copper cable trouble shooting session test equipment demo

65
Copper Cable Trouble Shooting Session & Test Equipment Demo

Upload: others

Post on 14-Jul-2022

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Copper Cable Trouble Shooting Session Test Equipment Demo

Copper Cable Trouble Shooting Session&

Test Equipment Demo

Page 2: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 2

Agenda

Outside Plant/Local Loop Issues for ADSL Deployment

Introduction to Access Technologies & Video Delivery

Home Wiring Physical Layer Issues

Test Set Demonstration

Page 3: Copper Cable Trouble Shooting Session Test Equipment Demo

Outside Plant / Local Loop Issuesfor

ADSL Deployment

Ray LanierOf

Concord Communications Associates, Inc.([email protected])

Office: 603-228-8627 Ext. 14Cell: 603-387-9300

Page 4: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 4

Cross Box DP(Pedestal)

Cross Box SpliceCase

RT

DLC Pair Gain Device

MDF

Typical POTS/ADSL Local Loop

RJ-11 JackSplitter/Filter

F1(Feeder)

F2(Distribution)

F3(Drop)

Exchange(CO)

COT

/HDSL/Fiber1/E1T

ToCOSWITCH

RJ-11 JackSplitter/Filter

DSLAM

Splitter

EthernetSwitch

T1

Internal Splitter

POTS

ADSL

ToATM&ISP

POTS+ADSL

Presenter
Presentation Notes
There are typically two ways to deploy ADSL. The traditional way is to Place the DSLAM (Digital Subscriber Line Access Multiplexer ) in the CO and using a splitter combined the POTS (Plane Old Telephone Service) and ADSL service on to a single twisted pair. An alternate method is to use a DLC (Digital Loop Carrier) that integrates the POTS and ADSL service over a common facility and delivers both services at RT (Remote Terminal) thereby bring both services closer to the customer.
Page 5: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 5

ADSL - The “Last-mile” BridgeUsing a Micro Filter

CopperTwisted Pair

PSTN

Exchange Local Loop CPE

Note: All connections are bi-directional

ATU-R

IPNetwork

DSLAMATU-C’s

Ethernet/USB

NIC

DEMARK

EndOfficeSwitch

IPRouter

DS3Or

OC-XOr

GigE

POTSSplitter/

CombinerNID

MDF

Micro Filter

Presenter
Presentation Notes
ADSL Rate is decreased the longer the loop. ADSL Internet service is a layered service of IP over ATM and ATM over ADSL on the local loop ADSL service is aggregated at the DSLAM and customers share bandwidth on the ATM backbone of the DSLAM The DSLAM on its line side contains the ADSL modem (ATU-C) and on its network side a wideband ATM signal that is carried over T1/E1, multiple T1s/E1s, DS3/E3, SONET/SDH transport signals. Depending on the size of the ADSL concentration the user to network bandwidth ratio can very from 5:1 to 20:1 with 10:1 as a typical value. A Splitter is used at the CO to Both Combine the out going POTS and ADSL signals on the Local Loop and split the incoming POTS and ADSL signals from the customer to their respective network elements, The Micro Filters isolate the ADSL signal from interfering with the POTS and isolate the telephone sets from the ADSL Modem (ATU-R). Micro Filters do not completely isolate the POTS signal from the ADSL modem and relies on the Modem’s filter to perform the isolation. The Customer’s ADSL modem is connected to the customer’s computer via either Ethernet or USB (Universal Serial Buss). If Ethernet is used as the interface the customer’s computer could have this connection on a NIC (Network Interface Card).
Page 6: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 6

ADSL - The “Last-mile” BridgeUsing a Splitter

CopperTwisted Pair

PSTN

Exchange Local Loop CPE

Note: All connections are bi-directional

ATU-R

IPNetwork

DSLAMATU-C’s

Ethernet/USB

NIC

DEMARK

EndOfficeSwitch

IPRouter

DS3Or

OC-XOr

GigE

POTSSplitter/

Combiner

NID&

POTSSplitter

MDF

Presenter
Presentation Notes
A Splitter can isolate both the telephones and POTS from the ADSL modem and signal much better than Micro Filters. Also with a splitter the inside wiring configuration of the telephones isn’t of concern as it is with Micro Filters. The splitter at the customer’s location acts in the same ways as the splitter at the CO both combining and splitting the POTS and ADSL signals.
Page 7: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 7

ADSL - The “Last-mile” Bridge

OC-X or GigEFiber

OrT1/HDSLCopper

Twisted Pair

PSTN

Exchange Feeder Cable Local Loop CPE

NID/POTSSplitter

Note: All connections are bi-directional

IPNetwork

EthernetOr

USBNIC

DEMARK

EndOfficeSwitch

TR8or

GR303

IPRouter

InternalPOTS

Splitter

ATU-C’s

POTS+DSLAM

DS3Or

OC-XOr

GigE

DLCCOT

DLCRT

MDFOr

LDF

RTMDF

OrLDF

Presenter
Presentation Notes
Using a DLC to Deploy ADSL allows Both the POTS and ADSL service to be derived over much shorter Local Loops than if deployed from the serving CO. When POTS and ADSL are intergraded using a DLC the RT line card includes and combines the three elements required to deliver the service, POTS circuitry, ADSL ATU-C modem and Splitter. POTS at the CO can be interfaced to the DLC COT (CO Terminal) using various standard based interfaces such as Analog ( Telcordia TR-57) or Digital (ITU V5.1 or V5.2, Telcordia GR303 or TR08).
Page 8: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 8

Technology: ADSL

Asymmetrical up and down stream locations

Sign

al (d

B)

Voice Data Up Data Down

Frequency (Hz)

Presenter
Presentation Notes
Data Up Maximum rate of 640 Kbps Twisted pairs exhibit better immunity to cross-talk at lower frequencies, the up stream being n the lower end of frequency spectrum reduces cross-talk at CO were the highest concentration of ADSL signals occur. Data Down Maximum rate of 6.4 Mbps for standard ADSL Maximum rate of 1.5 Mbps for G.lite Rate affected by cable length: Longer cable length means lower rate Approximately 256 Kbps Down and 100 Kbps Up at the maximum Local Loop lengths and expected noise levels. Cross talk is less of an issue as there is less ADSL signal concentration in the distribution cable plant were the down stream ADSL signal is weakest and being received by the modems at the customer's locations.
Page 9: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 9

DMT: Discrete Multi-ToneUp to 256 sub carriers. Each one is controlled by the ADSL protocol.

