ct is standard

17
IS 2705 (Part 1) : 1992 (Reaffirmed 1997) Edition 3.2 (2002-04) Indian Standard CURRENT TRANSFORMERS — SPECIFICATION PART 1 GENERAL REQUIREMENTS ( Second Revision ) (Incorporating Amendment Nos. 1 & 2) UDC 621.314.224 © BIS 2002 B U R E A U O F I N D I A N S T A N D A R D S MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG NEW DELHI 110002 Price Group 7

Upload: ashutosh2009

Post on 08-Nov-2014

22 views

Category:

Documents


1 download

DESCRIPTION

ct

TRANSCRIPT

Page 1: Ct is Standard

IS 2705 (Part 1) : 1992(Reaffirmed 1997)

Edition 3.2(2002-04)

Indian Standard

CURRENT TRANSFORMERS — SPECIFICATIONPART 1 GENERAL REQUIREMENTS

( Second Revision )(Incorporating Amendment Nos. 1 & 2)

UDC 621.314.224

© BIS 2002

B U R E A U O F I N D I A N S T A N D A R D SMANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG

NEW DELHI 110002

Price Group 7

Page 2: Ct is Standard

Instrument Transformers Sectional Committee, ETD 34

FOREWORD

This Indian Standard (Part 1) was adopted by the Bureau of Indian Standards, after the draft finalizedby the Instrument Transformers Sectional Committee had been approved by the ElectrotechnicalDivision Council.

This standard was first published in 1964 and revised in 1981. This revision has been undertaken tobring it in line with the latest developments at the international level.

Indian Standards on current transformers have been published in four parts:Part 1 General requirements,Part 2 Measuring current transformers,Part 3 Protective current transformers, andPart 4 Protective current transformers for special purpose applications.

On the basis of available meterological data concerning the temperature and other conditions prevailingin several parts of the country during different seasons, a reference ambient temperature of 40°C hasbeen specified in this standard.

It is recognized that for current transformers for use in special cases (for example, defence), specialprovisions like environmental testing may be necessary. In such cases additional requirements shouldbe separately specified.

In the preparation of this standard, assistance has been taken from the following:IEC 185 (1987) ‘Current transformers’, published by International Electrotechnical Commission.BS 3938 : 1973 ‘Specification for current transformers’ with latest amendments; published by theBritish Standards Institution.

Guidance regarding application of Current Transformers covered by this standard may be obtainedfrom IS 4201 : 1967 ( under revision ).

This edition 3.2 incorporates Amendment No. 1 (October 1996) and Amendment No. 2 (April 2002). Sidebar indicates modification of the text as the result of incorporation of the amendments.

For the purpose of deciding whether a particular requirement of this standard is complied with, thefinal value, observed or calculated, expressing the result of a test or analysis, shall be rounded off inaccordance with IS 2 : 1960 ‘Rules for rounding off numerical values ( revised )’. The number ofsignificant places retained in the rounded off value should be the same as that of the specified value inthis standard.

Page 3: Ct is Standard

IS 2705 (Part 1) : 1992

1

Indian Standard

CURRENT TRANSFORMERS — SPECIFICATIONPART 1 GENERAL REQUIREMENTS

( Second Revision )1 SCOPEThis Indian Standard (Part 1), specifies thegeneral requirements applicable to currenttransformers for use with electrical measuringinstruments and electrical protective devices atfrequencies from 15 to 100 Hz. This standardbasically applies to current transformers withseparate windings, but where appropriate, it willalso apply to auto-transformer type currenttransformers.

2 REFERENCESIndian Standards given in Annex A are necessaryadjuncts to this standard.

3 TERMINOLOGY3.0 For the purpose of this standard, the followingdefinitions shall apply.

3.1 Instrument Transformer

A transformer intended to supply measuringinstruments, meters, relays and other similarapparatus.

3.2 Current Transformer

An instrument transformer in which thesecondary current, in normal conditions of use, issubstantially proportional to the primary currentand differs in phase from it by an angle which isapproximately zero for an appropriate direction ofthe connections.

3.2.1 Current Transformer ( Wound Type )

A current transformer having a primary windingof more than one full turn wound on the core (s).

3.2.2 Current Transformer ( Bar Type )

A current transformer in which the primarywinding consists of a bar of suitable size andmaterial forming an integral part of the currenttransformer.

3.2.3 Current Transformer ( Dry Type )

A current transformer which does not require theuse of any liquid or semi-liquid material.

3.2.4 Current Transformer ( Liquid Immersed )

A current transformer which requires the use ofoil or other suitable liquid of suitablecharacteristics as insulating and/or coolingmedium.

3.2.5 Hermetically Sealed Current Transformer

A liquid immersed current transformer which issealed and does not communicate withatmospheric air.

3.2.6 Current Transformer ( Ring Type )

A current transformer which has an opening inthe center to accommodate a primary conductorthrough it.

3.2.7 Multi-Core Current Transformers

A current transformer having more than onesecondary core and winding with a commonprimary winding.

3.2.8 Multi-Ratio Current Transformer

A current transformer in which more than oneratio is obtainable by reconnection, or tappings, inprimary or secondary windings.

3.3 Measuring Current Transformer

A current transformer intended to supplyindicating instruments, integrating meters andsimilar apparatus.

3.4 Protective Current Transformer

A current transformer intended to supplyprotective relays and similar apparatus.

3.5 Dual Purpose Current Transformer

A current transformer intended to serve the dualpurposes of measuring and protection.

3.6 Primary Winding

The winding through which flows the current tobe transformed.

3.7 Secondary Winding

The winding which supplies the current circuits ofmeasuring instruments, meters, relays or similarapparatus.

3.8 Secondary Circuit

The external circuit supplied by the secondarywinding of a current transformer.

3.9 Rated Primary Current

The value of the primary current which appearsin the designation of the transformer and onwhich the performance of the current transformeris based.

Page 4: Ct is Standard

IS 2705 (Part 1) : 1992

2

3.10 Rated Secondary Current

The value of the secondary current which appearsin the designation of the transformer and onwhich the performance of the transformer isbased.

3.11 Actual Transformation Ratio

The ratio of the actual primary current to theactual secondary current.

3.12 Rated Transformation Ratio

The ratio of the rated primary current to the ratedsecondary current.

3.13 Current Error (Ratio Error)

The error with a transformer introduces into themeasurement of a current and which arises fromthe fact that the actual transformation ratio is notequal to the rated transformation ratio.

The current error expressed in percent is given bythe formula:

Current error, percent =

where

3.14 Phase Displacement

The difference in phase between the primary andsecondary current vectors, the direction of thevectors being so chosen that the angle is zero for aperfect transformer. The phase displacement issaid to be positive when the secondary currentvector leads the primary current vector. It isusually expressed in minutes.

NOTE — This definition is strictly correct for sinusoidalcurrents only.

3.15 Accuracy Class

A designation assigned to a current transformerthe errors of which remain within specified limitsunder prescribed conditions of use.

