copyright wmi/l. f. 'tex' hildebrand 02/2003 1 acid problems in ammonia refrigeration...

34
Copyright WMI/L. F. 'TEX' Hi ldebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference & Exhibition, Albuquerque, New Mexico

Upload: jaiden-ware

Post on 29-Mar-2015

226 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

1

Acid problems inAmmonia Refrigeration Systems

Presented at:

IIAR 2003 Ammonia Refrigeration Conference & Exhibition,

Albuquerque, New Mexico

Page 2: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

2

Acid problems inAmmonia Refrigeration Systems

Presented by:

L. F. “Tex” Hildebrand

Page 3: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

3

Acid problems inAmmonia Refrigeration Systems

IIAR Bulletin 108– Water in Ammonia causes

•loss of capacity•Increase of horsepower•“Chemical changes to compressor

oil. . .’–Organic acids–Sludges–etc.

Page 4: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

4

Acid problems inAmmonia Refrigeration Systems

Water, if left unchecked, in an ammonia refrigeration plant will result in:

– Contamination,– Sludge, and– Corrosion damage to

components

Page 5: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

5

Acid problems inAmmonia Refrigeration Systems

Symptoms of contamination Strainers clogging. Corrosion failure to float valve

cartridges, solenoid valves, thermal expansion valves, check valves, etc. (wherever liquid is throttled).

Sight glasses coated from inside with a brown emulsion (gooey stuff!).

Problems maintaining evaporating temperatures.

Page 6: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

6

Acid problems inAmmonia Refrigeration Systems

Causes of contamination - Let us look at The Players and their roles:

• AMMONIA• COMPRESSOR• OIL• AIR• WATER• CO2

• DISSOCIATION BY-PRODUCTS• SLUDGE (BECOMES THE “MAALOX”)• ANAEROBIC BACTERIA• ORGANIC ACID(S)

Page 7: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

7

Acid problems inAmmonia Refrigeration Systems

Remedies – The actual remedy applied will vary

with the extent of contamination found in the system. Generally the following class conditions will apply:1. When contamination is discovered at

an early stage2. When contamination has progressed

to a more serious state3. A very seriously contaminated system

Page 8: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

8

Acid problems inAmmonia Refrigeration Systems

Remedies (Class Condition-1). NOTE: This remedy should be used in conjunction to all others.– Install an ammonia still to remove

the water and stop the contamination from progressing.

– Liquid filters in pumped liquid lines will help clean up the contamination. (However, if water is not removed, contamination will continue to grow).

Page 9: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

9

Acid problems inAmmonia Refrigeration Systems

Remedies (Class Condition-2).– Shut down system and remove all

ammonia charge.– De-hydrate entire system with

appropriate evacuation – Re-charge system with

refrigeration grade ammonia.– Insure proper ventilation if CO2 is

in use in plant processes.

Page 10: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

10

Acid problems inAmmonia Refrigeration Systems

Remedies (Class Condition-3).– Shut down system and remove all

ammonia charge.– Using an appropriate mixture of

solvents, clean all vessels, and piping, if possible.

– Clean or replace all sight glasses, strainers, throttling device kits.

– Repair or replace all check valves.

Page 11: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

11

Acid problems inAmmonia Refrigeration Systems

Remedies (Class Condition-3 Cont’d).– Change oil and filters on all

compressors.– Dehydrate entire system with

appropriate evacuation.– Re-charge system with

REFRIGERATION GRADE AMMONIA.

Page 12: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

12

PHILLIPS 701 Pilot Valve Parts (1)

New Parts Damaged Parts

Page 13: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

13

PHILLIPS 701 Pilot Valve Parts (1)

Page 14: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

14

PHILLIPS 701 Pilot Valve Parts (2)

Page 15: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

15

Strainer basket

OldFrom -40 Deg. F. Liquid Makeup from Controlled Pressure Receiver

Newfor comparison

Page 16: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

16

TXV Cage Assembly

New

Used (1)

Page 17: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

17

Damaged TXV Cage Assembly

Used (2)

Used (1) Example of brown emulsion (gooey stuff!)

Page 18: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

18

Damaged TXV Cage Assembly

Used (1)

Used (1)

Page 19: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

19

Damaged TXV Cage Assembly

Used (2)

Used (2)

Page 20: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

20

Damaged Phillips Pilot Float Valve Cartridge

Used

Page 21: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

21

Damage on In-Line Check Valve Parts

Page 22: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

22

Acid problems inAmmonia Refrigeration Systems

Preventative Maintenance Insure that ammonia still is

installed and is functioning properly.

System Opening Policy (Line Breaking Permit Procedure).

