construction requirements for communication installations
TRANSCRIPT
-
7/25/2019 Construction Requirements for Communication Installations
1/75
Note: The source of the technical material in this volume is the Professional
Engineering Development Program (PEDP) of Engineering Services.
Warning: The material contained in this document was developed for Saudi
Aramco and is intended for the exclusive use of Saudi Aramcos
employees. Any material contained in this document which is notalready in the public domain may not be copied, reproduced, sold, given,
or disclosed to third parties, or otherwise used in whole, or in part,
without the written permission of the Vice President, Engineering
Services, Saudi Aramco.
Chapter : Communications For additional information on this subject, contact
File Reference: COP10106 J.S. Phillips on 873-0228
Engineering EncyclopediaSaudi Aramco DeskTop Standards
Construction Consideration
-
7/25/2019 Construction Requirements for Communication Installations
2/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards
CONTENTS PAGES
CONSTRUCTION REQUIREMENTS OF CIVIL WORK FOR
STRUCTURES ......................................................................................................1
Conduits .....................................................................................................1
Plastic Conduit - Types and Use .....................................................1
Manholes ....................................................................................................8
Types and Dimensions....................................................................9
Laterals............................................................................................9
Termination...................................................................................10
Grounding .....................................................................................12Sump.............................................................................................12
Pulling-In Irons.........................................................................................12
Ladders .........................................................................................14
Lids ...............................................................................................14
Racks.............................................................................................16
Pedestal Installations ................................................................................18
Direct Buried Cable..................................................................................21
Buried Service Wire......................................................................27
Installing Cable Markers ..........................................................................28
Marking and Identification ...........................................................28
Placement in Trenches ..................................................................34
Separation.................................................................................................34
SPLICING CABLE: METHODS, MATERIALS, AND NUMBERING
CODES ................................................................................................................39
Cable Numbering and Count Identification..............................................39Methods....................................................................................................44
Straight Splices .............................................................................45
Butt Splices...............................................................................................46
-
7/25/2019 Construction Requirements for Communication Installations
3/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards
Materials...................................................................................................48
Splice Closures .............................................................................48
Connectors/Bonding Clips ............................................................48
BURIED CABLE: SPLICING, BONDING, AND SEPARATION
REQUIREMENTS...............................................................................................51
Splicing.....................................................................................................51
Direct Buried ............................................................................................51
In Pedestal.....................................................................................52
Bonding and Grounding ...........................................................................52
Separation.................................................................................................54
TECHNIQUES AND DESIGN CONSIDERATIONS FOR PULLING,
RACKING, SPLICING, AND BONDING AND GROUNDING OF
UNDERGROUND CABLE .................................................................................55
Pulling ......................................................................................................55
Standards.......................................................................................56
Procedures.....................................................................................58
Racking.....................................................................................................61
Standards.......................................................................................61
Procedures.....................................................................................61
Hardware Requirements................................................................66
Safety........................................................................................................68
Splicing.....................................................................................................68
Bonding and Grounding ...........................................................................71
GLOSSARY ........................................................................................................72
-
7/25/2019 Construction Requirements for Communication Installations
4/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 1
CONSTRUCTION REQUIREMENTS OF CIVIL WORK FOR STRUCTURES
The following civil work for structures will be covered in this section:
Conduits
Manholes
Pedestal Installations
Direct Buried Cable
Installing Cable Markers
Separation
Conduits
The standards to be used for conduits are GTE Section No. 622-020-100 and Saudi Aramco
Engineering Standard (SAES)-T-911. The various types of conduit materials include plastic
and steel for Saudi Aramco applications. Single-bore, plastic conduit is the preferred type of
conduit for most of Saudi Aramcos needs.
Plastic Conduit - Types and Use
The type of conduit that is preferred for use in constructing Saudi Aramco Communication
Conduit Systems is Type DB which is also referred to as Type II duct. This conduit is a thick-
wall, round plastic (PVC) conduit with one bell end. This conduit is manufactured in standard
lengths of 20ft (6m) and is designed to be direct buried as long as the minimum cover can be
obtained. This conduit must conform to NEMA Standard TC-8 (AMS#15-312-017). Type
DB conduit may be installed in areas where the conduit will be exposed to sunlight
(ultraviolet radiation) as long as the conduit is treated and the thermal expansion and
contraction of the conduit are accounted for in the design through the use of expansion joints.
Straight, plastic conduit is furnished in the type and sizes that are shown in Figure 1. One
type has a bell end or a cemented coupling on one end. The other type is a straight, two
piece, snap-together plastic duct that is used to enclose existing cable.
-
7/25/2019 Construction Requirements for Communication Installations
5/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 2
Straight Plastic Conduit
Figure 1
-
7/25/2019 Construction Requirements for Communication Installations
6/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 3
Conduit is to be designed and engineered with the expectation that the conduit will continue
in service for 75 to 100 years. Underground conduit must be designed to withstand external
loads to which the conduit will be subjected. These external loads are caused by the
following sources:
Weight of the backfill material.
Weight of dead loads.
Weight of live (impact) loads.
Weight of any other loads that may be applied at the surface of the fill.
Detailed construction drawings are required for the placement of conduit in the following
situations:
Crossings of bridges and culverts.
Crossings where attachment is to be made to a specially designed structure.
Crossings under railroad tracks or embankments by means of boring, jacking,
or tunneling methods.
Installations where the conduit is to be laid through unstable ground that
requires piling or other means of support.
All conduit designs must take into consideration the vulnerability to future disturbance and
the degree of mechanical protection that is needed to safeguard the conduit and cable. The
following problem areas must be considered and avoided where possible:
Manmade troubles from other underground activities in the vicinity.
Unstable soil conditions.
Road rebuilds or relocations.
Future grade changes.
Unusual heavy traffic loading or the possibility of future heavy traffic loading.
-
7/25/2019 Construction Requirements for Communication Installations
7/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 4
Except for isolated conduits that are placed in buried cable runs, new and rebuilt conduit
systems (main, lateral, subsidiary) must be concrete-encased. The concrete is nonstructural
concrete in accord with SAES-Q-001 and 09-SAMSS-0917. The encasement that is required
is the top and sides in all situations. The top, sides, and bottom are encased in unstable soil
situations. Telecommunication main conduit structures that are placed in roadways and other
traffic areas must provide a minimum ground cover (depth) of 760mm (30 in).
Additional protective measures (PVC-coated steel pipe or higher strength concrete for
encasement) are needed in situations where the conduit is placed in traffic areas at depths of
less than 760mm (30 in). Main conduit sections must be placed at a minimum depth (cover)
of not less than 610mm (24 in) under the following conditions, provided that heavy duty
power-activated equipment is not employed for backfill compaction:
Along streets/roads but outside the area that is reserved for present or future
traffic.
In other non-traffic areas and other areas that are not subject to heavy vehicular
traffic.
The color orange must be used to identify telecommunication facilities. This color
identification of telecommunication conduit systems is accomplished through the use of the
following methods:
Mix orange dye with the concrete (refer to SAES-Q-001).
Mix orange dye with the top layer of concrete (refer to SAES-Q-001).
Place orange marker tape above the conduit concrete encasement surface. The
marker tape is to be located 300 - 600mm below grade and approximately
300mm above the conduit system upper surface.
