    4 Cooling Load Calculation

    4.1 Space Heat Gain and Space Cooling Load

    Space heat gain is the rate at which heat enters a space, or heat generated within a spaceduring a time interval.

    Space cooling load is the rate at which heat is removed from the conditioned space to maintaina constant space air temperature.

    Figure 3 shows the difference between the space heat gain and the space cooling load. The

    difference between the space heat gain and the space cooling load is due to the storage of aportion of radiant heat in the structure. The convective component is converted to spacecooling load instantaneously.

    ???

    Figure 3 Differences between Space Heat Gain and Space Cooling Load

  • 8/6/2019 Cooling Load Calculi Ti On

    2/28

    1 Thermal Control

    The thermal system of a building is described in Figure 1. The main heat flow quantities arelisted as follows:

    Qi = Internal heat gain from electric lights, people, power equipment and appliances.

    Qs = Solar heat gain through fenestration areas and, conduction heat gain through roofs andexternal walls by using the sol-air temperature.

    Qc = Conduction heat gain or heat loss through the enclosing elements, caused by atemperature difference between outside and inside.

    Qv = Ventilation heat gain or heat loss due to natural or mechanical ventilation and infiltration.

    Qm = Mechanical heating or cooling produced by some energy-based installation.

    Qe = Latent heat gain or loss from moisture transfer through permeable building materials.

    (1)

  • 8/6/2019 Cooling Load Calculi Ti On

    3/28

    If Eqn. (1) = 0, a thermal balance exists. If Eqn. (1) > 0, the indoor temperature increases. IfEqn. (1) < 0, the indoor temperature decreases. Except Qm which is quite small, net value ofall heat flow quantities in Eqn. (1) determines the requirement ofSPACE HEATING ANDCOOLING.

    Figure 1 Thermal System of Building Figure 2 Outdoor Dry-bulb and Wet-bulb

  • 8/6/2019 Cooling Load Calculi Ti On

    4/28

    Temperature Curves for A Typically Hot

    2 Design Conditions

  • 8/6/2019 Cooling Load Calculi Ti On

    5/28

    In principle, the heating and cooling loads are calculated to maintain the indoor designconditions when the outdoor weather data do not exceed the design values.

    2.1 Outdoor Design Conditions

    It is not economical to choose either the annual maximum or annual minimum values of theoutdoor weather data in determining the outdoor conditions. The outdoor design data isusually determined according to the statistical analysis of the weather data so that 1 to 5% ofthe total possible operating hours is equalled or exceeded the outdoor design values.

    2.1.1 Summer Design Condition

    The recommended summer design and coincident wet bulb temperature, when chosen asbeing equalled to or exceeded by 2.5% of the total number of hours (i.e. 2928 hours) in June,

    July, August and September, are

    (i) 23 oC dry bulb temperature, and

    (ii) 28 oC wet bulb temperature

    Figure 2 shows the outdoor dry bulb temperature and wet bulb temperature curves for atypically hot summer day in Hong Kong. Usually the maximum temperature of 33 oC occurs at2 p.m. and the minimum temperature of 28 oC occurs just before sunrise. The daily range ofdry bulb temperature is about 5 to 6 oC, and the daily mean dry bulb temperature is 30.5 oC.

  • 8/6/2019 Cooling Load Calculi Ti On

    6/28

  • 8/6/2019 Cooling Load Calculi Ti On

    7/28

    2.1.2 Winter Design Condition

    The recommended winter design and coincident relative humidity, when chosen as beingequalled to or exceeded by 1% or 2.5% of the total number of hours (i.e. 2160 hours) inDecember, January and February, are

    (i) 9 oC dry bulb temperature, and

    (ii) 50% relative humidity

    Minimum temperature occurs at 6 a.m. or 7 a.m. before sunrise and the daily range is about 6to 8 oC during very cold winter days.

