  • CONTROL PANELSRANGE OF PANELS FOR CONTROL ANDPROTECTION OF LOWARA ELECTRIC PUMPS

    50/60 Hz50/60 Hz50/60 Hz50/60 Hz50/60 Hz

    CCCCCod.od.od.od.od. 191007691 R 191007691 R 191007691 R 191007691 R 191007691 Revevevevev.C Ed.11/2013.C Ed.11/2013.C Ed.11/2013.C Ed.11/2013.C Ed.11/2013

  • 2

  • 3QSMQSMQSMQSMQSM Series ..........................................................................................................................................55555QPCQPCQPCQPCQPC Series ...........................................................................................................................................66666QPCQPCQPCQPCQPCSSSSS Series .........................................................................................................................................77777QSCQSCQSCQSCQSC Series ...........................................................................................................................................88888QSCQSCQSCQSCQSC Series (60 Hz) ...............................................................................................................................99999QSCQSCQSCQSCQSCSSSSS Series ...................................................................................................................................1010101010QSCQSCQSCQSCQSCSSSSS Series (60 Hz) .......................................................................................................................1111111111QCLP10QCLP10QCLP10QCLP10QCLP10 Series ...............................................................................................................................1212121212QCLP10/DIQCLP10/DIQCLP10/DIQCLP10/DIQCLP10/DI Series ..........................................................................................................................1313131313QMQMQMQMQM Series .......................................................................................................................................1414141414QTDQTDQTDQTDQTD Series ......................................................................................................................................1515151515Q3DQ3DQ3DQ3DQ3D Series ......................................................................................................................................1616161616Q3YQ3YQ3YQ3YQ3Y Series ......................................................................................................................................1717171717Q3IQ3IQ3IQ3IQ3I Series .......................................................................................................................................1818181818Q3AQ3AQ3AQ3AQ3A Series ......................................................................................................................................1919191919

    CONTENTSCONTENTSCONTENTSCONTENTSCONTENTS

  • 4Q3SFQ3SFQ3SFQ3SFQ3SF Series ...................................................................................................................................2020202020QDRMQDRMQDRMQDRMQDRM Series .................................................................................................................................2121212121QDRMCQDRMCQDRMCQDRMCQDRMC Series ...............................................................................................................................2222222222QDRQDRQDRQDRQDR Series .....................................................................................................................................2323232323QYRQYRQYRQYRQYR Series .....................................................................................................................................2424242424QDRM2QDRM2QDRM2QDRM2QDRM2 Series ...............................................................................................................................2626262626QDRMC2QDRMC2QDRMC2QDRMC2QDRMC2 Series ............................................................................................................................2727272727QXR20QXR20QXR20QXR20QXR20 Series ................................................................................................................................2828282828QDR2QDR2QDR2QDR2QDR2 Series ..................................................................................................................................2929292929QYR2QYR2QYR2QYR2QYR2 Series ...................................................................................................................................3030303030QCL5QCL5QCL5QCL5QCL5 Series ...................................................................................................................................3232323232QCL10QCL10QCL10QCL10QCL10 Series .................................................................................................................................3333333333KSLKSLKSLKSLKSL Series ......................................................................................................................................3434343434DPFDPFDPFDPFDPF Series .....................................................................................................................................3535353535KIT RILS20KIT RILS20KIT RILS20KIT RILS20KIT RILS20 Series .........................................................................................................................3636363636

    CONTENTSCONTENTSCONTENTSCONTENTSCONTENTS

  • 5QSM SeriesQSM SeriesQSM SeriesQSM SeriesQSM Series

    Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of a single-phase submersible electric pump for 4 wells

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALFEAFEAFEAFEAFEATURESTURESTURESTURESTURES QSM PF version with overvoltage protection.

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Main switch for manual control. Supply voltage: 1 x 220-240 V 5%. Frequency: 50 Hz. Power: 0,25 to 1,1 kW. Direct motor start. Protection class: IP54. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Plastic enclosure. Incorporated capacitor. Thermal protection with motor protector inside the panel.

    SERIE QSM

    MODEL RATED RATED CAPACITOR WEIGHT

    VOLTAGE CURRENT 450V A B C

    V kW HP A uF mm mm mm Kg

    QSM 02 220-240 0,25 0,33 2,6 12,5 80 210 65 0,45

    QSM 03 220-240 0,37 0,5 3,4 16 80 210 65 0,45

    QSM 05 220-240 0,55 0,75 4,8 20 80 210 65 0,45

    QSM 07 220-240 0,75 1 6,5 30 80 210 65 0,45

    QSM 11 220-240 1,1 1,5 8,3 40 80 210 65 0,45

    CB-QSM-en_c_te

    RATED

    POWER

    DIMENSIONS

    I

    0

    A

    B

    C

  • 6Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel

    QPC SeriesQPC SeriesQPC SeriesQPC SeriesQPC Series

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of a single-phase submersible electric pump for 4 wells.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES DPF single-phase module for overvoltage protection.

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Main switch for manual control. Supply voltage: 1 x 230 V 10%. Frequency: 50 Hz. Power: 0,25 to 2,2 kW. Direct motor start. Protection class: IP54. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted with fins. Plastic enclosure. Incorporated capacitor. Main switch with manual-reset thermal protection and power indicator light.

    SERIE QPC

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    QPC/02 1 x 230 V 10 % 0,25 0,33 3 170 170 75 1,1

    QPC/03 1 x 230 V 10 % 0,37 0,5 4 170 170 75 1,1

    QPC/05 1 x 230 V 10 % 0,55 0,75 5 170 170 75 1,1

    QPC/07 1 x 230 V 10 % 0,75 1 6 170 170 75 1,1

    QPC/11 1 x 230 V 10 % 1,1 1,5 9 170 170 75 1,1

    QPC/15 1 x 230 V 10 % 1,5 2 11 170 170 75 1,1

    QPC/22 1 x 230 V 10 % 2,2 3 16 170 170 127 1,2

    CB-QPC-en_a_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

    CAPACITOR

    F/450V

    12,5

    16

    70

    20

    30

    40

    50

    ATTENZIONE !

    TOGLIERE TENSIONE PRIMA DI APRIRE

    DISCONNECT THE POWER BEFORE OPENING

    VOR DEM OFFNEN NETZSTECKER ABSCHALTEN

    DEBRANCHER LA LIGNE AVANT OUVRIR LE COFFRET

    DANGER!

    ACHTUNG GEFAHR!

    DANGER!

    DESCONETAR TENSION ANTES DE ABRIR

    ATENCION!

    I

    0

    A

    B

    C

  • 7Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel

    QPCQPCQPCQPCQPCS SeriesS SeriesS SeriesS SeriesS Series

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of a single-phase submersible electric pump for 4 wells.

    Main switch with manual-reset thermal protection and power indicator light. Power, pump running, level control LED. Overvoltage discharges. Dry running control through probes or float or minimum pressure switch.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES Set of 3 electrodes (probes) without cable. Float. Pressure switch.

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through an external enable contact. Supply voltage: 1 x 230 V 10%. Frequency: 50 Hz. Power: 0,25 to 2,2 kW. 12 V AC low-voltage auxiliary circuit. Direct motor start. Protection class: IP54. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted with fins. Plastic enclosure with transparent cover. Incorporated capacitor.

    SERIE QPCS

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    QPCS/02 1 x 230 V 10 % 0,25 0,33 3 200 150 80 1,3

    QPCS/03 1 x 230 V 10 % 0,37 0,5 4 200 150 80 1,3

    QPCS/05 1 x 230 V 10 % 0,55 0,75 5 200 150 80 1,3

    QPCS/07 1 x 230 V 10 % 0,75 1 6 200 150 80 1,3

    QPCS/11 1 x 230 V 10 % 1,1 1,5 9 200 150 80 1,3

    QPCS/15 1 x 230 V 10 % 1,5 2 11 200 150 80 1,3

    QPCS/22 1 x 230 V 10 % 2,2 3 16 200 150 80 1,3

    CB-QPCS-en_a_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

    CAPACITOR

    F/450V

    12,5

    16

    70

    20

    30

    40

    50

    Elektroden Empfindlikeit

    ElectrodesSensibilit

    ProbesSensitivity

    SondeSensibilit

    Temporizzatore Timer Temporisation Zeiteinstellung

    Marcia Run Marche Betriebe

    Blocco livello Lack of water Manque d'eau Wassermangel

    Linea Main supply Tension Stromversorgung

    I GB F D

    InterruttoreGeneraleProtezioneTermica

    MainSwitchThermalOverload

    InterrupteurGeneralProtectionMoteur

    Attenzione : togliere tensione prima di aprire !Danger : disconnect power before opening !Danger : debrancher la ligne avant ouvrir le coffret !Achtung Gefahr : vor dem offnen Netzstecker abshalten!

