Page 1: CONTENT - Richardson Projects...The values below are given for normal operating condition as defined in IEC 60298, IEC 60694 10D 12kV METALCLAD SWITCHGEAR 2 Other values are available
Page 2: CONTENT - Richardson Projects...The values below are given for normal operating condition as defined in IEC 60298, IEC 60694 10D 12kV METALCLAD SWITCHGEAR 2 Other values are available

CONTENT

EPE METALCLAD SWITCHGEARS SERIESEPE 12A20 / 25 - 12KV METALCLAD SWITCHGEAR

EPE 10D - 12KV METALCLAD SWITCHGEAREPE 24A25 - 24KV METALCLAD SWITCHGEAREPE 36A25 - 36KV METALCLAD SWITCHGEAR

EPE METALCLAD SWITCHGEARS AMS SERIES12kV AMS METALCLAD SWITCHGEAR24kV AMS METALCLAD SWITCHGEAR

40.5KV AMS METALCLAD SWITCHGEAR

36KV COMPACT GAS SWITCHGEARHICLAD 30GA 36KV COMPACT GAS SWITCHGEAR

FEP SF6 GAS CIRCUIT BREAKER40.5KV FEP SF6 GAS CIRCUIT BREAKER

RING MAIN UNITOIL RING MAIN UNITSF6 RING MAIN UNIT

1234

567

8

9

1011

Page 3: CONTENT - Richardson Projects...The values below are given for normal operating condition as defined in IEC 60298, IEC 60694 10D 12kV METALCLAD SWITCHGEAR 2 Other values are available

Indoor air insulated metalclad switchgear.

Vacuum circuit breaker is mounted on truck for horizontal withdrawal and isolation.

Integral fault making earthing switch, class A on the circuit side. Busbar earthing truck is optional.

GENERAL DESCRIPTION

Other values are available on request.

Other values are available on request.

12A20 / 2512kV METALCLAD SWITCHGEAR

Rated voltageRated currentRated frequencyRated insulation level-Power frequency withstand voltage-Lightning impulse withstand voltage

Rated short circuit breaking currentRated short circuit withstand currentRated short circuit making current (peak)Mechanical enduranceRated operating sequence/duty

Rated closing timeRated opening timeRated breaking time

Standard trip/close supply (1)Standard motor charging supply (2)

kVAHz

kV/ 1 minkV, 1.2/50 μs

kA, rmskA/3skA10,000

0-0.3s-CO-3min-CO

msmsms

VdcVdc (Vac)

12630/1250/2000

50

28/3275/85

50/6320/2550/63

<60<50<60

30/11030/110(240 Vac)

Circuit Breaker Model VFT-12

Rated voltageRated frequencyRated insulation level-Power frequency withstand voltage/min-Lightning impulse withstand voltage (peak)

Rated normal current of BusbarRated short time withstand currentRated peak withstand currentStandard degree of protection (1) Enclosure Compartment

Dimension Width Depth Height

kVHz

kVkV, 1.2/50 μs

AkA/3skA

mmmmmm

1250

28/3275/85

800/1250/20002050

4X3X

600, 800, (2000A) 2200,2250 (with PT)

2300

1250

28/3275/85

2563

Switchgear Model 12A20 12A25

The values below are given for normal operating condition as defined in IEC 60298, IEC 60694, IEC 62271-100 / 200

Mechanical intelocks are provided to safeguards against maloperation.

Design type tested to IEC 62271-100/200, IEC 60298, IEC 60056, IEC 60694

1

Page 4: CONTENT - Richardson Projects...The values below are given for normal operating condition as defined in IEC 60298, IEC 60694 10D 12kV METALCLAD SWITCHGEAR 2 Other values are available

The cubicle is an earthed, metallic enclosure which is fully metalclad as defined in IEC 60298. The cubicle is divided into the following compartments which are seperated by metallic partitions: Busbars Circuit breaker Cables, earthing switch and instrument transformers

Low voltage auxiliary equipment when required

Each medium voltage compartment is provided with a pressure relief flap.

The standard degree of protection for the enclosure is IP4X and for the partitions is IP3X. Other values are available on request.

CUBICLE

Other values are available on request.

Other values are available on request.

Circuit Breaker Model VFT-12D

Switchgear Model EPE 10D

The values below are given for normal operating condition as defined in IEC 60298, IEC 60694

10D12kV METALCLAD SWITCHGEAR

2

Other values are available on request.

