CT Problems & Testing Techniques
Peter Fong
OMICRON electronics Corp. USA
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 2/23
Content
1. Differences Between Protection and Metering CT‘s
2. What to Test?
.
4. New Methods Available
© OMICRON 9 November 2009 Page 2
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 3/23
Protection CT
• Need to operate at high fault current with acceptableaccuracy
• Must have high excitation voltage to avoid saturation
• Multiple ratios• Transient characteristic is important
• Testing mainly concerned with saturation level
•
© OMICRON Page 3
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 4/23
Metering CT
• Must be accurate over a range of current
• Must be accurate over a ran e of burden
• Operate in range of load current
• Desirable to saturate early to protect the meter• Testing mainly concerned with accuracy
• Burden is important
© OMICRON Page 4
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 5/23
Protection CT Classes
C x00
C Rating: Less than 10% Relay Current Error at
20x Rated Current (5x20A = 100A) into 1, 2, 4, or
x00: The terminal voltage which the CT must
ma nta n w t n t e at ng , , ,C800)
© OMICRON Page 5
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 6/23
Determining C-Rating
1. Find Vexc where Iexc = 10A2. Calculate Vterm = Vexc – 100A*Rct3. Round Vterm down to nearest 100,
, , correspon ng oC100, C200, C400, C800
E.g. For Rct = 0.9Ω:
exc = a exc =Vterm = 400V – 100V (0.9) = 310V
C200 Rating
© OMICRON Page 6
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 7/23
Will the CT Saturate?
Apply Anticipated Fault Current and determine if the voltageimpressed on the CT will be greater than the CT rating:
E.g. For maximum Fault current of 24,000A into a 1200/5 C200 CT
w secon ary ur en an sa e y marg n o :Isec = (24,000 * 5)/1200 = 100A310V > 2x 100A * 1 = 200VCT is o.k. √
© OMICRON Page 7
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 8/23
What could go wrong?
,
Vterm = 200V – 100V (0.9) = 110V
Isec = (24,000 *5)/600 = 200A
110V > 2x 200A *1 = 400V->> not o. .
* Be careful about using a lowerta . The combination of a lower
kneepoint and higher secondarycurrent could significantly bringdown the saturation level of the CT
© OMICRON Page 8
or e same app ca on.
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 9/23
What else could go wrong?
• Impedance is too high due to long lead lengths
• Poor quality (i.e. low burden rating) CTs are used due to cost orspace constraints
• Small loads are put on powerful buses, and CT ratios areselected based on load current rather than fault duty
• Low ratio zero sequence CTs are placed on systems havinghigh ground fault duty
• Unusual burdens (e.g. stablizing resistors) are placed in the CTcircuit
© OMICRON Page 9
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 10/23
Metering CT Classes
0.3 0.1B
Metering Class CT
Accuracy in % (e.g. 0.3%)when 100% primarycurrent is applied.
Maximum Burden (e.g. 0.1Ω )
primary current is applied
(e.g. 0.6%)
© OMICRON Page 10
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 11/23
Rating Factor (RF)
Multiples of Rated Current which the CT canmaintain accuracy
yp ca : 1, 1.5, 2, 3, 4
E. . 200/5A CT with RF 2 means the CT willmaintain it’s accuracy certification up to 400A
© OMICRON Page 11
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 12/23
Secondary Burden
• CT accuracy is rated up to it’s maximum burdenrating
• ver- ur en ng w ten to pro uce error n avor othe customer
• -
– loose connections
– corrosion
– ro en stran e w res• Need to have excess burden capacity during
installation
© OMICRON Page 12
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 13/23
Failue Mode Test Technique Possible Cause
for Fai lure Mode of Failure Mode
Wiring Problems
TABLE. CT System Failure Modes
1 Cross Phasing of a CT Wire Verification Installation Error
2 Cross Phasing of a CT/PT Wire Verification Installation Error
3 X1X2/H1H2 Reversal of a CT Wire Verification Installation Error
4 X1X2/H1H2 Reversal of a PT Wire Verification Installation Error
5 Meter Socket Wire Error Wire Verification Installation Error
6 Loose Connections Burden Test Vibration/Wind/Installation Error
