control of hybrid ac/dc microgrid involving energy storage...
TRANSCRIPT
0093-9994 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2016.2613981, IEEETransactions on Industry Applications
1
Abstract—This paper presents real-time coordinated control of
hybrid AC/DC microgrids involving energy storage and pulsed
loads. Grid isolated hybrid microgrid applications require special
considerations due to the intermittent generation, online energy
storage control and pulsed loads. In this work, we introduce a
comprehensive frequency and voltage control scheme for a hybrid
AC/DC microgrid consisting of a synchronous generator, solar
generation emulator and bidirectional (AC/DC and DC/DC) con-
verters. A bidirectional controlled AC/DC converter, with an
active and reactive power decoupling technique is used to link the
AC bus with the DC bus while regulating the system voltage and
frequency. A DC/DC boost converter with a maximum power
point tracking (MPPT) function is implemented to maximize the
intermittent energy generation from solar generators. Current
controlled bidirectional DC/DC converters are applied to connect
each lithium-ion battery bank to the DC bus. Lithium-ion battery
banks act as energy storage devices that serve to increase the sys-
tem resiliency by absorbing, or injecting, power. Experimental
results are presented for verification of the introduced hybrid
AC/DC power flow control scheme.
Index Terms—Microgrid, energy management, pulsed load,
energy storage, battery bank, synchrophasor.
I. INTRODUCTION
YBRID power systems are gaining popularity due to in-
creasing microgrid deployments featuring renewable
power systems connected to low voltage AC distribution sys-
tems. Furthermore, DC grids are resurging due to the devel-
opment of new semiconductor technologies and sustainable DC
power sources such as solar energy. There has also been an
increase in DC loads, such as plug-in electric vehicles (PEVs)
[5]-[7] and light emitting diodes (LEDs), connected to the grid
to save energy and decrease greenhouse gas emissions. This
growth has been motivated by environmental concerns caused
by conventional fossil fueled power plants [24].
Thus far, a variety of control strategies have been introduced
for microgrids [1]-[4].One of the major technical challenges in
microgrids is the interconnection of pulsed loads, which can
cause voltage collapse, oscillation of the angular velocity in the
generators, and degradation of the overall system performance
[22],[23], [25]. The pulsed loads draw high currents during a
This work was partially supported by grants for the Office of Naval
Re-search and the US Department of Energy (DOE). The authors are with the
Energy Systems Research Laboratory, Department of Electrical and Computer
Engineering, Florida International University, Miami, FL 33174 (e-mail:
short period of time, which can cause considerable voltage and
frequency fluctuation [22]. These disturbances can trip other
normal loads offline, causing a serious outage. The power re-
quirements of such loads can range from kilowatts to megawatts
with a charge interval on the order of seconds to minutes [23].
Power converters opened new horizons for effective inte-
gration of AC and DC distribution networks in a microgrid
operation concept [8]. Thus far, in [9]-[10], several ideas and
models of AC/DC microgrids have been proposed, but their
systems operate without the influence of the pulsed loads.
System stability and coordination control of power electronic
devices, during islanded operation modes with the influence of
pulsed loads, is still an open issue.
At the same time, various utility grids and some hybrid mi-
crogrids are increasing the penetration of renewable energy
resources [11]-[12]. The intermittent nature of wind and solar
power can quickly add up to system-wide instability that can
force generators to ramp up and down wildly, push grid pro-
tection gear into states it’s not meant to handle, or force the wind
and solar generator to shut off altogether [13].
Hybrid power systems face far more challenges when oper-
ating in islanded mode than they do in grid connected mode.
During islanded mode, the AC side can no longer be viewed as
an infinite bus, which results in load variations adversely af-
fecting the frequency and voltage of the system. If the system
has a high penetration of renewable power, the situation can be
even worse. At any time, reactive and active power flow should
be balanced between the AC and DC sides to maintain stability
on both sides of the grid [14]-[15].
To the best knowledge of the authors, a realistic coordinated,
hybrid AC/DC microgrid control considering pulsed load mit-
igation with energy storage has not yet been studied. In this
paper, a real-time coordinated control of a grid-isolated, hybrid
AC/DC microgrid, involving energy storage and pulsed loads is
studied. This microgrid can be viewed as a PEV parking garage
power system or a ship power system that utilizes sustainable
energy and is influenced by pulsed load. We introduce a com-
prehensive frequency and voltage control scheme for a hybrid
AC/DC microgrid consisting of a synchronous generator, solar
generation emulator and bidirectional (AC/DC and DC/DC)
converters. A bidirectional controlled AC/DC converter with
active and reactive power decoupling technique is used to link
the AC bus with the DC bus, while regulating the system voltage
and frequency.
Control of Hybrid AC/DC Microgrid Involving
Energy Storage and Pulsed Loads
Tan Ma, Mehmet H. Cintuglu, Student Member, IEEE, and Osama A. Mohammed, Fellow, IEEE
H
0093-9994 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2016.2613981, IEEETransactions on Industry Applications
2
A DC/DC boost converter with a maximum power point
tracking (MPPT) function is implemented to maximize the
intermittent energy generation from solar generators. Current
controlled bidirectional DC/DC converters are applied to con-
nect each lithium-ion battery bank to DC bus [16].
