copy of chapter 12 heco system overview

21
March 14, 2008 7 Hawaiian Electric Company, Inc. HECO System Overview Generation (Continued) Jan Dec Sep Total Installed Net Capacity Predicted Peak Demand Minimum Capacity Required Available Reserve Spinning Reserve – capacity of the largest single unit Unit Overhaul Unit Overhaul Unit Overhaul Unit Overhaul Unit Overhaul Unit Overhaul Maint Outage Maint Outage Maint Outage Maint Outage 1672 MW Illustration showing how the available reserve is used to plan and schedule generating unit outages.

Upload: kyle-grousis-henderson

Post on 25-Sep-2015

233 views

Category:

Documents


6 download

DESCRIPTION

hawaiian electric system overview

TRANSCRIPT

  • March 14, 20087Hawaiian Electric Company, Inc.

    HECO System OverviewGeneration (Continued)

    Jan DecSep

    Total Installed Net Capacity

    Predicted Peak Demand Minimum

    Capacity Required

    Available Reserve

    Spinning Reserve capacity of the largest single unit

    Unit Overhaul

    Unit OverhaulUnit

    OverhaulUnit

    OverhaulUnit

    Overhaul

    Unit OverhaulMaint

    Outage

    Maint Outage

    MaintOutage

    MaintOutage

    1672 MW

    Illustration showing how the available reserve is used to plan and schedule generating unit outages.

    Matthias Frippslides from http://www.heco.com/vcmcontent/GenerationBid/HECO/HECOSystemOverview.pdf and http://www.heco.com/vcmcontent/GenerationBid/HECO/CompetitiveBid/2011-12-07_Technical_Conference_Presentation.pdf

    Matthias Fripp

  • March 14, 20088Hawaiian Electric Company, Inc.

    2007 Actual Maintenance Schedule

    HECO System Overview Generation (Continued)

    0

    50

    100

    150

    200

    250

    300

    350

    400

    1 31 61 91 121 151 181 211 241 271 301 331 361

    Me g

    a wa t

    t s

    Jan. Feb. Mar. Apr. May June July Aug. Sep. Oct. Nov. Dec.Note: Months are set at 30 day periods. Theref ore the markers may not be set exactly according to the calendar y ear.

    Reserve = Operating Capability (1698) - Largest Single Unit (180)- Predicted Peaks of 05/22/03

    POWER SUPPLY OPERATION & MAINTENANCE 2007 PLANNED MAINTENANCE SCHEDULE

    2007

    Revision Date: 01/17/04

    AES

    KP L

    P

    H9

    W6

    KPLP

    K6

    W7

    W8

    H9 HRRV

    K1

    K5

    K3

    K4

    H9

    HRRV

    H8

    W5

    W9

    H9

    W1 0

    W9

    W4

    W3

    K1

    W3

    W1 0

    Note: Jan, Feb, Mar, Apr, May, Jun, Jul, Aug, Sep, Oct, Nov, Dec Actual Peaks

    K2

    W8

    W8K4

    K1

    K5

    KPLP

    HRRV

    W3

    W6

    K4

    K5

    W9

    W3

    W3

    K2

    K6

    K5

    AES

    W3

    KPLP

    AES

    Revision Date: 1/18/08Reserve = Operating Capability (1698) Largest Single Unit (180) -Predicted Peaks of 5/23/07

  • March 14, 20089Hawaiian Electric Company, Inc.

    Midnight Midnight

    7 am 5 pm 9 pm

    Peak Period

    Shoulder PeakPriority Peak

    Off-PeakOff-Peak

    MW

    HECO System Overview Generation (Continued)

    Typical Daily System Demand (Load) Profile

    Minimum Load

    Peak Load

  • March 14, 200811Hawaiian Electric Company, Inc.

    Illustration of meeting daily demand

    12 midnight 6am 12 noon 6 pm 12 midnight

    100

    50

    Cycling

    Baseload

    PeakingPeaking units such as W9 & 10 start up to meet the highest peak periods

    Cycling units such as H8 & 9, W3-6 start up and shut down daily to support system peaks.

