribution board 40 No. 14,890 595,600.00
vi) 500 Pair telephone distribution board 4 No. 7,500 30,000.00
vii) 1000 Pair telephone distribution board 4 No. 12,500 50,000.00
7.0 Supply, installation, testing and commissioning of 32 Bit RISC Processor based
Telephone Exchange with System Management Terminal, Universal Auto Attendent
Facilities, configured for 4 P & T Lines/40 Extensions expandable with following
features:
4 No. 75,000 300,000.00
Dial by name facility
100% Non Blocking ISDN Exchange
Q Signalling Compliant
Remote maintenance
Automatic Call Distribution/ Universal Call Distribution In built
Voice Over IP Compatibility
Least Cost Routing
Computer Telephony Integration Interface
Digital Enhanced Cordless Telephony
20 Party Conferencing
Hot standby for CPU, RGU & Power
8.0 Supply, installation, testing and commissioning of Operator Console with minimum
100 keys.
4 No. #VALUE! 0.00
9.0 Providing, installation, testing and commissioning of Digital key Telephone.
1 No. 15,000 15,000.00
Digital Key Phone with 2 line Display and 8 free keys).
Speaker Phone with 8 flexible Keys
CTI interface (optional)
Low Power Consumption
LCD Display Type (24 x 2) Character
10.0 Providing, installation testing and commissioning of Analog Phone with CLI display
complete as required.1 No. 1,800 1,800.00
TOTAL OF TELEPHONE SYSTEM CARRIED OVER TO SUMMARY. 10,151,040.00
VI. DATA NETWORKING SYSTEM (PASSIVE COMPONENTS)
1.0 Supply, installation, testing & commissioning of following cables.
Stup Consultants P.Ltd 110 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
Stup Consultants P.Ltd 111 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
i) Supply & drawing of UTP 4 Pair CAT 6 cable in the existing surface/ recessed
steel/ PVC conduit as required . 82000 M. 33 2,706,000.00
2.0 Supply, installation, testing & commissioning of following Jack Panel.
i) 24 Port Powersum CAT 6 Jack Panel. 120 No. 8,363 1,003,560.00
3.0 Supply, installation, testing & commissioning of wall mounting cabinets (19 inch
depth) equipped with one door made of tinted glass, top and bottom cable entry
plates, ventilation grills at sides, color white RAL 9002 to be supplied with earthing
kit of following sizes :-
i) 6U capacity cabinet 30 No. 17,200 516,000.00
ii) 12U capacity cabinet 4 No. 22,100 88,400.00
iii) 15U capacity cabinet 1 No. 25,100 25,100.00
4.0 Supply, installation, testing & commissioning of free standing (floor mounted)
cabinets equipped with reversable door made of tinted glass, reversable metal rear
door, ventilation grills on all sides, cable entry on top and bottom color white RAL
9002 to be supplied with earthing kit of following sizes :-
i) 42U capacity cabinet 1 No. 118,400 118,400.00
5.0 Supply, installation, testing & commissioning of following RJ-45 connectivity.
i) Simplex Faceplate with RJ-45, information outlet with shutter compliant to TIA
568A/B with colour coding. 2448 No. 347 849,456.00
6.0 Supply and fixing metal box of following sizes (nominal size) on surface or in
recess with suitable size of phenolic laminated sheet cover in the front including
painting etc. as required.
i) 200mm x 250mm x 75mm deep. 80 No. 261 20,880.00
7.0 Supplying and fixing following size / modules, GI box alongwith modular base &
cover plate for modular switches in recess etc. as required.
i) 1 or 2 Module (75mm x 75mm) 2448 No. 166 406,368.00
8.0 Supplying and fixing of following sizes of medium class PVC conduit along with
accessories in surface/recess including cutting the wall and making good the same in
case of recessed conduit as required.
i) 20mm dia 25000 M 53 1,325,000.00
ii) 25mm dia 12000 M 65 780,000.00
9.0 Supply, installation, testing & commissioning of 50/125, MM, OM3, 6 Core,
Outdoor Fiber Cable complete as per specification & as required. 200 M 500 100,000.00
TOTAL OF DATA NETWORKING SYSTEM (PASSIVE COMPONENT)
CARRIED OVER TO SUMMARY. 7,939,164.00
VII. INTELLIGENT ADDRESSABLE FDA SYSTEM
1.0 Supply and fixing of following sizes of steel conduit alongwith the accessories in
surface/recess including painting in case of surface conduit or cutting the wall and
making good the same incase of recessed conduit as required.
i) 20mm dia 12000 M. 121 1,452,000.00
Stup Consultants P.Ltd 112 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
ii) 25mm dia 6000 M. 142 852,000.00
2.0 Supplying and drawing following sizes of FRLS PVC insulated copper conductor,
single core cable in the existing surface/ recessed steel/ PVC conduit as required.
i) 2 x 1.5 sq.mm. 27000 M. 36 972,000.00
3.0 Supply and fixing of the following fire detection and alarm accessories complete
with connections etc. as required.
i) Addressable Fire alarm, hooter cum strobe
44 No. 7,120 313,280.00
ii) Electronic Response indicator in aluminium housing. 497 No. 1,000 496,800.00
4.0 Supply, installation, testing and commissioning of Analogue addressable control
module complete with termination etc. as required.
80 No. 6,113 489,037.50
5.0 Supply, installation, testing and commissioning of fault/loop isolator module
complete with all accessiores as required. (to be used after every 20 detectors if
required). 1 No. 6,792 6,792.19
6.0 Supply & fixing of the following Analog addressable fire detection & alarm
accessories complete with connections etc. as required.
i) Supply, installation, testing and commissioning of Manual Call point (break glass
type). Manual Call point shall be made of ABS plastic, square in surface flash
mounting with mounting base and required accessories. It shall have a brak glass
message embossed on glass. The addressable module shall be enclosed alongwith
break glass in junction box.
36 No. 4,890 176,053.50
ii) Supply, installation, testing and commissioning of addressable multi criteria (Photo
+ Thermal) detector complete with inbuilt isolator with detector mounting base and
required accessories.
1740 No. 6,400 11,136,000.00
iii) Supply, installation, testing and commissioning of addressable Beam Detectors
with manual and 2 aclimate sensitivity settings, transmitter / receiver built into same
unit, Six user - selectable sensitivity levels 16' to 328' protection range, digital
display, built in automatic gain control compensates for signal deterioration from
dust builtup address switch to programme the detectors, complete as required.
10 Set 64,040 640,400.00
iv)
Supply, installation, testing and commissioning of Addressable Duct mounted
smoke detectors with unique optical sensing chamber, complete as required.
(Including cost of Smoke Detector)
10 No 23,093 230,934.38
v) Intelligent Thermal Heat Detectors with thermistors, rate of rise model, visible
LED's, addressable by device, suitable for 2 wire loop connection, built-in temper-
resistance feature, plug into separate base and housing constructed of LEXAN (or
poly carbonate) as required and as per specification.
1215 No. 5,410 6,573,150.00
Stup Consultants P.Ltd 113 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
9.0 Supply, installation, testing and commissioning of Intelligent Fire Detection &
Alarm panel of following loops in network connected to sensors, sounders, manual/
addressable pull station and operating as stand alone system and connected to
network of control module, in station working on 230 volt,50 Hz/24 VDC power
supply. Panel shall be completely field programmable and shall be complete with
Central Processing Unit (CPU), Display interface assembly DIA), Loop interface
board (LIB), Serial interface board (SIB) 30 key keypad, 80 character LCD display
with LED Backlite, History Events-10000, main power supply, 24volts DC
maintenance free battery and battery charger etc. and shall be complete as required
and shall be UL listed/Vds.
i) 10 loops (Expandable) panel. 6 Set 1,290,520 7,743,120.00
10.0 Supply, installation, testing and commissioning of Repeater Panel with 160
character backlit LCD display, functional keys like acknowledge, signal silence,
system reset, lamp test etc. complete as required.
3 Set 129,052 387,154.69
11.0 PUBLIC ADDRESS, EMERGENCY EVACUATION AND BACKGROUND
MUSIC SYSTEM
Paging Microphone ( Make/Model : Bosch LBB1956/00 or Equivalent)
Supply, Installation, Testing & Commissoning of Plena Voice Alarm Call Station
having gooseneck condenser microphone with six zone Selection Keys and an All-
Call-Key, PTT Switch, selectable gain, speech filter and limiter for improved
intelligibility, LED indication for zone selection, fault and emergncy state.
4 Set 30,312 121,248.70
Controller ( Make/Model : Bosch LBB1990/00 or Equivalent)
Supply Installation, Testing & Commissoning of Plena Voice Alarm Controller
having features like announcement to six zones expandable to 60 zones, built in
240W booster amplifier, emergency microphone on the front panel, 16 priority
levels including emergency, music to selected zones can be played, upto 255
messages can be stored in the internal 16MB flash ROM, individual BGM volume
control for each zone, Digital pre-recorded messages can be merged, full system
supervision,
1 Set 100,205 100,205.14
Power Amplifier ( (Make / Model : Bosch LBD1938/00 or Equivalent)
Supply, installation, testing & commissioning of Plena Booster Amplifier capable
of delivering 480W RMS power output, built-in fan for temperature control,built in
line matching transformer distortion typically 0.03% @ 1 KHz, Hum and Noise 90
dB below rated output. (Bosch Cat. No. LBD 1938 or Equivalent)
65 Set 37,342 2,427,235.75
6W RMS ceiling Speaker with built in 100V LMT.( (Make / Model : Bosch LBD
0606/10 or Equivalent)3500 Set 932 3,261,608.44
Stup Consultants P.Ltd 114 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
Stup Consultants P.Ltd 115 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
6W RMS cabinet Wall Mount Speaker with built in 100V LMT.( (Make / Model :
Bosch LBD 3902 or Equivalent)
678 Set 1,341 909,047.36
12 W Volume control for office cabins.( (Make / Model : Bosch LBC 1400/10 or
Equivalent)160 Set 2,907 465,129.00
DVD / CD Player for Background Music (Make / Model : Philiphs / Samsung /
Sony or Equivalent) 1 Set 129,052 129,051.56
Equipmet Rack
19" Equipment rack for housing above mentioned control equipments.(
(Make/Model : Custom or Equivalent)) 1 Set 129,052 129,051.56
Wiring ( (Make/Model : Delton / Skytone or Equivalent)
48/0.2 mm two core twin twisted speaker cable.25000 M 84 2,100,000.00
Supply & drawing of UTP 4 Pair CAT 6 cable in the existing surface/ recessed
steel/ PVC conduit as required . 500 M 33 16,500.00
NOTE :- PA system shall be intregated with FDA system by the system
intregrator. Automatic changeover to PA system in case of fire.
0 0.00
TOTAL OF INTELLIGENT ADDRESSABLE FDA SYSTEM CARRIED
OVER TO SUMMARY.
41,127,799.76
VIII
.
CCTV SYSTEM
1.0 Supply of 960H/ Equivalent analog indoor/ outdoor color dome camera. IP66; IK08;
12VDC/24VAC; DWDR; varifocal 2.8 to 10.5 mm lens; electronic day/night; 720
TVL; 3-axis adjustment; 4-zone motion detect; 4-zone privacy mask; PAL with
power supply
120 No 26,795 3,215,421.56
2.0 Supply of 960H/ Equivalent analog box camera. True day/night; DWDR; 720 TVL;
3-axis adjustment; 4-zone motion detect; 8-zone privacy mask; 230VAC; PAL with
960H varifocal IR-corrected lens. 1/3" sensor; CSmount; 4-pin DC-iris; F1.4-360; 5
to 50 mm, for camera/lens up to 262 mm (10.3 in.), 230 VAC, 50/60 Hz, heater,
blower, sunshield, outside BNC connector and outside power connector with pole
mount adaptor
18 No 91,705 1,650,697.18
3.0 Supply, installation, testing and commissioning of outdoor Pole/wall mounted day
light IP 66 rated PTZ Color dome camera 540 TV lines 360 degree continuous
rotation with 36 X Optical and 12 X digital zoom including power supply, Pole &
bracket as required.
9.6 No 294,203 2,824,346.73
Stup Consultants P.Ltd 116 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
4.0 Supply, installation, testing and commissioning of following channel Digital Video
recorder with 2 video outputs having 500 GB Hard Disk facility recording @ 25
frames per second with TCP/IP Connectivity as per secification required.4/8/16
Channel
16 Channel 8 No 169,528 1,356,224.86
8 Channel 6 No 155,210 931,261.06
5.0 Supply, installation, testing and commissioning of Central Monitoring Station
capable of handling ----------- cameras with PC as per the specifications.
1 No 100,000 100,000.00
6.0 Supply, installation, testing and commissioning of 21" inches high resolution LED
monitor.6 No 30,000 180,000.00
7.0 Supply, installation, testing & commissioning of power supply units for following
channels required for above cameras.
1 Channel30 No 600 18,000.00
2 Channel 50 No 600 30,000.00
4 Channel 20 No 750 15,000.00
6 Channel10 No 1,000 10,000.00
12 Channel 10 No 1,500 15,000.00
8.0 Supply, installation, testing & commissioning of following size cable for CCTV
camera in existing conduit complete with all accessories as required.
RG - 6
5000 M 28 140,000.00
RG - 112000 M 52 104,000.00
9.0 Supplying and fixing of following sizes of medium class PVC conduit along with
accessories in surface/recess including cutting the wall and making good the same in
case of recessed conduit as required.
20 mm4000 M 53 212,000.00
25 mm1000 M 65 65,000.00
10.0 Supplying and drawing following sizes of FRLS PVC insulated copper conductor,
single core cable in the existing surface/ recessed steel/ PVC conduit as required.
2 x 1.5 sq.mm. 7500 M. 36 270,000.00
Stup Consultants P.Ltd 117 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
11.0 Supplying, installation, testing & commissioning of the factory built UPS system of
following rating suitable for 230 volts single phase 50Hz. 4 wire A.C. supply input
and also 230 volts single phase 50Hz 4 wire A.C. Supply output, capable of
continuously delivering the 100% rated power, with proper LCD display Indication
panel. The output power factor shall not be less than 0.8 The system shall be as per
detailed specifications and shall be complete with all connections/ inter-connections
etc. complete as required.
1.5 KVA4 No 15,000 60,000.00
3 KVA4 No 40,000 160,000.00
12.0 Supplying, Installation testing and commissioning of Lead Acid sealed maintenance
free batteries suitable for 15 minutes backup in suitable numbers and Ampere Hour
capacity for the system given above in Sl. No. 11 complete with stand for stacking
the batteries, alongwith connection, interconnection etc. with suitable size copper
conductor cables. complete as required.
1.5 KVA 4 No 7,000 28,000.00
3 KVA4 No 15,000 60,000.00
### Analytical Software1 SET 100,000 100,000.00
TOTAL OF CCTV SYSTEM CARRIED OVER TO SUMMARY.
11,444,951.39
IX SMATV NIFRA-STRUCTURE
1.0 Supplying and fixing of following sizes of medium class PVC conduit along with
accessories in surface/recess including cutting the wall and making good the same in
case of recessed conduit as required.
20 mm 4500 M 53 238,500.00
2.0 Supply, installation, testing & commissioning of Splitter Box suitable for
following number of ways cosisting of power supply, step down transformer
rectifiers, display indicator console omplete as per specification and as required.
2 Way 40 No 1,500 60,000.00
4 Way 80 No 2,500 200,000.00
3.0 Supplying and fixing following size / modules, GI box alongwith modular base &
cover plate for modular switches in recess etc. as required.
1 or 2 Module (75mm x 75mm) 252 No 166 41,832.00
4.0 Supplying and fixing following modular switch/ socket on the existing modular
plate & switch box including connections but excluding modular plate etc. as
required.
Stup Consultants P.Ltd 118 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
TV antenna socket outlet 252 No 94 23,688.00
5.0 Supplying and fixing metal box of following sizes (nominal size) on surface or in
recess with suitable size of phenolic laminated sheet cover in front including
painting etc as required.
200 mm X 300 mm X 100 mm deep 40 No 309 12,360.00
6.0 Supplying and drawing co-axial TV cable RG-6 grade, 1.02 mm solid copper
conductor PE insulated, shielded with fine tinned copper braid and protected with
PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.
400 M 30 12,000.00
7.0 Supplying and drawing co-axial TV cable RG-59 grade, 0.8 mm solid copper
conductor PE insulated, shielded with fine tinned copper braid and protected with
PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.
12000 M 19 228,000.00
TOTAL OF SMATV SYSTEM CARRIED OVER TO SUMMARY. 816,380.00
X LIGHTNING PROTECTION SYSTEM
1.0 Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm
long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base
plate including holes etc. complete as required. 32 Each 369 11,808.00
2.0 Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any
other metallic object) by riveting / nut bolting/ sweating and soldering etc as
required. 960 Each 72 69,120.00
3.0 Providing and fixing GI tape 20mm x 3 mm thick on parapet or surface of wall for
lightning conductor complete as required. (For horizontal run)
3000 M. 68 204,000.00
4.0 Providing and fixing GI tape 20mm x 3 mm thick on parapet or surface of wall for
lightning conductor complete as required. (For vertical run) 1800 M. 98 176,400.00
5.0 Providing and fixing testing joint made of 20mm x 3mm thick GI strip 125mm long
with 4No. G.I. bolts, nuts, chuck nuts, spring washer etc. complete as required.
32 Each 71 2,272.00
6.0 Providing and laying G.I. Tape 32mm x 6mm from earth electrode directly in
ground as required. 160 M 141 22,560.00
7.0 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including
accessories, and providing masonry enclosure with cover plate having locking
arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as
required.32 Set 4,490 143,680.00
8.0 Providing and fixing B-class 50mm dia GI pipe (nominal) complete with GI fittings
including trenching and refilling etc. 160 M 450 72,000.000 0.00
TOTAL OF LIGHTNING PROTECTION SYSTEM CARRIED OVER TO
SUMMARY. 701,840.00
XI EARTHING SYSTEM
Stup Consultants P.Ltd 119 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
1.0 Earthing with copper earth plate 600mm x 600mm x 3mm thick including
accessories and providing masonary enclosure with cover plate having locking
arrangement and watering pipe etc.(with charcoal or coke and salt) complete as
required. 4 Set 9,292 37,168.00
2.0 Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth
electrode including connection with G.I. nut, bolt, spring, washer excavation and re-
filling etc. as required. 20 M 1,082 21,640.00
3.0 Providing and fixing 25 mm x 5 mm copper strip on surface or in recess for
connections etc. as required.600 M 856 513,600.00
4.0 Providing and fixing earth bus of 50 mm x 5 mm copper strip on surface for
connections etc. as required. 800 M 1,599 1,279,200.00
5.0 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including
accessories, and providing masonry enclosure with cover plate having locking
arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as
required. 10 Set 4,490 44,900.00
6.0 Earthing with G.I. earth pipe 4.6 Metre long , 40 mm dia including accessories, and
providing masonry enclosure with cover plate having locking arrangement and
watering pipe etc. with charcoal/ coke and salt as required.
6 Set 3,926 23,556.00
7.0 Supply Installation, Testing & Commissioning of earth pits material using
ISOGEL earth enhanced compound of 20 kgs, ISOROD advanced chemical
earth rod made with 'K' type copper tube of 2.5" dia, 8 ft long, 1.6mm thick
installed vertically complete with flanges bends top cover PCC cover on brick
masonary chamber including excavation and refilling etc complete in all respect.
2 set 45,000 90,000.00
8.0 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth
electrode including connection with G.I. nut, bolt, spring, washer excavation and re-
filling etc. as required. 80 M 391 31,280.00
9.0 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for
connections etc. as required. 675 M 142 95,850.00
10.0 Supply & Wiring of following sizes of single core insulated copper conductor earth
wire / cable as required.
10 sq.mm earth wire. 100 M 90 9,000.00
16 sq.mm earth wire. 150 M 120 18,000.00
25 sq.mm earth wire. 300 M 150 45,000.00
11.0 Providing and fixing 50 mm X 5 mm G.I. strip on surface or in recess for
connections etc. as required. 2600 M 450 1,170,000.00
TOTAL OF EARTHING CARRIED OVER TO SUMMARY. 3,379,194.00
XII UPS & BATTERIES
1.0 Supply, Installation, Testing & Commissioning of 200 KVA IGBT Based Online
UPS (3 Phase ) input & three phase output with 15Minutes backup, fully digital and
microprocessor controlled with following key features : -
- Input of 415V, + 15%,
Stup Consultants P.Ltd 120 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
Stup Consultants P.Ltd 121 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
- output voltage 415 + 1%,
- Frequency - 50Hz +5 %
- Inbuilt static bypass and manual maintenance bypass.
- Input phase sequence correction.
- Emergency backfeed protection circuitry as standard.
- Input Power Factor > 0.99
- Hermonics less than 5% with out using additional filters .
- Isolation Transformer at Inverter Output
- Parallel kit for Parallel operation
- Sealed maintenance free (smf) batteries for 15 minutes back-up with full 200 KVA
load complete with battery racks, interconnecting links & in-built DC Isolator with
fuse protection. 4 Set 2,541,800 10,167,200.00
2.0 Supply, Installation, Testing & Commissioning of 225 KVA IGBT Based Online
UPS (3 Phase ) input & three phase output with 15Minutes backup, fully digital and
microprocessor controlled with following key features : -
- Input of 415V, + 15%,
- output voltage 415 + 1%,
- Frequency - 50Hz +5 %
- Inbuilt static bypass and manual maintenance bypass.
- Input phase sequence correction.
- Emergency backfeed protection circuitry as standard.
- Input Power Factor > 0.99
- Hermonics less than 5% with out using additional filters .
- Isolation Transformer at Inverter Output
- Parallel kit for Parallel operation
- Sealed maintenance free (smf) batteries for 15 minutes back-up with full 225 KVA
load complete with battery racks, interconnecting links & in-built DC Isolator with
fuse protection. 2 Set 3,018,400 6,036,800.00
TOTAL OF UPS & BATTERIES CARRIED OVER TO SUMMARY. 16,204,000.00
XIII ACCESS CONTROL SYSTEM
1.0 Supplying and fixing of following sizes of medium class PVC conduit along with
accessories in surface/recess including cutting the wall and making good the same in
case of recessed conduit as required.
20 mm 2000 M 53 106,000.00
Stup Consultants P.Ltd 122 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
2.0 Supply, Installation, Testing & Commissioning of Access Intelligent Controller
support 4 standard Weigand Interface or up to 8 serial interface on RS 485 bus
technology , 8 Input & 8 Output port as per the specification with enclosure , power
supply ,& Maintenance free Batteries with 30 minutes back up . The controller
should be minimum 32 bit embedded microprocessor chip and on board TCP /IP as
per the Specification..The Controller Should have minimum of 2 GB of flash
Memory , can store 2 Lakh Card holder Access profile & 4 lakhs transaction in
offline mode. The Controller should have a 16-characters liquid crystal display
(LCD), and a button provided for selective display to show all its network
parameters and actual status like - IP address of the controller; MAC address of the
controller as per the specification Controller Should be UL 294, FCC, CE,EN as per
the specification
0 0.00
0 0.00
To Control 4 Access card reader (Bosch model no. APC-AMC-4WCF or
Equivalent) 10 No. 152,274 1,522,743.75
3.0 Supply, Installation, Testing & Commissioning of Exit button / emergency release
switch on protected side of room area complete as required. 40 No. 6,404 256,162.50
4.0 Supply, installation, testing and commissioning of Finger print(Biometrics) readers
with keypad & Smart card reader inbuilt having 5000 user template suitable for
mounting on metal surface / metal frames or wooden frames or wall or as required
based on site conditions including all accessories.
40 No. 98,196 3,927,825.00
5.0 Supply, Installation, Testing & Commissioning of Electro-magnetic lock complete
as required.
For Single Leaf door (One Lock) 40 No. 7,116 284,625.00
For Double Leaf door (Two Locks) 10 No. 18,501 185,006.25
6.0 Supply, Installation, Testing & Commissioning of Access Control System Server
Software consisting of Access Control system , Visitor management with all
employee visitor license, Elevetor Control , Guard Tour Management , Mantrap ,
Alarm Document , Alarm management , 2 client License , Graphical layout ,
integration with CCTV .All these along with high end security features consist in
single package as per specification 1 No. 925,031 925,031.25
7.0 Supply, Installation, Testing & Commissioning of Smart card with printed photo ID
and printed lenyard complete as required. 50 No. 569 28,462.50
8.0 Supply, Installation, Testing & Commissioning of 2 Core x 1.5 Sqmm Shielded
Cable complete as required. 2,400 M 228 546,480.00
9.0 Supply, Installation, Testing & Commissioning of 8 Core x 0.75 Sqmm Shielded
Cable complete as required. 1,200 M 256 307,395.00
10.0 Supply, installation, testing & commissioning of following cables.
11.0 Supply & drawing of UTP 4 Pair CAT 6 cable in the existing surface/ recessed
steel/ PVC conduit as required . 240 M 33 7,920.00
Note :- Any other item required to complete stand alone access control system
(for one door only) shall be deemed to be included in quoted rates above.
Stup Consultants P.Ltd 123 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
TOTAL OF ACCESS CONTROL SYSTEM CARRIED OVER TO
SUMMARY. 8,097,651.25
Stup Consultants P.Ltd 124 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
XIV QUEUE MANAGEMENT SYSTEM
1.0 Supply, installation, testing & commissioning of Queue Management System with
the following Components
Token Dispenser -cum- Queue Controller with 2 ISSUE key and thermal printer
with automatic cutter housed in powder coated MS Kiosk, 3 Feet high for printing
and issuing new token slip- 1 No.
No.
Counter Desk Units with CALL key for calling next token number Qty-6 Nos. No.
Local Counter Desk Display Units for displaying token number under service Qty.(2
Groups)- 6 Nos.No.
Multi-row Central LCD / LED Display Unit for displaying token number with
corresponding counter number for waiting area- 1 No.No.
Converter unit with PC Software for Showing Token Number with Corresponding
counter number on LCD monitor- 1 No.No.
Interconnecting Cable & Connector- 150 Mtrs. M
2.0 Supplying and fixing of following sizes of medium class PVC conduit along with
accessories in surface/recess including cutting the wall and making good the same in
case of recessed conduit as required.
20 mm- Lot M
3.0 Supplying and fixing of following sizes of Steel conduit along with accessories in
surface/recess including cutting the wall and making good the same in case of
recessed conduit as required.
25mm dia- Lot M.
4.0 Any other consequential and incidental work which become requisite through
not specifically mentioned in the specification or shown in the drawing which
required by the legistation or obviously necessary for the successary
completion and satisfactory operation of the entire installation. If none is
required, please write NIL otherwise full details of the item are to be given :-
TOTAL FOR QUEAUE MANAGEMENT SYSTEM 1.0 Lot 6,000,000 6,000,000.00
XV ELECTRONIC DISPLAY SYSTEM
1.00 Supply, installation, testing & commissioning of 42 Inch LED TV for Electronic
Display system 2 Set
50,000 100,000.00
2.00 Supply, installation, testing & commissioning of Compact & sleek Digital Sinage
Media Player, Pre-loaded with software as per following minimum technical
requirement
1 Set
100,000 100,000.00
1 Ghz Processor,
512 MB Ram
Stup Consultants P.Ltd 125 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
2 GB Hard Disk Drive
Stup Consultants P.Ltd 126 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
3.00 Supply, installation, testing & commissioning of VGA Splitter cable adaptor, (Y
type, 2 Monitor to 1 PC) suitable to broadcast simultaneously one VGA signal upto
2 different monitor / TV at same time.
1 No.
5,000 5,000.00
4.00 Supply & drawing of UTP 4 Pair CAT 6 cable in the existing surface/ recessed
steel/ PVC conduit as required .10 M
33 330.00
5.00Supply & Drawing of Twisted pair cable in existing conduit / under floor trunking 100 M
70 7,000.00
6.0 Supplying and fixing of following sizes of medium class PVC conduit along with
accessories in surface/recess including cutting the wall and making good the same in
case of recessed conduit as required.
20 mm 50 M 53 2,650.00
7.0 Supplying and fixing of following sizes of Steel conduit along with accessories in
surface/recess including cutting the wall and making good the same in case of
recessed conduit as required.
25mm dia 50 M. 142 7,100.00
8.00 Any other consequential and incidental work which become requisite through
not specifically mentioned in the specification or shown in the drawing which
required by the legistation or obviously necessary for the successary
completion and satisfactory operation of the entire installation. If none is
required, please write NIL otherwise full details of the item are to be given :-
TOTAL FOR ELECTRONIC DISPLAY SYSTEM 222,080.00
XVI INFRASTRUCTURE FOR CALL BELL SYSTEM
1.0 Supplying and fixing of following sizes of medium class PVC conduit along with
accessories in surface/recess including cutting the wall and making good the same in
case of recessed conduit as required.
20 mm 3750 M 53 198,750.00
25 mm 2000 M. 65 130,000.00
2.0 Supply and drawing of following pair 0.5mm diameter FRLS PVC Insulated
annealed copper conductor unarmoured telephone cable in existing surface/recess
Steel/ PVC conduit complete as required.
