control and chapterb11 tesys p c rotection omponents from ...b11/1 overload relays overload relays...

62
B11/1 Overload relays Overload relays from 0.16 to 630 A Thermal overload relays - For use with TeSys K contactors Type of product Range Pages Adjustable thermal overload relays For motors TeSys LRK From 0.16 to 16 A B11/2 Adjustable thermal overload relays For unbalanced loads TeSys LRK From 0.8 to 16 A B11/3 Thermal overload relays Class 10 A - For use with TeSys D contactors Adjustable thermal overload relays For motors TeSys LRD From 0.16 to 140 A B11/4 Adjustable thermal overload relays For unbalanced loads TeSys LRD From 0.16 to 140 A B11/4 Thermal overload relays Class 20 - For use with TeSys D contactors Adjustable thermal overload relays For motors TeSys LRD From 0.63 to 80 A B11/6 Adjustable thermal overload relays For unbalanced loads TeSys LRD From 0.63 to 32 A B11/6 Electronic thermal overload relays - For use with TeSys D contactors Adjustable electronic overload relay, Multi-class, multi-scale TeSys LR9D From 0.1 to 150 A B11/10 Electronic thermal overload relays - For use with TeSys F contactors Compensated and differential overload relays, with or without alarm TeSys LR9F From 50 to 630 A B11/11 Single pole magnetic over current relays Latching or non latching overload relays TeSys RM1 From 1.15 to 630 A B11/15 Thermistor-type protection units – For use detection of motor overheating Protection units and PTC probes, with or without fault memory TeSys LT3 From 90 to 170 °C B11/17 Electronic over current relays - For machine protection Predefined or adjustable starting times, Manual reset From 1.5 to 34 A B11/19 Automatic, electric or manual reset From 0.5 to 50 A B11/19 TeSys Control and Protection Components Chapter B11 Technical Data for Designers B11/21

Upload: others

Post on 26-Jan-2021

7 views

Category:

Documents


0 download

TRANSCRIPT

  • B11/1

    Ove

    rloa

    d re

    lays

    Overload relays from 0.16 to 630 A

    Thermal overload relays - For use with TeSys K contactorsType of product Range Pages

    Adjustable thermal overload relaysFor motorsTeSys LRK

    From 0.16 to 16 A B11/2

    Adjustable thermal overload relaysFor unbalanced loads TeSys LRK

    From 0.8 to 16 A B11/3

    Thermal overload relays Class 10 A - For use with TeSys D contactorsAdjustable thermal overload relaysFor motors TeSys LRD

    From 0.16 to 140 A B11/4

    Adjustable thermal overload relaysFor unbalanced loads TeSys LRD

    From 0.16 to 140 A B11/4

    Thermal overload relays Class 20 - For use with TeSys D contactorsAdjustable thermal overload relaysFor motors TeSys LRD

    From 0.63 to 80 A B11/6

    Adjustable thermal overload relaysFor unbalanced loads TeSys LRD

    From 0.63 to 32 A B11/6

    Electronic thermal overload relays - For use with TeSys D contactors

    Adjustable electronic overload relay, Multi-class, multi-scaleTeSys LR9D

    From 0.1 to 150 A B11/10

    Electronic thermal overload relays - For use with TeSys F contactors

    Compensated and differential overload relays, with or without alarmTeSys LR9F

    From 50 to 630 A B11/11

    Single pole magnetic over current relays

    Latching or non latching overload relaysTeSys RM1 From 1.15 to 630 A B11/15

    Thermistor-type protection units – For use detection of motor overheating

    Protection units and PTC probes,with or without fault memoryTeSys LT3

    From 90 to 170 °C B11/17

    Electronic over current relays - For machine protection

    Predefined or adjustable starting times,Manual reset From 1.5 to 34 A B11/19

    Automatic, electric or manual reset From 0.5 to 50 A B11/19

    TeS

    ys Control and Protection Components

    Chapter

    B11

    Technical Data for Designers B11/21

  • B11/2

    Ove

    rloa

    d re

    lays

    3-pole relays with screw clamp terminalsThese overload relays are designed for the protection of motors. They are compensated and phase failure sensitive. Resetting can either be manual or automatic.Direct mounting: under the contactor for versions with screw clamp terminals only; pre-wired terminals, see pages B11/28 and B11/30.Separate mounting: using terminal block LA7K0064 (see below).On the front face of the overload relay:b selection of reset mode: Manual (marked H) or Automatic (marked A),b red pushbutton: Trip Test function,b blue pushbutton: Stop and manual Reset,b yellow trip flag indicator: overload relay tripped.Protection by magnetic circuit breaker GV2LE, see pages A6/11 and A6/20.

    Class 10 A (the standard specifies a tripping time of between 2 and 10 seconds at 7.2 In)Relay setting range

    Fuses to be used with selected relayMaximum ratingType

    Reference

    aM gG BS88A A A A

    0.11…0.16 0.25 0.5 – LR2K0301

    0.16…0.23 0.25 0.5 – LR2K0302

    0.23…0.36 0.5 1 – LR2K0303

    0.36…0.54 1 1.6 – LR2K0304

    0.54…0.8 1 2 – LR2K0305

    0.8…1.2 2 4 6 LR2K0306

    1.2…1.8 2 6 6 LR2K0307

    1.8…2.6 4 8 10 LR2K0308

    2.6…3.7 4 10 16 LR2K0310

    3.7…5.5 6 16 16 LR2K0312

    5.5…8 8 20 20 LR2K0314

    8…11.5 10 25 20 LR2K0316

    10…14 16 32 25 LR2K0321

    12…16 20 40 32 LR2K0322

    Overload relaysThermal overload relays for TeSys K contactors - adjustable from 0.11 to 16 A Class 10 A

    References - TeSys LRKPF

    5262

    26.ti

    f

    LR2K0307

    Characteristics:pages B11/28 and B11/30

    Dimensions:page B11/30

    Schemes:page B11/30

    Overload relays for unbalanced loadsClass 10 A: to order, replace the prefix LR2 by LR7 in the references selected from above (only applicable to overload relays LR2K0305 to LR2K0322).Example: LR7K0308.

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=V2http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2K0301http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2K0302http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2K0303http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2K0304http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2K0305http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2K0306http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2K0307http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2K0308http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2K0310http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2K0312http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2K0314http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2K0316http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2K0321http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2K0322

  • B11/3

    Ove

    rloa

    d re

    lays

    Overload relaysThermal overload relays for TeSys K contactors - adjustable from 0.11 to 16 A Class 10 A

    References - TeSys LRK

    AccessoryDescription Type of connection Reference

    Terminal block for separate clip-on mounting of the overload relay on 35 mm 7 rail

    Screw clamp LA7K0064

    8125

    59.ti

    f

    LA7K0064

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7K0064

  • B11/4

    Ove

    rloa

    d re

    lays

    PF52

    6200

    .eps

    3-pole differential thermal overload relays for screw clamp connectors and lugs for use with fuses or magnetic circuit breakers GV2L and GV3L b Compensated relays with manual or automatic reset b with relay trip indicator b for a.c. or d.c.