-
7/25/2019 Construction Requirements for Communication Installations
8/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 5
Telecommunication cables or conduits must not be placed inside of the same concrete
encasement with power facilities or other underground utilities or facilities. Minimum
separation requirements between telecommunication facilities and non-
telecommunication/non-Saudi Aramco facilities must be maintained for identification,
protection from arcing, and reduction of stray currents. The minimum separation
requirements for telecommunication facilities are shown in Figure 2. These minimum
separation distances must be provided between telecommunication conduit structures and the
facilities that are listed in the figure.
Minimum Separation Requirements
Figure 2
-
7/25/2019 Construction Requirements for Communication Installations
9/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 6
Standard Saudi Aramco duct formations that consist of four or more ducts must be two or four
ducts wide. Exceptions to this formation must be approved in writing by the Saudi Aramco
Communications Engineering Division, Outside Plant Unit. Main conduit formations may
have to be changed, in some situations, to clear obstructions. The duct formation must return
to the original (at exit of previous manhole) formation before the conduit enters the next
manhole in these situations. The minimum amount of concrete encasement that is used must
be 75mm (3 in) along the sides and top of the duct formation. The concrete must be a
minimum of 75mm (3 in) when the concrete is to be placed on the bottom of the conduits.
Curves or bends in conduit runs should be avoided except for the minor curves that are
involved when splaying conduits at manhole entrances. The curves or bends that are
necessary in main conduit sections must not transverse more than 90 degrees and must not
have a radius of less than 6 meters (20 ft). The permissible length of a conduit section that
contains a bend or curve depends upon the angle between the straight conduit run on each
side of the curve and the radius of the curve. Generally, main conduit section lengths orvarious degrees of curve and radii of curve should not exceed those angles and radii that are
indicated in the chart in Figure 3. Figure 3 shows the angle in degrees and the radius in feet
(meters).
-
7/25/2019 Construction Requirements for Communication Installations
10/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 7
Conduit Lengths for Sections with One Curve
Figure 3
-
7/25/2019 Construction Requirements for Communication Installations
11/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 8
Conduit offsets change the direction of a conduit run. Conduit offsets that are in main conduit
runs must be constructed with large radius sweeps with a minimum of 30 m (100 ft) radius.
This radius sweep will minimize the resistance that is offered by the sweeps when cable is
pulled in.
Conduit spacers that provide a minimum of 38mm (1.5 in) separation between ducts must be
used in all concrete-encased curved sections of 15 m (50 ft) or less. This construction and all
conduit encasements must comply with the requirements of the following standards:
SAES-Q-101 - Criteria or Design and Construction of Concrete Structures
O9-SAMSS-088 - Aggregates for Concrete
09-SAMSS-097 - Ready Mixed Portland Cement Concrete
Manholes
The standards to be used for manholes are GTE Section No. 622-500-100, SAES-T-911, and
standard drawing AA-036795. All manholes should be constructed to provide sufficient and
suitable space for the cables and associated equipment that will be installed. Manholes that
are near the central office must be designed to provide duct space for the ultimate size of the
central office. All manholes must be designed to the following requirements:
Support the heaviest anticipated traffic weight (see also GTE 622-500-100,
SAES-Q-006, and NESC).
Be reasonably waterproof.
Provide sufficient racking space for the ultimate number of cables and other
equipment that will be placed in the manhole.
The types and sizes of the manholes will be indicated on the work order detail plans. Smaller
size manholes may be precast or they may be the poured type of manhole. Manhole
construction must comply to the following standards:
SAES-Q-001 - Criteria for Design and Construction of Concrete Structures.
09-SAMSS-088 - Aggregates for Concrete.
09-SAMSS-097 - Ready Mixed Portland Cement Concrete.
-
7/25/2019 Construction Requirements for Communication Installations
12/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 9
Types and Dimensions
Two types of manholes are available for use by Saudi Aramco:
Service manhole
Line manhole
Service manholes are designed for use as splicing or pulling points where no more than two
ducts (one duct for cable and one maintenance/repair duct) are located in the manhole. A line
manhole must be placed if more than two ducts are required. A service manhole must have
the minimum inside dimensions of 1.2m x 1.2m x 1.2m (4 feet x 4 feet x 4 feet) and must
permit cable racking on one wall only.
The line manhole is the basic manhole for telecommunications facilities. The dimensions of aline manhole are 3.75m x 1.85m x 2.0m (12 feet x 6 feet x 6.5 feet) (length x width x
headroom). This manhole can be a type A, J, L, or T manhole with the rearrangement of the
windows. The line manhole may contain a maximum of 24 main ducts in each end wall.
Line manholes must be designed for use in main and branch conduit systems when more than
two ducts will ultimately be required. If the number of loaded cable complements in the run
is insufficient to justify the construction of a loading manhole, this type of manhole may also
be used to house a minimum number of load coil cases. When the number and size of load
coil cases to be installed are small, load coils may be located in corners, attached to side
walls, or placed on the end walls of the manhole.
Laterals
A conduit and manhole system is only as good as the systems laterals that permit a readily
accessible network for distribution cables. When the laterals are built at the same time as the
main conduit, lateral ducts should be placed on top. This installation is not only the most
economical way to place the lateral duct, but it also affords some top protection for the main
run. Lateral ducts for future use should be placed at the same time as the main run. The only
additional cost that is involved is the cost of the material. This cost is negligible when
compared with the cost of the placement of a lateral system at a later date. Lateral ducts
between manholes that may be picked up and extended, when and where necessary, greatly
facilitate additions and changes in the distribution plant. Lateral ducts that are provided for
the future should be planned only after careful consideration of their future use. The length of
a lateral duct is limited mainly by the size of cable that will be pulled into the duct and by the
number of bends that the duct will contain.
-
7/25/2019 Construction Requirements for Communication Installations
13/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 10
Termination
The termination of ducts that enter precast or poured-in-place manholes is greatly simplified
through the provision of duct terminators. The application of interlocking two- or four-way
duct terminator units replaces the individual end bells. The interlocking duct terminator maybe combined before the installation to accommodate variation in the number of duct
entrances. Watertight duct entrances through the concrete manhole wall are made easier
when plastic duct can be cemented to the ABS duct terminator. The duct terminators are
constructed of high-impact, virgin ABS, that is formed into a double wall design of one piece
in the following manner:
The terminators are positioned as shown in Figure 4 in the thin wall (web) of
the manhole.
Reinforcing rods are placed in the spaces between the duct terminator walls.
The spaces ensure proper flow of the concrete aggregate.
The shoulder is made deep enough to accommodate the wall of the type II duct.
The radii must permit a smooth bearing surface for conductors or cable in order
to eliminate the possibility of damage that can be caused by sharp edges.
Solvent cement is applied to the interlocking surfaces to achieve a watertight
seal.
-
7/25/2019 Construction Requirements for Communication Installations
14/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 11
Duct Terminators
Figure 4
-
7/25/2019 Construction Requirements for Communication Installations
15/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 12
Grounding
Manholes are grounded through the use of a ground electrode that provides a ground
resistance of 25 ohms or less and must be provided along with the necessary bonding ribbon
and wire in each manhole. A ground rod that is used as the electrode must be a minimum of5/8 inches in diameter by 10 feet in length. After the hole has been excavated, the ground rod
must be driven in the corner of the manhole floor approximately 100mm from the side and
end walls. A second ground rod that is needed to obtain the required minimum ground
resistance must be driven into the manhole corner diagonally opposite to the first ground rod.
