37 Control & Monitoring Relays Introduction & Selection Guide United Kingdom: Tel: +44 020 8546 4283 Fax: +44 020 8547 3628 E-mail: [email protected] Germany: Tel: +49 208 46954-0 Fax: +49 208 46954-50 E-mail: [email protected] Export: Tel: +45 46 74 00 00 Fax: +45 46 75 73 36 E-mail: [email protected] MCU-10 DV/AV DC/AC MCU-10 MCU-10 P/N/T MCU-10 J/K/S/R MCU-10 U MXP-10 MXC-30 MXV-10 MXC-20 MXV-20 MXV-30 MXC-10 MCP-10 INTRO... MXP-20 MXL-10 MXT-10 47.98 INTRODUCTION The Brodersen monitoring relays are high quality products incorporating up-to-date circuit design together with modern, efficient components to en- sure a long trouble free life in a wide range of operating conditions. Power consumption and, thus, heat dissipation are minimal and the entire range has been de-signed and tested to the latest requirements for EMC immunity and emission. A wide range of commonly used standards of volt- age, current, temperature and process signals can be monitored by the Brodersen relays. The Brodersen Control and monitoring relays are produced in two design categories; installation and industrial design. The installation design is based on DIN rail or 11 pole plug-in mounting and are designed to fit into installation enclosures. The industrial design is in 22,5mm housing with the terminals placed to optimize installation time in industrial applications. MCU-10 Digital control relay MCP-10 Phase monitoring relay MXC-10 AC/DC current relay AC/DC Voltage AC/DC Current 3-phase Voltage 3-phase Monitoring Temperature RTDs Temperature Thermocouples Liquid Level, Conductive Standard Process Signal Output Relay Analogue Output, Setpoint Analogue Output, Measuring LCD Display LED Indication Setpoints Hysteretis Delay 36mm Installation Design for Din Rail or 11-Pole Plug-In Mounting Phase monitoring relay Digital voltage relay Digital current relay Digital thermostat relay Digital thermostat relay Digital process signal relay AC/DC voltage relay AC/DC voltage relay AC/DC current relay AC/DC current relay AC/DC current relay 3 phase voltage relay Phase monitoring relay Phase monitoring relay Liquid level relay Thermostat relay MCP-10 MCU-10 DV/AV MCU-10 DC/AC MCU-10 P/N/T MCU-10 J/K/S/R MCU-10 U MXV-10 MXV-20 MXC-10 MXC-20 MXC-30 MXV-30 MXP-10 MXP-20 MXL-10 MXT-10 Input Out- put Dis- play Adjust- ments Description Type Page •• •• •• •• •• •• •• SELECTION GUIDE 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 •• 22,5mm Industrial Design for Din Rail Mounting •• •• •• •• •• •• ••

Upload: trinhkhanh

Post on 20-Jul-2018

247 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

37

Control & Monitoring RelaysIntroduction & Selection Guide

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

MC

U-1

0D

V/A

VD

C/A

CM

CU

-10

MC

U-1

0P

/N/T

MC

U-1

0J/

K/S

/RM

CU

-10

UM

XP

-10

MX

C-3

0M

XV

-10

MX

C-2

0M

XV

-20

MX

V-3

0M

XC

-10

MC

P-1

0IN

TR

O...

MX

P-2

0M

XL-

10M

XT-

1047

.98

INTRODUCTION

The Brodersen monitoring relays are high qualityproducts incorporating up-to-date circuit designtogether with modern, efficient components to en-sure a long trouble free life in a wide range ofoperating conditions.Power consumption and, thus, heat dissipation areminimal and the entire range has been de-signedand tested to the latest requirements for EMCimmunity and emission.

A wide range of commonly used standards of volt-age, current, temperature and process signals canbe monitored by the Brodersen relays.

The Brodersen Control and monitoring relays areproduced in two design categories; installation andindustrial design. The installation design is basedon DIN rail or 11 pole plug-in mounting and aredesigned to fit into installation enclosures. Theindustrial design is in 22,5mm housing with theterminals placed to optimize installation time inindustrial applications.

MCU-10Digital control relay

MCP-10Phase monitoring relay

MXC-10AC/DC current relay

AC

/DC

Vol

tage

AC

/DC

Cur

rent

3-ph

ase

Vol

tage

3-ph

ase

Mon

itorin

gT

empe

ratu

re R

TD

sT

empe

ratu

re T

herm

ocou

ples

Liqu

id L

evel

, C

ondu

ctiv

eS

tand

ard

Pro

cess

Sig

nal

Out

put

Rel

ayA

nalo

gue

Out

put,

Set

poin

tA

nalo

gue

Out

put,

Mea

surin

g

LCD

Dis

play

LED

Ind

icat

ion

Set

poin

tsH

yste

retis

Del

ay

36mm InstallationDesign for Din Railor 11-Pole Plug-InMounting

Phase monitoring relay

Digital voltage relayDigital current relayDigital thermostat relayDigital thermostat relayDigital process signal relay

AC/DC voltage relayAC/DC voltage relayAC/DC current relayAC/DC current relayAC/DC current relay3 phase voltage relayPhase monitoring relayPhase monitoring relayLiquid level relayThermostat relay

MCP-10

MCU-10 DV/AVMCU-10 DC/ACMCU-10 P/N/TMCU-10 J/K/S/RMCU-10 U

MXV-10MXV-20MXC-10MXC-20MXC-30MXV-30MXP-10MXP-20MXL-10MXT-10

Input Out-put

Dis-play

Adjust-ments

Description Type Page

• • •

• • • • •• • • • •

• • • • •• • • • •

• • • • •

• • • • • •

• • • •• • • •

SELECTION GUIDE

38

4042444648

50525456586062646668

• ••••22,5mm IndustrialDesign for DinRail Mounting • • • • • •

• • • • •• • • • • •

• • • • •• • • • • ••

• • •

Page 2: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

39

Control & Monitoring RelaysPhase Failure Relay MCP-10

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

MC

U-1

0D

V/A

VD

C/A

CM

CU

-10

MC

U-1

0P

/N/T

MC

U-1

0J/

K/S

/RM

CU

-10

UM

XP

-10

MX

C-3

0M

XV

-10

MX

C-2

0M

XV

-20

MX

V-3

0M

XC

-10

MC

P-1

0IN

TR

O...

MX

P-2

0M

XL-

10M

XT-

1047

.98

PHASE MONITORING

1. Lightly loaded 3-phase motor and L1 interrupted (ϕ > 20°).2. Ohmic load or heavily loaded 3-phase motor and L2 interrupted(ϕ=180°).3. Reversed order of the phases L2 and L3 i.e. incorrect phase se-quence(ϕ=120°).

VOLTAGE MONITORING

1. Voltage drop on one phase.2. Voltage drop on all 3 phases (symmetrical).

If one of the phases connected to an idle 3-phase motor is inter-rupted, no changes can be measured in the voltage and phaseconditions, and the phase failure relay will not detect the failure.

DESCRIPTION

Control relay for monitoring of correct phase sequence, phase breakand undervoltage.Connection to 3-phase mains supply with or without neutral. Fixedlimits for energizing and de-energizing the single or double outputrelay. LED indication of supply voltage and phase failure.Versions available for DIN rail or 11-pole plug-in base mounting.Versions available for separate supply and measuring voltage.

OPERATION

The phase failure relay monitors phase sequence, phase break andundervoltage.The output relay is energized when all three phase voltages arepresent and the phase conditions (voltage and phase sequence) arecorrect.The phase failure relay has a fixed time delay to prevent faultyenergization and de-energization caused by short interferences.LED indication of supply voltage connected (green) and phase orvoltage failure (red).The phase failure relay uses L2 and L3 (6 and 7) for supply voltage.The indicators therefore only work if these phases are present.An improvement of the measuring range is obtained by connectingneutral to the relay (see the technical data).

OPTION

Separate supply and measuring voltage S.The supply voltage for the internal circuit is separated from the mea-suring voltage which allows the measuring circuit and the LEDindicators to work if one or more of the monitored phases areinterrupted.

VERSIONS/ORDERING CODES

Type: MCP-10 S 1 380 /S230Phase failure relay. MCP-10

Mounting:11-pole plug-in. SDIN rail. D

Output relay:SPDT. 1DPDT1). 2

Measuring/supply voltage: 3)

3 x 220V AC 2203 x 380V AC 3803 x 400V AC 4003 x 415V AC 415

Options: 3)

Separate supply voltage:220/240V AC ±10%. /S230

L1-N

L2-N

L3-N

With neutral

70% 80% 85% 90%

21

T T T T T

L1

L2

L3

Without neutral

60% 80% 80% 85%

21

T T T T T

L1

L2

L3

Page 3: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

38

Phase Failure Relay MCP-10

Control & Monitoring Relays

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

47.9

8

APPLICATION

Monitoring of the supply voltage to a 3-phase motor with signal lampindication of phase failure and motor contactor on.

TECHNICAL DATA

Phase measuring:With neutral: Fault: ϕ > 25°, typically by ϕ > 20°.Without neutral: Fault: ϕ > 50°, typically by ϕ > 40°.

Voltage measuring:With neutral:Change on 1 phase:

Energized output relay: > 90% of Vnom., typically by > 80%.Fault: < 65% of Vnom., typically by < 70%.

Change of 3 phases, symm.:Energized output relay: > 90% of Vnom.Fault: < 80% of Vnom., typically by < 85%.

Without neutral:Change on 1 phase:

Energized output relay: > 90% of Vnom., typically by > 80%.Fault: < 50% of Vnom., typically by < 60%.

Change on 3 phases, symm.:Energized output relay: > 90% of Vnom., typically by > 85%Fault: < 75% of Vnom., typically by < 80%.

Temperature drift: All specifications apply for the specifiedtemperature range.

Output relay: SPDT or DPDT.Load (cosϕ=1): D1/S1: 8A/240V AC

10mA/24V DCS2: 5A/240V AC

10mA/24V DCFrequency: Max. 1000 operations per hour at max. load.Mechanical lifetime: Min. 10 x 106 operations.Electrical lifetime: Min. 100.000 operations at full load.Time delay: 0.3-0.9 sec.

Mounting: S1/S2: 11-pole plug in.D1: Directly on 35 mm DIN rail (EN50022).

Terminals: Max. conductor size 4mm2.Screw type terminals with self-lifting clamps shrouded in accor-dance with VDE0106 (finger and back of hand protection).

Supply/measuring voltage:3 x 220V AC + 10%,3 x 380V AC + 10%,3 x 400V AC + 10%,3 x 415V AC + 10%.

220V AC ±10% (option S).240V AC ±10% (option S).

Other AC voltages on request.

Mains frequency: 45-66Hz.

Consumption: 1-3VA.

EMC: Conforming to EN 50081-1/EN 50082-2.

Isolation: 2kV AC according to EN 60950 class I.

Ambient temperature:-25 to 55°C.

Protection: S1/S2: IP40.

D1: IP20.

Housing: Noryl SE-1.

Weight: Typically 170 g.

NOTES/REMARKS

1) Double output relay only available in S2 version.2) Terminal 2 (A1) is only used when a separate supply voltage isconnected.3) Available with user-specified voltage. Plese specify voltage.

L1 L2 L3

M3~

F1-3

K1

K2ϕ V <

N

L1 L2 L3

N

K1Failure On

K2

MECHANICAL DIMENSIONS

WIRING DIAGRAMS

10 1047 36

80 45

53.553.513

note 2

L N

A115

L1 L2

16 18 A2

Supply

L3

L1 L2 L3

L N

12

3

45

67

8

9

1011

Supply

L1 L2 L3

note 2

L N

12

3

45

67

8

9

1011

Supply

L1 L2 L3

note 2

D1 S1 S2

Page 4: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

41

Control & Monitoring RelaysDigital Control Relay MCU-10...DV/AV

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

DC

/AC

MC

U-1

0M

CU

-10

P/N

/TM

CU

-10

J/K

/S/R

MC

U-1

0U

MX

P-1

0M

XC

-30

MX

V-1

0M

XC

-20

MX

V-2

0M

XV

-30

MX

C-1

0M

CP

-10

INT

RO

...M

XP

-20

MX

L-10

MX

T-10

MC

U-1

0D

V/A

V47

.98

FRONT

Front Front label

1. Output mode selector 2. LED indication of energized outputrelay 3. Button for setpoint read-out 4. Setpoint adjustment 5. Unitlabel position 6. Display field.