II. HYBRID AC/DC MICROGRID CONFIGURATION
Fig. 1 shows the complete schematics of the studied hybrid
microgrid. Fig.2 shows the DC side of the hybrid microgrid
configuration, where a photovoltaic (PV) emulator, battery
banks, and loads are connected [17], [18]. The AC and DC sides
are linked through a bidirectional three phase AC/DC converter
and a transformer. The system features constant and pulse loads
on both the AC and DC sides. The PV emulator is connected to
the DC bus as the DC energy source through a DC/DC boost
converter with MPPT functionality. Five 50Ah lithium-ion
battery banks with 51.8V terminal voltage, are connected to the
DC bus through five bi-directional DC/DC boost converters
[19]. The rated voltages of DC and AC sides are 300V and
208V phase to phase respectively. The system can be operated
in either grid-connected mode or islanding mode. To maximize
the utilization of the renewable sources, the PV emulator can be
operated in on/off maximum power point modes based on the
whole system power.
Energy balancing is handled by controlling the DC/DC boost
converter. In grid-connected mode, the proposed system can be
viewed as a PEVs car park system. The five batteries can be
viewed as five PEVs that can play the role of energy storage. By
controlling the charging process of the PEVs in the car park, the
hybrid microgrid can limit the PEVs’ charging impact to the
utility grid, and at the same time, provide some ancillary support
to the utility grid through V2G services, via frequency regula-
tion, reactive power compensation, and spinning reserve. In
islanded mode, the proposed system can be viewed as a ship
power system with solar panels. The bi-directional AC/DC
converter can take control of the AC side frequency and voltage
amplitude. The DC bus voltage is regulated by controlling the
charging and discharging of the battery banks, which also means
controlling the current flow through the bidirectional DC/DC
converter.
A. PV Panel Emulator
The PV panel can be viewed as a current source in parallel
with a diode. In this paper, the SunPower SPR-305-WHT solar
cell, with 305W maximum output power, is used. 33 cells are
used in the configuration of 11 parallel strings, with 3 serially
connected cells per string. Fig. 3 shows the non-linear P-V and
I-V electric characteristics of a single SunPower SPR-305-
WHT solar sell. Under different solar irradiations, the maxi-
mum power points of the power-voltage curves are associated
with different output voltages. Also, under certain solar irra-
diance, the output of the PV panel is varying with different
terminal voltages.
ST1 ST3 ST5
ST4 ST6 ST2
STC
STd
Rb
AC filter
RacLac
Cac
vpv+
-
Lpv Rpv
STpv
Vd
Cd
Remote Grid
Local Load
AC Pulsed Load
Synchronous Generator
Gps Clock
HMI
Phasor Data Concentrator
PMU (1) PMU (2)IED (1)
IED (2)
IED (3)
Fig. 1. Overview of AC side of hybrid microgrid configuration involving synchronous generators, inverter-based distributed energy resources, distribution line
and load models, synchrophasor, intelligent electronic devices (IED) protection setup, SCADA systems and human machine interface (HMI)
Lithium-ion battery bank
STM32F microcontroller
Signal converting circuit
Bidirectional DC-DC converter
Zigbee wireless transmitter
Converter power supply
Step-up Transformer
Grid-Tie Inverter
DC Load
L-C FilterEmbedded Controller
Fig. 2. Overview of DC side of hybrid microgrid configuration
involving bidirectional AC/DC, DC/DC converters
0093-9994 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2016.2613981, IEEETransactions on Industry Applications
3
Equations (1)-(3) show the mathematical model of the PV
panel with its output current Ipv and output voltage Vpv [19].
Related parameters are shown in Table I.
]1)))([exp(( spvs
pvsatpphppv RI
n
V
AkT
qInInI (1)
1000))((
STTkiII rssoph (2)
))
11()exp(()( 3
TTkA
qE
Tr
TII
r
gaprrsat (3)
B. Lithium-ion Battery Banks and Pulsed Load
An accurate battery cell model is needed to regulate the DC
bus voltage in islanding mode. The battery terminal voltage and
SOC need to be estimated during operation. A high fidelity
electrical model of lithium-ion battery model, with thermal
dependence, is used. The pulse load can be connected to both
the AC and DC side. On the DC side, the pulse load can usually
be viewed as a purely resistive load. On the AC side, the pulse
load can be either a resistive or inductive load, such as an in-
duction motor. However, those inductive loads are commonly
connected to the AC side through power electronic drives, such
as back-to-back converters. In this way, the inductive load can
be converted and act as a resistive load. In this paper, only 18
ohm resistive loads are used, and the programmable load is
designed accordingly.
III. COORDINATED CONTROL OF CONVERTERS
Three types of converters are utilized in this proposed hybrid
microgrid as shown in Fig. 1. These converters must be actively
controlled in order to supply uninterrupted power with high
efficiency and quality to pulse loads on the AC and DC sides
during grid-connected and islanding modes. The coordinated
control strategies for converters are discussed.