    HauptshalterUberlastungThermischerShutz

    I

    0

    A

    B

    C

  • 8SERIE QSC

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    QSC/02 1 x 230 V 10 % 0,25 0,33 2,5 4 205 220 160 1,7

    QSC/03 1 x 230 V 10 % 0,37 0,5 4 6,3 205 220 160 1,7

    QSC/05 1 x 230 V 10 % 0,55 0,75 4 6,3 205 220 160 1,7

    QSC/07 1 x 230 V 10 % 0,75 1 4 6,3 205 220 160 1,7

    QSC/11 1 x 230 V 10 % 1,1 1,5 6,3 10 205 220 160 1,7

    QSC/15 1 x 230 V 10 % 1,5 2 10 16 205 220 160 1,7

    QSC/22 1 x 230 V 10 % 2,2 3 16 20 205 220 160 2,7

    QSC/40 1 x 230 V 10 % 4 5,5 25 32 280 220 160 3

    CB-QSC-en_d_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

    CAPACITOR

    F/450V

    12,5

    30

    20

    90

    16

    40

    50

    70

    Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel

    QSC SeriesQSC SeriesQSC SeriesQSC SeriesQSC Series

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of a single-phase submersible electric pump for 4 wells.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES DPF single-phase module for overvoltage protection.

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Main switch for manual control. Supply voltage: 1 x 230 V 10%. Frequency: 50 Hz. Power: 0,25 to 4 kW. Direct motor start. Protection class: IP55. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Plastic enclosure. Incorporated capacitor. Main switch with manual-reset thermal protection.

  • 9SERIE QSC..6

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    QSC/036 1 x 230 V 10 % 0,37 0,5 4 6,3 205 220 160 1,7

    QSC/056 1 x 230 V 10 % 0,55 0,75 4 6,3 205 220 160 1,7

    QSC/056A 1 x 230 V 10 % 0,55 0,75 6,3 10 205 220 160 1,7

    QSC/076 1 x 230 V 10 % 0,75 1 6,3 10 205 220 160 1,7

    QSC/116 1 x 230 V 10 % 1,1 1,5 6,3 10 205 220 160 1,7

    QSC/116A 1 x 230 V 10 % 1,1 1,5 10 16 205 220 160 1,7

    QSC/156 1 x 230 V 10 % 1,5 2 10 16 205 220 160 1,7

    QSC/226 1 x 230 V 10 % 2,2 3 16 20 205 220 160 2,7

    QSC/406 1 x 230 V 10 % 4 5,5 25 32 280 220 160 3

    CB-QSC6-en_c_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

    CAPACITOR

    F/450V

    20

    35

    25

    75

    50

    25

    40

    40

    50

    Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel

    QSC SeriesQSC SeriesQSC SeriesQSC SeriesQSC Series(60 Hz)(60 Hz)(60 Hz)(60 Hz)(60 Hz)

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of a single-phase submersible electric pump for 4 wells.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES DPF single-phase module for overvoltage protection.

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Main switch for manual control. Supply voltage: 1 x 230 V 10%. Frequency: 60 Hz. Power: 0,37 to 4 kW. Direct motor start. Protection class: IP55. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Plastic enclosure. Incorporated capacitor. Main switch with thermal protection.

  • 10

    Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel

    QSCQSCQSCQSCQSCS SeriesS SeriesS SeriesS SeriesS Series

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of a single-phase submersible electric pump for 4 wells.

    Main switch with manual-reset thermal protection. Dry running control with float or minimum pressure switch (available separately).

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES DPF single-phase module for overvoltage protection. KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply).

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through an external enable contact. Supply voltage: 1 x 230 V 10%. Frequency: 50 Hz. Power: 0,25 to 2,2 kW. Direct motor start. Protection class: IP55. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Plastic enclosure. Incorporated capacitor.

    SERIE QSCS

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    QSCS/02 1 x 230 V 10 % 0,25 0,33 2,5 4 280 370 160 3,7

    QSCS/03 1 x 230 V 10 % 0,37 0,5 4 6,3 280 370 160 3,7

    QSCS/05 1 x 230 V 10 % 0,55 0,75 4 6,3 280 370 160 3,7

    QSCS/07 1 x 230 V 10 % 0,75 1 4 6,3 280 370 160 3,7

    QSCS/11 1 x 230 V 10 % 1,1 1,5 6,3 10 280 370 160 3,7

    QSCS/15 1 x 230 V 10 % 1,5 2 10 16 280 370 160 3,7

    QSCS/22 1 x 230 V 10 % 2,2 3 16 20 280 370 160 3,7

    QSCS/40 1 x 230 V 10 % 4 5,5 25 32 280 370 160 4

    CB-QSCS-en_c_te

    90

    70

    16

    40

    50

    CAPACITOR

    F/450V

    12,5

    30

    20

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

  • 11

    Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel

    QSCQSCQSCQSCQSCS SeriesS SeriesS SeriesS SeriesS Series(60 Hz)(60 Hz)(60 Hz)(60 Hz)(60 Hz)

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of a single-phase submersible electric pump for 4 wells.

    Main switch with thermal protection. Dry running control with float or minimum pressure switch (available separately).

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES DPF single-phase module for overvoltage protection. KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply).

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through an external enable contact. Supply voltage: 1 x 230 V 10%. Frequency: 60 Hz. Power: 0,37 to 2,2 kW. Direct motor start. Protection class: IP55. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Plastic enclosure. Incorporated capacitor.

    SERIE QSCS..6

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    QSCS/036 1 x 230 V 10 % 0,37 0,5 4 6,3 280 370 160 3,7

    QSCS/056 1 x 230 V 10 % 0,55 0,75 4 6,3 280 370 160 3,7

    QSCS/056A 1 x 230 V 10 % 0,55 0,75 6,3 10 280 370 160 3,7

    QSCS/076 1 x 230 V 10 % 0,75 1 6,3 10 280 370 160 3,7

    QSCS/116 1 x 230 V 10 % 1,1 1,5 6,3 10 280 370 160 3,7

    QSCS/116A 1 x 230 V 10 % 1,1 1,5 10 16 280 370 160 3,7

    QSCS/156 1 x 230 V 10 % 1,5 2 10 16 280 370 160 3,7

    QSCS/226 1 x 230 V 10 % 2,2 3 16 20 280 370 160 3,7

    QSCS/406 1 x 230 V 10 % 4 5,5 25 32 280 370 160 4

    CB-QSCS6-en_d_te

    75

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

    CAPACITOR

    F/450V

    20

    35

    50

    50

    25

    40

    40

    25

  • 12

    QCLP10 SeriesQCLP10 SeriesQCLP10 SeriesQCLP10 SeriesQCLP10 Series

    For connection of the electrodes to thepanel we recommend the followingcross sections:

    Three-pole cables can be used for shortlenghts.Otherwise we recommend the use ofunipolar cables placed at suitabledistance from each other to preventthe capacitive effect of the cable frominterfering with the proper operationof the electronic module.

    Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of a single-phase electric pump.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES Drop cable with circular cross section.

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through probes. Supply voltage: 1 x 230 V 10%. Frequency: 50/60 Hz. Voltage to probes: 7,5 V AC at 0,4 mA max. Protection class: IP55. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Enclosure made of plastic material, with clear door enabling access to the magnetothermal switch. Electrodes suitable for water at a maximum temperature of 60C. Set of three electrodes included in the supply. Short-circuit and overload protection C characteristic Power: 0,25 to 1,5 kW.

    TABELLA CAVI

    CABLE SECTION

    mm2

    0 50 0,5

    50 100 0,75

    100 200 1,0

    200 400 2,5

    CB-CASEL-en_b_te

    LENGHT

    m

    SERIE QCLP10

    TYPE MAGNETO- DIMENSIONS WEIGHT

    MAIN SECONDARY CLASS THERMAL SWITCH A x B x C

    V V V A mm Kg

    QCLP10/230 1x230 50/60 Hz - AC3 230 11 C 16A Icn 4,5 KA 205 x 220 x 160 1,5

    CB-QCLP10-en_c_te

    POWER SUPPLY CONTACTOR

    RANGE

  • 13

    SeriesSeriesSeriesSeriesSeriesQCLP10/DIQCLP10/DIQCLP10/DIQCLP10/DIQCLP10/DI

    For connection of the electrodes to thepanel we recommend the followingcross sections:

    Three-pole cables can be used for shortlenghts.Otherwise we recommend the use ofunipolar cables placed at suitabledistance from each other to preventthe capacitive effect of the cable frominterfering with the proper operationof the electronic module.

    Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES Drop cable with circular cross section.