    Relay setting range (A)

    Fuses to be used with selected relay For use with contactor LC1

    Reference WeightkgaM (A) gG (A) BS88 (A)

    LRDpp Class 10 A (1) for connection by screw clamp terminals or connectors0.10…0.16 0.25 2 – D09…D38 LRD01 0.1240.16…0.25 0.5 2 – D09…D38 LRD02 0.1240.25…0.40 1 2 – D09…D38 LRD03 0.124

    PF52

    6201

    .eps

    0.40…0.63 1 2 – D09…D38 LRD04 0.1240.63…1 2 4 – D09…D38 LRD05 0.1241…1.6 2 4 6 D09…D38 LRD06 0.1241.6…2.5 4 6 10 D09…D38 LRD07 0.1242.5…4 6 10 16 D09…D38 LRD08 0.1244…6 8 16 16 D09…D38 LRD10 0.1245.5…8 12 20 20 D09…D38 LRD12 0.1247…10 12 20 20 D09…D38 LRD14 0.1249…13 16 25 25 D12…D38 LRD16 0.12412…18 20 35 32 D18…D38 LRD21 0.12416…24 25 50 50 D25…D38 LRD22 0.124

    LRD3pp 23…32 40 63 63 D25…D38 LRD32 0.12430…38 40 80 80 D32 and D38 LRD35 0.124Class 10 A (1) for connection by EverLink® BTR screw connectors (3)

    9…13 16 25 25 D40A…D65A LRD313 0.37512…18 20 32 35 D40A…D65A LRD318 0.37517…25 25 50 50 D40A…D65A LRD325 0.375

    PF52

    6202

    .eps

    23…32 40 63 63 D40A…D65A LRD332 0.37530…40 40 80 80 D40A…D65A LRD340 0.37537…50 63 100 100 D40A…D65A LRD350 0.37548…65 63 100 100 D50A and D65A LRD365 0.37562...80 80 125 125 D80A LRD380 (4) 0.375Class 10 A (1) for connection by screw clamp terminals or connectors

    17…25 25 50 50 D80 and D95 LRD3322 0.51023…32 40 63 63 D80 and D95 LRD3353 0.51030…40 40 100 80 D80 and D95 LRD3355 0.510

    LRD33pp 37…50 63 100 100 D80 and D95 LRD3357 0.51048…65 63 100 100 D80 and D95 LRD3359 0.51055…70 80 125 125 D80 and D95 LRD3361 0.51063…80 80 125 125 D80 and D95 LRD3363 0.51080…104 100 160 160 D80 and D95 LRD3365 0.51080…104 125 200 160 D115 and D150 LRD4365 0.900

    PF52

    6203

    .eps

    95…120 125 200 200 D115 and D150 LRD4367 0.900110…140 160 250 200 D150 LRD4369 0.90080…104 100 160 160 (2) LRD33656 1.00095…120 125 200 200 (2) LRD33676 1.000110…140 160 250 200 (2) LRD33696 1.000Class 10 A (1) for connection by lugs

    Select the appropriate overload relay with screw clamp terminals or connectors from the table above and add one of the following suffixes:

    b figure 6 for relays LRD01 to LRD35 and relays LRD313 to LRD380 (4). b A66 for relays LRD3322 to LRD3363.

    Relays LRD43pp are suitable, as standard, for use with lug-clamps.LRD3pp6 Thermal overload relays for use with unbalanced loads

    Class 10 A (1) for connection by screw clamp terminals or lugsIn the references selected above, change the prefix LRD (except LRD43pp) to LR3D. Example: LRD01 becomes LR3D01.Example with EverLink®connectors: LRD340 becomes LR3D340.Example with lugs: LRD3406 becomes LR3D3406.(1) Standard IEC 60947-4-1 specifies a tripping time for 7.2 times the setting current IR: class 10 A: between 2 and 10 seconds.(2) Independent mounting of the contactor.(3) BTR screws: hexagon socket head. In accordance with local electrical wiring regulations, a size 4 insulated Allen key must be

    used (reference LADALLEN4, see page B8/29).(4) LRD380 available end 2017.

    References - TeSys LRD

    Characteristics:pages B11/32 to B11/34

    Dimensions:pages B11/35 to B11/37

    Schemes:page B11/37

    Overload relaysThermal overload relays for TeSys D contactors - Class 10 A

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=V2http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=V3http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD01http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD02http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD03http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD04http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD05http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD06http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD07http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD08http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD10http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD12http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD14http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD16http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD21http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD22http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD32http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD35http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD313http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD318http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD325http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD332http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD340http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD350http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD365http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD380http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3322http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3353http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3355http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3357http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3359http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3361http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3363http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3365http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD4365http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD4367http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD4369http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD33656http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD33676http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD33696

  • B11/5

    Ove

    rloa

    d re

    lays

    PF52

    6204

    .eps

    3-pole differential thermal overload relays for spring terminals for use with fuses or magnetic circuit breakers GV2L and GV3L b Compensated relays with manual or automatic reset b with relay trip indicator b for a.c. or d.c.

    Relay setting range (A)

    Fuses to be used with selected relay For use with contactor LC1

    ReferenceaM (A) gG (A) BS88 (A)

    Classes 10 A (1) for connection by spring terminals (only for direct mounting beneath the contactor)LRDpp3 0.10…0.16 0.25 2 – D09…D38 LRD013

    0.16…0.25 0.5 2 – D09…D38 LRD0230.25…0.40 1 2 – D09…D38 LRD0330.40…0.63 1 2 – D09…D38 LRD0430.63…1 2 4 – D09…D38 LRD0531…1.6 2 4 6 D09…D38 LRD0631.6…2.5 4 6 10 D09…D38 LRD0732.5…4 6 10 16 D09…D38 LRD0834…6 8 16 16 D09…D38 LRD1035.5…8 12 20 20 D09…D38 LRD1237…10 12 20 20 D09…D38 LRD1439…13 16 25 25 D12…D38 LRD16312…18 20 35 32 D18…D38 LRD21316…24 25 50 50 D25…D38 LRD223

    Class 10 A with connection by EverLink® BTR screw connectors (2) and control by spring terminals9…13 16 25 25 D40A…D65A LRD313312…18 20 32 35 D40A…D65A LRD318317…25 25 50 50 D40A…D65A LRD325323…32 40 63 63 D40A…D65A LRD332330…40 40 80 80 D40A…D65A LRD340337…50 63 100 100 D40A…D65A LRD350348…65 63 100 100 D50A and D65A LRD365362...80 80 125 125 D80A LRD3803 (3)

    Thermal overload relays for use with unbalanced loadsClasses 10 A (1) for connection by BTR screw connectors (2) and control by spring terminals

    In the references selected above, replace LRD3 with LR3D3.Example: LRD3653 becomes LR3D3653.

    Thermal overload relays for use on 1000 V suppliesClasses 10 A (1) for connection by screw clamp terminals

    For relays LRD06 to LRD35 only, for an operating voltage of 1000 V, and only for independent mounting, the reference becomes LRD33ppA66. Order an LA7D3064 terminal block separately, see page B11/9.

    Standard relay Relay for 1000 V networkLRD06 LRD3306A66LRD07 LRD3307A66LRD08 LRD3308A66LRD10 LRD3310A66LRD12 LRD3312A66LRD14 LRD3314A66LRD16 LRD3316A66LRD21 LRD3321A66LRD22 LRD3322A66LRD32 LRD3353A66LRD35 LRD3355A66(1) Standard IEC 60947-4-1 specifies a tripping time for 7.2 times the setting current IR: class 10 A: between 2 and 10 seconds. (2) BTR screws: hexagon socket head. In accordance with local electrical wiring regulations, a size 4 insulated Allen key must be

    used (reference LADALLEN4, see page B8/29).(3) LRD3803 available end 2017.

    References - TeSys LRD

    Overload relaysThermal overload relays for TeSys D contactors - Class 10 A

    Characteristics:pages B11/32 to B11/34

    Dimensions:pages B11/35 to B11/37

    Schemes:page B11/37

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=V2http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=V3http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD013http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD023http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD033http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD043http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD053http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD063http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD073http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD083http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD103http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD123http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD143http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD163http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD213http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD223http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3133http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3183http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3253http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3323http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3403http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3503http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3653http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3803http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD06http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD07http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD08http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD10http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD12http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD14http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD16http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD21http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3321A66http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD22http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3322A66http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD32http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3353A66http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD35http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD3355A66

  • B11/6

    Ove

    rloa

    d re

    lays

    PB11

    3030

    _S_3

    0.ep

    s 3-pole differential thermal overload relays for screw clamp connectors and lugs for use with fuses or magnetic circuit breakers GV2L and GV3L b Compensated relays with manual or automatic reset b with relay trip indicator b for a.c. or d.c.