Rated voltageRated frequencyRated insulation level-Power frequency withstand voltage/min-Lightning impulse withstand voltage (peak)

Rated normal current in BusbarShort time withstand currentPeak withstand currentStandard degree of protection (1) Enclosure Compartment

Dimension Width Depth Height

kVHz

kVkV, 1.2/50 μs

AkA/3skA

mmmmmm

1250

2850

800/1250/20002563

3X2X

700 1950 2400

Rated voltageRated currentRated frequencyRated insulation level-Power frequency withstand voltage-Lightning impulse withstand voltage

Rated short circuit breaking currentRated short circuit withstand currentRated short circuit making current (peak)Mechanical enduranceRated operating sequence/duty

Rated closing timeRated opening timeRated breaking time

Standard trip/close supply (1)Standard motor charging supply (2)

kVAHz

kV/ 1 minkV, 1.2/50 μs

kA, rmskA/3skA10,000 times

0-0.3s-CO-3min-CO

msmsms

VdcVdc (Vac)

12630/1250/2000

50

2875

252563

605060

30/11030/110(240 Vac)

Page 5: CONTENT - Richardson Projects...The values below are given for normal operating condition as defined in IEC 60298, IEC 60694 10D 12kV METALCLAD SWITCHGEAR 2 Other values are available

All control and indicating devices are located on the front of the circuit breaker unit. These include manual close/open knob, manual charging slot, position switch, operation counter, close/open indicator, spring charged and discharged indicator.

The circuit breaker is mounted on truck for horizontal withdrawal and isolation. Both the ‘service’ and ‘isolate/test’ positions are within the compartment.

Safety shutters are provided within the circuit breaker compartment. These automatic safety shutters cover the busbars and feeder spouts when the circuit breaker is at the ‘isolate/test’ position. They can be padlocked in the closed position if so desired and kept open for testing and maintenance purposes by means of manually operated catches, which in turn are self cancelling when the circuit breaker is returned to the unit.

24A2524kV METALCLAD SWITCHGEAR

Other values are available on request.

Other values are available on request.

Circuit Breaker Model VJ 22

Switchgear Model 24A25

The values below are given for normal operating condition as defined in IEC 60298, IEC 60694

Vacuum Circuit Breaker

2

Other values

IEC

3

Rated voltageRated frequencyRated insulation level-Power frequency withstand voltage/min-Lightning impulse withstand voltage (peak)

Rated normal current in BusbarShort time withstand currentPeak withstand currentStandard degree of protection (1) Enclosure Compartment

Dimension Width Depth Height

kVHz

kVkV, 1.2/50 μs

AkA/3skA

mmmmmm

2450

50125

1250/200025

62.5

1P3X1P2X

900, 1100 (2000A panel)3000, 3500 (with PT)

2350

Rated voltageRated currentRated frequencyRated insulation level-Power frequency withstand voltage-Lightning impulse withstand voltage

Rated short circuit breaking currentRated short circuit withstand currentRated short circuit making current (peak)Mechanical enduranceRated operating sequence/duty

Rated closing timeRated opening timeRated breaking time

Standard trip/close supply (1)Standard motor charging supply (2)

kVAHz

kV/ 1 minkV, 1.2/50 μs

kA, rmskA/3skA10,000 times

0-0.3s-CO-3min-CO

msmsms

VdcVdc (Vac)

24630/1250/2000

50

50125

2525

62.5

505070

110110

Page 6: CONTENT - Richardson Projects...The values below are given for normal operating condition as defined in IEC 60298, IEC 60694 10D 12kV METALCLAD SWITCHGEAR 2 Other values are available

VCB cannot be engaged or withdrawn unless it is open.

VCB can only be closed or opened if it is fully engaged or isolated. (not in-between)

VCB cannot be engaged if the control plug is removed.

VCB cannot be engaged when the earthing switch is closed and vice-versa.

Key interlocks are provided if required (optional).

Safety Interlocks

Other values are available on request.

Other values are available on request.