3.16 Burden

The impedance of the secondary circuit in ohmsand power factor.

NOTE — The burden is usually expressed as theapparent power in volt-amperes absorbed at a specifiedpower-factor and at the rated secondary current.

3.17 Rated Burden

The value of the burden on which the accuracyrequirements of this specification are based.

3.18 Rated outputThe value of the apparent power (in volt-amperesat a specified power factor) which the currenttransformer is intended to supply to thesecondary circuit at the rated secondary currentand with rated burden connected to it.

3.19 Highest System VoltageThe highest rms line-to-line voltage which can besustained under normal operating conditions atany time and at any point on the system. Itexcludes temporary voltage variations due to faultconditions and the sudden disconnection of largeloads.

3.19.1 Nominal System Voltage

The rms line-to-line voltage by which the systemis designated.

NOTE — The rated voltage of apparatus is notnecessarily the same as the nominal system voltage.

3.19.2 Rated Voltage

The rms value of the voltage used to designate thecurrent transformer for a particular highestsystem voltage.

3.20 Rated Insulation LevelThat combination of voltage values (powerfrequency and lightning impulse, or whereapplicable, lightning and switching impulse)which characterizes the insulation of atransformer with regard to its capability towithstand dielectric stresses.

3.21 Isolated Neutral SystemA system which has no intentional connection toearth except through indicating, measuring orprotective devices of very high impedance.

3.22 Resonant Earthed System (A SystemEarthed Through an Arc-SuppressionCoil) A system earthed through a reactor, the reactancebeing of such value that during a singlephase-to-earth fault, the power-frequencyinductive current passed by this reactorsubstantially neutralizes the power frequencycapacitive component of the earth-fault current.

NOTE — With resonant earthing of a system, thecurrent in the fault is limited to such an extent that anarcing fault in air is self-extinguishing.

3.23 Earth-Fault FactorAt a selected location of a three-phase system(generally the point of installation of anequipment) for a given system layout, the ratio ofthe highest rms phase-to-earth power-frequencyvoltage on a sound phase during a fault to earth(affecting one or more phases at any point) to therms phase-to-phase power-frequency voltagewhich would be obtained at the selected locationwith the fault removed.

NOTES1 This factor is a pure numerical ratio (higher than one)

Ka = rated transformation ratio,

Ip = actual primary current, and

Is = actual secondary current when Ip isflowing under the conditions ofmeasurement.

Ka . Is Ip–( ) 100×Ip

--------------------------------------------------

Page 5: Ct is Standard

IS 2705 (Part 1) : 1992

3

and characterizes in general terms the earthingconditions of a system as viewed from the selectedlocation, independently of the actual operating value ofthe voltage at that location. The earth-fault factor is theproduct of and the factor of earthing which has beenin general use up to now.2 The earth-fault factors are calculated from thephase-sequence impedance components of the system,as viewed from the selected location, using, for anymachines the subtransient reactances.3 The earth-fault factor does not exceed 1.4, if, for allsystem configurations, the zero-sequence reactance andresistance are less then, respectively, three and onetime(s) the positive-sequence reactance.

3.24 Earthed Neutral SystemA system in which the neutral is connected toearth, either solidly or through a resistance orreactance of low enough value to reduce transientoscillations and to give a current sufficient forselective earth fault protection.

3.24.1 Effectively Earthed Neutral System

A three-phase system with effectively earthedneutral at a given location in a systemcharacterized by an earth fault factor at this pointwhich does not exceed 1.4 under all conditions ofoperation.

3.24.2 Non-Effectively Earthed Neutral System

A three-phase system with non-effectively earthedneutral, at a given location, characterized by anearth-fault factor at this point that mayexceed 1.4.

NOTE — This includes resistance earthed systems andresonant earthed systems where earth faults are notallowed to persist for longer than 8 hours in any 24hours or a total of 125 hours per annum. For other caseswhere there is no intentional connection to earth exceptthrough indicating, measuring or protective devices ofvery high impedance or where the duration of earthfault exceeds the period referred above, themanufacturer shall be consulted.

3.25 Electrically Exposed InstallationAn installation in which the apparatus is subjectto overvoltages of atmospheric origin.

NOTE — Such installations are usually connected tooverhead transmission lines, either directly, or througha short length of cable.

3.26 Electrically Non-Exposed InstallationAn installation in which the apparatus is notsubject to overvoltages of atmospheric origin.

NOTE — Such installations are usually connected tocable networks.

3.27 Rated FrequencyThe value of the frequency on which therequirements of this standard are based.

3.28 Rated Short-Time Thermal Current ( Ith )The rms value of the primary current which thecurrent transformer will withstand for a ratedtime, with their secondary winding shortcircuited, without suffering harmful effects.

3.28.1 Rated TimeThe time in seconds for which the currenttransformer shall withstand the rated short-timethermal current in accordance with thespecification.

3.28.2 Rated Short Time Factor ( STF )

That factor which when multiplied by the ratedprimary current gives the rated short-timethermal current.

3.29 Rated Dynamic Current ( Idyn )

The peak value of the primary current which acurrent transformer will withstand, without beingdamaged electrically or mechanically by theresulting electromagnetic forces, the secondarywinding being short circuited.

3.30 Rated Continuous Thermal Current

The value of the current which can be permittedto flow continuously in the primary winding, thesecondary windings being connected to the ratedburdens, without the temperature rise exceedingthe specified values.

3.31 Type Tests

Tests carried out to prove the general qualitiesand design of a given type of current transformerin accordance with the requirements of thisstandard. Tests may be carried out on a prototypewhich may incorporate special arrangements forthe measurements required by this standard.

3.32 Routine TestsTests carried out on each current transformer tocheck requirements likely to vary duringproduction.

3.33 Optional TestsTests, which may be in the nature of type tests orroutine tests, and are carried out only byagreement between manufacturer and purchaser.

4 SERVICE CONDITIONS4.1 Unless otherwise specified, currenttransformers shall be suitable for the followingservice conditions. The manufacturer shall beinformed if the conditions, including theconditions under which Transformers are to betransported, differ from those specified.

4.2 Standard Ambient Conditions

3

a) Maximum ambient airtemperature

Not exceeding45°C

b) Maximum daily averageambient air temperature

Not exceeding35°C

c) Maximum yearly averageambient air temperature

Not exceeding30°C

d) Minimum ambient airtemperature

– 5°C

Page 6: Ct is Standard

IS 2705 (Part 1) : 1992

4

4.2.1 The standard reference ambienttemperature shall be 40°C.

4.2.2 Where the ambient temperature conditionsgiven by the user are substantially different fromthe standard conditions given in 4.2 and if theuser has not specified any reference ambienttemperature, the reference ambient temperaturemay be determined in accordance with IS 9676 :1980.

4.3 Altitude

Up to 1 000 m above mean sea level.

4.4 Atmospheric Conditions

Atmospheres which are not heavily polluted, andatmospheres not conducive to the growth of fungiand condensation of moisture.

