3 Contactor Relays Contents N... Contactor Relays, a.c. Operated Description ............................................................................................................................. 3/2 Ordering Details ..................................................................................................................... 3/3 Main Accessories ................................................................................................................... 3/4 NE... Contactor Relays, d.c. Operated with Double-Winding coil Description ............................................................................................................................. 3/6 Ordering Details ..................................................................................................................... 3/7 KC... and TKC... Contactor Relays, d.c. Operated with Solid Magnetic Circuit Description ............................................................................................................................. 3/8 Ordering Details ..................................................................................................................... 3/9 Technical Data ................................................................................................................... 3/10 Fitting Details for Main Accessories ................................................................................ 3/15 Additional Information Accessories and Coils .................................................................................................. Section 4 General Technical Data and Approvals ....................................................................... Section 7 Terminal Marking and Positioning ................................................................................ Section 8 Dimensions .................................................................................................................. Section 9 3/1 1SBC100122C0201

Upload: samiran-biswas

Post on 14-Oct-2014

110 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Control Contactor

3

Contactor Relays

Contents

N... Contactor Relays, a.c. Operated

Description ............................................................................................................................. 3/2

Ordering Details ..................................................................................................................... 3/3

Main Accessories ................................................................................................................... 3/4

NE... Contactor Relays, d.c. Operated with Double-Winding coil

Description ............................................................................................................................. 3/6

Ordering Details ..................................................................................................................... 3/7

KC... and TKC... Contactor Relays, d.c. Operated with Solid Magnetic Circuit

Description ............................................................................................................................. 3/8

Ordering Details ..................................................................................................................... 3/9

Technical Data ................................................................................................................... 3/10

Fitting Details for Main Accessories ................................................................................ 3/15

Additional Information

Accessories and Coils .................................................................................................. Section 4

General Technical Data and Approvals ....................................................................... Section 7

Terminal Marking and Positioning ................................................................................ Section 8

Dimensions .................................................................................................................. Section 9

3/11SBC100122C0201

Page 2: Control Contactor

3/2 Low Voltage Products1SBC100122C0201

N40E

14NO 24NO 34NO 44NO

13NO 23NO 33NO 43NO

5- 6- 7- 8-

5- 6- 7- 8-

A 1 A 2

2 2 0 - 2 3 0 V 5 0 H z2 3 0 - 2 4 0 V 6 0 H z

R 8 0

E18

72D

N... Contactor Relaysa.c. Operated

ApplicationN... contactor relays are used for switching auxiliary circuits and control circuits.

Description● Poles:

– 1-stack contactor relays: 4-pole.Auxiliary contacts for safety circuits: ☞ page 7/4.

– 2-stack contactor relays: 8-pole, with mechanically linked contact elements.The width of 8-pole devices is identical to that of 4-pole devices; only the depth is increased.

● Control circuit: a.c. operated with laminated magnet circuit.

● Accessories: a wide range of accessories is available (☞ next pages and section 4).

Variant ☞ next pages in this section

● d.c. operated: NE... contactor relays.

Terminal screws: Pozidriv (+,-) No. 2.

Stops for attaching front-mounted acces-sories.

Location of function marker.

Terminal marking according toIEC 60947-5-1, and EN 50011.

Clear marking of coil voltages andfrequencies.

Location of surge suppressors.

Holes for screw fixing (screws not supplied).Distance between holes according toEN 50002.

Location of side-mounted accessories(on right or left hand side).

Quick fixing on mounting rail accordingto IEC 715 and EN 50022 standards:35 x 7.5 mm or 35 x 15 mm.

Terminals delivered in open position withcaptive screws.Screwdriver guidance for all terminals.Degree of protection of terminals accordingto IEC 60947-1: IP 20 for all terminal.