Circuit Breaker Model VJ 32 VJ 32D

Switchgear Model 36A25 36A25

The values below are given for normal operating condition as defined in IEC 60298, IEC 60694

Single Bus Double Bus

36A2536kV METALCLAD SWITCHGEAR

4

Rated voltageRated frequencyRated insulation level-Power frequency withstand voltage/min-Lightning impulse withstand voltage (peak)

Rated normal current in BusbarShort time withstand currentPeak withstand currentStandard degree of protection (1) Enclosure Compartment

Dimension Width Depth Height

kVHz

kVkV, 1.2/50 μs

AkA/3skA

mmmmmm

3650

70170

1250/200025

62.5

1P3X1P2X

1100 11003650 36502150 2350

Rated voltageRated currentRated frequencyRated insulation level-Power frequency withstand voltage-Lightning impulse withstand voltage

Rated short circuit breaking currentRated short circuit withstand currentRated short circuit making current (peak)Mechanical enduranceRated operating sequence/duty

Rated closing timeRated opening timeRated breaking time

Standard trip/close supply (1)Standard motor charging supply (2)

kVAHz

kV/ 1 minkV, 1.2/50 μs

kA, rmskA/3skA10,000 times

0-0.3s-CO-3min-CO

msmsms

VdcVdc

36800/1250/2000

50

70170

2525

62.5

605070

30/11030/110(240 Vac)

Page 7: CONTENT - Richardson Projects...The values below are given for normal operating condition as defined in IEC 60298, IEC 60694 10D 12kV METALCLAD SWITCHGEAR 2 Other values are available

* Forced cooling ventilation is required ** DC Resistance of current transformer

������������������ ������� ����

Description

5

Rated voltageRated FrequencyRated insulation level-Power frequency withstand voltage/min-Lightning impulse withstand voltage (peak)

Rated normal current in BusbarShort time withstand currentPeak withstand currentS tandard degree of protection (1) Enclosure Compartment

DimensionW idth

Depth Height

kVHz

kVkV

AAkA

mmmmmm

7.2/12/15/17.550/60

4275/95

630/1250/1600/2000/2500/3150/4000630/1250/1600/2000/2500/3150/4000

50/63/80/125/130

4X2X

650 (800,1000)22501400

�������������������� ���������������

Circuit Breaker Model Rated voltageRated currentRated frequencyRated insulation level-Power frequency withstand voltage-Lightning impulse withstand voltage

Rated short circuit breaking currentRated short circuit withstand currentRated short circuit making current (peak)Electrical endurance

Rat ed operating sequence/duty

Rated closing timeRated opening timeRated breaking time

Rated auxiliary control voltage

kVAHz

kV/ 1 minkV, peak

kA, rmskA/4skA

274 (Class E2 in accordance with

O-0.3s-CO-180s-CO(up to 40kA)

msmsms

7.2/12/15/17.5630/1250/1600/2500/3150/400050/60

4275/95

20/25/31.5/40/5020/25/31.5/40/5050/63/80/125/130

35-7525-3540-50

IEC 62271-100 and GB 1984-2003)

O-0.3s-CO-180s-CO(50kA)

V AC110/220;DC 110/220

IEC 62271-100/200

Page 8: CONTENT - Richardson Projects...The values below are given for normal operating condition as defined in IEC 60298, IEC 60694 10D 12kV METALCLAD SWITCHGEAR 2 Other values are available

* DC Resistance of current transformer

��!����������������� ������� �����

6

DescriptionRated voltageRated frequencyRated insulation level-Power frequency withstand voltage/min-Lightning impulse withstand voltage (peak)

Rated normal current in BusbarShort time withstand current (4s)Peak withstand currentStandard degree of protection (1) Enclosure Compartment

DimensionWidth

Depth Height

kVHz

kVkV

AAkA

mmmmmm

2450/60

50/65125

630/1250/1600/2000/250020/25/31.550/63/80

1P4X1P2X

800 (1000)16802250

��!����������������� ���������������

Circuit Breaker Model Rated voltageRated currentRated frequencyRated insulation level-Power frequency withstand voltage-Lightning impulse withstand voltage

Rated short circuit breaking currentRated short circuit withstand currentRated short circuit making current (peak)Electrical endurance

Rated operating sequence/duty

Rated closing timeRated opening timeRated breaking time

Rated auxiliary control voltage

kVAHz

kV/ 1 minkV, peak

kA, rmskA/4skA

274 (Class E2 in accordance with

O-0.3s-CO-180s-CO

msmsms

24630/1250/1600/2000/250050

50/65125

20/25/31.520/25/31.550/63/80

505070

DescripRated voRated freRated ins-Power fr-Lightnin

Rated noShort timPeak witStandardSS Enclos Compa

DimensioWidth

Depth Height

IEC 62271-100 and GB 1984-2003)