    2.2 Indoor Design Conditions

  • 8/6/2019 Cooling Load Calculi Ti On

    8/28

    For most of the comfort air-conditioning systems used in the commercial and public buildings,the recommended indoor temperature and relative humidity are as follows:

    (i) Summer: 23.5 - 25.5 oC dry bulb temperature, 40 - 60 % relative humidity

    (ii) Winter: 21 - 23.5 oC dry bulb temperature, 20 - 30 % relative humidity

  • 8/6/2019 Cooling Load Calculi Ti On

    9/28

    3 Heating Load CalculationThe heat loss is divided into two groups:

    (i) the heat transmission losses through the confining walls, floor, ceiling, glass, or othersurfaces, and

    (ii) the infiltration losses through cracks and openings, or heat required to warm outdoor air

    used for ventilation.

    As a basis for design, the most unfavourable but economical combination of temperature andwind speed is chosen. The wind speed has great effect on high infiltration loss and on outsidesurface resistance in conduction heat transfer.

    Normally, the heating load is estimated for winter design temperature usually occurring atnight, therefore, internal heat gain is neglected except for theaters, assembly halls, industrialplant and commercial buildings. Internal heat gain is the sensible and latent heat emittedwithin an internal space by the occupants, lighting, electric motors, electronic equipment, etc.

    3.1 Heat Transmission Loss

    Heat loss by conduction and convection heat transfer through any surface is given by:

  • 8/6/2019 Cooling Load Calculi Ti On

    10/28

    (2)

    where Q = heat transfer through walls, roof, glass, etc.

    A = surface areas

    U = air-to-air heat transfer coefficient

    Ti = indoor air temperature

    To = outdoor air temperature

    Heat transfer through basement walls and floors to the ground depends on:

    (i) difference between room air temperature and ground temperature/outdoor air temperature,

    (ii) materials of walls and floor of the basement, and

    (iii) conductivity of the surrounding earth.

    These portion of heat transmission is neglected in Hong Kong because of the fact that the

    weather in winter is not so severe and the values are very small in comparison with otherforms of heat transmission.

    3.2 Infiltration and Ventilation Loss

  • 8/6/2019 Cooling Load Calculi Ti On

    11/28

    The heat loss due to infiltration and controlled natural ventilation is divided into sensible andlatent losses.

    3.2.1 Sensible Heat Loss, Qsb

    The energy associated with having to raise the temperature of infiltrating or ventilating air upto indoor air temperature is the sensible heat loss which is estimated by:

    (3)

    where r = air density

    V = volumetric air flow rate

    Cpa = specific heat capacity of air at constant pressure

    Ti = indoor air temperature

    To = outdoor air temperature

    3.2.2 Latent Heat Loss, Qla

  • 8/6/2019 Cooling Load Calculi Ti On

    12/28

    The energy quantity associated with net loss of moisture from the space is latent heat losswhich is given by:

    (4)

    where r = air density

    V = volumetric air flow rate

    wi = humidity ratio of indoor air

    wo = humidity ratio of outdoor air

    hfg = latent heat of evaporation at indoor air temperature

  • 8/6/2019 Cooling Load Calculi Ti On

    13/28

    Cooling Load Calculation

    4.1 Space Heat Gain and Space Cooling Load

    Space heat gain is the rate at which heat enters a space, or heat generated within a spaceduring a time interval.

    Space cooling load is the rate at which heat is removed from the conditioned space to maintaina constant space air temperature.

    Figure 3 shows the difference between the space heat gain and the space cooling load. Thedifference between the space heat gain and the space cooling load is due to the storage of aportion of radiant heat in the structure. The convective component is converted to space

    cooling load instantaneously.

    ???

  • 8/6/2019 Cooling Load Calculi Ti On

    14/28

    Figure 3 Differences between Space Heat Gain and Space Cooling Load

    4.2 Cooling Load Temperature Difference (CLTD) and Cooling Load Factor (CLF)

    Cooling load temperature difference and cooling load factor are used to convert the space sensible heatgain to space sensible cooling load.

    4.2.1 Cooling Load Temperature Difference

    The space sensible cooling load Qrs is calculated as:

    (5)

    where A = area of external wall or roof

    U = overall heat transfer coefficient of the external wall or roof.

    CLTD values are found from tables, as shown in Tables 1 and 2, which are designed for fixed conditions ofoutdoor/indoor temperatures, latitudes, etc. Corrections and adjustments are made if the conditions aredifferent.