4.5 System Earthing

One of the following to be specified:

a) Isolated neutral system ( see 3.21 ),

b) Resonant earthed system ( see 3.22 ),

c) Earthed neutral system ( see 3.24 ),

i) Effectively earthed neutral system ( see3.24.1 ), and

ii) Non-effectively earthed system ( see3.24.2 ).

5 CONSTRUCTION

5.1 The constructional features for liquidimmersed current transformers are given inAnnex B.

5.2 Earthing

5.2.1 The assembly comprising of the chassis,framework and the fixed parts of the metal casingof the current transformer, where used, shall beprovided with two separate earthing terminals.However, for the indoor type current transformersonly one earthing terminal may be provided.These terminals shall be provided over and aboveall other means provided for securing metallicenclosures (armour or other metallic coverings) ofcurrent carrying cables.

5.2.2 The earthing terminals shall be readilyaccessible and so placed that the earth connectionof the current transformer is maintained whenthe cover or any other movable part is removed.

5.2.3 The earthing terminals shall be of adequatesize, protected against corrosion and metallicallyclean. Under no circumstances shall a movablemetal part of the enclosure be insulated from thepart carrying the earthing terminal when themovable part is in place.

5.2.4 The earthing terminal shall be identified bymeans of the sign ‘ ’ marked in a legible andindelible manner on or adjacent to the terminals.

6 RATINGS6.1 Rated FrequencyUnless otherwise specified, the rated frequencyshall be 50 Hz.

NOTE — Current transformers for use on systems offrequency other than 50 Hz shall be considered tocomply with this standard if they conform in all otherrespects with the requirements of this standard at thefrequency for which they are intended.

6.2 Standard Values of Rated Primary Current6.2.1 Single Ratio TransformersThe standard values in amperes of rated primarycurrent are 10, 12.5, 15, 20, 25, 30, 40, 50, 60, 75,and their decimal multiples or fractions. Thepreferred values are those underlined.6.2.2 Multi-Ratio TransformersThe standard values given in 6.2.1 refer to thelowest values of rated current.6.3 Standard Values of Rated Secondary CurrentThe value of the rated secondary current shall be1A and 5A.

NOTE — For transformers intended for delta connectedgroups these ratings divided by are also standardvalues.

6.4 Rated Continuous Thermal CurrentUnless otherwise specified, the rated continuousthermal current shall be the rated primarycurrent.6.5 Rated OutputsThe standard value of rated output up to 30VAare: 2.5, 5.0, 7.5, 10, 15 and 30VA. Values above30VA may be selected to suit the application.

NOTE — For a given transformer, provided one of thevalues of rated output is standard and associated with astandard accuracy class, the declaration of other ratedoutputs, which may be non-standard values, butassociated with other standard accuracy classes, is notprecluded.

6.6 Short-Time Current RatingsCurrent transformers supplied with a fixedprimary winding or conductor shall comply withthe requirements of 6.6.1 and 6.6.2.6.6.1 Thermal RatingA rated short-time thermal current (Ith) or arated short-time factor (STF), for a rated time ofone second (unless a different rated time isspecified), shall be assigned to the currenttransformer.

NOTE — An assigned Ith for a rated time of one secondis related to other values of Ith for different rated times.

6.6.2 Dynamic RatingThe peak value of the rated dynamic current (Idyn)shall normally be 2.5 times the rated short-timethermal current (Ith), unless otherwise specified. 6.7 Rated Insulation Levels6.7.1 The rated insulation levels of current

3

Page 7: Ct is Standard

IS 2705 (Part 1) : 1992

5

transformers having highest system voltagesup to and including 72.5 kV, defined by thepower frequency and the lightning impulsewithstand voltage, shall be one of the sets ofvalues given in Table 1A.

Table 1A Rated Insulation Levels for Highest System Voltages Up to and Including 72.5 kV

( Clauses 6.7.1, 9.3.1, 9.8.1 and 9.9 )

NOTES1 Underlined values are preferred.2 The choice between Lists 1 and 2 should be made byconsidering the degree of exposure to lightning andswitching overvoltages, the type of system neutralearthing and the kind of the overvoltage protection.Some guidance is given in IS 2165 (Part 1) : 1977.

6.7.2 The rated insulation levels of currenttransformers having highest system voltages of123 kV and above, up to and including 245 kV,defined by the power frequency and lightningimpulse withstand voltages, shall be one of thevalues given in Table 1B.

Table 1B Rated Insulation Levels for Highest System Voltages of 123 kV and

Above, Up to and Including 245 kV( Clauses 6.7.2, 9.3.1, 9.8.1 and 9.9 )

NOTE — Underlined values are preferred.

6.7.3 The rated insulation levels of currenttransformers having highest system voltage of420 kV and above, defined by the rated switching

and lightning impulse withstand voltages, shallbe one of the sets of value given in Table 1C.Table 1C Rated Insulation Level for Highest

System Voltage of 420 kV and Above( Clauses 6.7.3, 9.3.1, 9.8.1, 9.9 and 9.11.1 )

6.7.4 The choice of rated insulation level of acurrent transformer shall be made in accordancewith IS 2165 (Part 1):1977 and IS 3716:1978. Ifthereby, the rated insulation level is less than anyof the sets of values in this standard, the lowestvalues therein specified shall apply.

7 REQUIREMENTS7.1 All current transformers shall comply withthe relevant requirements of Parts 2, 3 and 4 ofthis standard. Current transformers for dualpurpose applications shall comply with therequirements of current transformers for bothapplications.7.2 Limits of Temperature-Rise7.2.1 The temperature-rise of a currenttransformer winding when carrying a primarycurrent equal to the rated continuous thermalcurrent, at a rated frequency and with a unitypow er factor burden corresponding to rated outputconnected to the secondary windings, shall notexceed the appropriate values given in Table 2.The temperature-rise of the windings is limited bythe lowest class of insulation either of the windingitself or of the surrounding medium in which it isembedded.

Table 2 Limits of Temperature-Rise of Windings

( Clauses 7.2.1, 7.2.1.1, 7.2.1.2 and 7.2.4 )

NOTE — For some materials (such as epoxy resin) themanufacturer should specify the relevant insulationclass.