Voice Freq

1.1MHzTone#256

240kHzTone#56

160kHzTone#31

≈ 4kHz

4.3125kHz Spacing

20kHzTone

#1

“bit buckets” (DMT sub-carriers or “tones”)

DownstreamUpstream

4.3125kHz Spacing

69kHzPilot Tone

276kHzPilot Tone

Presenter
Presentation Notes
DMT Operation 256 carriers carry a maximum of 15 bits each for customer user. There are other bits added as overhead that are used by the DSLAM and customer’s modem. There can be a maximum of 200 carriers for the Downstream There can be a maximum of 25 carries for the Upstream If a data rate is provisioned that is less than what the local loop can handle the bits are evenly distributed amongst the available “bit buckets” rather than butting the maximum bits in fewer “buckets” Each Tone/Carrier is like an individual analog modem. The Pilot tones are the signals that start the synchronization process. Standard HDSL (2B1Q coded) can cause ADSL to be non operational by interfering with the Downstream Pilot Interfering signals can make some carries unusable but still allow service to be operational at a lower data rate ADSL signals within the same Binder group should be limited to 50% of the pairs As more ADSL customers are added a point can be reached where service is derogated for all users in the same binder group
Page 10: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 10

1100

ADSL

Downstream0 4 40

Tone Spacing = 4.3125 KHz

POTS

Unused Due to Line Conditions

Upstream

DMT: Discrete Multi-Tone

Actual Bits/Tone

Guard Band

Presenter
Presentation Notes
How DMT Works: Not all Tones (Bit Buckets) need to be present in order to enable synchronization between the DSLAM and the Customer’s modem. There only needs to be more available data capacity within the Tones available than that the service is provisioned for. If there is noise and/or interferes on the local loop that remove some tones for service these tones would be skipped over. If the local loop is long where it starts to affect the higher frequency tones (typically over 12 K feet/3.6 km) so that that are not available the lower frequency tones will have more bits per tone to make up the difference.
Page 11: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 11

ADSL Standards

ADSL2+ Vs ADSL2 Vs ADSL

ADSL

&ADSL2

Presenter
Presentation Notes
ADSL2+ Vs. ADSL2 Vs. Standard ADSL: ADSL2 and Standard ADSL has the same number of “bit buckets” ADSL2+ has twice as many down stream buckets allowing up to twice the data rate to be delivered to the customer.
Page 12: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 12

ADSL Standards

ADSL2+ Vs ADSL2– Higher Data Rate

Presenter
Presentation Notes
ADSL2+ Vs. ADSL2 On short loops (less than 3 kfeet/900 m) ADSL2+ can deliver 25 Mb/s. This would allow up to 5 high quality compress video channels to be delivered to a customer. This would also allow for one compressed HDTV channel to be delivered to a customer
Page 13: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 13

short cable

Frequency

long cable

Frequency Response To Cable Length

Loop gain

Presenter
Presentation Notes
Frequency Response to Cable Length: Twisted Pair telephone cable is highly capacitive and as such causes more signal loss at higher frequencies than at lower frequencies. This is why Load Coils, which combats capacitance, are used for POTS so that the higher frequencies of the human voice can be heard on long loop making the conversation and the talker more recognizable. As a cable becomes longer the loss at the higher frequencies becomes significantly greater making it impossible to use the higher ADSL DMT tones thereby reducing the down stream rate.
Page 14: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 14

DTM BIT Assignment

Loop gain

Frequency

Frequency

Frequency

+

=

Ideal Bits/tone

Actual Bits/Tone

BITS

BITS

BITS

Presenter
Presentation Notes
The affect of cable length: One of the characteristics of twisted pair cable is to attenuate higher frequency signals more than lower frequency signals as the cable gets longer. This is true for a good cable pair without any faults. But a cable with a fault would affect the signal even greater. This results in either the higher tones carrying fewer bits or not being available at all to carry any bits depending on the length of the cable pair. Once beyond 12 k feet/3.6 km the maximum ADSL data rate cannot be delivered.
Page 15: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 15

ADSL Data Rate vs. Loop Length & Noise

Figure 1

Figure 2

Presenter
Presentation Notes
ADSL Data Rate Vs. Loop Length & Noise: Figure 1: Cable length Vs. Down Stream Data Rate. As more noise is added to the cable pairs the data rate at the extreme length of the cable decrease For 24 gage with minimal noise (Blue line) the maximum data rate is approximately 1.8 Mb/s. For 24 gage with a high noise level (Yellow line) the maximum data rate is approximately 200 kb/s Also as more noise is added to the cable pairs the length at which the maximum ADSL data rate (6.4 Mb/s) can be obtained decreases. For 24 gage with minimal noise (Blue line) the maximum cable length that the maximum ADSL data rate can be obtained is 12 k feet/3.6 km. For 24 gage with a high noise level (Yellow line) the maximum cable length that the maximum ADSL data rate can be obtained is 7 k feet/2.1 km. Figure 2: Cable length Vs. Down Stream Data Rate With interferes: With the same noise and cable lengths as in Figure 1 the addition of 12 pairs with ADSL signals is added resulting in crosstalk (more noise) The maximum rate at the extreme length of the cable is further reduced The cable length at which the maximum ADSL rate can be obtained is also further reduced.
Page 16: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 16

Customer Premises Issues

No Flat (C-Wire) Drop Wire No Carbon Block protectors

– Solid State protectors preferred A good Station Ground must be present

– Insures proper protector operation– Reduces Power influence & ingress noise.