Manhole excavation in rock or other high soil resistive areas requires that the manhole
electrode be provided in the following manner:
Place a bare #6 AWG (or larger) tinned solid copper wire grid or counterpoise
under the manhole floor. Access points must be provided through the use of an
extension that is a minimum of 2.5 m of #6 AWG (or larger) wire above themanhole floor in diagonally opposite corners. This location is where the
ground rods would have been placed.
Bore the rock to provide access for the standard (or larger) ground rods or for a
ground well.
Sump
A sump hole must be provided in the floor of all new manholes. The sump must be at least
205mm (8 inches) deep and either 205mm (8 inches) in diameter or 205mm (8 inches) square.
The sump hole must be centered under the manhole opening and at a depth so that the
finished surface of the manhole floor can be sloped toward the sump.
Pulling-In Irons
A minimum of one pulling-in iron must be set (cast in concrete) in the manhole wall opposite
all manhole conduit entrances (window). The pulling-in iron as shown in Figure 5 must
extend far enough into the manhole to provide a minimum clear opening of 75mm (3 inches).
The pulling-in irons are located 150-300mm (6-12 inches) below the conduits with which the
pulling-in irons are associated and in-line with the centerline of the conduits. Pulling-in irons
must not be placed closer than 150mm (6 inches) to any manhole entrance window. Pulling-
in irons must not be allowed to bear against the outside face of the manhole wall (come incontact with earth), but the pulling-in irons must have adequate cover of concrete in
accordance with SAES-Q-001.
-
7/25/2019 Construction Requirements for Communication Installations
16/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 13
Pulling-In Irons
Figure 5
-
7/25/2019 Construction Requirements for Communication Installations
17/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 14
Ladders
Hot dipped galvanized steel manhole ladders must be installed in all newly constructed
manholes, except the service manhole. A manhole step is to be set in the roof opening of all
manholes that have headroom depths greater than 2.75m (9 feet) in order to provide a supportfor the ladder. A manhole step must be placed in all manhole openings of a 405mm (16
inches) neck depth. An additional step must be laced for each additional 305mm (12 inches)
of neck depth.
Lids
Telecommunication manhole lids (covers) must be Type B with 30-inch frames and covers,
and the lids must have the identification mark TELEPHONE stamped in the cover to
indicate ownership. Type B frames and covers, as shown in Figure 6, have a nominal
opening diameter of 30 inches, an outside diameter of 31 3/4 inches, and weigh 320 pounds.
Type B frames have a base frame with an outside diameter of 49 inches, inside diameter of 41
inches, height of 10 inches, and weigh 440 pounds. The lids are constructed with
corrugations and reinforcing ribs.
-
7/25/2019 Construction Requirements for Communication Installations
18/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 15
Lids
Figure 6
-
7/25/2019 Construction Requirements for Communication Installations
19/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 16
Racks
Each telecommunication manhole is to be fully equipped with cable racks and rack supports
at the time of construction. Non-metallic concrete inserts must be placed in the walls to
provide a means for attachment of the ultimate number of cable rack supports, brackets andother surface-mounted equipment. Cable racks are to be spaced at a maximum distance
838mm (33 inches) and as illustrated in GTE section 622-500-100 manhole diagrams. The
distance from the inside surface of the manhole wall to the first cable rack must be 760mm
(30 inches) or less. The manhole interior configuration that is shown in Figure 7 is the
standard to be used for telecommunications manholes. Ducts and cable racks are located in
manholes. The number of ducts and cable racks will vary in accordance with the dimensions
of the manhole.
-
7/25/2019 Construction Requirements for Communication Installations
20/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 17
Manhole Interior
Figure 7
-
7/25/2019 Construction Requirements for Communication Installations
21/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 18
Pedestal Installations
Two basic types of pedestal installations are available for use by Saudi Aramco:
Pedestal/Terminal
Facility Area Connector
The pedestal/terminal type installation provides a location to splice cables and to terminate
service drops. The most widely used communication terminal by Saudi Aramco is a GHC-8
(SAMSS-18-021-375). This communication terminal is available from Utility Products.
The self-supported installation of a GHC-8 is shown in Figure 8. The pedestal is placed in
150mm of excavated earth and 370mm of undisturbed earth. These depths are measured from
the ground line to the bottom of the pedestal lower cover and the bottom of the pedestalbackplate. The width of the excavated earth is 305mm. A ground line marker is provided on
the pedestal. The pedestal is grounded through the use of a #6 AWG solid, bare, tinned
ground wire. The ground wire is bonded to a ground rod by means of an exothermic weld or
a ground rod clamp. This bond must be UL-listed for direct burial. The ground rod is placed
600mm from the pedestal and at a depth of 100mm from the ground line. The ground rod
must be a minimum 5/8 inch in diameter and 8 feet in length. The actual ground resistance of
the ground rod must be 25 ohms or less.
-
7/25/2019 Construction Requirements for Communication Installations
22/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 19
GHC-8 (Self Supported Mounting)
Figure 8
-
7/25/2019 Construction Requirements for Communication Installations
23/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 20
The GHC-8 can also be stake-mounted as shown in Figure 9. A stake is attached to the
pedestal. The pedestal is mounted in the earth in accord with the same mounting dimensions
and grounding requirements as the self-supported GH-8.
GHC-8 (Stake Mounting)
Figure 9
-
7/25/2019 Construction Requirements for Communication Installations
24/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 21
The facility area connector (FAC) type installation provides an interface between feeder and
distribution cables. The most widely used communication FAC by Saudi Aramco is the
Feeder-Distribution Interface (FDI), 40EP-1-76S/1800 (SAMSS 18-013-165) from AT&T.
The AT&T Feeder-Distribution Interfaces are 40-type cabinets that are available with 76-type
binding posts. The FDI designation (40EP-1-76S/1800) describes the following construction
features:
40 - Cabinet type
E - Cabinet size
P - Pedestal mounting
1 - Splicing from front of cabinet
76 - 76-type binding post
S - Standard (feeder in or distribution)
1800 - Number of pairs
40-type (size E) pedestal cabinets have a width of 40 inches, a height of 54 inches, and a
depth of 12 inches. The construction of the pad foundation for an FDI can be referenced in
standard drawing AA-036389.
Direct Buried Cable
The following Saudi Aramco standards relate to buried cable installation:
SAES-T-629 - Buried Cable and Wire
SAES-T-928 - Buried Plant
SAES-T-629 modifies the GTE 629 series for Saudi Aramco outside plant applications. The
scope of this standard includes the requirements for the following topics:
General buried cable and wire requirements.
Buried cable and wire precautions.
Exchange buried cable, distribution and service wire placement.
Joint buried cable installation.
Optimize direct buried cable delivery system.
Guide-buried cable and wire installation.
Joint buried cable maintenance and emergency safety precautions.
-
7/25/2019 Construction Requirements for Communication Installations
25/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 22
SAES-T-928 modifies the GTE 928 series for Saudi Aramco outside plant applications. The
scope of this standard includes the requirements for the following topics:
General buried plant requirements.
Housing terminal exchange buried plant - flush construction.
Housing terminal exchange buried plant - pedestal construction.