Page 3: Control Contactor

3

Low Voltage Products 3/31SBC100122C0201

N 40 E

SB

7362

C2

N 44 E

SB

7586

C4

Ordering Details

Number of contacts Type Order code Weight1st stack 2nd stack kg

state coil voltage state coil voltage code Packing

(see table below) (see table below) 1 piece

4-pole, 1-stack

2 2 – – – – N 22 E (1) 1SBH 14 1001 R 22 0.340

3 1 – – – – N 31 E (1) 1SBH 14 1001 R 31 0.340

4 – – – – – N 40 E 1SBH 14 1001 R 40 0.340

(1) In mounting position 5, (☞ page 3/13) max. 2 x N.C. front-mounted contacts only are acceptable. The CAL 5-11 side-mounted blocks offeradditional N.C. contacts.

8-pole, 2-stack

4 – – 4 – – N 44 E 1SBH 14 1001 R 44 0.400

4 – 1 3 – – N 53 E 1SBH 14 1001 R 53 0.400

4 – 2 2 – – N 62 E 1SBH 14 1001 R 62 0.400

4 – 3 1 – – N 71 E 1SBH 14 1001 R 71 0.400

4 – 4 – – – N 80 E 1SBH 14 1001 R 80 0.400

with overlapping of lagging / leading contacts (☞ section 8)

3 1 – 2 1 1 N 33/11 1SBH 14 1001 R 39 0.400

4 – 1 1 1 1 N 51/11 1SBH 14 1001 R 59 0.400

Coil voltages and codes

Voltage Voltage Code V - 50Hz V - 60Hz

24 24 8 148 48 8 3110 110 ... 120 8 4220 ... 230 230 ... 240 8 0230 ... 240 240 ... 260 8 8380 ... 400 400 ... 415 8 5400 ... 415 415 ... 440 8 6

☞ Other voltages: page 0/1.

N... Contactor Relaysa.c. Operated

>> Auxiliary Contacts for Safety Circuits ................ page 7/4 >> Main Accessories ................................................. page 3/4>> General - Approvals ............................................. section 7 >> Technical Data .................................................... page 3/10>> Terminal Marking and Positioning ...................... section 8 >> Dimensions ........................................................... section 9

Page 4: Control Contactor

3/4 Low Voltage Products1SBC100122C0201

E02

73D

1

RV 5/..

VE 5-1

N 40 E

CAL 5-11

CA 5-10

CA 5-22 N

TP 40 DA

Fitting DetailsMany configurations of accessories are possible depending on whether these are front-mounted or side-mounted.

Contactor Front mounted accessories Side mounted accessoriestype Auxiliary contact Auxiliary contact Pneumatic timer Auxiliary contact Interlock unit

1-pole CA 5-.. 4-pole CA 5-.. TP .. A 2-pole CAL 5-11 VM 5-.. or VE 5-..

N 22 E (1)1 x VM 5-1 / VE 5-1

N 31 E (1) 1 to 4 x CA 5-.. or 1 x CA 5-.. (4-pole) or 1 x TP .. A + 1 to 2 x CAL 5-11 or+ 1 x CAL 5-11

N 40 E

N 44 EN 53 E

1 x VM 5-1 / VE 5-1N 62 E _ _ _ 1 to 2 x CAL 5-11 or

+ 1 x CAL 5-11N 71 EN 80 E

(1) In mounting position 5 (☞ page 3/13), max. 2 x N.C. front-mounted auxiliary contacts only are acceptable. The CAL 5-11 side-mounted blocks offer additional N.C. contacts.For N 22 E and N 31 E + TP..DA in mounting position 5, please consult us.

Contactor relay and main accessoriesOther accessories: ☞ section 4.

N... Contactor RelaysMain Accessories

{

{

Page 5: Control Contactor

3

Low Voltage Products 3/51SBC100122C0201

SB

7282

C2

SB

7400

C1

SB

7389

C1

RV 5/50 RC 5-1/50

VE 5-1

TP 40 DA

SB

7589

C3

CAL 5-11 CA 5-10

SB

8099

C2

SB

7375

C2

N... Contactor RelaysMain Accessories

Ordering DetailsAuxiliary Contact Blocks

Mounting on Positioning Contacts Type Order Code Packing Weightcontactor piece kgrelays 1 piece