NominalSystemVoltage

HighestSystemVoltage

Power Frequency Withstand

Voltage

Lightning Impulse

Withstand Voltage

(1)kV (rms)

(2)kV (rms)

(3)kV (rms)

(4)kV (peak)

List 1 List 2Up to

0.60 0.66 3 — —3.3 3.6 10 20 406.6 7.2 20 40 6011 12.0 28 60 7515 17.5 38 75 9522 24.0 50 95 12533 36.0 70 145 17045 52.0 95 250 25066 72.5 140 325 325

Nom inalSystemVoltage

HighestSystemVoltage

Power Frequency Withstand

Voltage

Lightning Impulse

Withstand Voltage

(1)kV (rms)

(2)kV (rms)

(3)kV (rms)

(4)kV (peak)

110 123 185230

450550

132 145 230275

550650

220 245 360395460

850950

1 050

Nom inalSystemVoltage

HighestSystemVoltage

Lightning Impulse

Withstand Voltage

Switching Impulse

Withstand Voltage

(1)kV (rms)

(2)kV (rms)

(3)kV (peak)

(4)kV (peak)

400 420 1 1751 3001 425

9501 0501 050

525 525 1 4251 550

1 0501 175

765 765 1 8002 1002 400

1 3001 4251 550

Class of Insulation(1)

M aximum Tem perature-Rise(2)(k)

All classes immersed in oil 55All classes immersed in oil

and hermetically sealed60

All classes immersed inbituminous compound

45

C lasses not im m ersed in oilor bitum inous com pound

YAEBFH

40557080

105130

Page 8: Ct is Standard

IS 2705 (Part 1) : 1992

6

7.2.1.1 The values given in Table 2 are based onthe standard reference ambient temperatureconditions given in 4.2.1. For higher referenceambient temperature in accordance with 4.2.2,the permissible temperature rise in Table 2 shallbe reduced by an amount equal to the differencebetween such reference ambient temperatureand 40°C.7.2.1.2 If a transformer is specified for service atan altitude in excess of 1 000 m and tested at analtitude below 1 000 m, the limits of temperature-rise given in Table 2 shall be reduced by thefollowing amounts for each 100 m, the altitude atthe operating site exceeds 1 000 m.

7.2.2 When the transformer is fitted withconservator tank or has any gas above the oil, oris hermetically sealed, temperature-rise of the oilat the top of the tank or housing shall notexceed 50 K.7.2.3 When the transformer is not fitted orarranged as in 7.2.2, the temperature-rise of theoil at the top of the tank or housing shall notexceed 45 K.

7.2.4 The temperature-rise measured on theexternal surface of the core and other metallicparts in contact with, or adjacent to, insulation (ifaccessible) shall not exceed the appropriate valuein Table 2.

7.3 Dielectric Tests

7.3.1 The current transformer shall withstand thespecified dielectric tests corresponding to therated insulation level specified.

8 MARKING

8.1 Rating PlateAll current transformers shall carry at least thefollowing markings:

a) The manufacturer’s name and country oforigin;

b) Year of manufacture;c) A serial number and a type designation;d) The rated primary and secondary currents

(for example, 200-100/1-1A);e) Rated frequency; andf) Rated output and the corresponding accuracy

class (for example, 10 VA, class 1 or10 VA/1);NOTE — When more than one separate secondarywindings are provided, the marking should indicatethe output of each secondary winding in VA, thecorresponding accuracy class and the rated currentof each winding.

g) Highest system voltage (for example,72.5 kV);

h) Rated insulation level (for example,140/325 kV);

NOTE — The items (g) and (h) may be combined intoone marking (for example, 72.5/140/325 kV).

j) Rated short-time thermal current or short-time factor with rated time (if different from1 second) (for example 13.1kA/0.5 orSTF 100/0.5);

k) Rated dynamic current if different than 2.5times the rated short-time thermal current;and

m) Reference to this standard.

8.1.1 All information shall be marked in anindelible manner on the current transformer itselfor on a rating plate securely attached to thetransformer.

8.1.2 The following shall be marked if required byagreement between the purchaser and themanufacturer:

a) Class of insulation, andb) The use of secondary winding(s) and the

corresponding terminals.NOTE — If several classes of insulating material areused, the one which limits the temperature-rise ofthe windings shall be indicated.

8.2 Terminal Markings

The terminal markings shall be in accordancewith Annex C.

8.3 The current transformers may also be markedwith BIS Standard Mark.

9 TESTS

9.1 Classification of Tests

9.1.1 Type Tests

The following shall constitute the type tests:a) Short-time current tests ( see 9.6 ).b) Temperature-rise test ( see 9.7 ).c) Lightning impulse test for current

transformers for service in electricallyexposed installation ( see 9.8 ).

d) Switching impulse voltage tests for currenttransformers of 420 kV and above( see 9.11 ).

e) High voltage power-frequency wet withstandvoltage tests on outdoor currenttransformers up to and including 245 kV( see 9.9 ).NOTE — If the porcelain weather casing/bushinghas been subjected to this test separately, therequirements of this test shall be deemed to havebeen complied with.

f) Determination of errors or other characteris-tics according to the requirements of theappropriate designation or accuracy class( see individual parts of this standard ).

NOTES

1 The dielectric type tests in (c), (d) and (e) shall all becarried out on the same transformer unless otherwiseagreed.

a) Oil-immersed transformers — 0.4 percent, and

b) Dry-type transformers — 0.5 percent.

Page 9: Ct is Standard

IS 2705 (Part 1) : 1992

7

2 After the current transformers have been subjected tothe dielectric type tests (c), (d) and (e) they shall besubjected to all the routine tests.3 Type tests may be omitted when the manufacturerholds a certificate of type tests made on a similartransformer which is acceptable to the purchaser.

9.1.2 Routine Tests

The following shall constitute the routine tests:a) Verification of terminal marking and

polarity ( see 9.2 ).b) Power frequency dry withstand tests on

primary windings ( see 9.3 ).c) Power frequency dry withstand tests on

secondary windings ( see 9.4 ).d) Over-voltage inter-turn test ( see 9.5 ),e) Partial discharge tests in accordance with

IS 11322 : 1985.NOTE — This test is applicable only for currenttransformers with solid insulation for highest systemvoltages 7.2 kV and above and current transformerswith liquid immersed insulation for highest systemvoltages of 72.5 kV and above.

f) Determination of errors or other characteris-tics according to the requirements of theappropriate designation or accuracy class( see individual parts of this standard ).

NOTES1 The determination of errors or other characteristics in(e) shall be carried out after the tests (b), (c) and (d). Theorder or possible combination of other tests is notstandardized.2 Repeated power frequency tests on the primarywindings shall be performed at 80 percent of thespecified test voltage, except when the method of 9.3.2.2is used.

9.1.3 Optional Tests

The following tests where applicable, shall becarried out by mutual agreement between thepurchaser and the manufacturer:

a) Chopped lightning impulse test as a typetest ( see 9.10 ).

b) M easurem ent of dielectric dissipation factorfor oil immersed current transformers of72.5 kV and above ( see 9.12 ).

c) Commissioning tests on new current trans-formers up to and including 36 kV( see 9.13 ).

9.2 Verification of Terminal Markings and PolarityTerminal markings and polarity shall be verifiedfor their compliance with 8.2.