The minimum cover, fill material, and depth of excavation requirements are referenced in
standard drawing AA-036748. Standard drawing AA-036748 shows design requirements for
the following three installation situations:
Trenches in non-traffic areas
Trenches in rock
Trenches in Saudi Aramco road/street paved areas
The design requirements for trenches in non-traffic areas is shown in Figure 10. The cable is
placed at a minimum depth of 600mm. The cable must also be placed so that a minimum
space of 50mm exists on each side of the cable. The bottom of the trench is backfilled with a
minimum of 50mm of sand. The bottoms of excavated trenches and the backfill material for
use by Saudi Aramco must be free of rocks and debris that could damage the cables. The
cable is covered with a minimum of 50mm of sand or selected fill material. The next layer ofbackfill consists of 100mm of material that has no sharp rocks, no rocks that are larger than
50mm in diameter, and no organic material. The final layer of backfill consists of 450mm of
material that has no rocks that are larger than 100mm in diameter and no organic material
bulk. This 450mm layer also includes a buried cable marker tape that is placed at
approximately 50 percent of the cable depth, but not closer than 300mm to the cable. The
trench backfill must be compacted in 150mm lifts (200mm maximum) to the applicable
standard requirement. The compactness of non-traffic area trench backfill must be equal to or
better than the compactness of the surrounding material. Machine compaction is not
permitted within 150mm of the cable. The surface at grade level must be restored to as good
or better than original condition.
-
7/25/2019 Construction Requirements for Communication Installations
26/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 23
Trenches in Non-Traffic Areas
Figure 10
-
7/25/2019 Construction Requirements for Communication Installations
27/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 24
The design requirements for trenches in rock are shown in Figure 11. The maximum
excavation that is required in rock is 300mm. This maximum excavation assumes a minimum
cover of 200mm. The cable is placed at the minimum depth of 200mm. The cable is also
placed so that a minimum space of 50mm exists on each side of the cable. The bottom of the
trench is backfilled with a minimum of 50mm of sand. The cable is covered with 150mm of
sand or selected fill material. The buried cable marker tape is placed at approximately 50
percent of the cable depth. The final layer is 100mm of 3000 psi concrete. This layer of
concrete provides the required mechanical protection for the placement of buried telephone
cable with less than 450mm of cover.
Trenches in Rock
Figure 11
-
7/25/2019 Construction Requirements for Communication Installations
28/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 25
The design requirements for trenches in Saudi Aramco road/street paved areas are shown in
Figure 12. The cable or conduit is placed at a minimum depth of 760mm. The cable or
conduit must also be placed so that there is a minimum space of 300mm on each side of the
cable or conduit. The bottom of the trench is backfilled with 50mm of sand or select fill
material. The cable is also covered with 150mm sand or selected fill material. The final layer
of backfill must be a minimum of 510mm of crushed aggregate or selected marl. This layer
of backfill must be placed in layers that are not more than 200mm. This method of backfill is
to achieve not less than a 95% density of the material. The
buried cable marker tape is located in this layer at a depth that is approximately 50 percent of
the cable depth but not closer than 300mm to the cable. The amount of roadway that must be
removed through the use of saw cuts must be 375mm back from the edge of the trench or half
the width of the trench, whichever distance is greater. The base of the roadway must be
primed, and the edges of the original pavement must be tacked. A minimum of 100mm (but
not less than the original) of pavement must be restored. This restoration consists of thefollowing two layers:
Bottom layer is a minimum of 50mm of a 4A bituminous mix.
Top layer is a minimum of 50mm of a 6A bituminous mix.
-
7/25/2019 Construction Requirements for Communication Installations
29/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 26
Trenches in Saudi Aramco Road/Street Paved Areas
Figure 12
-
7/25/2019 Construction Requirements for Communication Installations
30/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 27
Buried Service Wire
Buried service wire, as shown in Figure 13, is a shielded, double-jacketed, two-pair,
polyvinylchloride, insulated, conductor assembly that is designed for direct burial from a
buried cable terminal or equivalent point to the customers building structure. Four No. 20AWG (40 percent conductivity grade) copper-covered steel conductors are each insulated
with color-coded polyethylene compound and cabled into a star quad. The color codes are
red, green, black, and yellow. The red and green conductors are placed diagonally opposite to
each other and form pair one. The black and yellow conductors form the second pair.
The quad is enclosed in a polyvinylchloride jacket over which is applied 0.009-inch
ungalvanized, steel strips, in a helical serving with a flooding compound. A black
polyvinylchloride jacket is extruded over the entire assembly.
Buried Service Wire
Figure 13
-
7/25/2019 Construction Requirements for Communication Installations
31/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 28
The following is a list of the minimum cover design requirements (per standard drawing AA-
036748) of buried service wire in various installation situations:
500mm in non-traffic areas
900mm under drainage ditches
200mm in rock locations
760mm under roads and streets
The design length of an individual buried service wire drop should not exceed 150m (500
feet). Buried service wire lengths up to 300m (1000 feet) are permitted on the occasions
where there is a legitimate reason for the placement of a longer drop. This longer drop length
must be included in the loop resistance/transmission calculations. Telecommunication cables
must be used when the drop length exceeds 300m.
Installing Cable Markers
The installation of cable markers above and below grade is required by Saudi Aramco. The
proper marking, identification, and placement of cable markers can prevent inadvertent
damage to the telecommunication cables.
Marking and Identification
Telecommunication buried cable runs are marked in accordance with the standard drawing
AB-036897. This drawing identifies two types of signs, as shown in Figure 14, a warning
sign (sign A) and a directional sign (sign B or C). The warning sign (480mm x 90mm)
identifies that an underground telephone cable run is present. The directional sign (90mm x
90mm) is an arrow that identifies the direction of the cable run. The lettering and arrows on
these signs are solid black in color on an orange background.
-
7/25/2019 Construction Requirements for Communication Installations
32/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 29
Sign Types
Figure 14
-
7/25/2019 Construction Requirements for Communication Installations
33/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 30
The sign post, which is shown in Figure 15, is 100mm x 100mm x 1.21m in size and is
constructed from redwood. The sign post is painted white in residential areas and orange in
field locations. The sign post is placed 450mm below the finished grade. The length of the
sign post that is above the finished grade is 760mm. The warning sign and directional sign
are mounted to the sign post.
Sign Post
Figure 15
-
7/25/2019 Construction Requirements for Communication Installations
34/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 31
Underground cable runs and turns are marked as shown in Figure 16. A straight run as shown
in Figure 16 of underground cable is marked through the use of a sign post with a warning
sign (sign A) and a directional sign (sign B). Sign posts are placed in sufficient number, on
long straight runs of buried cable, to clearly indicate the route and to warn the public and
workmen of the cable. Sign post spacings are not to exceed 100 meters. The warning signs
and directional signs are attached to the sign posts and oriented so that the arrows point in
each direction along the cable run. A right angle turn, as shown in Figure 16, of underground
cable is marked through the use of a sign post with a warning sing (sign A) and two
directional signs (sign C). The sign post is placed at the intersection of the cable runs. The
two directional signs are oriented so that the arrows point each direction along the cable run.
An oblique turn of underground cable is marked similarly to a right angle turn through the use
of a marker post with a warning sign (sign A) and two directional signs (sign C). The major
difference in the way that an oblique turn is marked involves the marker post bevel details
that are required.
-
7/25/2019 Construction Requirements for Communication Installations
35/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 32
Cable Runs and Turns
Figure 16
-
7/25/2019 Construction Requirements for Communication Installations
36/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 33
Marker post bevel details (end view and front view) are shown in Figure 17. The top of the
marker post is trimmed at the necessary angle to align the directional sign (sign C) arrow with
the cable.