N... Front face 1 – CA 5-10 1SBN 01 0010 R1010 10 0.014– 1 CA 5-01 1SBN 01 0010 R1001 10 0.0144 – CA 5-40 N 1SBN 01 0040 R1240 2 0.0602 2 CA 5-22 N 1SBN 01 0040 R1222 2 0.060– 4 CA 5-04 N 1SBN 01 0040 R1204 2 0.060

Side 1 1 CAL 5-11 1SBN 01 0020 R1011 2 0.050

Pneumatic Timers

Mounting on Timing range Contacts Type Order Code Packing Weightcontactor piece kgrelays 1 piece

N... Direct 0.1 ... 40 s 1 1 TP 40 DA 1SBN 02 0300 R1000 1 0.070Direct 10 ... 180 s 1 1 TP 180 DA 1SBN 02 0300 R1001 1 0.070Inverse 0.1 ... 40 s 1 1 TP 40 IA 1SBN 02 0301 R1000 1 0.070Inverse 10 ... 180 s 1 1 TP 180 IA 1SBN 02 0301 R1001 1 0.070

Interlocks

Mounting on Feature Contacts Type Order Code Packing Weightcontactor piece kgrelays 1 piece

N... Mech. / electrical – 2 VE 5-1 1SBN 03 0110 R1000 1 0.076

Mechanical – – VM 5-1 1SBN 03 0100 R1000 1 0.066

Surge Suppressors

Mounting on Feature Voltage range Type Order Code Packing Weightcontactor piece kgrelays 1 piece

N... Varistor 24 ... 50 V a.c./d.c. RV 5/50 1SBN 05 0010 R1000 2 0.01550 ... 133 V a.c./d.c. RV 5/133 1SBN 05 0010 R1001 2 0.015110 ... 250 V a.c./d.c. RV 5/250 1SBN 05 0010 R1002 2 0.015250 ... 440 V a.c./d.c. RV 5/440 1SBN 05 0010 R1003 2 0.015

RC 24 ... 50 V a.c. RC 5-1/50 1SBN 05 0100 R1000 2 0.01250 ... 133 V a.c. RC 5-1/133 1SBN 05 0100 R1001 2 0.012110 ... 250 V a.c. RC 5-1/250 1SBN 05 0100 R1002 2 0.012250 ... 440 V a.c. RC 5-1/440 1SBN 05 0100 R1003 2 0.012

Other accessoriesA wide range of accessories is available: ☞ section 4– various auxiliary contact blocks for specific controls and use,– interface relays,– fuse holder blocks,– function marker.

>> Technical Data of Accessories ........................... section 4 >> Dimensions ........................................................... section 9

Page 6: Control Contactor

3/6 Low Voltage Products1SBC100122C0201

E18

74D

NE12E

14NO 22NC 32NC 86NC

13NO 21NC 31NC 85NC

4- 5- 6- 7-

4- 5- 6- 7-

A 1 A 2

2 4 V D CR 8 1

NE... Contactor Relaysd.c. Operated with Double-Winding Coil

ApplicationNE... contactor relays are used for switching auxiliary circuits and control circuits.

Description● 3-pole 1-stack version

● Control circuit: laminated magnet circuit and double-winding coil fed from d.c. supply via an insertion contact mounted on the device

● Accessories: a wide range of accessories is available (☞ section 4).

Auxiliary contacts for safety circuits: ☞ page 7/4.

NE... contactor relays specific design (☞ page 3/2 for general design)

● Built-in lagging contact for insertion of the second winding

Uc < 110 V d.c.

* Addition of RT 5 or RV 5 surge suppressor, if required.Please order separate (☞ page 3/5).

Uc > 110 V d.c.

* RV 5 surge supressor fitted as standard (RT 5 type on request).

A1Varistor

A2

A3

B2 = Holding

Uc (d.c.)

B1 = Pull-in

E15

95D

G

USurge

suppressor *

A1

Surge suppressor *

A2

A3

B2 = Holding

Uc (d.c.)

