ct analyzer whats new v430 enu
DESCRIPTION
Omicron CT AnalyzerTRANSCRIPT
-
CTA Toolset 4.30
Whats New?
-
Whats new in the CTA Software Version 4.30? Overview of new features and changed functionality:
1. support of the new IEC Standard for Current Transformers IEC 61869-2:
> Measurement according to the new specification
> Automated Assessment of the CT under test for compliance with IEC 61869-2
2. Extended Isn up to 25 A
3. Polarity check function together with the OMICRON CPOL polarity tester hardware
Whats new in the CTA Hardware?
> PC connection via USB interface
-
1 Whats new in the CTA Software Version 4.30?
1.1 Support of the NEW IEC Standard for Current Transformers IEC 61869-2
The new CT Analyzer software version enables the test of current transformers according to the new IEC 61869-2 standard. The new standard can be selected in the GUI on the CT-Object card. Simply move down in the menu to the Standard selection field and choose the desired standard from the pre-configured menu via the soft keys. If preferred, the IEC 61869-2 can also be configured as default start-up setting.
The newly released IEC Standard for Current Transformers IEC 61869-2 replaces the former IEC 60044-1 and IEC 60044-6 standards. The CT Analyzer still supports the old IEC standards 60044-1 and 60044-6 additionally to the new standard to enable the test of equipment designed according to the old standard. A short summary of the main changes regarding the CT Analyzer measurement and assessment process can be found in the Customer Area on the OMICRON website. For more detailed information please consult the standard document available on the IEC website.
1.2 Extended Isn range up to 25 A
It is now possible to test CTs with a rated secondary current of up to 25A.
-
1.3 Polarity check function together with the OMICRON CPOL polarity tester hardware
The new CT Analyzer software now supports the OMICRON CPOL polarity tester hardware as also used together with the CPC and CMC test equipment. The SW option is available via the Quick menu and is compatible with the existing test hardware delivered from OMICRON.
If you are interested in this option, please contact your sales representative for further information or a quote.
1.4 Miscellaneous
For more details about the new functions and their safe and appropriate operation, please consult the User Manual delivered as hard copy with new equipment or available as soft copy within the new installed PC Toolset in the section Manuals.
-
2 Whats new in the CTA Hardware?
2.1 PC connection via USB interface
CT Analyzer devices as of serial number JHxxxx or newer are equipped with a USB interface and a RS232 interface. If available, you can use both interfaces alternatively to connect the CT Analyzer to a computer. OMICRON recommends to use the USB interface since communication via USB is considerably faster than communication via RS232.
Since in this case the CT Analyzer provides two alternative interfaces, the user has to select the interface to be used (or check the selection) in the CT Analyzer settings before connecting the CT Analyzer. The factory default setting for those devices is USB.
4. Open the Main Menu on the CT Analyzer and select Settings.
5. In the Setting Menu page, select Remote Interface.
6. In the Select remote interface port page, select the interface actually used to connect the CT Analyzer to the computer: USB or RS232.
Note: The CT Analyzer will only communicate via the selected interface. It will not be recognized by the computer if the CT Analyzer settings do not match the interface used for connection. The following figures show the possible scenarios for connecting the CT Analyzer and the CT SB2 switch box to a computer.
RS232 interface
USB interface
(type B connector)
-
2.1.1 CT Analyzer connected via USB:
2.1.2 CT Analyzer connected via RS232 interface and a RS232/USB adapter on the PC side:
2.1.3 CT Analyzer connected via RS232 interface:
to PC
to PC
CTA
RS232
(crossover)
USB A/B
CT SB2
(opt ional)
CT Analyzer
USB A/B
CT Analyzer settings:
Main Menu -> Settings ->
Remote Interface -> USB
to PC
CTA
RS232
(crossover) CT SB2
(optional)
CT Analyzer
CT Analyzer settings:
Main Menu -> Settings ->
Remote Interface -> RS232
RS232
(1:1)
to PCRS232
(crossover)CT Analyzer
PC
RS232/USB
adapter
RS232/USB
adapter
to PC
CTA
RS232
(crossover) CT SB2
(optional)
CT Analyzer
CT Analyzer settings:
Main Menu -> Settings ->
Remote Interface -> RS232
RS232
(1:1)
to PCRS232
(crossover)CT Analyzer
PC
-
OMICRON is an international company serving the electrical power
industry with innovative testing and diagnostic solutions. The application of
OMICRON products provides users with the highest level of confidence in
the condition assessment of primary and secondary equipment on their
systems. Services offered in the area of consulting, commissioning,
testing, diagnosis, and training make the product range complete.
Customers in more than 140 countries rely on the company's ability to
supply leading edge technology of excellent quality. Service centers on all
continents provide a broad base of knowledge and extraordinary customer
support. All of this together with our strong network of sales partners is
what has made our company a market leader in the electrical power
industry.
Europe, Middle East, Africa
OMICRON electronics GmbH
Oberes Ried 1
6833 Klaus, Austria
Phone: +43 5523 507-0
Fax: +43 5523 507-999
Asia-Pacific
OMICRON electronics Asia Limited
Suite 2006, 20/F, Tower 2
The Gateway, Harbour City
Kowloon, Hong Kong S.A.R.
Phone: +852 3767 5500
Fax: +852 3767 5400
Americas
OMICRON electronics Corp. USA
3550 Willowbend Blvd.
Houston, TX 77054, USA
Phone: +1 713 830-4660
+1 800-OMICRON
Fax: +1 713 830-4661
www.omicron.at www.omicronusa.com