    Relay setting range (A)

    Fuses to be used with selected relay For use with contactor LC1

    ReferenceaM (A) gG (A) BS88 (A)

    Classes 20 (1) for connection by screw clamp terminalsLRD04L...LRD32L 0.4...0.63 1 2 - D09…D38 LRD04L

    0.63...1 2 4 - D09…D38 LRD05L

    1...1.6 2 4 6 D09…D38 LRD06L

    1.6...2.5 4 6 10 D09…D38 LRD07L

    2.5...4 6 10 16 D09…D38 LRD08L

    4...6 8 16 16 D09…D38 LRD10L

    PF52

    6201

    .eps

    5.5...8 12 20 20 D09…D38 LRD12L

    7...10 12 20 20 D09…D38 LRD14L

    9...13 16 25 25 D12…D38 LRD16L

    12...18 20 35 32 D18…D38 LRD21L

    17...24 25 50 50 D25…D38 LRD22L

    23...32 40 63 63 D25…D38 LRD32L

    Class 20 (1) for connection by EverLink® BTR screw connectors (2)9…13 20 32 35 D40A…D65A LRD313L

    12…18 25 40 40 D40A…D65A LRD318L

    LRD3ppL 17…25 32 50 50 D40A…D65A LRD325L

    23…32 40 63 63 D40A…D65A LRD332L

    30…40 50 80 80 D40A…D65A LRD340L

    37…50 63 100 100 D40A…D65A LRD350L

    48…65 80 125 125 D50A and D65A LRD365L

    PF52

    6206

    .eps

    Classes 20 (1) for connection by screw clamp terminals17…25 32 50 50 D80 and D95 LR2D3522

    23…32 40 63 63 D80 and D95 LR2D3553

    30…40 40 100 80 D80 and D95 LR2D3555

    37…50 63 100 100 D80 and D95 LR2D3557

    48…65 80 125 100 D80 and D95 LR2D3559

    55…70 100 125 125 D80 and D95 LR2D3561

    LR2D35pp 63…80 100 160 125 D80 and D95 LR2D3563

    Class 20 (1) for connection by lugsFor relays LRD04L to LRD32L and relays LRD313L to LRD365L, select the appropriate overload relay with screw clamp terminals or connectors from the table above and add the suffixe 6.Example: LRD04L becomes LRD04L6.Thermal overload relays for use with unbalanced loadsClass 20 (1) for connection by screw clamp terminals or lugs

    For relays LRD04L to LRD32L and relays LR2D3522 to LR2D3563, select the appropriate overload relay with screw clamp terminals or connectors from the table above and change the prefix LRD or LR2D to LR3D.Example: LRD04L becomes LR3D04L.(1) Standard IEC 60947-4-1 specifies a tripping time for 7.2 times the setting current IR:

    class 20: between 6 and 20 seconds (2) BTR screws: hexagon socket head. In accordance with local electrical wiring regulations, a size 4 insulated Allen key must be

    used (reference LADALLEN4, see page B8/29).

    References - TeSys LRD

    Overload relaysThermal overload relay for TeSys D contactors - Class 20

    Characteristics:pages B11/32 to B11/34

    Dimensions:pages B11/35 to B11/37

    Schemes:page B11/37

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=V2http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=V3http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD04Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD05Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD06Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD07Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD08Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD10Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD12Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD14Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD16Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD21Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD22Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD32Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD313Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD318Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD325Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD332Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD340Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD350Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD365Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2D3522http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2D3553http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2D3555http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2D3557http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2D3559http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2D3561http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR2D3563

  • B11/7

    Ove

    rloa

    d re

    lays

    3-pole differential thermal overload relays for screw clamp connectors and springs for use with fuses or magnetic circuit breakers GV2L and GV3L b Compensated relays with manual or automatic reset b with relay trip indicator b for a.c. or d.c.

    Relay setting range (A)

    Fuses to be used with selected relay For mounting beneath contactor LC1

    ReferenceaM (A) gG (A) BS88 (A)

    Class 20 (1) with connection by EverLink® BTR screw connectors (2) and control by spring terminals9…13 20 32 35 D40A…D65A LRD313L312…18 25 40 40 D40A…D65A LRD318L317…25 32 50 50 D40A…D65A LRD325L323…32 40 63 63 D40A…D65A LRD332L330…40 50 80 80 D40A…D65A LRD340L337…50 63 100 100 D40A…D65A LRD350L348…65 80 125 125 D50A and D65A LRD365L3(1) Standard IEC 60947-4-1 specifies a tripping time for 7.2 times the setting current IR:

    class 10: between 4 and 10 seconds, class 10 A: between 2 and 10 seconds, class 20: between 6 and 20 seconds.

    (2) BTR screws: hexagon socket head. In accordance with local electrical wiring regulations, a size 4 insulated Allen key must be used (reference LADALLEN4, see page B8/29).

    References - TeSys LRD

    Overload relaysThermal overload relay for TeSys D contactors - Class 20

    Characteristics:pages B11/32 to B11/34, pages B11/38 to B11/39

    Dimensions:pages B11/35 to B11/37 and B11/42

    Schemes:pages B11/39 and B11/43

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=V2http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=V3http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD313L3http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD318L3http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD325L3http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD332L3http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD340L3http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD350L3http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD365L3

  • B11/8

    Ove

    rloa

    d re

    lays

    DB4

    1591

    1.ep

    s

  • B11/9

    Ove

    rloa

    d re

    lays

    Separate components for relaysDescription For use with Sold in

    lots ofUnit reference

    Pre-wiring kit allowing direct connection of the N/C contact of relay LRD01…35 or LR3D01…D35 to the contactor

    LC1D09…D18 10 LAD7C1 (1)LC1D25…D38 10 LAD7C2 (1)

    Terminal block (2) for clip-on mounting on 35 mm rail (AM1DP200) or screw fixing; for fixing centres, see pages B11/35 to B11/37

    LRD01…35 and LR3D01…D35 1 LAD7B106LRD04L...LRD32L, LR3D04L...LR3D32L 1 LAD7B205LRD43pp, LRD33ppp, LR3D33ppp, LR2D35pp

    1 LA7D3064 (3)

    EverLink® terminal block for independent mounting

    LRD3pp, LRD3ppL and LR3D3pp 1 LAD96560

    Size 4 Allen key, insulated, 1000 V LRD3pp, LRD3ppL and LR3D3pp 5 LADALLEN4Terminal block adapter for mounting a relay beneath an LC1D115 or D150 contactor

    LRD33pp, LR3D33pp, LRD35pp 1 LA7D3058 (3)

    Mounting plates (4) for screw fixing on 110 mm centres

    LRD01…35, LR3D01…D35, LRD04L...LRD32L, LR3D04L...LR3D32L

    10 DX1AP25

    LRD3ppp, LR3D3ppp, LR2D35pp 1 LA7D902Marker holders, snap-in 8 x 18 mm

    LRD3pp 100 LAD90All relays except LRD01…35, LRD04L...32L, LR3D04L...D32LLR3D01…D35, LRD3pp, LRD3ppL and LR3D3pp

    100 LA7D903

    Bag of 400 blank legends (self-adhesive, 7 x 16 mm)

    All relays 1 LA9D91

    Stop button locking device All relays except LRD01…35, LRD04L...32L, LR3D04L...D32L LR3D01…D35, LR9 D and LRD313…LRD380 (9)

    10 LA7D901

    Remote Stop or electrical reset device (5)

    LRD01…35, LR3D01…D35, LRD04L...32L, LR3D04L...D32L and LRD313…LRD380 (9)

    1 LAD703p (6) (7)

    Remote tripping or electrical reset device (5)

    All relays except LRD01…35, LR9D01...32, LRD04L...32L, LR3D04L...D32L, LR3D01…D35, LR9D01...32, LRD3pp, LRD3ppL and LR3D3pp

    1 LA7D03p (6)

    Block of insulated terminals LR9 D 2 LA9F103 (7)IP 20 cover for lug type terminalsfor independent mounting