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through probes. Supply voltage: 1 x 230 V 10%. Frequency: 50/60 Hz. Voltage to probes: 7,5 V AC at 0,4 mA max. Protection class: IP55. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Enclosure made of plastic material, with clear door enabling access to the magnetothermal switch. Electrodes suitable for water at a maximum temperature of 60C. Set of three electrodes included in the supply. Short-circuit and overload protection C characteristic. Residual current device A type 30 mA. Power: 0,25 to 1,5 kW.

    TABELLA CAVI

    CABLE SECTION

    mm2

    0 50 0,5

    50 100 0,75

    100 200 1,0

    200 400 2,5

    CB-CASEL-en_b_te

    LENGHT

    m

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of a single-phase electric pump type residual current breaker with overload protection.

    SERIE QCLP10/DI

    TYPE MAGNETO- DIMENSIONS WEIGHT

    MAIN SECONDARY CLASS THERMAL SWITCH A x B x C

    V V V A mm Kg

    QCLP10/230/DI 1x230 50/60 Hz - AC3 230 11 C 16A Icn 4,5 KA 205 x 220 x 160 1,5

    CB-QCLP10-DI-en_a_te

    POWER SUPPLY CONTACTOR

    RANGE

  • 14

    Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel

    QM SeriesQM SeriesQM SeriesQM SeriesQM Series

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of a single-phase electric pump.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply).

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through an external enable contact. Supply voltage: 1 x 230 V 10%. Frequency: 50/60 Hz. Power: 0,25 to 2,2 kW. Direct motor start. Protection class: IP54. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Metal enclosure. Ready for installation of dry running control float or pressure switch (to be ordered separately). Power and thermal overload indicator lights

    SERIE QM

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    QM/02 1 x 230 V 10 % 0,25 0,33 1 1,6 235 265 150 5,8

    QM/03 1 x 230 V 10 % 0,37 0,5 1,6 2,5 235 265 150 5,8

    QM/05 1 x 230 V 10 % 0,55 0,75 2,5 4 235 265 150 5,8

    QM/07 1 x 230 V 10 % 0,75 1 4 6,3 235 265 150 5,8

    QM/15 1 x 230 V 10 % 1,5 2 6,3 10 235 265 150 5,8

    QM/22 1 x 230 V 10 % 2,2 3 10 16 235 265 150 5,8

    CB-QM-en_b_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

    A

    B

    C

    0

    1

    LINEA

    POWER

    TERMICO

    OVERLOAD

  • 15

    Three-phaseThree-phaseThree-phaseThree-phaseThree-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel

    QTD SeriesQTD SeriesQTD SeriesQTD SeriesQTD Series

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of a three-phase electric pump.

    SERIE QTD

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    QTD/02-03 3 x 400 V 10 % 0,25-0,37 0,33-0,50 0,63 1 235 265 150 5,8

    QTD/03-05 3 x 400 V 10 % 0,37-0,55 0,55-0,75 1 1,6 235 265 150 5,8

    QTD/05-07 3 x 400 V 10 % 0,55-0,75 0,75-1 1,6 2,5 235 265 150 5,8

    QTD/07-15 3 x 400 V 10 % 0,75-1,5 1-2 2,5 4 235 265 150 5,8

    QTD/15-22 3 x 400 V 10 % 1,5-2,2 2-3 4 6,3 235 265 150 5,8

    QTD/22-40 3 x 400 V 10 % 2,2-4 3-5,5 6,3 10 235 265 150 5,8

    QTD/40-75 3 x 400 V 10 % 4-7,5 5,5-10 10 16 235 265 150 5,8

    QTD/75-92 3 x 400 V 10 % 7,5-9,2 10-12,5 16 20 235 265 150 5,8

    CB-QTD-en_c_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply).

    SELECTIONSELECTIONSELECTIONSELECTIONSELECTION For a suitable choice of control panel, be sure the electrical input of the motor (Ampere) is included in the rated current value mentioned in the table below.

    A

    B

    C

    0

    1

    LINEA

    POWER

    TERMICO

    OVERLOAD

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Control through an external enable contact. Supply voltage: 3 x 400 V 10%. Frequency: 50/60 Hz. Power: 0,25 to 9,2 kW. Direct motor start. Short-circuit and overload protection. Protection class: IP54. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Metal enclosure. Ready for installation of dry running control float or pressure switch (to be ordered separately). Power and thermal overload indicator lights.

  • 16

    Ready for installation of dry running control float or pressure switch (to be ordered separately). Can be equipped with electronic protection module with electrodes.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply). Float. Pressure switch.

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Manual control through an Auto/Man selector switch. Automatic control through an external enable contact. Supply voltage: 3 x 400 V 10%. Frequency: 50/60 Hz. 24 V AC low voltage auxiliary circuit. Power: 0,25 to 37 kW. Direct motor start. Short-circuit and overload protection. Protection class: IP54. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Metal enclosure. Power, pump running, thermal overload and dry running indicator lights.

    Three-phaseThree-phaseThree-phaseThree-phaseThree-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of a three-phase electric pump.

    SERIE Q3D

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    Q3D/02-03 3 x 400 V 10 % 0,25-0,37 0,33-0,50 0,63 1 300 400 200 15

    Q3D/03-05 3 x 400 V 10 % 0,37-0,55 0,5-0,75 1 1,6 300 400 200 15

    Q3D/05-07 3 x 400 V 10 % 0,55-0,75 0,75-1 1,6 2,5 300 400 200 15

    Q3D/07-15 3 x 400 V 10 % 0,75-1,5 1-2 2,5 4 300 400 200 15

    Q3D/15-22 3 x 400 V 10 % 1,5-2,2 2-3 4 6,3 300 400 200 15

    Q3D/22-40 3 x 400 V 10 % 2,2-4 3-5,5 6,3 10 300 400 200 15

    Q3D/40-75 3 x 400 V 10 % 4-7,5 5,5-10 10 16 300 400 200 15

    Q3D/75-92 3 x 400 V 10 % 7,5-9,2 10-12,5 16 20 300 400 200 15

    Q3D/92-110 3 x 400 V 10 % 9,2-11 12,5-15 20 25 300 400 200 20

    Q3D/110-150 3 x 400 V 10 % 11-15 15-20 22 32 400 500 200 20

    Q3D/150-185 3 x 400 V 10 % 15-18,5 20-25 28 40 400 500 200 20

    Q3D/185-220 3 x 400 V 10 % 18,5-22 25-30 36 50 400 600 200 27

    Q3D/220-300 3 x 400 V 10 % 22-30 30-40 45 63 400 600 200 27

    Q3D/300-370 3 x 400 V 10 % 30-37 40-50 57 75 400 600 200 27

    CB-Q3D-en_a_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

    Q3D SeriesQ3D SeriesQ3D SeriesQ3D SeriesQ3D Series

    0

    200

    150A

    25

    0

    V 500300

    50 0

    L1-L2

    L2-L3

    L3-L1

    0M A

    A

    B

    C

  • 17

    Three-phaseThree-phaseThree-phaseThree-phaseThree-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel

    Q3Y SeriesQ3Y SeriesQ3Y SeriesQ3Y SeriesQ3Y Series

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of a three-phase electric pump.

    SERIE Q3Y

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    Q3Y/40-75 3 x 400 V 10 % 4-7,5 5,5-10 10 16 400 600 200 23

    Q3Y/75-92 3 x 400 V 10 % 7,5-9,2 10-12,5 16 20 400 600 200 23

    Q3Y/92-110 3 x 400 V 10 % 9,2-11 12,5-15 20 25 400 600 200 23

    Q3Y/110-150 3 x 400 V 10 % 11-15 15-20 22 32 400 600 200 23

    Q3Y/150-185 3 x 400 V 10 % 15-18,5 20-25 28 40 400 600 200 23

    Q3Y/185-220 3 x 400 V 10 % 18,5-22 25-30 36 50 500 700 200 32

    Q3Y/220-300 3 x 400 V 10 % 22-30 30-40 45 63 500 700 200 32

    Q3Y/300-370 3 x 400 V 10 % 30-37 40-50 57 75 600 800 250 68

    Q3Y/370-450 3 x 400 V 10 % 37-45 50-60 70 90 600 800 250 80

    Q3Y/450-550 3 x 400 V 10 % 45-55 60-75 80 108 600 900 250 80

    Q3Y/550-750 3 x 400 V 10 % 55-75 75-100 105 138 600p 1300p 300p 109

    Q3Y/750-900 3 x 400 V 10 % 75-90 100-125 138 185 600p 1300p 300p 109

    Q3Y/900-1100 3 x 400 V 10 % 90-110 125-150 175 210 600p 1500p 300p 120

    Q3Y/1100-1320 3 x 400 V 10 % 110-132 150-180 210 260 800p 1700p 400p 130

    Q3Y/1320-1600 3 x 400 V 10 % 132-160 180-218 250 305 800p 1700p 400p 130

    Q3Y/1600-2000 3 x 400 V 10 % 160-200 218-273 290 400 800p 1900p 400p 140

    Q3Y/2000-2500 3 x 400 V 10 % 200-250 273-340 400 460 1000p 1900p 400p 180

    Q3Y/2500-3150 3 x 400 V 10 % 250-315 340-430 450 580 1000p 1900p 400p 180

    Dimensions note : P indicates floor mounted control panel. CB-Q3Y-en_c_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

    Ready for installation of dry running control float or pressure switch (to be ordered separately). Can be equipped with electronic protection module with electrodes.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply). Float. Pressure switch.