DESCRIPTION

Digital control relay with 3½-digit LCD display.The control relay is used for control and measurement of AC/DCvoltage.The actual input signal type and measuring range must be specifiedwhen the control relay is ordered. 3½ digit LCD display with selectable read-out of actual input andsetpoint.Output relay with LED indication of energized output relay.Built-in power supply for direct mains supply. Galvanic isolationbetween input and supply.Standardized housing for 11-pole plug-in or DIN rail mounting.Bases for DIN rail,surface and chassis mounting are listed underAccessories for MCP-10, see page 128.

VERSION/ORDERING CODES

Type: MCU-10 S 1 230 DV3Digital control relay. MCU-10

Mounting:11-pole plug-in. SDIN rail. D

Output relay:SPDT 1

Supply voltage:12-48V DC/10-30V AC G2412V AC/DC 912 1)

24V AC/DC 924 1)

24V AC 024110/120V AC 115220/240V AC 230380/415V AC 400

Input:

Voltage:DC:0-19.99V. DV10-199.9V. DV20-500V. DV3

AC:0-19.99V. AV10-199.9V. AV20-500V. AV3

Input

Mode 1: Output relay energized below setpoint

hysteresis

setpoint

Input

Mode 2: Output relay energized above setpoint

hysteresis

setpoint

RPM

M C U

1 2

3

4

15 16 18 A2

1 2A1 +1 +2 -0

5

6

OPERATION

The display shows the actual input signal when the supply voltageis connected.The setpoint is displayed by pressing the S button and the setpointis adjusted on the front mounted potentiometer.The output mode switch for selecting whether the output relayshould be energized above or below the adjusted setpoint, see thediagrams below.The red LED indicator will light up when the output relay is energized.

Page 5: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

40

Control & Monitoring RelaysDigital Control Relay MCU-10...DV/AV

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

47.9

8

WIRING DIAGRAMS

AC DC

NOTES/REMARKS

1) There is no galvanic isolation between input and supply. Externalisolation should be provided to prevent damage to the controllerwhen measuring voltage/current or a G- or other version with in-ternal isolation should be used.

Temperature drift:Voltage, current andtemperature: Max. 0.01% per °C.

Display: 3½-digit LCD-type (-1999 to 1999).Digit height: 6.5 mm.Display update time: Typically 0.4 sec.

Scale: The scale is adjusted to the actual measuringrange listed in the ordering key.

Output relay: SPDT (single changeover contact).Load (cosϕ=1): D1/S1: Max. 8A/240V AC

Min. 10mA/24VDCFrequency: Max. 1000 operations per hour at max. load.Mechanical life time: Min. 10 x 106 operations.Electrical life time: Min. 100.000 operations at max. load.Time delay: Typically 1s.

Mounting: S1: 11-pole plug-in.D1: Directly on 35 mm DIN-rail (EN50022).

Terminals: Max. conductor size 4 mm2.Screw type terminals with self-lifting clamps shrouded in accord-ance with VDE0106 (finger and back of hand protection).

Supply voltage: 12-48VDC(10.5-60V)/12-30VAC.(10.5-35V).12V AC/DC (10-18V) 1).24V AC/DC (18-35V) 1).24V AC (22-26V).110/120V AC (95-135V).220/240V AC (195-265V).380/415V AC (342-418V).

Mains frequency: 45-66Hz.

Consumption: 1-3VA.

Protection: S1: IP40.D1: IP20.

EMC: Conforming to EN 50081-2/EN 50082-1.

Ambient temperature:-25-55°C.

Isolation:AC versions: 4kV AC according to EN 60950 class II.G24 version: 1kV AC

Dimensions: Identical to MCP-10, see page 38.

Housing: Black Noryl SE-1.

Weight: Typically 170 g.

+ / L - / N

A1

15

+1 +2

16 18 A2

Supply

-0

~

+ / L - / N

12

3

45

67

8

9

1011

Supply

~

+ / L - / N

A1

15

+1 +2

16 18 A2

Supply

-0

+ -

+ / L - / N

12

3

45

67

8

9

1011

Supply

+ -

TECHNICAL DATA

Measuring ranges:

AC DC 0-19.99V 0-19.99V 0-199.9V 0-199.9V 0-500V 0-500V

Input impedance:AC.: 1kOhm/V.DC: 1MOhm (>10V).

Measuring accuracy: 1% of full scale ± 1 digit.

Hysteresis: 1% of full range.

Page 6: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

43

Control & Monitoring RelaysDigital Control Relay MCU-10...DC/AC

DV/AV

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

MC

U-1

0D

V/A

VM

CU

-10

P/N

/TM

CU

-10

J/K

/S/R

MC

U-1

0U

MX

P-1

0M

XC

-30

MX

V-1

0M

XC

-20

MX

V-2

0M

XV

-30

MX

C-1

0M

CP

-10

INT

RO

...M

XP

-20

MX

L-10

MX

T-10

DC

/AC

MC

U-1

047

.98

OPERATION

The display shows the actual input signal when the supply voltageis connected.

The setpoint is displayed by pressing the S button and the setpointis adjusted on the front mounted potentiometer.

The output mode switch for selecting whether the output relayshould be energized above or below the adjusted setpoint, see thediagrams below.The red LED indicator will light up when the output relay is energized.

FRONT

Front Front label

1. Output mode selector 2. LED indication of energized outputrelay 3. Button for setpoint read-out 4. Setpoint adjustment 5. Unitlabel position 6. Display field.

DESCRIPTION

Digital control relay with 3½-digit LCD display.The control relay is used for control and measurement of AC/DCcurrent.The actual input signal type and measuring range must be specifiedwhen the control relay is ordered.3½ digit LCD display with selectable read-out of actual input andsetpoint.Output relay with LED indication of energized output relay.Built-in power supply for direct mains supply. Galvanic isolationbetween input and supply.Standardized housing for 11-pole plug-in or DIN rail mounting.Bases for DIN rail, surface and chassis mounting are listed underAccessories for MCP-10, see page128.

VERSION/ORDERING CODES

Type: MCU-10 S 1 230 DC1Digital control relay. MCU-10

Mounting:11-pole plug-in. SDIN rail. D

Output relay:SPDT 1

Supply voltage:12-48VDC/10-30V AC G2412V AC/DC 912 1)

24V AC/DC 924 1)

24V AC 024110/120V AC 115220/240V AC 230380/415V AC 400

Input:

Current:DC:0-19.99mA. DC10-199.9mA. DC20-10.00A. DC3 3)

0-100.0A. DC4 3)

AC:0-19.99mA. AC10-199.9mA. AC20-1.99A. AC30-199.9A. AC4 4)

0-500A. AC5 5)

RPM

M C U

1 2

3

4

15 16 18 A2

1 2A1 +1 +2 -0

5

6

Input

Mode 1: Output relay energized below setpoint

hysteresis

setpoint

Input

Mode 2: Output relay energized above setpoint

hysteresis

setpoint

Page 7: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

42

Control & Monitoring RelaysDigital Control Relay MCU-10...DC/AC

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

47.9

8

TECHNICAL DATA

Measuring ranges:

AC DC0-19.99mA 0-19.99mA0-199.9mA 0-199.9mA0-1.99A0-199.9A with external current 0-10.00A with external shunt0-500A transformer (1A sec.) 0-100.0A (60mV voltage drop)

Input impedance: 1VI max

.60mV with shunt.I max

Measuring accuracy: 1% of full scale ± 1 digit.

Hysteresis: 1% of full range.

Temperature drift:Voltage, current andtemperature: Max. 0.01% per °C.

Display: 3½-digit LCD-type (-1999 to 1999).Digit height: 6.5 mm.Display update time: Typically 0.4 sec.

Scale: The scale is adjusted to the actual measuringrange listed in the ordering key.

Output relay: SPDT (single changeover contact).Load (cosϕ=1): D1/S1: Max. 8A/240V AC

Min. 10mA/24VDCFrequency: Max. 1000 operations per hour at max.load.Mechanical life time: Min. 10 x 106 operations.Electrical life time: Min. 100.000 operations at max. load.Time delay: Typically 1s.

Mounting: S1: 11-pole plug-in.D1: Directly on 35 mm DIN-rail (EN50022).

Terminals: Max. conductor size 4 mm2.Screw type terminals with self-lifting clamps shrouded in accord-ance with VDE0106 (finger and back of hand protection).

Supply voltage: 12-48V DC(10.5-60V)/12-30V AC.(10.5-35V).12V AC/DC (10-18V) 1).24V AC/DC (18-35V) 1).24V AC (22-26V).110/120V AC (95-135V).220/240V AC (195-265V).380/415V AC (342-418V).

Mains frequency: 45-66Hz.

Consumption: 1-3VA.

Protection: S1: IP40.D1: IP20.

EMC: Conforming to EN 50081-2/EN 50082-1.

Ambient temperature: -25-55°C.

Isolation:AC versions: 4kV AC according to EN 60950 class II.G24 version: 1kV AC

Dimensions: Identical with MCP-10, see page 39.

Housing: Black Noryl SE-1.

Weight: Typically 170 g

WIRING DIAGRAMS

+ / L - / N

A1

15

+1 +2

16 18 A2

Supply

-0

~

+ / L - / N

12

3

45

67

8

9

1011

Supply

~

+ / L - / N

A1

15

+1 +2

16 18 A2

Supply

-0

+ -

+ / L - / N

12

3

45

67

8

9

1011

Supply

+ -

AC DC

NOTES/REMARKS

1) There is no galvanic isolation between input and supply. Externalisolation should be provided to prevent damage to the controllerwhen measuring voltage/current or a G- or other version with in-ternal isolation should be used.2) With external shunt type AAS-010 (0-10.0 A DC) or type AAS-100(0-100 A DC).3) With external current transformer type AAT-200.1.4) With external current transformer type AAT-500.1.

Page 8: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

45

Control & Monitoring RelaysDigital Control Realy MCU-10...P/N/T

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

MC

U-1

0D

V/A

VD

C/A

CM

CU

-10

MC

U-1

0J/

K/S

/RM

CU

-10

UM

XP

-10

MX

C-3

0M

XV

-10

MX

C-2

0M

XV

-20

MX

V-3

0M

XC

-10

MC

P-1

0IN

TR

O...

MX

P-2

0M

XL-

10M

XT-

10M

CU

-10

P/N

/T47

.98

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

DESCRIPTION

Digital control relay with 3½-digit LCD display.The control relay is used for control and measurement of Tempera-ture with Pt-100, Ni-100, and thermistorsThe actual input signal type and measuring range must be specifiedwhen the control relay is ordered. 3½ digit LCD display with selectable read-out of actual input andsetpoint.Output relay with LED indication of energized output relay.Built-in power supply for direct mains supply. Galvanic isolationbetween input and supply.Standardized housing for 11-pole plug-in or DIN rail mounting.Bases for DIN rail,surface and chassis mounting are listed underAccessories for MCP-10, see page 128.

OPERATION

The display shows the actual input signal when the supply voltageis connected.The setpoint is displayed by pressing the S button and the setpointis adjusted on the front mounted potentiometer.The output mode switch for selecting whether the output relayshould be energized above or below the adjusted setpoint, see thediagrams below.The red LED indicator will light up when the output relay is energized.

Input

Mode 1: Output relay energized below setpoint

hysteresis

setpoint

Input

Mode 2: Output relay energized above setpoint

hysteresis

setpoint

VERSION/ORDERING CODES

Type: MCU-10 S 1 230 P1Digital control relay. MCU-10

Mounting:11-pole plug-in. SDIN rail. D

Output relay:SPDT 1

Supply voltage:12-48VDC/10-30V AC G2412V AC/DC 912 1)

24V AC/DC 924 1)

24V AC 024110/120VAC 115220/240V AC 230380/415V AC 400

Input:

RTDs:Pt-100:-50.0-199.9°C. P1-50-850°C. P3

Ni-100:-50.0-199.9°C. N1

Thermistor (KTY):-30.0-100.0°C. T1

Front Front label

1 Output mode selector. 2 LED indication of energized output relay.3 Button for setpoint read-out. 4 Setpoint adjustment. 5 Unit labelposition. 6 Display field.

RPM

M C U

1 2

3

4

15 16 18 A2

1 2A1 +1 +2 -0

5

6

FRONT

Page 9: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

44

Control & Monitoring RelaysDigital Control Relay MCU-10...P/N/T

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

47.9

8

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

WIRING DIAGRAMS

RTD/Thermistor (2-wire) RTD/Thermistor (3-wire)

The MCU-10 temperature controller is supported by a wide range oftemperature sensors, see the temperature sensor data sheet fordetailed technical information and ordering codes.