    LRD3136…3806 (9) 1 LAD96570

    IP 20 cover for lug type terminalsfor mounting with contactor LC1D40A6…D65A6

    LRD3136…3806 (9) 1 LAD96575

    Terminal block for lug type terminals for independent mounting

    LRD3136…3806 (9) 1 LAD96566

    Remote control“Reset” functionDescription For use with Sold in

    lots ofUnit reference

    By flexible cable(length = 0.5 m)

    LRD01…35, LR3D01…D35, LR3D04L...D32L and LRD313…LRD380 (9), LRD04L...LRD32L

    1 LAD7305 (8)

    All relays except LRD01...35, LR3D01...D35, LRD3pp, LRD04L...32L, LR3D04L...D32L, LRD3ppL and LR3D3pp

    1 LA7D305

    "Stop" and/or "Reset" functionsThe terminal protection shroud must be removed and the following 3 products must be ordered separately:Adapter for door mounting LRD33pp, LR2D 1 LA7D1020Operating heads for spring return pushbutton

    Stop All relays 1 XB5AL84101Reset All relays 1 XB5AA86102

    (1) These pre-wiring kits cannot be used with reversing contactors.(2) Terminal blocks are supplied with terminals protected against direct finger contact and screws in the open, "ready-to-tighten" position.(3) To order a terminal block for connection by lugs, the reference becomes LA7D30646.(4) Remember to order the terminal block corresponding to the type of relay.(5) The time for which the coil of remote tripping or electrical resetting device LA7D03 or LAD703 can remain energised depends

    on its rest time: 1 s pulse duration with 9 s rest time; 5 s pulse duration with 30 s rest time; 10 s pulse duration with 90 s rest time; maximum pulse duration 20 s with a rest time of 300 s. Minimum pulse time: 200 ms.

    (6) Reference to be completed by adding the code indicating the control circuit voltage. Standard control circuit voltages (for other voltages, please consult your Regional Sales Office):

    Volts 12 24 48 96 110 220/230 380/400 415/44050/60 Hz – B E – F M Q NConsumption, inrush and sealed: < 100 VAc J B E DD F M – –Consumption, inrush and sealed: < 100 W.(7) Only one terminal block can be mounted below LR9D.(8) Not compatible with 3-pole relays fitted with spring terminals.(9) LRD380, LRD3806 available end 2017.

    References - TeSys LRD

    Overload relaysThermal overload relays for TeSys D contactors - Accessories

    LAD7Cp

    DF5

    3782

    0.ep

    s

    LAD7B106

    DF5

    3782

    1.ep

    s

    LAD96570 LAD96575

    LAD96570

    DF5

    3860

    8.ep

    s

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD7C1http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD7C2http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD7B106http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD04Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD32Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR3D04Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR3D32Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD7B205http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7D3064http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD96560http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LADALLEN4http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7D305http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD04Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD32Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR3D04Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR3D32Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=DX1AP25http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7D902http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD90http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR3D04Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7D903http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA9D91http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR3D04Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7D901http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR3D04Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD703phttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR3D04Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7D03p http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA9F103http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD96570http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD96575http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD96566http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR3D04Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD7305http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR3D04Lhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7D305http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7D1020http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=XB5AL84101http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=XB5AA86102

  • B11/10

    Ove

    rloa

    d re

    lays

    Electronic thermal overload relaysFor use with fuses or magnetic circuit breakers

    b compensated relays, with relay trip indicator,b for a.c.,b for direct mounting on contactor or independent mounting (1).

    Relay setting range

    Fuses to be used with selected relay

    For direct mounting beneath contactor LC1

    Reference

    aM gGA A AClasses 5.10.20.30 (1) selectable for direct connection on TeSys D contactors or connection using connectors

    0.1...0.5 D09…D38 LR9D01

    0.4...2 D09…D38 LR9D02

    1.6…8 D09…D38 LR9D08

    6.4…32 D09…D38 LR9D32

    Classes 5.10.20.30 (1) selectable for connection using connectors22…110 LR9D110S

    Classes 10 or 10 A (1) for connection using bars or connectors60…100 100 160 D115…D150 LR9D5367

    90…150 160 250 D115…D150 LR9D5369

    Classes 20 (1) for connection using bars or connectors

    60…100 125 160 D115…D150 LR9D5567

    90…150 200 250 D115…D150 LR9D5569

    Separate components for relaysDescription For use with Sold in

    lots ofUnit reference

    Terminal block (2)For clips-on mounting on 35 mm rails (AM1DP200) or screws fixing; for fixing centres, see pages B11/35 to B11/37

    LR9D01, LR9D02, LR9D08, LR9D32

    1 LAD7B205

    Electronic overload relays for balanced or unbalanced loadsRelay setting range

    Fuses to be used with selected relay

    For direct mounting beneath contactor LC1

    Reference

    aM gGA A AClasses 10 or 20 (1) selectable for direct connection using bars or connectors

    60…100 100 160 D115…D150 LR9D67

    90…150 160 250 D115…D150 LR9D69

    (1) Standard IEC 60947-4-1 specifies a tripping time for 7.2 times the setting current IR: class 5: between 0.5 and 5 seconds class 10: between 4 and 10 seconds class 10 A: between 2 and 10 seconds class 20: between 6 and 20 seconds class 30: between 9 and 30 seconds.

    (2) Terminal blocks are supplied with terminals protected against direct finger contact and screws in the open, "ready-to-tighten" position.

    (3) Power terminals can be protected against direct finger contact by the addition of shrouds and/or insulated terminal blocks, to be ordered separately (see page B8/20).

    Overload relaysElectronic thermal overload relays for TeSys D contactors

    References - TeSys LR9D

    Presentation, characteristics:pages B11/38 to B11/39

    Dimensions:page B11/42

    Schemes:page B11/43

    LR9D0p and LR9D32

    PB11

    4690

    R.e

    ps

    LR9D110S

    PB11

    4691

    R.e

    ps

    LAD7B205 mounted on LR9D01

    PB11

    4692

    R.e

    ps

    LAD7B205

    PB11

    3031

    R.e

    ps

    LR9D5597

    PB10

    8399

    R.e

    ps

    LR9D67

    PG11

    1268

    _SE.

    eps

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D01http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D02http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D08http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D32http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D110Shttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D5367http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D5369http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D5567http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D5569http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D01http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D02http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D08http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D32http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD7B205http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D67http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D69http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D32http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D110Shttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD7B205http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D01http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD7B205http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9D67

  • B11/11

    Ove

    rloa

    d re

    lays

    Compensated and differential overload relaysThermal overload relays:b compensated and differential,b with relay trip indicator,b for a.c.,b for direct mounting on contactor or independent mounting (1).

    Relay setting range

    Fuses to be used with selected relay

    For direct mounting beneath contactor LC1

    Reference Weight

    aM gGA A A kgClass 10 (2)

    30…50 50 80 F115…F185 LR9F5357 0.885

    48…80 80 125 F115…F185 LR9F5363 0.900

    60…100 100 200 F115…F185 LR9F5367 0.900

    90…150 160 250 F115…F185 LR9F5369 0.885

    132…220 250 315 F185…F265 LR9F5371 0.950

    200…330 400 500 F225…F500 LR9F7375 2.320

    300…500 500 800 F225…F500 LR9F7379 2.320

    380…630 630 800 F400…F630 and F800

    LR9F7381 4.160

    Class 20 (2)30…50 50 80 F115…F185 LR9F5557 0.885

    48…80 80 125 F115…F185 LR9F5563 0.900

    60…100 100 200 F115…F185 LR9F5567 0.900

    90…150 160 250 F115…F185 LR9F5569 0.885

    132…220 250 315 F185…F265 LR9F5571 0.950

    200…330 400 500 F225…F500 LR9F7575 2.320

    300…500 500 800 F225…F500 LR9F7579 2.320

    380…630 630 800 F400…F630 and F800

    LR9F7581 4.160

    (1) When mounting overload relays LR9F5●57...LR9F5●71 directly beneath the contactor, supporting the relays with a mounting plate is recommended (see page B11/14). With overload relays LR9F7●75...LR9F7●81, use of a support mounting plate is mandatory (see page B11/14). Power terminals can be protected against direct finger contact by the addition of shrouds and/or insulated terminal blocks, to be ordered separately (see page B11/14). Interconnection kit LA7F407 is required for mounting an LR9F5●71 thermal overload relay together with an LC1F185 contactor.