  • 8/6/2019 Cooling Load Calculi Ti On

    15/28

    4.2.2 Cooling Load Factor

    The cooling load factor is defined as:

    (6)

    CLF is used to determine solar loads or internal loads. Some CLF values are shown in Table 3.

    Table 1 Cooling Load Temperature Difference for Conduction through Window Glass

    Solar time, hour 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

    CLTD,oC 1 0 -1 -1 -1 -1 -1 0 1 2 4 5 7 7 8 8 7 7 6 4 3 2 2 1

    The values are calculated for an inside temperature (Ti) of 25.5oC and outdoor daily mean temperature (Tom) of 29.4oC.

    Correct CLTD = CLTD + (25.5 - Ti) + (Tom - 29.4)

    Table 2 Cooling Load Temperature Difference (40 degree North Latitude in July) for Roof

    and External Walls (Dark)

  • 8/6/2019 Cooling Load Calculi Ti On

    16/28

    Solar time, hour 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

    Roof 14 12 10 8 7 5 4 4 6 8 11 15 18 22 25 28 29 30 29 27 24 21 19 16

    External wall

    North

    North-east

    East

    South-east

    South

    South-west

    West

    North-west

    8

    9

    11

    11

    11

    15

    17

    14

    7

    8

    10

    10

    10

    14

    15

    12

    7

    7

    8

    9

    8

    12

    13

    11

    6

    6

    7

    7

    7

    10

    12

    9

    5

    5

    6

    6

    6

    9

    10

    8

    4

    5

    5

    5

    5

    8

    9

    7

    3

    4

    5

    5

    4

    6

    7

    6

    3

    4

    5

    5

    4

    5

    6

    5

    3

    6

    7

    5

    3

    5

    5

    4

    3

    8

    10

    7

    3

    4

    5

    4

    4

    10

    13

    10

    4

    4

    5

    4

    4

    11

    15

    12

    5

    5

    5

    4

    5

    12

    17

    14

    7

    5

    6

    5

    6

    13

    18

    16

    9

    7

    6

    6

    6

    13

    18

    17

    11

    9

    8

    7

    7

    13

    18

    18

    13

    12

    10

    8

    8

    14

    18

    18

    15

    15

    12

    10

    9

    14

    18

    18

    16

    18

    17

    12

    10

    14

    17

    17

    16

    20

    10

    15

    11

    13

    17

    17

    16

    21

    11

    17

    11

    13

    16

    16

    15

    21

    12

    18

    10

    12

    15

    15

    14

    20

    11

    17

    10

    11

    13

    14

    13

    19

    11

    16

    9

    10

    12

    12

    12

    17

    19

    15

    The values are calculated for an inside temperature of 25.5oC and outdoor daily mean temperature of 29.4oC.

    Correction values for 22 degree north latitude in July are as follows:

    Roof: +0.4oC

    Wall: N NE E SE S SW W NW

    +1.8oC +1.5oC -0.4oC -2.3oC -3.6oC -2.3oC -0.4oC +1.5oC

    Table 3 Cooling Load Factor for Window Glass with Indoor Shading Devices

    (North Latitude and All Room Construction)

  • 8/6/2019 Cooling Load Calculi Ti On

    17/28

    Solar time,

    hour

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

    Orientation:

    North

    North-east

    East

    South-east

    South

    South-west

    West

    North-west

    Horizontal

    0.08

    0.03

    0.03

    0.03

    0.04

    0.05

    0.05

    0.05

    0.06

    0.07

    0.02

    0.02

    0.03

    0.04

    0.05

    0.05

    0.04

    0.05

    0.06

    0.02

    0.02

    0.02

    0.03

    0.04

    0.04

    0.04

    0.04

    0.06

    0.02

    0.02

    0.02

    0.03

    0.04

    0.04

    0.03

    0.04

    0.07

    0.02

    0.02

    0.02

    0.03

    0.03

    0.03

    0.03

    0.03

    0.73

    0.56

    0.47

    0.30

    0.09

    0.07

    0.06

    0.07

    0.12

    0.66

    0.76

    0.72

    0.57

    0.16

    0.11

    0.09

    0.11

    0.27

    0.65

    0.74

    0.80

    0.74

    0.23

    0.14

    0.11

    0.14

    0.44

    0.73

    0.58

    0.76

    0.81

    0.38

    0.16

    0.13

    0.17

    0.59

    0.80

    0.37

    0.62

    0.79

    0.58

    0.19

    0.15

    0.19

    0.72

    0.86

    0.29

    0.41

    0.68

    0.75

    0.22

    0.16

    0.20

    0.81

    0.89

    0.27

    0.27

    0.49

    0.83

    0.38

    0.17

    0.21

    0.85

    0.89

    0.26

    0.24

    0.33

    0.80

    0.59

    0.31

    0.22

    0.85

    0.86

    0.24

    0.22

    0.28

    0.68

    0.75

    0.53

    0.30

    0.81

    0.82

    0.22

    0.20

    0.25

    0.50

    0.81

    0.72

    0.52

    0.71

    0.75

    0.20

    0.17

    0.22

    0.35

    0.81

    0.82

    0.73

    0.58

    0.78

    0.16

    0.14

    0.18

    0.27

    0.69

    0.81

    0.82

    0.42

    0.91

    0.12

    0.11

    0.13

    0.19

    0.45

    0.61

    0.69

    0.25

    0.24

    0.06

    0.06

    0.08

    0.11

    0.16

    0.16

    0.16

    0.14

    0.18

    0.05

    0.05

    0.07

    0.09

    0.12

    0.12

    0.12

    0.12

    0.15

    0.04

    0.05

    0.06

    0.08

    0.10

    0.10

    0.10

    0.10

    0.13

    0.04

    0.04

    0.05

    0.07

    0.09

    0.08

    0.08

    0.08

    0.11

    0.03

    0.03

    0.04

    0.06

    0.07

    0.07

    0.07

    0.07

    0.10

    0.03

    0.03

    0.04

    0.05

    0.06

    0.06

    0.06

    0.06

    4.3 Space Cooling Loads

    Space cooling load is classified into three categories:

    4.3.1 External Cooling Loads

    External cooling loads have the following components:

  • 8/6/2019 Cooling Load Calculi Ti On

    18/28

    4.3.1.1 Solar Heat Gain through Fenestration Areas, Qfes

    (7)

    where As = unshaded area of window glass

    Ash = shaded area of window glass

    max. SHGFsh = maximum solar heat gain factor for the shaded area on window glass (Table 4)

    max. SHGF = maximum solar heat gain factor for window glass (Table 5)

    SC = shading coefficient (Table 6)

    The corresponding space cooling load Qfs is:

    (8)

    Table 4 Maximum Solar Heat Gain Factor of Shaded Area

    Month Jan. Feb. Mar. Apr. May June July Aug. Sept. Oct. Nov. Dec.

    SHGFsh, W/m2 98 107 114 126 137 142 142 133 117 107 101 95

  • 8/6/2019 Cooling Load Calculi Ti On

    19/28

    Table 5 Maximum Solar Heat Gain Factor for Sunit Glass on Average Cloudness Days

    Month Maximum solar heat gain factor for 22 degree north latitude, W/m2

    North North-east /

    north-west

    East / west South-east /

    south-west-

    South Horizontal

    January.

    February.

    March.