A. Boost Converter Control with MPPT
To maximize the utilization of renewable energy from the PV
farm, the boost converter should be operated in on-MPPT mode
when the hybrid microgrid is connected to the utility grid. The
battery banks in the microgrid can be used as an energy buffer,
and the charging/discharging rates can be controlled based on
the status of the output power from the PV farm and the power
flow in the AC side. In islanded mode, the boost converter of the
PV farm can be operated in on-MPPT or off-MPPT, which is
based on the system’s power balance and the SOCs of the bat-
tery banks. In most cases, this boost converter can operate in the
on-MPPT mode since the variation ratio of the solar irradiance
is much lower compared to the power adjustment ability of the
small size AC generator. Therefore, for a constant load either on
the AC or DC side, the PV should supply as much power as
possible to maximize its utilization. However, if the battery
banks’ SOCs are high, (near fully charged) and the PV’s
maximum output power is larger than the total load in the hybrid
microgrid, the PV should be turned to off-MPPT to keep the
system power in balance. In this paper, a perturbation and ob-
serve (P&O) method is used to track maximum power point.
B. Bi-Directional DC/DC Converter Control
The bi-directional DC/DC converters are used to connect the
battery banks to the DC bus. The hardware setup of a battery
0 10 20 30 40 50 60 700
2
4
61 kW/m2
Curr
ent
(A)
Voltage (V)
Module type: SunPower SPR-305-WHT
0.75 kW/m2
0.5 kW/m2
0.25 kW/m2
0 10 20 30 40 50 60 700
100
200
300 1 kW/m2
Pow
er (
W)
Voltage (V)
0.75 kW/m2
0.5 kW/m2
0.25 kW/m2
Fig. 3. I-V and P-V curves for PV panel Sunpower SPR-305-WHT
TABLE I
PARAMETERS FOR PHOTOVOLATIC PANEL
Symbol Description Vaule
Voc Rated open circuit voltage 64.2 V
Iph Photocurrent 5.9602 A
Isat Module reverse satuation current 1.1753×10-8
q Electron charge 1.602×10-19 C
A Ideality factor 1.50
k Boltzman constant 1.38×10-23 J/K
Rs Series resistance of a PV cell 0.037998 Ω
Rp Parallel resistance of a PVcell 993.51 Ω
Isso Short-circuit current 5.96 A
ki SC current temperature coefficient 1.7×10-3
Tr Reference temperature 301.18 K
Irr Reverse saturation current at Tr 2.0793×10-6 A
Egap Energy of the band gap for silicon 1.1eV
np Number of cells in parallel 528
ns
S
T
Number of cells inseries
Solar radiation level
Surface temperature of the PV
480
0~1000 W/m2
350 K
Rac Lac
SPWM
eab PLL
ebc
Sa Sb
Sc
EqEd
θ
abc abc
abc
dqo dqo
dqo
vdc
refVdc+
idref
iqid
+
wLac+Rac
θ
-
PI
-
iqref
+
PI
PI
-
-wLac+Rac
+
+
+
+
vdcon
vqcon
0
+
RL
Fig. 5. The control block diagram for bi-directional AC/DC converter
in grid-connected mode
0093-9994 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2016.2613981, IEEETransactions on Industry Applications
4
bank, bi-directional DC/DC converter together with the meas-
urement circuit, and control driver circuit is shown in Fig. 2. In
grid-connected mode, these converters only regulate the battery
banks charging rates. Based on the SOCs of the battery banks
and the power flow conditions in the AC side, the charg-
ing/discharging current references are generated to regulate the
current flow in the converters.
Each battery has its own bi-directional DC/DC converter,
which means they can have different charging rates. The battery
banks can inject power to, or absorb power from, the DC bus.
Also, they can transfer energy between different battery banks if
necessary. In this case, only one closed current control loop with
PI controller is enough to regulate the current. The
bi-directional DC/DC converters of the battery banks play an
important role in islanding mode to regulate the DC bus voltage.
A two-loop control is used to regulate the DC bus voltage. The
control scheme for the bi-directional DC/DC converter is shown
in Fig. 4.
The outer voltage controlled loop is used to generate a ref-
erence charging current for the inner current controlled loop.
The error between the measured DC bus voltage and the system
reference DC bus voltage is set as the input of the PI controller,
and the output is the reference current. The inner current control
loop compares the reference current signal with the measured
current flow through the converter and, finally, generates a
PWM signal to drive the IGBTs to regulate the current flow
through the converter. For example, when the DC bus voltage is
higher than the reference voltage, the outer voltage controller
generates a negative current reference signal. The inner current
control loop adjusts the duty cycle to force the current flow from
the DC bus to the battery, which results in charging of the bat-
tery. In this way, the energy transfers from the DC bus to the
battery, and the DC bus voltage, then decreases to the rating
value. If the DC bus voltage is lower than the normal value, the
outer voltage control loop generates a positive current reference
signal, which regulates the current flow from the battery to the
DC bus. Because of the extra energy injected from the batteries,
the DC bus voltage increases to the rating value.