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Manual control through an Auto/Man selector switch. Automatic control through an external enable contact. Supply voltage: 3 x 400 V 10%. Frequency: 50/60 Hz. 24 V AC low voltage auxiliary circuit. Power: 4 to 315 kW. Star-delta starting. Short-circuit and overload protection. Protection class: IP54. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Metal enclosure. Power, pump running, thermal overload and dry running indicator lights.

    0

    200

    150A

    25

    0

    V 500300

    50 0

    L1-L2

    L2-L3

    L3-L1

    0M A

    A

    B

    C

  • 18

    Three-phaseThree-phaseThree-phaseThree-phaseThree-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel

    Q3I SeriesQ3I SeriesQ3I SeriesQ3I SeriesQ3I Series

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of a three-phase electric pump.

    SERIE Q3I

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    Q3I/40-75 3 x 400 V 10 % 4-7,5 5,5-10 10 16 400 600 250 35

    Q3I/75-92 3 x 400 V 10 % 7,5-9,2 10-12,5 16 20 400 600 250 35

    Q3I/92-110 3 x 400 V 10 % 9,2-11 12,5-15 20 25 400 600 250 35

    Q3I/110-150 3 x 400 V 10 % 11-15 15-20 22 32 500 700 250 50

    Q3I/150-185 3 x 400 V 10 % 15-18,5 20-25 28 40 500 700 250 50

    Q3I/185-220 3 x 400 V 10 % 18,5-22 25-30 36 50 500 700 250 50

    Q3I/220-300 3 x 400 V 10 % 22-30 30-40 45 63 500 700 250 65

    Q3I/300-370 3 x 400 V 10 % 30-37 40-50 57 75 500 700 250 65

    Q3I/370-450 3 x 400 V 10 % 37-45 50-60 70 90 600 900 250 65

    Q3I/450-550 3 x 400 V 10 % 45-55 60-75 80 108 600p 1300p 300p 100

    Q3I/550-750 3 x 400 V 10 % 55-75 75-100 105 138 600p 1300p 300p 100

    Q3I/750-900 3 x 400 V 10 % 75-90 100-125 138 185 600p 1500p 300p 100

    Q3I/900-1100 3 x 400 V 10 % 90-110 125-150 175 210 800p 1700p 400p 100

    Q3I/1100-1320 3 x 400 V 10 % 110-132 150-180 210 260 800p 1700p 400p 150

    Q3I/1320-1600 3 x 400 V 10 % 132-160 180-218 250 305 800p 1700p 400p 150

    Q3I/1600-2000 3 x 400 V 10 % 160-200 218-273 290 400 800p 1900p 400p 160

    Q3I/2000-2500 3 x 400 V 10 % 200-250 273-340 400 460 1000p 1900p 400p 180

    Q3I/2500-3150 3 x 400 V 10 % 250-315 340-430 450 580 1000p 1900p 400p 200

    Dimensions note : P indicates floor mounted control panel. CB-Q3I-en_c_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

    Ready for installation of dry running control float or pressure switch (to be ordered separately). Can be equipped with electronic protection module with electrodes.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply). Float. Pressure switch.

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Manual control through an Auto/Man selector switch. Automatic control through an external enable contact. Supply voltage: 3 x 400 V 10%. Frequency: 50/60 Hz. 24 V AC low voltage auxiliary circuit. Power: 4 to 315 kW. Impedance start. Short-circuit and overload protection. Protection class: IP54. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Metal enclosure. Power, pump running, thermal overload and dry running indicator lights.

    0

    200

    150A

    25

    0

    V 500300

    50 0

    L1-L2

    L2-L3

    L3-L1

    0M A

    A

    B

    C

  • 19

    Three-phaseThree-phaseThree-phaseThree-phaseThree-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel

    Q3A SeriesQ3A SeriesQ3A SeriesQ3A SeriesQ3A Series

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of a three-phase electric pump.

    SERIE Q3A

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    Q3A/40-75 3 x 400 V 10 % 4-7,5 5,5-10 10 16 500 700 250 50

    Q3A/75-92 3 x 400 V 10 % 7,5-9,2 10-12,5 16 20 500 700 250 50

    Q3A/92-110 3 x 400 V 10 % 9,2-11 12,5-15 20 25 500 700 250 50

    Q3A/110-150 3 x 400 V 10 % 11-15 15-20 22 32 500 700 250 50

    Q3A/150-185 3 x 400 V 10 % 15-18,5 20-25 28 40 500 700 250 50

    Q3A/185-220 3 x 400 V 10 % 18,5-22 25-30 36 50 500 700 250 50

    Q3A/220-300 3 x 400 V 10 % 22-30 30-40 45 63 600 900 300 80

    Q3A/300-370 3 x 400 V 10 % 30-37 40-50 57 75 600 900 300 80

    Q3A/370-450 3 x 400 V 10 % 37-45 50-60 70 90 600p 1300p 300p 90

    Q3A/450-550 3 x 400 V 10 % 45-55 60-75 80 108 600p 1500p 300p 120

    Q3A/550-750 3 x 400 V 10 % 55-75 75-100 105 138 600p 1500p 300p 120

    Q3A/750-900 3 x 400 V 10 % 75-90 100-125 138 185 600p 1700p 400p 150

    Q3A/900-1100 3 x 400 V 10 % 90-110 125-150 175 210 800p 1900p 400p 150

    Q3A/1100-1320 3 x 400 V 10 % 110-132 150-180 210 260 800p 1900p 400p 200

    Q3A/1320-1600 3 x 400 V 10 % 132-160 180-218 250 305 800p 1900p 400p 200

    Q3A/1600-2000 3 x 400 V 10 % 160-200 218-273 290 400 800p 1900p 400p 230

    Q3A/2000-2500 3 x 400 V 10 % 200-250 273-340 400 460 1000p 1900p 400p 230

    Q3A/2500-3150 3 x 400 V 10 % 250-315 340-430 450 580 1000p 1900p 400p 250

    Dimensions note : P indicates floor mounted control panel. CB-Q3A-en_c_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

    Ready for installation of dry running control float or pressure switch (to be ordered separately). Can be equipped with electronic protection module with electrodes.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply). Float. Pressure switch.

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Manual control through an Auto/Man selector switch. Automatic control through an external enable contact. Supply voltage: 3 x 400 V 10%. Frequency: 50/60 Hz. 24 V AC low voltage auxiliary circuit. Power: 4 to 315 kW. Starting autotransformer. Short-circuit and overload protection. Protection class: IP54. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Metal enclosure. Power, pump running, thermal overload and dry running indicator lights.

    0

    200

    150A

    25

    0

    V 500300

    50 0

    L1-L2

    L2-L3

    L3-L1

    0M A

    A

    B

    C

  • 20

    Three-phaseThree-phaseThree-phaseThree-phaseThree-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel

    Q3SF SeriesQ3SF SeriesQ3SF SeriesQ3SF SeriesQ3SF Series

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of a three-phase electric pump.

    Protections against phase failure / phase sequence / frequency out of limits on power supply line. Low-voltage protection on auxiliary circuits. Protection against starter overtemperature / overload / malfunction. Protection against overload / locked rotor / current asymmetry on motor side. Short-circuit protection on inputs and outputs. RS232 interface for remote control and RS485 for use of remote keypanel. Incorporated by-pass contactor.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply). Float. Pressure switch.

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Manual control through an Auto/Man selector switch. Automatic control through an external enable contact. Supply voltage: 3 x 400 V 10%. Frequency: 50/60 Hz. 24 V AC low voltage auxiliary circuit. Power: 5,5 to 160 kW. Softstart with torque control. Protection class: IP54. Ambient temperature: -5 to +40 C Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Metal enclosure. Dry running indicator light. Power - pump running - malfunction LEDs on starter keypanel. ON/OFF selector switch for activation of by-pass contactor. Ready for installation of dry running control float or pressure switch (to be ordered separately). Can be equipped with electronic protection module with electrodes.