2 Pair 7500 M 18 135,000.00
TOTAL FOR INFRASTRUCTURE FOR CALL BELL SYSTEM
CARRIED OVER TO SUMMARY. 463,750.00
XVII VIDEO PROJECTION & CONFERENCE SYSTEM
VIDEO PROJECTION SYSTEM
Stup Consultants P.Ltd 127 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
1.0 4000 ANSI Lumen Projector - 3 LCD, 1200 x 800 WXGA resolution, Aspect ratio :
16 : 9 , 3000: 1 contrast ratio, 245UHP lamp, Motorized zoom, focus & lens shift,
picture by picture. ( Make / Model : Chirstie LW 401 ) 4 No. 385,540 1,542,160.00
2.0 Motorized 133" Diagonal Matt White Screen with IR Remote Control, Aspect ratio :
16 : 9 (Make / Model : Liberty / Snow White ) 4 No. 71,160 284,640.00
3.0 Presentation point with 1 x HDMI, 1 x VGA, 1 x Audio, 2 x Power, 1 x data, 1 x
LAN at Stage for connecting laptop on Stage / Podium.(Make / Model : Custom)
4 No. 19,410 77,640.00
4.0 Switcher with 4 HDMI inputs , 2 VGA inputs, 2 composite and 2 component Video
inputs, single ouptput : 1 x HDMI, 1 X VGA, Control − RS−232 & IR(Make /
Model : Kramer VP-438) 4 No. 155,250 621,000.00
5.0 DVD player with USB(Make / Model : Sony ) 4 No. 9,060 36,240.00
6.0 Cable & Accessories
20 Mtrs HDMI to HDMI cable in existing conduit (Reputed) 8 Set 12,940 103,520.00
1 Mtrs HDMI to HDMI Patch Cord (Reputed) 8 Set 1,553 12,424.00
20 Mtrs VGA Cable with audio cable in existing conduit (Reputed) 4 Set 7,763 31,052.00
3 core 1.5 sqmm Power cable (Delton or Equivalent) 400 M. 97 38,800.00
Miscellaneous Patch cords, Connectors, adaptors, Projector Mount etc. 4 Lot 19,406 77,624.00
VIDEO CONFERENCE AND PRESENTATION SYSTEM FOR
CONFERENCE ROOM
Video Conferenec System
7.0 Video conference system with SD camera, HD Codec, 720p, up to 4 mbps and RF
remote control, upgradable to MCU (1+5) sites, camera : 1/4-type color CCD,
Image Sensor : 440,000 pixels, 10 X optical zoom, 4 X with digital zoom, Pan/Tilt
Angle Pan±100°/Tilt±25° .(Make / Model : Sony PCS-G60)
4 Set 410,120 1,640,480.00
8.0 Professional 55" LED display, Full HD (1920 x 1080) reolsution , Panel Backlit :
Edge LED, Brightness 450 cd / m sq, 20W Speaker. (Make / Model : Panasonic TH-
55VMT60DM ) 4 No. 219,940 879,760.00
9.0 Pop up Presentation Point with 1 x HDMI, 1 x VGA, 2 x audio (Left, Right) , 1 x
Power, 2 x RJ 45 for LAN. Durable pneumatic movement and mechanical latching
mechanism, terminal box will automatically prop up at 45°.(Make / Model :
Liberty) 4 No. 19,406 77,624.00
10.0 Cable & Accessories
10 Mtrs HDMI to HDMI cable in existing conduit (Reputed) 4 Set 10,350 41,400.00
2 Mtrs HDMI to HDMI Patch Cord Reputed) 4 Set 3,623 14,492.00
10 Mtrs VGA Cable with audio cable in existing conduit (Reputed) 4 Set 4,530 18,120.00
Stup Consultants P.Ltd 128 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
Miscellaneous Patch cords, Connectors , adaptors, Mic cable, Power cable etc.
4 Lot 6,470 25,880.00
TOTAL OF VIDEO PROJECTION SYSTEM CARRIED OVER TO
SUMMARY 5,522,856.00
XVIII SECURITY SYSTEM
1.0 Supply , installation, testing and commissioning of High Speed Electro mechanical
barrier for continuous use for vechicular span of up to 4.5 mtrs, includes 90x25mm
boom with rubber gasket for anti scratch, controller, flange, springe, base
plate&fork reset IP44 rating. Opening Closing Time Approximately 2.5 Sec, 100%
duty cycle complete with Blinking Light and Epoxy painted. ( Boom Barrier)
2 Nos. 190,000 380,000.00
2.0 Supply , installation, testing and commissioning of Micro processsor based access
control system engineered with 32 bit CPU to cater to the multiple Readers and
Multiple locations , Expandable, TCP/IP protocol compatible disributed
Intelligence, Supporting Two Readers, and having flash memeory , can be
expandable card data base upto 55000 cards and transaction buffer of 45000
transction, 128 accesss level , 127 time zone Levels, 8 supervised inputs and 4 Nos
of relay outputs for easy and reliable interface with the 3rd party systems. Complete
with Digital Power supply etc as required. Model: Pro- 3000. ( Access System
Controller)1 Nos. 93,500 93,500.00
3.0 Supply , installation, testing and commissioning of Single User Software Plateform
pioneer in integrating Video, access control and Intrusion detection Systems.The
Software is capable of managing the users from multiple locations,Real time event /
alarm Monitoring, Schedule Guard Tour feature , Model: Win Pack. ( Access
System Software) 1 No. 580,000 580,000.00
4.0 Supply, installation, testing & commissioning of PC with DVD Drive and 1 TB
HDD, 21" LCD Monitor and required Keyboard, Adapter for Ethernet networking
,compatible with TCP/IP network protocols with a minimum bandwidth of
100Mbps along with Microsoft Windows software OS complete in all respects as
per specifications. 1 set 75,000 75,000.00
4 Gigabyte of RAM memory
1 TB Gigabytes of hard disk space
DVD Combo Drive
21” LCD colour monitor
Optical Mouse with 2 Mouse Pads
Multimedia Keyboard
10/100/ 1000 MBPS PCI LAN onboard card.
5.0 Supply , installation, testing and commissioning of Long Range Proximity Reader
suitable for external / Internal environment applications with a Read range of 16"
(44cm) ( Barrier Access Reader) 2 Nos. 48,000 96,000.00
6.0 Supply, installation, testing & commissioning of HID 34-bit Proximity Access
Card. Standard HID proximity card with slot hole punch on the short side for badge
clips (BC-1). And with printing of details of Card Holder
3 No. 350 1,050.00
Stup Consultants P.Ltd 129 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
Stup Consultants P.Ltd 130 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
7.0 Supply and Installation , programming of Long range Vehicle Tags 2 No 300 600.00
8.0 Supply , installation, testing and commissioning of Photocell based safety device to
avoid closing of the barrier when a Vehicle is crossing the barrier. ( Anti Fall
Protection) 2 set 12,800 25,600.00
9.0 Supply , installation, testing and commissioning of Twin Channel Exit Push putton
for open close with green and red Buttons. 2 Nos. 1,350 2,700.00
10.0 Supply, installation, testing and commissioning of Ground Loop
Magnetic detector for automatic closing of the entry / exit barriers
complete as required. 2 Nos. 12,000 24,000.00
11.0 Supply of Floor Mountable padestal to mount the Proximity Reader. ( Reader
Mount ) 2 Nos. 2,000 4,000.00
12.0 Supply and Laying of 3x1.5 sq mm stranded Copper Conductor power Cable
100 RM 75 7,500.00
13.0 Supply and laying of Reader Cable 8Cx.5sqmm 100 RM 180 18,000.00
14.0 Supply , installation, testing and commissioning of Connectors, interfaces,
Mounting hardware, Cords, Jacks, Plugs,tags, identifiers, fixures, clamps, screws,
nut - bolts etc as required for the installation and commissioning.. ( Installation)
2 sets 300,000 600,000.00
15.0 Any other consequential and incidental work which become requisite through
not specifically mentioned in the specification or shown in the drawing which
required by the legistation or obviously necessary for the successary
completion and satisfactory operation of the entire installation. If none is
required, please write NIL otherwise full details of the item are to be given :-
1,000,000.00
TOTAL SECURITY SYSTEM CARRIED OVER TO SUMMARY. 2,907,950.00
XIX LIFT
1.1 Design, manufacture, supply, installation, testing, commissioning and
handing over in satisfactory working condition of lifts including the cost of
providing free comprehensive (Including the cost of spares, consumables
etc.) maintenance for two years after handing over complete as per
specifications, as required and as below.
1.2 Passenger Lift with 26 passengers capacity, 1.5 mps speed, ACVVVF
control, Full Collective Operation with 25 mm recess in floor for stone (300
kg) finish by Owners.
12 stops (Basement-2 to Terrace Floor) all on same side, travel 50 mtrs . 12 Nos. 3,500,000 42,000,000.00
1.3 Passenger Lift with 8 passengers capacity, 1.0 mps speed, ACVVVF control,
Full Collective Operation with 25 mm recess in floor for stone (300 kg)
finish by Owners.
3 stops (Basement-2 to Ground Floor) all on same side, travel 10 mtrs
simplex operation. 1 Nos. 1,600,000 1,600,000.00
Stup Consultants P.Ltd 131 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
1.4 Passenger Lift with 8 passengers capacity, 1.5 mps speed, ACVVVF
control, Full Collective Operation with 25 mm recess in floor for stone (300
kg) finish by Owners.
12 stops (Basement-2 to Terrace Floor) all on same side, travel 50 mtrs
simplex operation. 1 Nos. 2,000,000 2,000,000.00
1.5 Service Lift with 20 passengers capacity, 1.5 mps speed, ACVVVF control,
Full Collective Operation with 25 mm recess in floor for stone (300 kg)
finish by Owners.
12 stops (Basement-2 to Terrace Floor) all on same side, travel 50 mtrs
simplex operation. 4 Nos. 3,200,000 12,800,000.00
Not
e :
Vendor must work out and indicate the quantities of interior finishes and quote
accordingly for all the options as mentioned under. Contractor to quote for all options.
However, Rates quoted by him in item nos. 1.1, 1.2, 1.3, 1.4 and 1.5 shall include amount
of Option-A.
1 CEILING
Opti
on A
Silver coloured anodized aluminium with mirror finish
Opti
on B
Indirect lighting through milky-white sheet in painted steel ceiling.
Opti
on C
Indirect lighting through crystal acrylic blocks in painted steel sheet ceiling plate.
Opti
on D
Perforated metal Ceiling tiles
2 WALLS AND DOORS
Opti
on A
Front wall of cabin doors in brushed stainless steel, side and rear walls etched stainless
steel, to architects choice.
Opti
on B
Plastic laminated steel sheet in approved colour
Opti
on C
Stainless steel etching pattern finish.
3 FLOOR
Opti
on A
Lift supplier provide 20 mm recess and lift supplier to coordinate with marble / wooden
flooring supplier for fixing.
Stup Consultants P.Ltd 132 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
Opti
on B
Durable vinyl tiles 2 mm thick.
4 ENTRANCE COLUMN
Opti
on A
Stainless steel sheet
Opti
on B
Integrated type with front return panel
5 KICK PLATE
Opti
on A
Stainless steel sheet.
Opti
on B
Painted steel sheet
6 SILL
Opti
on A
Stainless steel
Opti
on B
Extruded hard aluminium
7 VENTILATION
Opti
on A
Electric blower with rear-side vents
Opti
on B
Electric blower with plastic grille.
Not
e :
i. Option, colour, shade, pattern and other finishes will be decided by the Architect and
all approvals will be taken from him before starting fabrication.
ii. Contractor to quote for all options. However, summary shall contain amount of
Option-A.
ii. Contractors to work out his own quantities of the specified car finishes of the
following elevators and quote accordingly.
Stup Consultants P.Ltd 133 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
1.7 Projected charges for comprehensive (including the cost of spare
consumables etc.) Annual Maintenance Contact (AMC) for Three years after
expiry of the initial Free Maintenance Period of two years.
Year - 1 1 Job. 11000000.00 11,000,000.00
Year - 2 1 Job. 14000000.00 14,000,000.00
Year - 3 1 Job. 18000000.00 18,000,000.00
TOTAL OF LIFT CARRIED OVER TO SUMMARY 101,400,000.00
XX SOLAR SYSTEM
Supply Installation testing & commissioning of Solar Power Unit of 15 KWP.
The System shall be alongwith following component :-
Solar Photo Voltiac Module Minimum 230 WP 132 Nos. 13759.29 1,816,226.28
Module Mounting Structure for 15KWP 2 Set 117253.08 234,506.16
Power Conditioning Unit :
120V, 50 Hz, 11 KVA, Power conditioning unit comprises of Solar charge controller
cum inverter, full sine wave, 240V DC Input, 50 Hz AC output with grid tied feature
along with all protection, controlling, arrangement and required accessories.2 Set 251256.60 502,513.20
Array Junction Box / Main Arrray Junction Box, Cables, Lugs and other hardware 2 Lot 29911.50 59,823.00
AC Distribution Box 2 Lot 14357.52 28,715.04
Earthing Kit 2 Lot 29911.50 59,823.00
Lightning Arrestors 2 Lot 19143.36 38,286.72
Installatiopn & accessories 2 Lot 270160.67 540,321.34
TOTAL OF SOLAR SYSTEM CARRIED OVER TO SUMMARY 3,280,214.74
XXI Advanced Telecommunication System
1a SIEMENS Unify – HIPATH Digital/ Equivalent, Non-Blocking, ISDN / ATM, IP
Communication Server System
Initially Equipped with:
Control section cPCI architecture
Based on Real Time 2gIP platform 1 No. 96,48,800/- 9,648,800.00
1b With CALLER ID ON DIGITAL AND ANALOG PUSH BUTTON TELEPHONES /
EXTENSION** Internal & External Both
Trunk Side:
12 PRI Lines
Extension side:
400 Video SIP Extn’s
400 IPl Extn’s
1200 Analog Extensions interface
TOTAL EXTN. SIDE – 1200
TOTAL SIP/IP EXTN. - 800
Digital Phones :
PC Base Operator Console with PC
Stup Consultants P.Ltd 134 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
Expandable at extra cost
Stup Consultants P.Ltd 135 of 248
RATE (INR) AMOUNT (INR)
Bill of Quantities- INTERNAL ELECTRICAL Work
S.NO. DESCRIPTION OF ITEMS QUANTITY Unit
4 No. 1,08,500/- 434,000.00
2 Siemens Unify Comsando/ Equivalent SIP License for the Third Party Video Phones.
400 No. 3,200/- 1,280,000.00
3 10 Seater OpenScape Call Center Solution with PC and Head Phone Accessories 10 No. 1,45,000/- 1,450,000.00
4 Voice Logger with PC for the voice recording of 06 PRI Lines 1 No. 16,72,000/- 1,672,000.00
5 Call Billing Software with PC 1 No. 2,54,000/- 254,000.00
6 Polycom VVX1500/ Equivalent Video Phone – Business Media Phone with Video
Capability and SD Voice with Touch Screen. 1 No. 72,500/- 72,500/-
7 Siemens Unify OpenStage 40 HFA / Equivalent :Customizable for various
workplace environments OpenStage 40 is recommended for use as an office
phone, e.g. for desk sharing, people working in teams or call center staff,
Display (Tiltable graphical display, backlit, Optical call alert) Keypad, 8 fixed
function keys (partly equipped, with red LEDs, 6 freely programmable touch
keys (illuminated) , with red LEDs (function, speed dial or line keys), Control
keys, 5-way navigator, Acoustics, Hands free talking (full duplex), Interfaces,
Headset jack ,Wall-mountable1 No. 24,500/- 24,500.00
8 Euroset 2025 / Equivalent- Caller ID display, Super clear sound system, 30 group phone book, Hands
free speaker, Date, time display, LCD Screen, 10 phone number- single key dial
1000 No. 1,995/- 1,995,000.00
9 Main System - Krone MDF 8000 Pair 1 No. 2,80,500/- 280,500.00
Floor - Krone MDF 200 Pair 10 No. 32,000/- 320,000.00
10 Call Billing Software with PC 1 No. 2,54,000/- 254,000.00
11 FCBC with Battery’s & Stand for the backup of Main System 1 No. 7,50,000/- 750,000.00
12 Voice Mail With Mail Boxes for HOD’s 1 No. 3,50,000/- 350,000.00
13 Server for the VM System Software - Hardware Platform Pentium 4 at 2.4 GHz, 2
GB RAM Software Platform: Server: Windows Server 2003 Client: Windows 2000,
Windows XP. ( DELL/IBM/ Equal ) 1 No. 2,45,000/- 245,000.00
14 Professional Services 1 No. 4,00,000/- 400,000.00
� Consulting & Design
� Installation & Commissioning
� Training
� On-Site Plus Services included
TOTAL OF ADVANCED TELECOMMUNICATION SYSTEM CARRIED OVER TO
SUMMARY 19357800
Stup Consultants P.Ltd 136 of 248
SCHEDULE OF QUANTITIES
1
2
3
4
a All materials, fixing materials, accessories, appliances tools, plants, equipment, transport,
labour and incidentals required in preparation for and in the full and entire execution, testing,
balancing, commissioning and completion of work called for in the item and as per
Specifications and Drawings.
b Wastage on materials and labour.
c Loading, transporting, unloading, handling/double handling, hoisting to all levels, setting, fitting
and fixing in position, protecting, disposal of debris and all other labour necessary in and for
the full and entire execution and for the job in accordance with the contract documents, good
practice and recognize principles.
d Liabilities, obligations and risks arising out of Conditions of Contract.
e All requirements of Specifications, whether such requirements are mentioned in the item or
not. The Specifications and Drawings where available, are to be read as complimentary to
and part of the Schedule of Quantities and any work called for in one shall be taken as
required for all.
f In the event of conflict between Schedule of Quantities and other documents including the
Specifications, the most stringent shall apply. The interpretation of the Consultant/Project
Manager shall be final and binding.
g Tenderer has to include the rate of all items/ operations as mentioned in the Technical
Specificationsas applicable and for all Heights and levels as required to complete the system
at site
5
6
GENERAL NOTES Electrical Sub Station :
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW , U.P.
All items of work under this Contract shall be executed strictly to fulfill the requirements laid down
under “Basis of Design” in the specifications. Type of equipment, material specification, methods of
installation and testing and type of control shall be in accordance with the specifications, approved
shop drawings and the relevant Indian Standards, however capacity of each component and their
quantities shall be such as to fulfill the above mentioned requirement.
The unit rate for all equipment or materials shall include cost in INDIAN RUPEES (INR) for
equipment and materials including all taxes and duties and also including forwarding, freight,
insurance and transport into Contractor’s store at site, storage, installation, testing, balancing,
commissioning and other works required.
For all imported items Owners shall arrange EPCG licence and open L/C in the name of principals.
Rates for all imported items shall be quoted in US Dollars. During award of work Owner shall be at
liberty to ask for proforma invoice in any convertible foreign currency. All relevant document for
import shall be taken care by the contractor. Port charges / octroi / inland transportation etc. upto
site shall be paid on actuals subject to ceiling of quoted amount.
The rate for each item of work included in the Schedule of Quantities shall, unless expressly stated
otherwise, include cost of :
The Contractor shall procure and bring Materials/Equipment to the site only on the basis of
drawings approved for construction and shop drawings and not on the basis of Bill of Quantities
which are approximate only. This also applies to the Contractor’s requisition for Owner supplied
materials.
The work shall be carried out in conformity with the drawings and within the requirements of
architectural, Plumbing, Fire Fighting, HVAC, Structural and other specialized services drawings.
Stup Consultants P.Ltd 137 of 234
7 The contractor shall cooperate with all trades and agencies working on the site. He shall make
provision for hangers, sleeves, structural openings and other requirements well in advance to
prevent hold up of progress of the construction schedule. All supports to the civil structure shall be
provided with anchor fasteners.
Stup Consultants P.Ltd 138 of 234
8
9
10
11
12
13
14
15
16
17
18
19
20
21
The contractor shall , from time to time, clear away all debris and excess materials accumulated at
the site failing which the same shall be done by Project Manager at contractor’s risk and cost and
cost of clean up shall be deducted from the contractors prorata bill.
Shop drawings are detailed working drawings coordinated with other trading work, which
incorporate the contractor’s details for execution of the work and incorporate equipment
manufacturer’s details and dimensions to ensure that the same can be installed in the space
provided.
All shop drawings should detail pipe routing and levels, showing location of other services at
crossings etc., cable runs, route cable trays etc. and all allied works and must be fully coordinated
with other services, before execution of the works.
All shop drawings will be made on AutoCAD and colored prints has to be produced for site work.
On award of the work, contractor shall submit a schedule of construction in the form of a PERT
chart or BAR chart for approval of the Project Manager.
On award of the work the contractor shall be issued set of consultant’s drawings. The drawings
shall be the basis of contractor’s shop drawings.
Any pipe crossing fire rated wall as per fire compartmentation will be provide with higher size of GI
sleeve. All floor crossing pipes will be provided with higher size GI sleeve.
This Schedule shall be fully priced and the extensions and totals duly checked. The rates for all
items shall be filled in INK including NIL items.
No alteration whatsoever is to be made to the text or quantities of this Schedule unless such
alteration is authorised in writing by Consultant. Any such alterations, notes or additions shall,
unless authorized in writing, be disregarded when tender documents are considered.
In the event of an error occurring in the amount of the Schedule, as a result of wrong extension of
the unit rate and quantity, the unit rate quoted by the tenderer shall be regarded as firm and the
extensions shall be amended on the basis of rates.
Any error in totaling in the amount column and in carrying forward total shall be corrected. Any error,
in description or in quantity, omission of items from this Schedule shall not vitiate this Contract but
shall be corrected and deemed to be variation required by the Consultant/Project Manager.
Rates have been called for a number of items of works, as alternatives which, for the present do not
form part of the total value of tender. However the rates for these items shall be quoted, with due
care so that in the event of choice of an alternative item of work, said rate shall form part of the
contract and shall not violate the contract any way.
On completion of all works, contractor shall demolish all stores, remove all surplus materials and
leave the site in a broom clean condition, failing which the same shall be done by the Project
Manager at the Contractor'’ risk and cost. Cost of the cleanup shall be deducted from the
contractor’s bills on pro-rata basis in proportion to his contact value.
After the fixtures, equipment and appliances have been installed and commissioned, contractor
shall cleanup the same and remove all plaster, paints, stains, stickers and other foreign matter or
discoloration leaving the same in a ready to use condition.
Stup Consultants P.Ltd 139 of 234
I. 33 KV SYSTEM 6,056,305.00
IIH.T. CABLE & TERMINATION
1,412,990.00
IIIDISTRIBUTION TRANSFORMER , DG SET & BUS TRUNKING
96,922,175.00
IVMAIN L.T. PANEL & CAPACITOR PANEL
29,699,581.00
VLT CABLES
16,464,127.00
VIEXHAUST PIPING
13,174,822.00
VIID.G. COOLING SYSTEM
5,021,412.17
VIIIACCOUSTIC INSULATION OF DG SET ROOM
4,095,900.68
IXFUEL HANDLING EQUIPMENT
1,921,083.13
XEARTHING & SAFETY EQUIPMENT
3,033,168.09
TOTAL 177,801,564.07
Bill of Quantities- Sub Station Work
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW , U.P.
SUMMARY SHEET ( SUBSTATION WORK )
SUB-HEAD SH. DESCRIPTION TOTAL SOST IN INR
Stup Consultants P.Ltd 140 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
I. 33 KV SYSTEM
1.0 33 KV H.T. ONE (1) BREAKER PANEL
Design, Manufacture, Supply, Installation, Testing andCommissioning of 33 KV, 1500MVA (25 KA), 1250A, HTOne (1) Panel vacuum circuit breaker panel cubicle type,made out of 14 swg sheet steel, totally enclosed, IP 4X,free standing, floor mounting, dust and vermin proof,indoor, powder coated painting suitable for operation on 33 KV, 3ph, 50 Hz system with copper busbars, vacuum circuitbreaker mounted on horizontally withdrawable truckincluding supply and installation of the following.
i) 1 No. 1500 MVA, 1250Amp 33KV, Vacuum Circuit Breakerwith motorised spring charged and manual closingmechanism. Shunt trip coil, closing coil & indication shalloperate in 24V DC voltage derived through a battery bank.
ii) 3 No. Single Phase double core current transformer
Bill of Quantities- Substation Work
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW IN U.P.
ii) 3 No. Single Phase double core current transformer150/75/5 Amp epoxy cast insulated class of insulation E.
- Core 1-15VA burden class 1.0 for metering.
- Core 2-15VA burden class 5P10 for protection.
iii) 3 Nos. Line PT 33KV/ √3, 110V/ √3, 200VA class 1.0epoxy cast resin type.
iv) IDMT relay with 2 O/C and 1 E/F element with hand resetcontacts & indicator (flag) (O/C- setting 50-200% & E/Fsetting 20-80%) with protection for O/C and E/F. (selfpowered version).
v) 1 No. Anti Pumping device.
vi) 1 No. Circuit breaker control switch for electrical (T/N/C).
vii) 1 No. limit switch for test & service position.
viii) 1 No. digital type Voltmeter (0-36KV) (96mm square)
ix) 1 No. digital type Ammeter (0-150Amp) (96mm square).
x) 1 No. electronic type digital energy analyser having 30 daysmemory and parameters of KW, KWH, Power factor,frequency etc.
Stup Consultants P.Ltd 141 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
xi) 1 Set of following indicating lamps.
- Red, Yellow & Blue for phase indication.
- Amber for Trip indication.
- Red `ON' Green `OFF'
- Spring charge indication.
- Auto trip indication.
xii) Trip coil operation at 24 volts DC.
xiii) 1 No. control Transformer of 1KVA for giving supply tospring charging motor, space heaters etc having 33 KV/415-230V AC rating epoxy cast resin dry type Transformer.The connection for control transformer shall be taken fromthe cable side before the circuit breaker tapping.
xiv) 1 No. master trip relay.
xv) 1 Set of fuses, ferrules, wiring etc. as required.
xvi) Brass glands suitable for 1 No. 3 core 300Sq.mm. 33KVXLPE AL AR cable for incoming as well as outgoing side.
1 set 1,064,407.00 1064407.00
2.0 (A) 33 KV H.T. FOUR (4 ) BREAKER SWITCHBOARD PANEL
Design, Manufacture, Supply, Installation, Testing andCommissioning of 33 KV, 1500MVA (25 KA), 1250A, HTFour (4) Panel vacuum circuit breaker switchboard (oneincomer, three outgoing vacuum circuit Breaker), cubicletype, made out of 14 swg sheet steel, totally enclosed, IP4X, free standing, floor mounting, dust and vermin proof,indoor, compartmentalised, powder coated paintingsuitable for operation on 33 KV, 3ph, 50 Hz system withcopper busbars, vacuum circuit breaker mounted onhorizontally withdrawable truck including supply andinstallation of the following.
INCOMING PANEL - 1 NO.
i) 1 No. 1500 MVA, 1250Amp 33KV, Vacuum Circuit Breakerwith motorised spring charged and manual closingmechanism. Shunt trip coil, closing coil & indication shalloperate in 24V DC voltage derived through a battery bank.
ii) 3 No. Single Phase double core current transformer150/75/5 Amp epoxy cast insulated class of insulation E.
Stup Consultants P.Ltd 142 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
- Core 1-15VA burden class 1.0 for metering.
- Core 2-15VA burden class 5P10 for protection.
iii) 3 Nos. Line PT 33KV/ √3, 110V/ √3, 200VA class 1.0epoxy cast resin type.
iv) IDMT relay with 2 O/C and 1 E/F element with hand resetcontacts & indicator (flag) (O/C- setting 50-200% & E/Fsetting 20-80%) with protection for O/C and E/F. (selfpowered version).
v) 1 No. Anti Pumping device.
vi) 1 No. Circuit breaker control switch for electrical (T/N/C).
vii) 1 No. limit switch for test & service position.
viii) 1 No. digital type Voltmeter (0-36KV) (96mm square)
ix) 1 No. digital type Ammeter (0-150Amp) (96mm square).
x) 1 No. electronic type digital energy analyser having 30 daysx) 1 No. electronic type digital energy analyser having 30 daysmemory and parameters of KW, KWH, Power factor,frequency etc.
xi) 1 Set of following indicating lamps.
- Red, Yellow & Blue for phase indication.
- Amber for Trip indication.
- Red `ON' Green `OFF'
- Spring charge indication.
- Auto trip indication.
xii) Trip coil operation at 24 volts DC.
xiii) 1 No. control Transformer of 1KVA for giving supply tospring charging motor, space heaters etc having 33 KV/415-230V AC rating epoxy cast resin dry type Transformer.The connection for control transformer shall be taken fromthe cable side before the circuit breaker tapping.
xiv) 1 No. master trip relay.
xv) 1 No. hooter.
xvi) 1 Set of fuses, ferrules, wiring etc. as required.
Stup Consultants P.Ltd 143 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
xvii) Brass gland suitable for 1 No. 3 core 300Sq.mm. 33KVXLPE AL AR cable.
OUTGOING PANEL - 3 Nos. each with
i) 1 No. 1500 MVA, 1250Amp 33KV, Vaccum Circuit Breakerwith motorised spring charged and manual closingmechanism. Shunt trip coil, closing coil & indication shalloperate in 24V DC voltage derived through a battery bank
ii) 3 No. Single Phase double core current transformer 50 / 5A,epoxy cast insulated class of insulation E.