Bevel Details
Figure 17
-
7/25/2019 Construction Requirements for Communication Installations
37/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 34
Placement in Trenches
Buried cable marker tape (18-079-890) is required to be placed in trenches at approximately
50 percent of the cable depth. The marker tape must not be placed closer than 300mm to the
cable.
Separation
The separation requirements for telecommunication conductors can be referenced in the
following Saudi Aramco Engineering Standards:
SAES-T-629 - Buried Cable and Wire
SAES-T-911 - Telecommunication Conduit System Design
SAES-T-928 - Buried Plant
Telecommunication cables can be placed in trenches by means of one of two methods. These
two methods are the random separation method and the fixed separation method. At Saudi
Aramco, telecommunication cables and power cables are not permitted to be direct buried
together in the same trench by the random separation method. The random separation method
that is shown in Figure 18 places the communication facilities (telephone) and other utilities
(CATV, secondary supply, gas, and primary supply) in the trench without any specific
separation distances. The minimum cover is 18 inches.
-
7/25/2019 Construction Requirements for Communication Installations
38/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 35
Random Separation
Figure 18
-
7/25/2019 Construction Requirements for Communication Installations
39/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 36
The fixed separation method as shown in Figure 19 requires that specific distances be
maintained between communication facilities (telephone cable) and other utilities (power
cable). The bottom of the trench is covered with 50mm of sand. The preferred distance
between the power cable and telephone cable is 1m or more in a joint trench. The distance
must not be less than 300mm of well tamped earth. The cables must be located a minimum of
50mm from the trench wall. The minimum cover that is required for the cables is 600mm.
Fixed Separation (Joint Trench Only)
Figure 19
-
7/25/2019 Construction Requirements for Communication Installations
40/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 37
The separation of telephone cables and power cables at crossovers can be accomplished
through the use of earth separation or concrete separation. Earth separation as shown in
Figure 20 requires a minimum vertical separation of at least 300mm of well tamped earth
between the power cable in the power trench and the telephone cable in the telephone trench.
If the power cable voltage exceeds 15kV phase-to-phase (8.7 kV phase-to-ground), the
telephone cable must be placed inside conduit at the crossover.
Crossover (Earth Separation)
Figure 20
-
7/25/2019 Construction Requirements for Communication Installations
41/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 38
Concrete separation as shown in Figure 21 requires a minimum vertical separation of at least
75mm of concrete between the power cable in the power trench and the telephone cable in the
telephone trench. The concrete slab must be a minimum of 100mm in width. The concrete
slab must also extend at least 300mm from the nearest point of the telephone cable to the edge
of the concrete.
Crossover (Concrete Separation)Figure 21
-
7/25/2019 Construction Requirements for Communication Installations
42/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 39
SPLICING CABLE: METHODS, MATERIALS, AND NUMBERING CODES
This section deals with the joining of multipair communication cable (and associated work) in
unclassified areas. The American Petroleum Institute (API) practices RP-500, A, B, and C
and the National Electrical Code (NEC) should be referenced for installations that are within
electrically classified (hazardous) areas, as defined by SAES-B-068. This section will cover
the following information:
Cable Numbering and Count Identification
Methods
Materials
Cable Numbering and Count Identification
Splicing operations are necessary to join cable conductors together. It is rare when an
individual cable will reach between the two desired locations. Splicing is the joining of two
or more cables together by splicing the conductors pair-for-pair and then covering the opening
with a water-tight case. In order to maintain correct polarity for the circuit when individual
cable pairs are being spliced together, it is necessary to splice the tip conductor of one cable to
the tip conductor of the other cable and to splice the ring conductor of one cable to the ring
conductor of the other conductor. At Saudi Aramco, splicing is normally referred to as color-
to-color throughout the cable within the correct binder group.
Splicing operations are necessary to complete cable transfers. The transfer of a working line
from one cable pair to another cable pair requires a change of the cross connection at the main
frame or rearrangement at a cross-connect terminal. Sectional transfers of cable pairs from
one cable to another cable where the pair count of the old and the new cable remain the same
may be done on a pair-for-pair basis. Cable numbering and count identification minimize the
chance of error during a cable transfer. Cable pairs that are energized are identified by
numerical designations, and dead pairs are identified by alphabetical designations. Cable
designations, as shown in Figure 22, are located on construction drawings and include the
following parts:
Cable Type Designation
Cable Number Designation
Dear Pair Designation
-
7/25/2019 Construction Requirements for Communication Installations
43/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 40
The cable type designation identifies the cable type, construction, number of pairs, and wire
gauge. The cable number designation consists of a numerical designation and the applicable
pair count. The dead pair designation consists of an alphabetical designation and the
applicable pair count. The splicer, engineer, and OSP records will treat this alphabetical
designation the same as if the alphabetical designation were a cable number. The dead pairs
in a cable will be shown in the exact order that the dead pairs appear in the cable.
A cable number designation, cable count, is an identification that is used as a common
designation throughout the length of a transmission circuit in a multi-circuit cable facility. It
usually originates in the Central Office Main Distribution Frame (MDF).
Sheath count is another important designation. The sheath count of a cable is the physical
identification of individual pairs of conductors in a piece of multi-pair cable. Physical
location of the cable count in the sheath count can be made by counting through a standard
PIC coding scheme, which is used to identify individual pairs of conductors or groups of pairs(binder group).
Cable Designation
Figure 22
-
7/25/2019 Construction Requirements for Communication Installations
44/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 41
The splice through example in Figure 23 shows that the cable A 101-200 is spliced through
the intermediate splice. The non-splice through example that is also shown in Figure 23
shows that the cable A 101-200 is not spliced through the intermediate splice.
Cable Count (Splice Through)
Figure 23
-
7/25/2019 Construction Requirements for Communication Installations
45/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 42
Cable count changes or transfers are also shown on construction drawings. A cable transfer
fill box as shown in Figure 24 provides the following information:
Splice Sequence No. (number) or Work Location No.
Number of PR (pairs) Transferred
Number of PR (pairs) Working
The cable transfer fill box at work location 2 indicates that 100 pairs are transferred and 21
pairs are working. The transfer or count change of a cable can also be indicated through the
use of parentheses.
A count change through the use of parentheses is also shown in Figure 24. The U600-24P
cable runs between manhole (MH) #3139A and MH #3139. This cable contains cable 14,1501-1800+, and cable 9, 1501-1800, and it has no count change. The U600-24P cable is
spliced to U900-24P and U100-22P in MH #3139. The original count of U900-24P consisted
of the following cables:
14, 1501-1800+
A, 301-500+
3, 201-300+
9, 1701-1750+
A 651-900
The new count for U900-24P changed to the following cables:
14, 1501-1700+
A, 201-600+
9, 1701-1750+
A, 651-900
-
7/25/2019 Construction Requirements for Communication Installations
46/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 43
The count change resulted in the removal of cable 3, 201-300+, and the decrease of 100 pairs
to cable 14, 1501-1800+. In the case of U100-22P, the cable 3, 201-300, was changed with
cable 9, 1526-160+, and A 76-100.
The use of parentheses for cable count changes should not be confused with the use of
parentheses to indicate the removal of cable. A cable removal example is also shown in
Figure 24. The cable UF 300-24P that is located in MH #3139 is indicated to be removed.
Cable Count Change (Transfer)
Figure 24
-
7/25/2019 Construction Requirements for Communication Installations
47/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 44
Methods
All Saudi Aramco cables are even count color coded plastic insulation cables (PIC). Standard
binder group to binder group, color to color splicing is the only type of splicing that is used by
Saudi Aramco.