    STSTSTSTSTAAAAATIC STTIC STTIC STTIC STTIC STARTERARTERARTERARTERARTERCHARACTERISTICCHARACTERISTICCHARACTERISTICCHARACTERISTICCHARACTERISTICSSSSS Static starter for gradual start-up/ shutdown, featuring: keypanel with liquid crystal display showing voltage, absorbed current, cos , operating hours, number of starts, last twenty messages on system status (events / alarms).

    0M A

    A

    B

    C

    SERIE Q3SF

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    Q3SF 75 3 x 400 V 10 % 5,5 - 7,5 7,5 -10 8,5 17 400 600 250 35

    Q3SF 150 3 x 400 V 10 % 9,2 - 15 12,5 - 20 15 30 500 700 250 40

    Q3SF 220 3 x 400 V 10 % 18,5 - 22 25 - 30 28 45 500 700 250 40

    Q3SF 300 3 x 400 V 10 % 30 40 42 60 600 800 300 50

    Q3SF 370 3 x 400 V 10 % 37 50 55 75 600 800 300 50

    Q3SF 450 3 x 400 V 10 % 45 60 70 85 600 800 300 50

    Q3SF 550 3 x 400 V 10 % 55 75 80 110 600 900 300 60

    Q3SF 590 3 x 400 V 10 % 59 80 105 125 600 900 300 60

    Q3SF 750 3 x 400 V 10 % 75 100 120 142 600p 1700p 400p 120

    Q3SF 900 3 x 400 V 10 % 90 125 135 190 600p 1700p 400p 120

    Q3SF 1100-1320 3 x 400 V 10 % 110 - 132 150 - 180 185 245 600p 1700p 400p 120

    Q3SF 1600 3 x 400 V 10 % 160 218 250 305 1200p 1900p 500p 200

    Dimensions note : P indicates floor mounted control panel. CB-Q3SF-en_c_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

  • 21

    ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps

    QDRM SeriesQDRM SeriesQDRM SeriesQDRM SeriesQDRM Seriessingle-phasesingle-phasesingle-phasesingle-phasesingle-phase

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of one single-phase drainage pump.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES Audible or visual signalling device, 12 Vdc 0.3 A max (two connection terminals provided inside the electrical panel) for high-level alarm.

    SERIE QDRM

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    QDRM/02 1 x 230 V 10 % 0,25 0,33 1 1,6 280 220 160 2,2

    QDRM/03 1 x 230 V 10 % 0,37 0,5 1,6 2,5 280 220 160 2,2

    QDRM/05 1 x 230 V 10 % 0,55 0,75 2,5 4 280 220 160 2,2

    QDRM/07 1 x 230 V 10 % 0,75 1 4 6,3 280 220 160 2,2

    QDRM/15 1 x 230 V 10 % 1,1 1,5 1,5 2 6,3 10 280 220 160 2,2

    QDRM/22 1 x 230 V 10 % 2,2 3 10 16 280 370 160 4,1

    CB-QDRM-en_c_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through electromechanical floats. Power supply voltage: 1 x 230 V 10%. Frequency: 50/60 Hz. Power: 0,25 to 2,2 kW. Direct motor start. Protection class: IP55 Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Plastic enclosure. Electronic control module with test and alarm reset buttons, and power-on, pump running, high level alarm indicator LEDs and thermal probe. Alarm silencing button.

  • 22

    ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps

    QDRMC SeriesQDRMC SeriesQDRMC SeriesQDRMC SeriesQDRMC Seriessingle-phasesingle-phasesingle-phasesingle-phasesingle-phase

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of one single-phase drainage pump with external capacitor.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES Audible or visual signalling device, 12 Vdc 0,3 A max (two connection terminals provided inside the electrical panel) for high-level alarm.

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through electromechanical floats. Power supply voltage: 1 x 230 V 10%. Frequency: 50/60 Hz. Power: 0,75 to 2,2 kW. Direct motor start. Protection class: IP55. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Plastic enclosure. Electronic control module with test and alarm reset buttons, and power-on, pump running, high level alarm, indicator LEDs and thermal probe. Alarm silencing button. Start and run capacitor incorporated in the control panel. /TS/GL versions for electropumps GLS/GLV series.

    SERIE QDRMC

    MODEL RATED WEIGHT C Cs

    VOLTAGE A B C

    V kW HP mm mm mm Kg uF uF

    QDRMC/15/TS/GL 1 x 230 V 10 % 1,5 2 6,3 10 280 370 160 4 35 100

    C= Run capacitor; Cs= Start capacitor CB-QDRMC-en_f_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

  • 23

    ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps

    QDR SeriesQDR SeriesQDR SeriesQDR SeriesQDR Seriesthree-phasethree-phasethree-phasethree-phasethree-phase

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of one three-phase drainage pump.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES Audible or visual signalling device, 12 Vdc 0,3 A max (two connection terminals provided inside the electrical panel) for high-level alarm.

    SERIE QDR

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    QDR/03 3 x 400 V 10 % 0,37 0,5 0,63 1 280 370 150 4,1

    QDR/05 3 x 400 V 10 % 0,55 0,75 1 1,6 280 370 150 4,1

    QDR/07 3 x 400 V 10 % 0,75 1 1,6 2,5 280 370 150 4,1

    QDR/15 3 x 400 V 10 % 1,1 1,5 1,5 2 2,5 4 280 370 150 4,1

    QDR/22 3 x 400 V 10 % 2,2 3 4 6,3 280 370 150 4,1

    QDR/40 3 x 400 V 10 % 3 4 4 5,5 6,3 10 280 370 150 4,1

    QDR/75 3 x 400 V 10 % 5,5 7,5 7,5 10 10 16 280 370 150 4,1

    QDR/07/TS 3 x 400 V 10 % 0,75 1 1,6 2,5 280 370 150 4,5

    QDR/15/TS 3 x 400 V 10 % 1,5 2 2,5 4 280 370 150 4,5

    QDR/22/TS 3 x 400 V 10 % 2,2 3 4 6,3 280 370 150 4,5

    QDR/07/WD 3 x 400 V 10 % 0,75 1 1,6 2,5 280 370 150 5

    QDR/15/WD 3 x 400 V 10 % 1,5 2 2,5 4 280 370 150 5

    QDR/22/WD 3 x 400 V 10 % 2,2 3 4 6,3 280 370 150 5

    The /WD option also includes the /TS option. CB-QDR-en_c_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through electromechanical floats. Power supply voltage: 3 x 400 V 10%. Frequency: 50/60 Hz. Power: 0,37 to 9,2 kW. Direct motor start. Protection class: IP55. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Plastic enclosure. Electronic control module with test and alarm reset buttons, and power-on, pump running, high level alarm, indicator LEDs and thermal probe. Alarm silencing button. /TS version equipped with stator thermal protection circuit. /WD version equipped with oil chamber water sensor control circuit and stator thermal protection.

  • 24

    ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps

    QYR SeriesQYR SeriesQYR SeriesQYR SeriesQYR Seriesthree-phasethree-phasethree-phasethree-phasethree-phase

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of one three-phase drainage pump with star-delta start.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES Audible or visual signalling device, 12 Vdc 0,3 A max (two connection terminals provided inside the electrical panel) for high-level alarm. Signal relay board kit RILS20 (power, auto/man, start/stop, thermal overload, high level).

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through electromechanical floats. Power supply voltage: 3 x 400 V 10%. Frequency: 50/60 Hz. Power: 3 to 75 kW. Star-delta motor start. Protection class: IP54. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Metal enclosure. Electronic board with power, thermal overload, high level alarm, pump start/stop indicator LEDs. Alarm silencing button. /TS version equipped with stator thermal protection circuit. /WD version equipped with oil chamber water sensor control circuit and stator thermal protection.