9.3 High Voltage power Frequency Test on Primary Windings9.3.1 Current Transformers Having HighestSystem Voltage up to and Including 245 kVThe test shall be conducted in accordance withIS 2071 (Part 1):1974 and IS 2071 (Part 2):1974.The value of the test voltage shall be theappropriate power frequency test voltage specified

in Tables 1A or 1B. The test voltage shall beapplied between the terminals of the primarywindings (connected together) and earth. Theframe, case (if any), core (if accessible and ifintended to be earthed) and all the terminals ofthe secondary windings shall be connectedtogether and earthed. The test voltage shall beapplied for one minute. There shall be nodisruptive discharge.9.3.2 Current Transformers Having HighestSystem Voltage of 420 kV and AboveThe test shall be carried out by either of twomethods given in 9.3.2.1 and 9.3.2.2, at thediscretion of the manufacturer, unless otherwiseagreed.9.3.2.1 Method 1The test shall be carried out in accordance withthe procedure set out in 9.3.1 except that thevalue of the test voltage shall be the appropriatevalue given in Table 3A.

Table 3A Power-Frequency Withstand Voltages for Transformer Windings with

Highest System Voltage of 420 kV and Above

9.3.2.2 Method 2The current transformer shall be subjected to theappropriate specified power-frequency prestressvoltage given in Table 3B for 10 seconds. Thevoltage shall then be reduced to the correspondingspecified partial discharge test voltage given inTable 3B without interruption and this voltageshall be maintained for 15 minutes. Themaximum permissible partial dischargemagnitude measured during the last minute atthe specified partial discharge test voltage shallbe 10 pC.

NOTE — The method in 9.3.2.2 may be preceded by alightning impulse test in order to complete the dielectricroutine tests of the primary windings.

Table 3B Power-Frequency Test Voltages for Transformer Windings having Highest

System Voltage of 420 kV and Above

Rated Lightning-Impulse Withstand

Voltage

Power-Frequency Short- Duration

Withstand VoltagekV (peak) kV (rms)

1 1751 3001 4251 5501 8002 1002 400

510570630680790880975

HighestSystemVoltage

Power-Frequency PrestressVoltage

PartialDischarge

Test VoltagekV (rms) kV (rms) kV (rms)

420 510 315525 630 395765 790/880* 575

* To be determined by the rated lightning impulsewithstand voltage.

Page 10: Ct is Standard

IS 2705 (Part 1) : 1992

8

9.3.3 For all current transformers, where theprimary winding is divided into two or moresections, each section shall withstand for oneminute a test voltage of 3 kV (rms) appliedbetween the section and earth. All other sections,windings, frame, and case (if any) shall have beenconnected together and earthed.9.3.4 If for any reason, it is considered necessaryto repeat the test, the test voltage shall bereduced to 80 percent of the prescribed testvoltage.9.4 High Voltage Power Frequency Test on Secondary WindingsThe test shall be conducted in accordance withIS 2071 (Part 1) : 1974. The test voltage of 3 kV(rms) shall be applied for one minute between theterminals of the secondary windings (connectedtogether) and earth. The frame, case (if any), core(if accessible and if intended to be earthed) and allterminals of the primary winding shall have beenconnected together and earthed. There shall be nodisruptive discharge.9.4.1 When there are more than one secondarywindings or sections, each winding or section shallwithstand, without disruptive discharge, a testvoltage of 3 kV (rms) applied between thatwinding or section and all other windings orsections connected together and earthed.9.5 Over-Voltage Inter-Turn TestAt the discretion of the manufacturer, the testmay be carried out by any of the methods givenin 9.5.1 and 9.5.2.9.5.1 With the secondary winding open-circuited,a voltage at power frequency shall be applied tothe primary winding. The value of the voltageshall be such as to produce a primary current ofrms value equal to the rated primary current (inthe case of a current transformer with anextended range, a current equal to the extendedrange primary current) or a value whichcorresponds to a secondary voltage of 4.5 kV peak,whichever is lower. The applied voltage shall bewithstood satisfactorily for one minute.9.5.2 With the primary winding open-circuited avoltage at a frequency not greater than five timesthe rated frequency shall be applied to thesecondary winding. The value of the voltage shallbe such as to produce a secondary current of rmsvalue equal to the rated secondary current (in thecase of a current transformer with an extendedrange, a current equal to the extended rangesecondary current) or a value of 4.5 kV peak,whichever is lower. The applied voltage shall bewithstood satisfactorily for one minute.

NOTE — The overvoltage inter-turn test is not intendedto reproduce service condition with the secondarywindings open-circuited, but only to indicate that theinter-turn insulation is sound. Open-circuiting ofsecondary winding/circuit under service conditions(particularly, if the secondary winding has a largenumber of turns) may produce excessive heating andpermanent magnetization in the core and dangerousdielectric stress on the insulation, which maypermanently damage the Current Transformer. Thiscondition is, therefore, to be avoided.

9.6 Short Time Current Tests9.6.1 Short Time Thermal Current TestThe transformer shall initially be at atemperature between 17°C and 40°C. The testshall be carried out with the secondary windingshort-circuited and at a current ‘I’ for a time ‘t’such that I2 t > = I2

th . tr where ‘tr’ is the ratedtime; provided ‘t’ has a value between 0.5 and 5seconds.

NOTE — Experience has shown that this requirementis complied with in the case of current transformerswith Class A insulation provided that the currentdensity in the windings, corresponding to the ratedshort-time current, does not exceed 180 A/mm2 for arated time of one second, where the winding is of copperof conductivity not less than 97 percent of the valuegiven in IS 613:1984. For other rated times, thecorresponding current density is obtainable from theformula I2

d, tr = 32 400, where ‘Id’ is the correspondingcurrent density at rated time ‘tr’. Consequently,compliance with this requirement may take the place oftests.

9.6.2 Dynamic Current TestThe test shall be carried out with the secondarywinding(s) short-circuited and with a primarycurrent, the peak value of which is not less thanthe rated dynamic current ( Idyn ) for at least onepeak.The dynamic current test may, at the discretion ofthe manufacturer, be combined with the thermalcurrent test, provided the first major peak of thetest current is not less than the rated dynamiccurrent ( Idyn ).

NOTES1 For dynamic current test, this requirement shall havebeen complied with if a current transformer having aproduct of primary turns and rated dynamic currentsame or less than that of a current transformers ofsimilar construction has passed this test. The primarycurrent rating, number of cores, its burdens andaccuracy class shall not be considered significant forthis test.2 If agreed between the manufacturer and thepurchaser, the short-time thermal current test anddynamic current tests may be carried out with aspecified value of connected burden.

9.6.3 The current transformer shall have passedthe short-time current tests if, after cooling toambient temperature, it satisfies the followingconditions:

a) It is not visibly damaged;b) In the case of measuring and protective

current transformers or measuring andprotective cores of multi-core currenttransformers, the errors at rated burden atthe connections at which the short-timecurrent tests were carried out do not differfrom those recorded before the tests by morethan half the limits of its accuracy class;In the case of current transformer or cores ofmulti-core current transformers conformingto Part 4 of this standard, the excitingcurrent at the rated minimum knee-pointvoltage and the turns ratio error at theconnections at which the short-time currenttests were carried out do not differ fromthose recorded before the tests by more thanhalf the permissible limits.