- Core 1-15VA burden class 1.0 for metering.
- Core 2-15VA burden class 5P10 for protection.
iii) IDMT relay with 2 O/C and 1 E/F element with hand resetcontacts & indicator (flag) (O/C- setting 50-200% & E/Fsetting 20-80%) with protection for O/C and E/F. (selfpowered version).
iv) 1 No. Anti Pumping device.iv) 1 No. Anti Pumping device.
v) 3 Nos. auxiliary relay for transformer fault, alarm and tripsuitable for 230V AC supply.
vi) 1 No. Circuit breaker control switch for electrical (T/N/C).
vii) 1 No. limit switch for test & service position.
viii) 1 No. digital type Ammeter (0-50Amp) (96mm square).
ix) 2 Set of following indicating lamps.
- Red, Yellow & Blue for phase indication.
- Amber for Trip indication.
- Red `ON' Green `OFF'
- Spring charge indication.
- Auto trip indication.
x) Trip coil operation at 24 volts DC.
xi) 1 Set of fuses, ferrules, wiring etc. as required.
xii) 1 No. hooter.
xiii) 1 No. master trip relay.
xiv) Brass gland suitable for 1 No. 3 core 185 Sq.mm. 33KV XLPE AL AR cable.
Stup Consultants P.Ltd 144 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
- All metering and protection devices, interconnections,necessary control wiring and all other accessories shall beprovided as per SLD or as required as per specificationsand technical particulars
1 Set
4080732.00
2.0 (B) Extra for SF6 Gas circuit breaker instead of vacuum circuitbreaker. 1 Set 500000.00
3.0 33 KV METERING PANEL
Design, Manufacture, Supply, Installation, Testing andCommissioning of 33 KV, Metering Panel complete with 3Nos. CT's of 150/5A, 0.5 Class, 15VA Burden and PT's of33KV/110V, 100VA & having 5Amp Elecronic Trivectormeter complete in all respects suitable for terminatingincoming & outgoing 33KV, 3C x 300 Sq.mm. XLPEarmoured cables, as required. CT's, PT's and Trivectormeter shall be got tested and approved from local electricitysupply authority. 1 set 235959.00
4.0 BATTERY CHARGER & BATTERIES
Supply, Installation, Testing and Commissioning of 1 (One)Supply, Installation, Testing and Commissioning of 1 (One)number 24 V Battery Charger & 4 (four) numbers of 12V180 AH maintenance free sealed lead acid batteries BatteryCharger shall be solid state, full wave fully controlledbridge, input suitable for single phase 230V AC suppply,conforming to degree of protection IP-42, Sheet steelenclosure 14 SWG thick, with automatic voltage regulation,current limiting circuitary, auto cut facility, smooth filtercircuit switches, Ammeter & voltmeter on DC side, RYBindicating lamps (LED type) on AC side complete in allrespect with float and boost/ trickel charging, switches /MCBs, earthing, powder coated painting etc as required.
i) 1 Set each for D.C Trip control supply to 33KV panels. 1 Set 175,207.00 175207.00
TOTAL OF SUBHEAD-I: 33 KV SYSTEM CARRIED
OVER TO SUMMARY 6056305.00
II H.T. CABLE & TERMINATION
1,0 Supply of following sizes 33KV XLPE aluminium conductor
armoured cable conforming to IS : 7098 complete as per
specification and as required.
i) 3 Core, 300 sq.mm 100 M 5,125.00 512500.00
ii) 3 Core, 185 sq.mm 100 M 3,989.00 398900.00
Stup Consultants P.Ltd 145 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
2.0 Laying of one number PVC insulated and PVC sheathed / XLPE
power cable of 33 KV grade of following sizes direct in ground
including excavation, sand cushioning, protective covering and
refilling the trench etc. as required.
i) Above 120sqmm and upto 400 sqmm. 70 M 280.00 19600.00
3.0 Laying of one number PVC insulated and PVC sheathed / XLPE
power cable of 33 KV grade of following size in the existing
RCC/HUME/ METAL pipe as required.
i) Above 120sqmm and upto 400 sqmm. 30 M 61.00 1830.00
4.0 Laying of one number PVC insulated and PVC sheathed / XLPE
power cable of 33 KV grade of following size in the existing
masonry open duct as required.
i) Above 120sqmm and upto 400 sqmm. 100 M 53.00 5300.00
5.0 Supplying and making outdoor cable end terminationwith heatshrink jointing kit complete with all accessories,with heatshrink jointing kit complete with all accessories,bimetallic washers and including lugs for the following sizeof 3 Core, XLPE alumimium conductor cable of 33 KVgrade as required.
a) OUTDOOR CABLE & TERMINATION
i) 3 Core 300 Sq.mm. 1 Set 59,181.00 59181.00
ii) 3 Core 185 Sq.mm. 3 Set 44,713.00 134139.00
6.0 Supplying & making indoor cable end termination with heatshrink jointing kit complete with all accessories,bimetallic washers and including lugs for the following sizeof 3 core XLPE aluminium conductor cable of 33 KV grade complete as required.
b) INDOOR CABLE & TERMINATION
i) 3 Core 300 Sq.mm. 5 Set 36,823.00 184115.00
ii) 3 Core 185 Sq.mm. 3 Set 32,475.00 97425.00
TOTAL OF H.T. CABLE & TERMINATION CARRIED
OVER TO SUMMARY 1412990.00
III DISTRIBUTION TRANSFORMER , DG SET & BUS
TRUNKING
1.0 DISTRIBUTION TRANSFORMER (OIL TYPE) (OLTC
TYPE)
Stup Consultants P.Ltd 146 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
Supply, installation, testing & commissioning of 2500 KVA
33KV/433V, 3 phase 50 Hz outdoor copper wound oil type
distribution transformer with OLTC (On Load Tap Changer) with
AVR and RTCC Panel. Vector group Dyn-11 ONAN cooled
having cable end box suitable for 3 core 300 sq.mm XLPE
Aluminium conductor 33KV cable on HV & bus duct on L.T.
side with all fittings & accessories, bucholtz relay alarm &
trip, WTI alarm & trip and oil temperature alarm & trip
control wiring, all civil work including foundation etc.
complete as per specifications & conforming to IS 2026-1977
and complying with specification and requirement of local electric
supply authority.
3 No. 3,036,929 9110787
2.0 Supply, installation, testing & commissioning of standard 2000
KVA, 415V, 3 phase, 1500 R.P.M, 0.8 PF, floor mounted Diesel
Generator Set coupled to alternator and DG Control Panel
complete with power command controller PC 3.3 complete with
all accessories required. Conforming to latest environment
protection regulations for emmission and noise levels complete
with and Diesel Engine developing minimum ------- BHP at 1500
RPM or actual BHP calculated considering de-rating factor if
any whichever is higher and all accessories including Engine
control panel, AMF Panel with meters, CTs and transducers for allcontrol panel, AMF Panel with meters, CTs and transducers for all
metering and protection, Day oil tank of 990 Ltrs., Exhaust
piping complete with bends, flexbile connections, antivibration
mountings, critical type exhaust silencer, electric starter, batteries
& battery charger, complete as per specification & as required.
(Manufacture shall insure taht BHP of Engine specified is after
considering derating factor).
3 Set 20,908,298.00 62724894.000.00
3.0 Supply, of silent type 600 to 640 KVA, 415V, 3 phase, 1500
R.P.M, 0.8 PF, floor mounted Diesel Generator Set coupled to
alternator and DG Control Panel complete with power command
controller PCC 3.3 complete and all accessories required. DG Set
shall Conforming to latest environment protection regulations for
emmission and noise levels complete with Diesel Engine
developing either ---------BHP at 1500 RPM or actual BHP
calculated considering de-rating factor if any whichever is higher
and all accessories including Engine control panel , AMF Panel
with meters, CTs and transducers for all metering and protection,
Day oil tank of 990 Ltrs., Exhaust piping complete with bends,
flexbile connections antivibration mountings, critical type
exhaust silencer, electric starter, batteries & battery charger, and
DG set acoustic enclosure shall conform to CPCB norms and
complete as per specification & as required.
1 Set 7,120,471.00 7120471.000.00
Note : 0.00
1.0 Ambient temperature for DG Sets operation is 45°C.
Stup Consultants P.Ltd 147 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
2.0 DG Manufacturer/OEM shall coordinate with Main L.T. Panel
supplier for synchronising of DG Set & auto start / auto stop
functioning including testing & commissioning.0.00
3.0 The DG Set Manufacture/OEM to guarantee that DG Set shall
generate minimum 4 units of Electric power per litre at loading
ranging from 40% to 85% under site conditions.4.0 If Manufacturer does not have the Power command controller of
Cumins PC 3.3 or equivalent then the supplier shall submit the
synchronizing panel PLC based DG Sets and scope of integration
4.0 The liasioning for inspection & approval of the layout drawing,
installation license from electricity supply authority, electrical
inspector, permission for operation of DG Set, approval from
Pollution Control Board etc. as required.
i) 2000 KVA 3 Job 630,658.00 1891974.00
ii) 625 KVA 1 Job 107,866.00 107866.00
5.0 L.T. BREAKER PANEL5.0 L.T. BREAKER PANEL
Supply, Installation, Testing and Commissioning of following
indoor/ outdoor type cubicle L.T. Breaker Panel consisting of FP
MDO ACB with microprocessor based releass, O/L, S/C & E/F
protection and ON/OFF indicating LED lights complete as
required & as per specification.
i) 4000 Amp FP MDO ACB (75KA Ics value) 3Set 600,000.00 1800000.00
ii) 3200 Amp FP MDO ACB (65KA Ics value) 3Set 500,000.00 1500000.00
iii) 1000 Amp FP MDO ACB (65KA Ics value) 1 Set 300,000.00 300000.00
6.0 BUS TRUNKING
Supply, installating by suspension on ceiling , testing &
commissioning of following capacity / rating IP 65 Rated
sandwich type Copper / Aluminium bus trunking suitable for
415 volts 3 phase, 4 wire 50Hz AC supply complete with all
accessories & necessary support etc. as per specification and as
required.
a) Copper Bus Trunking
i) 6000 Amp 65 KA SC for 1 Second 1 M 100,000.00 100000.00
ii) 4000 Amp 65 KA SC for 1 Second 1 M 93,442.70 93442.70
Stup Consultants P.Ltd 148 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
iii) 1000 Amp 65 KA SC for 1 Second 1 M 24,077.30 24077.30
a) Aluminium Bus Trunking0.00 0.00
i) 6000 Amp 65 KA SC for 1 Second 1 M 100,000.00 100000.00
ii) 4000 Amp 65 KA SC for 1 Second 123 M 93,443 11,446,731
iii) 1000 Amp 65 KA SC for 1 Second 25 M 24,077 601,933
(Note: The bus trunking shall be measured along the length of
enclosure. The aluminium/ copper strips which will go inside
LT panels & end termination box of transformers shall not be
taken into measurement of bus trunking quantity).
TOTAL OF DISTRIBUTION TRANSFORMER, DG SET &
BUS TRUNKING CARRIED OVER TO SUMMARY. 96922175
IV MAIN L.T. PANEL & CAPACITOR PANEL
1.0 MAIN L.T. PANEL
0.00
Supply , installation, testing & Commissioning of Main L.T.
Panel suitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz, A.C.
Supply totally enclosed type with short cirrcuit withstand
capacity as specified and as per local approving authority
requirement , free standing floor mounted dust and vermin proof
indoor type fabricated from 2mm thick CRCA sheet steel complete
with busbars, ammeter, ammeter selector switch, voltmeter,
voltmeter selector switch, indicating lamps, protection relays, CT's
protection mcb,interconnections with suitable size of copper lead /
solid aluminium strips / rod & control circuit including braker
control switch, auto / manual selector switch, auto/manual circuit,
anti pumping relay, spring charging indication, trip indication etc.
PLC mounted in panel shall ensure auto start / auto stop of DG
Sets,
auto changeover between grid & DG Supply, Load management in
Main L.T. Panel, interlocking and ensuring the panel is compatible
with DG Set Synchronizing panel or equivalent, and having
following incoming and outgoing Air Circuit Breakers (ACB),
Moulded Case Circuit Breaker (MCCB) and metering, protection,
battery charger, transducer, UPS & PLC of Allen Bradly or
equivalent complete as per the drawing and specifications. (Total
of A to F)
1 Set 14,237,637.00 14237637.00
Stup Consultants P.Ltd 149 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
A) TRANSFORMERS INCOMERS (3 SETS)
4000Amp FP Electrically operated horizontal drawout (EDO) type
Air Circuit Breaker (65KA Ics value) with Microprocessor release
for O/L, S/C & E/F protection (Incomer of 2500 KVA
transformer). Each Transformer incomer shall have following
Instruments / metering & protection relay:
(a) 3 Nos. 0 to 500 Volt digital voltmeter
(b) 1 Nos. 0 to 4000 /5Amp digital ammeter with selector switch &
CT's (for 2500 KVA Transformers)
(c) 1 Nos. 25A Breaker control switch (Rotary Type)
(d) 1 Nos. KWH Meter
(e) 1 Nos. Frequency Meter
(f) 1 Nos. Energy Analyser (Multi-function Meter)
(g) 1 Set of Phase Sequence Relay, Under voltage Relay, Over
Voltage Relay, Trip circuit, Supervision Relay, Master Trip Relay,
with a set of protection CT's with a set of protection CT's
(h) Automatic Power Factor Correction relay with CT's
(i) Auxiliary Contactor AC (2 NO +2 NC )
(j) 1 Set of phase indicating lights (RYB) with protection MCB
(k) 1 Set of ON / OFF / TRIP indicating lamp (LED Type)
B) DG SUPPLY INCOMERS (4 SETS)
i) 3 Nos. 3200 Amp FP Electrically operated horizontal drawout
(EDO) type 65 KA breaking capacity Air Circuit Breaker with
microprocessor release for O/L, S/C & E/F protection (Incomer for
2000 KVA DG Set supply ). Each DG supply incomer breaker
shall have electrically & mechanically interlocked with
transformer incommer breaker of respective bus section with
following instruments / metering & protection relays:
ii) 1 No. 1000 Amp FP Electrically operated horizontal drawout
(EDO) type 65 KA breaking capacity Air Circuit Breaker with
microprocessor release for O/L, S/C & E/F protection (Incomer for
625 KVA DG Set Supply ). Each DG supply incomer breaker
shall have electrically & mechanically interlocked with
transformer incommer breaker of respective bus section with
following instruments / metering & protection relays:
(a) 3 Nos. 0 to 500 Volt digital voltmeter.
Stup Consultants P.Ltd 150 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
(b) 3 No. 0 to 3200 /5 Amp digital ammeter with CT's (for 2000
KVA DG Set Supply ) & 1000 /5 Amp digital ammeter with CT's
(for 625 KVA DG Set Supply )
(c) 1 No. 25A Breaker control switch
(d) 1 No. KWH Meter
(f) 1 No. Energy Analyser / Multi function meter
(g) 1 No. Standby Earth Fault Relay
(h) 1 No. Trip circuit Supervision relay
(i) 1 No. Master Trip relay
(j) 2 Sets of Auxiliary Contactor AC ( 2 NO +2 NC ) Under & Over
voltage relays.
(k) 1 Sets of Auxiliary Contactor DC ( 2 NO +2 NC )
(l) 1 Set of phase indicating lights (RYB) with protection mcb.
(m) 2 Set of Start / Stop Push Button
(n) 1 Set of Emergency Push Button(n) 1 Set of Emergency Push Button
(o) 1 Set of 12 Window annunciator Panel
(p) 1 Set of Hooter
(q) 1 Set of Auto / Manual Selector Switch
(r) 1 No. KW Transducer (4-20 mA)
C) CONTROL PANEL (PART OF MAIN L.T. PANEL)
(i) All hardware & software required for synchronizing of 4 Nos. DG
Set (PCC 3.3 Cummins or equivalent Quantity 1 No. for each DG
set shall form part of DG Set supplier scope).
(ii) PLC (Micrologic 1500 of Allen Bradly or equivalent) with Panel
view 300.
(iii) UPS of 1 KVA with Power Backup for 30 minutes for PLC and
Common Circuits.
D) BUSCOUPLER
- 2 Nos. 4000Amp 75 KA/ 65 KA FP EDO ACB without release as
buscoupler with interlocking arrangement with incomers.
- 2 Sets of indicating lamps for ON & OFF with mcb, breaker
control switch, Auxiliary Contactors etc. complete with each
buscoupler
E) BUSBARS
- 5000 Amp TPN busbars of aluminium alloy (Bus Section-I, II &
III)
Stup Consultants P.Ltd 151 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
F) OUTGOING
- 3 Nos. 1200 Amp Three Pole Manually Operated Horizontal
Drawout (MDO) Air Circuit Breaker with neutral link of 50KA
(Ics) breaking capacity with microprocessor based O/C, S/C
protection release & ON / OFF indicating lamps.
- 14 Nos. 1000 Amp Three Pole Manually Operated Horizontal
Drawout (MDO) Air Circuit Breaker with neutral link of 50KA
(Ics) breaking capacity with microprocessor based O/C, S/C
protection release & ON / OFF indicating lamps.
- 2 Nos. 800 Amp Three Pole Manually Operated Horizontal
Drawout (MDO) Air Circuit Breaker with neutral link of 50KA
(Ics) breaking capacity with microprocessor based O/C, S/C
protection release & ON / OFF indicating lamps.
- 6 Nos. 630 Amp Three Pole Manually Operated Horizontal
Drawout (MDO) Air Circuit Breaker with neutral link of 50KA
(Ics) breaking capacity with microprocessor based O/C, S/C
protection release & ON / OFF indicating lamps.
- 2 Nos. 400 Amp Three Pole Moulded Case Circuit Breaker with
neutral link of 50KA (Ics) breaking capacity & microprocessor
based O/C, S/C protection release & ON / OFF indicating lamps.
- 6 Nos. 250 Amp Three Pole Moulded Case Circuit Breaker with
neutral link of 35KA (Ics) breaking capacity & microprocessor
based O/C, S/C protection release & ON / OFF indicating lamps.
- 4 Nos. 160 Amp Three Pole Moulded Case Circuit Breaker with
neutral link of 35KA (Ics) breaking capacity & microprocessor
based O/C, S/C protection release & ON / OFF indicating lamps.
- 3 Nos. 100 Amp Three Pole Moulded Case Circuit Breaker with
neutral link of 35KA (Ics) breaking capacity & microprocessor
based O/C, S/C protection release & ON / OFF indicating lamps.
- Necessary hardware shall be provided to achieve above functions
including PLC with real time clock, digital inputs / outputs, MMI
with 2 line display, power supply, auxillary relays, PB's indication
etc. & software for the above. All items required for complete
load management , auto start, auto stop of DG Sets, auto
changeover between grid & DG Set Incommer breakers shall form
part of item & deemed to be included in quoted rates whether or
not listed in BOQ item.
Stup Consultants P.Ltd 152 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
- Automatic system shall be user friendly and shall have manual
override.
Note: - All the incomers in outgoing feeders / breakers shall have
RS 485 port/ KWH meter compatible for BMS operation
with RS 485 port MODBUS output protocol.
2.0 D.G. SYNCHRONISING CUM LOAD SHARING PANEL
Supplying, Installation, Testing & Commissioning of cubical type
D.G. Synchronising Cum Load Sharing Panel suitable for
415V, 3 Phase, 4 wire 50 Hz AC supply system, fabricated in
compartmentalized (preferably) design from CRCA sheet steel of
2mm thick for frame work and covers, 3mm thick for gland plates
i/c cleaning & finishing complete with 7 tank process for powder
coating in approved shade, having 8000 amp capacity extensible
type TPN Aluminium Alloy bus bars of high conductivity,
DMC/SMC bus bars supports with short circuit withstand
capacity as specified and as per local approving authority
requirement, bottom base channel of MS section not less than
200mm x 100mm x 5mm thick, fabrication shall be done in
transportable sections, entire panel shall have a commontransportable sections, entire panel shall have a common
aluminium earth bar of size 25mm x 5mm at the rear with 2 Nos.
earth stud, solid connections from main bus bar to switch gears
with required size of AL bus bars and control wiring with 4.0 /
2.5 sq.mm PVC insulated copper conductor Single core cable,
cable alleys, cable gland plates in two half, i/c providing following
switch gears:- (All item for auto synchronising of 3 Nos 2000
KVA & 1 No 500 KVA DG Set shall deemed to be included in
this item. Synchronising system shall ensure auto start / auto stop
of 3 Nos. 2000 KVA DG Set and 1 No. 500 KVA DG , auto
changeover. Grid and DG Set feeder of existing Main LT Panel ).
Set 0.00
0.00
DG SETS SUPPLY ( 2000 KVA) 3 NOS. AND 1 NO. 625 KVA
3 Nos 3200 Amp FP Electrically operated horizontal drawout
(EDO) type Air Circuit Breaker of 65 KA with microprocessor
release for O/L, S/C & E/F protection
1 Nos 1000 Amp FP Electrically operated horizontal drawout
(EDO) type Air Circuit Breaker of 65 KA with microprocessor
release for O/L, S/C & E/F protection
METERING
4 Nos. 0 to 500 Volt digital voltmeter for 3 phase, 4 wire operation
with selector switches alongwith 3 Nos. control MCB's.
Stup Consultants P.Ltd 153 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
3 Nos. Digital Ammeter of suitable range (measure 0 to 3200
Amp) for 3 phase, 4 wire operation with selector switches and 9
Nos. suitable range of CT's.
1 No. Digital Ammeter of suitable range (measure 0 to 1000 Amp)
for 3 phase, 4 wire operation with selector switches and 3 Nos.
suitable range of CT's.
4 Sets of phase (RYB) indicating lamps, LED type for incomer
breakers and 3 Sets of 'ON', 'OFF' lamp LED type for Buscoupler.
4 Sets of CTs for REF & Differencial Protection.
Auxilary Contactor, 2 NO + 2 NC - 230 V AC (4 Nos.)
4 Nos. Reed type Frequency Meters for D.G. Sets
1 Set of Voltage Sensing Relay and Connection between Main
Panel & D.G. Synchronising Panel
4 Nos. Differencial Relay
4 Nos. REF Realy
1 No. 1 KVA UPS with 20 Minuts power backup.
INTERLOCKING
Electrical Interlocking between 4 Incomers and 2 bus couplers of
synchronising Panel & Main LT panel feeder & bus coupler .
AUTO SYNCHRONISATION FOR 4 NOS. D.G. SETS
SGC - 4 Relay ( 4 Nos.)
Mannual Synchronisation for 4 DG sets
40A Battery Charger ( 4 Nos.)
DC Voltmeter- 0-50V ( 4 Nos.)
DC Ammeter - 0-30A ( 4 Nos.)
Double Scale Frequency Meter 45-55 Hz. ( 1 No.)
Double Scale Voltmeter 0-500V ( 1 No.)
Synchro Max 40-70 Hz. ( 1 No.)
Dark Lamps 60W - 230V ( 4 Nos.)
Stup Consultants P.Ltd 154 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
S/SW 6A 1P 3W with off 61060 -PLC / Man / Solo ( 1 No.)
S/SW 6A 1P 3W with off 61060 -DG S/S ( 1 No.)
S/SW 16A Spring to Return Neutral-SG16-61361-V/S-Raise-
Lower ( 8 Nos.)
BCS-25A ( 8 Nos.)
Red Push Button-1NO-Engine Stop ( 4 Nos.)
Green Push Button-1NO-Engine Start ( 4 Nos.)
Red-Mushroom Head Stayput Push Button - 3NO - EMG Stop ( 4
Nos.)
Motorized Pot ( 4 Nos.)
Multifunction Timer ( 4 Nos.)
Window Facia 4 Big - 24V DC ( 4 Nos.)
Aux. Contactor, 2NO+2NC- 230V AC ( 6 Nos.)Aux. Contactor, 2NO+2NC- 230V AC ( 6 Nos.)
Aux. Contactor, 2NO+2NC- 24V DC ( 48 Nos.)
MIMIC with LED ( 1 No.)
6A SP MCB - 10KA ( 4 Nos.)
MISC. EQUIPMENTS
10A DC Regulated Power Supply ( 1 No.)
Interposing relay -24V DC ( 128 Nos.)
Panel General Accessories
Panel Light with door switch ( 4 Nos.)
Space Heater ( 1 No.)
Thermostat ( 1 No.)
6A SP MCB - 10KA ( 4 Nos.)
BUS COUPLER
2 Nos. 4000Amp 65 KA FP EDO ACB without release as
buscoupler with interlocking arrangement with incomers.
OUTGOINGS
Stup Consultants P.Ltd 155 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
3 Nos 3200 Amp FP Electrically operated horizontal drawout
(EDO) type Air Circuit Breaker of 65 KA with microprocessor
release for O/L, S/C & E/F protection
1 Nos 1000 Amp FP Electrically operated horizontal drawout
(EDO) type Air Circuit Breaker of 65 KA with microprocessor
release for O/L, S/C & E/F protection
NOTE:-
i) The bidder should go through the Drg. & B.O.Q. deeply and
include any other thing required to complete the system and quote
for comprehensive scheme.
ii) Necessary hardware and softwere including WOOD WARD
MAKE DG synchronising relay shall be provided to achieve all
required functions . Vendor to check and confirm additional items
required for complete synchronising of 4 Nos. DG Set, with auto
start / auto stop of DG Sets, auto changeover between grid & DG
Set Incommer breakers as per existing Main LT Panel .
Buscouplar switching and interlocking shall form part of item &
deemed to be included in quoted rates whether or not listed indeemed to be included in quoted rates whether or not listed in
BOQ item. The vendor should go through the Drawing, BOQ and
existing Main LT Panel to ensure all item required for proper
functioning of DG Set synchronisation 0f 3 Nos. 2000 KVA DG
Set and 1 No. 630 KVA DG Set are included in the quoted rate
and quote for comprehensive scheme in coordination with existing
Main LT Panel.
0.00
iii) DG Synchronising Panel supplier Shall Co ordinate with DG
DG Manufacturer/OEM for synchronising of DG Set & auto start /
auto stop functioning including testing & commissioning.0.00
0.00
iv) DG Synchronising Panel supplier Shall ensure weather
Manufacturer have the Power command controller of Cumins PC
3.3 or equivalent or not & accordingly synchronising panel ( PLC
Based ) design shall be finalised and further integration with
Main L.T. Panel.
1 set 11,689,428.00 11689428.00
3.0 CAPACITOR BANK PANEL - 150 KVAR
Stup Consultants P.Ltd 156 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
Supply, Installation, testing & commissioning of indoor type
Capacitor Panel fabricated from 2mm thick CRCA sheet steel with
busbars & having following incoming & outgoing switchgears and
suitable for automatic switching ON & OFF of capacitor unit with
APFC relay, capacitor duty contactor, push button, power factor
meter including capacitor bank complete with interconnections,
powder coated Panel after metal treatment etc. complete and
having following as required.
4 Sets 250,000.00 1000000.00
A) INCOMING
- 1 No. 500 Amp Four Pole Moulded Case Circuit Breaker 35KA
(Ics) breaking capacity with microprocessor based O/L, S/C & E/F
protection release with RS485 communication port and ON/OFF
indicating lamps.
B) BUSBARS
- 1 Set of 630 Amp TPN busbar of aluminium alloy.
C) INSTRUMENTS
- 1 No. 0 to 500 volts digital type voltmeter.
- 1 No. 0 to 500 Amp digital type ammeter with CT's.
- 1 No. Indicating lamp for each 25/12.5KVAR capacitor unit to
indicate that the unit is 'ON'.
- Power factor meter.
- 8 stepped Automatic Power Factor Correction relay (APFC relay).
D) OUTGOING
- 4 Nos. 63 Amp Three Pole Moulded Case Circuit Breaker with
neutral link of 25KA (Ics) breaking capacity.
- 4 Nos. 32 Amp Three Pole Moulded Case Circuit Breaker with
neutral link of 25KA (Ics) breaking capacity.
- 8 Nos. capacitor duty contactor (one for each 25/12.5 KVAR
capacitor unit).
- 4 Nos. 25 KVAR Capacitor Bank.
Stup Consultants P.Ltd 157 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
- 4 Nos. 12.5 KVAR Capacitor Bank.
- 8 Sets of push button stations Red and Green for manual operation
of capacitor units with auto/manual selector switches.
- 1 No. toggle switch for changing automatic to manual operation of
capacitor units.
4.0 CAPACITOR BANK PANEL(500 KVAR CAPACITY) 3 Sets 924,172.00 2772516.000.00
Supply, installation, testing & commissioning of Capacitor Panel
suitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz, A.C.
Supply totally enclosed type with free standing floor mounted dust
and vermin proof indoor type fabricated from 2mm thick CRCA
sheet steel complete with busbars, ammeter, ammeter selector
switch, voltmeter, voltmeter selector switch, indicating lamps,
protection relays, CT's protection fuses, interconnections with
suitable size of copper leads/solid aluminium strips/rod auto /
manual selector switch for operation of capacitor units, push
buttons for manual operation, capacitor duty contactors, capacitorbuttons for manual operation, capacitor duty contactors, capacitor
bank, APFC relay, power factor meter etc. complete and having
following incoming and outgoing Circuit Breakers etc. as per the
drawing and specifications complete as required. (TOTAL OF A
TO C)
A) INCOMER0.00
● 1 No. 1600 Amp Four Pole Moulded Case Circuit Breaker (50KA
Ics Value) with microprocessor release for O/L, S/C & E/F
protection.