Verify Electrical outlets are correctly wired– Use Standard Hardware store outlet checker– If outlet isn’t OK recommend they get rewired

before service is installed. Verify that Phone service is still operational

Presenter
Presentation Notes
Customer Premises Issues: Flat drop wire having no twist on the Tip-Ring pair and in some cases no shield have very little immunity to ingress noise and does not maintain the same cable characteristics at high frequencies a does standard telephone cable pairs. Carbon Block protectors offer poor impedance characteristics to high frequencies that can degrade ADSL performance. Gas tube or solid state protectors must be used with solid state preferred as they offer much more protection. This applies to both CO and CPE protectors. Station Ground should be verified when installing ADSL as a good station ground will enhance ADSL performance by allowing a good return path for noise. Phone Service should be verified after ADSL installation to make sure the Micro-filters or splitters are operating properly.
Page 17: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 17

Frequency

Frequency

Frequency

WidebandX-talk

(ADSL)

AM RadioOr

T1/HDSLInterference

DMT- Dynamic Adaptation to Line Conditions

+

=

BridgeTap

Ideal Bits/tone Loop gain

Actual Bits/Tone

CableAttenuation

Presenter
Presentation Notes
Dynamic Adaptation: It would be ideal if all “Bit Buckets” would be received so that they would be able to carry the maximum 15 bits of data bits but various line conditions reduce the maximum data bits to be carried. Conditions that reduce the maximum data rate on a given local loop. Long Loop Length: reduces the higher frequency bit buckets ability to carry the Maximum number of data bits. Short bridge taps that are less than 1000 feet/300 m that are within 500 feet/150 m of the customer’s modem “notch out” bit buckets. AM radio that are less than 1100 kHz, T1 and HDSL interferes can also notch bit buckets Wideband noise the worst being other ADSL signals within the same binder group can affect all bit buckets The result is the the data rate is reduced but in most cases the ADSL service can still operate as the modem will adapt to these line conditions.
Page 18: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 18

General Loop Issues

Maximum loop length– 18,000 ft over 24 gage– 14,000 ft over 26 gage

Remove Line Build-Out Capacitors

1300 Ohms maximum Tip to Ring Loop resistance

Presenter
Presentation Notes
General Loop Issues: Maximum loop length is dependent on cable gage Mix gage can reduce ADSL operational loop length Build out capacitors which typically deployed to make short POTS loop look longer to reduce signal levels must be removed as they can make ADSL inoperable. Load coils as a block to any signal above 4 kHz and therefore will block a ADSL signal Loops over 1300 ohms are electrically to long to support ADSL
Page 19: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 19

Loop ResistanceLoop Resistance Versus Wire Gage

0

200

400

600

800

1000

1200

1400

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

Loop Lenght (k feet)

Loop

Res

ista

nce

(Ohm

s)

26 Gage 24 Gage 22 Gage 19 Gage 1300 Ohms

Page 20: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 20

DMT Loop Hazards - Bridge Taps

Bridge Taps

Loopgain

Frequency

CustomerNetwork

Presenter
Presentation Notes
Bridge Taps A bridge tap affects a ATU-C or ATU-R the closer it is to it Maximum allowable length of all bridge taps on a loop is 2,500 feet Maximum length of a singe bridge tap is 2,000 feet Maximum number of bridge taps allowed on a loop is 3 Bridge taps as short as 225 feet can affect ADSL performance The closer a Bridge tap is to a ADSL receiver the more it can interfere with the signal whether located near the CO or Customer’s location
Page 21: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 21

DMT Loop Hazards - Bridge Taps

No Bridge-Tap longer than 2,000 feet Total length of all Bridge-Taps less than 2,500 feet No more than 3 Bridge-Taps No Bridge-Taps within 500 ft of Customer ADSL Modem Bridge-Taps add to the total length of the Cable Pair

– If pair distance to customer = 10,000 feet/– And Bridge-Tap is = 2,000 feet– Cable distance to the customer is considered to be 12,000 feet

Short Bridge-Taps “notch” out Bit Bucket tones– 200ft to 1,000 feet of Bridge-Tap affect down stream ADSL– 1,500 ft to >2,000 feet of Bridge-Tap affect upstream ADSL

Page 22: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 22

DWT Loop Hazards - Split & Resplit Pairs

Causes Imbalance on 2 pairs&

High level of CrosstalkBoth pairs are unusable for ADSL

SPLIT SPLIT“CORRECTION”

Presenter
Presentation Notes
Splits Causes pairs to be unbalanced and enable interfering noise and signals to impair ADSL data rate With a split two pairs are affected. A corrected split doesn’t correct the affect of the split All splits must be removed
Page 23: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 23

DMT Loop Hazards - Gage Changes

Mixed Wire Gauges

DMT No double gage change e.g., 26 AWG to 22 AWG not allowed Every gage change results in an additional 1 dB loss

Presenter
Presentation Notes
Gage Changes No double gage change e.g., 26 AWG to 22 AWG not allowed Every gage change results in an additional 1 dB loss Going from a fine gage (26 gauge) to a coarse gage (24 gauge) and than back to a fine gage (26gauge) is not recommended as additional loss of up to 3 dB can occur.
Page 24: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 24

DMT Loop Hazards - Weather

Wet Cable SectionsCauses drastic impedance changes resulting in signal reflections

Causes insulation breakdown resulting in poor balance & foreign battery

Presenter
Presentation Notes
Wet Cable sections Causes drastic impedance changes resulting in signal reflections The impedance will change dynamically as a cable gets wetter or begins to dry out. Causes insulation breakdown resulting in poor balance & foreign battery This results in an increase in noise on the cable pairs. The ADSL signal will dynamically adjust but the service will degrade significantly as more and more moisture enters the cable. Foreign battery is cause the other shield to deteriorate further removing the cables ability to isolate the pairs from external noise sources.
Page 25: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 25

DMT Loop Hazards - Cross Talk

Pairs in Same Binder Group (Cable Bundle) Other digital signals affect DTM performance

BRI ISDN, HDSL, E1 Carrier DMT ADSL signal in same Binder Group

Limit the number of ADSL customer within a binder group

Presenter
Presentation Notes
Cross Talk !n a 25 pair binder group a general rule is to not allow over 50% fill of like signal interferes A telephone cable’s twisted pair has less immunity to crosstalk at higher frequencies than at lower frequencies. Treat 2B1Q HDSL as a equal interferer to ADSL A 2B1Q HDSL Doublers can cause ADSL signals in the same binder group to be inoperable 2B1Q HDSL originating at a DLC and entering a binder group with ADSL originating from another location can cause the ADSL signal to be inoperable 2B1Q HDSL can affect both the up and down stream ADSL signals. BRI ISDN only can cause interference in the up stream ADSL signal, whereas T1 and E1 affect the down stream ADSL signal.
Page 26: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 26

DMT Loop Hazards - Bonding & Grounding

Improper Bonding & Grounding results in ingress interferesAC power influence

Increases foreign voltage and hazards to personnel & EquipmentLightning storm influence