B1 = Pull-in

E19

00D

G

Page 7: Control Contactor

3

Low Voltage Products 3/71SBC100122C0201

NE 12 E

SB

8063

C3

NE... Contactor Relaysd.c. Operated with Double-Winding Coil

Ordering Details

Contacts Type Order code Weightkg

state coil voltage state coil voltage code Packing

(see table below) (see table below) 1 piece

1 2 NE 12 E 1SBH 14 9001 R 12 0.340

2 1 NE 21 E 1SBH 14 9001 R 21 0.340

3 0 NE 30 E 1SBH 14 9001 R 30 0.340

Note: – If extra auxiliary contact blocks are required, use CA5-.. or CC5-.. single pole add-on auxiliary contact blocks. (☞ section 4).– In mounting position 5 (☞ page 3/13), max. 2 x N.C. front mounted contact only are acceptable. The CAL 5-11 side-mounted blocks

offer additional N.C. contacts.

Coil voltages and codes

Voltage Code V d.c

12 8 024 8 142 8 248 8 350 2 160 8 475 8 5110 8 6125 8 7220 8 8240 8 9250 3 8

>> Auxiliary Contacts for Safety Circuits ................ page 7/4 >> Main Accessories ................................................. page 3/4>> General - Approvals ............................................. section 7 >> Technical Data .................................................... page 3/10>> Terminal Marking and Positioning ...................... section 8 >> Dimensions ........................................................... section 9

Page 8: Control Contactor

3/8 Low Voltage Products1SBC100122C0201

KC 40 E

E18

75D

13

A1

23 33 43

5-

V DC24

6- 7- 8-

14 24 34 445-

6-7-

8-

KC... and TKC... Contactor Relaysd.c. Operated with Solid Magnetic Circuit

ApplicationKC... and TKC... contactor relays are used for switching auxiliary circuits and control circuits.

The TKC... contactor relays are designed to operate in control circuits with large voltage variations. Example: battery supply.

DescriptionKC... series: d.c. operated contactor relays.TKC... series: d.c. operated contactor relays with large coil voltage range.

● Poles:– 1-stack contactor relays: 4-pole.

Auxiliary contacts for safety circuits: ☞ page 7/4.

– 2-stack contactor relays: 8-pole, with mechanically linked contact elements.The width of 8-pole devices is identical to that of 4-pole devices, only the depth is increased.

● Control circuit: d.c. operated with solid magnetic circuit.

● Accessories: a wide range of accessories is available (☞ section 4).

Dove tail anchoring for surge suppressorassembly.

Clear marking of coil d.c. voltage.

Terminal marking according toIEC 60947-5-1 and EN 50011 standards.

Terminals delivered in open position withcaptive screws.Screwdriver guidance for all terminals.Degree of protection of terminalsaccording to IEC 60947-1:– Pole terminals: IP 10,– Coil terminals: IP 20.

Location of function marker.

Quick fixing on mounting rail according toIEC 715 and EN 50022 standards:35 x 7.5 mm or 35 x 15 mm.

Terminal screw: M 3.5 Pozidriv (+,-) Nr 2.

Stops for attaching front-mountedaccessories.

Holes for screw fixing (screws not supplied).Distance between holes according toEN 50002.

Page 9: Control Contactor

3

Low Voltage Products 3/91SBC100122C0201

KC 22 E

SB

8533

C2

TKC 22 E

SB

8644

C2

KC... and TKC... Contactor Relaysd.c. Operated with Solid Magnetic Circuit

Ordering Details: KC...

Auxiliary contacts Type Order code Weight1st stack 2nd stack kg

state coil voltage state coil voltage code . . Packing

(see opposite table) (see opposite table) 1 piece

4-pole, 1-stack

2 2 – – – – KC 22 E FPH 141 3001 R 22 0.540

3 1 – – – – KC 31 E FPH 141 3001 R 31 0.540

4 – – – – – KC 40 E FPH 141 3001 R 40 0.540

8-pole, 2-stack

4 – – 4 – – KC 44 E FPH 142 3001 R 44 0.600

4 – 2 2 – – KC 62 E FPH 142 3001 R 62 0.600

Ordering Details: TKC... (contactor relays with large coil voltage range)