    April

    May

    June

    July

    August

    September

    October

    November

    December

    88

    97

    107

    119

    142

    180

    147

    123

    112

    100

    88

    84

    140

    265

    404

    513

    572

    589

    565

    502

    388

    262

    142

    101

    617

    704

    743

    719

    687

    666

    671

    694

    705

    676

    606

    579

    789

    759

    663

    516

    404

    355

    391

    496

    639

    735

    786

    790

    696

    578

    398

    210

    139

    134

    140

    223

    392

    563

    686

    730

    704

    808

    882

    899

    892

    880

    877

    879

    854

    792

    699

    657

  • 8/6/2019 Cooling Load Calculi Ti On

    20/28

    Table 6 Shading Coefficient for Window Glasses with Indoor Shading Devices

    Windowglass

    Nominal

    thickness,

    mm

    Solartransmission

    Shading coefficient

    Venetian Roller shade, opaque Draperies, light colour

    Medium Light Dark White Openb Closedb

    Clear 3 - 12 0.78 - 0.79 0.64 0.55 0.59 0.25 0.65 0.45

    Heat-absorbing

    5 - 6 0.46 0.57 0.53 0.45 0.30 0.49 0.38

    Heat-absorbing

    10 0.34 0.54 0.52 0.40 0.28

    Reflectivecoated

    SCa=0.30

    SCa=0.40

    SCa=0.50

    SCa=0.60

    0.25

    0.33

    0.42

    0.50

    0.23

    0.29

    0.38

    0.44

    0.23

    0.33

    0.41

    0.49

    0.21

    0.28

    0.34

    0.38

    Insulatingglass:

    Clear out- 6 0.80 0.57 0.51 0.60 0.25 0.56 0.42

  • 8/6/2019 Cooling Load Calculi Ti On

    21/28

    clear in

    SCa=0.84

    Heat

    absorbingout-clearin

    SCa=0.55

    6 0.56 0.39 0.36 0.40 0.22 0.43 0.35

    Reflective

    SCa=0.20

    SCa=0.30

    SCa=0.40

    6

    0.80

    0.19

    0.27

    0.34

    0.18

    0.26

    0.33

    0.18

    0.27

    0.36

    0.16

    0.25

    0.29

    a Shading coefficient with no shading device.

    b Open weave means 40% openness, and closed weave indicate 3% openness.

    Table 7 Overall Heat Transfer Coefficient for Window Glasses

    Window Glass Overall heat transfer coefficient, W/m2K

    Summer (outdoor wind velocity = 3.33m/s) Winter (outdoor wind velocity = 6.67m/s)

    3 mm

    thickness

    5 mm

    thickness

    6 mm

    thickness

    12 mm

    thickness

    3 mm

    thickness

    5 mm

    thickness

    6 mm

    thickness

    12 mm

    thickness

  • 8/6/2019 Cooling Load Calculi Ti On

    22/28

    Single-glazed

    Reflective

    Double-glazed 6mm airspace

    Double glazed 12mm airspace

    5.4

    3.2

    2.8

    5.2

    3.0

    2.7

    5.0

    4.7

    2.9

    2.6

    4.3 6.1

    3.1

    2.7

    5.7

    2.9

    2.6

    5.4

    5.0

    2.8

    2.4

    4.6

    4.3.1.2 Conduction Heat Gain through Fenestration Areas, Qfe

    The space cooling load due to the conduction heat gain through fenestration area is calculated as:

    (9)

    where A = fenestration area

    U = overall heat transfer coefficient for window glass (Table 7)

    CLTD = cooling load temperature difference (Table 1)

    4.3.1.3 Conduction Heat Gain through Roofs (Qrs) and External Walls (Qws)

    The space cooling load due to the conduction heat gain through roofs or external walls is calculated as:

    (10)

  • 8/6/2019 Cooling Load Calculi Ti On

    23/28

    where A = area for external walls or roofs

    U = overall heat transfer coefficient for external walls or roof

    CLTD = cooling load temperature difference (Table 2)

    4.3.1.4 Conduction Heat Gain through Interior Partitions, Ceilings and Floors, Qic

    The space cooling load due to the conduction heat gain through interior partitions, ceilings and floors iscalculated as:

    (11)

    where A = area for interior partitions, ceilings or floors

    U = overall heat transfer coefficient for interior partitions, ceilings or floors

    Tb = average air temperature of the adjacent area

    Ti = indoor air temperature

    4.3.2 Internal Cooling Loads

    4.3.2.1 Electric Lighting

    Space cooling load due to the heat gain from electric lights is often the major component for commercialbuildings having a larger ratio of interior zone. Electric lights contribute to sensible load only. Sensible heatreleased from electric lights is in two forms:

  • 8/6/2019 Cooling Load Calculi Ti On

    24/28

    (i) convective heat from the lamp, tube and fixtures.

    (ii) radiation absorbed by walls, floors, and furniture and convected by the ambient air after a time lag.