    (2) Standard IEC 60947-4 specifies a tripping time for 7.2 times the setting current In: - class 10: between 4 and 10 seconds, - class 20: between 6 and 20 seconds.

    Overload relaysElectronic thermal overload relays for TeSys F contactors

    References - TeSys LR9FPF

    5262

    64.ti

    f

    LR9F53pp

    PF52

    6265

    .tif

    LR9F73pp

    Presentation:page B11/44

    Characteristics:pages B11/45 to B11/47

    Dimensions, schemes:pages B11/48 to B11/49

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F5357http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F5363http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F5367http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F5369http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F5371http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F7375http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F7379http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F7381http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F5557http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F5563http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F5567http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F5569http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F5571http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F7575http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F7579http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F7581

  • B11/12

    Ove

    rloa

    d re

    lays

    Compensated overload relays, class 10 or 20 with alarmThermal overload relays:b compensated,b with relay trip indicator,b for a.c.,b for direct mounting on contactor or independent mounting (1),b class 10 or 20 by selector switch,b protection of 3-phase or single-phase circuits by selector switch,b with alarm function that enables tripping to be forestalled. Relay setting range

    Fuses to be used with selected relay

    For direct mounting beneath contactor LC1

    Reference Weight

    aM gGA A A kg

    30…50 50 80 F115…F185 LR9F57 0.885

    48…80 80 125 F115…F185 LR9F63 0.900

    60…100 100 200 F115…F185 LR9F67 0.900

    90…150 160 250 F115…F185 LR9F69 0.885

    132…220 250 315 F185…F265 LR9F71 0.950

    200…330 400 500 F225…F500 LR9F75 2.320

    300…500 500 800 F225…F500 LR9F79 2.320

    380…630 630 800 F400…F630 and F800

    LR9F81 4.160

    (1) When mounting overload relays LR9F57...LR9F71 directly beneath the contactor, supporting the relays with a mounting plate is recommended (see page B11/14). With overload relays LR9F75...LR9F81, use of a support mounting plate is mandatory (see page B11/14). Power terminals can be protected against direct finger contact by the addition of shrouds and/or insulated terminal blocks, to be ordered separately (see page B11/14). Interconnection kit LA7F407 is required for mounting an LR9F71 thermal overload relay together with an LC1F185 contactor.

    Overload relaysElectronic thermal overload relays for TeSys F contactors

    References - TeSys LR9FPF

    5262

    66.ti

    f

    LR9F57

    Presentation:page B11/44

    Characteristics:pages B11/45 to B11/47

    Dimensions, schemes:pages B11/48 to B11/49

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F57http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F63http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F67http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F69http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F71http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F75http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F79http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR9F81

  • B11/13

    Ove

    rloa

    d re

    lays

    Control accessoriesDescription Sold in

    lots ofUnit reference

    Remote electrical reset device (1) 1 LA7D03p (2)

    Remote Reset function controlby flexible cable (length = 0.5 m)

    1 LA7D305

    Remote Stop and/or Reset function control

    Adapter for door mounted operator

    1 LA7D1020

    Rod (snap-off end to obtain required length, between 17 and 120 mm)

    10 ZA2BZ13

    Operating head for spring return pushbutton

    1 ZA2Bpppp (3)

    Connection accessoriesFor mounting an LR9F5p71 thermal overload relay together with an LC1 F185 contactorDescription Reference

    Set of 3 busbars LA7F407

    For mounting a thermal overload relay beneath a reversing contactor or star-delta contactorsApplication Width of

    terminal lugSet of 3 busbars ReferenceFor relay For contactor

    mmLR9F5p57, F5p63, F5p67, F5p69, LR9F57, F63, F67, F69

    LC1 F115 15 LA7F401

    LR9F5p57, F5p63, F5p67, F5p69, LR9F57, F63, F67, F69

    LC1 F150, F185 20 LA7F402

    LR9F5p71, LR9F71

    LC1 F185 25 LA7F407

    LR9F5p71, LR9F71

    LC1 F225, F265 25 LA7F403

    LR9F7p75, F7p79, LR9F75, F79

    LC1 F225...F400 25 LA7F404

    LR9F7p81, LR9F81

    LC1 F400 25 LA7F404

    LR9F7p75, F7p79, F7p81, LR9F75, F79, F81

    LC1 F500 30 LA7F405

    LR9F7p81, LR9F81

    LC1 F630, F800 40 LA7F406

    (1) The time for which the coil of remote electrical reset device LA7D03 can remain energised depends on its rest time: 1 s pulse duration with 9 s rest time; 5 s pulse duration with 30 s rest time; 10 s pulse duration with 90 s rest time. Maximum pulse duration of 20 s with rest time of 300 s. Minimum pulse time: 200 ms.

    (2) Reference to be completed by adding the coil voltage code. Standard control circuit voltages, (for other voltages, please consult your Regional Sales Office):

    Volts 12 24 48 96 110 220/

    230380/ 400

    415/ 440

    a 50/60 Hz – B E – F M Q NConsumption, inrush and sealed: < 100 VA c J B E DD F M – –Consumption, inrush and sealed: < 100 W.(3) Stop: ZA2BL432 and Reset: ZA2BL639.

    Overload relaysElectronic thermal overload relays for TeSys F contactors Accessories (to be ordered separately)

    References - TeSys LR9F

    RR

    8195

    59.e

    ps

    LA7D305

    8195

    58.e

    ps

    LA7D03p

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7D03p http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7D305http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7D1020http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=ZA2BZ13http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7F407http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7F401http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7F402http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7F407http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7F403http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7F404http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7F404http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7F405http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7F406

  • B11/14

    Ove

    rloa

    d re

    lays

    Mounting plates for overload relayFor use with relays Reference

    LR9F5p57, F5p63, F5p67, F5p69, F5p71, LR9F57, F63, F67, F69, F71

    LA7F901

    LR9F7p75, F7p79, F7p81, LR9F75, F79, F81

    LA7F902

    Sets of power terminal protection shrouds, single-poleFor use with relays

    Number of shrouds per set

    Set reference

    LR9F5p57, LR9F57

    6 LA9F701

    LR9F5p63, F5p67, F5p69, LR9F63, F67, F69

    6 LA9F702

    LR9F5p71, LR9F71

    6 LA9F705

    LR9F7p75, F7p79, F7p81, LR9F75, F79, F81

    6 LA9F703

    Power terminal protection shrouds, 3-poleFor use with relays

    Reference

    LR9F5p57, F5p63, F5p67, F5p69, LR9F57, F63, F67, F69

    LA7F701

    LR9F5p71, LR9F71

    LA7F702

    LR9F7p75, F7p79, F7p81, LR9F75, F79, F81

    LA7F703

    Insulated terminal blocks For use with relays

    Set of 2 blocks Reference

    LR9F5p57, F5p63, F5p67, F5p69, LR9F57, F63, F67, F69

    LA9F103

    Marking accessoriesDescription Sold in

    lots ofUnit reference

    Clip-in marker holder 100 LA7D903

    Bag of 400 blank self-adhesive legends 7 x 16 mm

    1 LA9D91

    Overload relaysElectronic thermal overload relays for TeSys F contactors Accessories (to be ordered separately)

    References - TeSys LR9F81

    9561

    .eps

    LA7F90p

    8195

    62.e

    ps

    LA9F70p

    8195

    64.e

    ps

    LA7F70p

    8195

    63.e

    ps

    LA9F103

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7F901http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7F902http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA9F701http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA9F702http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA9F705http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA9F703http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7F701http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7F702http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7F703http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA9F103http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA7D903http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA9D91

