Cutler-Hammer January 2001 Vol. 1, Ref. No. [0575] Molded Case Circuit Breakers 800 - 2500 Amperes 12-109 R-Frame 100% Rated Digitrip RMS 810 Circuit Breakers The NEC allows the breaker to be rated at 100% of its frame size in an assembly, provided that 90°C wire is applied at 75°C ampacity. Order as individual components: Breaker Frame (which includes Trip Unit) and Rating Plug. Table 12-170.100% Rated Digitrip RMS 810 Circuit Breakers®® Maximum Continuous Ampere Rating @40°C Circuit Breaker Frame Only L - Adjustable Long Delay Pickup (lrl with Adjustable Long Delay Time S - Adjustable Short Delay Pickup with Adjustable Short Delay Time (I 2 ! or Flat Response) 1 - Adjustable Instantaneous Pickup G - Adjustable Ground Fault Pickup with Adjustable Ground Fault Time Delay (l z t or Flat Response) LI | LS LSI | LIG | LSG | LSIG Catalog Number Digitrip Rating Plug Only Rated Current dn> Fixed Rating Plug Catalog Number 3-Pole Standard Interrupting Capacity 600V AC Rated65 kAIC © 480V AC 1600 2000 CRD316T81W CRD320T81W CRD316T83W CRD320T83W CRD316T82W CRD320T82W CRD316T84W CRD320T84W CRD316T85W CRD320T85W CRD316T86W CRD320T86W 800 1000 1200 1600 1000 1200 1600 2000 RP6R16A080 RP6R16A100 RP6R16A120 RP6R16A160 RP6R20A100 RP6R20A120 RP6R20A160 RP6R20A200 3-Pole High Interrupting Capacity 600V AC Rated 100 kAIC © 480V AC 1600 2000 CRDC316T81W CRDC320T81W CRDC316T83W CRDC320T83W CRDC316T82W CRDC320T82W CRDC316T84W CRDC320T84W CRDC316T85W CRDC320T85W CRDC316T86W CRDC320T86W 800 1000 1200 1600 1000 1200 1600 2000 RP6R16A080 RP6R16A100 RP6R16A120 RP6R16A160 RP6R20A100 RP6R20A120 RP6R20A160 RP6R20A200 ® See Table 12-171 below for prices. ® Includes B2016RDL rear connectors. _ .j Note: Instruction Leaflet/FRED Number 29C107 for Breaker; Number 29C888 for Digitrip 810 Trip Unit; DS29170R for Dimensions/FRED 2917016 Table 12-171.100% Rated Digitrip RMS 810 Circuit Breakers Prices Catalog Number CRDC316T81W CRDC316T82W CRDC316T83W CRDC316T84W CRDC316T85W CRDC316T86W CRDC320T81W CRDC320T82W CRDC320T83W CRDC320T84W Price U.S. $ 25,590. 27,460. 25,970. 28,080. 28,450. 29,940. 27,180. 27,550. 28,670. 29,660. Catalog Number CRDC320T85W CRDC320T86W CRD316T81W CRD316T82W CRD316T83W CRD316T84W CRD316T85W CRD316T86W CRD320T81W CRD320T82W Price U.S.S 30,030. 31,150. 23,620. 25,480. 23,990. 26,100. 26,470. 27,970. 25,040. 26,910. Catalog Number CRD320T83W CRD320T84W CRD320T85W CRD320T86W RP6R16A080 RP6R16A100 RP6R16A120 RP6R16A160 RP6R20A100 RP6R20A120 Price U.S.S 25,420. 27,530. 27,900. 29,390. 112. 112. 112. 112. 112. 112. Catalog Number RP6R20A160 RP6R20A200 Price U.S.S 112. 112. Discount Symbol. CB-2 CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog F.T*iy

Upload: vutuyen

Post on 15-Jun-2018

231 views

Category:

Documents


0 download

TRANSCRIPT

Cutler-HammerJanuary 2001Vol. 1, Ref. No. [0575]

Molded Case Circuit Breakers800 - 2500 Amperes 12-109

R-Frame

100% Rated Digitrip RMS 810 Circuit BreakersThe NEC allows the breaker to be rated at 100% of its frame size in an assembly, provided that 90°C wire is applied at 75°Campacity. Order as individual components: Breaker Frame (which includes Trip Unit) and Rating Plug.