    Control box

    0 O

    FF

    1 ON

    LINEA

    POWER

    BLOCCO

    TERMICO

    ALLARME

    OVER

    LOAD

    ALARM

    RESET

    ALLARME

    ALARM

    AUT MAN

    AUT MAN

    OFF ON

    P1

    OFF ON

    P2

    COD.168276440

    A

    B

    C

  • 25

    QYR SERIES PQYR SERIES PQYR SERIES PQYR SERIES PQYR SERIES PANELSANELSANELSANELSANELSELECTRICAL DAELECTRICAL DAELECTRICAL DAELECTRICAL DAELECTRICAL DATTTTTA TA TA TA TA TABLEABLEABLEABLEABLESERIE QYR

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    QYR/40 3 x 400 V 10 % 3 4 4 5,5 6,3 10 400 500 200 25

    QYR/75 3 x 400 V 10 % 5,5 7,5 7.5 10 10 16 400 500 200 25

    QYR/92 3 x 400 V 10 % 9,2 12,5 16 20 400 500 200 25

    QYR/110 3 x 400 V 10 % 11 15 20 25 400 500 200 25

    QYR/150 3 x 400 V 10 % 15 20 22 32 400 600 200 27

    QYR/185 3 x 400 V 10 % 18,5 25 28 40 400 600 200 27

    QYR/220 3 x 400 V 10 % 22 30 36 50 500 700 200 32

    QYR/300 3 x 400 V 10 % 30 40 45 63 500 700 200 32

    QYR/370 3 x 400 V 10 % 37 50 57 75 600 800 250 32

    QYR/450 3 x 400 V 10 % 45 60 70 90 600 800 250 32

    QYR/550 3 x 400 V 10 % 55 75 80 108 600 900 250 37

    QYR/750 3 x 400 V 10 % 75 100 105 138 600p 1300p 300p 70

    QYR/22/TS 3 x 400 V 10 % 2,2 3 4 6,3 400 500 200 25

    QYR/40/TS 3 x 400 V 10 % 3 4 4 5,5 6,3 10 400 500 200 26

    QYR/75/TS 3 x 400 V 10 % 5,5 7,5 7,5 10 10 16 400 500 200 26

    QYR/92/TS 3 x 400 V 10 % 9,2 12,5 16 20 400 500 200 26

    QYR/110/TS 3 x 400 V 10 % 11 15 20 25 400 500 200 26

    QYR/150/TS 3 x 400 V 10 % 15 20 22 32 400 600 200 27

    QYR/185/TS 3 x 400 V 10 % 18,5 25 28 40 400 600 200 27

    QYR/220/TS 3 x 400 V 10 % 22 30 36 50 500 700 200 32

    QYR/300/TS 3 x 400 V 10 % 30 40 45 63 500 700 200 32

    QYR/370/TS 3 x 400 V 10 % 37 50 57 75 600 800 250 33

    QYR/450/TS 3 x 400 V 10 % 45 60 70 90 600 800 250 33

    QYR/550/TS 3 x 400 V 10 % 55 75 80 108 600 900 250 37

    QYR/750/TS 3 x 400 V 10 % 75 100 105 138 600p 1300p 300p 70

    QYR/40/WD 3 x 400 V 10 % 3 4 4 5,5 6,3 10 400 500 200 26

    QYR/75/WD 3 x 400 V 10 % 5,5 7,5 7,5 10 10 16 400 500 200 26

    QYR/92/WD 3 x 400 V 10 % 9,2 12,5 16 20 400 500 200 26

    QYR/110/WD 3 x 400 V 10 % 11 15 20 25 400 500 200 26

    QYR/150/WD 3 x 400 V 10 % 15 20 22 32 400 600 200 28

    QYR/185/WD 3 x 400 V 10 % 18,5 25 28 40 400 600 200 28

    QYR/220/WD 3 x 400 V 10 % 22 30 36 50 500 700 200 33

    QYR/300/WD 3 x 400 V 10 % 30 40 45 63 500 700 200 33

    QYR/370/WD 3 x 400 V 10 % 37 50 57 75 600 800 250 33

    QYR/450/WD 3 x 400 V 10 % 45 60 70 90 600 800 250 33

    QYR/550/WD 3 x 400 V 10 % 55 75 80 108 600 900 250 38

    QYR/750/WD 3 x 400 V 10 % 75 100 105 138 600p 1300p 300p 71

    Dimensions: p = floor-standing cabinet. CB-QYR-en_e_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

  • 26

    ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps

    QDRM2 SeriesQDRM2 SeriesQDRM2 SeriesQDRM2 SeriesQDRM2 Seriessingle-phasesingle-phasesingle-phasesingle-phasesingle-phase

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of two single-phase drainage pumps.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES Audible or visual signalling device, 12 Vdc 0,3 A max (two connection terminals provided inside the electrical panel) for high-level alarm. Signal relay board kit RILS20 (power, auto/man, start/stop, thermal overload, high level).

    SERIE QDRM2

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    QDRM2/02 1 x 230 V 10 % 0,25 0,33 1 1,6 260 380 150 9,4

    QDRM2/03 1 x 230 V 10 % 0,37 0,5 1,6 2,5 260 380 150 9,4

    QDRM2/05 1 x 230 V 10 % 0,55 0,75 2,5 4 260 380 150 9,4

    QDRM2/07 1 x 230 V 10 % 0,75 1 4 6,3 260 380 150 9,4

    QDRM2/15 1 x 230 V 10 % 1,1 1,5 1,5 2 6,3 10 260 380 150 9,4

    QDRM2/22 1 x 230 V 10 % 2,2 3 10 16 260 380 150 9,4

    CB-QDRM2-en_a_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through electromechanical floats. Power supply voltage: 1 x 230 V 10%. Frequency: 50/60 Hz. Power: 0,25 to 2,2 kW. Direct motor start. Protection class: IP54. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Metal enclosure. Electronic board with power, thermal overload, high level alarm, pump start/stop indicator LEDs. Alarm silencing button.

    Control box

    0 O

    FF

    1 ON

    LINEA

    POWER

    BLOCCO

    TERMICO

    ALLARME

    OVER

    LOAD

    ALARM

    RESET

    ALLARME

    ALARM

    AUT MAN

    AUT MAN

    OFF ON

    P1

    OFF ON

    P2

    COD.168276440

    A

    B

    C

  • 27

    ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps

    QDRMC2 SeriesQDRMC2 SeriesQDRMC2 SeriesQDRMC2 SeriesQDRMC2 Seriessingle-phasesingle-phasesingle-phasesingle-phasesingle-phase

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of two single-phase drainage pumps with external capacitor.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES Audible or visual signalling device, 12 Vdc 0,3 A max (two connection terminals provided inside the electrical panel) for high-level alarm. Signal relay board kit RILS20 (power, auto/man, start/stop, thermal overload, high level).

    Control box

    0 O

    FF

    1 ON

    LINEA

    POWER

    BLOCCO

    TERMICO

    ALLARME

    OVER

    LOAD

    ALARM

    RESET

    ALLARME

    ALARM

    AUT MAN

    AUT MAN

    OFF ON

    P1

    OFF ON

    P2

    COD.168276440

    A

    B

    C

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through electromechanical floats. Power supply voltage: 1 x 230 V 10%. Frequency: 50/60 Hz. Power: 0,75 to 2,2 kW. Direct motor start. Protection class: IP54. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Plastic enclosure. Electronic board with power, thermal overload, high level alarm, pump start/stop indicator LEDs. Start and run capacitor incorporated in the control panel. /TS/GL versions for electropumps GLS/GLV series.

    SERIE QDRMC2

    MODEL RATED WEIGHT C Cs

    VOLTAGE A B C

    V kW HP mm mm mm Kg uF uF

    QDRMC2/15/TS/GL 1 x 230 V 10 % 1,5 2 6,3 10 390 470 130 10 35 100

    C = Run capacitor; Cs = Start capacitor. CB-QDRMC2-en_e_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

  • 28

    ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps

    QXR20 SeriesQXR20 SeriesQXR20 SeriesQXR20 SeriesQXR20 Seriessingle-phasesingle-phasesingle-phasesingle-phasesingle-phase

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of two single-phase drainage pumps.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES Signal relay board kit RILS20 (power, auto man, start/stop, thermal overload, high level).

    SERIE QXR20

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    QXR20 1 x 230 V 10 % 0,25 1,5 0,33 2 1 10 205 220 160 1,5

    CB-QXR20-en_a_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through electromechanical floats. Power supply voltage: 1 x 230 V 10%. Frequency: 50/60 Hz. Power: 0,25 to 1,5 kW. Direct motor start. Protection class: IP55. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Plastic enclosure. Electronic board with power, thermal overload, acustic alarm of high level, pump, start/stop indicator LEDs. Alarm silencing button. Cyclic exchange starting pumps. Aut-0-Man selector (1 for each pump). One pump is controlled by the closing of internal contact that is inside the control card.

  • 29

    ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps

    QDR2 SeriesQDR2 SeriesQDR2 SeriesQDR2 SeriesQDR2 Seriesthree-phasethree-phasethree-phasethree-phasethree-phase

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of two three-phase drainage pumps.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES Audible or visual signalling device, 12 Vdc 0,3 A max (two connection terminals provided inside the electrical panel) for high-level alarm. Signal relay board kit RILS20 (power, auto/man, start/stop, thermal overload, high level).