  • B11/15

    Ove

    rloa

    d re

    lays

    Non-latchingWith 1 C/O contact block, non-latchingRecommanded operating range (motor In)

    Setting range (trip current)

    Maximum continuous current a or c

    Reference

    A A Aa or c 0.7…1.15 1.25…4 1.6 RM1XA001

    1.16…1.8 2…6.3 2.5 RM1XA002

    1.9…2.9 3.2…10 4 RM1XA004

    3…4.6 5…16 6.3 RM1XA006

    4.7…7.2 8…25 10 RM1XA010

    7.3…11.5 12.5…40 16 RM1XA016

    11.6…18 20…63 25 RM1XA025

    18.1…29 32…100 40 RM1XA040

    29.1…46 50…160 63 RM1XA063

    46.1…72 80…250 100 RM1XA100

    73…115 125…400 160 RM1XA160

    116…145 160…500 200 RM1XA200

    146…230 250…800 315 RM1XA315

    231…360 400 …1250 500 RM1XA500

    a 361…630 630…2200 1000 RM1XA101

    c 361…570 630…2000 1000 RM1XA101

    Accessory (to be ordered separately)Description Reference

    1 C/O contact block, non-latching RM1ZG21

    Overload relaysSingle-pole magnetic over current relays

    References - TeSys RM1

    Characteristics:page B11/50

    Dimensions:page B11/51

    Schemes:page B11/51

    DF5

    3355

    8.tif

    RM1XA001

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA001http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA002http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA004http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA006http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA010http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA016http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA025http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA040http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA063http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA100http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA160http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA200http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA315http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA500http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA101http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA101http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1ZG21

  • B11/16

    Ove

    rloa

    d re

    lays

    Latching with manual resetWith 1 C/O contact block, latching with manual resetRecommanded operating range (motor In)

    Setting range (trip current)

    Maximum continuous current a or c

    Reference

    A A Aa or c 0.7…1.15 1.25…4 1.6 RM1XA0011

    1.16…1.8 2…6.3 2.5 RM1XA0021

    1.9…2.9 3.2…10 4 RM1XA0041

    3…4.6 5…16 6.3 RM1XA0061

    4.7…7.2 8…25 10 RM1XA0101

    7.3…11.5 12.5…40 16 RM1XA0161

    11.6…18 20…63 25 RM1XA0251

    18.1…29 32…100 40 RM1XA0401

    29.1…46 50…160 63 RM1XA0631

    46.1…72 80…250 100 RM1XA1001

    73…115 125…400 160 RM1XA1601

    116…145 160…500 200 RM1XA2001

    146…230 250…800 315 RM1XA3151

    231…360 400…1250 500 RM1XA5001

    a 361…630 630…2200 1000 RM1XA1011

    c 361…570 630…2000 1000 RM1XA1011

    Accessories (to be ordered separately)Description Reference

    1 C/O contact block, latching RM1ZH21

    Electrical reset (1) (consumption: inrush, sealed: 500 VA) (fitted to the relay together with a latching contact block) Basic reference. Complete with code indicating control circuit voltage (2)

    ER1XA2p

    (1) The impulse duration must not exceed 2 seconds within 10 minute intervals.(2) Standard coil voltages for electrical reset:Volts 110 220

    50 Hz F M

    Overload relaysSingle-pole magnetic over current relays

    References - TeSys RM1D

    F533

    559.

    tif

    RM1XA0011

    DF5

    3356

    0.tif

    RM1XA1001+ER1XA2p

    RM1XA0011+RM1ZH21

    DF5

    3356

    1.tif

    Characteristics:page B11/50

    Dimensions:page B11/51

    Schemes:page B11/51

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA001http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA002http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA004http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA006http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA010http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA016http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA025http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA040http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA063http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA100http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA160http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA200http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA315http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA500http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA101http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1XA101http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM1ZH21http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=ER1XA2p

  • B11/17

    Ove

    rloa

    d re

    lays

    Protection units (without fault memory)Units with automatic reset with thermistor short-circuit detectionConnection Voltage Output

    contactReference

    Cage connectors a 50/60 Hz 115 V N/C LT3SE00F

    230 V N/C LT3SE00M

    c 24 V N/C LT3SE00BD

    Units with automatic reset with thermistor short-circuit detectionOn front panel: fault and voltage signalling indicator.

    Connection Voltage Output contact

    Reference

    Cage connectors a 50/60 Hz 115/230 V N/C + N/O LT3SA00M

    c 24/48 V N/C + N/O LT3SA00ED

    a 50/60 Hz or c

    24…230 V 2 C/O LT3SA00MW

    Protection units (with fault memory)Units with manual reset with thermistor short-circuit detection

    On front panel:- fault and voltage signalling indicator,- Test and Reset button.

    Connection Voltage Output contact

    Reference

    Cage connectors a 50/60 Hz 400 V N/C + N/O LT3SM00V

    24/48 V N/C + N/O LT3SM00E

    115/230 V N/C + N/O LT3SM00M

    c 24/48 V N/C + N/O LT3SM00ED

    a 50/60 Hz or c

    24…230 V 2 C/O LT3SM00MW

    (1) PTC: Positive Temperature Coefficient.

    Overload relaysThermistor protection units for use with PTC thermistor probes (1)

    References - TeSys LT3PF

    5262

    63-2

    4-M

    .tif

    LT3SM00M

    PF52

    6261

    -24-

    M.ti

    f

    LT3SE00M

    PF52

    6262

    -24-

    M.ti

    f

    LT3SA00M

    Characteristics:pages B11/52 to B11/55

    Dimensions:page B11/56

    Schemes:pages B11/56 and B11/57

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT3SE00Fhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT3SE00Mhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT3SE00BDhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT3SA00Mhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT3SA00EDhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT3SA00MWhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT3SM00Vhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT3SM00Ehttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT3SM00Mhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT3SM00EDhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT3SM00MW

  • B11/18

    Ove

    rloa

    d re

    lays

    PTC thermistor probes (1)Description Nominal

    Operating Temperature (NOT)

    Colour Sold in lots of

    Unit reference

    ° CIntegrated triple probes

    90 Green/green 10 DA1TT090

    110 Brown/brown 10 DA1TT110

    120 Grey/grey 10 DA1TT120

    130 Blue/blue 10 DA1TT130

    140 White/blue 10 DA1TT140

    150 Black/black 10 DA1TT150

    160 Blue/red 10 DA1TT160

    170 White/green 10 DA1TT170

    Surface probes 60 White/grey 10 DA1TS060

    70 White/brown 10 DA1TS070

    80 White/white 10 DA1TS080

    90 Green/green 10 DA1TS090

    100 Red/red 10 DA1TS100

    Accessories (to be ordered separately)Mounting accessoriesDescription Applicationi Sold in

    lots ofUnit reference

    Adapter For fixing on 4 rail DZ5 MB

    10 RHZ66

    Marking accessoriesClip-in markers(maximum of 5 per unit)

    Strips of 10 identical numbers (0 to 9)

    25 AB1Rp (2)

    Strips of 10 identical capital letters (A to Z)

    25 AB1Gp (2)

    (1) PTC: Positive Temperature Coefficient.(2) When ordering, replace the p in the reference with the number or letter required.