If several energy storage systems are connected to the
common DC bus of the hybrid power system individually
through their own bidirectional DC-DC converter, a conven-
tional PID controller could not be used to regulate the DC bus
voltage. If all of them are used to regulate the DC bus voltage,
they may conflict with each other and cause instability prob-
lems; however, if only one of them is used to regulate the DC
bus voltage, distributing power flow becomes unclear to the
other controllers, which may cause SOC unbalance between
energy storage systems. Therefore, droop control is used to
regulate and dispatch power flow for multiple lithium-ion bat-
tery modules on the DC side of the hybrid power system. With
the SOC information, the five battery modules are ranked based
on their SOC. With the SOC rank and the measured DC bus
voltage, a central aggregator calculates and assigns the droop
coefficient to each battery module. Each bidirectional DC-DC
converter can generate its charging rate with the droop coeffi-
cient.
C. Bi-Directional AC/DC Converter
In grid-connected mode, the AC side can be viewed as an
infinite bus; therefore, the deviation of the voltage amplitude
and frequency can be ignored. In this case, the bi-directional
AC/DC converter only needs to regulate the DC bus voltage. In
order to operate in unit power factor, reference iq can be set as 0.
The controller only needs to control the id, which controls the
active power flow through the converter. The control block
diagram for bi-directional AC/DC converter in grid-connected
mode is shown in Fig. 5. As discussed earlier, a two-loop con-
troller is used to regulate the DC bus voltage. Based on the error
between the DC bus reference voltage and measured voltage,
the outer voltage control loop generates the id reference, which
is used to regulate id in the bi-directional converter. In d-q co-
ordinates, Id is controlled to regulate the active power flow
through the inverter, and Iq is controlled to regulate the reactive
power flow through the inverter. In the AC side, the active and
reactive power flow will influence the frequency and voltage
amplitude respectively.
In islanded operation mode, the frequency and voltage am-
plitude of the three phases AC side are volatile. The
bi-directional AC/DC inverter is used to regulate the active and
reactive power by controlling the id and iq, respectively. The
control scheme for the bi-directional AC/DC inverter is shown
in Fig. 6. Two-loop controllers are applied for both frequency
and voltage regulation. For frequency control, error between
measured frequency and reference frequency is sent to a PI
controller which generates the id reference.
PI -1 PI 1/(sLb +Rb) db 1/sCd
Vd*
Vd
Id*
Id
+ +
- -
Vd
Fig.4. The control block diagram for bi-directional DC/DC converter
Rac Lac
SPWM
eab PLL
ebc
Sa Sb
Sc
EqEd
θ
abc abc
abc
dqo dqo
dqo
idref
vdc
fref
f
+
-
PI
PI
refVam
Vam
+- iq
ref
iqid
id
iq
+
+
PI
PI
-
-
iq -wLac+Rac
wLac+Rac
θ
Ed
Eq Vq Vd
Δq
Δd
Fig. 6. The control block diagram for bi-directional AC/DC converter
in islanded mode
0093-9994 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2016.2613981, IEEETransactions on Industry Applications
5
To control the voltage amplitude, the error between the
measured voltage amplitude and the reference voltage ampli-
tude is sent to a PI controller to generate iq reference.
Equations (4) and (5) show the AC side voltage equations of
the bi-directional AC/DC inverter in ABC and d-q coordinates,
respectively. Where (Va, Vb, Vc) are AC side voltages of the
inverter, and (Ea, Eb, Ec) are the voltages of the AC bus. (Δa, Δb,
Δc) are the adjusting signals after the PI controller in the current
control loop.
c
b
a
c
b
a
c
b
a
c
b
a
ac
c
b
a
ac
E
E
E
V
V
V
i
i
i
R
i
i
i
dt
dL (4)
q
d
q
d
q
d
q
d
acac
acac
q
d
ac E
E
V
V
i
i
RL
LR
i
i
dt
dL
(5)
When the pulse load is connected or disconnected to the AC
side, the frequency or voltage amplitude changes. After de-
tecting the deviation using the phase lock loop (PLL) or voltage
transducer, Id and Iq reference signals are adjusted to regulate
power flow through the bi-directional AC/DC inverter. Because
of the power flow deviation, the DC bus voltage is also influ-
enced. The DC bus voltage transistor senses the voltage varia-
tion in DC bus, and the bi-directional DC/DC converter regu-
lates the current flow between the battery and the DC bus. In the
end, the energy is transferred between the battery and the AC
side to balance the power flow.
For further frequency and voltage regulation, a droop control
is implemented for solving the microgrid primary control
problem as shown in Fig. 7. Synchronous generator and grid-tie
inverter adjust their power output according to the no-load
speed setting with respect to the system frequency. The power
output for any given system frequency can be controlled. The
no-load frequency of a given generator can be set to obtain any
desired power output according to its droop slope R.
max min( ) / ( ) sysNL NL FLf P f f P P f (6)
sysNLf P R f (7)
Here, R is typically formulated with the maximum and
minimum power outputs of the DG, Pmax and Pmin. The no-load
and full-load frequencies, fNL and fFL, are normally chosen as the
bounds which the system frequency must not cross. The sec-
ondary level control covers the residual frequency error and
puts back the frequency value to 60 Hz.