Damage to Network & CP equipmentSpurious noise

Reduces ADSL rate & can cause modem resynchronise

X

Presenter
Presentation Notes
Bonding & Grounding: First and foremost Bonding and Grounding is for protection of those who work on cable pairs and the customer against high voltages and current that can be on a telephone line from either electrical storms or from a cross power line that comes in contact with the telephone cable. Good bonding and grounding allows for any external noise source induction to be removes from interfering with the twisted pair that carry the telephone and ADSL signal. Bonding and grounding is the first line of defense to block external noise from entering the cable pairs such as power line influence, AM radio signals and lightning induction.
Page 27: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 27

Clearing the Way for ADSL

Loop Testing

Presenter
Presentation Notes
This section is on basic copper measurements and how to use them to more effectively troubleshoot ADSL on the local loop. The intended results is a better understanding of: AC and DC current loadcoils Resistance Capacitance and opens Balance and “stress” Noise Resulting in helping better troubleshoot the most common causes of trouble for ADSL: loadcoils, bridged taps, and bad balance.
Page 28: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 28

POTS Local Loop Requirements

Span Voltage (Vdc)

Ringing Voltage (Vac)– Older switches >85 Vac– Newer switches >105 Vac– Minimum @ CP Demark 79 Vac

Presenter
Presentation Notes
POTS local loop requirements: Span Voltage: Tip-to-Ring (T-R) voltage when measured without a termination at the customer’s location should measure at 52 volts. Tip-to-Ground (T-G) voltage should read less than 5 volts. Since the Tip is at the same potential as ground at the CO there shouldn’t be any difference except for foreign induced voltage. Ring-to-Tip (R-T) voltage when measured without a termination at the customer’s location should measure at -52 volts. Ringing Voltage: Measured at the customer’s location the ringing voltage (20 Hz) should not be less than 79 volts in order to be able to ring 5 standard ringer equivalent telephone station sets.
Page 29: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 29

POTS Local Loop Requirements

Loop Capacitance– Loop Capacitance is the Sum of

• Tip to Ring• Tip to Shield• Ring to Shield• Tip to all surrounding conductors• Ring to all surrounding conductors

– Capacitance Balance• Tip-Shield and Ring-Shield capacitance balance >98%

Ring to Shield

Tip to Shield

Tip to Ring

conductors insulation

A twisted pair hasCapacitance becauseit has 2 conductorsseparated by insulation

Presenter
Presentation Notes
POTS local loop requirements: Loop Capacitance All twisted pair telephone cable is primarily capacitive and resistive in nature having very little inductance. The capacitance of a cable is the primary cause of AC signal lost. The resistance of a cable is the cause for DC current lost. Capacitance Balance: When measuring T-G and R-G capacitance there shouldn’t be a difference between the measurements of more than 2%. If there is a difference grater than 2% there is either a left in tip or ring lead or water in the cable.
Page 30: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 30

Capacitance

22 AWG

26 AWG

.083 µF/mile

Insulation thickness varies,

µF/mi CONSTANT

shield

T-G, R-G

fill types:Pulp, Aircore, Jelly

T – G(Shield)

T – R

µF/mi varies

Presenter
Presentation Notes
While we can use an opens or “kick” meter to convert capacitance to distance because the capacitance is CONSTANT between T – R, This is NOT TRUE between any other leads: the game really changes! If you do not set the meter or calculate with the right value per mile, an open meter will be WAY OFF. A meter still measures the capacitance, whether between T – Shield (ground), T1 – T2, or otherwise, it cannot give you an accurate distance without knowing the microfarads per mile, which must be pretty close to constant over the length of the pair. But cable is sometimes of mixed gage: Feeder, distribution and drop can vary. AND, the fill type (the insulation in this case) also varies for T-G and R-G measurements such as air core, pulp, jelly. So the value for capacitance can be way off in this environment. It’s critical to know the gage and fill type for most of the cable to get an accurate distance reading on one side to ground. You must enter the gage and fill type on your meter, if you know it in order to get the most accurate measurement. If you’re not sure, verify an open measurement with a TDR (Time Domain Refectometer) The TDR is good at measuring the distance to the end of the pair (an open). At least back up your estimates with the TDR when calculating distance on one side.
Page 31: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 31

Capacitance Balance Tip to Ground C = Ring to Ground C +/-2% If Capacitance Balance not meet pair is

susceptible to ingress noise

shield

R – G(Shield)

R – G(Shield)

Presenter
Presentation Notes
Capacitance Balance: This is the comparison measurement of capacitance between T-G and R-G and should be 2% or less in value. Typically if Capacitance balance isn’t met a poor Longitudinal Balance measurement will also be made.
Page 32: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 32

POTS Local Loop Requirements

Loop Insulation Resistance– Tip to Ground = Ring to Ground

• If not equal pair is unbalanced• If > 4,000 ohms and < 3.5 M ohms a high resistance fault is present

• 3.5 Meg Ohms limit is based on Mechanical Meter movement– e.g., Brown Meter, Kick Meter, KS test set

• Newer “Electronic” meters will typically give a higher resistance value than a Mechanical meter

Presenter
Presentation Notes
POTS local loop requirements: In order have good telephone performance the insulation around the copper conductors of the tip and ring must have a minimum of resistance between all conductors. However, the greater the resistance the better the cable will perform especially when high frequency signals are on the cable such as ADSL. The traditional minimal insulation resistance value has been 3.5 Meg ohms based on the “Kick” meter (sometimes referred as a “Brown” meter or “KS” meter) but this meter has a relatively low ohms per volt sensitivity as compared to newer “digital” meters. As a result newer meters may read different resistance values than a “Kick” meter. All insulation measurements (T-R, T-G and R-G) should be relatively equal
Page 33: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 33

Resistive Balance

Tip Resistance = Ring Resistance If Resistance Balance not meet pair is

susceptible to ingress noise Tip – Ground ohms = Ring – Ground ohms T – G Vs R – G difference < 3%

High Resistance Splice

Presenter
Presentation Notes
Resistive Balance: Risistive imbalance is caused when the tip or the ring have a greater resistance than its mating ring or tip. This is sometimes referred as High Resistance Open or a “HiRO” which is a high resistive serial fault. The typical causes of resistive imbalance is either a poor made connection (joint) or corrosion caused by moisture entering a connection (joint). Other locations where this type of fault occurs is a screw down terminals and telephone station set jacks that are corroded. The resultant affect of resistive imbalance is poor a Longitudinal Balance measurement causing noise to be heard on a POTS connection. For ADSL connection the result is intermittent connections and poor ADSL modem speeds. The best tool to find a high resistive serial fault is a TDR. However, because of the relatives resistance low resistance of the fault it is usually required to do the testing as close to the fault as possible.
Page 34: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 34