Number of contacts Type Order code Weight1st stack 2nd stack kg

state coil voltage state coil voltage code . . Packing

(see opposite table) (see opposite table) 1 piece

4-pole, 1-stack

2 2 – – – – TKC 22 E FPH 141 3061 R 22 0.540

3 1 – – – – TKC 31 E FPH 141 3061 R 31 0.540

4 – – – – – TKC 40 E FPH 141 3061 R 40 0.540

8-pole, 2-stack

4 – – 4 – – TKC 44 E FPH 142 3061 R 44 0.600

4 – 2 2 – – TKC 62 E FPH 142 3061 R 62 0.600

Coil voltages and codes: KC...

Voltage - Uc Code V d.c R ..

12 0 .. 724 0 .. 142 0 .. 248 1 .. 650 1 .. 760 0 .. 375 2 .. 2110 0 .. 4125 2 .. 7220 0 .. 5240 3 .. 3250 3 .. 4

Coil voltages and codes: TKC...

Voltage - Uc Code V d.c R ..

17 ... 32 5 .. 125 ... 45 5 .. 236 ... 65 5 .. 442 ... 78 5 .. 850 ... 90 5 .. 577 ... 143 6 .. 290 ... 150 6 .. 6152 ... 264 6 .. 8

Other voltages: please consult us.

Voltage tolerances (-15 % and+10 %) included in the Uc min.and Uc max. values for theTKC... contactor relays.

>> Auxiliary contacts for safety circuits .................. page 7/4 >> Main Accessories ................................................. page 3/4>> General - Approvals ............................................. section 7 >> Technical Data .................................................... page 3/10>> Terminal Marking and Positioning ...................... section 8 >> Dimensions ........................................................... section 9

!

Page 10: Control Contactor

3/10 Low Voltage Products1SBC100122C0201

B2A A B1

C2

C1

E02

02D

1

ABB

B2A A B1

C2

C1

E02

02D

1

ABB

General Technical Data for N... and NE... Contactor Relays

Contactor relay types N... NE...

Rated insulation voltage Ui

according to IEC 60947-4-1 V 690according to UL/CSA V 600

Rated impulse withstand voltage Uimp. kV 8

Standards Devices complying with international standards IEC 60947-5-1 / 60947-4-1and European standards EN 60947-5-1 / 60947-4-1

Certifications - Approvals ☞ section 7

Air temperature close to contactor ☞ "Conditions for use", page 3/13, for control voltage limits, and authorized mounting positions– for operation in free air °C -40 to +70– for storage °C -60 to +80

Climatic withstand acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II

Operating altitude m < 3000

Shock withstandacc. IEC 60068-2-27 and EN 60068-2-27Mounting position 1 (☞ page 3/13) 1/2 sinusoidal shock for 11 ms: no change in contact position

Shock directionA, C1, C2: 20 gB1: 5 gB2: 15 g

General Technical Data for KC... and TKC... Contactor Relays

Contactor relay types KC... TKC...

Rated insulation voltage Ui

according to IEC 60947-4-1 V 690according to UL/CSA V 600

Rated impulse withstand voltage Uimp. kV 8

Standards Devices complying with international standards IEC 60947-5-1 / 60947-4-1and European standards EN 60947-5-1 / 60947-4-1

Certifications - Approvals ☞ section 7

Air temperature close to contactor ☞ "Conditions for use", page 3/13, for control voltage limits, and authorized mounting positions– for operation in free air °C -40 to +70 -40 to +55– for storage °C -60 to +80

Climatic withstand acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II

Operating altitude m < 3000

Shock withstandacc. IEC 60068-2-27 and EN 60068-2-27Mounting position 1 (☞ page 3/13) 1/2 sinusoidal shock for 11 ms: no change in contact position

Shock Shock Making Breakingdirection direction position positionA, C1, C2 20 g A 15 g 10 gB1 5 g B1 10 g 5 g (1)

B2 15 g B2 10 g 6 g (2)

C1 10 g 4 gC2 10 g 4 g

Exceptions: (1) 4 g for TKC 22, 3 g for TKC 62(2) 5 g for TKC 31, 3 g for TKC 62Consult us for TKC 44

N..., NE..., KC... and TKC... Contactor RelaysTechnical Data

Page 11: Control Contactor

3

Low Voltage Products 3/111SBC100122C0201

Contact Utilization Characteristics

Contactor relay types N... NE... KC... TKC...