TECHNICAL DATA

Measuring ranges:

RTDs/ThermistorsPt-100 Ni-100 Thermistor (KTY)-50.0-199.9°C -50.0-199.9°C -30.0-100.0°C-50-850°C

Measuring accuracy: 1% of full scale ± 1 digit.

Hysteresis: 1% of full range.

Temperature drift: Max. 0.01% per °C.

Display: 3½-digit LCD-type (-1999 to 1999).Digit height: 6.5 mm.Display update time: Typically 0.4 sec.

Scale: The scale is adjusted to the actual measuring range listed in the ordering key, exceptU1 version with user adjustable scale(-1999 to 1999, max. 2000 steps).

Output relay: SPDT (single changeover contact).Load (cosϕ=1): D1/S1: Max. 8A/240V AC

Min. 10mA/24VDCFrequency: Max. 1000 operations per hour at max. load.Mechanical life time: Min. 10 x 106 operations.Electrical life time: Min. 100.000 operations at max. load.Time delay: Typically 1s.

Mounting: S1: 11-pole plug-in.D1: Directly on 35 mm DIN-rail (EN50022).

Terminals: Max. conductor size 4 mm2.Screw type terminals with self-lifting clamps shrouded in accord-ance with VDE0106 (finger and back of hand protection).

Supply voltage: 12-48V DC (10.5-60V)/12-30V AC(10.5-35V).12V AC/DC (10-18V) 1).24V AC/DC (18-35V) 1).24V AC (22-26V).110/120V AC (95-135V).220/240V AC (195-265V).380/415V AC (342-418V).

Mains frequency: 45-66Hz.

Consumption: 1-3VA.

Protection: S1: IP40.D1: IP20.

EMC: Conforming to EN 50081-2/EN 50082-1.

Ambient temperature:-25-55°C.

Isolation:AC versions: 4kV AC according to EN 60950 class II.G24 version: 1kV AC

Dimensions: Identical to MCP-10, see page 38.

Housing: Black Noryl SE-1.

Weight: Typically 170 g.

NOTES/REMARKS

1) There is no galvanic isolation between input and supply. Externalisolation should be provided to prevent damage to the controllerwhen measuring voltage/current or a G- or other version with in-ternal isolation should be used.

+ / L - / N + / L - / N

12

3

45

67

8

9

1011

A1

15

+1 +2

16 18 A2

Supply

-0

Supply

+ / L - / N + / L - / N

12

3

45

67

8

9

1011

A1

15

+1 +2

16 18 A2

Supply

-0

Supply

Page 10: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

47

Control & Monitoring RelaysDigital Control Relay MCU-10...J/K/S/R

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

MC

U-1

0D

V/A

VD

C/A

CM

CU

-10

MC

U-1

0P

/N/T

MC

U-1

0U

MX

P-1

0M

XC

-30

MX

V-1

0M

XC

-20

MX

V-2

0M

XV

-30

MX

C-1

0M

CP

-10

INT

RO

...M

XP

-20

MX

L-10

MX

T-10

MC

U-1

0J/

K/S

/R47

.98

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

DESCRIPTION

Digital control relay with 3½-digit LCD display.The control relay is used for control and measurement of tempera-ture with thermocouples.The actual input signal type must be specified when the control relayis ordered.3½ digit LCD display with selectable read-out of actual input andsetpoint.Output relay with LED indication of energized output relay.Built-in power supply for direct mains supply. Galvanic isolationbetween input and supply.Standardized housing for 11-pole plug-in or DIN rail mounting.Bases for DIN rail,surface and chassis mounting are listed underAccessories for MCP-10, see page 128.

VERSION/ORDERING CODES

Type: MCU-10 S 1 230 J1Digital control relay. MCU-10

Mounting:11-pole plug-in. SDIN rail. D

Output relay:SPDT 1

Supply voltage:12-48V DC/10-30V AC G2412V AC/DC 912 1)

24V AC/DC 924 1)

24V AC 024110/120V AC 115220/240V AC 230380/415V AC 400

Input:

Fe-CuN-50-1200°C. J12)

NiCr-Ni:-50-1350°C. K12)

PtRh-Pt 10%:-50-1750°C. S12)

PtRh-Pt 13%:-50-1750°C. R12)

OPERATION

The display shows the actual input signal when the supply voltageis connected.

The setpoint is displayed by pressing the S button and the setpointis adjusted on the front mounted potentiometer.

The output mode switch for selecting whether the output relayshould be energized above or below the adjusted setpoint, see thediagrams below.The red LED indicator will light up when the output relay is ener-gized.

Input

Mode 1: Output relay energized below setpoint

hysteresis

setpoint

Input

Mode 2: Output relay energized above setpoint

hysteresis

setpoint

RPM

M C U

1 2

3

4

15 16 18 A2

1 2A1 +1 +2 -0

5

6

FRONTFront Front label

1. Output mode selector 2. LED indication of energized outputrelay 3. Button for setpoint read-out 4. Setpoint adjustment 5.Unit label position 6. Display field.

Page 11: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

46

Control & Monitoring RelaysDigital Control Relay MCU-10...J/K/S/R

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

47.9

8

TECHNICAL DATA

Temperature drift:Voltage, current andtemperature: Max. 0.01% per °C.Standard process: Max. 0.02% per °C.

Display: 3½-digit LCD-type (-1999 to 1999).Digit height: 6.5 mm.Display update time: Typically 0.4 sec.

Output relay: SPDT (single changeover contact).Load (cosϕ=1): D1/S1: Max. 8A/240V AC

Min. 10mA/24VDCFrequency: Max. 1000 operations per hour at max.load.Mechanical life time: Min. 10 x 106 operations.Electrical life time: Min. 100.000 operations at max. load.Time delay: Typically 1s.

Mounting: S1: 11-pole plug-in.D1: Directly on 35 mm DIN-rail (EN50022).

Terminals: Max. conductor size 4 mm2.Screw type terminals with self-lifting clamps shrouded in accord-ance with VDE0106 (finger and back of hand protection).

Supply voltage: 12-48V DC (10.5-60V)/12-30V AC(10.5-35V).12V AC/DC (10-18V) 1).24V AC/DC (18-35V) 1).24V AC (22-26V).110/120V AC (95-135V).220/240V AC (195-265V).380/415V AC (342-418V).

Mains frequency: 45-66Hz.

Consumption: 1-3VA.

Protection: S1: IP40.D1: IP20.

EMC: Conforming to EN 50081-1/EN 50082-2.

Ambient temperature:-25-55°C.

Isolation:AC versions: 4kV AC according to EN 60950 class II.G24 version: 1kV AC

Dimensions: Identical to MCP-10, see page 38.

Housing: Black Noryl SE-1.

Weight: Typically 170 g.

Measuring ranges:

Thermocouples Fe-CuNi NiCr-Ni PtRh-Pt 10% PtRh-Pt 13% -50 -1200°C -50 -1350°C -50 -1750°C -50 -1750°C

Measuring accuracy: 1% of full scale ± 1 digit 2).

Hysteresis: 1% of full range.1

2

3

45

67

8

9

1011

A1

15

+1 +2

16 18 A2

+ / L - / N

Supply

-0

+ / L

Supply

- / N

+ -+ -

WIRING DIAGRAMS

Thermocouple

The MCU-10 temperature controller is supported by a wide range oftemperature sensors, see the temperature sensor data sheet fordetailed technical information and ordering codes.

NOTES/REMARKS

1) There is no galvanic isolation between input and supply. Externalisolation should be provided to prevent damage to the controllerwhen measuring voltage/current or a G- or other version withinternal isolation should be used.2) The specified accuracy is valid within the subranges:J1: 0 -1100 °C. S1: 150 -1550 °C.K1: 0 -1150 °C. R1: 150 -1550 °C.

Page 12: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

49

Control & Monitoring RelaysDigital Control Relay MCU-10...U

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

MC

U-1

0D

V/A

VD

C/A

CM

CU

-10

MC

U-1

0P

/N/T

MC

U-1

0J/

K/S

/RM

XP

-10

MX

C-3

0M

XV

-10

MX

C-2

0M

XV

-20

MX

V-3

0M

XC

-10

MC

P-1

0IN

TR

O...

MX

P-2

0M

XL-

10M

XT-

1047

.98

MC

U-1

0U

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

VERSION/ORDERING CODES

Type: MCU-10 S 1 230 U1Digital control relay. MCU-10

Mounting:11-pole plug-in. SDIN rail. D

Output relay:SPDT 1

Supply voltage:12-48V DC/10-30V AC G2412V AC/DC 912 1)

24V AC/DC 924 1)

24V AC 024110/120V AC 115220/240V AC 230380/415V AC 400

Input:Standard process signals:0-20mA DC/4-20mA DCand 0-10V DC/2-10V DC U1

DESCRIPTION

Digital control relay with 3½-digit LCD display.The scaling facilities of the MCU-10...U make it ideal as a monitor orcontrol device for normal standard process signals, e.g. 4-20mA.Any output from a transmitter can be scaled to engineering units anda unit label can be inserted on the front of the control relay. A sheetwith common units is enclosed with the relay.Typical applications:General process instrumentation.Signal monitor with read-out in engineering units.3½ digit LCD display with selectable read-out of actual input andsetpoint.Output relay with LED indication of energized output relay.Built-in power supply for direct mains supply. Galvanic isolationbetween input and supply.Standardized housing for 11-pole plug-in or DIN rail mounting.Bases for DIN rail,surface and chassis mounting are listed underAccessories for MCP-10, see page 128.

FRONT

Front Front label

1. Input selector 2. Output mode selector 3. LED indication ofenergized output relay 4. Decimal point position 5. Button forsetpoint read-out 6. Setpoint adjustment 7. Scale and offset ad-justment 8. Unit label position 9. Display field.

RPM

M C U

2

1

3

4

5

6

7

15 16 18 A2

1 2A1 +1 +2 -0

8

9

OPERATION

The display shows the actual input signal when the supply voltageis connected.The setpoint is displayed by pressing the S button and the setpointis adjusted on the front mounted potentiometer.The output mode switch for selecting whether the output relayshould be energized above or below the adjusted setpoint, see thediagrams below.The red LED indicator will light up when the output relay is energized.

Input

Mode 1: Output relay energized below setpoint

hysteresis

setpoint

Input

Mode 2: Output relay energized above setpoint

hysteresis

setpoint

Page 13: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

48

Control & Monitoring RelaysDigital Control Relay MCU-10...U

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

47.9

8

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

TECHNICAL DATA

Measuring ranges:

DC0-20mA/4-20mA and 0-10V/2-10V.The actual input signal is selected via a switch on the control relay.

Measuring accuracy: 1% of full scale ± 1 digit.

Hysteresis: 1% of full range.

Input impedance:Voltage: 1Mohm.Current: 50Ohm.

Temperature drift: Max. 0.02% per °C.

Display: 3½-digit LCD-type (-1999 to 1999).Digit height: 6.5 mm.Display update time: Typically 0.4 sec.

Scale: The scale is adjusted to the actual measur-ing range which is user adjustable(-1999 to 1999, max. 2000 steps).

Decimal point: Selectable _._ _ _ _ _._ _ _ _ _._ _ _ _ _

Output relay: SPDT (single changeover contact).Load (cosϕ=1): D1/S1: Max. 8A/240V AC

Min. 10mA/24VDCFrequency: Max. 1000 operations per hour at max. load.Mechanical life time: Min. 10 x 106 operations.Electrical life time: Min. 100.000 operations at max. load.Time delay: Typically 1s.

Mounting: S1: 11-pole plug-in.D1: Directly on 35 mm DIN-rail (EN50022).

Terminals: Max. conductor size 4 mm2.Screw type terminals with self-lifting clamps shrouded in accord-ance with VDE0106 (finger and back of hand protection).

Supply voltage: 12-48VDC(10.5-60V)/12-30VAC(10.5-35V).12V AC/DC (10-18V) 1).24V AC/DC (18-35V) 1).24V AC (22-26V).110/120V AC (95-135V).220/240V AC (195-265V).380/415V AC (342-418V).

Mains frequency: 45-66Hz.

Consumption: 1-3VA.

Protection: S1: IP40.D1: IP20.

EMC: Conforming to EN 50081-1/EN 50082-2.

Ambient temperature:-25-55°C.