● 1 No. 0-1600A. Ammeter with selector switch & CT's.
● 1 No. 0-500A. Voltmeter with selector switch
● 1 Set of phase indicating lamps
B) BUSBARS
● 2000A TPN Aluminium busbars
C) OUTGOING
● 14 stepped Automatic Power Factor Correction relay (APFC
relay).
● 4 Nos. 40 Amp Three Pole Moulded Case Circuit Breaker (25KA
Ics Value) with thermal magnetic release for O/L, S/C & E/F
protection and neutral link.
Stup Consultants P.Ltd 158 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
● 2 Nos. 63 Amp Three Pole Moulded Case Circuit Breaker (25KA
Ics Value) with thermal magnetic release for O/L, S/C & E/F
protection and neutral link.
● 4 Nos. 100 Amp Three Pole Moulded Case Circuit Breaker (25KA
Ics Value) with thermal magnetic release for O/L, S/C & E/F
protection and neutral link.
● 2 Nos. 250 Amp Three Pole Moulded Case Circuit Breaker (35KA
Ics Value) with thermal magnetic release for O/L, S/C & E/F
protection and neutral link.
● 14 Nos. Capacitor duty contactor (one for each 100 KVAR /
50KVAR / 25KVAR / 12.5KVAR) Capacitor unit.
● 2 Nos. 100 KVAR Capacitor Bank.
● 4 Nos. 50 KVAR Capacitor Bank.
● 2 Nos. 25 KVAR Capacitor Bank.
● 4 Nos. 12.5 KVAR Capacitor Bank.
● 14 Sets of push button stations Red and Green for manual● 14 Sets of push button stations Red and Green for manual
operation of capacitor units with auto/manual selector switches.
● 1 No. Indicating lamp for each 100 KVAR / 50KVAR / 25KVAR
/ 12.5KVARcapacitor unit to indicate that the unit is 'ON'.
● 1 No. Toggle switch for changing automatic to manual operation
of capacitor units.
● 1 No. Power factor meter.
TOTAL OF MAIN LT PANEL & CAPACITOR PANEL
CARRIED OVER TO THE SUMMARY. 29699581.00
V LT CABLES
1.0 A) Supply of following size of 1.1KV grade multicore aluminium
conductor XLPE insulated & PVC sheathed armoured cable as
per IS: 7098 (Part-1) 1988 complete as required.
i) 3.5 core, 400 Sq.mm. 4000 M. 1,790.00 7160000.000.00 0.00
ii) 3.5 core, 300 Sq.mm. 2000 M. 1,400.00 2800000.000.00 0.00
iii) 3.5 core, 240 Sq.mm. 1300M. 1,150.00 1495000.000.00 0.00
iv) 3.5 core, 185 Sq.mm. 300 M. 910.00 273000.000.00 0.00
v) 3.5 core, 150 Sq.mm. 500 M. 735.00 367500.00
vi) 3.5 core, 120 Sq.mm. 1000 M. 620.00 620000.00
vii) 3.5 core, 95 Sq.mm. 2000 M. 500.00 1000000.000.00 0.00
Stup Consultants P.Ltd 159 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
viii) 3.5 core, 50 Sq.mm. 200 M. 295.00 59000.000.00 0.00
ix) 3.5 core, 35 Sq.mm. 200 M. 230.00 46000.000.00 0.00
x) 4 core, 25 Sq.mm. 200 M. 200.00 40000.00
xi) 4 core, 16 Sq.mm. 200 M. 145.00 29000.00
1.0 B) Supply & laying / fixing of following sizes of 1.1KV copper
conductor PVC insulated & PVC sheathed armoured control cable
conforming to IS : 7098 (Part-I) 1988.
i) 4 core, 2.5 Sq.mm. 100.00 M 173.00 17300.00
ii) 8 core, 2.5 Sq.mm. 100.00 M 287.00 28700.00
iii) 12 core, 2.5 Sq.mm.100.00 M 414.00 41400.00
2.0 Laying of one number PVC insulated and PVC sheathed / XLPE
power cable of 1.1 KV grade of following size direct in ground
including excavation, sand cushioning, protective covering and
refilling the trench etc as required.
i) Upto 35 sq. mm 50 M. 195.00 9750.00
ii) Above 35 sq. mm and upto 95 sq. mm 100 M. 202.00 20200.00
iii) Above 95 sq. mm and upto 185 sq. mm 100 M. 210.00 21000.00
iv) Above 185 sq. mm and upto 400 sq. mm 200 M. 233.00 46600.00
3.0 Laying of one number additional PVC insulated and PVC
sheathed / XLPE power cable of 1.1 KV grade of following size
direct in ground in the same trench in one tier horizontal formation
including excavation, sand cushioning, protective covering and
refilling the trench etc as required.
i) Upto 35 sq. mm 50 M. 133.00 6650.00
ii) Above 35 sq. mm and upto 95 sq. mm 100 M. 141.00 14100.00
iii) Above 95 sq. mm and upto 185 sq. mm100 M. 149.00 14900.00
0.00
iv) Above 185 sq. mm and upto 400 sq. mm 100 M. 171.00 17100.00
4.0 Laying of one number PVC insulated and PVC sheathed / XLPE
power cable of 1.1 KV grade of following size in the existing
RCC/ HUME/ METAL pipe as required.
i) Upto 35 sq. mm 50 M. 16.00 800.00
ii) Above 35 sq. mm and upto 95 sq. mm 100 M. 25.00 2500.000.00 0.00
iii) Above 95 sq. mm and upto 185 sq. mm 100 M. 33.00 3300.000.00 0.00
iv) Above 185 sq. mm and upto 400 sq. mm 100 M. 58.00 5800.00
Stup Consultants P.Ltd 160 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
5.0 Laying of one number PVC insulated and PVC sheathed / XLPE
power cable of 1.1 KV grade of following size in the existing
masonry open duct as required.
i) Upto 35 sq. mm 100 M. 12.00 1200.000.00 0.00
ii) Above 35 sq. mm and upto 95 sq. mm 200 M. 20.00 4000.000.00
iii) Above 95 sq. mm and upto 185 sq. mm 200 M. 27.00 5400.000.00 0.00
iv) Above 185 sq. mm and upto 400 sq. mm 500 M. 50.00 25000.00
6.0 Laying and fixing of one number PVC insulated and PVC
sheathed / XLPE power cable of 1.1 KV grade of following size
on cable Tray as required.
i) Upto 35 sq. mm (clamped with 1mm thick saddle)350 M. 20.00 7000.00
ii) Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS
flat clamp)
1200 M. 48.00 57600.00
iii) Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm
MS flat clamp) 800 M. 59.00 47200.000.00 0.00
iv) Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm iv) Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm
MS flat clamp) 6400 M. 91.00 582400.00
7.0 Suppling and making indoor end termination with brass
compression gland and aluminium lugs for following size of PVC
insulated and PVC sheathed / XLPE aluminium conductor cable of
1.1 KV grade as required.
0.00
i) 3.5 core, 400 Sq.mm. 50 Set 1,369.00 68450.000.00 0.00
ii) 3.5 core, 300 Sq.mm. 28 Set 1,086.00 30408.00
iii) 3.5 core, 240 Sq.mm. 10 Set 969.00 9690.000.00 0.00
iv) 3.5 core, 185 Sq.mm. 4 Set 784.00 3136.00
v) 3.5 core, 150 Sq.mm. 4 Set 576.00 2304.000.00 0.00
vi) 3.5 core, 120 Sq.mm. 12 Set 484.00 5808.00
vii) 3.5 core, 95 Sq.mm. 10 Set 466.00 4660.000.00
viii) 3.5 core, 50 Sq.mm. 4 Set 342.00 1368.000.00 0.00
ix) 3.5 core, 35 Sq.mm. 6 Set 270.00 1620.000.00 0.00
x) 4 core, 25 Sq.mm. 6 Set 248.00 1488.00
xi) 4 core, 16 Sq.mm. 6 Set 245.00 1470.00
Stup Consultants P.Ltd 161 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
Supply and installation of following sizes of ladder type M.S.
cable trays made out of 75x20x2mm thick runners & 40x15x2mm
thick rungs at interval of 250mm complete with vertical bends,
reducers, tees, cross membrs and other accessories as required and
duly suspended from the ceiling with M.S. suspender or fixed at
wall with the help of suitable fixing arrangement including
painting (powder coating) etc. as required.
0.00 0.00
i) 900mm x 75mm x 2.0 mm 400 M. 1,500.00 600000.00
ii) 750mm x 75mm x 2.0 mm 300 M. 1,000.00 300000.00
iii) 600mm x 75mm x 2.0 mm 200 M. 900.00 180000.00
iv) 450mm x 50mm x 2.0 mm 250 M. 800.00 200000.00
8.0 Supply and installing following size of perforated M.S. cable trays
with perforation not more than 17.5% in convenient sections,
joints with connectors suspended from the ceiling with M.S.
suspenders and including bolts & nuts, painting suspenders etc. as
required.
i) 150 mm width X 50 mm depth X 1.6 mm thickness 50 M. 520.00 26000.00
ii) 300 mm width X 50 mm depth X 1.6 mm thickness 25 M. 789.00 19725.00
iii) 600 mm width X 50 mm depth X 2.0 mm thickness100 M. 1,386.00 138600.00
TOTAL LT CABLES CARRIED OVER TO THE
SUMMARY. 16464127.00
VI EXHAUST PIPING
1.0 Supply, installation, testing and commissioning of following sizes
MS ERW Black exhaust piping conforming to IS : 3589 complete
with all accessories such as bends, flanges etc. as required.
i) 500 mm dia MS pipe (4.85mm thick) 100M 17,945.89 1794588.82
ii) 450 mm dia MS pipe (4.85mm thick) 100M 15,449.45 1544944.82
iii) 400 mm dia MS pipe (4.85mm thick) 100M 13,758.45 1375845.50
iv) 350 mm dia MS pipe (4.85mm thick) 100M 7,742.08 774207.90
v) 300 mm dia MS pipe (4.85mm thick) 100M 6,892.13 689213.24
vi) 250 mm dia MS pipe (4.85mm thick) 50M 5,865.97 293298.33
Stup Consultants P.Ltd 162 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
vii) 200 mm dia MS pipe (4.85mm thick) 50M 4,676.93 233846.56
2.0 Supply and fixing of 80 mm thick LRB Mineral Wool / Rock wool
having thermal conductivity 0.034 K Cal/Hr-Sqm degree C/M and
density not less than 150Kg/m3
respectively with 24 SWG
aluminium cladding (around the existing exhaust pipe) suitable for
higher temperature complete with fixing arrangement as required
at site.
i) 500 mm dia MS pipe 100M 5,620.33 562032.75
ii) 450 mm dia MS pipe 100M 5,269.67 526966.89
iii) 400 mm dia MS pipe 100M 4,918.12 491812.03
iv) 350 mm dia MS pipe 100M 4,391.24 439124.24
v) 300 mm dia MS pipe 100M 3,864.36 386436.45
vi) 250 mm dia MS pipe 50M 3,512.82 175640.80
vii) 200 mm dia MS pipe 50M 3,161.27 158063.37
3.0 Fabrication, supply & erection of MS support for fixing of exhaust
piping and MS structure including Angle / chanels / flats / beam as
per approved drawings for supporting of DG exhaust stack from
basement floor level and above terrace level complete in all
respect.
20 TON 167,783.02 3355660.38
4.0 Supply and fixing of following size suspension type stainless steel
Bellows.
i) 500 mm dia 2 Nos. 46,446.24 92892.490.00
ii) 450 mm dia 2 Nos. 40,045.39 80090.78
iii) 400 mm dia 2 Nos. 32,962.80 65925.60
iv) 350 mm dia 2 Nos.28,056.25 56112.50
v) 300 mm dia 2 Nos.21,718.58 43437.17
vi) 250 mm dia 2 Nos.17,340.69 34681.38
TOTAL FOR EXHAUST PIPING CARRIED OVER TO
SUMMARY. 13174822.00
Note : The contractor / DG Set Vendor to confirm the Exhaust pipe
sizes and quantities matches the requirement of DG
manufacturer.
Stup Consultants P.Ltd 163 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
VII D.G. COOLING SYSTEM
1.0 Supply, installation, testing & commissioning of FRP induced
draught cooling tower suitable for complete with fan, motor,
surface & spray section, eliminators, steel supports as per
specification and requirement and consisting of following :-
- FRP water basin.
- PVC fillings with integral louvers and drift eliminators.
- Statically & dynamically balanced axial flow fan.
- TEFC Squirral cage induction motor.
- Suction screen, make up and quick fill arrangement, overflow &
drain connections with valves.
- Inspection ladder, access panel/door for maintenance.
- Anti vibration mountings, supporting channels etc. complete as per- Anti vibration mountings, supporting channels etc. complete as per
specifications & drawings. (All civil pedestral / foundation for
- Motor shall be suitable for 415V/+ 10% 50Hz AC power supply .
a) Rated heat rejection capacity suitable for 2000 KVA DG Sets
(Approx.200 TR). 3 Set 502,232.00 1506696.00
b) Rated heat rejection capacity suitable for 625 KVA DG Sets
(Approx. 60 TR). 1 Set 184,139.00 184139.00
2.0 Supply, laying/fixing, testing and commissioning of M.S. heavy
class ERW piping conforming to IS:l239 & 3589 with necessary
clamps, supports, anti vibration mountings, hangers and fittings
such as bends, tees, reducers etc. painted as per specifications:
i) 250 mm dia 50 M 5,865.97 293298.33
ii) 150 mm dia 50 M3,896.40 194820.22
iii) 100 mm dia 9 M2,659.31 23933.78
iv) 80 mm dia 18 M1,805.80 32504.45
v) 50 mm dia 5 M1,138.31 5691.53
vi) 32 mm dia 15 M690.64 10359.56
Stup Consultants P.Ltd 164 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
vii)25 mm dia 15 M
445.00 6674.97
Note :The contractor shall submit the certificates for suitablity to
Cooling Tower pipe sizes, Pumps and Scheme as per
manufacturer of DG Set from Manufacturer's authorised
person. If Manufacturer have the different scheme, then
submit the scheme and quantities3.0 VALVES & STRAINERS
Supply, fixing and testing of following valves, strainers, in the
D.G. cooling system piping complete with companion flanges, nut
bolts, gaskets, supports and painted etc. as per specifications.:
3.1 Butterfly / Ball valves :
i) 250 mm dia 14 Nos.26,675.86 373462.090.00 0.00
ii) 150 mm dia 14 Nos.8,675.69 121459.590.00 0.00
iii) 125 mm dia 1 Nos.7,627.27 7627.270.00 0.00
iv) 100 mm dia 3 Nos.6,084.91 18254.72
v) 80 mm dia 6 Nos. 4,873.62 29241.72
vi) 50 mm dia 4 Nos. 4,273.76 17095.05
3.2 Gate valve
i) 25 mm dia 4 Nos.1,811.14 7244.57
ii) 32 mm dia 4 Nos. 2,161.80 8647.21
3.3 Non return valves :-
0.00 0.00
i) 150 mm dia 4 Nos. 22,843.54 91374.15
ii) 80 mm dia 2 Nos. 8,862.58 17725.170.00
3.4 Y-strainers :-
i) 150 mm dia 4 Nos. 36,901.03 147604.13
ii) 80 mm dia 2 Nos.12,034.53 24069.06
3.5 Pot Strainers:-
0.00
i) 250 mm dia 2 Nos. 60,259.88 120519.760.00 0.00
Stup Consultants P.Ltd 165 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
3.6 Rubber Bellows
i) 150 mm dia 4 Nos. 6,783.55 27134.21
ii) 80 mm dia 2 Nos.4,096.65 8193.31
0.00 0.00
3.7 Balancing Valve
i) 150 mm dia 3 Nos. 75,891.78 227675.33
ii) 80 mm dia 1 Nos. 26,492.52 26492.520.00 0.00
3.8 Pressure Gauge
20 Nos. 3,124.78 62495.55
3.9 Temperature Gauge 8 Nos.3,124.78 24998.22
4.0 Supply, installation, testing & commissioning of monoblock pump
set with following LPM capacity & head with totally enclosed
2900 RPM, induction motor with class ‘B’ insulation suitable for
415volts, + 10% 3 phase, 50 Hz AC supply mounted on a common
structural base plate with 100mm dia pressure gauge at inlet &
outlet of pump with gun metal ball valve and piping, suitableoutlet of pump with gun metal ball valve and piping, suitable
antivibration pads complete as required.
i) 1760 LPM, 25 M Head. Nos. 100,242.00 400968.00
ii) 540 LPM, 25 M Head. Nos.43,887.00 87774.000.00 0.00
5.0 Supply, installation, testing and commissioning of M.V. cubicle
type totally enclosed free standing type, dust, damp and vermin
proof D.G. Auxillary Panel made out of 2mm thick CRCA Sheet
steel complete with aluminium busbars, ammeter, ammeter
selector switch, voltmeter, voltmeter selector switch, indicating
lamps, CT’s, interconnections with suitable capacity aluminium
leads/solid aluminium strips/ rods, interlocking, wiring powder
coated and having following incoming and outgoing moulded case
circuit breakers with rotary operating handle, starters, timers, etc.
complete as per drawing and specification. Panel shall have
starter with auto / manual mode. Pump & Cooling Tower fan of
respective DG Set shall automatically start on starting of
respective DG Set. PLC of Main L.T. Panel shall provide signal
command to start of Pump & Cooling Tower's fan. Wiring from
PLC to DG Auxillary Panel shall deemed to be included in quoted
rate of DG Auxillary Panel.
1 Set 877,638.84 877638.84
(Note:- All MCB shall be of motor duty)
Stup Consultants P.Ltd 166 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
INCOMING
- 2 Nos. 160Amp TP MCCB with neutral link.
- 2 Nos. 160 Amp FP Power contactor. (AC-3)
- 2 No. 0 to 500 volt voltmeter with selector switch.
- 2 Nos. 0 to 160Amp ammeter with selector switch with C.T’s.
- 2 Set of phase indicating lamp with HRC fuses.
- 2 Nos. electronics type three phase 160/5Amp CT type KWH
meter with sealing and lockable arrangement.
- Electrical interlocking between incoming contactors.
BUSBARS
- 200Amp TPN busbar of aluminium alloy.
OUTGOINGOUTGOING
- 6 Nos. 63Amp FP Miniature circuit breaker with Star/Delta Starter
suitable for DG Cooling pump (10 HP).
- 6 Nos. 40Amp FP Miniature circuit breaker with DOL Starter
suitable for DG Cooling fan of 5 HP.
- 7 Nos. 16Amp FP Miniature circuit breaker with DOL starter
suitable for priming pump & HSD pumps (3 HP).
- 1 No. 16Amp FP Miniature circuit breaker with DOL starter for
spare.
- 1 No. 40Amp FP Miniature circuit breaker with DOL starter for
spare.
- 1 No. 63Amp FP Miniature circuit breaker with Star/Delta Starter
for spare.
- (Starter rating shall be as per motor sizes) Contactor shall be
AC -3 duty
- Each DOL starter shall essentially have following.
* 1 No. FP Power contactor.
* 1 No. Overload relay with single phase preventer (MN-Type)
* 1 No. PLC./Manual selector switch.
* 2 No. start/stop push buttons.
Stup Consultants P.Ltd 167 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
* 2 No. ON/OFF indicating lights.
* 1 No. Direct type ammeter.
* 1 No.Auxillary contacts (4NO+ 4 NC).
* 1 Set control fuses.
- Each Star / Delta Starter shall essentially have following.
* 3 No. FP Power contactor.
* Timer for fully automatic operation.
* 1 No. Overload relay (MN-Type)
* Single phase preventor
* 1 No. PLC./Manual selector switch.
* 2 No. start/stop push buttons
* 2 No. ON/OFF indicating lights.
* 1 No. Direct type ammeter.
* 1 No.Auxillary contacts (4NO+ 4 NC).
* 1 Set control fuses.
7.0 Supply and fixing of 40Amp four pole Isolator (MCB Type) in
sheet steel enclosure (Weather proof type) to be mounted on wall
or suitable bracket near Cooling Tower fan motor complete as
required.
4 No. 8,899.96 35599.86
TOTAL FOR DG COOLING SYSTEM CARRIED OVER
TO SUMMARY. 5021412.17
VIII ACCOUSTIC INSULATION OF DG SET ROOM
Stup Consultants P.Ltd 168 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
1.0 Providing and fixing acoustic treatment lining on walls and ceiling
of DG room by means of 25mm thick resin bonded 32 kg/m2
density glass wool laid on a 600 mm x 600 mm grid 25x40x25 GI
channel of 22 SWG (Tisco/SAIL/ Jindal ) framework fixed to
walls and ceilings covered with glass fiber tissue paper including
cladding of the glass wool insulation with 22 SWG GI
perforated 40% perforation GI sheet complete with GI
hardware as required.
400 Sq.M 5,306.16 2122463.51
2.0 Providing and fixing of double openable acoustic doors for DG
room comprising of frame made of M.S. sheet 14 SWG (2mm
thick) frame clad on both sides with 2 mm thick MS sheets with
cavity fill of 75 mm thick resin bonded glass wool of 32 kg/m2
density including nitrile rubber gaskets between MS sheet
cladding and frame of MS tube 100 x 40 mm of 14 SWG, self
lubricating double openable door mechanism and heavy duty
hardware/ locking mechanism etc. complete as required.
18 Sq.M 26,302.06 473437.17
3.0 Providing and fixing of Accostic Louvers for Fresh Air/ Exhaust
Air Ventillation in DG Room
60 Sq.M 25,000.00 1500000.00
Note :-
The minimum norms of insertion loss of 25 dBA at a distance of
0.5 m from the DG room. The contractor shall arrange the testing
of the same as per norms of central pollution board.
TOTAL OF ACOUSTIC INSULATION CARRIED OVER
TO SUMMARY. 4095900.68
IX FUEL HANDLING EQUIPMENT
1.0 Supply, installation, testing & commissioning of 30 KL capacity
mild steel horizontal cylindrical underground HSD tank (2.65M
dia & 6.0M length) with shell 6mm and end plate 10mm thick
suitable for underground installation complete with manhole
accessories, fittings, piping inside the tank Decanting hose, foot
valve, dip stick etc. with paint with inside surface scrapped clean.
Underground HSD Tank shll be conform to IS 10987 : 1992 and
shall be tested at works under hydrostatic pressure of 5 psi before
being painted with two coats of Red Oxide Primer complete with
manhole accessories, fittings, piping inside the tank Decanting
hose, foot valve, dip stick etc. with paint with inside surface
scrapped clean complete as required as per specifications and as
required by the concern authorities.
1 Set 1,419,084.19 1419084.190.00 0.00
Stup Consultants P.Ltd 169 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
2.0 Supply and fixing of 990 Litres Over Flow tank made out of 3mm
thick MS Sheet and as per CCE Norms including providing high
and low level sensors with inlet and outlet connections for Diesel
Pipes, painting, wiring from sensor to pump starting panel etc. as
per specifications. 2 Set 70,954.08 141908.150.00
3.0 Supply, fixing, testing and commissioning of M.S. heavy class
ERW piping (Class-C) conforming to IS : l239 with necessary
clamps, supports, anti vibration mountings, hangers and fittings
such as bends, tees, reducers etc. painted as per specifications and
approved drawing.0.000.00
i) 80 mm dia 1 M1,805.80 1805.800.00 0.00
ii) 50 mm dia 1 M 1,138.31 1138.310.00 0.00
iii) 40 mm dia 1 M802.78 802.780.00 0.00
iv) 32 mm dia 1 M 690.64 690.640.00 0.00
v) 25 mm dia 1 M534.00 534.00
4.0 VALVES & STRAINERS
Supply, fixing and testing of following valves, strainers, in the
H.S.D. Fuel Handling System piping complete with companion
flanges, nut bolts, gaskets, supports and painted etc. as per
specifications :
5.1 Ball valves :0.00 0.00
i) 80 mm dia 1 Nos. 12,074.58 12074.58
ii) 50 mm dia. 1 Nos.4,070.84 4070.84
0.00 0.00
iii) 25 mm dia. 1 Nos.1,381.27 1381.270.00 0.00
5.2 Non return valves :-
0.00 0.00
i) 25 mm dia 1 No. 5,023.14 5023.14
5.3 Y - strainer :-
i) 25 mm dia. 1 No.3,552.87 3552.87
5.4 POT - strainer :-
0.00 0.00
i) 80 mm dia 1 Nos.10,503.74 10503.74
Stup Consultants P.Ltd 170 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
ii) 25 mm dia. 1 Nos.5,708.44 5708.44
5.0 Supply & erection of 3 HP Flame Proof positive displacement type
HSD pump inside the fuel tank yard having mechanical seal
complete with all accessories, fixing on M.S. channel including
making earthing as required.
i) Suction head not less than 3.5 m
2 Nos. 82,049.66 164099.32
6.0 Supply and fixing of flow meter for diesel line as required.
i) 80 mm dia 1 Nos.57,084.37 57084.37
ii) 50 mm dia. 1 Nos.48,521.72 48521.72
iii) 32 mm dia. 1 Nos.43,098.97 43098.97
TOTAL FOR FUEL HANDLING EQUIPMENT CARRIED
OVER TO SUMMARY. 1921083.13
X EARTHING & SAFETY EQUIPMENT
1.0 Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick
including accessories, and providing masonry enclosure with cover
plate having locking arrangement and watering pipe of 2.7 metre
long etc. with charcoal/ coke and salt as required.14 Set 9,292.00 130088.00
2.0 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick
including accessories, and providing masonry enclosure with cover
plate having locking arrangement and watering pipe of 2.7 metre
long etc. with charcoal/ coke and salt as required.
20 Set 4,490.00 89800.00
3.0 Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including
accessories, and providing masonry enclosure with cover plate
having locking arrangement and watering pipe etc. with
charcoal/coke and salt as required. 2 Set 3,926.00 7852.00
4.0 Providing and fixing of following copper strip on surface of wall/
trench or in recess for connection etc. as required.0.00 0.00
i) 75mm x 6 mm 200 M. 4,844.25 968850.120.00 0.00
ii) 50mm x 6mm 100 M. 3,776.25 377625.49
5.0 Providing and fixing of following G.I. earth strip on surface/trench
existing cable tray etc. as required.
i) 75mm x 6mm 300 M. 672.84 201851.19
Stup Consultants P.Ltd 171 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
ii) 50mm x 6mm 200 M. 448.56 89711.64
iii) 40mm x 6mm 200 M 384.48 76895.69
iv) 25mm x 6mm 100 M 289.25 28924.88
Providing & laying of following sizes of GI pipe in ground from
earth electrode as required.
i) 80mm dia 100 M 1,911.71 191171.24
ii) 65mm dia 75 M 1,476.50 110737.81
SAFETY EQUIPMENTS
i) Rubber hand gloves suitable for 33KV.1 Pair 3,582.24 3582.24
ii) Shock treatment chart both in Hindi & English for treating person
suffering due to electric shock mounted on wall hooks. 2 No. 1,333.21 2666.430.00 0.00
iii) Providing & fixing H.T. danger notice plate of 250mm x 200mm,4 No.made of mild steel, at least 2mm thick & vitreous enamelled white 4 No. 1,548.59 6194.38
iv) Providing & fixing M.V. danger notice plate of 200mm x 150mm
made of mild steel, atleast 2mm thick and vitreous enamelled 4 No. 3,038.45 12153.79
v) Carbon dioxide fire extinguishers of 9 Kgs. each mounted on wall
hook / trolley mounted as per IS 2878-1976. 4 No. 14,578.14 58312.570.00 0.00
vi) Dry chemical fire extinguisher 5 Kg as per IS : 2171-19764 No. 28,660.56 114642.22
vii) G.I. Fire buckets 4Nos. 9 litre capacity filled with dry sand and
fixed on wall hook made out of 13mm dia MS rod & conformation 2 No. 1,289.60 2579.21
viii
)
First aid box containing material as prescribed by St. John
ambulance brigade or Indian Red Cross complete as required. 1 No. 2,435.92 2435.92
ix) Supply & fixing of fire retardant/ extinguishing Electrical
insulated synthatic mat of 2.0 mm thick +/- 10% confirming to
BIS: DOC NO. ET-02 (5440) meeting requirments of IS: 15652
:2006 (with upto date amendment), suitable for all voltages not
exceeding 3.3 KV and having minimum width of 1000 mm +/-
20mm and including supply of required quantity of adhensive/
compound and fixing the same at size as per site requirments.100 M 4,338.73 433873.26
x) Supply & fixing of fire retardant / extinguishing Electrical
Insulated synthetic mat of 10 mm thick + 10% conforming to latest
BIS: DOC NO. ET-02 (5440) meeting requirements of IS 3043, IS
5216 (part-1, 2&3), IS 8437 and IEC 479, suitable for all voltages
not exceeding 33 KV AC and having minimum width of 1000 mm
+/- 20 mm and including supply of required quantity of adhensive
/ compound and fixing the same at site as per site requirement.