Rated operational voltage Ue max. V 690

Rated frequency limits Hz 25 ... 400

Conventional free-air thermal current Ith

according to IEC 60947-5-1,open contactors θ ≤ 40 °C A 16 10

Rated operational current Ie / AC-15according to IEC 60947-5-1

24-127 V 50/60 Hz A 6230-240 V 50/60 Hz A 4400-415 V 50/60 Hz A 3

500 V 50/60 Hz A 2690 V 50/60 Hz A 2

Rated operational current Ie / DC-13according to IEC 60947-5-1

24 V d.c. A / W 6 / 14448 V d.c. A / W 2.8 / 13472 V d.c. A / W 1 / 72

125 V d.c. A / W 0.55 / 69250 V d.c. A / W 0.3 / 75

Rated making capacityaccording to IEC 60947-5-1 10 x Ie / AC-15

Rated breaking capacityaccording to IEC 60947-5-1 10 x Ie / AC-15

Short-circuit protectionUe < 500 V a.c. - gG type fuse A 10

Rated short-time withstand current Icw

at 40 °C ambient temp., in free air,from a cold state 1.0 s A 100 50

0.1 s A 140 100

Minimum switching capacitywith failure rate bellow 10-6 17 V / 5 mA 24 V / 5 mA

Heat dissipation per pole at 6 A W 0.10 0.15

Non-overlapping time betweenN.O. and N.C. contacts ms > 2

Insulation resistance at 500 V d.c.after durability test MOhm 5

Max. electric switching frequency cycles/h 1200

Electrical durability ☞ page 4/35

Mechanical durability– millions of operating cycles > 20 30– max. mechanical switching frequency cycles/h 6000

N..., NE..., KC... and TKC... Contactor RelaysTechnical Data

Page 12: Control Contactor

3/12 Low Voltage Products1SBC100122C0201

Magnet System Characteristics for N... Contactor Relays

Contactor relay types N...

Rated control circuit voltage Uc

50/60 Hz V 20 ... 690

Coil operating limits θ < 55 °Cacc. to IEC 60947-5-1: 0.85 ... 1.1 x Uc

Drop-out voltage in % of Uc 40 ... 65 %

Coil consumptionAverage pull-in value 50 Hz VA 70

60 Hz VA 8050/60 Hz (1) VA / VA 74 / 70

Average holding value 50 Hz VA / W 8 / 260 Hz VA / W 8 / 2

50/60 Hz (1) VA / W 8 / 2

Operating timebetween coil energization and:– N.O. contact closing ms 10 ... 26– N.C. contact opening ms 7 ... 21between coil de-energization and:– N.O. contact opening ms 4 ... 11– N.C. contact closing ms 9 ... 16

(1) 50/60 Hz coils: voltage codes 8 0 to 8 8. ☞ page 0/1.

Magnet System Characteristics for NE..., KC..., and TKC... Contactor Relays

Contactor relay types NE... KC... TKC...

Rated control circuit voltage Uc V d.c. 12 ... 250 24 ... 240

Coil operating limits θ < 55 °Cacc. to IEC 60947-5-1: 0.85 ... 1.1 x Uc Uc min. ... Uc max.

Drop-out voltage in % of Uc 10 ... 30 % 9 ... 25 % of Uc max.