IV. SIMULATION AND EXPERIMENTAL RESULTS
The operation of the hybrid microgrid is tested on both
simulation environment and experimental setup. 10.07 kW PV
farm under the influence of a 10 kW pulse load is applied to
verify the proposed hybrid microgrid control. The total rated
power of the synchronous generators are 13.8 kW, and a 4 kW
constant load is connected in the AC side. Five 51.8V, 21Ah
Lithium-ion battery banks are connected individually to DC bus
through bidirectional DC/DC converters with the rated power of
10 kW. The rated power of the grid-tied bidirectional AC/DC
inverter is 26 kW. In steady state, the hybrid AC/DC system is
operated with 300V rated DC bus voltage and 208V,
phase-to-phase AC bus voltage. Further system parameters for
hybrid microgrid are listed in Table II.
A. Simulation Results
In both grid-connected mode and islanded mode, to maxim-
ize the utilization of renewable energy, the boost converter
works in on-MPPT mode to keep seeking the maximum output
power from the PV farm. The MPPT of the boost converter is
enabled at 0.4s. The output power, the terminal voltage of the
PV panel, the duty cycle of the boost converter, and the solar
irradiance levels are shown in Fig. 8. For general study, two
kinds of solar irradiance deviation with different charging rates
are used. Before 0.4s, the duty cycle is set at 0.5, the terminal
voltage of the PV panel is 149V, and the output power from the
System f = 60 Hz
Frequency (Hz)
fNL=61.0
fNL=60.5
fNL=59.5
10.750.50.250-0.25
Power Output (p.u.)
Grid-TieInverter
Synchronous Generator
Fig. 7. Droop control implementation
TABLE II
HYBRID MICROGRID SYSTEM PARAMETERS
Symbol Description Vaule
Cpv Solar panel capacitor 100 uF
Lpv Inductor for solar Panel boost converter 5mH
Cd DC bus capacitor 6000 uF
Lac AC filter inductor 1.2mH
Rac Inverter equivalent resistance 0.3ohm
Lb Battery converter inductor 3.3mH
Rb Resistance of Lb 0.5 Ω
f
Vd
Vm
n1/n2
Rated AC grid frequency
Rated DC bus voltage
Rated AC bus p-p voltage (rms)
Transformer ratio
60Hz
300V
208K
1:1
0 0.5 1 1.5 2 2.5 3 3.5 40
5
10
Po
wer
(kW
)
0 0.5 1 1.5 2 2.5 3 3.5 4
100
150
200
Vo
ltag
e (
V)
0 0.5 1 1.5 2 2.5 3 3.5 40.4
0.5
0.6
Du
ty c
ycle
0 0.5 1 1.5 2 2.5 3 3.5 4
500
1000
Time (s)
Irra
dia
nce (
W/m
2)
Fig. 8. PV output power control with MPPT
0093-9994 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2016.2613981, IEEETransactions on Industry Applications
6
PV panel is only 9.56 kW. After the MPPT is enabled, the duty
cycle is decreased to 0.45 and the terminal voltage is increased
to 165V. This allows the PV panel to reach the maximum power
output of 10.07 kW. The simulation results show that the boost
converter, with MPPT functionality, can track the maximum
power point within a short response time.
In grid-connected mode, the DC bus voltage is regulated by
the bi-directional AC/DC converter. In this mode, the AC side
can be viewed as an infinite bus, therefore the 10 kW resistive
pulse load that is connected to the AC side would not have an
influence on the grid. Therefore, only the DC pulse load case is
studied. Fig 9 (a) shows the DC bus voltage. The bi-directional
AC/DC converter was enabled at 0.05s. Before being enabled, it
operates as an uncontrolled rectifier. After enabling the
bi-directional converter, the DC bus voltage reached steady
state in less than 0.3s. During this period, the solar irradiance is
1kW/m2. From 0.4s to 1.7s, the system under two kinds of solar
irradiance variations is simulated. The output power from PV
decreased from 10kW to 2.5kW in 0.3 second, and recovered
back from 2.5kW to 10kW also in 0.3 second. After that, the PV
output decreased from 10kW to 2.5 kW in 0.05 second at 1.3s,
and it went back from 2.5kW to 10kW at 1.65s. The PV output
power is shown in Fig. 9 (b). The DC bus voltage was stable and
stayed in the range of 293V to 307V during this process,
therefore, the bi-directional converter can keep the DC side
stable under rapid alteration of solar irradiance and PV output
power. From 2s to 2.8s, the charging/discharging of battery
banks impact to the DC bus is simulated. At 2s, the current
references of the bi-directional DC/DC converters of those five
batteries were changed from 0A to -4A, which means dis-
charging those battery banks with 4A. At 2.4 seconds, the cur-
rent references of the bi-directional DC/DC converters of the
five battery banks were changed from 0A to 4A. At this point,
the system began charging the battery banks. The current flow
of one bi-direction DC/DC converter is shown in Fig. 9 (c).
During this period, the DC bus voltage was still stable with less
than 3V voltage deviation. From 3s to 3.5s, a 10kW resistive
load is connected to the DC bus. During the connection and
disconnection of the 10 kW pulse load, the bi-directional
AC/DC inverter active power flow was greatly changed to
regulate the DC bus voltage. The DC bus was still stable, within
12V voltage deviation, during the transient response. The power
flow through the bi-directional AC/DC inverter is shown in Fig.