This section covers the following methods for copper cable splicing:
Straight Splices
Butt Splices
-
7/25/2019 Construction Requirements for Communication Installations
48/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 45
Straight Splices
Telecommunication cable of the same size can be joined through the use of a straight splice.
A straight splice joins like-color binder groups only, and the cable pairs are joined color to
color. All binder groups are marked at both ends of the straight splice. The straight splice asshown in Figure 25 joins, by means of a connector, the matching cable pair conductors (ring
to ring and tip to tip) from one cable to another cable to form a complete circuit. The cable
pair conductor must be seated firmly against the stop to ensure a satisfactory electrical
connection.
Straight Splice
Figure 25
-
7/25/2019 Construction Requirements for Communication Installations
49/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 46
Butt Splices
Bridge and tap connections can be accomplished through the use of butt splices. The bridge
connection joins three or more cable pair conductors (ring-to-ring or tip-to-tip) to form a
parallel circuit. The bridge connection, or half tap connection, as shown in Figure 26 joins
three cable pair conductors through the use of a connector. The cable pair conductors must be
set firmly against the stop to ensure a satisfactory electrical connection. The connectors are
bundled in place with a cable tie in a completed connection.
Half Tap Connection
Figure 26
-
7/25/2019 Construction Requirements for Communication Installations
50/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 47
The tap connection joins an additional cable pair conductor to a circuit to form a branch
circuit. The tap connection as shown in Figure 27 joins the cable pair conductor of a through
circuit to the cable pair conductor of a branch circuit through the use of a connector. The
cable pair conductors complete the electrical circuit through a contact that is inside the
connector.
Tap Connection
Figure 27
-
7/25/2019 Construction Requirements for Communication Installations
51/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 48
Materials
This section will cover the following splice devices and materials that can be specified for a
particular job:
Splice Closures
Connectors/Bonding Clips
Splice Closures
The purpose of splice closures is to protect joined (spliced) cable pairs. Splice closures can
be applied in manhole and buried cable installations.
The following splice closures are available for use in manhole installations:
Preformed SS splice closure
REDDI seal
The following splice closures are available for use in buried cable installations:
REDDI seals
Better buried splice closure
Connectors/Bonding Clips
The following list of splicing materials/connectors as shown in Figure 28, are the most widely
used for splicing polyethylene conductors:
UR 18-021-952 (3M Scotchlok)
UG 18-021-953 (3M Scotchlok)
PICA Bond 18-022-018 (Amphenol)
The UR and UG connectors consist of a transparent thermoplastic base with a red or green
plastic button in an orifice at the top of the base. Metal inserts are molded into the plastic
button. These inserts have sawtooth edges that puncture the cable insulation and make
electrical contact with the conductors when the button is fully compressed. The UR
connectors are filled with silicone grease. This grease serves as a moisture barrier for the
connection. The UR connector can be used to insulate, butt splice, and seal any two or three
-
7/25/2019 Construction Requirements for Communication Installations
52/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 49
19, 22, 24, or 26 gauge cable conductors. The UR connector can be used with 19 gauge filled
conductor. The UG connector can be used for tap splices.
The Picabond or AMP connector is smaller than the Scotchlok connectors. The use of a
Picabond connector results in a much smaller splice bundle. This smaller splice bundle is
very desirable in high pair count cables. The Picabond connector is available with sealant for
through and bridge connections in a butt splice configuration. Each Picabond connector as
shown in Figure 28 consists of a preassembled two-piece housing (contact retainer housing
and wire entry housing) and an insulation displacement contact. This contact will accept solid
copper conductors in any combination of 19 through 26 AWG in the conductor holes This
conductor is crimped with a standard crimping tool.
-
7/25/2019 Construction Requirements for Communication Installations
53/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 50
Connectors
Figure 28
Bonding clips are provided to permit reliable electrical connections to the aluminum shield for
noise-shielding purposes and for maintenance of electrical continuity. The use of bonding
clips is specified by a particular splice closure. Scotchlok brand 4460-S shield connectors
(18-021-980) are available for use by Saudi Aramco to bond cable to other ground systems.
Scotchlok brand 4460-S shield connectors require standard hand tools to form a bullet bond.
-
7/25/2019 Construction Requirements for Communication Installations
54/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 51
BURIED CABLE: SPLICING, BONDING, AND SEPARATION REQUIREMENTS
All cables for direct burial must be thoroughly inspected before, during, and after installation
(before back filling trench) to determine that the cable is placed without damage to sheath,
shield, or conductors. These inspections are necessary because location and repair are much
more difficult after installation.
With respect to buried cable, this section will cover requirements for the following:
Splicing
Bonding and Grounding
Separation
Splicing
This section describes splicing design considerations for the following applications:
Direct Buried
In Pedestal
Direct Buried
All direct buried cable splices must be filled with a reenterable encapsulating compound onair core as well as filled cables. The splice closure that is used must be a type that is
manufactured and designed to hold the encapsulating compound. The pressure wrap kit, or a
similar product that utilizes a perforated web liner, must be used in all encapsulated
reenterable splice closures. Saudi Aramco communications personnel do not normally
directly bury splices. The splices are placed inside pedestals such as the GHC-8.
Saudi Aramco has approved for use the following types of splice closures:
REDDI Seal Cable Closure (Preformed Line Products)
Better Buried Closure (3M)
The REDDI seal cable closure that is manufactured by Preformed Line Products is the most
widely used splice closure in Saudi Aramco for buried cable splices. This splice closure is
designed to be filled with a reenterable encapsulating compound. This compound protects the
splice bundle from the surrounding environment. The REDDI Seal Cable Closures are
available in three different diameters, 4 in (10.16 cm), 6 1/2 in (16.51 cm) and 9 1/2 in (24.13
cm).
-
7/25/2019 Construction Requirements for Communication Installations
55/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 52
The 3M Companys RJ Series Better Buried Closure System (material that is available from a
local vendor) provides acceptable closures for this purpose. This closure comes in different
series and sizes that will accommodate cables with outside diameters that range from 25mm to
101mm. A support assembly will be used with 125mm and larger diameter-filled closures
that are installed in manholes.
The 3M Better Buried Closure Body Sleeve Halves and End Caps are designed and made of
material that withstands acids, detergents, chemicals, and other harmful elements to ensure
direct buried splice integrity. The Better Buried Closures are available as complete closure
kits, component kits or as individual parts to meet specific application requirements for direct
buried straight and butt splices, cable repair, and other direct buried applications such as tap
splicing and sheath repairs.
In Pedestal
Conductor splices and terminations are to be made in accordance with the appropriate sectionof SAES-T-632. Upon completion of the splice, the two conductor groups should be
physically and electrically isolated from each other and the pedestal.
Bonding and Grounding
The shield of all cables will be bonded together electrically with the use of bonding clips.
Bonding clips should be applied as required to obtain shield continuity of the cables.
A ground wire clamp is attached to each bonding clip, as shown in Figure 29. The ground
wires are bonded through use of a ground wire connector. An additional ground wire is used
to bond the entire assembly to a ground rod. The resistance of the ground rod must be lessthan 25 ohms. Below ground connections between the ground rod and ground wire is
achieved through the use of a cadweld bond.