15 M 3,239.59 48593.81
Stup Consultants P.Ltd 172 of 234
S.NO. Description QTY Unit RATE (INR) AMOUNT (INR)
Bill of Quantities- Substation Work
xi) Providing and fixing of DMC/SMC insulator for supporting
neutral earth strips. 350 No. 53.40 18689.93
8.0 Supply and erection of RCC Hume pipe in ground complete with
excavation and refilling / on surface / on RCC slab complete as
i) 300 mm dia 25 M 1,438.23 35955.86
ii) 150 mm dia 25 M 799.22 19980.42
TOTAL FOR EARTHING & SAFETY EQUIPMENTS
CARRIED OVER TO SUMMARY 3033168.09
Stup Consultants P.Ltd 173 of 234
ITEM DESCRIPTION
A. FIRE FIGHTING ITEMS
B. FIRE PUMPS
TOTAL 137324650
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW IN U.P.
SUMMARY OF COSTS-FIRE FIGHTING
AMOUNT
134224816
3099833
Stup Consultants P.Ltd 174 of 234
SCHEDULE OF QUANTITIES
1
2
3
4
a
All materials, fixing materials, accessories, appliances tools, plants, equipment, transport, labour and
incidentals required in preparation for and in the full and entire execution, testing, balancing,
commissioning and completion of work called for in the item and as per Specifications and Drawings.
b Wastage on materials and labour.
c
Loading, transporting, unloading, handling/double handling, hoisting to all levels, setting, fitting and fixing
in position, protecting, disposal of debris and all other labour necessary in and for the full and entire
execution and for the job in accordance with the contract documents, good practice and recognize
principles.
d Liabilities, obligations and risks arising out of Conditions of Contract.
e
All requirements of Specifications, whether such requirements are mentioned in the item or not. The
Specifications and Drawings where available, are to be read as complimentary to and part of the
Schedule of Quantities and any work called for in one shall be taken as required for all.
f
In the event of conflict between Schedule of Quantities and other documents including the
Specifications, the most stringent shall apply. The interpretation of the Consultant/Project Manager shall
be final and binding.
gTenderer has to include the rate of all items/ operations as mentioned in the Technical Specifications as
applicable and for all Heights and levels as required to complete the system at site
5
6
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW IN U.P.
GENERAL NOTES FIRE FIGHTING WORKS :
All items of work under this Contract shall be executed strictly to fulfill the requirements laid down under
“Basis of Design” in the specifications. Type of equipment, material specification, methods of installation and
testing and type of control shall be in accordance with the specifications, approved shop drawings and the
relevant Indian Standards, however capacity of each component and their quantities shall be such as to fulfill
the above mentioned requirement.
The unit rate for all equipment or materials shall include cost in INDIAN RUPEES (INR) for equipment and
materials including all taxes and duties and also including forwarding, freight, insurance and transport into
Contractor’s store at site, storage, installation, testing, balancing, commissioning and other works required.
For all imported items Owners shall arrange EPCG licence and open L/C in the name of principals. Rates for
all imported items shall be quoted in US Dollars. During award of work Owner shall be at liberty to ask for
proforma invoice in any convertible foreign currency. All relevant document for import shall be taken care by
the contractor. Port charges / octroi / inland transportation etc. upto site shall be paid on actuals subject to
ceiling of quoted amount.
The rate for each item of work included in the Schedule of Quantities shall, unless expressly stated otherwise,
include cost of :
The Contractor shall procure and bring Materials/Equipment to the site only on the basis of drawings
approved for construction and shop drawings and not on the basis of Bill of Quantities which are approximate
only. This also applies to the Contractor’s requisition for Owner supplied materials.
The work shall be carried out in conformity with the drawings and within the requirements of architectural,
Plumbing, HVAC, Electrical, Structural and other specialized services drawings.
Stup Consultants P.Ltd 175 of 234
GENERAL NOTES FIRE FIGHTING WORKS :
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
The contractor shall , from time to time, clear away all debris and excess materials accumulated at the site
failing which the same shall be done by Project Manager at contractor’s risk and cost and cost of clean up
shall be deducted from the contractors prorata bill.
After the fixtures, equipment and appliances have been installed and commissioned, contractor shall cleanup
the same and remove all plaster, paints, stains, stickers and other foreign matter or discoloration leaving the
same in a ready to use condition.
On completion of all works, contractor shall demolish all stores, remove all surplus materials and leave the
site in a broom clean condition, failing which the same shall be done by the Project Manager at the
Contractor'’ risk and cost. Cost of the cleanup shall be deducted from the contractor’s bills on pro-rata basis
in proportion to his contact value.
In the event of an error occurring in the amount of the Schedule, as a result of wrong extension of the unit rate
and quantity, the unit rate quoted by the tenderer shall be regarded as firm and the extensions shall be
amended on the basis of rates.
Any error in totaling in the amount column and in carrying forward total shall be corrected. Any error, in
description or in quantity, omission of items from this Schedule shall not vitiate this Contract but shall be
corrected and deemed to be variation required by the Consultant/Project Manager.
Rates have been called for a number of items of works, as alternatives which, for the present do not form part
of the total value of tender. However the rates for these items shall be quoted, with due care so that in the
event of choice of an alternative item of work, said rate shall form part of the contract and shall not violate the
contract any way.
Any pipe crossing fire rated wall as per fire compartmentation will be provide with higher size of GI sleeve. All
floor crossing pipes will be provided with higher size GI sleeve.
This Schedule shall be fully priced and the extensions and totals duly checked. The rates for all items shall be
filled in INK including NIL items.
No alteration whatsoever is to be made to the text or quantities of this Schedule unless such alteration is
authorised in writing by Consultant. Any such alterations, notes or additions shall, unless authorized in writing,
be disregarded when tender documents are considered.
Shop drawings are detailed working drawings coordinated with other trading work, which incorporate the
contractor’s details for execution of the work and incorporate equipment manufacturer’s details and
dimensions to ensure that the same can be installed in the space provided.
All shop drawings should detail pipe routing and levels, showing location of other services at crossings etc.,
cable runs, route cable trays etc. and all allied works and must be fully coordinated with other services, before
execution of the works.
All shop drawings will be made on AutoCAD and colored prints has to be produced for site work.
On award of the work the contractor shall be issued set of consultant’s drawings. The drawings shall be the
basis of contractor’s shop drawings.
The contractor shall cooperate with all trades and agencies working on the site. He shall make provision for
hangers, sleeves, structural openings and other requirements well in advance to prevent hold up of progress
of the construction schedule. All supports to the civil structure shall be provided with anchor fasteners.
On award of the work, contractor shall submit a schedule of construction in the form of a PERT chart or BAR
chart for approval of the Project Manager.
Stup Consultants P.Ltd 176 of 234
1 Providing, Fixing, testing and commissioning of following sizes of MS
over Ground pipes confirming to IS:1239-Part-1, Heavy grade, C-Class /
3589 - 6mm thick . It shall be complete with all fittings including but not
limited to bends, elbows, flexible joints at the building joints, tees,
reducers, sockets, flanges, gaskets, nut bolt, washers etc. It includes the
supporting by means clevis type hanger for ceiling support using anchor
fasteners of suitable sizes, sleeves, finishing of pipes by means of two
coats of zinc chromate primer and two coats of synthetic enamel paint,
complete in all respect as per technical specifications and all requirements
of contract works.
1.1 250 mm Meter 18 6154 110772
1.2 200 mm Meter 30 4760 142800
1.3 150 mm Meter 8875 1951 17315125
1.4 100 mm Meter 1850 1355 2506750
1.5 80 mm Meter 3688 987 3639563
1.6 65 mm Meter 6690 797 5331930
1.7 50 mm dia Meter 5358 680 3643100
1.8 40 mm dia Meter 4059 518 2102433
1.9 32 mm dia Meter 2684 458 1229158
1.10 25 mm dia Meter 45519 385 17524719
1.11 Providing, Fixing, testing and commissioning of following sizes of MS
pipes confirming to IS:1239-Part-1, Heavy grade, C-Class. It shall be
complete with all required fittings including but not limited to
Flanges,bends, elbows, tees, reducers, sockets,Gaskets,Bolts,Nuts &
Washers etc. painting with one coat of solvent based rubberised asphaltic
primer and wrapping with a multi layered pipe coat hyper puncture
resistant non woven polyster mat (minimum 4 mm thk) as per
manufacturer recommendations including necessary excavations refilling,
masonry supports complete in all respect as per technical specifications
and all requirements of contract works.
1.11.1150 mm dia
Meter 1200 1959 2350800
2 Providing, Fixing, testing and commissioning of following sizes of forged
lever operated brass ball valve for sprinkler system drain as per technical
specifications and all requirements of contract works.
2.1 25 mm Each 80 998 79840
Bill of Quantities- Fire Fighting Work
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW IN U.P.
AMOUNT (INR)DESCRIPTION OF ITEMSS.NO. UNIT QUANTITYRATE
(INR)
Stup Consultants P.Ltd 177 of 234
Bill of Quantities- Fire Fighting Work
AMOUNT (INR)DESCRIPTION OF ITEMSS.NO. UNIT QUANTITYRATE
(INR)
3 Providing, Fixing, testing and commissioning of following sizes of cast
iron, non rising bronze spindle sluice valve, confirming to IS standards as
per specifications complete with suitable MS flange, gaskets, nut-bolts &
washers and suitable for test pressure up to 1.5 times the working
pressure of system as per technical specifications and all requirements of
contract works.
3.1 250 mm Each 1 76440 76440
3.2 200 mm Each 5 51925 259625
3.3 150 mm Each 9 31861 286749
3.4 100 mm Each 1 20729 20729
4 Providing, fixing, testing and commissioning of flanged pattern ductile
iron body and disc butterfly valve with flanges, gasket, nut-bolts &
washers as per specifications, meant for horizontal or vertical mounting,
complete as per specifications and all requirements of contract works.
4.1 150mm Each 94 9328 876832
4.2 100 mm Each 1 8019 8019
4.25 80 mm Each 5 7595 37975
4.3 65 mm Each 1 7171 7171
4.4 50 mm Each 2 5516.1538 11032
5 Providing, Fixing, testing and commissioning of following sizes of cast
iron body, bronze trim and disc check valves, wafer type, confirming to IS
standards complete with flanges, gasket, nut bolts as per specifications,
suitable for horizontal & vertical mounting, suitable for test pressure up to
1.5 times the working pressure of system as per technical specifications
and all requirements of contract works.
5.1 200 mm Each 1 25848 25848
5.2 150 mm Each 11 11810 129910
5.3 65 mm Each 1 6169 6169
5.4 80 mm Each 80 7592.6154 607409
5.5 50 mm Each 2 4745.3846 9491
Stup Consultants P.Ltd 178 of 234
Bill of Quantities- Fire Fighting Work
AMOUNT (INR)DESCRIPTION OF ITEMSS.NO. UNIT QUANTITYRATE
(INR)
6 Providing, fixing, testing and commissioning of precharged air vessel
(size 450 mm dia & 2000 mm height) for pressurization of hydrant /
sprinkler system complete with adequate pressure switches (as per design
/ requirement) with valves to operate as per operating sequences
including 40 mm NB drain valve, air release valve with stop cock on the
top, minimum 50 mm dia inlet with isolating valve duly painted from
inside and outside with two coats of synthetic enamel paint over a coat of
primer complete as required. (Vessel should be suitable for rated working
pressure).
Each 1 52490.025 52490
7 Providing, Fixing, testing and commissioning of single headed gun metal
fire hydrant valve, oblique pattern with 80mm dia flanged inlet, brass
spindle control and 63mm dia female instantaneous coupling complete
with rubber cap and chain for internal hydrants as per technical
specifications and all requirements of contract works.
Each 194 12929 2508226
8 Providing, Fixing, testing and commissioning of wall mounted, swinging
type first aid fire hose reel with drum, hanging bracket, 30 meters long &
20mm dia high pressure hose reel tube with hose clamps, gun metal shut-
off nozzle with shut off valve, orifice plate to restrict pressure maximum
to 4.5 bars, necessary ball valve, GI union, dia 25mm pipe from riser to
hose reel mounted on adjoining wall by means of anchor fasteners as per
technical specifications and all requirements of subcontract works.
Each 172 14809 2547148
9 Providing and fixing 63 mm dia, 15 meters long hoses for internal and
external hydrants with gun metal male and female coupling at both ends,
bound and riveted to hose pipe with 1.5mm copper wire complete as per
technical specifications and all requirements of subcontract works.
9.1 Non percolating RRL (For Internal Hydrant) Each 344 9775 3362600
9.2 Controlled Percolating (For external Hydrant) Each 44 8452 371888
10 Providing and fixing 63 mm dia male outlet Stainless Steel branch pipe
with nozzle of 20mm nominal bore outlet as per technical specifications
and all requirements of subcontract works suitable to fit with
instantaneous type 63 mm dia female coupling of Hoses as required.
Each 194 3236 627784
11 Providing and fixing 100mm dia bourden type, stainless steel, dial type
pressure gauge complete with brass isolation valve as per technical
specifications and all requirements of contract works.
Each 125 910 113750
Stup Consultants P.Ltd 179 of 234
Bill of Quantities- Fire Fighting Work
AMOUNT (INR)DESCRIPTION OF ITEMSS.NO. UNIT QUANTITYRATE
(INR)
12 Providing and fixing standard firemans axe with heavy rubber handle.
Each 194 1547 300118
13 Providing, Fixing, testing and commissioning of 4-way gun metal fire
brigade inlet connection consisting of 4No, 63mm dia instantaneous
female couplings with cap and chain, in built check valves, 150mm dia
flange outlet complete with 1no. 150mm dia Sluice valve, 1no 150mm dia
check valve, in glass fronted MS cabinet as per technical specifications
and all requirements of contract works.
Each 1 105524 105524
14 Providing, Fixing, testing and commissioning of gun metal fire brigade
suction hose coupling (Draw out connection) with nut for female coupling
as per IS specifications complete with 100mm dia GI pipe connection and
100mm dia foot valve (To be provided inside water tank), glass fronted
MS cabinet complete as per technical specifications and all requirements
of contract works.
Each 3 35458 106374
15 Providing and fixing of MS fire hose cabinet of size 2100 x 900 x 600
fabricated complete with 2mm thick sheet, 4mm thick front glass,
necessary locking arrangement with allan key, supporting arrangement,
painted with approved colour & paint as per technical specifications and
all requirements of contract works. (For Internal). Each 172 12075 2076900
16 Providing and fixing of MS fire hose cabinet of size 750 (length) x 600
(width) x 250mm (depth) hydrant cabinet fabricated complete with 4mm
thick front glass, necessary locking arrangement with allan key,
supporting arrangement, painted with approved colour & paint as per
technical specifications and all requirements of contract works. (For
External).
Each 22 4833 106326
17 Supply, installation, testing and commissioning of dia 150 mm, flanged
type water flow alarm check valve with ductile iron body, bronze seat ring
and cast iron /ductile iron clapper, suitable for operation in working
pressure range of 1.4 bars to 20 bars complete with pressure gauges with
brass isolation valves, by-pass check valve, main drain valve, alarm test
valve, turbine principled alarm gong, strainer and test terminal box as per
technical specifications and all requirements of contract works.
Each 10 62455 624550
18 Providing, fixing, testing and commissioning of 15/20mm nominal dia
outlet, quartzoid bulb type sprinkler heads made of high quality material
as described in technical specifications and all requirements of contract
works suitable to operate as per specified temperatures.
18.1 Quick Response Side Wall Each 175 471 82425
18.2 Quick Response Upright Sprinkler Each 9275 405 3756375
18.3 Quick Response Pendent Sprinkler Each 18075 405 7320375
Stup Consultants P.Ltd 180 of 234
Bill of Quantities- Fire Fighting Work
AMOUNT (INR)DESCRIPTION OF ITEMSS.NO. UNIT QUANTITYRATE
(INR)
18.4 Providing & fixing water curtain nozzle in Brass (ASTM B'16) suitable
for 20 to 100 psi effective working pressure, with 1/2" BSPT inlet, K-33
and coverage of 2.5 meter either side at 1.4 Bar Each 2375 356 845500
19 Providing and fixing electrically operated deluge valve complete with
strainer, emergency release station, pressure guage and other accessories
complete as required for proper functioning of the deluge valve. The
deluge valve shall be double interlocked and will get operted on getting
the signal from both fire detection panel as well as sprinkler system
simultaneously to operate.19.1 150 mm dia Each 36 98655.868 3551611
20 Providing, fixing, testing & commissioning of U.L.listed corrugated SS-
304 Braided flexible sprinkler pipe droplet for 12 kg/ sq. cm. working
pressure with 1/2" BSP threaded outlet & 1" BSP threaded inlet with
reducer nipple, snap, clamp, T-bar bracket etc. with necessary fitting
complete as required.
20.1 1500 mm length Each 15000 1532 22980000
21 Providing and Fixing of electrically operated water flow switches (Vane
type) of following dia including tamper switch and accessories, complete
with tap off socket arrangement as required, with potential free contact
with 2 No. NONC.
21.1 For 100mm dia Pipe Each 1 5892 5892
21.2 For 65mm dia Pipe Each 1 5892 5892
21.3 For 150mm dia Pipe Each 7 8838 61866
21.2 For 80mm dia Pipe Each 80 4713.6 377088
22 Providing and fixing inspectors 25mm dia test assembly complete with
test valve, sight glass sectional drain valve, union; necessary piping,
threading, jointing & with corrosion resistant orifice all complete strictly
as per drawing.
Each 90 15169.617 1365266
23 Providing and fixing C.I.`Y' strainer with bronze perforated sheet basket
including rubber gasket, flanges, nuts, bolts and washers, complete as
required.
23.1 200mm dia Each 3 38047 114141
23.2 80mm dia Each 2 6000 12000
24 Providing, fixing, testing & commissioning of MS air cushion tank on top
of each riser fabricated from 6mm thick MS plate, 200 mm in diameter
and 1.2 m in height with dished ends fabricated from 6 mm thick MS
plate with Air release valve & stop cock, flanged inlet connection with all
accessories as required and conforming to IS 4736-1968. (The cushion
tank should be tested for 2 times working pressure).
No. 12 21310 255720
Stup Consultants P.Ltd 181 of 234
Bill of Quantities- Fire Fighting Work
AMOUNT (INR)DESCRIPTION OF ITEMSS.NO. UNIT QUANTITYRATE
(INR)
25 Providing, Fixing, testing & commissioning of 25mm dia spring actuated
air release valve, suitable for pressure 1.5 times the working pressure of
system, threaded type complete as per standard, specifications & all
requirements of contract works.
Each 17 2800 47600
26 Supply and fixing of following types of fire extinguishers confirming to
codes & standards, capacity and associated accessories as mentioned in
technical specifications and all requirements of contract works.
26.1 6 Kg ABC Dry Chemical type Each 100 4362 436200
26.2 9 Litres water CO2 Each 100 4988 498800
26.3 4.5 Kg CO2 Each 50 10872 543600
26.4 9.0 Litres AFFF Each 50 5238 261900
27 Constructing brick masonary chamber (for housing valve) in brick work
with bricks of class 75 in cement mortar 1:5 (1 cement : 5 fine sand) 12
mm thick plaster on inside with a floating coat of neat cement &rough
plaster on external faces with cement mortar 1:3 (1 cement : 3 coarse
sand. Including providing R.C.C. top slab complete in all respect. Cost
shall be inclusive of excavation in earth, shoring, dewatering, support to
valve and access rungs as required to complete the work.
27.1 Size 900 x 900 x 1000 mm deep No. 3 9500 28500
27.2 Providing & fixing CI medium duty manhole cover with frame of 560
mm internal dia for valve chamber. No. 3 2500 7500
28 Supplying and installing at approved location approved make fire
buckets of 24 gauge galvanized steel sheet confoming to IS: 2546,
standard 9 litre capacity and of round bottom shape, painted white inside
and red outside and black on the bottom, inscribed with letters “FIRE” in
black and gold. Cost shall be inclusive of providing MS stand duly
painted over a coat of primer. No. 25 500 12500
29 Supply, Installation, Testing and Comissioning of Automatic Fire
suppression and Detection system (containing clean agent
Novec1230/ HFC 227ea/ Low Pressure CO2/ other clean agent as
per NFPA2001), CCE approved Seamless Cylinder with
accessories viz. Automatic Discharge Valve and Pressure Gauge,
Isolation Valve etc.),MS Piping with fittings,Pipe
Supports,Discharge Nozzles.The System will be designed &
installed in accordance with NFPA 2001/relevant & pertinent Indian
Standard for server room/s each measuring 12MX6MX4 M ht. with
complete assembly of adequate capacity for Server rooms.Fire
Detection System based on conventional Multi-sensor Detectors
and Control Panel as per NFPA 72/ relevent & applicable Indian
Standard/s for agent Release complete with all other devices &
components i.e.Manual Release Unit,Manual Abort Unit,Electrical
Cabling,Alarm Sounders,Battery Charging Unit,Battery Bank of
Adequate Capacity and Warning Signs are included in this item,Lot 2 3680000 7360000
30 Pre-Engineered Automatic Clean Agent Fire Detection &
Suppression System for small electrical panels
Stup Consultants P.Ltd 182 of 234
Bill of Quantities- Fire Fighting Work
AMOUNT (INR)DESCRIPTION OF ITEMSS.NO. UNIT QUANTITYRATE
(INR)
30.1 Supply, Installation, Testing and Comissioning of pre-engineered
Polymer Detection Tube based clean agent( HFC 227ea/ Novec
1230 /other agents as per NFPA 2001) consisting of Cylinder
Discharge Head Assembly, DOT/CCE approved Cylinder,
Pressure Gauge ,other accessories as & if required viz. Isolation
Valve, Pressure Swich, Pushin tube connector/ compression fitting
at discharge outlet and first fill of fire extinction agent , of following
capacity.
i. 1 Kg Nos. 100 30000 3000000
ii. 2 Kg Nos. 70 45000 3150000
30.2 Supply, Installation, Testing and Comissioning of Linear
Pneumatic Heat Detection Tube ( Rated at 90 Degree
Centigrade,Colour Code-Black ) complete with SS Pushin/
compression fittings such as Straight Connector, Tee Connector or
Cross Connector.
RM 3500 1500 5250000
31.0 HIGH PRESSURE CO2 GAS BASED SYSTEM
Supply, fixing, testing and commissioning of Fixed High Pressure
CO2 Fire Detection & Suppression System for Electrical Panels ,
for DG Sychronizing Panel, Main LT Panel and HT Panel
consisting of the following components:
31.1 2 Nos. CCE Approved Seamless CO2 cylinders 45 Kg Capacity
each (1 Working + 1 Standby) complete with Automatic Discharge
Valve ,High Pressure Flexible Hose,Discharge Manifold
,Seamless Schedule 80 Pipe Work,Diverting Valve & Nozzles ,Pilot
Nitrogen Cylinder and interconnecting high pressure
tubing,Detection System & Gas Release Panel,all Other required
Devices viz.Electronic Sounder,Linear Heat Sensing Cable,Manual
Release Unit,Manual Abort Unit,Electrical Cabling,Battery Bank &
Battery Charger,Warning Sign as required according to IS-
15528/NFPA12Set 1 1000000 1000000
31.2 6 Nos. CCE Approved Seamless CO2 cylinders 45 Kg Capacity
each (3 Working + 3 Standby) complete with Automatic Discharge
Valve ,High Pressure Flexible Hose,Discharge Manifold
,Seamless Schedule 80 Pipe Work,Diverting Valve & Nozzles ,Pilot
Nitrogen Cylinder and interconnecting high pressure
tubing,Detection System & Gas Release Panel,all Other required
Devices viz.Electronic Sounder,Linear Heat Sensing Cable,Manual
Release Unit,Manual Abort Unit,Electrical Cabling,Battery Bank &
Battery Charger,Warning Sign as required according to IS-
15528/NFPA12Set 1 250000 250000
31.3 Weight Measurement and warning Device for Each Cylinder &
associated accessories No. 8 50000 400000
Note: The items indicated above are notable items. The vendor to
include all allied and implied items in required quantity at no extra
cost.
Stup Consultants P.Ltd 183 of 234
Bill of Quantities- Fire Fighting Work
AMOUNT (INR)DESCRIPTION OF ITEMSS.NO. UNIT QUANTITYRATE
(INR)
TOTAL CARRIED TO SUMMARY 134224816
B. FIRE PUMPS
1 Supply, installation, testing and commissioning of electric driven fire
pump set for Sprinkler and hydrant system, complete with electric motor
mounted on common rigid drip-rim base, with power transmission from
the driver by means of listed and approved flexible couplings, suitable for
automatic / manual operation as per technical specifications, all
requirements of contract works and consisting of following:
Horizontal split casing, high pressure Multi / Single stage, centrifugal
pump complete with motor capable of delivering 2850 LPM against 100m
head as per requirement of system.
Common base plate for mounting pump and motor fabricated of MS steel
rigid channel as per manufacturer recommendations complete with heavy
duty anti-vibration pads (Minimum 6No) as required.
The system shall be complete with necessary fittings including but not
limited to: eccentric and concentric reducer (if required), automatic air
vent, casing relief valve, capacity plate etc as required.
No. 2 411826.5 823653
2 Supply, installation, testing and commissioning of diesel engine driven
fire pump set complete with engine mounted on common rigid drip-rim
base, with power transmission from the driver by means of listed and
approved flexible couplings, suitable for automatic / manual operation as
per technical specifications, all requirements of contract works and
consisting of following:
Horizontal split casing, high pressure Multi / single stage, centrifugal
pump complete with motor capable of delivering 2850 LPM against 100m
head as per requirement of system.
The diesel engine driver shall meet or exceed all the requirements of
NFPA-20 and as per technical specifications, all requirements of
subcontract works & pump room drawing. The engine shall be equipped
with following standard features but not limited to: Governor to regulate
engine speed with in 10%, Over speed shut down device with manual
reset, battery contactors, alternator or generator for battery recharging,
cooling system, Engine oil heater, Battery rack and cables, Flexible
exhaust connector, instrument panel, Dual set batteries, fuel tank and
Exhaust silencer, anti vortex plate, eccentric and concentric reducer (if
required), discharge tee, automatic air vent, casing relief valve, capacity
plate etc as required.
Stup Consultants P.Ltd 184 of 234
Bill of Quantities- Fire Fighting Work
AMOUNT (INR)DESCRIPTION OF ITEMSS.NO. UNIT QUANTITYRATE
(INR)
Common base plate for mounting pump and motor fabricated of MS steel
rigid channel as per manufacturer recommendations complete with heavy
duty anti-vibration pads (Minimum 6No) as required.
The system shall be complete with necessary fittings including but not
limited to:eccentric and concentric reducer (if required), automatic air
vent, casing relief valve, capacity plate etc as required.
No. 1 885546 885546
2.5 Providing & fixing MS Class ‘C’ diesel engine exhaust pipe (including
all fittings, clamps, steel support) of 100mm dia for the engine. The pipe
shall be insulated with 100 mm thick mineral wool insulation wrapped in
chicken mesh and clad with 24 gauge aluminium sheet.RM 60 3000 180000
3 Supply, installation, testing and commissioning of fire authority approved
electrical driven jockey pump for system as per technical specifications,
pump room drawing and all requirements of contract works, comprising
of following:
Vertical multi/ single stage centrifugal pump complete with squirrel cage
induction motor, totally enclosed fan cool type (TEFC) capable of
delivering below mentioned flow & head as per technical specifications.
Common base plate for mounting pump and motor fabricated of MS steel
rigid channel as per manufacturer recommendations complete with heavy
duty anti-vibration pads.
System shall be complete with necessary fittings including but not limited
to: eccentric and concentric reducer (if required), automatic air vent,
casing relief valve, capacity plate etc as required. However the other
associated items like suction / delivery header, control valves, test header,
flow meters etc. shall be measured separately.
3.1 180 LPM with 100m head No. 2 163342.47 326685
4 Design, fabrication, assembling, wiring, supply, installation, testing and
commissioning of motor control centre shall be fabricated out of 14 gauge
CRCA sheet steel in form in 3b formation with reinforcement of suitable
size angle iron, channel ‘T’ sections irons and/or flats wherever
necessary. Cable gland plates shall be provided on top as well as at the
bottom of the panels. Panels shall be treated with all anticorrosive process
before painting as per specifications with 2 coats of red oxide primer and
final approved shade of powder coated paint. 2 Nos. earthing terminals
shall be provided for 3 phase, 4 wire, 50 Hz supply system. Lifting hooks
shall also be provided in case of large panels. Approval shall be taken for
each panel before fabrication. Cadmium Plated hardware shall be used in No. 1 429461.84 429462
1 MCC-1 for fire fighting equipments
Incoming
a. 2 Nos. 630 amps 35KA breaking Capacity 4 pole mechanical
interlocked incoming MCCB complete with the following
i. 0-500 volts 96 x 96mm square voltmeter with selector switch shall be
protected by 2 amps TP MCB 1 Set
Stup Consultants P.Ltd 185 of 234
Bill of Quantities- Fire Fighting Work
AMOUNT (INR)DESCRIPTION OF ITEMSS.NO. UNIT QUANTITYRATE
(INR)
ii. 0-630 amps 96 x 96 mm square ammeter with 630/5 amps 15 VA CL:1
CT's and selector switch 1 Set
iii. Phase indicating lamps shall be protected by 2 amps SP MCB
6 Sets
b. Aluminium bus bar sleeves type, rated at 800 amps for three phase &
neutral phase bus bar shall have maximum current density of 1 amps per
sq.cm. and the neutral bus bar of not less than 50% capacity.