Page 11: Ct is Standard

IS 2705 (Part 1) : 1992

9

NOTE — All measurements after the short-timecurrent tests shall be necessarily carried out onlyafter the cores have been demagnetized.

c) It withstands the dielectric tests specifiedin 9.3, 9.4 and 9.5 with the test voltages orcurrent reduced to 90 percent of those given;

d) Subject to the Note below, on examination,the insulation next to the surface of theconductor does not show significantdeterioration (for example carbonization).NOTE — Examination (d) is not necessary providedthe current density in winding, corresponding to therated short-time thermal current for one second, doesnot exceed 160 A/mm2 where the winding is of copperof conductivity not less than 97 percent of IACS or105 A/mm2 where the winding is of aluminium ofconductivity not less than 55 percent of IACS. Thecorresponding current densities for other rated timesmay be obtained by the formulae:‘I2

d, tr’ is 25 600 for copper windings and 11 025 foraluminium windings, where ‘Id’ is the requiredcurrent density at rated time ‘tr’.

9.7 Temperature-Rise Test

The current transformer shall be tested forcompliance with 7.2. The transformer shall bemounted in the manner representative of themounting in service. It shall be deemed to haveattained a steady temperature when the rate ofrise of temperature does not exceed 1 K per hour.The ambient temperature shall not exceed 40°C.The temperature-rise of the windings shall, wherepracticable be measured by the increase inresistance method, but for windings of very lowresistance, thermometer or thermocouples may beemployed. The temperature-rise of parts otherthan windings, shall be measured bythermometers or thermocouples. For methods oftemperature measurements ( see Annex D ).

9.8 Lightning Impulse Voltage Test forCurrent Transformers for Service inElectrically Exposed Installations

9.8.1 Current transformers for service inelectrically exposed installations shall withstandthe appropriate full wave lightning impulsevoltage specified in Tables 1A, 1B and 1Caccording to the highest system voltage and thespecified insulation level.9.8.2 The test shall be conducted in accordancewith IS 2071 (Part 1) : 1974 and IS 2071 (Part 2) :1974. The test voltage shall be applied betweenthe terminals of the primary winding (connectedtogether) and earth. The frame, case (if any), core(if intended to be earthed) and all the terminals ofthe secondary winding shall be connected togetherand earthed. The test voltage shall have theappropriate values specified in Tables 1A, 1B or1C according to the highest system voltage andthe rated insulation level. The reference impulsevoltage shall be between 50 percent and 75percent of the rated impulse withstand voltage.The peak value and the waveshape of the impulsevoltages shall be recorded.9.8.2.1 For indoor current transformers up to andincluding 36 kV, five consecutive full wave

impulses of each polarity with correction foratmospheric conditions shall be applied.For Current Transformers up to and including245 kV, fifteen consecutive full wave lightningimpulses of each polarity without correction foratmospheric conditions shall be applied. If othertests to check the external insulation (forexample, separate lightning impulse test on theporcelain weather casing/bushing of oil immersedcurrent transformers) have been carried out, thenumber of lightning impulses should be reducedto three of each polarity without correction foratmospheric conditions.9.8.2.2 The current transformer shall have passedthe test if:

a) no disruptive discharges occur in thenon-self-restoring insulation;

b) no flashovers occur along the non-self-restoring external insulation;

c) no more than two flashovers occur across theself-restoring external insulation (onlywhere 15 impulses of each polarity areapplied); and

d) no other evidence of failure is detected.9.8.3 For Current Transformers of 420 kV, threeconsecutive impulses of each polarity withoutcorrection for atmospheric conditions shall beapplied.9.8.3.1 The current transformer shall have passedthe test if the conditions of 9.8.2.2 have beensatisfied.

9.9 High Voltage Power Frequency WetWithstand Voltage Tests on OutdoorCurrent TransformersThe external insulation of outdoor currenttransformers shall be subjected for one minute toa power frequency voltage having a peak valueequal to times the value specified in Tables1A, or 1B corrected for atmospheric conditionsappropriate to the highest system voltage and therated insulation level. The test shall be conductedin accordance with IS 2071 (Part 1):1974 andIS 2071 (Part 2):1974. This test is applicable onlyfor outdoor current transformers up to andincluding 245 kV highest system voltage.9.10 Chopped Lightning Impulse Test onPrimary Winding9.10.1 The chopped lightning impulse test shallbe carried out with the negative polarity only andshall be combined with the negative polarity fullwave lightning impulse test in the followingmanner:

a) For highest system voltages up to andincluding 245 kV where it is considerednecessary to test for external insulation:— one 100 percent full impulse,— two 100 percent chopped impulses, and— fourteen 100 percent full impulses.

b) For highest system voltages up to 245 kVwhere external insulation need not be

2

Page 12: Ct is Standard

IS 2705 (Part 1) : 1992

10

checked by 15 full wave impulses and forhighest system voltage of 420 kV and above:

— one 100 percent full impulse,— two 100 percent chopped impulses, and— two 100 percent full impulses.

9.10.2 The standard lightning impulse shall bechopped after 2 to 5 micro seconds and thechopping circuits shall be so arranged that theamount of overswing to the positive polarity islimited to 30 percent of the chopped impulse.

9.10.3 Significant changes in wave shape of fullwave application before and after the applicationof the chopped impulses are indicative of internalfault.

9.10.4 Flashovers during chopped impulses alongself-restoring external insulation should bedisregarded during this test.

9.11 Switching Impulse Test on CurrentTransformers Having Highest SystemVoltage of 420 kV and Above

9.11.1 The test shall be carried out in accordancewith IS 2071 (Part 2):1974. The test voltage shallhave the appropriate value in Table 1C accordingto the specified rated insulation level.

9.11.2 The switching impulse test voltage shall beapplied between the terminals of the primarywinding (connected together) and earth. Theframe, case (if any), core (if intended to beearthed) and all terminals of the secondarywindings shall be connected together and earthed.

9.11.3 Fifteen consecutive impulses of bothpositive and negative polarity, corrected foratmospheric conditions, shall be applied. Outdoortype transformers shall be subjected only to wettests. Dry test is not required.

9.11.4 The transformer shall have passed the testif the conditions given in 9.8.2.2 have beensatisfied.

9.12 Measurement of DielectricDissipation Factor for Liquid ImmersedCurrent Transformers of 72.5 kV andAbove

The measurement of dielectric dissipation factor(tan δ) shall be made after the power frequencytest on the primary windings. The ambienttemperature and the temperature of theequipment under test shall be between 10°C and40°C. The measurement of tan shall be made bymeans of a Schering Bridge or other equivalentmethod.

The test voltage, which shall be agreed betweenthe manufacturer and the purchaser but in nocase exceeding the highest system voltage dividedby , shall be applied to the primary terminalsconnected together. The secondary terminals, anyscreen and isolated metal casing shall beconnected to the measuring bridge. If thetransformer has a special device (terminal)suitable for the measurement, the other terminalsshall be short-circuited and connected to theearthed or the screened metal casing. The valuemeasured shall not exceed the value agreedbetween the manufacturer and the purchaser.