Table 12-170.100% Rated Digitrip RMS 810 Circuit Breakers®®MaximumContinuousAmpereRating@40°C

Circuit Breaker Frame OnlyL - Adjustable Long Delay Pickup (lrl with Adjustable Long Delay TimeS - Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2! or Flat Response)1 - Adjustable Instantaneous PickupG - Adjustable Ground Fault Pickup with Adjustable Ground Fault Time Delay (lzt or Flat Response)LI | LS LSI | LIG | LSG | LSIGCatalog Number

Digitrip Rating Plug OnlyRatedCurrentdn>

FixedRating Plug

Catalog Number3-Pole Standard Interrupting Capacity 600V AC Rated 65 kAIC © 480V AC

1600

2000

CRD316T81W

CRD320T81W

CRD316T83W

CRD320T83W

CRD316T82W

CRD320T82W

CRD316T84W

CRD320T84W

CRD316T85W

CRD320T85W

CRD316T86W

CRD320T86W

8001000120016001000120016002000

RP6R16A080RP6R16A100RP6R16A120RP6R16A160RP6R20A100RP6R20A120RP6R20A160RP6R20A200

3-Pole High Interrupting Capacity 600V AC Rated 100 kAIC © 480V AC1600

2000

CRDC316T81W

CRDC320T81W

CRDC316T83W

CRDC320T83W

CRDC316T82W

CRDC320T82W

CRDC316T84W

CRDC320T84W

CRDC316T85W

CRDC320T85W

CRDC316T86W

CRDC320T86W

800100012001600

1000120016002000

RP6R16A080RP6R16A100RP6R16A120RP6R16A160RP6R20A100RP6R20A120RP6R20A160RP6R20A200

® See Table 12-171 below for prices.® Includes B2016RDL rear connectors. _ .jNote: Instruction Leaflet/FRED Number 29C107 for Breaker; Number 29C888 for Digitrip 810 Trip Unit; DS29170R for Dimensions/FRED 2917016

Table 12-171.100% Rated Digitrip RMS 810 Circuit Breakers PricesCatalogNumber

CRDC316T81WCRDC316T82WCRDC316T83WCRDC316T84WCRDC316T85WCRDC316T86WCRDC320T81WCRDC320T82WCRDC320T83WCRDC320T84W

PriceU.S. $

25,590.27,460.25,970.28,080.28,450.29,940.27,180.27,550.28,670.29,660.

CatalogNumber

CRDC320T85WCRDC320T86WCRD316T81WCRD316T82WCRD316T83WCRD316T84WCRD316T85WCRD316T86WCRD320T81WCRD320T82W

PriceU.S.S

30,030.31,150.23,620.25,480.23,990.26,100.26,470.27,970.25,040.26,910.

CatalogNumber

CRD320T83WCRD320T84WCRD320T85WCRD320T86WRP6R16A080RP6R16A100RP6R16A120RP6R16A160RP6R20A100RP6R20A120

PriceU.S.S

25,420.27,530.27,900.29,390.

1 1 2 .1 1 2 .1 1 2 .1 1 2 .1 1 2 .1 1 2 .

CatalogNumber

RP6R20A160RP6R20A200

PriceU.S.S

1 1 2 .1 1 2 .

Discount Symbol. CB-2

CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog F.T*iy

12-2

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E

January 2001

12

Product Line OverviewVol. 1, Ref. No. [0468]

Product Line DescriptionCutler-Hammer Molded Case Circuit Breakers are designed to provide circuit protection for low voltage distribution systems. They are described by NEMA as, “. . . a device for closing and inter-rupting a circuit between separable contacts under both normal and abnormal conditions,” and furthermore as, “. . . a breaker assembled as an integral unit in a supporting and enclosing housing of insulating material.” The NEC describes them as, “A device designed to open and close a circuit by non-automatic means, and to open the circuit automatically on a predetermined overload of current, without injury to itself when properly applied within its rating.”

So designed, Cutler-Hammer circuit breakers protect conductors against overloads and conductors and con-nected apparatus, such as motors and motor starters, against short circuits.

In low voltage distribution systems, there are many varied applications of molded case circuit breakers. Cutler-Hammer offers the most comprehensive family of molded case circuit breakers in the industry.

This family of circuit breakers includes:

■ Thermal Magnetic Trip Breakers■ Electronic rms Trip Breakers■ Molded Case Switches■ Motor Circuit Protectors■ Current Limiting Breakers■ Special Application Breakers■ World Breakers

Special CalibrationSpecial non-UL-listed calibrations are available for certain ambient temperatures other than 40°C and for frequencies other than 50/60 Hz or DC. Reduced interrupting ratings will apply for 400 Hz applications. Maximum thermal calibration is limited to 135A at 400 Hz.

50°C CalibrationAdd suffix V to Catalog Number for complete breaker, listed above, when ordering listed ampere ratings for breakers to be used in 50°C ambients.