Coil consumption (3)

– pull-in value W 90 7 9– holding value W 2 7 9

Coil time constant– open L/R ms 2 40– closed L/R ms 9 90

Operating timebetween coil energization and:– N.O. contact closing ms 10 ... 16 50 ... 75 50 ... 75– N.C. contact opening ms 8 ... 12 45 ... 70 45 ... 70between coil de-energization and:– N.O. contact opening ms 5 ... 14 (1) (2) 15 ... 30 (1) 15 ... 30 (1)

– N.C. contact closing ms 11 ... 17 (1) (2) 17 ... 32 (1) 17 ... 32 (1)

(1) The use of surge suppressors increases the opening time on a scale of 1.1 to 1.5 for a varistor suppressor and on a scale of 4 to 8 for a diode.(2) NE Contactor Relays, and Uc > 110 V d.c.: table values for contactor relays with RV5 surge suppressors (factory mounted).(3) Average values for NE... and KC... contactor relays, at Uc max. and θ = 20 °C for TKC types.

Note: For the influence of the length of conductors used in control circuit, use the curves in pages 2/90 and 2/91

N..., NE..., KC... and TKC... Contactor RelaysTechnical Data

Page 13: Control Contactor

3

Low Voltage Products 3/131SBC100122C0201

Position 1

Position 3

Position 4

Position 2

E02

00D

5

Position 5

Position 1 ± 30°

-30° +30°

Position 6

ABB

ABB

AB

B

AB

B

Mounting Characteristics

Contactor relay types N... NE... KC... TKC...

Mounting positions ☞ "Conditions for use"

Mounting distancesNo mounting distance required between contactors ☞ "Dimension drawings" (section 9)

for distances required between contactors

Fixingon DIN rail 35 x 7.5 mmaccording to IEC 715 and EN 50022 35 x 15 mm

by screws (not supplied) 2 x M4

Conditions for UseSustainable utilization conditions for contactors involving at the same time the Mounting position, Ambient temperature and Control Voltage operatinglimits are summarized in the table below.

Contactor relays Mounting position Ambient temperature Control voltage

N..., NE...1, 1 + 30°, 2, 3, 4, 5

< 55 °C 0.85 ... 1.1 x Uc

55 ... 70 °C Uc

6< 55 °C 0.95 ... 1.1 x Uc

> 55 °C unauthorized –

KC...1, 3, 4, 5

< 55 °C 0.85 ... 1.1 x Uc

55 ... 70 °C Uc

1 + 30°, 2< 55 °C 0.95 ... 1.1 x Uc

55 ... 70 °C Uc

6< 55 °C 0.95 ... 1.1 x Uc

> 55 °C unauthorized –

TKC...1, 1 + 30°, 3, 4

< 55 °C Uc min. ... Uc max.

> 55 °C unauthorized –

2, 5, 6 unauthorized – –

Mounting Positions (see the above table for authorized positions)

N..., NE..., KC... and TKC... Contactor RelaysTechnical Data

Page 14: Control Contactor

3/14 Low Voltage Products1SBC100122C0201

Ll

N..., NE..., KC... and TKC... Contactor RelaysTechnical Data

Connecting Characteristics

Contactor relay types N... NE... KC... TKC...

Terminals

with cable clamp

Connecting capacity (min. ... max.)

(Poles and coil terminals)

Rigid solid 1 x mm2 1 ... 42 x mm2 1 ... 4

Flexible with cable end 1 x mm2 0.75 ... 2.5 1 ... 2.52 x mm2 0.75 ... 2.5

Lugs L mm ≤ 8l mm > 3.7

Degree of protection Protection against direct contact acc. to VDE 0106 - Part. 100acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529

– Pole terminals IP 20 IP 10– Coil terminals IP 20

Screw terminals– Pole terminals M 3.5 (+, -) pozidriv 2 screws with cable clamp– Coil terminals M 3.5 (+, -) pozidriv 2 screws with cable clamp

Tightening torquePole terminals– recommended Nm / lb.in 1.00 / 9– max. Nm 1.20

Coil terminals– recommended Nm / lb.in 1.00 / 9– max. Nm 1.20

Terminal marking and positioning ☞ section 8

Page 15: Control Contactor

3

Low Voltage Products 3/151SBC100122C0201

N..., NE..., KC... and TKC... Contactor RelaysFitting Details for Main Accessories

N... and NE... Contactor RelaysBasic unit Front-mounted accessories Side-mounted accessories

Built-incontacts1st 2nd

stack stack

Auxiliary contact Auxiliary contact Pneumatic timer Auxiliary contact Interlock unitTypes 1-pole CA 5-.. 4-pole CA 5-.. TP .. A 2-pole CAL 5-11 VM 5-.. or VE 5-..