POTS Local Loop Requirements

Loop Current– Required to maintain proper Signal Volume & Touch Tone

level

– For Station Ground <25 ohms • Ring to Gnd current needs to be at least 1.33 times grater than Tip

to Ring loop current

Presenter
Presentation Notes
Loop Current: At the customer location’s drop termination the tip to ring loop current needs to be equal to or greater than 23 ma when terminated into 430 ohms. When making a Ring to Ground current measurement the current should be equal to 46 ma. The reason the required current is more than the tip to ring loop current is the ground resistance to the CO is required to be 25 ohms or less this is much less than the “tip ground resistance” that can be as high as 950 ohms.
Page 35: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 35

POTS Local Loop Requirements

Tone Level– Nominal 1004 Hz loss

– Gain Slop

MinLevel

MaxLevel

Frequency

0 DB0 dB1004 HzReference

-2 dB5 dB404 Hz

-9.5 dB1.5 dB2804 Hz

Presenter
Presentation Notes
Tone Levels: The maximum allowable loss on a local loop must be no greater than 8 dB at 1004 Hz. Gain Slop is a measurement of low (404 Hz) and high (2804 Hz) frequencies as compared to 1004 Hz. If these frequency levels are out of the specified range than either there is a fault within the POTS connection or the loop is to long.
Page 36: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 36

POTS Local Loop Requirements

Balance– A pairs ability to reject power line influence– Balance = PI – (Metallic Noise)

– For DSL lines Balance MUST be > 60dBrnC

P.I., Noise & Balance Limits

Presenter
Presentation Notes
POTS Local Loop Requirements: When noise metallic (tip-to-ring) is marginal or unacceptable and power influence (tip-to-ground & ring-to-ground) is acceptable Suspect a pair problem The pair is unbalanced either resistively (going open) or capacitively (one side open on a lateral (bridge-tap) beyond the working terminal, or crossed with a nonworking pair) In most cases a capacitive unbalance pair can be identified and isolated with an open meter. When both noise metallic and power influence are marginal ar unacceptable, suspect a grounding, bonding, or associated power company problem. Some typical power company problems can be an open capacitor bank, bad transformer, open neutral, etc.
Page 37: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 37

Power Influence

AC volts tests:look for hazardous levelscheck ambient AC levels

3 factors effecting PI:1. Distance to source2. Strength of field3. Distance pairs to parallel power

Presenter
Presentation Notes
When most technicians troubleshoot a loop, they first measure AC volts: to check for hazardous voltages (note too the shield can have them) (We know that at 60Hz, only a small amperage can kill a person) To check for ambient, or stray AC voltages (Power Influence and possible hi-voltage crosses) Normally a few volts of AC is allowed: 3 to 10 (above 10 is unacceptable) The major source of ambient voltages comes from Power Influence This power influence creates noise This happens because (recall high school electricity experiments): we have a moving electromagnetic field (the “alternating” current in the power lines) A stationary conductor in this moving field= induced current on the conductor (like an electromagnet). Also like when conductors rotate inside magnets (on the front of everyone’s engine block in their car, the alternator). 3 factors determine how much current is induced: distance from the conductor to the source, the strength of the field, and most important, how far the lines parallel!
Page 38: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 38

Power Influence

T

R

MutualTermination

“LOUD”

PI

PI

“Quiet”

Presenter
Presentation Notes
Let’s represent this induced current on a pair with arrows (this is in a perfect world, though I realize a few of your phone lines are a little less than perfect). Both conductors are influenced equally by the PI, so an equal current is induced. If we were to connect a butt set from R –G, we would hear a “roar” or a “hum”: this is the PI passing through to ground. But if we clip our buttset across T & R (mutual), we don’t hear the “hum”. the equal PI on T & R block each other and we do not hear it (and neither does the customer, a good thing). But what happens if one side, and not the other, has a ground?
Page 39: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 39

Power Influence

T

R

MutualTermination

PI

PI

Noise

Smaller PI on RING does not stop all of the PI on TIP

Presenter
Presentation Notes
The ground give some of the PI a path other than R, so not all of the induced current flows to the meter/telephone. � PI on one side is larger, and is not completely blocked by the PI of the other lead The excess PI crosses the termination as noise (your customer hears this if more than 20dB which is bad) The noise is actually caused by the PI on the good lead, flowing to ground (remember how AC behaves) So it’s important that the leads are the same so they counter noise, and this “sameness” between them is called: BALANCE Q: did the ground on R CAUSE the noise? NO the fault only provided a path for induced AC, which caused the noise Faults are passive, they do not actually cause noise. Lets see now a situation you may have seen where it’s important to understand balance (next slide)
Page 40: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 40

Power Influence

T

R

“Power Influence”measured to ground

PI: 90

PI: 60

Noise 30(mutual)

P.I. 90N 30BAL 60

Presenter
Presentation Notes
Have you ever used a buttset on a pair and heard noise (mutual), but then checked balance and it was OK? (many have) Note that balance is fine in this situation. But yet the noise is too high? (20 is the max noise allowed across T – R, or mutual) Should we fix this pair (don’t answer yet)? Another critical, important lesson: SIDEKICKS READ JUST THE OPPOSITE OF THE DYNATEL AND HST! (memory aid: Little meters use little numbers, large meters use large numbers) If you forget everything else today, REMEMBER THIS.
Page 41: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 41

Noise & Balance

BAL = 75The balance is good

WithArtificial Test Set Induced

Power Influence

PI 90N 15BAL 75

Ever “stress” the line, and it’s OK, but you still hear noise on your butt set?

The balance is goodBut the PI is too High

Presenter
Presentation Notes
In this situation of two pairs: the PI, noise and balance are all fine On the second pair: the PI and noise are too high: IS THIS PAIR BROKEN? SHOULD WE FIX IT? (ask the audience) NO: the pair is NOT broken! The balance is fine, it is doing the job it was designed to do: balance of at least 60! YOU Refer this to the noise specialists or engineers!
Page 42: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 42

ADSL & Noise

T

R

PI: 90

PI: 60

Noise 30(mutual)

This noise criticalto ADSL!