Moisture-Fungus TreatmentAll circuit breaker cases are molded from glass-polyester which does not support the growth of fungus. Any parts which are susceptible to the growth of fungus will require special treatment.

Freeze-Tested Circuit BreakersThe circuit breakers may be ordered with freeze testing. This option uses special lubrication and mechanical operation is verified at -40°C.

Marine ApplicationsF-Frame circuit breakers can be sup-plied to meet the following marine specifications:

■ U.S. Coast Guard CFR 46 ABS — American Bureau of Shipping IEEE 45

These specifications generally require molded case circuit breakers to be supplied with 50°C ambient calibration, special nameplating, and plug-in adapter kits. When plug-in adapter kits are used, no terminals need be supplied.

Circuit breakers can also be supplied to meet UL489 Supplement SA (Marine Use) and UL489 Supplement SB (Naval Use).

UL489 Supplement SA applies to vessels over 65 feet in length. Requirements include 40°C ambient calibration, spe-cial labeling, and no use of aluminum conductors or terminals.

UL 489 Supplement SB requires 50°C ambient calibration, vibration testings, special nameplating and no use of aluminum conductors or terminals.

Standards and CertificationsMolded case circuit breakers are designed to conform with the follow-ing standards:

■ Underwriters Laboratories, Inc., Standard UL489, Molded Case Circuit Breakers and Circuit Breaker Enclosures

■ National Electrical Manufacturers Association Standards Publication No. AB1-1993, Molded Case Circuit Breakers

■ Australian Standard AS 2184, Molded Case Circuit Breakers

■ British Standards Institution Standard BS 4752: Part 1, Switchgear and Control Gear Part 1: Circuit Breakers

■ Canadian Standards Association Standard C22.2 No. 5, Service Entrance and Branch Circuit Breakers

■ International Electrotechnical Commission Recommendations IEC 157-1, Circuit Breakers

■ Japanese T-Mark Standard Molded Case Circuit Breakers

■ South African Bureau of Standards, Standard SABS 156, Standard Specification for Molded Case Circuit Breakers

■ Swiss Electro-Technical Association Standard SEV 157-1, Safety Regula-tions for Circuit Breakers

■ Union Technique de l’Electricite Standard NF C 63-120, Low Voltage Switchgear and Control Gear Circuit Breaker Requirements

■ Verband Deutscher Elektrotechniker (Association of German Electrical Engineers) Standard VDE 0660, Low Voltage Switchgear and Control Gear, Circuit Breakers

Conformance with these standards satisfies most local and international codes, assuming user acceptability and simplified application.

Molded case circuit breakers equal or exceed Federal Specification Classifi-cation W-C-375b requirements for the particular class associated with the cir-cuit breaker frame being considered.

Note: For further information, see Circuit Breaker, CD-ROM SA.74A.01.T.E.

Suffix H01 400 Hz 20% Adder

Suffix J01 Fungus Treated $325. + 20% Adder

Suffix F01 Freeze Tested 20% Adder

Suffix H08 “Marine” 10% Adder

Suffix H09 “Naval” 10% Adder

CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

12January 2001 Product Line OverviewVol. 1, Ref. No. [0471]

Table 12-1. Industrial Circuit Breakers (Continued)

� N.I.T. is non-interchangeable trip unit and I.T. is interchangeable trip unit.� Two-pole circuit breaker, or two poles of three-pole circuit breaker at 250V DC.

CircuitBreakerType

Cont.AmpRating@ 40°C

No.Poles

Volts Type of Trip �

Federal Spec.W-C-375b

UL Listed Interrupting Ratings rms Symmetrical Amperes PageNumberAC DC AC Ratings Volts DC �

120 120/240 240 277 480 600 125 250 125/250

R-FrameRD 1600CRD 1600RD 2000RD 2500CRD 2000RDC 1600CRDC 1600RDC 2000RDC 2500CRDC 2000

800 – 1600800 – 1600

1000 – 20001000 – 25001000 – 2000800 – 1600800 – 1600

1000 – 20001000 – 25001000 – 2000

3, 43, 43, 43, 43, 43, 43, 43, 43, 43, 4

600600600600600600600600600600

— —————————

N.I.T.N.I.T.N.I.T.N.I.T.N.I.T.N.I.T.N.I.T.N.I.T.N.I.T.N.I.T.