Isolation:AC versions: 4kV AC according to EN 60950 class II.G24 version: 1kV AC

Dimensions: Identical to MCP-10, see page 39.

Housing: Black Noryl SE-1.

Weight: Typically 170 g.

WIRING DIAGRAMS

Voltage Current

CONFIGURATION/CALIBRATION

The control relay for standard process signals is fully user adjust-able within in the scale limits -1999 to 1999 with a maximum spanof 2000 steps, e.g. a scale from -1000 to 1000.

The offset is adjustable within the range -1999 to 1999 ,however,the maximum offset must be smaller than the required span:Max. offset≤≤≤≤≤ Span = Max. scale - Min. scalea scale e.g. 500 to 800 ( 500 ≤ 300 = 800 - 500 ) can therefore notbe obtained.Selectable decimal point position: _ . _ _ _ _ _._ _ _ _ _._ _ _ _ _

Selectable input range:0-20mA/0-10V or 4-20mA/2-10V.Example: Adjust the control relay to a scale -1000 to 1000, inputsignal 4-20mA.1) Set the switches for input, output mode and decimal pointposition. Mount the front label and connect the supply voltage.2 ) Apply min. signal 4mA and adjust Offset to display read-out 0000.3) Apply max. signal 20mA and adjust Scale to a display read-out1999. Adjust Offset to display read-out1000.4) Apply min. signal 4mA and check display read-out is -1000. Ifincorrect, return to step 2 and readjust the control relay.

The control relay is now calibrated and ready to use.

+ / L - / N

12

3

45

67

8

9

1011

Supply

V 0+ -

+ / L - / N

A1

15

+1 +2

16 18 A2

Supply

-0

V 0+ -

+ / L - / N

12

3

45

67

8

9

1011

Supply

mA 0+ -

+ / L - / N

A1

15

+1 +2

16 18 A2

Supply

-0

mA 0+ -

NOTES/REMARKS

1) There is no galvanic isolation between input and supply. Externalisolation should be provided to prevent damage to the controllerwhen measuring voltage/current or a G- or other version with in-ternal isolation should be used.

-1999 1999-1000 1000

Minimumdisplayread-out

Maximumdisplay read-out

Maximum span2000 steps

Offset range-1999 to 1999

0

Page 14: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

51

Control & Monitoring RelaysSingle Phase Voltage Relay MXV-10

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

MC

U-1

0D

V/A

VD

C/A

CM

CU

-10

MC

U-1

0P

/N/T

MC

U-1

0J/

K/S

/RM

CU

-10

UM

XP

-10

MX

C-3

0M

XC

-20

MX

V-2

0M

XV

-30

MX

C-1

0M

CP

-10

INT

RO

...M

XP

-20

MX

L-1

0M

XT

-10

MX

V-1

047

.98

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

DESCRIPTION

Single phase voltage relay for detecting AC/DC over-or under-voltageThe relay is delivered in two variations for over-and under-voltage.Over-voltage:When the monitored voltage rises and reaches the determined setpoint,which is adjusted on the front panel, the relay energises. When thevoltage drops and passes the setpoint, minus the hysteresis which isadjustable on the front, the relay de-energises.Under-voltage:When the monitored voltage drops and reaches the determinedsetpoint, which is adjusted on the front panel, the relay energises.When the voltage rises and passes the setpoint , plus the hysteresiswhich is adjustable on the front, the relay de-energisesThere is also a latch function where the relay after energising willremain energised, regardless of input voltage, until the latch jumper orthe operating voltage is disconnected. Typically used in safety cir-cuits. The contact function of the relay can also be inverted.The relay has an analogue, 2-10VDC, output which when connectedto an external voltmeter can be used for the accurate adjustment of thesetpoint.

Features

• Monitoring of 1-500VAC/DC in 5 ranges in one version.• Adjustable setpoint.• Adjustable hysteresis of 0,5-20%.• Automatic locking function (latch).• Inversion of the relay function.• Output SPDT and 2-10VDC with reference to setpoint.• Supply voltage 24VDC, 24/115VAC or 24/230VAC.

VERSIONS/ORDERING CODES

Type: MXV-10 230 1Single phase voltage relay MXV-10

Supply voltage24V DC 924115V AC / 24V AC 115230V AC / 24V AC 230

Over/under voltageOver voltage 1Under voltage 2

OPERATION

Over voltage, code 1

Under voltage , code 2

MECHANICAL DIMENSIONS

supplyhysteresis

latch

setpoint

inv

inv

hysteresis

latch

setpoint

supply

inv

inv

80.0

mm

104.0 mm

80.0

mm

22.5 mm

Page 15: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

50

Control & Monitoring RelaysSingle Phase Voltage Relay MXV-10

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

47.9

8

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

TECHNICAL DATA

Input:Input signal Impedance Umax1-5V AC/DC 500k 700V AC4-20V AC/DC 500k 700V AC10-50V AC/DC 500k 700V AC40-200V AC/DC 500k 700V AC100-500V AC/DC 500k 700V AC

Frequency : 45-65 HzTemperature drift Max. 0,05%/°CSetting accuracy: Typically± 10%Hysteresis: 0,5-20% of chosen range, adjustableResponse time: time constant τ = 0,8s,

Worst case of response time max. 5 x τ

Output:SPDT relay: Contact material, AgNi 0,15 with hardened

gold plating Au.Max load AC, 8A/240V AC (cosϕ=1)Max. breaking capacity 2000VA.Inductive load. See fig. 1.Max load DC, 8A/24V DCMax breaking capacity 50-270W see fig. 2.

Max. in rushcurrent: 15A (max. 4s/duty cycle less than 10%).Min. in rushcurrent: 10mA, 24V DC.Frequency : Max. 1000 operations pr. hour.Life span: Mech. Min. 3 x 107 operations

Elect. Min 1x 105 operations with full load.Delay; <20ms.Analogue output: 2-10V DC, refers to setpoint in chosen range.

Imax=2mA /Rload >5kOhm.Accuracy better than +/- 0,5%.

Supply voltage:Versions: 924=24V DC (20,4-27,6 )V DC.

115=24/115V AC (20,4-27,6 /98-132)V AC.230=24/230V AC (20,4-27,6/196-264)V AC.

Net frequency: 45-65Hz.Consumption: AC; 3VA

DC; 2W

SPECIFICATIONSMXV-10 is designed and developed with regard to relevant specifications:• EN60204-1 / VDE0113 electrical material on machines.• VDE0110 / IEC664 Isolation specifications/creepage and clearancedistances.• Electrical safety in accordance with EN61010.• IEC414 Safety regulations for control and monitoring equipment.• EMC: Emission EN50081-1.

Immunity EN50082-2.• Humidity in accordance with IEC68-2-3; RH=95%, 40°C.• Vibration in accordance with IEC68-2-6:• Shock when mounted, in accordance with IEC68-2-27.

MXV-10 is CE-marked in accordance with EMC-and the Low VoltageDirective.

OUTPUT LOAD DIAGRAMS

Fig. 1

Fig. 2

0,9

0,8

0,7

0,6

0,5

0,4

1,0

0,2 0,4 0,6 0,8 1,0cosϕ

Red

uct

ion

fac

tor

Input 0 L- +

15

16 18

15 Y1

X1

Relayinverted

Latchactive

-

+

µ

AC supplyDC supply

16 18

A1Y1

15Y2

X1A3

Z1Y3

Z2

A2

L(24V)L (115/230)+ (24V)

N-(0V)

WIRING DIAGRAM

Coding: Relay inv.; Jumper Y1 - Z1 Latching; Jumper Y1 - Z2

Analogue output 2-10V DC;X1 = (+) VY1 = (-) 0

General data::Ambient temperature:-20 to 55°C.Storage temperature: -40 to 80°C.Mounting: 35mm DIN-rail (EN50022).Terminals: Screw terminals with dual compartment.

Terminal screws are combined crosshead/slotted. Up to 2 x 2,5mm2 wire (2 x 1,5mm2

inc. ferrule).Recommended torque, 0,5Nm.Max 0,7 Nm. (VDE0609-1).Terminal identification in accordance withDIN46199/EN50005.

Indicators: Green LED = operating voltage.Red LED = relay switched on.

Protection: IP20.Electrical isolation: 3,75kVAC (1 min.) between input, supply

and relay output (EN60950).Note: No galvanic isolation between input andanalogue output.

Housing: Noryl (GE), UL94V1.Terminal block: Noryl (GE), UL94V0.Weight: 180 g.

0,1 0,2 0,5 1,0 5,0 8,0

300

200

100

50

20

2,0 I [A]

U [V]

Page 16: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

53

Control & Monitoring RelaysSingle Phase Voltage Relay MXV-20

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

MC

U-1

0D

V/A

VD

C/A

CM

CU

-10

MC

U-1

0P

/N/T

MC

U-1

0J/

K/S

/RM

CU

-10

UM

XP

-10

MX

C-3

0M

XV

-10

MX

C-2

0M

XV

-30

MX

C-1

0M

CP

-10

INT

RO

...M

XP

-20

MX

L-10

MX

T-10

MX

V-2

034

.99

PRELIMINARY

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

DESCRIPTION

Single phase voltage relay for detecting a level of AC or DC voltage.

When the monitored voltage rises and reaches the determinedsetpoint, which is adjusted on the front panel, the relay energises.When the voltage drops and passes the setpoint, minus the hyster-esis which is adjustable on the front, the relay de-energises. Withinverted relay function the internal relay work the opposite way.

The Voltage Relay has a latch function where the relay after energis-ing will remain energised, regardless of input voltage, until the latchjumper or the operating voltage is disconnected. Typically used insafety circuits.

Features

• Monitoring of 1-500V AC/DC in 5 ranges.• Adjustable setpoint.• Adjustable hysteresis of 3-35%.• Automatic locking function (latch).• Inversion of the relay function.• Output SPDT.• Supply voltage 24VDC, 24VAC, 115VAC, 230VAC or 400VAC.

VERSIONS/ORDERING CODES

Type: MXV-20 230 1Single phase voltage relay MXV-20

Supply voltage24V DC 92424V AC 024115V AC 115230V AC 230400V AC 400

Measuring range:1-5V AC/DC 14-20V AC/DC 210-50V AC/DC 340-200V AC/DC 4100-500V AC/DC 5

MECHANICAL DIMENSIONS

80.0

mm

104.0 mm

80.0

mm

22.5 mm

OPERATION

hysteresis

latch

setpoint

supply

inv

inv

Page 17: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

52

Control & Monitoring RelaysSingle Phase Voltage Relay MXV-20

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

06.9

9

PRELIMINARY

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

TECHNICAL DATA

Input:Input signal Impedance Umax1-5V AC/DC 5,5kOhm 50V AC4-20V AC/DC 22kOhm 100V AC10-50V AC/DC 55kOhm 150V AC40-200V AC/DC 220kOhm 300V AC100-500V AC/DC 550kOhm 525V AC

Accuracy 1%Temperature drift Max. 0,05%/°CSetting accuracy: Typically ± 10%Hysteresis: Adjustable 3-35%Response time: Time constant τ = 0,2s,

Worst case of response time max. 5 x τ

Output:SPDT relay

Contact material: AgNi 0,15 with hardened gold plating Au.Max load AC: 8A/240V AC (cosϕ=1)

Max. breaking capacity 2000VA,Inductive load. See fig. 1.

Max load DC: 8A/24V DCMax breaking capacity 50-270W see fig. 2.

Max. in rush current: 15A (max. 4s/duty cycle less than 10%).Min. in rush current: 10mA, 24V DC.Frequency : Max. 1000 operations pr. hour.Life span: Mech. Min. 3 x 107 operations

Elect. Min 1x 105 operations with full load.Delay: <20ms.

Supply voltage:Versions: 924=24V DC (20,4-27,6 )V DC.

024=24V AC (20,4-27,6)V AC.115=115V AC (98-132)V AC.230=230V AC (196-264)V AC.400=400VAC (340-460)V AC.

Net frequency: 40-70Hz.Consumption: AC; max. 3VA

DC; max. 2W

0,9

0,8

0,7

0,6

0,5

0,4

1,0

0,2 0,4 0,6 0,8 1,0cosϕ

Red

uct

ion

fac

tor

WIRING DIAGRAM

Coding:Relay inv.; Jumper Y1 - Z1Latching; Jumper Y1 - Z2

General data:Ambient temperature:-20 to 55°C.Storage temperature:-40 to 80°C.Mounting: 35mm DIN-rail (EN50022).Terminals: Screw terminals with dual compartment.