-
7/25/2019 Construction Requirements for Communication Installations
56/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 53
Bonding and Grounding
Figure 29
-
7/25/2019 Construction Requirements for Communication Installations
57/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 54
Separation
The separation of buried cables is required for identification, protection from arcing, and the
reduction of stray currents that result from the cathodic protection on pipelines. Detailed
drawings that show separation distances are shown in the civil work for structures in this
Module. These drawings can also be referenced in standard drawing AA-036748. The
minimum separation chart that is shown in Figure 30 summarizes the minimum separation
distances between buried telephone cable and various utilities (buried power, water, gas,
sewer lines, buried CATV, instrumentation cables, and oil field pipelines).
Minimum Separation Chart
Figure 30
-
7/25/2019 Construction Requirements for Communication Installations
58/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 55
TECHNIQUES AND DESIGN CONSIDERATIONS FOR PULLING, RACKING,
SPLICING, AND BONDING AND GROUNDING OF UNDERGROUND CABLE
In regard to underground cables this section will cover techniques and design considerations
for the following:
Pulling
Racking
Safety
Splice Closures
Bonding and Grounding
Pulling
Cable pulling is the operation that places underground copper cables in conduits that are
between manholes. Cable pulling operations can also remove telecommunication cables from
conduits that are between manholes.
-
7/25/2019 Construction Requirements for Communication Installations
59/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 56
Standards
The following is a list of the Saudi Aramco Engineering Standards that apply to cable pulling:
SAES-T-628 Underground Cable
This standard describes the mandatory requirements that govern the design
and installation of telecommunications underground cables. The scope of
this standard includes the following topics:
- Installation of Rodding Ducts and the Placement of Pull Line (Rope)
Underground Cable
- The Installation and Removal of Underground Cable and Rubber
Conduit Plugs
- The Description and Use of Cable Underground Conduit Sealing Kit
PR-851
- Installation Precautions for Underground Cable
- Procedures for Open Flames in Manholes
- The Testing and Ventilating Procedures for Underground Manholes
and Cable Vaults
- The Placement of Underground Cable in Main Conduit
- The Installation of Cable Guards at Riser Poles and Buildings
- The Placement of Underground Cable in Subsidiary Conduit
- Splicing Arrangements in Manholes
- The Placement of Underground Cable Loading Coil Cases
- The Removal of Underground Cable
- The Placement and Splicing of Bonded ASP Cable
-
7/25/2019 Construction Requirements for Communication Installations
60/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 57
SAES-T-911 Telecommunication Conduit System Design
This standard describes the mandatory requirements that govern the design and installation of
telecommunications conduit and manhole systems. The scope of this standard includes the
following topics:
- General Considerations for Conduit
- Manhole Design
- Underground Conduit Materials
- Inspection, Information for Concrete, Mortar, and Reinforced
Concrete
- Conduit Design and Layout
- Conduit Design of Formations
- Engineering Considerations for Long Pulls of Underground Cable
- Underground Entrances to Central Office Buildings
- Conduit Duct Selection and Cable Measurement
-
7/25/2019 Construction Requirements for Communication Installations
61/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 58
Procedures
Underground cable pulls must be based on joint engineering and construction evaluations.
These evaluations consider theoretical, practical, and job experience factors. Cable pull
calculations must be included in the design package. Cable pulling procedures must take thefollowing factors into consideration:
Tension Limitations
Total Pull Length
Cable Reel Setup Location
Cable Pull Direction
Cable Pull Locations
There is a limit to the amount of tension that can be used to pull cables into a length of
conduit. Pulling tension is determined by the weight of the cable, the coefficient of friction of
the conduit, and the geometry of the duct run. Cable tension calculation can be done through
use of the tension formula in SAES-T-911, section 4.7.5, page 52 or through use of the CSD
computer program.
In newer duct installations, the manhole intervals can be as high as 1000 feet because cables
are now manufactured in longer lengths. Also the lighter weight, composite sheaths make the
pulling of the longer lengths much easier.
The duct should be checked for obstructions such as misaligned conduit or collections of silt.
This check is made by rodding. The rods are short enough to fit into a manhole and are
threaded on both ends. One section of the rod is pushed into the duct and another section is
screwed on. This operation is continued until the advance rod enters the next manhole.
Usually, a pulling line is attached to the end, and the rods are removed section by section.
The duct then is cleaned. Mandrel tests are required as directed by SAES-T-628, 4.1.3.
A reel of cable is positioned at one manhole in order to pull the cable into a duct. The reel of
cable must be able to rotate. A winch is located in the next manhole. The winch line is pulled
through the duct with the attached cable.
Prior to a cable pull operation, all equipment should be checked to make sure the equipment is
properly positioned. Prior to the start of the operation, the type and use of signals should also
be discussed and thoroughly understood by the personnel who are involved in the operation.
-
7/25/2019 Construction Requirements for Communication Installations
62/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 59
The first 20 feet of the cable should be generously lubricated to reduce initial duct friction.
The amount of the lubricant that is required during the remainder of the pull should be
determined by the conditions that are encountered. Conditions such as bends, long pulls, or
pulls through manholes may require more lubricant. Only lubricants specifically approved by
Saudi Aramco may be used.
The cable as shown in Figure 31 must be pulled slowly until at lest two feet of cable has
entered the duct. This length (two feet) may be determined by the measurement of the
distance from the top of the cable feeder to the duct entrance, plus two feet. An equal
distance should then be measured from the end of the cable and marked with vinyl tape. The
cable is pulled slowly until the tape marking reaches the funnel of the cable feeder. The
required two feet of cable are in the duct when the tape marking reaches the funnel. From this
point, the cable may be pulled, steadily and continuously, at a rate of 80 to 100 feet per
minute.
The cable pulling speed should be reduced when the cable has been pulled to within 20 feet of
the manhole. This distance (20 feet) is determined by the quantity of cable that remains on
the reel. The cable should be pulled at the reduced speed until the swivel link is 6 inches from
the sheave that is located in the manhole.
The tension on the winchline should be maintained if the cable pull is stopped because of reel
trouble or other reasons unless the operator is asked to release the line tension. The pulling
speed should be increased gradually until the cable moves freely when the cable pull is
resumed.
An approved luffing grip as shown in Figure 31 should be used to pull the additional specifiedquantity of cable into the manhole. A luffing grip differs from ordinary cable grips in that the
luffing grip is equipped with an offset eye that permits the grip to be placed on the cable at
locations other than the end. Split cable grips, nylon slings, and frayed rope slings may be
used as luffing grips.
-
7/25/2019 Construction Requirements for Communication Installations
63/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 60
Cable Pulling
Figure 31
-
7/25/2019 Construction Requirements for Communication Installations
64/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 61
Racking
Cable racking design for copper cables must consider the following factors:
To minimize the changes in cable level.
To determine that the racking of a given cable in the proposed manner will not
block or restrict the use of any vacant duct or racking position.
To make the radius of a cable bend as large as possible (the radius of the bend
must be a minimum of 10 times the diameter of the cable).
Standards
The following is a list of the Saudi Aramco Engineering Standards that apply to cable racking:
SAES-T-628 - Underground Cable
SAES-T-911 - Telecommunication Conduit System Design
Procedures
The following racking space requirements as shown in Figure 32 must be maintained for
copper cable in manholes:
For racking stub and lateral cables, a minimum space of 385mm (15 in) must
be maintained in all manholes between the roof of the manhole and the center
of the top main cable.
A minimum space of 385mm (15 in) must be maintained between the manhole
floor and the center of the bottom main cable.
A minimum vertical space of 195mm (7.5 in) for staggered splices and 230mm
(9 in) for non-staggered splices.