24a24a24a24a24a25a25a25a25a25a

— —————————

— —————————

125,000125,000125,000200,000125,000200,000200,000200,000200,000200,000

— —————————

65,00065,00065,00065,00065,000

100,000100,000100,000100,000100,000

50,00050,00050,00050,00050,00065,00065,00065,00065,00065,000

— —————————

— —————————

— —————————

12-10012-10312-10012-10012-10312-10212-10312-10212-10212-103

Series C HMCP Motor Circuit Protectors 12-118

Current Limit R Current Limiting Circuit Breakers — Non-Fused TypeFCL 15 – 100 2, 3 480 — N.I.T. — — — 200,000 — 150,000 — — — — 12-129

LCL 125 – 400 2, 3 600 — N.I.T. — — — 200,000 — 200,000 100,000 — — — 12-130

Tri-Pac Current Limiting Circuit Breakers — Fused TypeFB 15 – 100 2, 3 600 250 N.I.T. 16a, 16b,

17a, 26a— — 200,000 — 200,000 200,000 — — 100,000 12-132

LA 70 – 400 2, 3 600 250 I.T. 16a, 16b,17a, 26a

— — 200,000 — 200,000 200,000 — — 100,000 12-133

NB 300 – 800 2, 3 600 250 I.T. 16b, 17a,26a

— — 200,000 — 200,000 200,000 — — 100,000 12-135

PB 600 – 1600 2, 3 600 250 I.T. 17a, 26a — — 200,000 — 200,000 200,000 — — 100,000 12-137

Cutler-HammerJanuary 2001Vol. 1, Ref. No. [0563]

Molded Case Circuit Breakers800 - 2500 AmperesR-Frame

12-97

ContentsDescription

Product Description .Technical Data

and Specifications .Dimensions/WeightsProduct Selection ...

Page12-97

12-9712-9912-99

R-Frame Product DescriptionR-Frame Circuit Breakers are avail-able as frame (which includes tripunit), rating plug and terminals.

All R-Frame circuit breakers aresuitable for reverse feed use.

Typical R-Frame Circuit Breaker

Technical Data and SpecificationsTable 12-148. UL489/CSA Interrupting Capacity RatingsCircuitBreakerType

RDCRD®RDCCROC®

Numberof Poles

3,43,43,4

3,4

Interrupting Capacity (Symmetrical Amperes) (kA)Volts AC (50/60 Hz)240

125

125

200

200

277

——

480

65

65

100

100

600

50

50

65

65

® Utilization Category A circuit breakers.® 100% Rated breakers.Note: See Page 12-98 for Trip Unit Specifications.

Table 12-149. IEC 947-2 Interrupting Capacity Ratings <CircuitBreakerType

RDleuIcsRDCleuIcs

Number ofPoles

3,4

3,4

Interrupting Capacity (Symmetrical Amperes) (kA)Volts AC (50/60 Hz)240

135100

200100

415

7050

10050

690

2513

3518

® Utilization Category A circuit breakers.

CAT.200.01.T.E For more information contact Cutler-Hammer at www.ch.cutler-hammer.com/catalog F.T-iy

Cutler-HammerJanuary 2001Vol. 1, Ref. No. [05651

H Molded Case Circuit Breakers 17 qq• 800 -2500 Amperes

R-Frame

Dimensions/WeightsTable 12-151. Dimensions in Inches (mm)Numberof Poles

34

'

Width Height

15.5(394) 16(406)20 (508) 16 (406)

Depth

9.75 (248)

9.75 (248)

^ ' i

Table 12-152. Approximate Shipping Weight, Lbs. (kg)BreakerType

Complete BreakerNumber of Poles3 4

1600ARD, CRD, RDC, CROC 102(46.3) 135(61.2)

2000ARD, RDCCRD, CROC

102 (46.3)130 (59.0)

135(61.2)175 (79.4)

2500ARD, RDC 135(61.2) 182 (82.6)

Product SelectionThis information is presented only as an aid to understanding Catalog Numbers. It is not to be used to build Catalog Numbersfor circuit breakers or trip units.

Table 12-153. Circuit Breaker/Frame Catalog Numbering System ______ _______ ________________ _____

RD 3 16 T32 W

Numberof Poles

3 = 3 Poles4 = 4 Poles

rCircuit Breaker/

Frame Ampere Rating16= 1600A20 = 2000A

J JTrip Type ®

T32T53T65T86T96T106T107

= Digitrip RMS 310 LSI= Digitrip RMS 510 LS= Digitrip RMS 610 LSG= Digitrip RMS 810 LSIG= Digitrip RMS 910 LSIG= Digitrip OPTIM 1050 LSIG= Digitrip OPTIM 1050 LSIA

SuffixW = Without TerminalsP = 100% Protected Neutral PoleR = Ground Fault Remote

(310 Only)K = Molded Case Switch

® For complete list of available trip types refer to Pages 12-100-12-113 .I ••.•.

CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog F.T'N