    Baseload units such as K1-6, W7 & 8, AES, KPLP, HRRV, operate 24 x 7 and are dispatched up during peak periods and dispatched down to near minimum loads

    HECO System Overview Generation (Continued)

  • March 14, 200812Hawaiian Electric Company, Inc.

    Spinning Reserve and QLPU on a Daily Basis

    12 midnight 6am 12 noon 6 pm 12 midnight

    100

    50

    Cycling

    Baseload

    PeakingPeaking units typically operate at less than normal capacity to support SR and QLPU criteria

    Selected cycling units operate less than normal capacity to support SR and QLPU criteria

    Selected baseload units operate less than normal capacity to support SR and QLPU criteria

    HECO System Overview Generation (Continued)

    Minimum Spinning Reserve

  • March 14, 2008Hawaiian Electric Company, Inc.

    Illustration of Spinning Reserve and Quick Load Pickup Operating Criteria

    MW Output

    Normal Capability Rating = 100 MW

    Operating level serving load = 70 MW

    Individual Unit Contribution to Spinning Reserve = 30 MW 3-Second Quick Load Pickup (QLPU) = 18 MW

    QLPU provides a portion of the units spinning reserve within 3 seconds

    HECO System OverviewGeneration (Continued)

    100 MW Generating Unit

  • March 14, 200819Hawaiian Electric Company, Inc.

    Automatic Generation Control (AGC)determines how many MW to increase or decrease on selected generators to correct for Time Error or minor Frequency Deviation from 60 Hz. AGC is capable of controlling frequency between 59.8 Hz and 60.2 Hz.

    Economic Dispatch Calculation (EDC)determines what generators to use and which way the generators should move.

    Energy Management System (EMS) translates the desired movement into up or down pulses and sends the pulses to the Turbine Control Systems of the selected generators.

    The Turbine Control System moves the unit up or down in output in response to the EMS pulses.

    AGC

    EDC

    0.2 sec pulse every 10 seconds to raise or lower generator output

    VOLTAGE REGULATOR

    EMS

    EMS Raise/Lower

    Pulses

    Under normal conditions system frequency is regulated by the Energy Management System (EMS)

    Energy Management System (EMS)

    Raise/Lower Pulses

    Frequency Regulation Normal Conditions(Continued)

  • March 14, 200823Hawaiian Electric Company, Inc.

    Examples of what can trigger a disturbance:

    Loss of generation due to protective trips (Supply < Demand)

    Loss of transmission lines due to line faults (Supply > Demand)

    Loss of a major substation transformer(Supply > Demand)

    Loss of a large customer due to customer equipment malfunctions (Supply > Demand)

    Impact of natural causes, i.e, storms, lightning, earthquake, tsunami, sea grass, jellyfish, etc.

  • March 14, 200825Hawaiian Electric Company, Inc.

    Illustration of a Disturbance Caused by Loss of Generation

    When a generator trips unexpectedly, a shortfall is created where the demand (load) is greater than supply and system frequency begins to sag to a value below 60 Hz. The rate of frequency sag (droop) depends on the size of the mismatch between Supply and Demand. As soon as underfrequency is detected, generation reserves are added via droop control till the frequency stops dropping. At this point the scale is still out of balance, but stable at a frequency below 60 Hz. To restore frequency back to the predisturbance level of 60 Hz, more generation from available spinning reserves is required.

    (Supply < Demand)

    6061

    6258

    59

    System Underfrequency (Hz)

    Load

    (MW)

    Generation

    (MW)(Demand)

    (Supply)

    Pre-disturbance Generation

    Generator Trip

    Generation Reserve

    Generation Overspeed ProtectionUnderfrequency Load Shedding

    QLPU added to arrest the sudden drop-off in frequency

  • March 14, 200826Hawaiian Electric Company, Inc.

