d-aaa-cub (rev.0-2011)
DESCRIPTION
D-AAA-CUB (Rev.0-2011)TRANSCRIPT
-
305661956.xls
________________________________________________________________________________________
Page 1 of 45
Standard Technical Specifications for Electrical Works
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES
( Data Sheets )
Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
-
305661956.xls
________________________________________________________________________________________
Page 2 of 45
ADWEA/ADDC/AADC STANDARD : D-AAA-CUB (Rev.0-2011)
-
305661956.xls
_____________________________________________________________________________________________________________
Page 2 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES
Table of Content
Page
1.00 GENERAL 5 A. Protection (Free Standing Panels/Cubicles) 5 B. Local (LCC) / Remote Control Panels/Cubicles 6 C. Transformer AVR Panels/Cubicles 8 D. Tele-Communication Panels/Cubicles, incl. Optic Heads/Termination Boxes 18 E. Fire Fighting System Panels/Cubicles 20 F. Air Conditioning System Panels/Cubicles 22 G. Interface Panels/Cubicles 23 H. Other Free-Standing Panels/Cubicles 25 I. Other Wall-Mounted Cubicle / Marshalling Boxes 25
2.00 CONSTRUCTION DATA 26 A. Indoor Type Panels/Cubicles, Marshalling Boxes 26 B. Outdoor Type Cubicles/Panels, Marshalling Boxes 28 C. Wiring 29 D. Terminal Blocks 30 E. Contactor 32 F. Auxiliary Contactor 33 G. MCB 33 H. Strip Fuse Ways 33 I. Indicator Lamps 34 J. Push Buttons 34 K. Selector Switch 34 L. Ventilation * 35 M. Anticondensing Heater 36 N. Lighting (if applicable) 36 O. Socket (if applicable) 37 P. Cubicle Vermin Proof? 37
Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
-
305661956.xls
_____________________________________________________________________________________________________________
Page 3 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES
Table of Content
Page
Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Q. Corrosion Protection Details 37
R. Earthing Arrangement 38 S. Danger Sign Details 38 T. Identification Sign Details 39 U. Lifting Devices Details (if applicable) 40 V. Provision of Safety Equipment 40 W. Pocket on Door for Drawings 40 X. 41
Y. Door Locks and Keys 41 Z. Stainless steel used for handles, hinges, signs,bolts, nuts, etc. 41
3.00 ELECTRICAL DATA 41 A. Wiring 41 B. Terminal Blocks 41 C. Contactor 43 D. Auxiliary Contactor 43 E. MCB 43 F. Fuses 44 G. Indicator Lamps 44 H. Push Buttons 44 I. Selector Switch 44 J. Ventilation Motor (if applicable) 44 K. Anticondensing Heater 45 L. Lighting (if applicable) 45 M. Socket (if applicable) 45
Door Fixing Devices Provided (to keep door in open position in case of maintenance)
-
305661956.xls
_____________________________________________________________________________________________________________
Page 4 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES
Table of Content
Page
Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
4.00 SUPPORTING DOCUMENTS 45
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 5 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.00 GENERAL
A. Protection (Free Standing Panels/Cubicles)
1.01 Manufacturer
1.01.1 name
1.01.2 country of manufacturing
1.02 Applicable standards IEC
1.03 Housing material type
1.03.1 protection class (IEC 60529) IP 54
1.03.2 anti-corrosion treatment
1.03.3 hardware and metallic parts
1.03.4 walls
1.03.4.1 inside
1.03.4.1.1 color RAL
1.03.4.1.2 thickness mm
1.03.4.2 outside
1.03.4.2.1 color RAL 7032/7035
1.03.4.2.2 thickness mm
1.04 Swing frame provided yes/no yes
1.05 Heat dissipation
1.05.1 natural convection yes/no
1.01.2 air flow yes/no
1.06 Panel access
1.06.1 front yes/no yes
1.06.2 rear (if applicable) yes/no yes
1.06.3 front door
1.06.3.1 opening minimum angle deg 120
1.06.3.2 door switch yes/no yes
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 6 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.06.4 Internal lighting with socket yes/no yes
1.07 Dimensions
1.07.1 height mm 2200
1.07.2 width mm 800
1.07.3 depth mm 800
1.07.3 wall thickness mm
1.08 Cable entries
1.08.1 numbers No.