Terminal screws are combined crosshead/slotted. Up to 2 x 2,5mm2 wire (2 x 1,5mm2

inc. ferrule).Recommended torque, 0,5Nm.Max 0,7 Nm. (VDE0609-1).Terminal identification in accordance withDIN46199/EN50005.

Indicators: Green LED = operating voltage.Red LED = relay switched on.

Protection: IP20.Electrical isolation: 3,75kVAC (1 min.) between input, supply

and relay output (EN60950).Housing: Noryl (GE), UL94V1.Terminal block: Noryl (GE), UL94V0.Weight: ~180 g.

0,1 0,2 0,5 1,0 5,0 8,0

300

200

100

50

20

2,0 I [A]

U [V]

16 18

15

µ

Relayinverted

Latchactive

Input 0 L- +

AC supplyDC supply

16 18

A1Y1

15Y2

Z1Z2

A2

N-(0V)

L (24/115/230/400)+ (24V)

SPECIFICATIONSMXV-20 is designed and developed with regard to relevant specifica-tions:• EN60204-1 / VDE0113 electrical material on machines.• VDE0110 / IEC664 Isolation specifications/creepage and clear- ance distances.• Electrical safety in accordance with EN61010.• IEC414 Safety regulations for control and monitoring equipment.• EMC: Emission EN50081-1.

Immunity EN50082-2.• Humidity in accordance with IEC68-2-3; RH=95%, 40°C.• Vibration in accordance with IEC68-2-6:• Shock when mounted, in accordance with IEC68-2-27.

MXV-20 is CE-marked in accordance with EMC-and the LowVoltage Directive.

OUTPUT LOAD DIAGRAMS

Fig. 1

Fig. 2

Page 18: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

55

Control & Monitoring Relays Single Phase Current Relay MXC-10

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

MC

U-1

0D

V/A

VD

C/A

CM

CU

-10

MC

U-1

0P

/N/T

MC

U-1

0J/

K/S

/RM

CU

-10

UM

XP

-10

MX

C-3

0M

XV

-10

MX

C-2

0M

XV

-20

MX

V-3

0M

CP

-10

INT

RO

...M

XP

-20

MX

L-10

MX

T-10

MX

C-1

047

.98

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

DESCRIPTION

A relay for monitoring AC or DC Current via an internal shunt.The relay is delivered in two variations for over- or under-current.Over-current:When the monitored current rises and reaches the determinedsetpoint, which is adjusted on the front panel, the relay energises.When the current drops and passes the setpoint, minus the hyster-esis which is adjustable on the front, the relay de-energises.Under-current:When the monitored current drops and reaches the determinedsetpoint, which is adjusted on the front panel, the relay energises.When the current rises and passes the setpoint, plus the hysteresiswhich is adjustable on the front, the relay de-energisesThere is also a latch function where the relay after energising willremain energised, regardless of input current, until the latch jumperor the operating voltage is disconnected. Typically used in safetycircuits. The contact function of the relay can also be inverted.The relay has an analogue, 2-10V DC, output which when con-nected to an external voltmeter can be used for the accurateadjustment of setpoint.

Features

• Monitoring of 4mA - 2A AC/DC, in 5 ranges, in one version.• Adjustable setpoint.• Adjustable hysteresis 0,5-20%.• Automatic locking function (Latch).• Inversion of the relay function.• Output SPDT and 2-10V DC referenced to the setpoint.• Operating voltage 24VDC , 24/115VAC or 24/230VAC.

VERSIONS/ORDERING CODES

Type: MXC-10. 230. 1Single phase current relay MXC-10

Supply voltage24V DC 924115V AC/ 24V AC 115230V AC / 24V AC 230

Over/under currentOver current 1Under current 2

OPERATION

Over current, code 1

Under current, code 2

MECHANICAL DIMENSIONS

hysteresis

latch

setpoint

supply

inv

inv

supplyhysteresis

latch

setpoint

inv

inv

80.0

mm

104.0 mm

80.0

mm

22.5 mm

Page 19: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

54

Single Phase Current Relay MXC-10Control & Monitoring Relays

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

47.9

8

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

SPECIFICATIONS:MXC-10 is designed and developed with regard to relevant specifica-tions:• EN60204-1 / VDE0113 electrical material on machines.• VDE0110 / IEC664 Isolation specifications/creepage and clear-ance distances.• Electrical safety in accordance with EN61010.• IEC414 Safety regulations for control and monitoring equipment.• EMC: Emission EN50081-1.

Immunity EN50082-2.• Humidity in accordance with IEC68-2-3; RH=95%, 40°CVibration in accordance with IEC68-2-6:• Shock when mounted, in accordance with IEC68-2-27.

MXC-10 is CE-marked in accordance with EMC- and the LowVoltage Directive.

OUTPUT LOAD DIAGRAMS

Fig.1

Input: Terminals:4-20mA10-50mA Y1/Y240-200mA

100-500mA Y1/Y30,4-2A

Coding:Relay inverter.Jumper Y1-Z1

Latching, Jumper Y1-Z2

Analogue output 2-10V DC;X1 = (+) VY1 = (-) 0

TECHNICAL DATA

Input:Input signal: Imax: Impedance RI: Terminals:4-20mA AC/DC;10-50mA AC/DC; 340mA 50ohm Y1/Y240-200mA AC/DC;100-500mA AC/DC;0,4-2A AC/DC; 5A 0,1ohm Y1/Y3

Frequency: 45-65 Hz.Temperature drift: Max. 0,05%/°C.Setting accuracy: Typically ± 10%.Hysteresis: 0,5-20% of chosen range,adjustableResponse time: time constant τ = 0,8s,

Worst case of response time max. 5 x τ.

Output:SPDT relay: Contact material, AgNi 0,15 with hardened

gold plating Au.Max load AC, 8A/240V AC (cosϕ=1)Max. breaking capacity 2000VA.Inductive load. See fig. 1.Max load DC, 8A/24V DCMax. breaking capacity 50-270W, See fig.2.

Max. in rushcurrent: 15A (max. 4s/duty cycle less than 10%).Min. in rushcurrent: 10mA, 24V DC.Frequency : Max.1000 operations pr.hour.Life time: Mech. Min.3 x 107 operations.

Elect. Min 1x105 operationswith full load.

Delay: <20ms.

Analogue output: 2-10V DC, refers to setpoint in chosenrange.

Imax=2mA /Rload >5kOhm.Accuracy better than ± 0,5%.

Supply voltage:Versions: 924=24V DC (20,4-27,6)V DC.

115=24/115V AC (20,4-27,6 /98-132)V AC.230=24/230V AC (20,4-27,6/196-264)V AC.

Net frequency: 45-65Hz.

0,1 0,2 0,5 1,0 5,0 8,0

300

200

100

50

20

2,0 I [A]

U [V]

Fig. 2

0,9

0,8

0,7

0,6

0,5

0,4

1,0

0,2 0,4 0,6 0,8 1,0cosϕ

Red

uct

ion

fac

tor

WIRING DIAGRAM

16 18

15 Y1

X1

-

+

µ

Relayinverted

Latchactive

Input 0 LLOW LHIGH

- + +

AC supplyDC supply

16 18

A1Y1

15Y2

X1A3

Z1Y3

Z2

A2

N-(0V)

L(24V)L (115/230)+ (24V)

Consumption: AC; 3VA.DC; 2W.

General data:Ambient temperature:-20 to 55°C.Storage temperature:-40 to 80°C.Mounting: 35mm DIN-rail (EN50022).Terminals: Screw terminals with dual compartment.

Terminal screws are combined crosshead/slotted.Up to 2 x 2,5mm2 wire (2 x 1,5mm2 inc.ferrule).Recommended torque, 0,5 Nm.,Max 0,7 Nm. (VDE0609-1).Terminal identification in accordance withDIN46199/EN50005.

Indicators: Green LED = working voltage.Red LED = relay switched on.

Protection: IP20.Electrical isolation: 3,75kVAC (1 min.) between input,

supply and relay output (EN60950).Note: No galvanic isolation between inputand analogue output.

Housing: Noryl (GE), UL94V1.Terminal block: Noryl (GE), UL94V0.Weight: 180 g.

Page 20: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

57

Control & Monitoring Relays Single Phase Current Relay MXC-20

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

47.9

8D

C/A

CM

CU

-10

MC

U-1

0P

/N/T

MC

U-1

0J/

K/S

/RM

CU

-10

UM

XP

-10

MX

C-3

0M

XV

-10

MX

V-2

0M

XV

-30

MX

C-1

0M

CP

-10

INT

RO

...M

XP

-20

MX

L-10

MX

T-10

MC

U-1

0D

V/A

VM

XC

-20

PRELIMINARY

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

DESCRIPTION

Single phase current relay for detecting a level of AC or DC current.

When the monitored current rises and reaches the determinedsetpoint, which is adjusted on the front panel, the relay energises.When the current drops and passes the setpoint, minus thehysteresis which is adjustable on the front, the relay de-energises.With inverted relay function the internal relay work the opposite way.

The Current Relay has a latch function where the relay afterenergising will remain energised, regardless of input current, untilthe latch jumper or the operating current is disconnected. Typicallyused in safety circuits.

Features

• Monitoring of 10mA - 5A AC/DC in 5 ranges.• Adjustable setpoint.• Adjustable hysteresis 3-35%.• Automatic locking function (Latch).• Inversion of the relay function.• Output SPDT.• Operating voltage 24VDC , 24VAC, 115VAC, 230VAC or 400VAC.

VERSIONS/ORDERING CODES

Type: MXC-20. 230. 1Single phase current relay MXC-20

Supply voltage24V DC 92424V AC 024115V AC 115230V AC 230400V AC 400

Measuring range:10-50mA 140-200mA 20,1A-0,5A 30,4A-2A 41-5A 5

OPERATION

MECHANICAL DIMENSIONS

hysteresis

latch

setpoint

supply

inv

inv

80.0

mm

104.0 mm

80.0

mm

22.5 mm

Page 21: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

56

Single Phase Current Relay MXC-20Control & Monitoring Relays

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

06.9

9

PRELIMINARY

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

SPECIFICATIONS:MXC-20 is designed and developed with regard to relevant specifica-tions:• EN60204-1 / VDE0113 electrical material on machines.• VDE0110 / IEC664 Isolation specifications/creepage and clear-ance distances.• Electrical safety in accordance with EN61010.• IEC414 Safety regulations for control and monitoring equipment.• EMC: Emission EN50081-1.

Immunity EN50082-2.• Humidity in accordance with IEC68-2-3; RH=95%, 40°CVibration in accordance with IEC68-2-6:• Shock when mounted, in accordance with IEC68-2-27.

MXC-20 is CE-marked in accordance with EMC- and the LowVoltage Directive.

OUTPUT LOAD DIAGRAMS

Fig.1

Coding:Relay inverter: Jumper Y1-Z1Latching: Jumper Y1-Z2

TECHNICAL DATA

InputInput signal Impedance Imax10-50mA AC/DC 4,7Ohm 0,7A40-200mA AC/DC 1Ohm 1,4A0,1-0,5A AC/DC 0,47Ohm 2,5A0,4-2A AC/DC 0,1Ohm 5,5A1-5A AC/DC 0,047Ohm 8A

Frequency atAC-input: 45-65 Hz.Accuracy: 1%.Temperature drift Max. 0,05%/°C.Setting accuracy: Typically ± 10%.Hysteresis: Adjustable 3-35%.Response time: Time constant τ = 0,2s,

Worst case of response time max. 5 x τ.Voltage drop: 0,2V@FS.

Output:SPDT relay

Contact material: AgNi 0,15 with hardened gold plating Au.Max load AC: 8A/240V AC (cosϕ=1)

Max. breaking capacity 2000VA, Inductiveload. See fig. 1.

Max load DC: 8A/24V DCMax. breaking capacity 50-270W see fig. 2.

Max. in rush current: 15A (max. 4s/duty cycle less than 10%).Min. in rush current: 10mA, 24V DC.Frequency : Max. 1000 operations pr. hour.Life span: Mech. Min. 3 x 107 operations.

Elect. Min 1x 105 operations with full load.Delay; <20ms.

Supply voltage:Versions: 924=24V DC (20,4-27,6 )V DC.

024=24V AC (20,4-27,6 )V AC.115=115V AC (98-132)V AC.230=230V AC (196-264)V AC.400=400VAC (340-460)V AC.