    When load is lost unexpectedly due to transmission faults and other load related causes, a situation with excess generation is created that will cause system frequency to rise to a value above 60 Hz. As long as Supply > Demand, system frequency will continue to rise until all generators trip on overspeed. The rise in frequency can be arrested if generators are able to reduce their load before reaching their overspeed protection points.

    (Supply > Demand)

    6061

    6258

    59

    System Overfrequency (Hz)

    Load

    (MW)

    Generation

    (MW)

    (Demand)

    (Supply)

    Pre-disturbance Load

    Underfrequency Load Shedding

    Generator Load Reduction

    Illustration of a Disturbance Caused by Loss of Load

    Generation Reserve

    Generation Overspeed Protection

  • December 7, 2011

    Managing System Frequency Governor response

    Hawaiian Electric generators use active droop with little or no dead band

    Generation is normally controlled via AGC Frequency Control Economic Dispatch (normal condition)

    Local Frequency Control (LFC) at each generating unit takes control of managing the system frequency during disturbances

    Fast start generators Load management programs (CIDLC and RDLC) Manual & automatic under frequency load shedding Manual & automatic generator trip for excessive over

    frequency 11

  • March 14, 200827Hawaiian Electric Company, Inc.

    Abnormal Frequency Mitigation - Generation

    Full range of operating frequencies

    Generating Unit Turbine Control

    Droop 5% continuous

    Underfrequency:59.5 Hz to 59.8 Hz

    Overfrequency: 60.2 Hz to 60.5 Hz

    Generating UnitLocal Frequency Control (LFC)- 0.2 second pulse every 2 seconds outside of the control range

    - 0.2 second pulse every 4 secondsinside the control range

    59.8 Hz to 60.2 HzSystem Operation

    Automatic Generation Control AGC)- 0.2 second pulse every 10 seconds

    Control RangeLocationControl Device

  • December 7, 2011

    Underfrequency Management 59.97 Hz Targeted Frequency Control Range Economic Dispatch. 59.97 Hz (1) AGC Off-Economic Frequency Regulation Control Modes. 59.90 Hz 59.80 Hz

    Internal (Hawaiian Electric Dispatch) Frequency Alarm. External (Paging) Frequency Alarm Issued.

    59.70 Hz RDLC Automatic UF Load Shedding. 59.50 Hz Hawaiian Electric Generators Switch To Local Frequency Control

    Unit For Emergency Ramping. CIDLC Automatic UF Load Shedding.

    58.50 Hz 58.00 Hz to 57.00 Hz

    UF Auto Load Shed Kicker Block After 10-second delay. UF Automatic Load Shedding, No Delay. AES Trip at 58.2 Hz w/ 82 sec. time delay H-Power Trip at 58.0 Hz w/10 sec. time delay

    57.00 Hz 56.50 Hz

    Hawaiian Electric Generator Automatic Trip After 70-second delay. Hawaiian Electric Generator Automatic Trip, No Delay. Kahipa WF trip at 57.0 Hz w/ 6 sec. time delay Kalaeloa Trip at 56.8 Hz in 0.15 seconds

    Notes: (1) Approximate, AGC switches based on Area Control Error (ACE) rather than

    frequency. 13

  • December 7, 2011

    Overfrequency Management 66.00 Hz (2) Hawaiian Electric Generator Automatic Overspeed Trip.

    61.50 Hz (2) Hawaiian Electric Generator Overspeed Governors And Controls.

    60.50 Hz Hawaiian Electric Generators Switch To Local Frequency Control Unit For Emergency Ramping.

    60.20 Hz 60.10 Hz

    External (Paging) Frequency Alarm Issued. Internal (Hawaiian Electric Dispatch) Frequency Alarm.

    60.03 Hz (1) AGC Off-Economic Frequency Regulation Control Modes.

    60.03 Hz Targeted Frequency Control Range Economic Dispatch.

    Notes: (1) Approximate, AGC switches based on Area Control Error (ACE) rather than

    frequency. (2) Approximate, similar but may differ by unit make and model.