Outgoing:
a. 2 Nos. 250 amps 35 KA breaking capacity TPN MCCB outgoing
feeders with 70 KW DOL starters out going feeders to Hydrant /
Sprinkler pump motor. The compartment shall contain CT operated
ammeter of 0-250 amps range with selector switch auto / manual selector
switch and indicating lamp with MCBs for `ON'/OFF`TRIP' status of
motor.
b. 3 Nos. 63 amps 25 KA breaking Capacity TPN MCCB, 12 KW Direct
online starter with single phase preventer and outgoing feeder to jockey
pump and terrace pump motor. The compartment shall contain CT
operated ammeter of 0-63 amps and indicating lamps with MCBs for
`ON'/OFF`TRIP' status of pump motors.
c. 2 No. suitable rating MPCB for 1.5 KW DOL starter and outgoing
feeder to sump pumps in plant room (including 1 Nos. standby). Each
compartment shall contain auto / manual selector swtich and indicating /
pushbutton lamps with MCB for ON / OFF / TRIP of motor.
d. Providing and fixing 1 No. auto start panel activated with pressure
switch for diesel engine complete with all accessories, batteries, battery
charger of suitable rating, MCB timers, push buttons, microprocessor
based alarm annunciator, wiring and cabling including connection to
diesel engine complete as required ready for working.
e. Necessary cable alleys space for spare switches, internal wiring and
copper earthing of all equipment shall also be included. All switch gears /
control gears shall be motor duty rating.
Note: All MCCB's to be suitable for motor duty and shall be of 25 KA breaking
capacity.
Provision shall be made for providing potential free contacts to all pumps
starters for connection to building automation system.
5 S/I/T/C of UL Listed Flow Meter as per technical specifications. No. 1 6458.7726 6459
6 Supply, installation, testing & commissioning of UL listed, pressure
sensor switches suitable for pressure complete with independent low/high
pre-calibrated adjustments as per technical specifications and all
requirements of contract works.
No. 5 6002 30010
7 S/I/T/C of level meter as per technical specifications. No. 2 10935.422 21871
Stup Consultants P.Ltd 186 of 234
Bill of Quantities- Fire Fighting Work
AMOUNT (INR)DESCRIPTION OF ITEMSS.NO. UNIT QUANTITYRATE
(INR)
8 Supplying & laying of following 1100 volt grade PVC insulated copper /
Aluminium conductor armoured cables as per specification in existing
trenches, cable trays ducts over bed of sand, clamped to wall with suitable
clamps, saddles fixing bolts including connecting testing and
commissioning. This is inclusive of GI cable tray of suitable size complete
with bends, couplers as required at site.
8.1 3.5 Core 95 Sqmm Aluminium Conductor cable (Main Panel to Main
Electric Pump) Meter 80 2244 179520
8.2 3.5 Core 70 Sqmm Aluminium Conductor cable (Fire Panel to Main
Electric Pump) Meter 60 2248 134880
8.3 3.5 Core 25 Sqmm Copper Conductor cable (Fire Panel to Jockey Pump).
Meter 60 884 53040
8.4 4 core 2.5 sq.mm copper conductor control cable (Fire Panel to diesel
engine). Meter 40 490 19600
9 Cable end termination of the following aluminium / copper conductor
armoured cables of 1100 volt grade including supplying and fixing of
bimetallic crimping lugs, double compression glands with earthing facility
and cable sockets etc. complete as required.
9.1 3.5 Core 95 Sqmm for Aluminium Conductor cable Each 2 1500 3000
9.2 3.5 Core 70 Sqmm for Aluminium Conductor cable Each 4 950 3800
9.3 3.5 Core 25 Sqmm for Copper Conductor cable Each 4 475 1900
9.4 4 core 2.5 sq.mm for copper conductor control cable Each 2 204 408
TOTAL CARRIED TO SUMMARY 3099833
Stup Consultants P.Ltd 187 of 234
SCHEDULE OF QUANTITIES
GENERAL NOTES :
1
2
3
4
a All materials, fixing materials, accessories, appliances tools, plants, equipment, transport, labour and incidentals
required in preparation for and in the full and entire execution, testing, balancing, commissioning and completion
of work called for in the item and as per Specifications and Drawings.
b Wastage on materials and labour.
c Loading, transporting, unloading, handling/double handling, hoisting to all levels, setting, fitting and fixing in
position, protecting, disposal of debris and all other labour necessary in and for the full and entire execution and
for the job in accordance with the contract documents, good practice and recognize principles.
d Liabilities, obligations and risks arising out of Conditions of Contract.
e All requirements of Specifications, whether such requirements are mentioned in the item or not. The
Specifications and Drawings where available, are to be read as complimentary to and part of the Schedule of
Quantities and any work called for in one shall be taken as required for all.
f In the event of conflict between Schedule of Quantities and other documents including the Specifications, the
most stringent shall apply. The interpretation of the Consultant/Project Manager shall be final and binding.
5
6
7
8
9
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW IN U.P.
The contractor shall cooperate with all trades and agencies working on the site. He shall make provision for hangers,
sleeves, structural openings and other requirements well in advance to prevent hold up of progress of the construction
schedule. All supports to the civil structure shall be provided with anchor fasteners.
On award of the work, contractor shall submit a schedule of construction in the form of a PERT chart or BAR chart for
approval of the Project Manager.
On award of the work the contractor shall be issued two (2) sets of consultant’s drawings. The drawings shall be the
basis of contractor’s shop drawings.
The work shall be carried out in conformity with the HVAC drawings and within the requirements of architectural,
Plumbing, Fire Fighting, Electrical, Structural and other specialized services drawings.
All items of work under this Contract shall be executed strictly to fulfill the requirements laid down under “Basis of
Design” in the specifications. Type of equipment, material specification, methods of installation and testing and type of
control shall be in accordance with the specifications, approved shop drawings and the relevant Indian Standards,
however capacity of each component and their quantities shall be such as to fulfill the above mentioned requirement.
The unit rate for all equipment or materials shall include cost in INDIAN RUPEES (INR) for equipment and materials
including all taxes and duties and also including forwarding, freight, insurance and transport into Contractor’s store at
site, storage, installation, testing, balancing, commissioning and other works required.
For all imported items Owners shall arrange EPCG licence and open L/C in the name of principals. Rates for all
imported items shall be quoted in US Dollars. During award of work Owner shall be at liberty to ask for proforma
invoice in any convertible foreign currency. All relevant document for import shall be taken care by the contractor.
Port charges / octroi / inland transportation etc. upto site shall be paid on actuals subject to ceiling of quoted amount.
The rate for each item of work included in the Schedule of Quantities shall, unless expressly stated otherwise, include
cost of :
The Contractor shall procure and bring Materials/Equipment to the site only on the basis of drawings approved for
construction and shop drawings and not on the basis of Bill of Quantities which are approximate only. This also applies
to the Contractor’s requisition for Owner supplied materials.
Stup Consultants P.Ltd 188 of 234
10
11
12
13
14
15
16
17
18
19
20
21
The contractor shall , from time to time, clear away all debris and excess materials accumulated at the site failing
which the same shall be done by Project Manager at contractor’s risk and cost and cost of clean up shall be deducted
from the contractors prorata bill.
After the fixtures, equipment and appliances have been installed and commissioned, contractor shall cleanup the
same and remove all plaster, paints, stains, stickers and other foreign matter or discoloration leaving the same in a
ready to use condition.
Any pipe crossing fire rated wall as per fire compartmentation will be provide with higher size of GI sleeve. All floor
crossing pipes will be provided with higher size GI sleeve.
This Schedule shall be fully priced and the extensions and totals duly checked. The rates for all items shall be filled in
INK including NIL items.
No alteration whatsoever is to be made to the text or quantities of this Schedule unless such alteration is authorised in
writing by Consultant. Any such alterations, notes or additions shall, unless authorized in writing, be disregarded when
tender documents are considered.
Shop drawings are detailed working drawings coordinated with other trading work, which incorporate the contractor’s
details for execution of the work and incorporate equipment manufacturer’s details and dimensions to ensure that the
same can be installed in the space provided.
All shop drawings should detail pipe routing and levels, showing location of other services at crossings etc., cable
runs, route cable trays and all allied works and must be fully coordinated with other services, before execution of the
works.
All shop drawings will be made on AutoCAD and colored prints has to be produced for site work.
On completion of all works, contractor shall demolish all stores, remove all surplus materials and leave the site in a
broom clean condition, failing which the same shall be done by the Project Manager at the Contractor'’ risk and cost.
Cost of the cleanup shall be deducted from the contractor’s bills on pro-rata basis in proportion to his contact value.
In the event of an error occurring in the amount of the Schedule, as a result of wrong extension of the unit rate and
quantity, the unit rate quoted by the tenderer shall be regarded as firm and the extensions shall be amended on the
basis of rates.
Any error in totaling in the amount column and in carrying forward total shall be corrected. Any error, in description or
in quantity, omission of items from this Schedule shall not vitiate this Contract but shall be corrected and deemed to be
variation required by the Consultant/Project Manager.
Rates have been called for a number of items of works, as alternatives which, for the present do not form part of the
total value of tender. However the rates for these items shall be quoted, with due care so that in the event of choice of
an alternative item of work, said rate shall form part of the contract and shall not violate the contract any way.
Stup Consultants P.Ltd 189 of 234
No. Amount
A 227927900
B 22263995
C 85309480
D 33565125
E 2500000
371566500
SUMMARY- HVAC Work
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR
,LUCKNOW IN U.P.
SUMMARY OF COST-HVAC
Description
SYSTEM TESTING, BALANCING & COMMISSIONING BY THIRD
PARTY
TOTAL
EQUIPMENT
PIPING-CHILLED, HOT WATER AND CONDENSER WATER
AIR DISTRIBUTION
THERMAL INSULATION
Stup Consultants P.Ltd 190 of 234
RATE (INR) AMOUNT (INR)
A. EQUIPMENT
1 Supplying, installing, testing and commissioning of CENTRIFUGAL WATER CHILLING UNITS
each complete with 525 TR actual capacity centrifugal compressor with motor, starter panel
machine mounted/ free standing, water cooled condenser, Variable Speed Drive (including cost
of cabling, Cable Termination Box or other necessary arrangement between VFD and motor),
insulated chiller, flow switch at chiller and condenser, vibration isolators, integral refrigerant
piping and wiring, BMS interface unit for software integration, grooved couplings for condenser
and cooler water in/out connections, complete charge of refrigerant and oil, accessories as
required and called for, automatic and safety controls mounted in central micro-processor based
console panel and all mounted on a steel frame complete as per specifications. Motor shall be
suitable for 415±10% 50 cycles. 3 phase AC supply and motor cable terminal box shall be
suitable to connect Aluminium Cabling. Refrigerant used shall be Ozone friendly HFC-134a as
detailed in specifications. First chiller shall be factory tested at design conditions at 100%, 75%,
50% and 25% load. The centrifugal chiller shall be capable of working on lower chilled water flow
down to 30% of design flow, since chilled water system is with primary variable chilled water
pumping .
Chiller
Chilled Water IN 57°F
Chilled Water OUT 45°F
Fouling factor 0.0005 FPS
Condenser
Condenser Water IN 90°F(Amb. Wet bulb+60F)
Condenser Water OUT 100°F(∆T of 10oF)- Approx
Condenser Water Flow 1573 US GPM
Fouling factor 0.001 FPS
Maximum Power Consumed : Not greater than 0.65 in IkW/TR
Minimum NPLV - 0.37
Minimum COP (At ARI conditions) : 6.3Nos 5 12,755,020 63775100
Bill of Quantities- HVAC Work
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW IN U.P.
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
Stup Consultants P.Ltd 191 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
2. Supplying, installing, testing and commissioning of CENTRIFUGAL PUMPS, factory mounted on
a common base with electric motor for recirculation of water for the central air conditioning
system as per specifications. All pumps shall be aligned properly as required. The pump motor
shall be suitable for 415 ± 10% volts, 50 cycles, 3 phase power supply. The motor selected shall
be energy efficient having efficiency (Class I) at full load ranging between 91.5% to 94% in
accordance with motor rating as per specification. Minimum pump efficiency shall be 75%. The
motor of Primary Variable chilled water pumps shall be suitable for operation on adjustable
frequency drive. The quoted price shall include cost of thermal insulation and cladding as
mentioned in specifications. Pumps with performance characteristics as given below :
Primary Variable Speed Chilled water pumps
Water flow rate = 1050 USGPM
Head = 140 Ft. of water
Motor hp = 60
Quantity indicated includes one standby. Nos 6 743,424 4460544
Note : Above cost shall be inclusive of Supplying, installing, testing and commissioning of
VARIABLE SPEED PUMPING SYSTEM consisting of adjustable frequency drive (AFD) for
each pump, one dedicated microprocessor based pump controller housed within the enclosure
of one of the AFD with parallel pumping software duly down loaded and multiple differential
pressure sensor / transmitters along with complete control cabling from transmitter to AFD Panel
as per the site requirement. The entire system along with primary pumps as described under
item 2 must be sourced from single manufacturer only, to ensure unit responsibility. Necessary
factory test certificates for entire system shall be submitted along with the equipment. Sensor /
Transmitters as described in specification. System shall be BMS compatible with open protocol
communication port, so that complete data can be transported to remote IBMS console.
The system shall be complete in all respects and suitable for following motor ratings:
2.1 Differential Sensor/ Transmitters - 7 Nos.
2.2 60 hp VFDs - 6Nos.
Stup Consultants P.Ltd 192 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
3 Supplying, installing, testing and commissioning of CENTRIFUGAL PUMPS, factory mounted on
a common base with electric motor for recirculation of cooling water for the central air
conditioning system as per specifications. All pumps shall be aligned properly as required.
Minimum efficiency of the pump shall be 75%. The pump motor shall be suitable for 415 ± 10%
volts, 50 cycles, 3 phase power supply. The motor selected shall be energy efficient having
efficiency (Class I) at full load ranging between 91.5% to 94% in accordance with motor rating as
per specification. The performance shall be as given below :
3.1 Condensing water pumps
Water flow rate = 1575 USGPM
Head = 82 Ft. of water
Motor hp = 50
Quantity indicated includes one standby. Nos 6 350,829 2104974
4 Supplying, installing, testing and commissioning of PRESSURISED chilled WATER
EXPANSION TANK suitable for total volume of water in chilled water circuits along with
necessary accessories such as centrifugal air separator, pumps etc. in order to keep chilled
water system under (+) pressure and to prevent entrapment of pressure and to prevent
entrapment of air in the system. The tank shall be precharged steel expansion tank with
replaceable heavy duty butyl rubber bladder. The tank shall have 50 MM system connection and
20 mm drain and charging valve connection to facilitate the on site charging of the tank to meet
system requirement. The tank shall be fitted with lifting rings and a floor mounting skirt for
vertical installation. The tank and air separator must be constructed in accordance with section
VIII of the ASME Boiler and pressure vessel (Unfired)code and stamped 175 PSI working
pressure. The complete system shall be preferred to be sourced from single manufacturer and
supplied and installed with all accessories and safety fixtures and safety fixtures required for
proper functioning of the complete hydronic system.
The Approximate total Volume of water in chilled water circuit = 15000 gallons and static head of
approximate 45 mts to be considered . The contractor shall verify and submit calculations for
total system volume and tank sizing calculations.Nos. 1 2,179,574 2179574
Stup Consultants P.Ltd 193 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
5 Supply, installing, testing and commissioning of horizontal FAN COIL UNITS (2 PIPE
SYSTEMS), blow thru type, each complete with 3 rows deep Chilled Water Coil, one or more
centrifugal fans, cleanable fabric filters, main condensate extended SS drain pans, RA insulated
plenum, as described in specifications, casing, coil piping connections, through copper pipes,
condensate drain connections, wiring, control wiring in conduit upto thermostat boxes. Fan coil
unit shall be factory fitted with valve package comprising of pressure independent Balancing
cum Control Valve with integrated 2 way motorized actuator in a single body for modulating
operation suitable for static pressure of 1600 kPa and actuator shall be capable of withstanding
400 kPa shut off pressure, 24 V AC incoming power supply, ball valve with Y-strainer at inlet &
Ball valve at outlet and necessary copper coil piping connections. The actuator of modulating
valve shall be provided with interface cards to receive 0-10V or 4-20 mA signal from
Thermostat.
The actuator of the valve shall have necessary torque to overcome pressure differential of 4
bars rating. All fan coil units shall be suitable for 220±6% volts, 50 cycles, single phase power
supply. Fan coil units shall be of following refrigeration capacities as listed.
5.1 1.5 TR nominal capacity - 600 CFMNos. 1 51,114 51114.2
5.2 2.0 TR nominal capacity - 800 CFMNos. 1 52,722 52721.9
5.2 2.5 TR nominal capacity - 1000 CFMNos. 2 58,350 116700
6 Supplying, installing, testing and commissioning of Pressure Independent Variable Air voulme
Terminal units, suitable for installtion in horizontal ducts. The casing shall be double skin
acoustically lined and constructed with galvanised sheet steel.Should include all accessories
such as single / multileaf damper (with equal % characteristics) etc. actuators, control cabling ,
thermostat , feed back control cabling upto VFD panel / DDC Panel in AHU room and any other
ancilary requirement for the functioning of the units. Cost of duct mounted Diff. pressure
transmitter (Except for Treated Fresh Air VAVs) with cabling upto VFD panel shall also be
included.
CFM Range of VAV shall be from 20 % (MIN) to 150% (MAX)
6.1 320 CFM Nos. 36 45,960 1654560
6.2 420 Nos. 36 45,960 1654560
Stup Consultants P.Ltd 194 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
6.3 650 Nos. 36 45,960 1654560
6.4 765 Nos. 36 45,960 1654560
6.5 850 Nos. 252 45,960 11581920
6.6 1030 Nos. 144 47,620 6857280
6.7 1200 Nos. 72 48,781 3512232
6.8 1375 Nos. 36 49,943 1797948
6.9 1500 Nos. 36 52,018 1872648
6.10 1780 Nos. 36 53,096 1911456
6.11 T Fresh Air 3300 Nos. 36 68,597 2469492
6.1.1 Supply, installation, testing and commissioning of INTEGRATOR for VAV boxes, capable of
giving industry standard (Modbus / Lon Works / Bacnet) output to BMS system. Mapping shall
be required for monitoring individual room temperature, air flow and damper position for areas
conditioned through VAV boxes. It shall be inclusive of wiring in MS conduit between integrator
and individual VAV Boxes.
Integrator as described above for 30 numbers VAV Boxes. Nos. 40 34,343 1373720
7 Supply, installation, testing and commissioning of THERMOSTAT for simultaneous heating and
cooling. The thermostat shall be electronic room temperature controller with digital display & fan
speed control, capable of providing individual space temperature control for cooling / heating
application. The controller shall have provision to produce a dual output to cooling and heating
coils in response to load change in rooms. Nos. 5 3,500 17500
8 Supply of HVAC dedicated VFDs with minimum IP 55 enclosures & disconnect, complying with
the tender specifications and having:
Built-in dual 5% impedance DC link reactor (harmonic filters) on the positive and negative rails of
the DC bus of the VFD.
Built-in EMC Filters (electromagnetic compatibility filters) for restriction of conducted emissions
to comply with IEC61800: 3 (unrestricted distribution):2004 Category C 1 for 50 meters of cable
length between motor & VFD,
Automatic Energy Optimization / Load dependent flux optimization functionality for maximum
energy savings.
BACKNET/ MODBUS RTU as the communication protocol between BMS & VFDs.
Stup Consultants P.Ltd 195 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
VFDs not meeting above requirements shall provide external disconnect, external harmonic
filters, additional external EMC Filters to comply with IEC61800: 3 (unrestricted
distribution):2004 Category C 1 for 50 meters of cable length between motor & VFD, external
PLCs / DDCs to achieve 3 Feedback PID Controller functionality and external devices controlling
capabilities.
8.1 The system shall be complete in all respects and suitable for following motor rating:
AHUs - 15 HP Nos. 40 154,793 6191720
AHUs -7.5 HP Nos. 4 106,589 426356
Car Parking-3 HP Nos. 1 85,664 85664
Car Parking-5 HP Nos. 6 105,073 630438
Car Parking-7.5 HP Nos. 8 106,589 852712
Car Parking-10 HP Nos. 1 116,678 116678
Car Parking-12.5 HP Nos. 1 154,793 154793
Car Parking-15 HP Nos. 20 154,793 3095860
9 Supplying, installing, testing and commissioning of double skin construction draw thru type AIR
HANDLING UNITS with Thermal Break Profile as per specification, each complete with pre-filter
section (90% down to 10 microns), min 6 Row Deep water coil of copper tube & aluminium fins
construction, squirrel cage induction motor, airfoil centrifugal fan belt drive and vibration
isolators, coil size shall be selected for a maximum face velocity of 500 feet/minute and
static pressure shall be as indicated. The motor selected shall be energy efficient having
efficiency (Class I) at full load ranging between 82.5% to 92% in accordance with motor rating as
per specification. Motor shall be suitable for 415±10% volts, 50 cycles, 3 phase AC supply. Fan
motor assembly (as whole) shall be statically and dynamically balanced to grade G 6.3 as per
ISO-1940/AMCA 204-3.All units shall be complete with opposed blade volume control dampers
at oulet, return and fresh air connections. Duct flexible connector (fire proof) shall be provided at
outlets and return connection of AHU.
Air moving capacity shall be as follows:
Floor Mounted AHUs
CFM Area TR ESP (mmwg) Motor (kW)
Stup Consultants P.Ltd 196 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
i 26000 Wing Typical 66 45 11.2 No. 34 607,671 20660814
ii 15000 Wing 9th Floor, Audi 40 45 5.6 No. 6 393,264 2359584
iii 32000 Wing Gr. Floor 80 45 11.2 No. 4 747,748 2990992
Ceiling Suspended AHUs
iv 10000 Audi, Foyer 25 45 3.7 No. 2 261,993 523986
v 5000 Bank Audi 10 45 2.2 No. 5 157,196 785979
vi 3000 Audi 7.5 45 2.2 No. 3 94,317 282952.44
10 Supply, installation, testing and commissioning of micro-processor controlled precision air-
conditioning unit with scroll compressor(s) on HFC-134a / HFC-410a/ 407c, air cooled
condenser with installation stand, insulated refrigerant piping with supports, cooling coil,
electrical heating coil, steam/ infrared humidifier, necessary measuring and control devices,
evaporator fan with motor, pre and micro-vee filters and inbuilt starter. Power will be provided by
other agency near the indoor unit inbuilt starter. Power and control cabling from indoor to
outdoor unit along with supports / cable trays shall be included.
10.1 7.5 TR Nos. 2 991,573 1983146
10.2 10 TR Nos. 2 1,547,114 3094228
10.3 15 TR Nos. 2 1,799,899 3599798
Stup Consultants P.Ltd 197 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
11 Supplying, installing, testing and commissioning of HEAT RECOVERY UNIT (HRU) double
skin construction. The unit shall comprise of filter section, heat recovery unit, fresh air inlet /
exhaust air outlet, motorized volume contol dampers with Bird Screen, fan section with DIDW
fan with motor and drive package, Control Panel, wiring upto control Panel etc. . The unit shall
be installed above Fan and interconnected in a manner so as to receive part return air which
shall be passed through HRW and transfer sensible and latent cooling to incoming fresh air.
The precooled fresh air shall be let into the mixing box of the main AHU and return air is
exhausted outdoors. The exhaust section of the unit shall be provided with motor actuated GSS
damper duly interlocked with the fan. Minimum sensible and latent heat transfer efficiency of
heat recovery unit shall be 80%.
Double skinned panels shall be about 46 mm thick made of galvanized steel, pressure
injected with foam insulation (density 40 kg/m3) with K factor not exceeding 0.02 Watt/Mc
shall be fixed to 1.5 mm thick aluminium alloy twin box section structural framework with
stainless steel screws. Outer sheet of panels shall be made of galvanised
preplasticised sheet of 0.63 mm thick, and inner sheet of 24 Gauge plain G.I.Sheet.The
profile of section shall be thermal break.
External Static Pressure-20mmWG
Design conditions shall be as follows
Fresh Air
1. DB - 107.6 deg F
2. WB - 75.5 deg F
Exhaus/Return Air Temp.
1. DB - 84 deg F
2. WB - 73 deg F
Air moving capacity shall be as follows :
Fresh Air CFM Exhaust/Return air CFM
25000 25000 No. 4 2,821,793 11287172
Stup Consultants P.Ltd 198 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
12 Supplying, installing, testing and commissioning of AIR HANDLING UNITS ( FAN SECTIONS
ONLY) with double skin construction as per specificatopns, each complete with squirrel cage
induction motor (mounted internally), airfoil centrifugal fan belt drive and vibrations
isolators.Motors shall be suitable for 415 +- 10% volts, 50 cycles , 3 phase AC supply and static
pressure shall be as indicated . Fan-motor assembly (as whole) shall be statically & dynamically
balanced to grade G6.3 as per ISO-1940/AMCA 204-3. All AHUS (Fan sections) shall be
suitable for outdoor duty and complete with duct flexible connections and volume control damper
. In additional all supply fans (SF) shall be provided with prefilter
Note EF- Exhaust Fan , SF - Supply Fan
Fan Tag Space Fed CFM SP Motor HP
(mmwg)
EF 1-2 Service Area 25000 50 10 Nos. 2 261,993 523986
Fresh Air SF 1-2 AHUs 25000 50 12 Nos. 2 261,993 523986
13 Supplying, installing, testing and commissioning of smoke spill fans as per specifications.Fan
shall be with belt driven tube/vane axial fan.Fan and casing shall be suitable for smoke exhaust
application.Motor and belt drive shall be mounted outside ,so that it is not exposed to smoke
stream & thermally rated for 2500C for 2 hours as per [BS-7346 Part-2 : 1090] Class-B. Motors
shall be suitable for 415+10% volts, 50 cycles , 3 phase AC supply and static pressure shall be
as indicated . Fans shall be activated from fire signal from fire alarm system .Fan shall be with
flexible fire proof flexibel connection at inlet and outlet
Space Fed CFM SP Motor HP
(mmwg)13.1 Basement Parking 10000 32 5.0 Nos. 4 120,962 483848
13.2 Basement Parking 15000 /16000 32 7.5 Nos. 18 125,764 2263752
13.3 Basement Parking 20000 32 7.5 Nos. 2 152,943 305886
13.4 Basement Parking 22500 32 10 Nos. 6 189,604 1137624
13.5 Basement Parking 30000 32 15.0 Nos. 28 225,983 6327524
13.6 Basement Parking 45000 32 20.0 Nos. 26 310,660 8077160
13.7 Office Floor (Typ. Wing) 26000 50 20.0 Nos. 36 202,797 7300692
13.8 Office (9th Flr) 15000 50 10.0 Nos. 4 189,604 758416
13.9 Auditorium 30000 32 15.0 Nos. 2 225,983 451966
13.10 Auditorium 15000 32 7.5 Nos. 2 125,764 251528
Stup Consultants P.Ltd 199 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
13.11 STP Plant Room 30000 32 15.0 Nos. 1 225,983 225983
13.12 HVAC Plant Room 45000 32 20.0 Nos. 1 310,660 310660
14 Supply, installation, testing and commissioning of Axial Fans for supplying fresh air suitable for
installing in any position in Horizontal or vertical. The motor shall be suitable for 415 V + 10%
volts three phase 50cycle, AC supply and suitable for operating through VFD. The fan shall be
low RPM
Nos.
Space Fed CFM SP Motor HP
(mmwg)
14.1 Liftwell Pressurization Fans 10000 40 5.0 Nos. 12 120,962 1451544
14.2 Liftwell/ Lift Lobby Pressurization Fans 5000 40 3.0 Nos. 12 66,617 799404
14.3 Staircase Pressurization Fans 5500 40 3.0 Nos. 16 69,000 1104000
14.4 Staircase Pressurization Fans 5000 40 3.0 Nos. 8 66,617 532936
14.5 STP Plant Room 30000 32 15.0 Nos. 1 204,067 204067
14.6 HVAC Plant Room 45000 32 20.0 Nos. 1 261,617 261617
15 Supplying, installing, testing and commissioning of INLINE FANS suitable for installing in any
position in vertical or horizontal ducts. The casing shall be double skin, internally acoustically
lined and constructed of galvanised steel. The fan shall be DIDW with forward curve impeller
fitted with maintenance free external rotor motor. The motor shall be suitable for 220±10% volt
single phase 50 cycles AC supply. All units shall be complete with duct flexible connector and
volume control damper.
The fan shall have low sound level exceeding not more than 40 DBA at three metre distance.