9 (d). After the system entered steady state, the system kept the
unit power factor as the reactive power was 0. The active power
flow varied with the solar irradiance influence, battery banks
charging/discharging influence and pulse load influence. The
bi-directional inverter can quickly adjust the power flow.
B. Experimental Result
Complementary to simulation results and extension of [16],
the real-time experimental performance of the hybrid microgrid
is tested under islanding and pulsed load conditions. The is-
landing experiment was realized by opening the circuit breaker
of PMU2, shown in Fig.1. Fig.10 illustrates the islanding tran-
sition of the microgrid and the corresponding primary and
secondary controls. Primary control is the immediate response
of the synchronous generator, and the grid-tie inverter arrests
deviations in power system frequency. Secondary control ad-
justs the dispatchable assets shortly after frequency and voltage
deviations to restore the system to nominal operating condi-
tions.
1) Islanding of Hybrid AC/DC Microgrid
The objective of this experiment is to present proper centrally
coordinated actions to reinstate frequency to its nominal value.
In a conventional power system operation approach, if an un-
controlled islanding is formed due to emergency conditions, the
primary control responds rapidly according to droop adjust-
ments of the generators inside the island. Droop based primary
control deviates the frequency from the nominal value, ac-
cording to the system loading conditions. Upon separation, it
may be necessary to shed some of the predetermined loads in the
islanded area in order to balance generation and load. The
measurements are taken from synchrophasors deployed on the
AC side of the microgrid [20]. During the synchronized opera-
tion, the islanded power system was importing power from the
remote power system. When the islanding situation takes place
at t= 130s, the imported power becomes zero.
( ) ( ) ( )( ) Gen t Load t import tP t P P P (8)
As per equation (9), the power imbalance inside the mi-
crogrid results in a frequency drift in the islanded area:
dt
df
f
HtPtPtP s
n
tot
loadgen
2))()(()(
(9)
The active power imbalance introduces frequency deviation
in islanded microgrid (9), where Htot is the total inertia, fn is the
nominal frequency, and fs is system frequency [21]. The phase
angle difference between the two areas increases. The figure
shows the oscillation of the phase angle of the system generators
during primary control. Between t= 130s and at t= 147s, the
primary control is established. The generation in the islanded
area increases and the frequency settles in a stable region. At
t= 181s, the system frequency reaches the minimal value. Au-
tomatic generation control (AGC) based secondary control
0 0.5 1 1.5 2 2.5 3 3.5 4280
300
Vo
ltag
e (
V)
(a)
0 0.5 1 1.5 2 2.5 3 3.5 40
5
10
Po
wer
(kW
)
(b)
0 0.5 1 1.5 2 2.5 3 3.5 4-5
0
5
Cu
rren
t (A
)
(c)
0 0.5 1 1.5 2 2.5 3 3.5 4-2
0
2x 10
4
Po
wer
(VA
)
(d)
Time (s)
P
Q
Vdc-ref
Vdc-mea
Fig. 9. Hybrid microgrid performance in grid-connected mode
Pulsed Load Phase Angle
Deviation
0093-9994 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2016.2613981, IEEETransactions on Industry Applications
7
Islanding
Instant Secondary
Control
Primary Control
Grid-connected
Operation Islanded
Operation
Phase Angle
Difference
Loss of Power Import from Grid
Generation in Microgrid Increased
Fig. 10. Islanding of hybrid AC/DC microgrid
is used to restore system frequency to nominal value. A
common way to enable AGC in power systems is to implement a
proportional-integral (PI) controller. An area control error
(ACE) in a power system is given as (10), where B is the fre-
quency bias factor, ∆PT is the deviation of active power balance
in area, and ∆PAGC is the control command to be sent to the
grid-tie inverter. β1 and β2 are the PI control coefficients.
1 2
T
AGC
ACE P B f
P ACE ACEdt
(10)
In real-time applications, angular stability is measured by the
difference in generator voltage angles of the two points and
compared with a predefined threshold angle during pulsed load:
1 2PMU PMU (11)
where is defined as the tolerance in degrees. The tolerance
in this study is selected to be 10 degrees. When the angular
separation between two PMU measurements is exceeded, the
instability should check whether the system is in a stable or
unstable swing. Specifically, the microgrid buses are assumed
as two-machine system implementing swing equation to de-
termine the out-of-step condition in the two-area system.
As classical generator dynamics are defined as:
.
i i
i i
ii m e
dH P P
dt
(12)
2
1
1
cos cos( )i
n
e i ii ii i j ij i j ij
j
j
P E Y E E Y
(13)
where Hi is the inertia constant of ith generator, i is the in-
ternal voltage angle of ith generator, i is the rotor speed of the
ith generator, /i ie mP P electrical/mechanical output power of
the ith generator, ,i jE E voltage behind transient reactance, Y
is the admittance matrix reduced at the internal generator node.