N 22 E (1) 2 2 – –N 31 E (1) 3 1 – –N 40 E 4 – – –

1 to 4 x CA 5-.. or 1 x CA 5-.. (4-pole) or 1 x TP .. A + 1 to 2 x CAL 5-11 or1 x VM 5-1 or VE 5-1

NE 12 E 1 2 – – + 1 x CAL 5-11NE 21 E 2 1 – –NE 30 E 3 – – –

N 44 E 4 – – 4N 53 E 4 – 1 3

– – – 1 to 2 x CAL 5-11 or1 x VM 5-1 or VE 5-1

N 62 E 4 – 2 2 + 1 x CAL 5-11N 71 E 4 – 3 1N 80 E 4 – 4 –

(1) In mounting position 5 (☞ page 3/13), max. 2 x N.C. front-mounted auxiliary contacts only are acceptable. The CAL 5-11 side-mounted blocks offer additional N.C. contacts.For N 22 E and N 31 E + TP..DA in mounting position 5, please consult us.

KC... Contactor RelaysBasic unit Front-mounted accessories (1)

Built-incontacts1st 2nd

stack stack

Auxiliary contact Auxiliary contact Pneumatic timer Interlocking unit Add-on auxiliary contactTypes 1-pole CA 5-.. 4-pole CA 5-.. TP .. A VBC 30 CA 5-.. for each contactor

KC 22 E (2) 2 2 – – 1 to 4 x CA 5-.. or 1 x CA 5-.. (4-pole) – or 1 x VBC 30 + 1 to 2 x CA 5-.. (1-pole)

KC 31 E 3 1 – –1 to 4 x CA 5-.. or 1 x CA 5-.. (4-pole) or 1 x TP.. A or 1 x VBC 30 + 1 to 2 x CA 5-.. (1-pole)

KC 40 E 4 – – –

KC 44 E 4 – – 4– – – – –

KC 62 E 4 – 2 2

(1) In mounting position 5 (☞ page 3/13) max. 2 x N.C. auxiliary contacts only are acceptable, and use only the TP .. DA pneumatic timer (TP .. IA unauthorized).(2) Whatever the mounting position max. 2 x N.C. auxiliary contacts only are acceptable. In mounting position 1 ±30°, front-mounted accessories unauthorized.

TKC... Contactor RelaysBasic unit Front-mounted accessories

Built-incontacts1st 2nd

stack stack

Auxiliary contact Auxiliary contact Pneumatic timer Interlocking unit Add-on auxiliary contactTypes 1-pole CA 5-.. 4-pole CA 5-.. TP .. A VBC 30 CA 5-.. for each contactor

TKC 22 E (1) 2 2 – – 1 to 4 x CA 5-.. or 1 x CA 5-.. (4-pole) – or 1 x VBC 30 + 1 to 2 x CA 5-.. (1-pole)

TKC 31 E (2) 3 1 – –1 to 4 x CA 5-.. or 1 x CA 5-.. (4-pole) – or 1 x VBC 30 + 1 to 2 x CA 5-.. (1-pole)

TKC 40 E (3) 4 – – –

TKC 44 E 4 – – 4– – – – –

TKC 62 E 4 – 2 2

(1) Whatever the mounting position the N.C. auxiliary contacts are unauthorized.(2) In mounting position 1, 3 or 4 (☞ page 3/13) max. 2 x N.C. auxiliary contacts only are acceptable. In mounting position 1 ±30°, front-mounted accessories unauthorized.(3) In mounting position 1, 3 or 4 (☞ page 3/13) max. 1 x N.C. auxiliary contact only is acceptable. In mounting position 1 ±30°, front-mounted accessories unauthorized.

>> Auxiliary Contacts for Safety Circuits ...................................................................................................................................................................................................................... page 7/4