NOTE — The dielectric dissipation factor is dependenton both voltage and temperature. Measurements of thedielectric dissipation factor at low voltage (for example2.5 kV or 10 kV) may be used as a reference inmonitoring the condition of insulation in service.

9.13 Commissioning Tests on New Transformers9.13.1 Power-Frequency Test on PrimaryWindings

By agreement between the manufacturer and thepurchaser, separate source power frequency testson the primary winding insulation may be madeafter erection on site provided that thetransformer is in a satisfactory conditions fortesting and has not been in service. Thetransformers shall be temporarily disconnectedfrom any other apparatus to which it may beconnected. The one minute test voltage shall 80percent of specified power frequency test voltage.

9.13.1.1 If for any special reasons the duration ofthe test exceeds one minute, the relationshipbetween duration of the test and the percentage ofthe one-minute test voltage shall be as given inTable 4.

NOTE — Commissioning test on current transformesfor highest system voltage over 36 kV are deprecated.

Table 4 Applied Power-Frequency High Voltage Tests for Duration Exceeding One

Minute (After Erection on Site)

10 INFORMATION TO BE GIVEN WITHENQUIRY AND ORDER10.1 The particulars given in Annex E shall befurnished by the purchaser with each enquiry andorder.

Duration of Test

(1)minutes

Percentage of One-MinuteTest Voltage

(2)

2345

1015

83.575.070.066.660.057.7

3

Page 13: Ct is Standard

IS 2705 (Part 1) : 1992

11

ANNEX A( Clause 2 )

LIST OF REFERRED INDIAN STANDARDS

ANNEX B( Clause 5.1 )

CONSTRUCTIONAL FEATURES OF LIQUID IMMERSED CURRENT TRANSFORMERS

B-1 PORCELAIN INSULATORS

B-1.1 The hollow porcelain insulator or housingwhere provided, shall conform to IS 5621:1980.

B-1.2 Where demountable bushings are provided,these shall conform to IS 2099:1986.

B-1.3 For outdoor current transformers for use inpolluted atmospheres, the minimum creepagedistance measured on the insulation surface andthe maximum creepage factor shall be as givenbelow:

NOTES1 Unless otherwise agreed between the manufacturerand the purchaser the Pollution Level shall be deemedto be normal.2 The creepage factor equals l/S where l is the totalcreepage distance of the insulator, and S is the arcingdistance, which is the shortest distance in air outsidethe insulator, not considering arcing horns, between themetallic parts to which the voltage is normally applied.3 If an insulator has a profile with a creepage factorhigher than the limits indicated, the insulator profilemay be used if experience in operation, or laboratorytest reproducing operation conditions, permits theassumption of good performance. An insulator orbushing, the dimensions of which have beenstandardized by any Indian Standard shall also beconsidered to meet this criteria.4 Protected creepage distance shall not be specified as aparameter characterizing a shed profile.

B-2 OILB-2.1 Unless otherwise agreed, the oil used inliquid immersed current transformers shallconform to IS 335:1983.

IS No. Title

335 : 1983 New insulating oils

613 : 1984 Copper rods and bars forelectrical purposes

2053 : 1974 Thermocouple pyrometers

2071 (Part 1) : 1974

Methods of high voltage testing:Part 1 General definitions andtest requirements

2071 (Part 2) : 1974

Methods of high voltage testing:Part 2 Test procedures

2099 : 1986 Bushings for alternating voltagesabove 1 000 V

2147 : 1962 Degree of protection provided byenclosures for low voltageswitchgear and controlgear

2165 (Part 1) : 1977

Insulation coordination: Part 1Phase to earth insulationcoordination

IS No. Title

3716 : 1978 Application guide for insulationcoordination

4201 : 1983 Application guide for currenttransformers

5621 : 1980 Hollow insulators for use inelectrical equipment

9676 : 1980 Reference ambient temperature forelectrical equipment

10601 : 1983 Dimensions of terminals for highvoltage switchgear and controlgear

11322 : 1985 Method for partial dischargemeasurement in instrumenttransformers

12360 : 1988 Voltage bands for electricalinstallations including preferredvoltages and frequency

Pollution Level

Minimum Nominal Specific Creepage

Distance Between Phase and Earth ( mm/kV of

Highest System Voltage )

Maximum Creepage Factor

Light 16 3.5

Normal 20 3.5

Heavy 25 4.0

Very Heavy 31 4.0

Page 14: Ct is Standard

IS 2705 (Part 1) : 1992

12

B-2.2 The current transformer shall be soconstructed as to ensure that the oil does not flowout or leak out even when the current transformeris used continuously at the maximum allowabletemperature.

B-3 PRIMARY TERMINALSB-3.1 It is suggested (without being mandatory)that the primary terminals of currenttransformers to which the line connections are tobe made shall have the dimensions given inIS 10601:1983.

B-4 SECONDARY TERMINALSB-4.1 The secondary terminals of outdoor current

transformers shall be brought out in a suitablecompartment which shall have a removable cover.The terminal box, with the cover closed andtightened and the cable/conduit in position whensupplied shall have a degree of protectionconforming to IP 54 of IS 2147 : 1962, unlessotherwise agreed.

B-5 Unless otherwise agreed, the externalsurfaces of the steel tanks or casing of currenttransformers shall be painted with one coat ofprimer and two coats of synthetic enamel paint.The internal surfaces of the steel tanks or casingshall be painted with two coats of a suitableoil-insoluble paint.

ANNEX C( Clause 8.2 )

TERMINAL MARKING

C-1 GENERALC-1.1 The terminal marking shall identify:

a) the primary and secondary windings;b) the winding sections, if any;c) the relative polarities of windings and

winding sections; andd) the intermediate tappings, if any.

C-2 METHOD OF MARKINGC-2.1 The terminals shall be marked clearly and

indelibly either on their surface or in theirimmediate vicinity.

C-2.2 The marking shall consist of lettersfollowed, or preceded, where necessary, bynumbers. The letters shall be in block capitals.

C-2.3 The marking of current transformers shallbe as indicated in Fig. 1 to 4.

C-2.4 All the terminals marked P1, S1 and C1shall have the same polarity at any instant.

FIG. 1 SINGLE RATIO TRANSFORMER

FIG. 2 TRANSFORMER WITH AN INTERMEDIATE TAPPING ON SECONDARY WINDING

FIG. 3 TRANSFORMER WITH PRIMARY WINDING IN TWO SECTIONS INTENDED FOR CONNECTION

EITHER IN SERIES OR PARALLEL

FIG. 4 TRANSFORMER WITH TWO SECONDARY WINDINGS

Page 15: Ct is Standard

IS 2705 (Part 1) : 1992

13

ANNEX D( Clause 9.7 )

METHODS OF TEMPERATURE MEASUREMENT

D-1 SELF RESISTANCE METHODD-1.1 In the self-resistance method, thetemperature-rise of winding is determined by theincrease in the resistance of the conductor itself.