    12

  • March 14, 200830Hawaiian Electric Company, Inc.

    Kahe 5 Droop Example

    0 150

    58

    59

    60

    61

    62F r

    e qu e

    n cy

    ( Hz )

    Unit Output (MW)

    Initial set-point at 75 MW, 5% droop

    Generator MW output would slide back and forth along the 5% droop curve in an attempt to stabilize (match) supply and demand regardless of the frequency.

    1005025 75 125

  • March 14, 200831Hawaiian Electric Company, Inc.

    Underfrequency Load Shedding as a Mitigation Measure

  • December 7, 2011

    Comparison of Existing and Proposed UFLS Schemes & NERC Limits

    60 Hz

    57 Hz

    58 Hz

    59 Hz

    60 Hz

    57 Hz

    58 Hz

    59 Hz

    60 Hz

    57 Hz

    58 Hz

    59 Hz

    in 10 sec

    in 5 & 10 sec

    Floor

    60 sec

    Existing Scheme

    Proposed Scheme

    93MW

    93MW

    80MW

    93MW 40MW

    46MW 47MW

    92MW

    105MW

    105MW

    40MW

    25MW

    439MW

    445MW

    Freq. to remain above a log linear curve from 58 to

    59.3 for 60 sec or until steady-state

    above 59.3

    NERC Design Parameters PRC-006-1

    25% Gen. Loss

    14

  • March 14, 200836Hawaiian Electric Company, Inc.

    F re q

    u en c

    y ( H

    z )

    60 Hz

    Time (sec.)

    58.5

    6 12

    58.0

    57.0

    Block 1 trip

    Block 2 trip

    Kicker Block trip

    2

    Kicker Block timer initiated

    Illustration of HECOs Underfrequency (UF)Load Shedding Scheme Design

  • March 14, 200832Hawaiian Electric Company, Inc.

    Illustration of a Small versus Large Generating Unit Trip

    System Frequency, Hz

    60.0

    58.5

    10 sec time delay

    Time, seconds

    Smaller unit trip or more QLPU

    Unit trip

    Shed load

    Assumes system frequency does not go below 58.0 Hz

    Effects of a Small Unit Trip

    Effects of a Large Unit Trip

  • March 14, 200834Hawaiian Electric Company, Inc.

    System Frequency Based on Time of Day (24 Hour Clock)

    System Frequency Based on Expanded Time Scale (33.5 seconds)

    Actual example of a relatively large unit trip that did not result in load shedding (AES trip from 140 MW)

  • March 14, 200835Hawaiian Electric Company, Inc.

    Frequency Response: AES, HRRV, K3 Gen Trip - 12/19/02(Waiau Site - Zoom)

    57.00

    57.50

    58.00

    58.50

    59.00

    59.50

    60.00

    1 35 0

    4 8

    1 37 7

    8 5

    1 40 5

    2 2

    1 43 2

    5 9

    1 45 9

    9 6

    1 48 7

    3 3

    1 51 4

    7 0

    1 54 2

    0 7

    1 56 9

    4 4

    1 59 6

    8 1

    1 62 4

    1 8

    1 65 1

    5 5

    1 67 8

    9 2

    1 70 6

    2 9

    1 73 3

    6 6

    1 76 1

    0 3

    1 78 8

    4 0

    1 81 5

    7 7

    1 84 3

    1 4

    1 87 0

    5 1

    1 89 7

    8 8

    1 92 5

    2 5

    1 95 2

    6 2

    1 97 9

    9 9

    Raw Data Count: approx 9 minutes elasped time

    F re q

    u en c

    y ( H

    z )

    AES Trip

    Kicker Block (58.5Hz)

    Block 1 (58.0Hz)Block 2 (57.7Hz)

    HRRV & K3 Trip

    ~10 seconds

    Actual example of a relatively large unit trip that resulted inload shedding (AES trip from 180 MW)