CFM SP
(mmwg)
15.1 1500 15 Nos. 1 69,804 69804.48525
Stup Consultants P.Ltd 200 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
16 Supplying, installing, testing and commissioning of direct driven PROPELLER FANS for exhaust
air as shown in drawings. Each fan shall be complete with permanent split capacitor or shaded
pole motor, mounting plate, accessories like wire guard, bird screen and fixed louvers for
weather protection as required. Fan selection arrangement and Electrical characteristics shall be
as follows :
16.1 900 mm dia 700 RPM fan suitable for 415±10% volts 50 cycles, 3 phase AC supply. Nos. 1 46,214 46214
16.2 600 mm dia 900 RPM fan suitable for 220±6% volts 50 cycles, 1 phase AC supply. Nos. 1 27,949 27949
16.3 450 mm dia 900 RPM fan suitable for 220±6% volts 50 cycles, 1 phase AC supply. Nos. 1 15,895 15895
16.4 375 mm dia 900 RPM fan suitable for 220±6% volts 50 cycles, 1 phase AC supply. Nos. 1 11,271 11271
16.5 300 mm dia 900 RPM fan suitable for 220±6% volts 50 cycles, 1 phase AC supply. Nos. 1 9,148 9148
17 Supply, installation, testing and commissioning of FRP INDUCED OR FORCED DRAFT
COOLING TOWERS. Fan and motor shall be suitable for VFD. Each tower shall be complete
with basin, casing, distribution system, filling, louvers, ladder, fan and motor. Motor shall be
suitable for 415±10% volts, 50 cycles, 3 phase power supply, Isolator panel with MCCB at
cooling tower and earthing, shall also be included. Tower for airconditioning system shall be
selected on the basis of ambient wet bulb 84oF. The tower shall be sized for 10% extra capacity
over heat rejection duty specified through water temperature difference and flow rate below :
17.1 Cooling tower of 720 TR Capacity suitable for centrifugal chillers ( 575 TR) plant having flow
rate of 1725 USGPM inlet temperature of 90 °F and outlet temperature of 100 °F. Nos. 4 1,186,610 4746440
19 Supplying, installing, testing and commissioning of CELLULOSE FILL AIR WASHER
(Including fans), giving 95% adiabatic saturation efficiency at 500 FPM air velocity across pads,
factory assembled and complete with 16 gauge GI casing, SS water sump , Cellulose fill, water
distribution header, GI piping, butterfly valves, for quick fill; isolation of tank and pumps, Y
strainers and necessary fittings.
Stup Consultants P.Ltd 201 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
The quoted price shall also include provision of GSS partitions duly reinforced at intake side of
air washer and GSS louvers with bird-screen fabric filters and drift eliminators. The price shall
also include horizontal monoblock pumps of Beaconweir / KBL / Equivalent make of suitable
rating, factory mounted on mild steel channel base with electric motor for circulation of water
alongwith starter panel. Pumps shall be aligned and suitable for 415±10% volts, 50 cycles 3
phase power supply. One No. 3 phase isolator switch in weather proof enclosure shall be
provided near motor.
SPACE CFM
Kitchen 25000 Nos. 2 503,893 1007786
20 Supplying, installing, testing and commissioning of Electrical Hot Water generator of vertical/
horizontal construction equipped with sufficient number of flanges and electrical immersion heaters. The
pressure vessel shall be constructed as per ASME standards and insulated on all sides with 100 mm thick
fibreglass. The hot water generator shall be equipped with all automatic and safety controls such as
manual reset high temperature water outlet, step controller and recycling relay, ON-OFF switch,
thermostats, pilot light, ‘ON’ status of individual banks, low water cut off all as per manufacturers
recommendations. All basic controls and terminal shall be located in an internal control cabinet, factory
wired and tested. The hot water generator shall be suitable for 415 ± 10% volts, 50 cycles, 3 phase power
supply.The entire hot water generator and control cabinet shall be factory assembled on common base and
tested, requiring only connection to services.
Hot water entering temperature = 110 deg F
Hot water leaving temperature = 120 deg F
Total water flow = 340 USGPM
500 KW Hot Water Generator as described above (3W + 1 Standby)Nos. 4 773,980 3095920
21 Supply, Installation, Testing and Commissioning of Scrubber each comprising of extract air
intake section, electrostatic precipitation technology, dry type air cleaner to remove oil, smoke
and fumes from exhaust air, as per the Specifications.
Stup Consultants P.Ltd 202 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
Electrostatic section shall be made of 16 gauge galvanised sheet, high bake epoxy powder
coated, washable type aluminium mesh filters, stainless steel spiked ionizers to create high
voltage DC field, aluminum collector plates which should be alternatively charged positive and
negative with large collecting area with 14" deep cell, to work as magnet for charged smoke and
oil particles. Average efficiency of 90-95% in single pass as per ASHRAE test method.
Electrostatic Precipitator should be able to charge particles from 0.01 micron to 10 microns
through solid state power supply. Collector cell should be of permanent type and incorporate
slide out facility for easy removal for cleaning. Power supplies shall be 100% solid state
preferably UL Listed, Module of capacity above 3000 CFM shall be equipped with Pulse width
modulating (PWM).The system should be fitted with interlock switch for safety . The system
should allow connection to a fan section to achieve 500 FPM velocity across the air cleaner.
Operating Voltage : 220V, 50 Hz
Ionizing Voltage : 12.5 to 13 KVDC
Collector Cell Voltage : 6 to 6.5 KVDC
Power Consumption : Not more than 50W per cell.
Air Moving Capacities shall be as follows:
Space CFM
Kitchen 25000 Nos. 2 1,542,841 3085682
22 Supply, installing, testing and commissioning of Ceiling Suspended/ wall mounted water cooled
split air conditioning unit. The unit shall be complete with decorative type High Wall/ Fan coil unit
and condensing unit, complete in all respects, inclusive of interconnected copper refrigerant
piping, Class B GI condensate drain piping, Heavy class MS Condenser water piping with
valves, Y Strainers etc. Quoted price shall also include cost of cooling thermostat, power wiring,
control wiring and earthing. The unit capacities shall be as follows:
2.0 TR Split air conditioning Unit for Hub Room No. 16 125,000 2000000
The unit shall be integrated & connected with exhaust fan sections for kitchen including all
necessary accessories to complete the installation.
Stup Consultants P.Ltd 203 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
24 MOTOR CONTROL CENTRES FOR AIR CONDITIONING (PLANT ROOM)
Design, manufacture, supply, installation, testing and commissioning of the following cubicle
type 2 mm thick sheet steel enclosed separate compartment for each feeder, front operated,
rear connections indoor type LT motor control panel, dust and vermin proof, drawout/hinged
and lockable doors, complete with internal wiring, colour coding with ferrules, cable glands,
bonding to earth and painting. Quoted price for each panel & motor control centre shall include
all cabling & earthing over cable trays into various equipment, all associated control wiring and
interlocking circuitary.
Each MCC shall include cost of wiring, control wiring & inter locking between chillers, primary
CHW pumps, condenser water pumps, motorized valves at chillers and condensers, flow meter
& flow switch installed in de-coupler by-pass line, in order to execute the required sequence of
operation.
All outgoing shall be provided with Stop/Manual/ Auto/selector switch to facilitate operation
through BAS. All starters shall be provided with potential free Contact for Connections to
Building Automation System.
A separate set of CTs to be provided for BAS and wiring from CT’s and voltage transducers to
be brought on to separate set of terminals.
24.1 Motor Control Centre 415V Bus Section-1 consisting of
a. Incoming
One No. 1600 amps 50KA breaking capacity TPN manual drawout type incoming
microprocessor based ACB complete with the following :
i. 0 - 500 volts 96 x 96 sq mm digital voltmeter with selector switch.
ii. 0 -2000 amps 96 x 96 sq mm digital ammeter with ……./5 amps CT’s and selector switch
iii. Over voltage tripping mechanism for persistent voltage exceeding 110% of the rated voltage for
more than 5 minutes
iv. Phase indicating lamps, with toggle switches.
Stup Consultants P.Ltd 204 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
b. TPN bus bars shall be of aluminium and shall be sleeved. Phase bus bars shall be rated at 2000
amps and neutral bus bar shall be of 50% capacity.
Maximum density of aluminium bus bars for current carrying capacity shall be one amp per
square mm.
Outgoing
c. 6 Nos. 160 amps 35 KA breaking Capacity MCCB and 6 Nos. outgoing feeders to Adjustable
Frequency Drive (AFD) panel to Primary chilled water pump motors (5 working + 1 standby)
The compartments shall contain CT operated digital ammeter 0 - 100 amps range with selector
switch and an indicating lamp with MCB and toggle switch for ‘ON’ status of pump motors.
d. 6 Nos. 160 amps 35 KA breaking Capacity MCCB 50 HP star delta starter, over load relay with
built in single phasing protection and outgoing feeders to condenser water pump motors (5
working + 1 standby) . Each of these compartment shall contain CT operated digital ammeter of
0-100 amps range with selector switch, and an indicating lamp with MCB and toggle switch for
‘ON’ status of pump motors.
e. 4 Nos.80 amps 25 KA breaking Capacity MCCBs, outgoing feed to 4 No. VFDs and outgoing
feeder to cooling tower fan motor. The compartment shall contain an indicating lamp with MCB
and toggle switch for ‘ON’ status of fan motor.
f. Necessary cable alleys, space for spare switches (4 Nos. 160 Amp MCCBs , 2 Nos. 80 Amp
MCCBs), internal wiring, control wiring/cabling and copper earthing of all equipment shall also be
included. All switches and other components shall be motor duty rating.
Motor Control Centre No. 1 as described above. No. 1 1,767,232 1767232
25 CONTROL PANELS FOR FANs (OPERATED THROUGH VFD) without VFD
Design, manufacture, supply, installation, testing and commissioning of the following cubicle
type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall,
incoming cable wiring terminating into MCCB and copper earthing, in each panel shall be
provided by the electrical contractor.
Stup Consultants P.Ltd 205 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation
through BAS. All starters shall be provided with potential free Contact for Connections to
Building Automation System.
All internal wiring, power cabling and copper earthing of motors from the panel to VFD & to the
motor shall be included.
The panel shall include the following components & accessories.
a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of
25 KA.
b. Terminal block for power distribution as required.
c. Contactor, over load relay with built in single phasing protection.
d. Phase indicating lights and indicating light for `ON’ status.
e. 144 mm x 144 mm voltmeter and digital ammeter.
f. Time delay relay for delayed automatic restart of motor.
g. Wiring for microswitch for stopping the fan when fire damper closes (in case of Fan only).
h. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel
to facilitate override of the automatic operation.
i. 3 Nos of Single Pole MCB's Shall be provided at the incoming section of the starter panel for
DDC Panel , fire damper actuator & as a spare.
j. All starters shall be provided with suitable potential free contract for connections to the Building
Automation System.
k. 220 / 24 V Transformer
The number of control panels shall be as follows.
25.1 40 amps MCCB, 15-20 HP VFD No. 1 83,020 83020
Stup Consultants P.Ltd 206 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
25.2 40 amps MCCB, 10/12.5 HP VFD No. 20 70,057 1401140
25.3 30 amps MCCB, upto 7.5 HP VFD No. 14 57,192 800688
26 CONTROL PANELS FOR FANS
Design, manufacture, supply, installation, testing and commissioning of the following cubicle
type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall,
wiring terminating into MCCB and copper earthing, in each panel shall be provided by the
electrical contractor.
All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation
through BAS. All starters shall be provided with potential free Contact for Connections to
Building Automation System.
All wiring and copper earthing of motors from the panel shall be included.
The panel shall include the following components & accessories.
a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of
25 KA.
b. DOL / SD starter as per HP gratings given.
c. Terminal block for power distribution as required.
d. Contactor, over load relay with built in single phasing protection.
e. Phase indicating lights and indicating light for `ON’ status.
f. 144 mm x 144 mm voltmeter and digital ammeter.
g. Time delay relay for delayed automatic restart of motor.
h. Wiring for microswitch for stopping the fan when fire damper closes (in case of Fan only).
i. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel
to facilitate override of the automatic operation.
j. All starters shall be provided with suitable potential free contract for connections to the Building
Automation System.
The number of control panels shall be as follows.
26.1 25 amps MCCB, 1.0 HP with DOL Starter No. 1 42,626 42626
26.2 25 amps MCCB, 1.5 HP with DOL Starter No. 1 42,626 42626
26.3 25 amps MCCB, 2.0 HP with DOL Starter No. 32 42,626 1364032
26.4 25 amps MCCB, 3.0 HP with DOL Starter No. 6 42,626 255756
Stup Consultants P.Ltd 207 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
26.5 40 amps MCCB, 5.0 HP with DOL Starter No. 14 42,626 596764
26.6 63 amps MCCB, 7.5 HP with Star-Delta Starter No. 10 48,890 488900
26.7 63 amps MCCB, 10 HP with Star-Delta Starter No. 28 49,181 1377068
26.8 63 amps MCCB, 12.5 HP with Star-Delta Starter No. 6 51,681 310086
26.9 63 amps MCCB, 15 HP with Star-Delta Starter No. 22 54,909 1207998
25.10 80 amps MCCB, 20 HP with Star-Delta Starter No. 1 60,881 60881
25.11 125 amps MCCB, 75 HP with Star-Delta Starter No. 1 140,358 140358
27 CONTROL PANELS FOR AHUs (OPERATED THROUGH VFD) & Smoke Exhaust Fans
Design, manufacture, supply, installation, testing and commissioning of the following cubicle
type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall,
incoming cable wiring terminating into MCCB and copper earthing, in each panel shall be
provided by the electrical contractor.
All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation
through BAS. All starters shall be provided with potential free Contact for Connections to
Building Automation System.
All internal wiring, power cabling and copper earthing of motors from the panel to VFD & to the
motor and for Motor of Smoke exhaust Fan shall be included.
The panel shall include the following components & accessories.
a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of
25 KA.
b. Terminal block for power distribution as required.
c. Contactor, over load relay with built in single phasing protection.
d. Phase indicating lights and indicating light for `ON’ status.
e. 144 mm x 144 mm voltmeter and digital ammeter.
f. Time delay relay for delayed automatic restart of motor.
g. Wiring for microswitch for stopping the fan when fire damper closes (in case of Fan only).
Stup Consultants P.Ltd 208 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
h. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel
to facilitate override of the automatic operation.
i. 3 Nos of Single Pole MCB's Shall be provided at the incoming section of the starter panel for
DDC Panel , fire damper actuator & as a spare.
j. All starters shall be provided with suitable potential free contract for connections to the Building
Automation System.
k. 220 / 24 V Transformer
The number of control panels shall be as follows.
27.1 AHU -- 15 HP with VFD & Smoke Exhaust fan -20 HP No. 38 15,000 570000
Incoming :
63 Amps 25 KA breaking Capacity TP MCCB -- 1set
Busbar
100 Amps TPN aluminium busbar having
suitable fault level, with PVC heat shrunk
sleeves on SMC/DMC supports.
Outgoing :
For AHU- 15 HP)
63 Amps ,TP MCCB -- 1set
(0-500) V digital Voltmeter with built in Selector
switch -- 1set
Digital Ammeter with built in selector
switch- 1set
Stup Consultants P.Ltd 209 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
Current Transformers - 1set
LED type RYB phase indication lights- 1set
START-STOP Push Buttons -- 1 set
Space for VFD for AHU fan motor
Auto-Manual type selector switch
to facilitate auto start of AHUs
after restoration of power -- 01 set.
Control wiring and safety circuit as required
with start-stop push buttons stay put or
lockable type -1 set.
For Axial Fan for Smoke Exhaust- 20 HP
63 Amps 25 KA breaking capacity TP MCCB -- 1 set
Digital Ammeter with built in selector
switch-1set
LED type ON & OFF indication lights --1 set
START-STOP Push Buttons -- 1 set
20 HP Star Delta starter with built-in single phasing
preventor & overload relay & adjustable timer-- 1 set
Control wiring and safety circuit as required
with start-stop push buttons stay put or
lockable type -1 set.
27.2 AHU -- 7.5 HP with VFD & Smoke Exhaust fan -10 HP No. 4 10,000 40000
Incoming :
Stup Consultants P.Ltd 210 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
63 Amps 25 KA breaking capacity TP MCCB -- 1set
Busbar
63 Amps TPN aluminium busbar having
suitable fault level, with PVC heat shrunk
sleeves on SMC/DMC supports.
Outgoing :
For AHU- 7.5 HP)
40 Amps 25 KA breaking Capacity TP MCCB -- 1 set
(0-500) V digital Voltmeter with built in Selector
switch -- 1set
Digital Ammeter with built in selector
switch- 1set
Current Transformers - 1set
LED type RYB phase indication lights- 1set
START-STOP Push Buttons -- 1 set
Space for VFD for AHU fan motor
Auto-Manual type selector switch
to facilitate auto start of AHUs
after restoration of power -- 01 set.
Control wiring and safety circuit as required
with start-stop push buttons stay put or
lockable type -1 set.
For Axial Fan for Smoke Exhaust- 10 HP
Stup Consultants P.Ltd 211 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
40 Amps 25 KA breaking Capacity TP MCCB -- 1 set
Digital Ammeter with built in selector
switch-1set
LED type ON & OFF indication lights --1 set
START-STOP Push Buttons -- 1 set
10 HP Star Delta starter with built-in single phasing
preventor & overload relay & adjustable timer-- 1 set
Control wiring and safety circuit as required
with start-stop push buttons stay put or
lockable type -1 set.
28 CONTROL PANELS FOR AHUs & Smoke Exhaust Fans for Auditorium
Design, manufacture, supply, installation, testing and commissioning of the following cubicle
type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall,
incoming cable wiring terminating into MCCB and copper earthing, in each panel shall be
provided by the electrical contractor.
All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation
through BAS. All starters shall be provided with potential free Contact for Connections to
Building Automation System.
All internal wiring, power cabling and copper earthing of motors from the panel to the motor
and for Motor of Smoke exhaust Fan shall be included.
The panel shall include the following components & accessories.
a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of
25 KA.
b. Terminal block for power distribution as required.
c. Contactor, over load relay with built in single phasing protection.
d. Phase indicating lights and indicating light for `ON’ status.
Stup Consultants P.Ltd 212 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
e. 144 mm x 144 mm voltmeter and digital ammeter.
f. Time delay relay for delayed automatic restart of motor.
g. Wiring for microswitch for stopping the fan when fire damper closes (in case of Fan only).
h. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel
to facilitate override of the automatic operation.
i. 3 Nos of Single Pole MCB's Shall be provided at the incoming section of the starter panel for
DDC Panel , fire damper actuator & as a spare.
j. All starters shall be provided with suitable potential free contract for connections to the Building
Automation System.
k. 220 / 24 V Transformer
The number of control panels shall be as follows.
28.1 AHU -- 15 HP with VFD & Smoke Exhaust fan -20 HP No. 2 15,000 30000
Incoming :
63 Amps 25 KA breaking Capacity TP MCCB -- 1set
Busbar
100 Amps TPN aluminium busbar having
suitable fault level, with PVC heat shrunk
sleeves on SMC/DMC supports.
Outgoing :
For AHU- 15 HP)
63 Amps ,TP MCCB -- 1set
Stup Consultants P.Ltd 213 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
(0-500) V digital Voltmeter with built in Selector
switch -- 1set
Digital Ammeter with built in selector
switch- 1set
Current Transformers - 1set
LED type RYB phase indication lights- 1set
START-STOP Push Buttons -- 1 set
Auto-Manual type selector switch
to facilitate auto start of AHUs
after restoration of power -- 01 set.
Control wiring and safety circuit as required
with start-stop push buttons stay put or
lockable type -1 set.
For Axial Fan for Smoke Exhaust- 20 HP
63 Amps 25 KA breaking Capacity TP MCCB -- 1 set
Digital Ammeter with built in selector
switch-1set
LED type ON & OFF indication lights --1 set
START-STOP Push Buttons -- 1 set
20 HP Star Delta starter with built-in single phasing
preventor & overload relay & adjustable timer-- 1 set
Control wiring and safety circuit as required
with start-stop push buttons stay put or
lockable type -1 set.
28.2 AHU -- 7.5 HP with VFD & Smoke Exhaust fan -10 HP No. 2 15,000 30000
Stup Consultants P.Ltd 214 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
Incoming :
63 Amps 25 KA breaking capacity ,TP MCCB -- 1set
Busbar
100 Amps TPN aluminium busbar having
suitable fault level, with PVC heat shrunk
sleeves on SMC/DMC supports.
Outgoing :
For AHU- 7.5 HP)
40 Amps ,TP MCCB -- 1set
(0-500) V digital Voltmeter with built in Selector
switch -- 1set
Digital Ammeter with built in selector
switch- 1set
Current Transformers - 1set
LED type RYB phase indication lights- 1set
START-STOP Push Buttons -- 1 set
Auto-Manual type selector switch
to facilitate auto start of AHUs
after restoration of power -- 01 set.
Control wiring and safety circuit as required
with start-stop push buttons stay put or
lockable type -1 set.
Stup Consultants P.Ltd 215 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
For Axial Fan for Smoke Exhaust- 10 HP
40 Amps ,TP MCCB -- 1 set
Digital Ammeter with built in selector
switch-1set
LED type ON & OFF indication lights --1 set
START-STOP Push Buttons -- 1 set
10 HP Star Delta starter with built-in single phasing
preventor & overload relay & adjustable timer-- 1 set
Control wiring and safety circuit as required
with start-stop push buttons stay put or
lockable type -1 set.
AHU -- 5.0 HP with VFD & Smoke Exhaust fan -5/ 7.5 HP
28.3 No. 2 15,000 30000
Incoming :
63 Amps 25 KA breaking Capacity TP MCCB -- 1set
Busbar
100 Amps TPN aluminium busbar having
suitable fault level, with PVC heat shrunk
sleeves on SMC/DMC supports.
Outgoing :
For AHU- 5.0 HP)
40 Amps ,TP MCCB -- 1set
(0-500) V digital Voltmeter with built in Selector
switch -- 1set
Stup Consultants P.Ltd 216 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
Digital Ammeter with built in selector
switch- 1set
Current Transformers - 1set
LED type RYB phase indication lights- 1set
START-STOP Push Buttons -- 1 set
Auto-Manual type selector switch
to facilitate auto start of AHUs
after restoration of power -- 01 set.
Control wiring and safety circuit as required
with start-stop push buttons stay put or
lockable type -1 set.
For Axial Fan for Smoke Exhaust- 10 HP
40 Amps ,TP MCCB -- 1 set
Digital Ammeter with built in selector
switch-1set
LED type ON & OFF indication lights --1 set
START-STOP Push Buttons -- 1 set
10 HP Star Delta starter with built-in single phasing
preventor & overload relay & adjustable timer-- 1 set
Control wiring and safety circuit as required
with start-stop push buttons stay put or
lockable type -1 set.
Total : "A" Carried to Summary 227927900
455855800.1
Stup Consultants P.Ltd 217 of 234
RATE (INR) AMOUNT (INR)
B. PIPING-CHILLED, HOT WATER AND CONDENSER
WATER
PIPING-CHILLED/ HOT WATER
1
Supplying, laying/ fixing, testing and commissioning of
following nominal sizes of chilled water piping inside
the building with necessary clamps, vibration isolators
and fittings like bends, elbows, tees, reducers, mating
flanges & sockets for BAS, fabricated to size and shape
in workshop or brought out ready made where available
of acceptable quality but excluding valves, strainers,
gauges etc.) duly insulated with following closed cell
elastometric nitrile rubber of class 'O' insulation applied
by adhesive confirming to standard specifications and
finally applying 0.63mm aluminium sheet cladding
complete with type3 , grade 1 roofing feltstrip (as per
IS:1322 as amended up to date ) at joints and repairing
of damage to building etc. as per specifications and as
required complete in all respect.
Note:-The Pipes of sizes 150mm & below shall be M.S.
'C' class as per IS : 1239 and pipes size above 150mm
shall be welded black steel pipe heavy class as per IS:
3589, from minimum 6.35mm thick M.S. Sheet for pipes
upto 350 mm dia. and from minimum 7mm thick M.S.
Sheet for pipes of 400 mm dia. and above .
1.1 400mm dia. (32 mm thick insulation) RM 180 9268 1668240
350mm dia. (32 mm thick insulation) RM 65 6151 399815
300mm dia. (32 mm thick insulation) RM 2 5564 11128
250mm dia. (32 mm thick insulation) RM 465 4805 2234325
200mm dia. (32 mm thick insulation) RM 225 3858 868050
150mm dia. (32 mm thick insulation) RM 50 2733 136650
125mm dia. (32 mm thick insulation) RM 60 2409 144540
100mm dia. (32 mm thick insulation) RM 125 1980 247500
80mm dia. (32 mm thick insulation) RM 475 1458 692550
65mm dia. (32 mm thick insulation) RM 30 1201 36030
50mm dia. (32 mm thick insulation) RM 40 1034 41360
40mm dia. (32 mm thick insulation) RM 10 843 8430
32mm dia. (19 mm thick insulation) RM 20 666 13320
25mm dia. (19 mm thick insulation) RM 30 559 16770
2
Supplying, fixing, testing and commissioning of following
valves, strainers, gauges in the chilled water plumbing
duly insulated to the same specifications adequately
supported as per specifications.
Bill of Quantities- HVAC Work
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW IN
U.P.
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
Stup Consultants P.Ltd 218 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
2 BUTTERFLY VALVE (MANUAL) with C I body SS Disc,
Nitrile Rubber Seal & O- Ring PN 16 pressure rating
with counter flanges, nuts & bolts and gasket to suit
pressure ratingfor chilled water/ hot eater circulation
as specified
2.1 250 mm dia Nos. 8 13728 109820
2.2 200 mm dia Nos. 17 10982 186694
2.3 150mm dia. Nos. 1 6499 6499
2.4 125mm dia. Nos. 4 5654 22616
2.5 100mm dia. Nos. 4 5205 20820
2.6 80mm dia. Nos. 80 3638 291040
2.7 65mm dia. Nos. 2 3269 6538
2.8 50mm dia. Nos. 2 2978 5956
2.9 40mm dia. Nos. 6 2629 15774
3 BALANCING VALVE WITH BUILT IN MEASURING
FACILITY with C I body flanged construction with EPDM
coated disc with long pitch with protected out pipe
insulation & PN 16 pressure rating for chilled / hot water
circulation as specified.
3.1 250mm dia Nos. 4 60819 243275
3.2 200mm dia Nos. 5 48655 243275
3.3 150mm dia. Nos. 1 27028 27028
3.4 125mm dia. Nos. 4 18608 74432
3.5 100mm dia. Nos. 2 11839 23678
3.6 80mm dia. Nos. 40 7318 292720
3.7 65 mm dia Nos. 1 7024 7024
3.8 50mm dia. Nos. 1 6317 6317
3.9 40 mm dia Nos. 5 3119 15595
4 BUTTERFLY VALVE (Without ON/ OFF actuator) for
Motorised fuction) with C I body SS Disc, Nitrile Rubber
Seal & O- Ring PN 16 pressure rating with counter
flanges, nuts & bolts and gasket for chilled water/ hot
eater circulation as specified.
4.1 200 mm dia Valves. Nos. 6 10982 65892
4.2 150 mm dia Valves. Nos. 1 6499 6499
4.3 125 mm dia Valves. Nos. 4 5654 22616
5 NON - RETURN VALVE with duel plate of C I body
SS plates vulcanized NBR seal flanged end & PN 16
pressure rating for chilled / hot water circulation
including insulation as specified.
5.1 200mm dia. Nos. 6 9530 57180
5.2 150mm dia. Nos. 1 6354 6354
5.3 125mm dia. Nos. 1 5046 5046
5.4 100mm dia Nos. 1 3776 3776
6 Y - STRAINER of Ductile CI Body flanged ends with
stainless steel strainer for chilled/ hot water circulation
including insulation as specified.
6.1 200mm dia Nos. 6 20741 124446
6.2 150mm dia. Nos. 1 10418 10418
6.3 125mm dia. Nos. 1 9880 9880
Stup Consultants P.Ltd 219 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
6.4 100mm dia Nos. 2 6806 13612
6.5 80mm dia Nos. 40 4948 197920
6.6 65mm dia. Nos. 1 4746 4746
6.7 50mm dia. Nos. 2 3446 6892
6.8 40mm dia. Nos. 5 2423 12115
7 Providing and fixing in position the industrial type
pressure gauges with gun metal / brass valves
complete as required Nos. 150 958 143700
8 Providing & fixing in position the mercury in glass
industrial type thermometers. Nos. 120 688 82560
PIPING-CONDENSER WATER
9 Supplying, fixing, testing and commissioning of
condenser water pipes of following sizes of MS 'C' class
along with necessary clamps, vibration isolators and
fittings such as bends,tees, reducers, mating flanges &
sockets for BAS, fabricated to size and shape in
workshop or brought out ready made where available of
acceptable quality but excluding valves, strainers,
gauges etc. adequately supported on rigid supports duly
painted/buried in ground excavation and refilling etc. as
per specification and as required complete in all
respect.
Note:-The Pipes size 150mm & below shall be M.S. 'C'
class as per IS : 1239 and pipes size above 150mm
shall be welded black steel pipe heavy class as per IS:
3589, from minimum 6.35mm thick M.S. Sheet for pipes
upto 350 mm dia. And from minimum 7mm thick MS
sheet for pipes of 400 mm dia and above.