Your “stress” test or Longitudinal Bal test is oneof the best pair quality tests, if not

THE BEST

Presenter
Presentation Notes
So what’s all this balance and noise stuff got to do with ADSL? Remember: what kind of signal is ADSL? DC or AC (AC) We have also already talked about bridged taps and balance, the degree to which the TIP ring is electrically the same as the RING lead. And we now know that good balance reduces the effect of power influence (and other noise too). AND NOISE IS CRITICAL TO DIGITAL SERVICES, such as ADSL, HDSL, T1, ISDN, etc.. The quality of the digital ADSL signal on the loop is affected by: signal to noise ratio (most important) loop resistance and faults (cause signal echoes and reflections) Bridged taps (increased capacitance and signal echoes) capacitance (higher ADSL frequencies attenuated more, where downstream data is carried). Some other disturbers: AM radio, fluorescent lights, electric motors, static electricity, cross talk from other services in the bundle (such as HDSL2 and E1) A balance test tells us so much about the quality of the loop, that it’s the best single test to tell you if the pair is good for ADSL (and other digital services)
Page 43: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 43

Resistance versus Capacitance Length

24 AWG51 Ohms SHORT

No faults on lateral/Bridge-Tap

Will this lateral/Bridge-Tap affect resistance measurement?

T

R

Presenter
Presentation Notes
To help us understand the differences, I’ll start by asking a question: (describe the loop: shorted, a bridged tap ½ way down the loop between our meter on the left end and the short on the far end; the lateral has no faults). CLICK mouse to display questions: Q1: will this lateral affect my resistance/ohmmeter? (NO) Q2: will this lateral affect my opens/capacitance meter? (YES) Why is this? Ohmmeters use DC current, which seaks a continuous path from one pole of the source back to the other pole of the source, like a car battery. It ignores other paths that don’t lead back. (it was key that the lateral had no faults, as some faults could provide a path back to the source). Opens meters use AC current, which seeks any path to ground, and will follow any path in search of ground. So the opens meter “sees” the bridged tap and lateral.
Page 44: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 44

Resistance versus Capacitance Length

0.0381 µF OPENR

T

Will this lateral/Bridge-Tap affect Capacitance measurement? No faults

on lateral/Bridge-Tap

Presenter
Presentation Notes
To help us understand the differences, I’ll start by asking a question: (describe the loop: shorted, a bridged tap ½ way down the loop between our meter on the left end and the short on the far end; the lateral has no faults). CLICK mouse to display questions: Q1: will this lateral affect my resistance/ohmmeter? (NO) Q2: will this lateral affect my opens/capacitance meter? (YES) Why is this? Ohmmeters use DC current, which seaks a continuous path from one pole of the source back to the other pole of the source, like a car battery. It ignores other paths that don’t lead back. (it was key that the lateral had no faults, as some faults could provide a path back to the source). Opens meters use AC current, which seeks any path to ground, and will follow any path in search of ground. So the opens meter “sees” the bridged tap and lateral.
Page 45: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 45

(No faults on lateral)

51 ohms Resistance = 1500 ft

Opens = 0.0381 = 2500 ft

Why the big difference?1000 ft of Bridge - Tap

Resistance versus Capacitance Length

T

R

Presenter
Presentation Notes
Let’s say we took our resistance reading, and converted it to feet: we came up with 1500 feet (457 m). Then we used our opens meter and came up with 2500 feet (762 m): What have we just discovered/found? A BRIDGED TAP! Remember, the ohmmeter uses DC current that bypasses the bridged tap An Opens or capacitance meter uses AC current that goes down all paths Can we locate our tap with resistance or opens? No So we need a TDR: the best use of a TDR is to look for a fault when you already know it is there! It is very difficult to use a TDR when you just clip it on and look at the all the bumps and squiggles (confirm this with a tech). Let’s talk a little more now about a capacitance/opens meter.
Page 46: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 46

Testingwith

aTDR

(Time Domain Reflectometer)

Presenter
Presentation Notes
Testing with a TDR: A TDR (Time Domain Reflectometer) is a test tool that operates similar to RADAR and is sometimes referred to as a “Cable Radar Set”. A TDR sends out a electrical “pulse” of energy and depending on the type of line imperfection it encounters energy in the form of modified pulse is bounced back to the TDR. If a line had no imperfections and was terminated in the resistive or impedance characteristic of the line (typically 100 to 135 ohms for a telephone cable pair) no energy pulse would be returned to the TDR. TDR parameter adjustments A TDR calculates and displays the distance to an event and/or fault by knowing what the speed of the pulse it transmits on a specific cable pair type. By knowing the speed at which the pulse travels the TDR knows when a pulse is returned to it that half of the time it took to return to the TDR is equal to the distance to the event and/or fault. A telephone cable pair restricts electricity to travel at speed that is less than the speed of light mainly because of capacitance and resistance that is inherent in the cable pair. To adjust the TDR for different cable types a TDR usually allows the user to select the Cable type, such as Air Core, Jelly Filled, etc., to compensate for the speed at which a pulse will travel for a given cable type. If exact distance to event and/or fault location is required most TDRs allow the user to adjust the “Velocity of Propagation” that can be set to the actual speed that a pulse travels on a specific cable pair.
Page 47: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 47

Testing with a TDR How it works for an Open

– A Pulse is sent out

– When the Pulse encounters a fault it reflects energy back

– The reflected pulse energy returns and the distance is ½ the time

Presenter
Presentation Notes
Testing with a TDR: Depending on the range that a TDR is set to the will adjust the size of the pulse that is transmitted. The larger the pulse width the more energy that is transmitted. Short Range: A smaller pulse is transmitted because not very much energy is required to identify cable pair events when they are not far from the TDR All TDR pulses create a “blind” spot, so it is important to have the smallest pulse possible when looking for faults that are relatively at a short distance from the TDR so that they wont be “hidden” by the “blind” spot. Long Range: A larger pulse is used for a TDR’s longer ranges so that there is enough energy for the TDR to display faults that are ate a great distance from the TDR. Since a TDR’s pulse will lose energy with every “event” (splices/joints and or fault) it encounters as well as loss caused by the cable itself it needs more energy to reach the end of the cable. Finally the pulse not anly must deal with the cable loss as it travels down the cable pair but also it encounters the same loss on the return trip back to the TSR. How it works for an Open: When a TDR pulse encounters the end of the cable that is an un-terminated open (very high resistance) the pulse is returned as a positive pulse with a sharp leading edge. If the TDR pulse encountered a high resistance at the end of a cable pair the pulse that is returned would have a lesser value than a cable pair what was open.
Page 48: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 48