O-0.3s-CO-180s-CO

V AC110/220;DC 110/220

IEC 62271-100/200

Page 9: CONTENT - Richardson Projects...The values below are given for normal operating condition as defined in IEC 60298, IEC 60694 10D 12kV METALCLAD SWITCHGEAR 2 Other values are available

* Forced cooling ventilation is required ** DC Resistance of current transformer

!"#$��������������� ������� ����

7

DescriptionRated voltageRated frequencyRated insulation level-Power frequency withstand voltage/min-Lightning impulse withstand voltage (peak)

Rated normal current in BusbarShor t time withstand current (4s)Peak withstand currentStandard degree of protection (1) Enclosure Compartment

Dimension Width Depth Height

kVHz

kVkV

AAkA

mmmmmm

33/36/40.550/60

95185

630/1250/1600/2000/2500/315025/31.563/80

1P4X1P2X

120025002400

�!"#$�����

Circuit Breaker Model

Rated voltageRated currentRated frequencyRated insulation level-Power frequency withstand voltage-Lightning impulse withstand voltage

Rated short circuit break ing currentRated shor t circuit withstand currentRated short circuit making current (peak)Electrical endurance

Rat ed operating sequence/duty

Rated closing timeRated opening timeRated breaking time

Rated auxiliary control voltage

kVAHz

kV/ 1 minkV, peak

kA, rmskA/4skA

274 (Class E2 in accordance with

O-0.3s-CO-180s-CO

msmsms

33/36/40.5630/1250/1600/2000/2500/315050/60

95185

25/31.525/31.563/80

55-8025-4060

IEC 62271-100 and GB 1984-2003)

O-0.3s-CO-180s-CO

V AC 110/220;DC 110/220

������������ ���������������

IEC 62271-100/200

Page 10: CONTENT - Richardson Projects...The values below are given for normal operating condition as defined in IEC 60298, IEC 60694 10D 12kV METALCLAD SWITCHGEAR 2 Other values are available

Switchgear typeApplicable standardsClasification of switchgearService condition

Rated voltage (kV)Rated current (A)Rated frequency (Hz)Insulation level- 1 min power frequency (kV rms)- 1.2x50 μs impulse (kV peak)Rated short-time withstand current (kA-sec)Degree of protection HV compartmentLV compartmentOperating boxGas pressureRated pressure (MPa)Low pressure alarm stage-1 (MPa)Low pressure alarm stage-2 (MPa)High pressure (MPa)Operation of 3-position isolatorAuxiliary voltageControl circuit (Vdc)Motor circuit (Vac/Vdc)

BGA-36IEC 60298, BS 5227

SF6-insulated metal enclosedAltitude <1000m�������������� ��������������������Relative humidity - 24 Hrs, average <95%-1 month average <90%

361250, 2000

50/60

7017025-3

IP65IP40IP30

0.080.060.050.12

Motorized/manual

110240/110

Switchgear Model HICLAD-30GA

�� ����%"��%&��� '��� ��������� ����

��(�)*� �*��+�

The standard factory-assambled switchgear developed on the basis of a modem design concept and technology with SF6 gas insula-tion.

The HICLAD-30GA is fully type-tested, indoor type, 36 kV metal-clad switchgear, factory asembled under rigorous quality control and tests.

VCB modelApplicable standardsRated voltage (kV)Rated current (A)Rated frequency (Hz)Insulation level- 1 min power frequency (kV rms)- 1.2x50 μs impulse (kV peak) Rated short circuit breaking current (kA)Rated short circuit making current (kA peak)Rated short-time withstand current (kA-sec)Operating duty

Rated closing time (sec)Rated opening time (sec)Rated break time (sec) Rated TRV for terminal faultRate of rise (kV/μs)TRV peak voltage (kV)Type of operating mechanism Tripping systemSpring charging motorAuxiliarry voltage (Vac/Vdc)Output (W)Current (A)Closing coilAuxiliary voltage (Vdc)Current (A)Tripping coilAuxiliary voltage (Vdc)Current (A)

VGA-32IEC 62271-100

361250, 2000

50/60

70170256325

0-0.3sec-CO-3min-CO0-0.3sec-CO-3min-CO

0.050.050.07

0.57 62

Motor charged spring stored energyShunt trip

240/11060

1.5A 230 Vac

1105A

1106A

Vacuum Circuit-Breaker (VCB) It is designed to accomodate high-performance vacuum circuit breaker (VCB) which has been designed, manufactured and tested in accordance with IEC 56 and BS 5311.