9.1 600mm dia. RM 435 12420 5402700
9.2 300mm dia. RM 110.0 4140 455400
9.3 250mm dia RM 1 3485 3485
9.4 200mm dia. RM 1 2875 2875
9.5 150mm dia. RM 1 1942 1942
9.6 125mm dia. RM 1 1671 1671
9.7 100mm dia. RM 10 1399 13990
Supplying, fixing, testing and commissioning of following
valves, gauges and strainers for condenser water
circulation as per specifications.
10 BUTTERFLY VALVE (MANUAL) with C I body SS disc
nitrile sheet & O - ring & PN 16 pressure rating as
specified with counter flanges, nuts & bolts and gasket
to suit pressure rating.
10.1 600mm dia. Nos. 6 137444 824663
10.2 300mm dia. Nos. 8 28654 229235
10.3 250mm dia. Nos. 5 22017 110085
10.4 200mm dia. Nos. 1 10199 10199
10.5 150mm dia. Nos. 1 5845 5845
10.6 125mm dia. Nos. 1 5068 5068
Stup Consultants P.Ltd 220 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
10.7 100mm dia. Nos. 4 4615 18460
10.8 80mm dia. Nos. 1 3256 3256
10.9 65mm dia. Nos. 1 2921 2921
10.10 50mm dia. Nos. 12 2634 31608
10.11 40mm dia. Nos. 8 2329 18632
11 Double regulating manual BALANCING VALVES.
11.1 300 mm dia. Nos. 4 148776 595104
11.2 250 mm dia. Nos. 5 108304 541519
11.3 200 mm dia. Nos. 1 46655 46655
12 BUTTERFLY VALVE (Without ON/ OFF actuator) for
Motorised fuction) with C I body SS Disc, Nitrile Rubber
Seal & O- Ring PN 16 pressure rating with counter
flanges, nuts & bolts and gasket to suit pressure rating
12.1 300 mm dia Valves. Nos. 4 28654 114617
12.2 250 mm dia Valves. Nos. 5 12749 63744
12.3 200 mm dia Valves. Nos. 1 10199 10199
13 Providing and fixing in position following ball valves
without Y strainer.
13.1 40 mm dia valves Nos. 1 2000 2000
13.2 32 mm dia valves Nos. 1 1800 1800
13.3 25 mm dia valves Nos. 1 1300 1300
14 Providing and fixing in position the following ball valves
withY strainer
14.1 25 mm dia Valves Nos. 1 1800 1800
15 Providing and fixing in position the following globe
valves :
15.1 32 mm dia valves Nos. 1 2500 2500
15.2 25 mm dia valves Nos. 1 2100 2100
15.3 20 mm dia valves Nos. 1 1800 1800
16 Providing and fixing in position the following check
valves with dual plate of C I body SS plates vulcanized
NBR seal flanged end & PN 16 pressure rating as
specified.
16.1 250mm dia. Nos. 6 10925 65550
16.2 200mm dia. Nos. 1 8740 8740
16.3 150mm dia. Nos. 1 5705 5705
17 Providing and fixing in position the following ‘Y’
Strainers :
Stup Consultants P.Ltd 221 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
17.1 250 mm dia strainers Nos. 6 25301 151808
17.2 200 mm dia strainers Nos. 1 20241 20241
18 Providing and fixing in position the following Automatic
Backwash type pot strainers
18.1 600 mm dia pipes Nos. 2 1027208 2054416
18.2 400 mm dia pipes Nos. 1 652055 652055
19
Supplying, laying/ fixing, testing and commissioning of
following nominal sizes of AHU/ FCU Condensate Drain
water piping with necessary clamps,and fittings like
bends, elbows, tees, reducers, mating flanges,
fabricated to size and shape in workshop or brought out
ready made where available of acceptable quality but
excluding valves, strainers, gauges etc.) duly insulated
with following closed cell elastometric nitrile rubber of
class 'O' insulation applied by adhesive confirming to
standard specifications and finally applying 0.63mm
aluminium sheet cladding complete with type3 , grade 1
roofing feltstrip(as per IS:1322 as amended up to date )
at joints and repairing of damage to building etc. as per
specifications and as required complete in all respect.
Note:-The Pipes of sizes 150mm & below shall be M.S.
'C' class as per IS : 1239 Alternatively GI
'B' Class piping can also be used as per instruction of
Site Engineer.
19.1 50mm dia. (32 mm thick insulation) RM 1 1034 1034
19.2 40mm dia. (32 mm thick insulation) RM 200 843 168600
19.3 32mm dia. (19 mm thick insulation) RM 1 666 666
11 2 Way Control Valves with Actuator and Thermostat
complete with control wiring for AHUs. The actuator
shall be capable of accepting 2-10 VDC / 4-20 mA
electric signal and shall provide similar transduced
feedback output signal to control system for flow
measurement. The minimum close off pressure
actuator must be 1.5 times shut off head of pump 5 bars
whichever is maximum. The valves shall be suitable for
following pipe sizes (CV ratings to be checked by the
Contractor and shall get approved) :
11.1 80 mm dia. Nos. 2 41462 82924
11.2 65 mm dia. Nos. 40 37992 1519693
11.3 50 mm dia. Nos. 1 24556 24556
11.4 40 mm dia. Nos. 5 20535 102674
Total : "B" Carried to Summary 22263995
C. AIR DISTRIBUTION
(FOR FACTORY FABRICATED DUCTS )
Stup Consultants P.Ltd 222 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
1 Supply, installation, balancing and commissioning of
factory fabricated GSS sheet metal rectangular/round
ducting complete with neoprene rubber gaskets,
elbows, splitter dampers, vanes, hangers, supports etc.
as per approved drawings and specifications of
following sheet thickness complete as required.
1.1 Thickness 0.63 mm sheet sq.m 18000 725 13050000
1.2 Thickness 0.80 mm sheet sq.m 11250 890 10012500
1.3 Thickness 1.00 mm sheet sq.m 9375 1004 9412500
1.4 Thickness 1.25 mm sheet sq.m 12500 1257 15712500
2 Kitchen ducting 1.25 mm GSS sheet with all
accessories as per specifications. (with clean outs as
per NFPA at base of vertical riser and change in
direction and maximum at every 6.1 M in horizontal &
every third floor of vertical riser ) sq.m 750 1697 1272713
3 (FOR DUCTS FABRICATED AT SITE AS PER “IS”
CODES)
Supply, installation, balancing and commissioning of
fabricated at site GSS sheet metal rectangular/round
ducting complete with neoprene rubber gaskets,
elbows, splitter dampers, vanes, hangers, supports etc.
as per approved drawings and specifications of
following sheet thickness complete as required.
3.1 Thickness 0.63 mm sheet sq.m 6750 605 4083750
3.2 Thickness 0.80 mm sheet sq.m 3750 728 2730000
3.3 Thickness 1.00 mm sheet sq.m 2500 949 2372500
3.4 Thickness 1.25 mm sheet sq.m 2500 1072 2680000
4 Supply, installation, testing and commissioning of fire
retardant paint/ wraping complete in all respects, on
kitchen exhaust ducts, smoke extraction ducts with
“Fire duct wrap (3M) / Fire paint (Starcoat-CRC / Flame
bar BW11) or cladding (Promat)/ Equivalent Fire
Retardant Paint to provide 1 Hr fire rating. sq.m 3000 897 2691000
5 Supply, fabrication, installation and testing the flexible
connections constructed of fire resistance flexible
double canvas sleeve as per the approved shop
drawings. sq.m 600 9000 5400000
6 Supply, installation and testing of galvanised steel
construction Louver dampers within ducts to be
provided with suitable ducts lever and quadrants
complete with neoprene rubber gaskets, nuts, bolts,
screws linkages, flanges etc, as per specifications for
manual control of volume of air flow and for proper
balancing of the air distribution system. sq.m 200 5413 1082600
7 Supply, installation, testing and commissioning of
Motorized (ON-OFF Type) duct mounted GI volume
control damper with enthalpy/ other sensor & controller
and necessary control wire (minimum 1.5 sqmm) for
integration within AHU room
7.1 Damper Sqmtr 80 6168 493440
7.2 Actuator Nos. 90 5342 480780
Stup Consultants P.Ltd 223 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
8 Supply, installation, testing and commissioning of
motorised combined smoke & fire damper in supply air
duct/main branch and return air path as and where
required of required sizes i/c control wiring , the damper
shall be motorized and spring return so as to close the
damper in the event of power failure automatically and
open the same in case of power being restored. The
spring return action shall be inbuilt mechanism and not
externally mounted. The damper shall also be closed in
the event of fire signal complete as required .Cost shall
be complete with control panel, inter connecting wiring
at locations shown in approved shop drawings and as
per specifications.
8.1 Smoke & Fire Dampers. sq.m 250 7053 1763250
8.2 Actuators Nos. 336 6551 2201136
9 Supply, installation, testing and balancing of powder
coated Extruded Aluminium supply air Grilles/ Linear
Grilles with removable core with aluminium volume
control dampers in accordance with the approved shop
drawings and specifications.
sq.m 450 7107 3198150
10 Supply, installation, testing and balancing of powder
coated Extruded Aluminium return air Grilles/ / Linear
Grilles with removable core without volume control
dampers in accordance with the approved shop
drawings and specifications. sq.m 500 4040 2020000
11 Supply, installation, testing and balancing of supply air
diffusers of powder coated aluminium with removable
core & anti smudge ring & with volume control
dampers as per approved drawings and specifications.sq.m 95 8661 822795
12 Supply, installation, testing and balancing of return air
diffusers of powder coated aluminium with removable
core & anti smudge ring without volume control
dampers as per approved drawings and specifications.sq.m 95 5594 531430
13 Supply, installation, testing and balancing of powder
coated Extruded Aluminium supply air and return air
grilles with Aluminium volume control Dampers in
accordance with the approved shop drawings and
specifications for Parking, Mechanical and Service
areas. sq.m 120 7107 852840
16 Supply, installation, testing and balancing of Powder
Coated Extruded Aluminium Linear supply Air Multi
Slot Diffuser complete with air pattern controllers &
Hit & Miss volume control damper as per specifications
and approved drawings. sq.m 1 8661 8661
17 Supply, installation, testing and commissioning of
Powder Coated Extruded Aluminium Multi Slot return
Air Diffuser with air pattern controller as per
specification and approved drawings. sq.m 1 5594 5594
Stup Consultants P.Ltd 224 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
18 Supplying & fixing of opposed blade volume control
dampers of GI in supply air duct collars as per
approved drawings and specifications. sq.m 0.1 5413 541
19 Supply, installation, testing and balancing of inlet air
louvers with bird screen and volume damper for fresh
air as per specifications and approved shop drawings.
19.1 Powder coated/Anodised extruded aluminium
construction. sq.m 150 7107 1066050
20 Supply, installation , testing and commissioning Powder
Coated Extruded Aluminium Air transfer door grilles
with rear side frame as per approved shop drawings.sq.m 10 7107 71070
22 Supply, installation, testing and balancing of louvers
with bird screen for exhaust air as per specifications
and approved drawings.
22.1 Powder coated/Anodised extruded aluminium
construction. sq.m 60 4040 242400
23 Motorised fresh air GI volume control dampers with
controllers, control Panel and control wiring complete
with gaskets, nut bolts, screws, linkages, flanges etc.
Damper actuator shall work on 230 V supply (derived
from AHU starter panel). Controller shall receive 4-20
mA / 0-10 V control signal from remote BMS system &
accordingly modulate fresh air quantity to the AHU.
Control shall give feed back signal to remote BMS
System. Fresh air dampers shall also be modulated
based on signal recieved from CO2 sensors. (CO2
sensors shall be by others).
23.1 Fresh Air Damper sq.m 30 6168 185040
23.2 Actuator Nos. 45 5342 240390
24 Constant Volume Regulator (For Toilet Exhaust ducts) Nos. 1000 611 610850
25 Supply, installation, testing and commissioning of
sound attenuators in supply & return air / exhaust ducts sq.m 1 15000 15000
Note :
The length of all sound attenuators shall be minimum
1200 – 1500 mm to be based on insertion loss
requirements as indicated in specification.
Total : "C" Carried to Summary 85309480
D THERMAL INSULATION
Stup Consultants P.Ltd 225 of 234
RATE (INR) AMOUNT (INR)
Bill of Quantities- HVAC Work
S.NO. DESCRIPTION OF ITEMS UNIT QUANTITY
1 Supplying and fixing of following thickness duly
laminated aluminum foil of mat finish closed cell Nitrile
rubber (class "O") insulation with protective coating on
existing duct after applying two coats of cold setting
adhesive (CPR X compound). The joints shall sealed
with 50 mm wide and 3 mm thick self adhesive nitrile
rubber tape insulation complete as per specifications
and as required.
1.1 19 mm thick nitrile rubber insulation for supply air ducts
in return air path / return air ducts. sq.m 30000 816 24480000
1.2 25 mm thick nitrile rubber insulation for supply duct (not
in RA path). sq.m 5000 1029 5145000
1.3 25 mm thick nitrile rubber insulation for supply & return
air ducts exposed to weather. sq.m 2000 1029 2058000
2 Supply and fixing of acoustic lining of supply air duct
and plenum with 25 mm thick resin bonded glass wool
having density of 32 kg/m³, with 25 mm X 25 mm GI
section of 1.25 mm thick, at 600 mm centre to centre
covered with Reinforced Plastic tissue paper and 0.5
mm thick perforated aluminum sheet fixed to inside
surface of ducts with cadmium plated nuts, bolts, stick
pins, CPRX compound etc. complete as required and
as per specifications.
Alternatively acoustic linning can be done by fixing High
Density glass wool Acoustic Board (UP Twiga or
Equivalent make) with the help of Stick pins and
suitable adhesive after getting the same approved from
the consultant. sq.m 1875 543 1018125
3 Supplying, fixing acoustic lining on wall of AHU rooms
(except walls on periphery/ adjoing shafts) and ceiling of
AC Plant rooms with 50mm thick, density 32 kg/cu.m
resin bonded glass fiber insulation friction fixed in
610mm x 610 mm frame work made of 25 X 50 X50 X
50 X 25 mm made out of 0.6mm thick GI sheet U
shaped channel and covered with reinforced fiber glass
tissue and finished with 0.80 mm perforated aluminium
sheet etc. complete as required and as per
specifications. sq.m 1000 864 864000
Total : "D" Carried to Summary 33565125
E. SYSTEM TESTING, BALANCING & COMMISSIONING
BY THIRD PARTY Lot 2500000
Total : "E" Carried to Summary 0
Stup Consultants P.Ltd 226 of 234
TOTAL
A.CENTRAL CONTROL STATIONS FOR BAS & FAS
SYSTEM140,000.00
B. SOFTWARES 2,429,072.00
C. CONTROLLERS 11,611,002.00
D. CABLES & ACCESSORIES 3,026,880.00
TOTAL 17,206,954
Bill of Quantities- BMS Work
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW, U.P.
SUMMARY OF COST
S.No. Description
Stup Consultants P.Ltd 227 of 234
No. Description Qty. Unit Rate Amount
1 Supplying, Installing, Testing & Commissioning of the Central
Control Stations consisting of the following
1.1 i7 or Equivalent Machine as per specification with cordless mouse
and cordless keyboard as per specification.1 No. 70,000.00 70,000.00
1.2 21" color monitor flat screen LED display as per specifications. 1 No. 35,000.00 35,000.00
1.3 Laser Jet Colour Printer (A3 size) as per Specification 1 No. 35,000.00 35,000.00
1.4 UPS Backup for BMS to be provided from Centralised UPS System
TOTAL CARRIED TO SUMMARY 140,000.00
B SOFTWARES
1 Supply, installation, testing & commissioning of the
following Software for BAS:
1.1 Testing and Commissioning of the Software for Building
Automation System as per Specifications. Software shall have the
capacity to accommodate1500 I/ O points or more.
1 Lot 628,992 628,992.00
1.2 Developing and commissioning of software interface with 60 __Nos
LM / KWH meters for two way flow of data between central control
station and static power meters.The price shall include the necessary
integrator required for integration and also the networking of all load
managers include network cabling.All necessary cabling (
Communication / signal & power ) from integrator / convertor to
each equipment shall be included in the scope.
1 Lot 570,040 570,040.00
Note : Above Cost shall also include Developing & commissioning
of Software interface for 6 Nos. VFD (for Primary Variable Pump ),
for 4 Nos. DG , 5 Nos Chiller Panels for two way flow of data
between central control station and Panels
1.3 Developing and commissioning of software interface with 2 Nos
Fire Alarm Panel for two way flow of data between central control
station and Fire Alarm panels.The price shall include the necessary
integrator required for integration and also the networking of all
include network cabling.All necessary cabling ( Communication /
signal & power ) from integrator / convertor to each equipment shall
be included in the scope.
1 Lot 560,000 560,000.00
1.4 Developing and commissioning of software interface with 44 Nos
BTU Meter for two way flow of data between central control station
and Meters and with 6 Nos UPS for two way flow of data between
central control station and Panels.The price shall include the
necessary integrator required for integration and also the networking
of all Chiller Panels. include network cabling.All necessary cabling (
Communication / signal & power ) from integrator / convertor to
each equipment shall be included in the scope.
1 Lot 570,040 570,040.00
1.5 Developing and commissioning of software interface with 18 Nos
Elevators Meter for two way flow of data between central control
station and Elevatorss.The price shall include the necessary
integrator required for integration and also the networking of all
Chiller Panels. include network cabling.All necessary cabling (
Communication / signal & power ) from integrator / convertor to
each equipment shall be included in the scope.
1 Lot 100,000.00 100,000.00
Bill of Quantities- BMS Work
CONSTRUCTION OF U.P.POLICE BHAWAN AT GOMTI NAGAR ,LUCKNOW IN U.P.
Stup Consultants P.Ltd 228 of 234
No. Description Qty. Unit Rate Amount
Bill of Quantities- BMS Work
TOTAL CARRIED TO SUMMARY 2,429,072.00
C BUILDING AUTOMATION SYSTEM
1 CONTROLLERS
Supply, Installation & Commissioning of following
equipment for BAS
1.1 Stand alone Intelligent DDC Controllers as per the specifications
for1500 IO points. The contractor shall decide upon the number of
contollers, depending on his Controller capacity. Expandable
modules for Inputs/Outputs are not allowed.Contractor shall
furnish quantity and unit rate for each type of controller
considered by him. The above shall be housed in a vandal proof,
lockable & secure MS powder coated Cabinets to be supplied along
with the Controllers.
1 Lot 3,377,308 3,377,308
1.2 System Integration Units consisting of Gateways, Interface units as
required The above shall be housed in a vandal proof, lockable &
secure MS powder coated cabinets to be supplied along with the
Controllers
1 Lot
1,140,080
1,140,080
1.3 Supply, installation, testing and commissioning of hand held
portable operator terminals.(POT). These shall be required if the
Controllers and Integration Units do not have a built in keypad on
the facia .
1 No 23,880.00 23,880.00
2 SENSORS & FIELD DEVICES
Supply, Installation & Commissioning of following
equipment for BAS
2.1 Differential pressure switches across the pumps for indicating the pumps status25 Nos 22,612 565,300.00
Water Flow Switches
2.2 Level Transmitter for monitoring water level in tanks 20 Nos 16,000.00 320,000.00
2.3 Supply, Installation, testing & commissioning of level switch
suitable for mounting for Sumps.( Low & High )20 Nos 8,500.00 170,000.00
2.4 Supply, installation, testing and commissioning of Actuator for
Motorised Butterfly Valve (Butterfly Valve to be installed by HVAC
contractor) of the following sizes with ON/OFF type actuators for
Chiller & Cooling Tower. The actuator shall have built-in limit
switches for close and open status and those switches shall be wired
to the DDC Panel and providing power supply to actuator shall be
scope of BAS. The valve with counter flange, gaskets & sutaible
nut-bolts.
2.4.1 300 mm 4 Nos 50,000 200,000.00
2.4.2 250 mm 5 Nos 45,000 225,000.00
2.4.3 200 mm 6 Nos 40,000 240,000.00
2.4.4 150 mm 1 Nos 37,000 37,000.00
2.4.5 125 mm 4 Nos 35,000 140,000.00
2.5 DP Switch Air for Monitoring Blower, Fan & Filter Status 228 Nos 5,060 1,153,680
Stup Consultants P.Ltd 229 of 234
No. Description Qty. Unit Rate Amount
Bill of Quantities- BMS Work
2.60 Duct Dew point Temperature Sensor 2 Nos 3,000 6,000
2.7 Duct type Temp. & RH Sensor 2 Nos 12,544.00 25,088
2.8 Immersion Temperature Sensor 13 Nos 5,976.00 77,688
2.9 CO Sensor as per specification 34 Nos. 20,154 685,236
2.10 Outdoor CO2 Sensor 1 Nos. 53,068 53,068
2.11 Duct Type CO2 Sensor 44 Nos. 53,068 2,334,992
2.12 Outside Air Temperature &Humidity Sensor 1 Nos 31,662 31,662
2.13 Water Hardness Analyiser 1 Nos 30,000.00 30,000
2.14 PH Analyiser 1 Nos 50,000.00 50,000
2.15 TDS Meter 1 Nos 40,000.00 40,000
Stup Consultants P.Ltd 230 of 234
No. Description Qty. Unit Rate Amount
Bill of Quantities- BMS Work
2.16 Air Velocity Sensor 44 Nos 9,000.00 396,000
2.17 Flame proof level transmitter 4 Nos 10,000.00 40,000
2.18 Water Flow Switch 2 Nos 7,200.00 14,400
2.19 Flame proof Oil level Switch 4 Nos 9,000.00 36,000
2.20 Outdoor Lux Sensor 1 Nos 30,620.00 30,620
2.21 Duct Temp. Sensor 56 Nos 3,000.00 168,000
TOTAL CARRIED TO SUMMARY 11,611,002.00
D CABLES & ACCESSORIES
1 CABLES & ACCESSORIES FOR BAS
1.1 Supplying, installing, testing and commissioning of 2 x 1.5 mm
signal / power cables armoured as per specification. (per I/O points
hard wired to DDC). More than two cables should not be saddled
to wall /ceiling. Perforated Cable tray /trunking of apropriate size
should be used more than two cables to be layed thru ceiling /walls.
37500 RMTR 50.00 1,875,000.00
1.2 Supplying, installing, testing and commissioning of 24 AWG
communication cables as per specifications.1800 RMTR 56.00 100,800.00
1.3 Supplying, installing, testing and commissioning of LAN cable. ( Cat-
6)2400 RMTR 55.00 132,000.00
1.4 Supplying, installing, testing and commissioning of 2 mm thick GI
trunking with cover of the following sizes complete with angle iron
supports/hanging arrangement etc
a. 40 x 300 x 40 360 RMTR 985.00 354,600.00
b. 40 x 200 x 40 360 RMTR 879.00 316,440.00
c. 25 x 150 x 25 360 RMTR 689.00 248,040.00
Total D 3,026,880.00
Stup Consultants P.Ltd 231 of 234
S.NO. PARTICULARS COST IN INR
1 ACOUSTICAL INTERIORS 10,489,250.00
2 SOUND REINFORCEMENT SYSTEM 11,704,992.00
3 VIDEO PROJECTION SYSTEM 4,478,000.00
4 STAGE LIGHTS AND FURNISHING 5,257,500.00
5 Audio Video other optional items (usagae subject to approval of design and
requirement)
22,385,163.00
Total Amount 54,314,905.00
SUMMARY OF COST OF AUDITORIUM SERVICES
CONSTRUCTION OF PROPOSED UP POLICE BHAVAN AT GOMTI NAGAR EXTENSION AT LUCKNOW.UP
Stup Consultants P.Ltd 232 of 234
S.No. ITEM OF WORK AREA IN
SQ.MT.
RATE TOTAL IN INR
1
1.1 WALL TREATMENT
1.1.1 Melamine foam fabric panels over perforated plywood.
Providing and fixing of fire retardant fabric panels (colour as approved by the consultant) consisting of FR grade fabric fixed to 25mm thick melamine foam over a layer of 9 mm thick commercial ply with 15% perforations fixed over a framework of 48mm GI Stud of 0.55mm thk @ 600mm c/c . The ply to have perforations as per design drawings. The foam to be backed with 50mm thick fibre glass resin bonded insulation of density 24kg/cum. The rate includes for all Geometry of wall, openings etc. and for complete item including all the required approved material, labour and fixing as per drawings. The work shall be executed by the suppliers Authorized applicators. Approved Make: Malimiano of ABSOUND Overseas/ BASF Basotect or equivalent.
340 4,250 1,445,000
1.1.2 P/F wood grained sound slats paneling
Providing and fixing Wood melamine finish MDF based panels with lineal perforations to be fixed on walls.The panels shall be with melamine laminate finish of size 2430mm x 128mm x15mm wirh 4mm slats at 28 mm pitch, Toungue and Groove edges for seamless mounting having density of 800kg/m3 . The back of the panels are perforated with 10mm diameter circular holes with a nonwoven fabric covering of 0.2mm for providing Sound absorption via the acoustic impedance method.Panel is to be fixed on GI framework as recommended by the manufacturer with screw fixed horizontal / vertical to wall at every 600mm c/c with centre & edge bracket in tongue & groove system on GI framework. The cavity of framework should be inserted with 50mm thick fibre glass resin bonded insulation of density 24kg/cum. Approved Make:ABSOUND Overseas/ ANUTONE Sound Slats or equivalent.
230 4,350 1,000,500
1.1.3 Wood-grained laminated reflective paneling
P/F acoustical paneling on the side walls and rear walls of the
auditorium as shown in the drawings, using:
• GI frame work of 48mm GI Studs, 0.55mm th. @ 610mm c/c . With
an air-gap of 50mm from the wall surface. (Alternately, using 50mm x
50mm softwood members, with fire and pest retardant treatment done,
at a spacing of 610 x 610mm, in both directions)
• The frame work to be filled with glass wool of 50mm thick of 24 kg/m
Cu. (Owens Corning/ UP Twiga) laminated with Black FRP Tissue on
the outer side, and chicken wire mesh support on the rear side
abutting the wall face
• The panels to be finished with 12mm MR grade commercial ply, and
1.0mm woodgrained laminate as per approval, in pattern as per
detailed drawing.
100 2,000.00 200,000.00
CONSTRUCTION OF PROPOSED UP POLICE BHAVAN AT GOMTI NAGAR EXTENSION AT LUCKNOW.UP
ACOUSTICAL INTERIORS
Stup Consultants P.Ltd 233 of 234
S.No. ITEM OF WORK AREA IN
SQ.MT.
RATE TOTAL IN INR
1 ACOUSTICAL INTERIORS
1.1.4 Steam Beech/ Hardwood slatted paneling
P/F wooden slatted paneling on auditorium side walls consisting of a
softwood framework made of 50mm x 50mm softwood members, with
fire and pest retardant treatment done, at a spacing of 610 x 610mm,
in both directions, filled with 48kg density glasswool, covered with
markin cloth of approved shade, finished in 100mm x 12.5mm Steam
Beech wooden slats, placed horizontally with a 25mm gap between
adjascent slats, as shown in drawings.
10 3,500.00 35,000.00
1.1.5 Stretched fabric in UPVC grippers paneling
P/F acoustical Panels on the side walls of the auditorium using:
• GI frame work of 48mm GI Studs using 0.55mm thick and stud
channels at 610mm x 610mm, 0.5mm thick, fixed with MS angle cleats
1220x610mm centers to wall by using metal fasteners, backed with 22
SWG x 12.5mm GI Chicken Wire Mesh with air gap a minimum of
50mm on back side, as per detailed drawing.
• The frame work to be filled with glass wool of 50mm thick of 48 kg/m
Cu. (Owens Corning/ UP Twiga) laminated with Black FRP Tissue on
the outer side, and chicken wire mesh support on the rear side abuting
the wall face.
Finished in stretched fabric finish, using UPVC grippers (Waltract/
equivalent) fixed to 50mm x 12.5mm MDF runners. The fabric to be fire-
retardant and scotch-guarded.
170 3,000.00 510,000.00
1.1.6 Wood wool fibre paneling
P/F acoustical Paneling on side and rear walls of the auditorium using:
• GI frame work at 610mm centers of 50mm x 50mm sectionS in 18
gauge fixed with MS angle cleats to wall by using metal fasteners,
• Glass wool fill 50mm thick of 48 kg/m Cu. Density with a minimum of
50mm air-gap.
• Finished in woodwool fiber tiles.
25 2,200.00 55,000.00
1.1.7 Black Woodwool Micro-fiber acoustical tiles paneling tiles
paneling
P/F acoustical Paneling on the side walls of stage area using:
• GI frame work at 610mm centers of 50mm x 50mm sectionS in 18
gauge fixed with MS angle cleats to wall by using metal fasteners,
• Glass wool fill 50mm thick of 24 kg/m Cu. Density with no air-gap.
Fixing Micro-fiber acoustical tiles (Anutone MAT-Ebony/ equivalent) of
size 595x595x15 mm, to the GI framework, providing an NRC 0.9.
Meeting the stringent fire test required having Class ‘P’ rating for
ignitability test as per BS 476 part 5 and Class ‘1’ rating as per BS 476
part 7 for surface spread of flame test.
190 2,500.00 475,000.00
1.2 ACOUSTICAL FALSE CEILING
Stup Consultants P.Ltd 234 of 234