2) Performance during Pulsed Loads
To further verify the proposed control algorithm for hybrid
AC-DC power system operation with pulse load mitigation, a
hardware experiment is demonstrated. PMUs are connected to
synchronous generator and grid-tie inverter buses. System fre-
quency and voltage variations, phase angle displacement and
pulsed loading are shown in Fig. 11. A 4 kW pulsed load is
applied three consecutive times. It is noticed that the system
frequency experiences an oscillation during the transition,
which eventually settles to the reference value. The terminal
voltage experiences temporary spikes during transition as well,
and it settled within limits due to reactive power control inside
the island. The phase angle displacement between microgrid
buses are kept under 10 degree threshold. From the results, it
can be seen that during the pulse load duration, the DC micro
grid can inject power to help the system regulate the frequency
and the frequency only dropped to around 57.5 Hz. The voltage
dropped to around 115 V. The proposed coordinated converter
control was able to perfectly mitigate frequency and voltage
dips according to pulsed loading. The islanded low inertia hy-
brid microgrid was able to withstand the pulsed loading condi-
tions.
0093-9994 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2016.2613981, IEEETransactions on Industry Applications
8
V. CONCLUSION
In this paper, a coordinated power flow control method of
multi power electronic devices is proposed for a hybrid AC/DC
microgrid operated in both grid-connected and islanded modes.
The microgrid consists of a PV module, battery bank and a
synchronous generator that supply energy to its DC and AC
side. Battery banks are connected to the DC bus through
bi-directional DC/DC converter. The AC side and DC side are
linked by the bi-directional AC/DC inverter. The control algo-
rithms are tested with the harsh influence of pulse loads and
islanding conditions. The simulation and experimental results
show that the proposed microgrid with the control algorithm can
greatly increase the system stability and robustness.
REFERENCES
[1] Olivares DE, Mehrizi-Sani A, Etemadi AH, Canizares C, Iravani R,
Kazerani M, Hajimiragha AH, Gomis-Bellmunt O, Saeedifard M, Pal-
ma-Behnke R, Jimenez-Estevez G. Trends in microgrid control. Smart
Grid, IEEE Transactions on. 2014 Jul;5(4):1905-19.
[2] C. K. Sao and P. W. Lehn, “Control and power management of con-
verterfed MicroGrids,” IEEE Trans. Power Syst., vol. 23, no. 3, pp.
1088–1098, Aug. 2008
[3] A. Mohamed, F. Carlos, T. Ma, M. Farhadi, O. Mohammed, “Operation
and protection of photovoltaic systems in hybrid AC/DC smart grids,”
IECON 2012 – 38th Annual Conference on IEEE Industrial Electronics
Society, pp.1104-1109, 25-28 Oct. 2012
[4] R. H. Lasseter and P. Paigi, “Microgrid: A conceptual solution,” in Proc.
IEEE 35th PESC, Jun. 2004, vol. 6, pp. 4285–4290.
[5] C. Liu, K.T. Chau, D. Wu, and S. Gao, “Opportunities and challenges of
vehicle-to-home, vehicle-to-vehicle and vehicle-to-grid technologies,”
Proceeding of the IEEE, Invited Paper, vol. 101, no. 11, pp. 2409-2427,
Nov. 2013.
[6] T. Ma and O. A. Mohammed, "Optimal Charging of Plug-in Electric
Vehicles for a Car-Park Infrastructure," in IEEE Transactions on Indus-
try Applications, vol. 50, no. 4, pp. 2323-2330, July-Aug. 2014.
[7] T. Ma and O. A. Mohammed, "Economic Analysis of Real-Time
Large-Scale PEVs Network Power Flow Control Algorithm With the
Consideration of V2G Services," in IEEE Transactions on Industry Ap-
plications, vol. 50, no. 6, pp. 4272-4280, Nov.-Dec. 2014.
[8] X. Liu, P. Wang and P. C. Loh, “A Hybrid AC/DC Microgrid and Its
Coordination Control,” IEEE Trans. Smart Grid, vol.2, no.2, pp.278,286,
June 2011.
[9] Rocabert, J., Luna, A., Blaabjerg, F. and Rodriguez, P., 2012. Control of
power converters in AC microgrids. Power Electronics, IEEE Transac-
tions on, 27(11), pp.4734-4749.
[10] Loh, Poh Chiang, Ding Li, Yi Kang Chai, and Frede Blaabjerg. "Au-
tonomous operation of hybrid microgrid with AC and DC sub-
grids." Power Electronics, IEEE Transactions on 28, no. 5 (2013):
2214-2223.
[11] M. Schuerger, H. Johal, L. Roose, M. Matsuura,and R. Piwko, “Catching
Some Rays: Variable Generation Integration on the Island of Oahu,”
Power and Energy Magazine, IEEE , vol.11, no.6, pp.33,44, Nov. 2013
[12] M. Ahlstrom, et al “Knowledge Is Power: Efficiently Integrating Wind
Energy and Wind Forecasts,” Power and Energy Magazine, IEEE ,
vol.11, no.6, pp.45,52, Nov. 2013
[13] N. Miller, C.Loutan, Shao Miaolei, K. Clark, “Emergency Response: U.S.
System Frequency with High Wind Penetration, ” Power and Energy
Magazine, IEEE , vol.11, no.6, pp.63,71, Nov. 2013
[14] T. Ma, B. Serrano and O. Mohammed, "Distributed control of hybrid
AC-DC microgrid with solar energy, energy storage and critical
load," Power Systems Conference (PSC), 2014 Clemson University,
Clemson, SC, 2014, pp. 1-6.