    Overload relaysThermistor protection units for use with PTC thermistor probes (1)

    References - TeSys LT381

    3383

    .tif

    DA1TTppp

    8133

    84.ti

    f

    DA1TSppp

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=DA1TT090http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=DA1TT110http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=DA1TT120http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=DA1TT130http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=DA1TT140http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=DA1TT150http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=DA1TT160http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=DA1TT170http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=DA1TS060http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=DA1TS070http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=DA1TS080http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=DA1TS090http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=DA1TS100http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RHZ66

  • B11/19

    Ove

    rloa

    d re

    lays

    References - TeSys LR97D, LT47

    LR97D electronic over current relaysRelay setting range

    Usable range (1)

    For use with contactor (2)

    Relay supply voltage

    Reference (3)

    A A0.3…1.5 0.3…1.3 LC1 D09…D38 a 200…240 V LR97D015M7

    a 100…120 V LR97D015F7c/a 24 V LR97D015Bc/a 48 V LR97D015E

    1.2…7 1.2…6 LC1 D09…D38 a 200…240 V LR97D07M7a 100…120 V LR97D07F7c/a 24 V LR97D07Bc/a 48 V LR97D07E

    5…25 5…21 LC1 D09…D38 a 200…240 V LR97D25M7a 100…120 V LR97D25F7c/a 24 V LR97D25Bc/a 48 V LR97D25E

    20…38 20…34 LC1 D25…D38 a 200…240 V LR97D38M7a 100…120 V LR97D38F7c/a 24 V LR97D38Bc/a 48 V LR97D38E

    LT47 electronic over current relaysRelay setting range

    Usable range (1)

    Relay supply voltage

    Reference

    A ALT47 relay with manual/electric reset

    0.5…6 0.5…5 a 200…240 V LT4706M7Sa 100…120 V LT4706F7Sc/a 24 V LT4706BSc/a 48 V LT4706ES

    3…30 3…25 a 200…240 V LT4730M7Sa 100…120 V LT4730F7Sc/a 24 V LT4730BSc/a 48 V LT4730ES

    5…60 5…50 a 200…240 V LT4760M7Sa 100…120 V LT4760F7Sc/a 24 V LT4760BSc/a 48 V LT4760ES

    LT47 relay with automatic reset0.5…6 0.5…5 a 200…240 V LT4706M7A

    a 100…120 V LT4706F7Ac/a 24 V LT4706BAc/a 48 V LT4706EA

    3…30 3…25 a 200…240 V LT4730M7Aa 100…120 V LT4730F7Ac/a 24 V LT4730BAc/a 48 V LT4730EA

    5…60 5…50 a 200…240 V LT4760M7Aa 100…120 V LT4760F7Ac/a 24 V LT4760BAc/a 48 V LT4760EA

    Accessories (to be ordered separately)Description For

    use withSold in lots of

    Unit reference

    Pre-wiring kits allowing connection of the LR97D relay N/C contact directly to the contactor

    LC1 D09…D18 10 LAD7C1LC1 D25…D38 10 LAD7C2

    Terminal block for clip-on mounting on 35 mm rail (AM1 DP200)

    LR97D 1 LAD7B106

    (1) To allow adjustment of the tripping sensitivity, see adjustment method (page B11/58).(2) Please see chapter B8.(3) If a pre-wiring kit is used, it is no longer possible to electrically wire signalling of tripped status.

    Overload relaysElectronic over current relays

    DF5

    2632

    9-40

    -M.ti

    f

    LR97D07pp

    DF5

    2633

    0-40

    -M.ti

    f

    LT4730ppp

    Presentation, description:page B11/58

    Curves:pages B11/59 and B11/60

    Characteristics:pages B11/60 and B11/61

    Dimensions, schemes: page B11/62

    http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR97D015M7http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR97D015F7http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR97D015Bhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR97D015Ehttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR97D07M7http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR97D07F7http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR97D07Bhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR97D07Ehttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR97D25M7http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR97D25F7http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR97D25Bhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR97D25Ehttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR97D38M7http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR97D38F7http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR97D38Bhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LR97D38Ehttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4706M7Shttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4706F7Shttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4706BShttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4706EShttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4730M7Shttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4730F7Shttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4730BShttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4730EShttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4760M7Shttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4760F7Shttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4760BShttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4760EShttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4706M7Ahttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4706F7Ahttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4706BAhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4706EAhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4730M7Ahttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4730F7Ahttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4730BAhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4730EAhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4760M7Ahttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4760F7Ahttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4760BAhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LT4760EAhttp://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD7C1http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD7C2http://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD7B106

  • B11/20

    Ove

    rloa

    d re

    lays

  • B11/21

    Ove

    rloa

    d re

    lays

    Technical Data for Designers

    TeSy

    s LR

    x, R

    M1,

    LT

    ContentsGeneral ..............................................................B11/22 to B11/27TeSys LRK - thermal overload protection: > characteristics ....................................................... B11/28 to B11/29 > dimensions and schemes ..................................................... B11/30TeSys LRD - thermal overload protection: > presentation and characteristics ........................... B11/31 to B11/34 > dimensions ............................................................ B11/35 to B11/37 > schemes ................................................................................ B11/37TeSys LR9D - electronic thermal overload protection: > presentation and characteristics ........................... B11/38 to B11/41 > dimensions ............................................................................ B11/42 > schemes ................................................................................ B11/43TeSys LR9F - electronic thermal overload protection: > presentation and characteristics ........................... B11/44 to B11/47 > dimensions ............................................................................ B11/48 > schemes ................................................................................ B11/49TeSys RM1 - single pole magnetic over current relays: > presentation and characteristics ........................................... B11/50 > dimensions and schemes ..................................................... B11/51TeSys LT3 - thermistor protection unit: > characteristics ....................................................... B11/52 to B11/55 > dimensions and schemes ..................................... B11/56 to B11/57TeSys LR97, LT47 - electronic over current relays: > presentation .......................................................................... B11/58 > curves ................................................................... B11/59 to B11/60 > characteristics ....................................................... B11/60 to B11/61 > dimensions and schemes ..................................................... B11/62

  • B11/22

    Ove

    rloa

    d re

    lays

    General

    Overload relays Motor and machine protection

    IntroductionExceeding the operating limits of an electric motor will lead, eventually, not only to destruction of the motor itself but also of the mechanisms it drives.

    This type of load can be the cause of electrical or mechanical faults. b Electrical faults: v overvoltage, voltage drop, imbalance and phase failure which cause variations in

    the current drawn, v short-circuits which can cause the current to reach levels capable of destroying

    the load.

    b Mechanical faults: v locked rotor, v brief or prolonged overload which leads to an increase in the current drawn by

    the motor, and therefore overheating. The cost of these faults must take into account loss of production, loss of raw materials, repair of the production tool, poor quality of production and delays in delivery.

    These faults can also have dramatic consequences on the safety of persons in direct or indirect contact with the motor.

    To prevent these faults, protection measures are necessary. They make it possible to isolate the equipment to be protected from the mains supply by measuring variations in electrical values (voltage, current, etc.).

    Each motor starter must therefore have:

    b short-circuit protection, to detect and break, as quickly as possible, abnormal currents generally greater than 10 times the rated current (In).

    b overload protection, to detect increases in current up to about 10 In and switch off the starter before overheating of the motor and conductors damages the insulation.

    This protection is provided by specific devices such as fuses, circuit breakers and thermal overload relays, or by more integrated devices offering several types of protection.

  • B11/23

    Ove

    rloa

    d re

    lays

    Causes, effects and consequences of various faults There are two types of fault:

    b Internal faults within the motor b External faults: these are located outside the electric motor but their

    consequences can lead to damage inside the motor.

    Faults Causes Effects Consequences on the motor and on the machine

    Short-circuit Contact between several phases, or between one phase and neutral or between several turns of the same phase.

    b Current peak b Electrodynamic forces on the

    conductors

    Destruction of windings

    Overvoltage b Lightning b Electrostatic discharge b Operation

    Dielectric breakdown in the windings Destruction of the windings due to loss of insulation

    Phase imbalance and phase failure

    b Opening of a phase b Single-phase load upstream of the

    motor b Short-circuit between the turns of

    the same winding

    b Reduction of usable torque, efficiency and speed

    b Increase in losses b Starting impossible if phase failure

    Overheating (1)

    High starting frequency

    b Failure of the automation system b Too many manual control

    operations b Numerous fault trips

    High stator and rotor temperature rise due to the frequent start current

    Overheating (1)Consequences on the process

    Voltage variations b Instability of the mains voltage b Connection of heavy loads

    b Reduction of usable torque b Increase in losses

    Overheating (1)

    Harmonics b Pollution of the mains supply by variable speed drives, inverters, etc...

    b Reduction of usable torque b Increase in losses

    Overheating (1)

    Long starting time

    b Resistive torque too high (load too heavy)

    b Voltage drop

    Increase in starting time Overheating (1)

    Jamming b Mechanical problem (crusher) b Seizures

    Overcurrent Overheating (1) Consequences on the process

    No-load running b Pump running empty b Mechanical break in drive to the

    load

    Drop in current drawn Consequences on the process

    Frequency fluctuations

    b Overload of a supply powered by limited independent sources

    b Faulty alternator speed regulator

    b Increase in losses b Interferes with synchronous devices

    (clock, recorder, ...)