The switchgear itself conforms to IEC 60298 and BS 5227, and the all primary components employed therein are in accordance with the relevant IEC and/ or BS Standars. The modern production process has been introduced for the manufacture of main components, primarily in sheet-metal forming and gas-tight tank, the technique of gas tightness and jointing frameworks,surface protection and so on.

SF6 gas insulation used in conjunction with vacuum circuit-breaker (VCB) has set new standard with respect to:

Operational realiability and availability Reduced maintenance work Safety for operators Free from environmental pulution Reduced dimensions and less space requirements Capability of current interuption with zero gas pressure (at atmospheric pres sure) Motorised Busbar Live Transfer Discon nectors are provided for double Busbar switchgears

8

)*� �*��+�

Page 11: CONTENT - Richardson Projects...The values below are given for normal operating condition as defined in IEC 60298, IEC 60694 10D 12kV METALCLAD SWITCHGEAR 2 Other values are available

!"#$���,�������,&���(� ��������������

DescriptionRated voltageRated currentRated frequency Rated insulation level- Power frequency withstand voltage/min- Lightning impulse withstand voltage (peak)Rated short circuit breaking currentRated short time withstand current (4s)Rated short circuit making current (peak)Rated peak value withstand current (peak)Rated operating sequence

Rated auxiliary control voltageMechanical endurance

Annual leakage rateSF6 rated pressureSF6 alarm pressure

kVA

Hz

kVkVkAkAkAkA

VNo. oftimes %/YMPaMPa

40.5630/1250/1600/2000/250050/60

9518525/31.525/31.563/8063/80O-0.3s-CO-180s-COO-180s-CO-180s-COAC 110/220;DC 110/220

10000< 0.10.35 ± 0.020.28 ± 0.01

9

Page 12: CONTENT - Richardson Projects...The values below are given for normal operating condition as defined in IEC 60298, IEC 60694 10D 12kV METALCLAD SWITCHGEAR 2 Other values are available

Rated voltageRated Insulation Level- 1.2/50 Wave-Form- Power FrequencyRated normal current - Switch- BusbarsRated Breaking Current - Oil switches onlyMaximum Fuse Rating

Fused switches to IEC 420Fault Ratings (Lines and Earth Switches)- ASTA certified to IEC265, BS5463, and complies also with AS1025Additional Proving Tests- Generally in accordance with BS2631-1955,AS1025 and AS2024

254 mm

359 mm

12 kV15.5 kV

Up to 15.5 kV

Up to 110 kVUp to 50 kV RMS

630 A630 A 630 A at 0.7 pf100 A at 6.6 kV80 A at 11 kV150 A at 6.6 kV120 A at 11 kV80 A at 15.5 kV

20 kA21.9 kA RMS3 second rating55.9 kA pk. make

Technical Specification

�'-�'7�8*��(The ROSSS consists of three switch units, whereas the ROKSS is a switch-fuse unit, combined with two switch units. In both units the switch and/ or switch fuses are mounted side by side in common welded steel tanks.

On both units, the tank is fitted with four hinged access covers. The left-hand covers the ROKSS gives access to the fuses while the other covers on both the ROSSS and ROKSS permit contact or cable testing on the circuit switches and switch-fuse where fitted.

In addition to the normal non-extinsible and extensible ROKSS units a direct connected tee-off switch-fuse version is available for mounting directly onto a transformer. The flange lines up with a standard transformer flange.

�'�����9�����9�89���'-�'7�8*��(The ROS is a single switch units whereas the ROK is a single switch fuse unit.

The oil filled welded steel tank is common to both types and is fitted with two hinged access covers. The right-hand cover gives access to the circuit switch for contact inspection or cable testing. On the ROK unit the left hand cover gives access to the three oil immersed fuses.