[15] Cintuglu, M.H.; Youssef, T.A.; Elsayed, A.T.; Mohammed, O.A., "Fre-
quency and voltage control of microgrids upon unintentional cascading
islanding," in SoutheastCon 2015 , vol., no., pp.1-6, 9-12 April 2015
[16] Ma, Tan, Mehmet Hazar Cintuglu, and Osama Mohammed. "Control of
hybrid AC/DC microgrid involving energy storage, renewable energy and
pulsed loads." Industry Applications Society Annual Meeting, 2015
IEEE. IEEE, 2015.
[17] Salehi, Vahid, Ahmed Mohamed, Ali Mazloomzadeh, and Osama A.
Mohammed. "Laboratory-based smart power system, Part I: Design and
system development." Smart Grid, IEEE Transactions on 3, no. 3 (2012):
1394-1404.
[18] Salehi, Vahid, Ahmed Mohamed, Ali Mazloomzadeh, and Osama A.
Mohammed. "Laboratory-based smart power system, part II: Control,
monitoring, and protection." Smart Grid, IEEE Transactions on 3, no. 3
(2012): 1405-1417.
[19] Ma, Tan. "Hybrid Power System Intelligent Operation and Protection
Involving Plug-in Electric Vehicles." (2015).
[20] Cintuglu, Mehmet H., Ahmed T. Elsayed, and Osama A. Mohammed.
"Microgrid automation assisted by synchrophasors." Innovative Smart
Grid Technologies Conference (ISGT), 2015 IEEE Power & Energy
Society. IEEE, 2015.
[21] Cintuglu, Mehmet H., Tan Ma, and Osama A. Mohammed. "Aggregated
active distribution networks for secondary control of islanded power
systems." In Power & Energy Society General Meeting, 2015 IEEE, pp.
1-5. IEEE, 2015.
[22] M. Farhadi and O. Mohammed, "Adaptive Energy Management in
Redundant Hybrid DC Microgrid for Pulse Load Mitigation," in IEEE
Transactions on Smart Grid, vol. 6, no. 1, pp. 54-62, Jan. 2015.
[23] J. M. Crider and S. D. Sudhoff, "Reducing Impact of Pulsed Power Loads
on Microgrid Power Systems," in IEEE Transactions on Smart Grid, vol.
1, no. 3, pp. 270-277, Dec. 2010.
[24] Bronin, Sara C., and Paul McCary. "Peaceful Coexistence: Independent
Microgrids are Coming." Public Utilities Fortnightly (2013).
[25] Y. Han; H. Li; P. Shen; E. Coelho; J. Guerrero, "Review of Active and
Reactive Power Sharing Strategies in Hierarchical Controlled Mi-
crogrids," in IEEE Transactions on Power Electronics , vol.PP, no.99,
pp.1-1
Frequency
Disturbance
Phase Angle
Deviation Pulsed Load
Frequency Disturbance
Pulsed Load
Phase Angle Deviation
Fig. 11. Consecutive pulsed loads and system disturbance
0093-9994 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2016.2613981, IEEETransactions on Industry Applications
9
Tan Ma (M’16) received the M.
E. degree in control theory and con-
trol engineering from Huazhong
University of Science and Technol-
ogy (HUST) in China in 2009 and the
Bachelor of Eng. degree in automa-
tion from HUST in China in 2007.
He received his Ph.D. degree in
electrical and computer engineering
at Florida International University.
His research interests include Power
System Operations, Control and Protection, Artificial Intelli-
gence Applications to Power Systems, Energy Conservation and
Alternate Energy Sources and smart grid power systems design
and optimization.
Mehmet H. Cintuglu received
the B.S. and M.S. degrees in elec-
trical engineering from Gazi Uni-
versity, Ankara, Turkey, in 2008
and 2011, respectively. He is cur-
rently pursuing the Ph.D. degree
from the Energy Systems Research
Laboratory, Electrical and Com-
puter Engineering Department,
College of Engineering and Computing, Florida International
University, Miami, FL, USA. From 2009 to 2011, he was a
Power Systems Project Engineer at an electric utility company
in Turkey. His current research interests include multi agent
systems, distributed control, cyber physical systems for active
distribution networks and microgrids.
Osama A. Mohammed is a Pro-
fessor of Electrical Engineering and
is the Director of the Energy Systems
Research Laboratory at Florida In-
ternational University, Miami, Flor-
ida. He received his Master and
Doctoral degrees in Electrical En-
gineering from Virginia Tech in
1981 and 1983, respectively. He has
performed research on various topics
in power and energy systems in ad-
dition to design optimization and physics passed modeling in
electric drive systems and other low frequency environments.
Professor Mohammed is a world renowned leader in electrical
energy systems. He has performed research in the area of elec-
tromagnetic signature, wideband gap devices and switching,
and ship power systems modeling and analysis. He has current
active research projects for several Federal agencies dealing
with; power system analysis and operation, smart grid distrib-
uted control and interoperability, cyber physical systems, and
co-design of cyber and physical components for future energy
systems applications.