Net frequency: 40-70Hz.Consumption: AC; max. 3VA

DC; max. 2W

General data:Ambient temperature: -20 to 55°C.Storage temperature: -40 to 80°C.Mounting: 35mm DIN-rail (EN50022).Terminals: Screw terminals with dual compartment.

Terminal screws are combined crosshead/slotted. Up to 2 x 2,5mm2 wire (2 x 1,5mm2

inc. ferrule).Recommended torque, 0,5Nm.Max. 0,7 Nm. (VDE0609-1).Terminal identification in accordance withDIN46199/EN50005.

Indicators: Green LED = operating voltage.Red LED = relay switched on.

Protection: IP20.Electrical isolation: 3,75kVAC (1 min.) between input, supply

and relay output (EN61010).

Housing: Noryl (GE), UL94V1. BlackTerminal block: Noryl (GE), UL94V0. BlackWeight: 180 g.

0,1 0,2 0,5 1,0 5,0 8,0

300

200

100

50

20

2,0 I [A]

U [V]

Fig. 2

0,9

0,8

0,7

0,6

0,5

0,4

1,0

0,2 0,4 0,6 0,8 1,0cosϕ

Red

uct

ion

fac

tor

WIRING DIAGRAM

16 18

15

µ

Relayinverted

Latchactive

Input 0 L- +

AC supplyDC supply

16 18

A1Y1

15Y2

Z1Z2

A2

N-(0V)

L (24/115/230/400)+ (24V)

Page 22: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

59

Single Phase High Current Relay via External Shunts MXC-30Control & Monitoring Relays

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

MC

U-1

0D

V/A

VD

C/A

CM

CU

-10

MC

U-1

0P

/N/T

MC

U-1

0J/

K/S

/RM

CU

-10

UM

XP

-10

MX

V-1

0M

XC

-20

MX

V-2

0M

XV

-30

MC

P-1

0IN

TR

O...

MX

P-2

0M

XL-

10M

XT-

10M

XC

-10

MX

C-3

047

.98

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

VERSIONS/ORDERING CODES

Type: MXC-30 230 1Single phase high current relay. MXC-30

Supply voltage:24V DC. 924115V AC/ 24V AC. 115230V AC / 24V AC. 230

Over/under current:Over current. 1Under current. 2

DESCRIPTION

A relay for monitoring high AC or DC current by connecting ACcurrent transformator with secundary current of 0-1,0A AC or a DCshunt with voltage drop of 0-60mV DC.The relay is delivered in two variations for over-or under-current.Over-current:When the monitored current rises and reaches the determinedsetpoint, which is adjusted on the front panel, the relay energises.When the current drops and passes the setpoint, minus the hyster-esis which is adjustable on the front, the relay de-energises.Under-current:When the monitored current drops and reaches the determinedsetpoint, which is adjusted on the front panel, the relay energises.When the current rises and passes the setpoint, plus the hysteresiswhich is adjustable on the front, the relay de-energisesThere is also a latch function where the relay after energising willremain energised, regardless of input current, until the latch jumperor the operating voltage is disconnected. Typically used in safetycircuits. The contact function of the relay can also be inverted.The relay has an analogue, 2-10V DC, output which when con-nected to an external voltmeter can be used for the accurateadjustment of setpoint.

Features:

• Monitoring of up to 500A, range depend of the connected ACcurrent transformator or DC shunt.• Adjustable setpoint and hysteresis.• Latch function and inversion of the relay function.• Output SPDT and 2-10V DC referenced to the setpoint.• Operating voltage 24VDC , 24/115VAC or 24/230VAC.

OPERATION

Over current, code 1

Under current, code 2

MECHANICAL DIMENSIONS

hysteresis

latch

setpoint

supply

inv

inv

supplyhysteresis

latch

setpoint

inv

inv

80.0

mm

104.0 mm

80.0

mm

22.5 mm

Page 23: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

58

Control & Monitoring RelaysSingle Phase High Current Relay via External Shunts MXC-30

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

06.9

9

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

OUTPUT LOAD DIAGRAMS

Fig.1

Fig. 2

SPECIFICATIONS

MXC-30 is designed and developed with regard to relevant specifica-tions:• EN60204-1 / VDE0113 electrical material on machines.• VDE0110 / IEC664 Isolation specifications/creepage and clear-ance distances.• Electrical safety in accordance with EN61010.• IEC414 Safety regulations for control and monitoring equipment.• EMC: Emission EN50081-1.

Immunity EN50082-2.• Humidity in accordance with IEC68-2-3; RH=95%, 40°C• Vibration in accordance with IEC68-2-6:• Shock when mounted, in accordance with IEC68-2-27.

MXC-30 is CE-marked in accordance with EMC- and the LowVoltage Directive.

TECHNICAL DATA

Input:Input signal:0-60mV DC; Vmax = 10V0-1,0A AC; Imax = 1,4ARMS

Temperature drift: Max. 0,05%/°C.Setting accuracy: Typically ± 10%.Hysteresis: 3-30% of chosen range, adjustable.Response time: Time constant τ = 0,12s,

Worst case of response time max. 5 x τ.

Output:SPDT relay: Contact material, AgNi 0,15 with hardened

gold plating Au.Max. load AC, 8A/240V AC (cosϕ=1)Max. breaking capacity 2000VA.Inductive load. See fig. 1.Max. load DC, 8A/24V DCMax. breaking capacity 50-270W, See fig. 2.

Max. in rushcurrent: 15A (max. 4s/duty cycle less than 10%).Min. in rushcurrent: 10mA, 24V DC.Frequency : Max. 1000 operations pr.hour.Life time: Mech. Min. 3 x 107 operations.

Elect. Min. 1x 105 operations with full load.Delay; <20ms.

Analogue output: 2-10V DC, refers to setpoint in chosen range.Imax=2mA /Rload >5kOhm.Accuracy better than ± 0,5%.

Supply voltage:Versions: 924=24V DC (20,4-27,6)V DC.

115=24/115V AC (20,4-27,6 /98-132)V AC.230=24/230V AC (20,4-27,6/196-264)V AC.

Net frequency: 45-65Hz.Consumption: AC; 3VA.

DC; 2W.

0,9

0,8

0,7

0,6

0,5

0,4

1,0

0,2 0,4 0,6 0,8 1,0cosϕ

Red

uct

ion

fac

tor

WIRING DIAGRAM

General data:Ambient temperature:-20 to 55°C.Storage temperature:-40 to 80°C.Mounting: 35mm DIN-rail (EN50022).Terminals: Screw terminals with dual compartment.

Terminal screws are combined crosshead/slotted.Up to 2 x 2,5mm2 wire (2 x 1,5mm2 inc.ferrule).Recommended torque, 0,5 Nm.,Max. 0,7 Nm. (VDE0609-1).

Indicators: Green LED = working voltage.Red LED = relay on.

Protection: IP20.Electrical isolation: 3,75kVAC (1 min.) between i supply and

output (EN60950).Housing: Noryl (GE), UL94V1.Terminal block: Noryl (GE), UL94V0.Weight: Approx. 200g.

Input: Terminals:0-60mVDC Y1/Y20-1,0A AC Y1/Y3

Coding:Relay inverter Jumper Y1- Z1Latching, Jumper Y1- Z2

Analogue output 2-10V DC;X1 = (+) V

Y1 = (-) 0

15

16 18

15 Y1

X1

Relayinverted

Latchactive

-

+

Input

µ

AC supplyDC supply

mV DC

A AC~

÷ +

~

16 18

A1Y1

15Y2

X1A3

Z1Y3

Z2

A2

L(24V)L (115/230)+ (24V)

N-(0V)

0,1 0,2 0,5 1,0 5,0 8,0

300

200

100

50

20

2,0 I [A]

U [V]

DC

Vo

ltag

e

ACCESSORIES

• Brodersen current transformators: Type AAT-xxx.x• Brodersen DC current shunts: Type AAS-xxx

Page 24: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

61

47.9

8

3-Phase Voltage Relay MXV-30Control & Monitoring Relays

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

MC

U-1

0D

V/A

VD

C/A

CM

CU

-10

MC

U-1

0P

/N/T

MC

U-1

0J/

K/S

/RM

CU

-10

UM

XP

-10

MX

V-1

0M

XC

-20

MX

V-2

0M

CP

-10

INT

RO

...M

XP

-20

MX

L-10

MX

T-10

MX

C-1

0M

XC

-30

MX

V-3

0

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

DESCRIPTION

A relay for monitoring a 3-phase AC power supply with/withoutNeutral. When the voltage of the 3 phases U,V,W (L1, L2, L3) arewithin the range, adjustable on the front, the relay is energised. Ifone or more of the phase voltages moves outside the limits, therelay de-energises. A LED indicates over or under voltage. Whenall the voltages are again within the limits the relay will re-energise.There is also a latch function where the relay after de-energising willremain de-energised, regardless of input voltage, until the latchjumper or the operating voltage is disconnected. Typically used insafety circuits. LED indication is still available when latched.With connection of Neutral the measuring abilities are optimal, asNeutral works as a measuring reference. Without Neutral, thephase monitoring relay generates a Neutral reference from theconnected phases.Note: 3x400 gives a nominal voltage between phases of 400VAC.The voltage between Phase and Neutral will be 230V AC.

Features• Monitoring of over and under voltage, on 3 phase power supplywith or without Neutral.• Adjustable upper and lower voltage limits (80-99% /101-120% ofUn).• Automatic locking (Latch).• Output SPDT.• Separate operating voltage 230V AC, or 400V AC.

VERSIONS/ORDERING CODES

Type: MXV-30 230 / 2303-phase voltage relay MXV-30

Supply voltage230V AC 230400V AC 400

Measurement voltage3 x 230V AC (132V L/N) 2303 x 400 V AC (230V L/N) 400

OPERATION

Over and under voltage

UL1

supply

VL2

WL3

latch

MECHANICAL DIMENSIONS

80.0

mm

104.0 mm

80.0

mm

22.5 mm

Page 25: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

60

3-Phase Voltage Relay MXV-30Control & Monitoring Relays

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

47.9

8

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

TECHNICAL DATA

Input:Input signal Impedance UMAX3 x 230V AC+N 316kOhm 600V AC3 x 400V AC+N 560kOhm 600V AC

Frequency: 45-65Hz.Measuring cycle: 80ms.Response time: τ = 0,5s, worstcase 5 x τ.Temperature drift: Max.0,05%/°C.Setting accuracy: Un = Typically ± 3%.Hysteresis: Set 2%.

Output:SPDT relay: Contact material, AgNi 0,15 with hardened

gold plating Au.Max. load AC, 8A/240V AC (cos ϕ=1)Max. breaking capacity2000VA . Inductive load. See fig. 1.Max. load DC, 8A/24V DCMax. breaking capacity 50-270W. See fig. 2.

Max. in rushcurrent: 15A (max. 4s/duty cycle less than 10%).Min. in rushcurrent: 10mA, 24V DC.Frequency : Max. 1000 operations pr. hour.Life time: Mech. Min. 3 x 107 operations

Elect. Min. 1x 105 operations with full load.Delay: <20ms.

Supply voltage: 230V AC (184-276V).400V AC (320-480V).

Consumption: 3VA.

SPECIFICATIONS:MXV-30 is designed and developed with regard to relevant specifi-cations:• EN60204-1 / VDE0113 electrical material on machines.• VDE0110 / IEC664 Isolation specifications/creepage and clear-ance distances.• Electrical safety in accordance with EN61010.• IEC414 Safety regulations for control and monitoring equipment.• EMC: Emission EN50081-1.

Immunity EN50082-2.• Humidity in accordance with IEC68-2-3; RH=95%, 40°C.• Vibration in accordance with IEC68-2-6:.• Shock when mounted, in accordance with IEC68-2-27.

MXV-30 is CE-marked in accordance with EMC-and the Low Volt-age Directive.

OUTPUT LOAD DIAGRAMS

Fig. 1

Fig. 2

0,1 0,2 0,5 1,0 5,0 8,0

300

200

100

50

20

2,0 I [A]

U [V]

0,9

0,8

0,7

0,6

0,5

0,4

1,0

0,2 0,4 0,6 0,8 1,0cosϕ

Red

uct

ion

fac

tor

General data:Ambient temperature:-20 to 55°C.Storage temperature:-40 to 80°C.Mounting: 35mm DIN-rail (EN50022).Terminals: Screw terminals with dual compartment.

Terminal screws are combined crosshead/slotted.Up to 2 x 2,5mm2 wire (2 x 1,5mm2 inc.ferrule).Recommended torque, 0,5Nm.Max. 0,7 Nm. (VDE0609-1).Terminal identification in accordance withDIN46199/EN50005.