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through electromechanical floats. Power supply voltage: 3 x 400 V 10%. Frequency: 50/60 Hz. Power: 0,37 to 9,2 kW. Direct motor start. Protection class: IP54. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Metal enclosure. Electronic board with power, thermal overload, high level alarm, pump start/stop indicator LEDs. Alarm silencing button. /TS version equipped with stator thermal protection circuit. /WD version equipped with oil chamber water sensor control circuit and stator thermal protection.

    Control box

    0 O

    FF

    1 ON

    LINEA

    POWER

    BLOCCO

    TERMICO

    ALLARME

    OVER

    LOAD

    ALARM

    RESET

    ALLARME

    ALARM

    AUT MAN

    AUT MAN

    OFF ON

    P1

    OFF ON

    P2

    COD.168276440

    A

    B

    C

    SERIE QDR2

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    QDR2/03 3 x 400 V 10 % 0,37 0,5 0,63 1 260 380 150 9,4

    QDR2/05 3 x 400 V 10 % 0,55 0,75 1 1,6 260 380 150 9,4

    QDR2/07 3 x 400 V 10 % 0,75 1 1,6 2,5 260 380 150 9,4

    QDR2/15 3 x 400 V 10 % 1,1 1,5 1,5 2 2,5 4 260 380 150 9,4

    QDR2/22 3 x 400 V 10 % 2,2 3 4 6,3 260 380 150 9,4

    QDR2/40 3 x 400 V 10 % 3 4 4 5,5 6,3 10 260 380 150 9,4

    QDR2/75 3 x 400 V 10 % 5,5 7,5 7,5 10 10 16 260 380 150 9,4

    QDR2/92 3 x 400 V 10 % 9,2 12,5 16 20 300 400 180 11

    QDR2/07/TS 3 x 400 V 10 % 0,75 1 1,6 2,5 400 400 200 14

    QDR2/15/TS 3 x 400 V 10 % 1,1 1,5 1,5 2 2,5 4 400 400 200 14

    QDR2/22/TS 3 x 400 V 10 % 2,2 3 4 6,3 400 400 200 14

    QDR2/07/WD 3 x 400 V 10 % 0,75 1 1,6 2,5 400 500 200 18

    QDR2/15/WD 3 x 400 V 10 % 1,1 1,5 1,5 2 2,5 4 400 500 200 18

    QDR2/22/WD 3 x 400 V 10 % 2,2 3 4 6,3 400 500 200 18

    The /WD option also includes the /TS option. CB-QDR2-en_b_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

  • 30

    ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps

    QYR2 SeriesQYR2 SeriesQYR2 SeriesQYR2 SeriesQYR2 Seriesthree-phasethree-phasethree-phasethree-phasethree-phase

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Protection and control of two three-phase drainage pumps with star-delta start.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES Audible or visual signalling device, 12 Vdc 0,3 A max (two connection terminals provided inside the electrical panel) for high-level alarm. Signal relay board kit RILS20 (power, auto/man, start/stop, thermal overload, high level).

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through electromechanical floats. Power supply voltage: 3 x 400 V 10%. Frequency: 50/60 Hz. Power: 3 to 75 kW. Star-delta motor start. Protection class: IP54. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Metal enclosure. Electronic board with power, thermal overload, high level alarm, pump start/stop indicator LEDs. Alarm silencing button. /TS version equipped with stator thermal protection circuit. /WD version equipped with oil chamber water sensor control circuit and stator thermal protection.

    Control box

    0 O

    FF

    1 ON

    LINEA

    POWER

    BLOCCO

    TERMICO

    ALLARME

    OVER

    LOAD

    ALARM

    RESET

    ALLARME

    ALARM

    AUT MAN

    AUT MAN

    OFF ON

    P1

    OFF ON

    P2

    COD.168276440

    A

    B

    C

  • 31

    SERIE QYR2

    MODEL RATED WEIGHT

    VOLTAGE A B C

    V kW HP mm mm mm Kg

    QYR2/40 3 x 400 V 10 % 3 4 4 5,5 6,3 10 500 700 200 55

    QYR2/75 3 x 400 V 10 % 5,5 7,5 7,5 10 10 16 500 700 200 55

    QYR2/92 3 x 400 V 10 % 9,2 12,5 16 20 500 700 200 55

    QYR2/110 3 x 400 V 10 % 11 15 20 25 500 700 200 55

    QYR2/150 3 x 400 V 10 % 15 20 22 32 600 800 250 68

    QYR2/185 3 x 400 V 10 % 18,5 25 28 40 600 800 250 68

    QYR2/220 3 x 400 V 10 % 22 30 36 50 600 900 250 75

    QYR2/300 3 x 400 V 10 % 30 40 45 63 600 900 250 75

    QYR2/370 3 x 400 V 10 % 37 50 57 75 600p 1300p 300p 92

    QYR2/450 3 x 400 V 10 % 45 60 70 90 800p 1700p 300p 125

    QYR2/550 3 x 400 V 10 % 55 75 80 108 800p 1700p 300p 125

    QYR2/750 3 x 400 V 10 % 75 100 105 138 800p 1900p 300p 148

    QYR2/22/TS 3 x 400 V 10 % 2,2 3 4 6,3 500 700 200 55

    QYR2/40/TS 3 x 400 V 10 % 3 4 4 5,5 6,3 10 500 700 200 55

    QYR2/75/TS 3 x 400 V 10 % 5,5 7,5 7,5 10 10 16 500 700 200 55

    QYR2/92/TS 3 x 400 V 10 % 9,2 12,5 16 20 500 700 200 55

    QYR2/110/TS 3 x 400 V 10 % 11 15 20 25 500 700 200 55

    QYR2/150/TS 3 x 400 V 10 % 15 20 22 32 600 800 250 68

    QYR2/185/TS 3 x 400 V 10 % 18,5 25 28 40 600 800 250 68

    QYR2/220/TS 3 x 400 V 10 % 22 30 36 50 600 900 250 75

    QYR2/300/TS 3 x 400 V 10 % 30 40 45 63 600 900 250 75

    QYR2/370/TS 3 x 400 V 10 % 37 50 57 75 600p 1300p 300p 92

    QYR2/450/TS 3 x 400 V 10 % 45 60 70 90 800p 1700p 300p 125

    QYR2/550/TS 3 x 400 V 10 % 55 75 80 108 800p 1700p 300p 125

    QYR2/750/TS 3 x 400 V 10 % 75 100 105 138 800p 1900p 300p 148

    QYR2/40/WD 3 x 400 V 10 % 3 4 4 5,5 6,3 10 500 700 200 55

    QYR2/75/WD 3 x 400 V 10 % 5,5 7,5 7,5 10 10 16 500 700 200 55

    QYR2/92/WD 3 x 400 V 10 % 9,2 12,5 16 20 500 700 200 55

    QYR2/110/WD 3 x 400 V 10 % 11 15 20 25 500 700 200 55

    QYR2/150/WD 3 x 400 V 10 % 15 20 22 32 600 800 250 68

    QYR2/185/WD 3 x 400 V 10 % 18,5 25 28 40 600 800 250 68

    QYR2/220/WD 3 x 400 V 10 % 22 30 36 50 600 900 250 75

    QYR2/300/WD 3 x 400 V 10 % 30 40 45 63 600 900 250 75

    QYR2/370/WD 3 x 400 V 10 % 37 50 57 75 600p 1300p 300p 92

    QYR2/450/WD 3 x 400 V 10 % 45 60 70 90 800p 1700p 300p 125

    QYR2/550/WD 3 x 400 V 10 % 55 75 80 108 800p 1700p 300p 125

    QYR2/750/WD 3 x 400 V 10 % 75 100 105 138 800p 1900p 300p 148

    Dimensions: p = floor-standing cabinet. CB-QYR2-en_b_te

    A

    RATED

    POWER

    DIMENSIONSRATED

    CURRENT

    QYR2 SERIES PQYR2 SERIES PQYR2 SERIES PQYR2 SERIES PQYR2 SERIES PANELSANELSANELSANELSANELSELECTRIC DAELECTRIC DAELECTRIC DAELECTRIC DAELECTRIC DATTTTTA TA TA TA TA TABLEABLEABLEABLEABLE

  • 32

    For connection of the electrodes to thepanel we recommend the followingcross sections:

    Three-pole cables can be used for shortlenghts.Otherwise we recommend the use ofunipolar cables placed at suitabledistance from each other to preventthe capacitive effect of the cable frominterfering with the proper operationof the electronic module.

    LevelLevelLevelLevelLevelControlControlControlControlControlPPPPPanelanelanelanelanel

    QCL5 SeriesQCL5 SeriesQCL5 SeriesQCL5 SeriesQCL5 Series

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Accessory for electric pump control panels, suitable for tank filling or drainage applications or for activation of audible or visual alarms.