    Overload b Increase in resistive torque b Voltage drop b Drop in power factor

    Increase in current consumption Overheating (1)

    Loss of machine excitation

    b Significant drop in excitation current

    b Break in rotor winding

    b Increase in active power b Drop in power factor

    Significant overheating of rotor and cage

    Phase-Earth fault b Accidental Phase-Earth contacts b Accidental Phase-machine casing

    contacts (casing connected to earth)

    b Overvoltage developed in the mains supply

    b Rise in earth potential (safety of persons)

    Consequences on safety of persons

    (1) Then, in the longer or shorter term, depending on the seriousness of the fault and/or its frequency, short-circuit and destruction of the windings.

    General

    Overload relays Motor and machine protection

  • B11/24

    Ove

    rloa

    d re

    lays

    General

    Overload relays Motor and machine protection

    Protection functions Short-circuit protectionGeneral

    A short-circuit results in a very rapid rise in current which can reach several hundred times the value of the operational current. The consequences of a short-circuit are dangerous to both equipment and persons. It is therefore imperative to use protection devices to detect the fault and very quickly break the circuit. Two types of protection are commonly used:

    b fuses (cutout) which break the circuit by melting, which then requires their replacement,

    b magnetic trip circuit breakers, often more simply called "magnetic circuit breakers", which only require re-setting to put them back into service.Short-circuit protection can also be built-into multifunction devices such as motor circuit breakers and contactor-breakers.

    The main characteristics of short-circuit protection devices are: b their breaking capacity: this is the highest prospective short-circuit current value

    that a protection device can break at a given voltage. b their making capacity: this is the highest current value that the protection device

    can make at its rated voltage in specified conditions. The making capacity is equal to k times the breaking capacity.

    Fuses (cutouts) Fuses provide individual phase protection (single-pole), with a high breaking capacity in a compact size:

    b mounted either in fuse carriers, b or in isolators, replacing the original links or shunt bars.

    For motor protection, aM type fuses are used. Their design characteristics allow them to conduct the high magnetising currents that occur when motors are switched on. They are therefore unsuitable for overload protection (unlike gG type fuses). This is why an overload relay must be included in the motor power supply circuit.

    Magnetic circuit breakers These circuit breakers protect installations against short-circuits, within the limit of their breaking capacity. Magnetic circuit breakers provide omnipole breaking as standard. For relatively low short-circuit currents, the operation of a circuit breaker is faster than that of fuses. This protection conforms to standard IEC 60947-2. The thermal and electrodymanic effects are also limited, therefore ensuring better protection of cables and equipment.

    LS1 D32fuse carrier

    DF5

    2617

    7-21

    -M.ti

    f

    DF5

    2617

    8-21

    -M.ti

    f

    GS2 N3switch disconnectors

    DF5

    2617

    9-22

    -M.ti

    f

    GV2 Lmagnetic circuit-breraker

    DF5

    2618

    0-22

    -M.ti

    f

    TeSys U LUB 12 starter with LUCApp control unit

  • B11/25

    Ove

    rloa

    d re

    lays

    Protection functionsOverload protectionGeneral

    An overload condition is the most frequently encountered fault. The symptoms are a rise in the current drawn by the motor and thermal effects. A rapid return to normal operating conditions is important.The actual operating conditions (ambient temperature, operating altitude and type of standard duty) are essential to determine the operating values of the motor (power, current) and to be able to select effective overload protection. These operational values are given by the motor manufacturer.

    According to the level required, protection can be provided by: b overload relays and thermal overload relays (bi-metallic or electronic type) which

    protect motors in the event of: v overload, by monitoring the current drawn by each phase, v phase imbalance or failure, by their differential mechanism. b relays with PTC thermistor probes (Positive Temperature Coefficient). b overtorque relays, b multifunction relays.

    Overload relaysThese relays protect motors against overload. They must allow the temporary overload that occurs on starting and must only trip if the starting time is abnormally long.The overload relay will be selected according to the length of the starting time (tripping class) and the motor rating.These relays have a thermal memory (except for certain electronic overload relays, indicated by their manufacturers) and can be connected:

    b either in series with the load, b or to current transformers placed in series with the load.

    Bi-metallic thermal overload relays Combined with a contactor, these relays protect the line and the equipment against small and prolonged overloads. They must be protected against strong overcurrent by a circuit breaker or fuses. These relays may be used on an a.c. or d.c. system and are generally:

    b 3-pole, b compensated, i.e. insensitive to ambient temperature variations, b with manual or automatic reset, b graduated with a "motor FLC" scale: allowing direct setting to the full load current

    as shown on the motor rating plate. They can also be sensitive to phase failure: this is known as 'differential'. This function conforms to standards IEC 60947-4-1 and 60947-6-2. This type of relay is extremely reliable and is a relatively low cost device.

    Electronic thermal overload relays Electronic thermal overload relays have the advantage of electronics which allow a more complex thermal image of the motor to be created.They can be combined with products having complementary functions, such as:

    b temperature sensing via PTC probes, b protection against jamming and overtorque, b protection against phase reversal, b earth fault protection, b protection against no-load running, b alarm function.

    General

    Overload relays Motor and machine protection

    DF5

    2618

    1-30

    -M.ti

    f

    LRD 02thermal overload relay

    PF52

    6182

    .tif

    LRD365thermal overload relay

    DF5

    2618

    3-21

    -M.ti

    f

    RM4 JA current measurement relay

    PF52

    6184

    .tif

    TeSys U starter with “thermal overload alarm” function module

  • B11/26

    Ove

    rloa

    d re

    lays

    General

    Overload relays Motor and machine protection

    Protection functions (continued) Overload protection (continued)Relays for use with PTC thermistor probes

    With direct sensing of the stator windings, these relays can be used to protect motors against:

    b overload, b a rise in ambient temperature, b a ventilation circuit fault, b a high starting frequency, b mechanical shocks, etc.

    Overload (or overtorque) relays These relays protect the drive line in the event of a locked rotor, seizure or mechanical shocks. This is an additional protection.Unlike thermal overload relays, these relays do not have a thermal memory. They have definite time characteristics (adjustable current threshold and time delay).The overtorque relay can be used as overload protection for motors with long starting times or very frequent starting (for example, lifting hoists).

    Multifunction relays b Overcurrent relays are limited when it is necessary to take into account problems

    associated with voltage, temperature or special applications. New production or maintenance management needs have prompted manufacturers to offer products which provide not only adaptable protection, but also complete management of the motor and its load. They incorporate:

    b current and voltage sensors (TeSys T controllers), b hybrid analog and digital electronic technology, b the use of communication buses for data exchange and control, b powerful motor modelling algorithms, b integrated application programs whose parameters can be set.

    These products make it possible to reduce installation and operating costs by reducing maintenance and downtime.

    TeSys U starters:The multifunction relay is incorporated in the motor starter. This solution is very compact with reduced wiring. It is limited to 32 A.

    TeSys U controllers: The multifunction relay is separate from the power line and reuses the function blocks from the TeSys U solution. It can be used in conjunction with a contactor up to 810 A.

    TeSys T controllers: The multifunction relay is separate from the power line and incorporates inputs and outputs. It can be used in conjunction with a contactor up to 810 A.

    DF5

    2618

    5-