Indicators: Red LED = over voltage (failure-relayoff).Red LED = under voltage (failure-relayoff).

Protection: IP20.Electric isolation: 3,75kVAC (1 min.) between input, supply

and relay output (EN60950).Housing: Noryl (GE), UL94V1.Terminal block: Noryl (GE), UL94V0.Weight: 180 g.

16 18

15

Latchactive

Input L1 L2 L3 N

µ

AC supply

16 18

A1U

15V

Z1

NW

Z2

A2

L N

WIRING DIAGRAM

Coding:Latching: Jumper, Z1-Z2

Phases can be connected in any order, as the phase sequence isnot of importance.

Page 26: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

63

Control & Monitoring Relays3-Phase Monitoring Relay MXP-10

47.9

8

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

MC

U-1

0D

V/A

VD

C/A

CM

CU

-10

MC

U-1

0P

/N/T

MC

U-1

0J/

K/S

/RM

CU

-10

UM

XV

-10

MX

C-2

0M

XV

-20

MX

V-3

0M

CP

-10

INT

RO

...M

XP

-20

MX

L-10

MX

T-10

MX

C-1

0M

XC

-30

MX

P-1

0

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

VERSION/ORDERING CODES

Type: MXP-10 230Phase monitoring relay MXP-10

Supply voltage/measuring voltage3 x 115V AC 1153 x 230V AC 2303 x 400V AC 400

DESCRIPTION

A relay for monitoring a 3-phase AC power supply with or withoutNeutral. The relay monitors that all phases are available and in thecorrect phase sequence (U,V,W), that none of the phases areshifted more than 20°C in relation to each other and that one or moreof the phase voltages are not too low. When all three monitoringcriteria are fulfilled the relay is activated. If one or more of the criteriaare not fulfilled the relay de-energises and a red LED indicatesfailure. The nominal phase voltage is adjustable ± 15% of theselected voltage version (3 x 115/3x230/3x400VAC). The low-voltage limit is also adjustable from 60-98% thus allowing detectionof a motor-generated phase.With connection of Neutral the measuring abilities are optimal, asNeutral works as a measuring reference. Without Neutral, the phasemonitoring relay generates a Neutral reference from the connectedphases.

Features• Monitoring of

• Phase rotation• Phase shift less than 20°• Low voltage

• Adjustable measuring voltage Un +/- 15% of rated voltage Un.• Low voltage detection, adjustable 60- 98% of measuring voltageUn.• Output SPTD.• Operating voltage via phases V and W (L2 and L3).

OPERATION

Voltage monitoring

Phase monitoring

Examples of types of phase error:1. Motor-generated phase, for example, when L1 is disconnected toan unloaded or lightly loaded 3-phase motor (∆ϕ>20°).2.Ohmic load or heavily loaded 3-phased motor, where L2 is dis-connected (∆ϕ=180°).3.Reversed phase sequence (L2 and L3) (∆ϕ=120°).

OPTION:Can be delivered with separate supply voltage

MECHANICAL DIMENSIONS

L1

L2

L3

60-9

8% U

N

60-9

8% U

N

80.0

mm

104.0 mm

80.0

mm

22.5 mm

L1

L2

L3

Page 27: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

62

Control & Monitoring Relays3-Phase Monitoring Relay MXP-10

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

47.9

8

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

16 18

15

µ

Input/ L1 L2 L3 NSupply

Separatesupply

Optional

16 18

A1U

15V

NW

A2

L N

SPECIFICATIONS:MXP-10 is designed and developed with regard to relevant specifi-cations:• EN60204-1 / VDE0113 electrical material on machines.• VDE0110 / IEC664 Isolation specifications/creepage andclearance distances.• Electrical safety in accordance with EN61010.• IEC414 Safety regulations for control and monitoring equipment.•EMC: Emission EN50081-1

Immunity EN50082-2• Humidity in accordance with IEC68-2-3; RH=95%, 40°C• Vibration in accordance with IEC68-2-6:• Shock when mounted, in accordance with IEC68-2-27.

MXP-10 is CE-marked in accordance with EMC-and the Low Volt-age Directive.

OUTPUT LOAD DIAGRAMS

Fig. 1

Fig. 2

WIRING DIAGRAMTECHNICAL DATA

Input:Input signal Impedance Umax3 x 115V AC + N 150 kOhm 600V AC3 x 230V AC + N 316 kOhm 600V AC3 x 400V AC + N 560 kOhm 600V AC

Frequency: 47-53Hz.Measuring cycle: 80ms.Temperature drift: Max. 0,05%/°C.Response time: τ = 0.2s, worstcase 5 x τ.Setting accuracy: Un = Typically ±3V AC.

Low voltage typically ±1%.

Output:SPDT relay: Contact material;AgNi0.15 with hardened gold

plating Au.Max. Load AC; 8A/240VAC (cosϕ=1)Max. breaking capacity 2000VA.Inductive load. See fig. 1.Max. load DC, 8A/24V DCMax. breaking capacity 50- 270W. See fig. 2.

Max. in rushcurrent: 15A (max. 4s/duty cycle less

than 10%).Min. in rushcurrent: 10mA, 24V DC.Frequency : Max. 1000 operations pr.

hour.Life time: Mech.Min. 3 x 107 operations.

Elect.Min. 1 x 105 operations.with full load.

Delay; <20ms.

Supply voltage:Supplied via phase: V(L2) and W(L3).Consumption: 3VA.

General data:Ambient temperature:-20 to 55°C.Storage temperature:-40 to 80°C.

Mounting: 35mm DIN-rail (EN50022).

Terminals: Screw terminals with dual compartment.Terminal screws are combined crosshead/slotted.Up to 2 x 2.5mm2 wire(2 x 1.5mm2 inc.ferrule).Recommended torque, 0.5 Nm.,

0,1 0,2 0,5 1,0 5,0 8,0

300

200

100

50

20

2,0 I [A]

U [V]

0,9

0,8

0,7

0,6

0,5

0,4

1,0

0,2 0,4 0,6 0,8 1,0cosϕ

Red

uct

ion

fac

tor

Max. 0,7 Nm. (VDE0609-1).Terminal identification in accordance withDIN46199/EN50005.

Indicators: Green LED = operating voltage.RedLED = relay off - failure.

Protection: IP20.

Electric isolation: 3.75kVAC (1 min.) between input,supply and relay uotput (EN60950).

Housing: Noryl (GE), UL94V1.

Terminal block: Noryl (GE), UL94V0.

Weight: 180 g.

Page 28: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

65

Control & Monitoring Relays Phase Monitoring Relay MXP-20

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

MC

U-1

0D

V/A

VD

C/A

CM

CU

-10

MC

U-1

0P

/N/T

MC

U-1

0J/

K/S

/RM

CU

-10

UM

XP

-10

MX

V-1

0M

XC

-20

MX

V-2

0M

XV

-30

MC

P-1

0IN

TR

O...

MX

L-10

MX

T-10

MX

C-1

0M

XC

-30

MX

P-2

047

.98

PRELIMINARY

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

DESCRIPTION

A relay for monitoring a 3-phase AC power supply with or withoutNeutral. The relay monitors that all phases are available and in thecorrect phase sequence L1, L2, L3 (U,V,W), that none of the phasesare shifted more than 20° in relation to each other and that one or moreof the phase voltages are not too low. When all three monitoring criteriaare fulfilled the relay is activated. If one or more of the criteria are notfulfilled the relay de-energises and a red LED indicates failure.Fixed limits for energizing and de-energizing the single output relay.With connection of Neutral the measuring abilities are optimal, asNeutral works as a measuring reference. Without Neutral, the phasemonitoring relay generates a Neutral reference from the connectedphases.

Features:

• Monitoring of• Phase rotation• Phase shift less than 20°• Low voltage

• Output SPTD.• Operating voltage via phases L2 and L3 (V and W).• Delay= 0,5s to prevent faulty energization and deenergizationcaused by short interferences.

VERSION/ORDERING CODES

Type: MXP-20 230Phase monitoring relay. MXP-20

Supply voltage/measuring voltage:3 x 115V AC 1153 x 230V AC 2303 x 400V AC 400

OPERATION

Voltage monitoring

Phase monitoring

Examples of types of phase error :1. Motor-generated phase, for example, when L1 is disconnected toan unloaded or lightly loaded 3-phase motor (∆ϕ>20°).2. Ohmic load or heavily loaded 3-phased motor, where L2 is dis-connected (∆ϕ=180°).3. Reversed phase sequence (L2 and L3) (∆ϕ=120°).

MECHANICAL DIMENSIONS

L1

L2

L3

75-8

5% U

N

75-8

5% U

N

L1

L2

L3

80.0

mm

104.0 mm

80.0

mm

22.5 mm

Page 29: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

64

Control & Monitoring RelaysPhase Monitoring Relay MXP-20

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

47.9

8

PRELIMINARY

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

SPECIFICATIONS:MXP-20 is designed and developed with regard to relevant specifi-cations:• EN60204-1 / VDE0113 electrical material on machines.• VDE0110 / IEC664 Isolation specifications/creepage andclearance distances.• Electrical safety in accordance with EN61010.• IEC414 Safety regulations for control and monitoring equipment.• EMC: Emission EN50081-1

Immunity EN50082-2• Humidity in accordance with IEC68-2-3; RH=95%, 40°C• Vibration in accordance with IEC68-2-6:• Shock when mounted, in accordance with IEC68-2-27.

MXP-20 is CE-marked in accordance with EMC-and the Low Volt-age Directive.

OUTPUT LOAD DIAGRAMS

Fig. 1

Fig. 2

TECHNICAL DATA

Input:Input signal Impedance Umax3 x 115V AC + N 150 kOhm 300V AC3 x 230V AC + N 316 kOhm 435V AC3 x 400V AC + N 560 kOhm 580V AC

Frequency: 45-66Hz.

Temperature drift: All specifications apply for the specified temperature range.

Delay: 0.3s-0.7s.

Phase measuring:With neutral: Fault: ∆ϕ >25°, typically ∆ϕ >20°Without neutral: Fault: ∆ϕ >50°, typically ∆ϕ >40°

Voltage measuring:With neutral:Change on 1 phase:

Energized output relay: >90% of Vnom., typically by >80%.Fault: <65% of Vnom., typically by <70%.

Change of 3 phases, symm.:Energized output relay: 90% of Vnom.Fault: <80% of Vnom., typically by <85%.

Without neutral:Change on 1 phase:

Energized output relay: >90% of Vnom., typically by >80%.Fault: <50% of Vnom., typically by <60%.

Change of 3 phases, symm.:energized output relay: 90% of Vnom., typically by >85%.Fault: <75% of Vnom., typically by <80%.

Output:SPDT relay: Contact material;AgNi0.15 with hardened

gold plating Au.Max. Load AC; 8A/240V AC (cosϕ=1)Max. breaking capacity2000VA. Inductive load. See fig. 1.Max. load DC, 8A/24V DCMax. breaking capacity 50- 270W. See fig. 2.

Max. in rushcurrent: 15A (max. 4s/duty cycle less

than 10%).Min. in rushcurrent: 10mA, 24V DC.Frequency : Max. 1000 operations pr. hour.Life time: Mech. Min. 3 x 107 operations.Elect: Min. 1x 105 operations with full load.Delay: <20ms.

WIRING DIAGRAM

0,9

0,8

0,7

0,6

0,5

0,4

1,0

0,2 0,4 0,6 0,8 1,0cosϕ

Red

uct

ion

fac

tor

0,1 0,2 0,5 1,0 5,0 8,0

300

200

100

50

20

2,0 I [A]

U [V]

Supply voltage:Supplied via phase: V(L2) and W(L3).Consumption: 3VA.

General data:Ambient temperature:-20 to 55°C.Storage temperature:-40 to 80°C.Mounting: 35mm DIN-rail (EN50022)Terminals: Screw terminals with dual compartment.

Terminal screws are combined crosshead/slotted.Up to 2 x 2.5mm2 wire(2 x 1.5mm2 inc.ferrule).Recommended torque, 0.5 Nm.,Max. 0,7 Nm. (VDE0609-1).Terminal identification in accordance withDIN46199/EN50005.

Weight: 180 g.Indicators: Green LED = operating voltage.

Red LED = relay off - failure.Protection: IP20.Electric isolation: 3.75kVAC (1 min.) between input,

supply and relay output (EN60950).Housing: Noryl (GE), UL94V1.Terminal block: Noryl (GE), UL94V0.