-
7/25/2019 Construction Requirements for Communication Installations
65/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 62
Racking Space
Figure 32
-
7/25/2019 Construction Requirements for Communication Installations
66/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 63
The cable racking requirements for a total of six to twelve main ducts that enter on each end
wall must provide for double bay, single cable racking on each side wall.
The cable racking requirements for a total of fourteen to twenty four main ducts entering on
each end wall must provide for double bay, double cable racking on each side wall.
The Saudi Aramco procedures for duct assignments is that cables be assigned to bottom ducts
first, for the following reasons:
Cable splicers will not have to work underneath cables that are placed at higher
levels.
In the event that damage is done to the conduit system, the empty top ducts
would probably be damaged first. The lower ducts would remain protected.
Ducts should be selected to avoid the following situations:
Cable crossovers between the duct entrance and the cable rack.
Blockage of future access to vacant ducts.
Racking arrangement and order of duct selection for a line manhole are shown in Figure 33.
The duct numbers indicate the order of assignment selection. Single cable racking is shown
on the 2-wide duct configurations. Double cable racking is shown on the 4-wide duct
configurations.
-
7/25/2019 Construction Requirements for Communication Installations
67/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 64
Single and Double Cable Racking
Figure 33
The numerical order of duct selection that is shown in Figure 33 should not be confused with
the numerical designation of ducts. Ducts are designated by numbers in accordance with
-
7/25/2019 Construction Requirements for Communication Installations
68/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 65
SAES-T-911, section 4.9.24. Duct numbers are designated left to right, bottom to top, and
start with the bottom left side duct. (This view faces away from the central office).
-
7/25/2019 Construction Requirements for Communication Installations
69/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 66
Hardware Requirements
All manhole hardware must be of the non-corrosive type such as hot dipped galvanized or
better. The requirements for the racking of copper cable can vary with the type of manhole.
The basic telecommunications manhole can have a maximum of 24 main ducts in eachendwall.
Cables and completed splices that are located in manholes should be supported with cable
hooks. Cable hooks are available in several sizes (4 in, 7 1/2 in, 10 in, and 14 in). The cable
hook as shown in Figure 34 has a tab that can be inserted into the cable rack upright. Cable
rack hook positions in all manholes are numbered from the top down to the bottom of the
uprights. The slots in the cable hook permit the cable to be secured to the cable hook through
the use of a lashed cable support.
The hardware requirement for situations where the distance between the cable racks is such
that the weight of splice closure results in cable sag, the splice closure should be secured to apiece of pipe or other support material. This support material is laid across the cable hooks.
The splice closure is secured tightly to the pipe with lashed cable supports.
-
7/25/2019 Construction Requirements for Communication Installations
70/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 67
Cable Hooks
Figure 34
-
7/25/2019 Construction Requirements for Communication Installations
71/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 68
Safety
Cable pulling and racking operations require manhole entry and specific safety precautions as
a result of the following contaminants that can be present in manholes:
Vapors or gases that have escaped from underground storage or from the
piping of liquids or gases such as gasoline, natural gas, liquified petroleum gas,
propane, and butane.
Gases from fermentation of naturally occurring organic matter such as
methane, carbon dioxide, and hydrogen sulfide.
Gases such as carbon dioxide or carbon monoxide that are created as by-
product of combustion (from vehicles or equipment).
Manhole pre-entry combustible gas tests are made to ensure that there is no risk of explosionwhile, or immediately after, the removal of the manhole cover. Continuous forced ventilation
ensures an adequate oxygen supply and prevents possible build-up of combustible/toxic gases
or vapors. Periodic combustible gas tests provide an additional margin of safety that ensures
that no combustible gas is building up in the manhole. The Work Permit Systems in G.I.
2.100 and Gas Testing Procedures in G.I. 2.708 must be referenced when atmospheres that
exceed 60 percent of the Lower Explosive Limit (LEL) are detected in the manhole.
Splicing
The design requirements for the placement of splice closures vary with the number of ducts
and the length of the manhole. Splice closures can be placed in non-staggered and staggeredarrangements. Staggered splices are employed in those manholes where there are a large
number of entering ducts and where the length of the manhole is sufficient to place three
cable racks.
-
7/25/2019 Construction Requirements for Communication Installations
72/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 69
The design requirements for the splicing of underground cable require the use of the
following splice closures:
Preformed stainless steel splice closures
REDDI seal cable closure
The preformed stainless steel (SS) splice closure is designed to hold air pressure. An
encapsulating compound is not placed in SS splice closures. The SS splice closures are
preferred for manhole splices. The SS splice closures should be installed between the
manhole racks. The SS splice closures are designed for numerous re-entries.
The Reddi Seal Cable Closure is manufactured by Preformed Line Products (PLP) for use on
filled cable in underground and buried plant splices. This closure must be filled with a
reenterable encapsulating compound whether the closure is used on filled or air core typecables or whether the spliced cables are buried or underground. This closure will not hold air
pressure, and Reddi Seal end plates are not interchangeable with the pressurized preformed
splice case.
These closures are available in many sizes, as shown in Figure 35. The table shows
maximum end plate cable capacity for several cables (1, 2, 3, and 4 cables) and each of the
splice closures.
-
7/25/2019 Construction Requirements for Communication Installations
73/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 70
Splice Closure Data
Figure 35
-
7/25/2019 Construction Requirements for Communication Installations
74/75
Engineering Encyclopedia Communications
Construction Consideration
Saudi Aramco DeskTop Standards 71
Bonding and Grounding
In underground cables, as shown in Figure 36, shield and armors, if present, should be bonded
together in each manhole and/or pedestal. The metallic shields, including any armor of all
cables through splices, splice cases, terminals, apparatus, cabinets, etc., must be continuous
throughout the length of the cable, except where the cable is purposely broken by an
insulating joint. All bonds are to be connected to a common ground to ensure that all cables
are at the same potential after all the metallic shield and armor of the cables are made
continuous with a bonding wire.
Underground Bonding and Grounding
Figure 36
-
7/25/2019 Construction Requirements for Communication Installations
75/75
Engineering Encyclopedia Communications
Construction Consideration
GLOSSARY
Bonding A low-impedance path that is obtained by permanently jointing all
noncurrent-carrying metal parts to ensure electrical continuity and
that has the capacity to safely conduct any current that is likely to be
imposed on it.
Bundle Several individual fibers that are contained within a single jacket or
buffer tube. Also, a group of buffered fibers that are distinguished
in some fashion from another group in the same cable core.
Buried cable A cable that is installed under the surface of the ground in such a
manner that it cannot be removed without disturbance to the soil.
Also referred to as direct-buried cable.
Cable An assembly of one or more conductors or optical fibers that are
placed within an enveloping sheath and that are constructed to
permit use of the conductors singly or in groups (FED-STD-1037A).
Cable Rack The vertical or horizontal open support (usually made of hot dipped
galvanized steel) that is attached to a ceiling or wall.
Conduit A rigid or flexible metallic or nonmetallic raceway of circular cross
section through which cables can be pulled or in which cables can
be housed.
Pull Cord/Pull Wire Cord or wire that is placed within a raceway and that is used to pull
wire and cable through the raceway.
Splice Closure A container that is used to protect joined (spliced) cable pairs.
Trench A narrow furrow dug into the earth for the direct installation of
buried cable or for the installation of underground cable within
troughs or ducts.
Underground Cable A telecommunications cable installed under the surface of the earth