Periodic inspections for negative pressure leaks (shaft seals, valve stems, etc.)

Page 23: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

23

Acid problems inAmmonia Refrigeration Systems

Preventative Maintenance (Cont’d).

In plants where CO2 is used in the process, special care should be placed on proper ventilation systems to preclude the CO2

concentration from entering the Refrigeration System, through possible vacuum leaks or during service/maintenance operations.

Page 24: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

24

Acid problems inAmmonia Refrigeration Systems

Preventative Maintenance (Cont’d).

Regular oil samples from all compressors should be analyzed for water, particle count, wear debris, Total Acid Number (TAN), and properties of the lubricant, i.e. viscosity, additive depletion, etc. Trend charts for monitoring change are useful.

Page 25: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

25

Acid problems inAmmonia Refrigeration Systems

Preventative Maintenance (Cont’d).

Oil sample from new oil (to establish baseline) should be included with compressor oil samples.

Periodic samples from oil in oil pots should be sent to lab for analysis to determine Total Acid Number (TAN), water, and particle count.

Page 26: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

26

Acid problems inAmmonia Refrigeration Systems

Preventative Maintenance (Cont’d).

Oil samples should always be collected adhering to a written oil sample procedure to insure accuracy and repeatability.

Periodic tests should be performed according to IIAR Bulletin 108.

Install filter in liquid ammonia lines.

Page 27: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

27

Acid problems inAmmonia Refrigeration Systems

Summary Water seriously damages the

lubricating properties of oil and promotes component corrosion. Increased water concentrations indicate possible condensation, coolant leaks, or process leaks around the seals. Improper maintenance procedures may also contribute to this problem.

Page 28: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

28

Acid problems inAmmonia Refrigeration Systems

Summary (Cont’d) Organic acids, a by-product of oil

oxidation, degrade oil properties and lead to corrosion of the internal components.

The Total Acid Number (TAN) is lowest as a virgin oil and can gradually increase with use.

Page 29: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

29

Acid problems inAmmonia Refrigeration Systems

Summary (Cont’d) A steady rise in the Total Acid

Number (TAN) is an alarm for an oil change.

Increase in acid levels is typically caused by oil oxidation over time. However, acids generated due to contamination by-products will send the Total Acid Number (TAN) soaring in a relatively short time span.

Page 30: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

30

Acid problems inAmmonia Refrigeration Systems

Summary (Cont’d)•The invasion of contaminants from

the surrounding environment in the form of dirt, water, and process contamination are the leading cause of machine degradation and failure. Monitoring increased contamination should be the trigger to take action in order to save the oil and avoid unnecessary machine wear.

Page 31: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

31

Acid problems inAmmonia Refrigeration Systems

Summary (Cont’d)•By identifying potential sources of

contamination, it is possible to more effectively monitor the level of contaminants in the lubricating oils. Potential contaminants and sources of ingression will be identified. This will allow for proper monitoring, and specific corrective action when contamination is found.

Page 32: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

32

Elements Possible Source Elements Possible Source

I ron (Fe)Shafts, Gears,Housing, PistonRings, Cylinder Walls

Silicon (Si)Dirt, DefoamantAdditive

Copper (Cu)Brass/ Bronze Alloys,Bearings, Bushings,Thrust Washers

Boron (B)Anti-corrosion inCoolants

Lead (Pb)Bearings, Anti-WearGears

Sodium (Na)Detergent Additive,Coolant Additive

Tin (Sn)Bearing Alloys,Bearing Cages,Solder

Barium (Ba)Rust and CorrosionInhibitors

Aluminum(Al)

Pumps, ThrustWashers, Pistons

Calcium (Ca)Detergent/ DispersantAdditive

Chromium(Cr)

Roller Bearings,Piston Rings,Cylinder Walls

Phosphorus(P)

Anti-wear Additive, EPGear Additive

Nickel (Ni)Pumps, GearPlatings, Valves

Potassium (K) Coolant Additive

Titanium (Ti) Exotic AlloyMolybdenum(Mo)

EP Additive

Silver (Ag) Some Bearings Zinc (Zn) Anti-wear Additive

Magnesium(Mg)

Detergent Additive,Coolant Additive

Vanadium (V) Turbine Blades

Identification of elements in particulate matter

Page 33: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

33

Acid problems inAmmonia Refrigeration Systems

Questions?

Page 34: Copyright WMI/L. F. 'TEX' Hildebrand 02/2003 1 Acid problems in Ammonia Refrigeration Systems Presented at: IIAR 2003 Ammonia Refrigeration Conference

Copyright WMI/L. F. 'TEX' Hildebrand 02/2003

34

Thank You!“Tex”