cooling_with_dehumidification.pdf
TRANSCRIPT
-
8/10/2019 Cooling_with_Dehumidification.pdf
1/9
The following article was taken from a larger work on psychrometrics by
Norm Christopherson
COOLING WITH DEHUMIDIFICATION
Cooling is a sensible heat process. Cooling with dehumidification is a
sensible and latent heat combination. Strictly cooling air raises the relative
humidity. This may require that some dehumidification be accomplished toreduce the humidity to comfortable levels. The chart in figure 8-1 shows a
typical process line for cooling with dehumidification.
F ig u r e 8 - 1
-
8/10/2019 Cooling_with_Dehumidification.pdf
2/9
The state point on the right is warmer and lower in relative humidity than
the point on the left. Moving to the left on the chart indicates a reduction in
temperature as well as an increase in relative humidity.
Also notice that the state point on the right is higher on the chart than that
on the left. As this air was cooled it moved to the left but, it also dropped to
a lower specific humidity (grains) line. This indicates that the air was notonly cooled but, some actual grains of moisture were removed. The number
of grains removed per pound of air can be determined by finding thedifference between the number of grains at each state point.
The following example of a typical cooling with dehumidification process
illustrates how the process works.
-
8/10/2019 Cooling_with_Dehumidification.pdf
3/9
COOLING WITH DEHUMIDIFICATION
Fi g u r e 8 - 2
The cooling system in figure 8-2 is cooling and dehumidifying the air
simultaneously. This is the most common air conditioning process. This
system is moving 2000 CFM of air. Dry bulb and wet bulb temperatures aretaken of the supply and return air and found to be as follows:
-
8/10/2019 Cooling_with_Dehumidification.pdf
4/9
RETURN AIR SUPPLY AIR
DB 80 degrees DB 60 degrees
WB 65 degrees WB 55 degrees
The state points for each of these conditions are located on a psychrometricchart. (See figure 8-3) From the chart the following additional conditions
are read and recorded.
%RH about 46% %RH about 73%
Grains about 68.5 gr Grains about 57 gr
Notice as the air was cooled the relative humidity increased. This is due to
the contraction of the air. The moisture is contained in a smaller volume ofair thus the relative humidity is higher.
Also notice that the actual humidity in grains decreased. The cooling coil
removed grains (68.5 - 57) 11.5 grains of moisture removed for each poundof air treated by the coil. The moisture removed attached itself to the coil
and fins, ran down the fins and into the condensate pan where it is drainedoff.
-
8/10/2019 Cooling_with_Dehumidification.pdf
5/9
THE SYSTEM COOLING CAPACITY
Since this system is removing both sensible and latent heat the total heat
formula must be used to determine the operating capacity.
Using the wet bulb temperatures for the supply and return air conditions,look up the matching enthalpy for each on the wet bulb to enthalpy
conversion chart found on page xxx. The enthalpy values from the chart arefound to be as follows:
RETURN AIR SUPPLY AIR
WB 65 = an enthalpy of 30.06 btu\lb WB 55 = an enthalpy of 23.22 btu\lb
Find the difference in enthalpy by subtracting. 30.06 - 23.22 = 6.84 btu\lb
Now we know that 6.84 btu of heat was removed from each pound of air
that passed over the evaporator coil. Some of this heat was sensible heatbecause the air was cooled, and some was latent heat because grains of
moisture were removed. Now the total cooling capacity of the coil can bedetermined.
-
8/10/2019 Cooling_with_Dehumidification.pdf
6/9
The Total Heat Formula
-
8/10/2019 Cooling_with_Dehumidification.pdf
7/9
APPARATUS DEW POINT OR EFFECTIVE COIL TEMPERATURE
The ADP (apparatus dew point) or ETC (effective coil temperature) is the
temperature of the evaporator coil for this system operating under theseconditions. The temperature is determined by drawing a straight line
between the two state points and extending this line to the saturation
(100%) line on the chart as in figure 8-4.
The coil temp, apparatus dew point or effective coil temperature is read atthe saturation curve.
F ig u r e 8 - 4
You should be able to read this temperature as somewhere between 47 and48 degrees on a psychrometric chart. A very careful evaluation will show
the reading to be 47.5 degrees. The coil temperature is useful in
determining the coil bypass factor.
-
8/10/2019 Cooling_with_Dehumidification.pdf
8/9
COIL BYPASS FACTOR
The bypass factor is the percentage of air passing over the coil that is not
affected by the coil. This is air that passes between the coil tubes and finswithout making physical contact thus is untreated by the evaporator.
The leaving air dry bulb (LA DB) is the dry bulb temperature of the air
leaving the coil. This is the supply air dry bulb of 60 degrees. The enteringair dry bulb temperature is the dry bulb temperature of the air entering the
coil. This is the return air dry bulb temperature of 80 degrees. The ECT isthe temperature of 47.5 degrees.
-
8/10/2019 Cooling_with_Dehumidification.pdf
9/9