16 18

15

µ

Input/ L1 L2 L3 NSupply

16 18

L115L2

NL3

Page 30: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

67

Control & Monitoring Relays Level Relay MXL-10

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

MC

U-1

0D

V/A

VD

C/A

CM

CU

-10

MC

U-1

0P

/N/T

MC

U-1

0J/

K/S

/RM

CU

-10

UM

XP

-10

MX

V-1

0M

XC

-20

MX

V-2

0M

XV

-30

MC

P-1

0IN

TR

O...

MX

P-2

0M

XT-

10M

XC

-10

MX

C-3

0M

XL-

1047

.98

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

DESCRIPTION

A level control relay for most conductive fluids. With a 2 or 3 wireprobe, one or two levels in a container can be controlled.

The probe is a conducting rod, the length of which can be adjustedto the container and the levels which have to be controlled.To control 1 level (2-wire probes), one of the probes is constantlycovered by the fluid and the length of the probe dictates the level.To control 2 levels (3-wire probes), one of the probes is constantlycovered by fluid and the length of the two other probes dictates min.and max. levels.

As conductivity will differ from fluid to fluid, the sensitivity can beadjusted on the front panel, to adjust the reaction time from the timethe actual level is registered, to the relay being energised/de-energised.

Features

• Monitoring/control of levels of conducting fluids via 2 or 3 wireprobes.• Signal at max. and min. level in the same version.• Sensitivity adjustable on input 5 - 50kOhm.• Response time adjustable 0,1 - 5 sec.• Automatic locking (Latch).• Output SPDT.• Supply voltage 24/115VAC or 24/230VAC and 24VDC.

VERSION/ORDERING CODES

Type: MXL-10 230Level relay MXL-10

Supply voltage24V DC 924115V AC / 24V AC 115230V AC / 24V AC 230

OPERATION

Signal at maximum (with jumper).

Signal at minimum (without jumper)

supply

Y3 level

Y2 level

latch

Y1 Y2 Y3

supply

Y3 level

latch

Y1 Y3

supply

Y3 level

Y2 level

latch

Y1 Y2 Y3

supply

Y3 level

latch

Y1 Y3

Page 31: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

66

Control & Monitoring RelaysLevel Relay MXL-10

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

47.9

8

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

MECHANICAL DIMENSIONS

TECHNICAL DATA

Input:Sensitivity: 5kOhm-50kOhm, adjustable.Probe Voltage: Max. 12Vp-p AC, 1kHz.Probe current: Max. 360µA.Temperature drift: Max. 0,05%/°C.Hysteresis: <0,1%.Reaction time: 0,1-5s, adjustable.Probe Cabel: Max. length 100m.

Capacity max. 10nF.Isolation resistance>220kOhm.

Output:SPDT relay: Contact material, AgNi 0,15 with hardened

gold plating Au.Max. load AC: 8A/240V AC (cosϕ=1)Max. breaking capasity2000VA. Inductive load. See fig.1.Max. load DC: 8A/24V DC.Max. breaking capasity 50-270W. See fig. 2.

Max in rush current: 15A (max. 4s/duty cycle less than 10%).Min in rush current: 10mA, 24V DC.Frequency : Max. 1000 operations pr. hour.

Life time: Mech. Min. 3 x 107 operations.Elect. Min. 1 x 105 operations with full load.

Delay: <20ms.

Supply voltage:Versions: 924=24V DC (20,4-27,6)V DC

115=24/115V AC (20,4-27,6 /98-132)V AC230=24/230V AC (20,4-27,6/196-264)V AC

Net frequency: 45-65HzConsumption: AC; 3VA

DC; 2W

SPECIFICATIONS:MXL-10 is designed and developed with regard to relevant specifi-cations:• EN60204-1 / VDE0113 electrical material on machines.• VDE0110 / IEC664 Isolation specifications/creepage and clear-ance distances.• Electrical safety in accordance with EN61010.• IEC414 Safety regulations for control and monitoring equipment.• EMC: Emission EN50081-1.

Immunity EN50082-2.• Humidity in accordance with IEC68-2-3; RH=95%, 40°C.• Vibration in accordance with IEC68-2-6:.• Shock when mounted, in accordance with IEC68-2-27.

MXL-10 is CE-marked in accordance with EMC-and the Low VoltageDirective.

OUTPUT LOAD DIAGRAMS

Fig. 1

Fig. 2

0,1 0,2 0,5 1,0 5,0 8,0

300

200

100

50

20

2,0 I [A]

U [V]

0,9

0,8

0,7

0,6

0,5

0,4

1,0

0,2 0,4 0,6 0,8 1,0cosϕ

Red

uct

ion

fac

tor

80.0

mm

104.0 mm

80.0

mm

22.5 mm

16 18

15

Latchactive

Signal atmax. level

Input Com Min Max

µ

AC supplyDC supply

16 18

A1Y1

15Y2

Z1A3

Y3

Z2

A2

N-(0V)

L(24V)L (115/230)+ (24V)

Y1 Y3

Y1 Y2 Y3

WIRING DIAGRAM

One level:

Two levels:

Coding:Signal at max. level: Y1-Z1Latching, Y1-Z2

General data::

Ambient temperature:-20 to 55°C.Storage temperature:-40 to 80°C.Mounting: 35mm DIN-rail (EN50022).Terminals: Screw terminals with dual compartment.

Terminal screws are combined crosshead/slotted. Up to 2 x 2,5mm2 wire (2 x 1,5mm2

inc. ferrule).Recommended torque, 0,5Nm, max 0,7Nm(VDE0609-1).Terminal identification in accordance withDIN46199/EN50005.

Indicators: Green LED = operating voltageRed LED = relay switched on.

Protection: IP20Electric isolation: 3,75kVAC (1 min.) between input, supply

and relay output (EN60950)Housing: Noryl (GE), UL94V1.Terminal block: Noryl (GE), UL94V0.Weight: 180 g.

Page 32: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

69

Control & Monitoring RelaysThermostat Relay MXT-10

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

MC

U-1

0D

V/A

VD

C/A

CM

CU

-10

MC

U-1

0P

/N/T

MC

U-1

0J/

K/S

/RM

CU

-10

UM

XP

-10

MX

V-1

0M

XC

-20

MX

V-2

0M

XV

-30

MC

P-1

0IN

TR

O...

MX

P-2

0M

XL-

10M

XC

-10

MX

C-3

0M

XT-

1047

.98

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

OPERATION

Temperature monitoring

MECHANICAL DIMENSIONS

DESCRIPTION

A thermostat relay for the monitoring or control of temperature in therange -50 to 300°C. The probe is a standard Pt100, either 2 or 3 wire.LED indication of a non-functional probe and relay activated.When the temperature rises and reaches the determined setpoint,plus the hysteresis, which is adjusted on the front, the relay de-energises. As the temperature falls and passes the setpoint, minusthe hysteresis, the relay re-energises. By strapping 2 terminals, therelay can be inverted allowing the thermostat relay to be used for thecontrol of heating as well as cooling systems.The relay has two analogue 0-10VDC outputs, one for measuredtemperature and the other for the setpoint.

Features• 2/3 wire Pt100 input (DIN43760).• Monitoring or control of temperature - 50 to 300°C in 5 ranges inone version.• Adjustable Setpoint.• Hysteresis adjustable ±0,5-20%.• Inversion of the relay contact function - heating/cooling control.• LED indication of probe failure.• Outputs.• SPDT.• Analogue 0 - 10VDC with ref. to measuredtemperature.• Analogue 0 - 10VDC with ref. to setpoint.• Supply voltage 24VDC, 24/115VAC or 24/230VAC.

VERSIONS/ORDERING CODES

Type: MXT-10 230Thermostat relay MXT-10

Supply voltage24V DC 924115V AC / 24V AC 115230V AC / 24V AC 230

hysteresis

setpoint

supply

inv

80.0

mm

104.0 mm

80.0

mm

22.5 mm

Page 33: Control & Monitoring Relays Introduction & Selection Guide · Control & Monitoring Relays Introduction & Selection Guide United Kingdom: ... Digital control relay MCP-10 Phase monitoring

68

Thermostat Relay MXT-10Control & Monitoring Relays

United Kingdom:Tel: +44 020 8546 4283Fax: +44 020 8547 3628E-mail: [email protected]

Germany:Tel: +49 208 46954-0Fax: +49 208 46954-50E-mail: [email protected]

47.9

8

Export:Tel: +45 46 74 00 00Fax: +45 46 75 73 36E-mail: [email protected]

SPECIFICATIONS:MXT-10 is designed and developed with regard to relevant specifi-cations:• EN60204-1 / VDE0113 electrical material on machines.• VDE0110 / IEC664 Isolation specifications/creepage and clear-ance distances.• Electrical safety in accordance with EN61010.• IEC414 Safety regulations for control and monitoring equipment.• EMC: Emission EN50081-1

Immunity EN50082-2• Humidity in accordance with IEC68-2-3; RH=95%, 40°C.• Vibration in accordance with IEC68-2-6:• Shock when mounted, in accordance with IEC68-2-27.

MXT-10 is CE-marked in accordance with EMC-and the Low Volt-age Directive.

OUTPUT LOAD DIAGRAMS

Fig. 1

Fig. 2

TECHNICAL DATA

Input: Pt-100 probe(DIN 43760), 3 conductorswithcompensation for cable resistance.

Temperature range: -50-50°C0-50°C0-100°C100-200°C200-300°C

Temperature drift Max. 0,05%/°CSetting accuracy: Typically ± 10%Hysteresis: ±0,5-20% of chosen area, adjustableResponse time: time constant τ = 0,2s,

Worst case of response time max. 5 x τ

Output:SPDT relay: Contact material, AgNi 0,15 with hardened

gold plating Au.Max. load AC: 8A/240V AC (cos ϕ=1)Max. breaking capasity2000VA. Inductive load. See fig. 1.Max. load DC: 8A/24V DCMax. breaking capasity 50- 270W. See fig. 2.

Max. in rushcurrent: 15A(max. 4s/duty cycle less than 10%).Min. in rushcurrent: 10mA, 24V DCFrequency: Max. 1000 operations pr. time.Life span: Mech. Min. 3 x 107 operations

Elect. Min. 1x 105 operations with full load.Delay; <20ms.Analogue outputs: 0-10V DC, refers to setpoint and measured

temperature in chosen areas.Imax=2mA /Rload >5 kOhm.

Accuracy: Setpoint: ±1%Measured value ±5%

Supply voltage:Versions: 924=24V DC (20,4-27,6)V DC

115=24/115V AC (20,4-27,6 /98-132)V AC230=24/230V AC (20,4-27,6/196-264)V AC

Net frequency: 45-65Hz.Consumption: AC; 3VA

DC; 2W

0,1 0,2 0,5 1,0 5,0 8,0

300

200

100

50

20

2,0 I [A]

U [V]

WIRING DIAGRAM

Coding:Relay inverter, Jumper Y1-Z1

Analogue output 0-10V DCSetpoint: X1= (+) V

Y1= (-) 0

Measuredtemperature: X2=(+) V

Y1=(-) 0

General data:Ambient temperature:-20 to 55°C.Storage temperature:-40 to 80°C.Mounting: 35mm DIN-rail (EN50022).Terminals: Screw terminals with dual compartment.

Terminal screws are combined crosshead/slotted.Up to 2 x 2,5mm2 wire(2 x 1,5mm2 inc. ferrule).Recommended torque, 0,5 Nm,max. 0,7 Nm (VDE0609-1).Terminal identification in accordance withDIN46199/EN50005.

Indicators: Green LED = operating voltage.Red LED (constant)= relay switched on.Red LED (flashing)= non-functional probe.

Protection: IP20.Electric isolation: 3,75kVAC (1 min.) between input, supply

and relay output (EN60950).Note: No galvanic isolation between inputand analogue output.

Housing: Noryl (GE), UL94V1.Terminal block:Noryl (GE), UL94V0.

Weight: 180 g.

0,9

0,8

0,7

0,6

0,5

0,4

1,0

0,2 0,4 0,6 0,8 1,0cosϕ

Red

uct

ion

fac

tor

16 18

15

Inversionrelay

µ

InputPt100

Y1

X2

-

+

Y1

X1

-

+

AC supplyDC supply

16 18

A1Y1

15Y2

X1A3

Y3

X2

A2

Z1

L(24V)L (115/230)+ (24V)

N-(0V)