Testing with a TDR

How it works for a Short

– A Pulse is sent out

– When the Pulse encounters a fault it reflects energy back

Presenter
Presentation Notes
Testing with a TDR How it works for a Short When a TDR pulse encounters a short (cross) the returned pulse will be inverted (negative) in value. Any event that is less in value that the characteristic impedance of the cable pair will be negative in value.
Page 49: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 49

Testing with a TDR How it works for a Bridge Tap

– A Pulse is sent out

– When the Pulse encounters a fault it reflects energy back

Presenter
Presentation Notes
Testing with a TDR How it works for a Bridge-Tap When a TDR pulse encounters the location where a Bridge-Tap is attached to the main cable pair it appears as a lower impedance that the cable pair’s characteristic impedance and therefore returns a negative pulse. Additional pulse energy from the TDR continues to travel down the main cable pair and the Bridge-Tap cable pair. When the pulse energy reaches the end of the main cable pair and the Bridge-Tap cable pair end positive pulses are returned. Depending if the Bridge-Tap cable pair or the main cable pair is longer will depend on what pulse appears further away. The Bridge-Tap cable pair length can be measured if first of all the total length of the main cable pair is known thereby allowing the user to recognize which positive pulse is associated with the end of the main cable pair. The Bridge-Tap cable pair than can be measured from the leading edge of the negative returned pulse to the leading edge of the positive pulse associated with the end of the Bridge-Tap cable pair.
Page 50: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 50

TechniquesFor

Cable Fault Locating

Page 51: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 51

Cable Characteristics

Each pair in a binder group has a different twist per meter.

0.083mf/mile Cable Capacitance can very from 0.075mf/mile to 0.089mf/mile.– Capacitance doesn’t very with temperature

Cable resistance varies with Temperature– The higher the temperature the higher the resistance

Page 52: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 52

Cable Failures: Wet Section Using a TDR to locate a Wet Section

– Signature:• Downward dip at the point the Cable pair encounters water• TDR trace in the wet section usually is curved slightly • Wet section trace is also uneven• Upward rise @ end of the wet section where the pair leaves the water

– Affects:• After the entering the wet section the TDR trace is no longer valid

– Distance measurement is no longer accurate• Water attenuates the TDR signal

– Long length of a wet section may prevent the end of a wet section to be seen

Page 53: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 53

Resistance Bridge

Factors that affect Ohms measurements– Gauge

– Temperature• Every degree Celsius of temperature change causes a cable to appear

0.00218 feet per degree Fahrenheit longer or shorter– Wire composition

• Copper, Aluminum, Mixed alloy– All affect the Electrical distance that will be different than the actual

distance• Adjustments must be made in test sets to account for the difference

FEET/OHM @ 68° F

GAUGE

124.2419

61.6522

35.5424

2426

Presenter
Presentation Notes
Resistance Bridge: Factors that affect Ohms measurements Since resistance for any material will change when temperature increases or decreases it is necessary to calibrate any measurement device to the temperature of the material that is to be measured. For Copper conductors as temperature increases its resistance increases and as temperature decreases its resistance decreases. Because the resistance of a copper conductor changes with temperature its “electrical” length changes with respect to the actual length of the copper wire. Wire Composition Different material used as conductors in telephone cables have difference resistance per unit length and their receptivity changes at a different rated than other materials and therefore need to be calibrated accordingly.
Page 54: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 54

Resistance Bridge

Setup and Operation– Identify the faulted conductor

• Use a High-Impedance meter to ID the faulted conductor– A low impedance meter cannot measure above 3.5

Megohms and will dry out faults.• If both Tip & Ring are faulted use the conductor with the

lowest resistive fault

– Test the good pair• Use a High-Impedance meter to verify the pair is good• The pair must test good in the Megohm range

Presenter
Presentation Notes
Resistive Bridge: Setup and Operation A High Impedance ohm meter requires less current to identify resistive fault and therefore has less chance to “dry” out the moisture that can cause a high resistance fault. By determining the location of a resistive fault on the conductor with the lowest resistance a more accurate distance to the fault will be measured as compared to trying to locate the fault using the conductor with the higher fault resistance. If both tip and ring are faulted nether can be used as a good pair as inaccurate measures will result. A “good” pair must have a resistance better than 3.5 meg ohms.�
Page 55: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 55

Resistance Bridge

Setup and Operation (Con’t)– Attach a far end strap

• If one side of the pair test good strap Tip to Ring

• If both Tip & Ring are faulted strap the Tip & Ring of the good pair to the conductor showing the lowest resistive fault

Presenter
Presentation Notes
Resistive Bridge The far end strap must be of good quality and attached properly and have minimal resistance.
Page 56: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 56

Open (Capacitance) Meter

Unbalance Pair Measurements

– Connect one test lead & cable sheath section to ground– If Tip and Ring measure different Shorter distance is to open

Presenter
Presentation Notes
Open Meter: Unbalance Pair Measurements If either the tip or ring conductor is longer then the other conductor of the pair the distance to the open of the longer conductor is inaccurate. This caused by the capacitance of the longer conductor changing its value beyond the shorter conductors open. Always go to the shorter conductors open as it is the more accurate distance to its open.
Page 57: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 57

Open (Capacitance) Meter

Non-Working Pairs Measurement

– Open Meters are designed to be used on working pairs– If Tip & Ring measurements are shorter than the mutual

capacitance unit is non-working– 12 or more pairs in the same unit must be working or

grounded for accurate measurement – If a unit has fewer than 12 non-working pairs length

measurements will be shorter than actual length

Presenter
Presentation Notes
Open Meter: If a pair’s tip-to-ground and ring-to-ground capacitance measurements is shorter than the tip-to-ring mutual capacitance measurement the binder group is non working. There are two ways to measure to an open in a non working binder group: Calibrate the Open meter on a know good pair in the binder group to a know length Ground 12 pairs in the binder group this will make the binder group pairs appear as working pairs and provide an accurate open meter measurement.
Page 58: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 58

Locating Splits

Splits occur when conductors of pairs with different twist are spliced

– Causes noticeable cross-talk on POTS– 5 feet of split pairs will cause noticeable cross-talk– Detrimental to Digital service, i.e. ADSL

Presenter
Presentation Notes
Locating Splits: A Split Occurs when conductors of pairs with a twists are spliced together along a cable route. This is a man-made problem, and usually occurs in splice , however a split can also occur in cross boxes and access points. Because the twist control is destroyed the capacitance balance of the cable pair is affected The resultant affect is auditable crosstalk for POTS and no modem sync for ADSL. A split can look like a one side open fault if all the other pairs are in use in a binder group. Using an Open meter the pair will appear balanced from both ends
Page 59: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 59

Locating Splits

Split & Corrected Split

– Two wrongs do not make a right!