    The sensible heat released (Qles) from electric lights is calculated as:

    (12)

    where Input = total light wattage obtained from the ratings of all fixtures installed

    Fuse = use factor defined as the ratio of wattage in use possibly at design condition to the installationcondition

    Fal = special allowance factor for fluorescent fixtures accounting for ballast loss, varying from 1.18 to 1.30

    The corresponding sensible space cooling load (Qls) due to heat released from electrical light is:

    (13)

    CLF is a function of

    (i) number of hours that electric lights are switched on (for 24 hours continuous lighting, CLF = 1), and

    (ii) types of building construction and furnishings.

    Therefore, CLF depends on the magnitude of surface and the space air flow rates.

  • 8/6/2019 Cooling Load Calculi Ti On

    25/28

    4.3.2.2 People

    Human beings release both sensible heat and latent heat to the conditioned space when they stay in it.The space sensible (Qps) and latent (Qpl) cooling loads for people staying in a conditioned space arecalculated as:

    (14)

    (15)

    where n = number of people in the conditioned space

    SHG = sensible heat gain per person (Table 8)

    LHG = latent heat gain per person (Table 8)

    Adjusted values for total heat shown in Table 8 is for normal percentage of men, women and children ofwhich heat released from adult female is 85% of adult male, and that from child is 75%.

    CLF for people is a function of

    (i) the time people spending in the conditioned space, and

    (ii) the time elapsed since first entering.

    CLF is equal to 1 if the space temperature is not maintained constant during the 24-hour period.

    Table 8 Heat Gain from Occupants at Various Activities (At Indoor Air Temperature of 25.5 oC)

  • 8/6/2019 Cooling Load Calculi Ti On

    26/28

    Activity Total heat, W Sensible heat, W Latent heat, W

    Adult, male Adjusted

    Seated at rest

    Seated, very light work, writing

    Seated, eating

    Seated, light work, typing,

    Standing, light work or walking slowly,

    Light bench work

    Light machine work

    Heavy work

    Moderate dancing

    Athletics

    115

    140

    150

    185

    235

    255

    305

    470

    400

    585

    100

    120

    170b

    150

    185

    230

    305

    470

    375

    525

    60

    65

    75

    75

    90

    100

    100

    165

    120

    185

    40

    55

    95

    75

    95

    130

    205

    305

    255

    340

    b Adjusted for latent heat of 17.6W person released from food.

    4.3.2.3 Power Equipment and Appliances

  • 8/6/2019 Cooling Load Calculi Ti On

    27/28

    In estimating a cooling load, heat gain from all heat-producing equipment and appliances must be takeninto account because they may contribute to either sensible or latent loads, and sometimes both. Theestimation is not discussed in this lecture note. For more information, Chapter 26 of ASHARE Handbook -1993 Fundamentals can be referred.

    4.3.3 Loads from Infiltration and Ventilation

    Infiltration load is a space cooling load due to the infiltrated air flowing through cracks and openings andentering into a conditioned room under a pressure difference across the building envelope. Theintroduction of outdoor ventilation air must be considered in combination with the infiltrated air. Table 9shows the summer outdoor design dry bulb and wet bulb temperatures at 22 degree north latitude.

    Infiltration and ventilation loads consist of both sensible and latent cooling loads. Eqns (3) and (4) are validto estimate the sensible and latent cooling loads respectively.

    Table 9 Summer Outdoor Design Dry Bulb And Wet Bulb Temperatures At 22 Degree North Latitude

    Solar time,hour

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

    Dry bulbtemp. oC

    28.4 28.3 28.2 28.1 28.0 28.0 28.2 29.0 29.9 30.8 31.8 32.2 32.8 33.0 32.7 32.5 31.8 31.1 30.4 29.7 29.1 28.8 28.6 28.4

    Wet bulbtemp. oC

    25.8 25.7 25.7 25.6 25.6 25.5 25.7 26.4 26.7 27.0 27.5 27.6 27.8 28.0 27.9 27.6 27.4 27.1 26.8 26.7 26.5 26.3 26.1 25.9

  • 8/6/2019 Cooling Load Calculi Ti On

    28/28