Technical Specification Rated voltageRated Insulation Level- 1.2/50 Wave-Form- Power FrequencyRated normal current - Switch- BusbarsRated Breaking Current - ROS onlyMaximum Fuse Rating - ROK only

Fused switches to IEC 420Fault Ratings (Lines and Earth Switches)- ASTA certified to IEC265, BS5463, and complies also with AS1025Additional Proving Tests- Generally in accordance with BS2631-1955,AS1025

Up to 15.5 kV

Up to 110 kVUp to 50 kV RMS

630 A630 A 630 A at 0.7 pf100 A at 6.6 kV80 A at 11 kV150 A at 6.6 kV120 A at 11 kV80 A at 15.5 kV

20 kA21.9 kA RMS3 second rating55.9 kA pk. make

254 mm

359 mm

12 kV15.5 kV

10

Page 13: CONTENT - Richardson Projects...The values below are given for normal operating condition as defined in IEC 60298, IEC 60694 10D 12kV METALCLAD SWITCHGEAR 2 Other values are available

11

SF� RING MAIN UNIT��������� ����

The Sabre VRN 2a (6a) is compact SF6 insulated Vacuum Ring Main Unit (RMU). The unit can be mounted to the smallest distribution transformer or be sited in a free standing format. Designed to be used both indoors and outdoors, the unit has a long service life and requires virtually zero maintenance.

Design

Bracketed dimensions are alternative lower heightDimensions in millimetres

Under licensed by Lucy Switchgear

Page 14: CONTENT - Richardson Projects...The values below are given for normal operating condition as defined in IEC 60298, IEC 60694 10D 12kV METALCLAD SWITCHGEAR 2 Other values are available

12

VRN2a VRN6a

Rated Voltage

Impulse Withstand Voltage (kV Peak)

Normal Current

Ring Switches

Circuit Breaker

Busbar

Short Circuit Peak Making Current

Ring Switches

Tee-off Circuit Breaker

Short Circuit Breaking Current

Tee-off Circuit Breaker

3 Second Short Time Current

Ring Switches

Tee-off Circuit Breaker

Earth Switch Peak Making Current

Ring Switches

Tee-off Circuit Breaker

Internal Arc Rating

Freestanding

Transformer Mounted

Gas Pressure

MOP

IP Rating

Up to IP54W

Dimensions

Height (mm)

Width (mm)

Depth (mm)

Weight (kg)

Weight of SF6 (kg)

Protection

TLF - Time Limit Fuse

Auxiliary Powered Relay

Self Powered Relay

Testing Standards Applicable

IEC 62271-103

IEC 62271-100

IEC 62271-102

IEC 60056

IEC 60265-1

IEC 60129

IEC 60694

IEC 60298

ENA TS 41-36

IEC 62271-200

12kV (15.5kV)

75kV (95kV)

630A

250A

630A

50kA

50kA

20kA RMS

20kA

20kA

50kA

7.9kA

20kA 1 sec

20kA 1 sec in ENA Housing

zero bar (G)

Up to IP54W

1715, 1635 or 1415

950

1080

350

1.46

12kV (15.5kV)

75kV (95kV)

630A

630A

630A

50kA

50kA

20kA RMS

20kA

20kA

50kA

50kA

20kA 1 sec

20kA 1 sec in ENA Housing

zero bar (G)

Up to IP54W

1775, 1690 or 1470

950

1080

360

1.46

Technical Data (rating in brackets are optimal)

Key features- Compact Design

- 12kV and 15.5kV

- Indoor / Outdoor application

- Mimic Diagram

- Vacuum tee off circuit breakers

- Enhanced duty, in excess of IEC requirements

- Pre-wired for motor actuation

- Fault passage indicators

- Common switching chamber

- Full ratings with zero atmospheric pressure

- Isolation in clean SF6 gas

Options

���������All options provide transformer over current protection for phase to phase faults. Earth protection covering phase to earth faults is also available if required.

�� �������Internal arc test cable boxes are available with IEC and ENA specifications.Interlocked cable boxes are also provided as options.

���������The Sabre VRN2a can be pre-wired for automation. Single or double rotary actuators can be easily and rapidly fitted on site whilst the unit is in service - no access is required to the internal workings of the RMU.

Page 15: CONTENT - Richardson Projects...The values below are given for normal operating condition as defined in IEC 60298, IEC 60694 10D 12kV METALCLAD SWITCHGEAR 2 Other values are available