7 Corroded Connections/Terminals Burden Test Moisture
8 Insulation Stripping Error Burden Test Installation Error
9 Excessive W ire Length/Small W ire Burden Test Installation Error10 Broken Wire Strands Burden Test Installation Error
11 Meter Overburdened Burden Test Installation Error
r mary econ ary urren un ro ems12 Shorted Turns (Wiring & Leakage Current) Ratio/Burden Test Lightning/Ground Fault
13 Shorted Turns (Turn to Turn) Ratio/Burden Test Lightning/Ground Fault
14 S horted Turns (Turn to Ground) Ratio/B urden Tes t Lightning/Ground Fault
15 Theft (Secondary Shunt) Ratio/Burden Test Tampering16 Theft (Primary Shunt) Ratio/Burden Test Tampering
e rap a o ur en es amper ng
18 Theft (Primary Tap) Ratio/Burden Test Tampering
19 Theft (Secondary Tap) Ratio/Burden Test Tampering
Current Transformer Problems20 Open Secondary Ratio Test Installation Error/Tampering
or e econ ary a o es ns a a on rror amper ng
22 Magnetized CT Ratio/Burden Test Lightning/Ground Fault23 Dual Ratio Error Ratio Test Installation Error
24 Inaccurate Ratio on CT Ratio Test Manufacturer Defect
25 Wire Wrap Error on CT Ratio Test Manufacturer Defect
26 Inaccurate Rated Burden on CT Burden Test Manufacturer Defect
Page 13
28 CT Mounted Backwards Wire Verification Installation Error
29 Polarity Dot on W rong Side of CT W ire V erific ation Manufacturer Defec t
30 Overburdened CT Ratio/Burden Test Secondary Burden31 Overdriven CT Ratio/Burden Test Excessive Current
32 CT Phase Shift Wire Verification Harmonic Loading
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 14/23
What To Test?
© OMICRON Page 14
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 15/23
Tests for Protection CT
• Commissioning: – Ratio, Polarity, Rct, Saturation
–
– If possible for transient studies and network modeling:
Remenance Flux Factor, Secondary Time Constant• a ntenance au t nvest gat on:
– Saturation, Rct
– Secondary Burden
© OMICRON Page 15
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 16/23
Tests for Metering CT
• Commissioning: – Ratio and Phase at 0%, 25%, 50%, 100% of Rated Burden
– , , , …
– Calculation of RCF (Ratio Correction Factor)
– Secondary Burden• Routine:
– Same if possible
– -
– Can use portable tester for quick verification and send CTback to test lab if in result is suspect
© OMICRON Page 16
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 17/23
What to Watch Out For?
© OMICRON Page 17
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 18/23
Ratio Test (Bushing CT)
• Short the bushings andwindings you are not testing
• emagnet ze t e e oretest
• Test Voltage should be belowe sa ura on neepo n
• Beware of EM interference(use coaxial cable or test at
o - requency
© OMICRON Page 18
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 19/23
Saturation Test
• Test on full winding• If testing on tapped winding,
-effect
• Do not short any taps• a se e es vo age s ow y
• Lower the test voltage todemagnetize CT
• Beware of insulation level ofall parts of CT circuit and usesafe test voltage levels
© OMICRON Page 19
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 20/23
New Methods (Saturation Test)
• Low voltage, variable frequency saturation test• Above 120Vac fre uenc is reduced to roduce
higher flux in CT to saturation level
• Result is transformed back to 60Hz• Can test effective saturation voltage of up to 30kV
with test voltage of only 120Vac
• ,
© OMICRON Page 20
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 21/23
New Methods (Ratio Test)
• Magnetizing branch of the CT is measured accuratelyfor losses
• Use measured data for ratio, saturation, Rct to
determine ratio and phase accuracy at different levels
• No need for external Burden
• On-site verification of meterin class CT ossible to
0.1 class)
© OMICRON Page 21
8/3/2019 CT Testing Techniques OMICRON
http://slidepdf.com/reader/full/ct-testing-techniques-omicron 22/23
Summary
• CT is not so straight-forward• Protection and Meterin CTs have different
considerations
• Choose the tests that are appropriate to the type of CT• Take care of on-site conditions when testing CT
• New methods are available to make CT testing safer
© OMICRON Page 22