Presenter
Presentation Notes
Locating Splits: If a far-end-to-split measurement is shorter than the distance-to-split , locate two access points whose separation matches the far-end-to-split measurement The split should be at each access location. If the far-end-to-split measurement is longer than the distance-to-split measurement, the cable should be opened at an access point near to the middle of the cable. One split will be seen in each direction
Page 60: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 60

Locating Splits

Using a TDR to find a Split & Corrected Split fault– Crosstalk Mode:

• Connect TDR Main and Reference leads to both split pairs

EndOf

cable pair

Splitlocation

Re-splitLocation

Presenter
Presentation Notes
Locating Splits with a TDR (Crosstalk Method): Connect both split pairs to the TEST and Reference leads of the TDR. For this test the TDR sends a pulse down the test pair and displays the pulse reflections on the reference pair. The display will be flat except where the crosstalk occurs at the split. At the crosstalk point a sharp spike will be present identifying the split location.. The spike may be positive or negative depending how the test leads are connected to the TDR.
Page 61: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 61

Locating Splits

Using a TDR to find a Split & Corrected Split fault– Comparison Mode:

• Connect TDR Main and Reference leads to both split pairs

Splitlocation

EndOf

cable pair

“Good”Pair

SplitPair

Split PairAppearsShorter

Presenter
Presentation Notes
Locating Splits with a TDR (Comparison method): Compares a Split pair to a known “Good” pair. The split pair will indicate a large reflection at the split location. If the open end of the cable pair can be seen by the TDR the distance for the split pair will measure shorter than the good pair that is in the same binder group. If the pair also contains a re-split, the best method for finding the re-split is to find the split first then locate the re-split using either the Crosstalk or Comparison methods.
Page 62: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 62

Quality of Service Parameters Loop Current

– Less than 20 ma Unacceptable– 20 ma to 23 ma Marginal– 23 ma to 65 ma acceptable– Greater than 65 ma Unacceptable

Presenter
Presentation Notes
Quality of Service Parameters: Loop Current A typical 1500 ohm office is made up of the following 450 ohms CO Ballast Resistance for protection against shorts at the MDF A maximum loop resistance of 1300 ohms 430 allocated for inside wiring and the telephone station equipment Minimum Battery voltage of 44 Volts DC Using Ohms Law we get: (450 + 1300 + 430}= 2180 ohms Loop Current with Low CO Battery 44 Vdc ÷ 2180 Ω = 20 ma Loop Current with Typical Battery float Voltage 52 Vdc ÷ 2180 Ω = 24 ma
Page 63: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 63

Quality of Service Parameters Circuit Loss

– Acceptable level equal or greater than 8 dB loss– Marginal level between 8 db & 10 dB loss– Unacceptable level less than 10 dB loss– 26 gauge 8 dB limit @ 14.6 k feet – 24 gauge 8 dB limit @ 18.5 k feet

Loop Attenuation @ 1000 Hz

0

2

4

6

8

10

12

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19LOOP LENGTH (K feet)

LOSS

(dB

)

26 ga 24 ga Minimum Acceptable Minimum Marginal

Presenter
Presentation Notes
Quality of Service Parameters: Circuit loss @ 68 F (20 C) 26 gauge loss @ 1000 Hz = 2.90 dB/Mile (1.80 dB/km) 8 dB loss @ 14.6 k ft (4.44 km) 24 gauge loss @ 1000 Hz = 2.28 dB/Mile (1.42 dB/km) 8 dB loss @ 18.5 k ft (5.63 km) 22 gauge loss @ 1000 Hz = 1.80 dB/Mile (1.12 dB/km) 8 dB loss @ 23.5 k ft (7.14 km) 1300 ohm Loop Resistance Limits @ 68 F (20 C) 26 gauge = 15.6 k ft (4.72 km) 24 gauge = 23.1 k ft (7.00 km) 22 gauge = 40.0 k ft (12.12 km)
Page 64: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 64

Quality of Service Parameters

Station Ground– Station ground < 25 ohms

• Assures protector operation in presents of Lightning & power faults– Measuring station ground

• First measure Tip-to-Ring loop current • Strap (short) Tip to Ring

• Remove strap and measure current to ground

• Results: Loop current should increase from T-R to R-G Measurement – > 150% for T-R > 60 ma: Example for 70 ma T-R, R-G > 150 ma– > 170% for T-R > 40 ma < 60 ma: Example for 50 ma T-R, R-G > 85 ma– > 180% for T-R > 23 ma < 40 ma: Example for 30 ma T-R, R-G > 54 ma

Exchange

TIP

RING

CurrentMeter Station

Ground

MeterTIPLead

MeterRINGLead

Exchange

TIP

RING

CurrentMeter Station

Ground

MeterTIPLead

MeterRINGLead

Presenter
Presentation Notes
Quality of Service Parameters: Station Ground The station ground should test to be 25 ohm or less to assure the station protector will fire when power or lightning is present on a circuit and therefore protect the customer and station equipment from damage.
Page 65: Copper Cable Trouble Shooting Session Test Equipment Demo

© 2007 JDSU. All rights reserved. 65

“Enabling The Internet to Perform”

Be Pro-active– Test Every POTS & ADSL Line After Installation & Repair– Test Both Voice & Dial-up Data and ADSL Lines are meeting

requirements Document Your Network Performance

– Use HST-3000/TB-4000 Close Out Test & “SAVE” results Have Data to Support Your Network Quality

– Insure Quality Assurance (QA) Goals are being met Stay on Top of Your Network’s Performance