D-1.1.1 The temperature of the winding and theoil or other medium surrounding the windingmeasured before beginning the test should notdiffer. The initial resistance and the initialtemperature of the winding should be measuredunder steady temperature conditions, at the sametime.

D-1.1.2 Since the resistance of copper over arange of temperature varies in direct proportionto the temperature as measured from minus234.5°C, the ratio of the hot temperature ( T2 ) tothe cold temperature ( T1 ) may be calculated fromthe ratio of the hot resistance ( R2 ) to the coldresistance ( R1 ) as follows:

or

D-1.1.3 The temperature-rise is the differencebetween the calculated temperature T2 and thatof the surrounding air at the conclusion of thetest.

D-1.2 The method of testing by increase inresistance is applicable at the ambienttemperature of the test room to all windingshaving a resistance of not less than 0.01 ohm. Forwindings having a resistance of less than 0.01ohm, the surface temperature should be taken bythermometer or thermocouple.

D-2 THERMOMETER METHODD-2.1 Three types of thermometers may beemployed, namely bulb thermometers containingmercury or alcohol and resistance thermometers.

D-2.2 When bulb thermometers are used in placeswhere there is any varying or moving magneticfield, those containing alcohol should be used in

preference to those containing mercury in whicheddy currents may produce sufficient heat to yieldmisleading results.

D-2.3 When a thermometer is used to measurethe temperature of a surface such as that of awinding, the bulb shall be surrounded by a singlewrapping of tin foil having a thickness of not lessthan 0.025 mm. The tin foil shall form a completecovering for the bulb, which shall then be securedin contact with the surface under test. Theexposed part of the wrapped bulb shall becompletely covered with a pad of heat-insulatingmaterial, without unduly shielding the testsurface from normal cooling.

D-3 THERMOCOUPLE METHODD-3.1 The two conductors between which thethermo-electric effect is produced shall be weldedat both the hot and cold junction ( see IS 2053 :1974 ).

D-3.2 When applied to the surface thetemperature of which is to be measured, the hotjunction shall be covered with insulation andwrapped with tin foil as described for bulbthermometers. The thermocouple circuits shall beearthed to minimize the possibility of capacitancecurrents.

D-3.3 The protecting pad of heat insulatingmaterial specified in D-3.2 shall be employedwhether the junction is insulated or not.

D-3.4 The cold junction shall be maintained at asteady temperature. When an oil bath is used, theoil should preferably be contained in a vacuumflask or be thermostatically controlled, and the oiltemperature shall be measured by means of athermometer.

D-4 MEASUREMENT OF AMBIENT TEMPERATURED-4.1 The temperature of the surrounding airshall be measured by means of at least twothermometers, so placed as to take account of themaximum and minimum temperatures, and themean reading shall be adopted.

R2

R1-------

T2 234.5+T1 234.5+----------------------------=

T2 R2R1------- T1 234.5+( ) 234.5–=

Page 16: Ct is Standard

IS 2705 (Part 1) : 1992

14

ANNEX E( Clause 10.1 )

INFORMATION TO BE GIVEN WITH ENQUIRY AND ORDER

At the time of enquiry and order, the followinginformation may be given:

a) Type of current transformer, type of supplyand earthing conditions

(for example indoor/outdoor, ring type/castresin/oil immersed, etc)

b) Highest system voltage, type of supply andearthing conditions

(for example 7.2 kV, 3-phase, effectivelyearthed)

c) Rated insulation level

(for example 230/550 kV)

d) Rated short-time thermal current (and itsduration if different from 1 second)( e.g. 13.1 kA/0.5 s )

e) Frequency, if other than 50 Hz.

f) Rated transformation ratio

(for example 200/1 for a single ratio currenttransformer or 200-100/1-1 for a multi-ratio,multi-core current transformer)

g) Rated output and corresponding accuracyclass for measuring or protective currenttransformers(for example 15 VA/0.5 for a measuringcurrent transformer or 15 VA/5P10 for aprotective current transformer.

h) Rated knee-point voltage and limitations ofexciting current for Class PS currenttransformers(for example Vk not less than 40(RCT + 19)and exciting current at 0.25 Vk not morethan 30 mA)

j) Service conditions including, for example,whether the current transformers are foruse indoors or outdoors, whether for use atunusually low temperature, altitudes (if over1 000 metres), humidity, and any specialconditions likely to exist or arise, such asexposure to steam or vapour, fumes,explosive gases, vibrations, excessive dust,etc.

k) Special features, such as limitingdimensions.

Page 17: Ct is Standard

Bureau of Indian Standards

BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promoteharmonious development of the activities of standardization, marking and quality certification of goods andattending to connected matters in the country.

Copyright

BIS has the copyright of all its publications. No part of these publications may be reproduced in any formwithout the prior permission in writing of BIS. This does not preclude the free use, in the course ofimplementing the standard, of necessary details, such as symbols and sizes, type or grade designations.Enquiries relating to copyright be addressed to the Director (Publications), BIS.

Review of Indian Standards

Amendments are issued to standards as the need arises on the basis of comments. Standards are alsoreviewed periodically; a standard along with amendments is reaffirmed when such review indicates that nochanges are needed; if the review indicates that changes are needed, it is taken up for revision. Users ofIndian Standards should ascertain that they are in possession of the latest amendments or edition byreferring to the latest issue of ‘BIS Catalogue’ and ‘Standards : Monthly Additions’.

This Indian Standard has been developed from Doc : No. ETD 34 (3387).

Amendments Issued Since Publication

Amend No. Date of Issue

Amd. No. 1 October 1996

Amd. No. 2 April 2002

BUREAU OF INDIAN STANDARDS

Headquarters:

Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002.Telephones: 323 01 31, 323 33 75, 323 94 02

Telegrams: Manaksanstha(Common to all offices)

Regional Offices: Telephone

Central : Manak Bhavan, 9 Bahadur Shah Zafar MargNEW DELHI 110002

323 76 17323 38 41

Eastern : 1/14 C. I. T. Scheme VII M, V. I. P. Road, KankurgachiKOLKATA 700054

337 84 99, 337 85 61337 86 26, 337 91 20

Northern : SCO 335-336, Sector 34-A, CHANDIGARH 160022 60 38 4360 20 25

Southern : C. I. T. Campus, IV Cross Road, CHENNAI 600113 235 02 16, 235 04 42235 15 19, 235 23 15

Western : Manakalaya, E9 MIDC, Marol, Andheri (East)MUMBAI 400093

832 92 95, 832 78 58832 78 91, 832 78 92

Branches : AHMED ABAD . BANG ALOR E. BHO PAL. BH UBANE SH WAR . C OI MB ATOR E. FARI DA BAD. G HAZI ABA D. GUWAH ATI . H YDER ABAD . JAI PUR . K ANPUR . LUCKNOW. NAGPUR. NALAGARH. PATNA. PUNE. RAJKOT. THIRUVANANTHAPURAM.VISHAKHAPATNAM.