    SERIE QCL5

    TYPE POWER SUPPLY DIMENSIONS WEIGHT

    VOLTAGE FREQUENCY POWER TYPE A x B x C

    V Hz W V A mm Kg

    QCL5/24 1 x 24 50/60 2

    QCL5/230 1 x 230 50/60 2

    CB-QCL5-en_a_te

    CONTACT

    0,5

    RANGE

    90 x 130 x 60NO-C-NC 48 3

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES Drop cable with circular cross section.

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through probes. Supply voltage: 1 x 230 V 10% or 1 x 24 V 10%. Frequency: 50/60 Hz. Voltage to probes: 15 V AC at 0,5 mA max. Switch contact 48 V AC at 3 A max (250 W max). Protection class: IP55. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Plastic enclosure. Electrodes suitable for water at a maximum temperature of 40C. Set of three electrodes included in the supply.

    TABELLA CAVI

    CABLE SECTION

    mm2

    0 50 0,5

    50 100 0,75

    100 200 1,0

    200 400 2,5

    CB-CASEL-en_b_te

    LENGHT

    m

    Control box

    A

    B

    C

  • 33

    QCL10 SeriesQCL10 SeriesQCL10 SeriesQCL10 SeriesQCL10 Series

    For connection of the electrodes to thepanel we recommend the followingcross sections:

    Three-pole cables can be used for shortlenghts.Otherwise we recommend the use ofunipolar cables placed at suitabledistance from each other to preventthe capacitive effect of the cable frominterfering with the proper operationof the electronic module.

    LevelLevelLevelLevelLevelControlControlControlControlControlPPPPPanelanelanelanelanel

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Accessory for electric pump control panels, suitable for tank filling or drainage applications or for activation of audible or visual alarms.

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES Drop cable with circular cross section.

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Automatic control through probes. Supply voltage: 1 x 230 V 10% or 1 x 24 V 10%. Frequency: 50/60 Hz. Voltage to probes: 7,5 V AC at 0,4 mA max. Protection class: IP55. Ambient temperature: -5 to +40 C (according to EN 60439-1). Maximum relative humidity: 50% at +40C, provided that no condensation occurs (according to EN 60439-1). Wall mounted. Plastic enclosure. Electrodes suitable for water at a maximum temperature of 60C. Set of three electrodes included in the supply.

    TABELLA CAVI

    CABLE SECTION

    mm2

    0 50 0,5

    50 100 0,75

    100 200 1,0

    200 400 2,5

    CB-CASEL-en_b_te

    LENGHT

    m

    SERIE QCL10

    TYPE DIMENSIONS WEIGHT

    MAIN SECONDARY CLASS A x B x C

    V V V A mm Kg

    QCL10/24 1x230 50/60 Hz 1x 24 50/60 Hz

    QCL10/230 1x230 50/60 Hz -

    CB-QCL10-en_a_te

    POWER SUPPLY CONTACTOR

    1

    RANGE

    170 x 170 x 130AC3 230 9

    ATTENZIONE !

    TOGLIERE TENSIONE PRIMA DI APRIRE

    DISCONNECT THE POWER BEFORE OPENING

    VOR DEM OFFNEN NETZSTECKER ABSCHALTEN

    DEBRANCHER LA LIGNE

    AVANT OUVRIR LE COFFRET

    DANGER!

    ACHTUNG GEFAHR!

    DANGER!

    DESCONETAR TENSION ANTES DE ABRIR

    ATENCION!

    A

    B

    C

  • 34

    For connection of the electrodes to thepanel we recommend the followingcross sections:

    Three-pole cables can be used for shortlenghts.Otherwise we recommend the use ofunipolar cables placed at suitabledistance from each other to preventthe capacitive effect of the cable frominterfering with the proper operationof the electronic module.

    KitKitKitKitKit24 V Level24 V Level24 V Level24 V Level24 V LevelProbeProbeProbeProbeProbe

    KSL SeriesKSL SeriesKSL SeriesKSL SeriesKSL Series

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Accessory for Lowara electric panels.

    SERIE SLD

    TYPE DIMENSIONS WEIGHT PANELS

    MAIN POWER TYPE A x B x C

    V VA V~ A mm Kg

    KIT KSL/24 1x24 50/60 Hz 3,5 N0-C-NC 250 8 90 x 36 x 60 0,5QSCS-QM-QTD-Q3D-Q3Y-

    Q3A-Q3I-Q3SF

    CB-SLD-en_b_te

    POWER SUPPLY CONTACT

    RANGE

    OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES Drop cable with circular cross section.

    TABELLA CAVI

    CABLE SECTION

    mm2

    0 50 0,5

    50 100 0,75

    100 200 1,0

    200 400 2,5

    CB-CASEL-en_b_te

    LENGHT

    m

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Electronic module for use of probes as protection against dry running. Supply voltage: 1 x 24 V 10%. Frequency: 50/60 Hz. Absorbed power: 3,5 VA max. Voltage to probes: 7,5 V AC at 0,4 mA max. Switch contact 24 V AC at 5 A max (250 W max). Designed for installation on Lowara electric panels featuring DIN bar. Electrodes suitable for water at a maximum temperature of 60C.

    CONSTRUCTIONCONSTRUCTIONCONSTRUCTIONCONSTRUCTIONCONSTRUCTIONCHARACTERISTICCHARACTERISTICCHARACTERISTICCHARACTERISTICCHARACTERISTICSSSSS Module made of plastic material with DIN bar attachment. Cables with quick plug-in connectors. Set of three electrodes included in the supply. Electrodes with nylon 6 body, stainless steel sensitive element brass washer and nitrile rubber seal.

  • 35

    LightningLightningLightningLightningLightningProtectionProtectionProtectionProtectionProtection

    DPF SeriesDPF SeriesDPF SeriesDPF SeriesDPF Series

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Accessory for Lowara electric panels.

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS Varistor for overvoltage protection of single-phase lines. Operating voltage: 460 V AC. Maximum varistor voltage: 750 V with 100 A peak current. To be connected between the phase and neutral conductor by the user (installer).

    SERIE VR

    TYPE VOLTAGE PANELS

    V

    DPF 1 x 220-240 50/60 Hz QSM - QSC - QSCS - QPC

    CB-VR-en_e_te

  • 36

    ElectronicElectronicElectronicElectronicElectronicboardboardboardboardboard

    KIT RILS20KIT RILS20KIT RILS20KIT RILS20KIT RILS20SeriesSeriesSeriesSeriesSeries

    APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS Accessory for Lowara electric panels. (QYR, QDRM2, QDRMC2, QXR20, QDR2, QYR2).

    SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS 12 Vdc power input from motherboard. Six low profile 12 Vdc relays with 1A 230 Vac exchange contact. Indicator LEDs available for each relay. Available signals: power-on, manual/automatic mode, pump 1 running, pump 2 running, thermal overload, level alarm. Assembly: with board guides as well as 4 holes for flat-mounting on uprights. Customer-side output connections: removable clamp. Maximum dimensions: A=112 mm, B=80 mm, C=22 mm.

    PRODUCTPRODUCTPRODUCTPRODUCTPRODUCTFEAFEAFEAFEAFEATURESTURESTURESTURESTURESComplete electronic board providing cleansystem status contacts. Can be connected,via an 8-way serial cable with sealed plug,to boards SM20C, SDR20B (1000 mm longcable supplied). 1500 mm long cableavailable on request.

    A

    B

    C

  • 37

  • 38

  • Xylem Water Solutions Italia Srl reserves the right to make modi cation without prior notice.Lowara, Xylem are trademarks of Xylem Inc. or one of its subsidiaries 2013 Xylem, Inc.

    Legal head of ceXylem Water Solutions Italia Srl

    Via Gioacchino Rossini 1/A20020 Lainate (MI) - ItalyTel. (+39) 02 90358.1Fax (+39) 02 9019990www.xylemwatersolutions.com

    For information and technical support Xylem Service Italia Srl

    Via Dottor Vittorio Lombardi 1436075 - Montecchio Maggiore (VI) - ItalyTel. (+39) 0444 707111Fax (+39) 0444 491043www.lowara.com

    1) The tissue in plants that brings water upward from the roots; 2) a leading global water technology company.

    Were approximately 12,900 people uni ed in a common purpose: creating innovative solutions to meet our worlds water needs. Developing new technologies that will improve the way water is used, conserved, and re-used in the future is central to our work. We move, treat, analyze, and return water to the environment, and we help people use water ef ciently, in their homes, buildings, factories and farms. In more than 150 countries, we have strong, long-standing relationships with customers who know us for our powerful combination of leading product brands and applications expertise, backed by a legacy of innovation.

    For more information on how Xylem can help you, go to xyleminc.com.

    Xylem |zl m|e