1.08.2 type
1.09 Gland plate
1.09.1 material
1.09.1.1 hot-dip galvanised steel yes/no
1.09.1.1.1 min. thickness mm 3
1.09.1.2 aluminium yes/no
1.09.1.2.1 min. thickness mm 4
1.09.2 length mm
1.09.3 width mm
1.10 Gland
1.10.1 material brass
1.10.2 grade
1.11 MCB`s (supervised) provided for:
1.11.1 AC
1.11.1.1 each Panel Nos. 1
1.11.2 DC
1.11.2.1 each Panel at Main DC Board Nos. 1
1.11.2.2 alarm / supervision Nos. 1
1.11.2.3 each DC supply unit inside the Panel Nos. 1
1.12 Reset button
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 7 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.12.1 location outside the access door
1.12.1.1 Alarm Annunciators installed
1.12.2 16 windows for each bay yes/no yes
1.13 Weight kg
1.14 Floor load (maximum) 600
1.15 Heater with thermostat provided yes/no yes
1.17 Earth plate with screw terminal connection yes/no yes
1.18 Lifting lugs yes/no yes
1.19 Electrical interference environment
1.19.2 insulation class
1.19.3 insulation resistance
1.19.4 dielectric strength, 50Hz, 1min.
B. Local (LCC) / Remote Control Panels/Cubicles
1.20 Free-standing
1.20.1 Manufacturer
1.20.1.1 name
1.20.1.2 country of manufacturing
1.20.2 Applicable standards IEC
1.20.3 Housing material type
1.20.3.1 protection class (IEC 60529) IP 41
1.20.3.2 anti-corrosion treatment
1.20.3.2.1 hardware and metallic parts
1.20.3.2.2 walls
1.20.3.2.2. inside
1.20.3.2.2 color RAL
1.20.3.2.2 thickness mm
1.20.3.2.2. outside
daN/m2
M
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 8 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.20.3.2.2 color RAL 7032/7035
1.20.3.2.2 thickness mm
1.20.4 Swing frame provided yes/no yes
1.20.5 Heat dissipation
1.20.5.1 natural convection yes/no
1.20.5.2 air flow yes/no
1.20.6 Panel access
1.20.6.1 front yes/no yes
1.20.6.2 rear (if applicable) yes/no yes
1.20.6.3 front door
1.20.3.1 opening minimum angle deg 120
1.20.3.2 door switch yes/no yes
1.20.6.4 Internal lighting with socket yes/no yes
1.20.7 Dimensions
1.20.7.1 height mm 2200
1.20.7.2 width mm 800
1.20.7.3 depth mm 800
1.20.7.4 wall thickness mm
1.20.8 Cable entries
1.20.8.1 numbers No.
1.20.8.2 type
1.20.9 Gland plate
1.20.9.1 material
1.20.1.1 hot-dip galvanised steel yes/no
1.20.1.1.1 min. thickness mm 3
1.20.1.2 aluminium yes/no
1.20.1.2.1 min. thickness mm 4
1.20.9.2 length mm
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 9 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.20.9.3 width mm
1.20.10 Gland
1.20.10.1 material brass
1.20.10.2 grade
1.20.11 MCB`s (supervised) provided for:
1.20.11.1 AC
1.20.11.1.1 each Panel Nos. 1
1.20.11.2 DC
1.20.11.2.1 each Panel at Main DC Board Nos. 1
1.20.11.2.2 alarm / supervision Nos. 1
1.20.11.2.3 each DC supply unit inside the Panel Nos. 1
1.20.12 Reset button
1.20.12.1 location outside the access door
1.20.13 Alarm Annunciators installed
1.20.13.1 16 windows for each bay yes/no yes
1.20.14 Weight kg
1.20.15 Floor load (maximum) 600
1.20.16 Heater with thermostat provided yes/no yes
1.20.17 Earth plate with screw terminal connection yes/no yes
1.20.18 Lifting lugs yes/no yes
1.20.19 Electrical interference environment
1.20.19.2 insulation class
1.20.19.3 insulation resistance
1.20.19.4 dielectric strength, 50Hz, 1min.
C. Transformer AVR Panels/Cubicles
1.21 Free-standing
1.21.1 Manufacturer
daN/m2
M
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 10 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.21.1.1 name
1.21.1.2 country of manufacturing
1.21.2 Applicable standards IEC
1.21.3 Housing material type
1.21.3.1 protection class (IEC 60529) IP 54
1.21.3.2 anti-corrosion treatment
1.21.3.2.1 hardware and metallic parts
1.21.3.2.2 walls
1.21.3.2.2. inside
1.21.3.2.2 color RAL
1.21.3.2.2 thickness mm
1.21.3.2.2. outside
1.21.3.2.2 color RAL 7032/7035
1.21.3.2.2 thickness mm
1.21.4 Swing frame provided yes/no yes
1.21.5 Heat dissipation
1.21.5.1 natural convection yes/no
1.21.5.2 air flow yes/no
1.21.6 Panel access
1.21.6.1 front yes/no yes
1.21.6.2 rear (if applicable) yes/no yes
1.21.6.3 front door
1.21.3.1 opening minimum angle deg 120
1.21.3.2 door switch yes/no yes
1.21.6.4 Internal lighting with socket yes/no yes
1.21.7 Dimensions
1.21.7.1 height mm 2200
1.21.7.2 width mm 800
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 11 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.21.7.3 depth mm 800
1.21.7.4 wall thickness mm
1.21.8 Cable entries
1.21.8.1 numbers No.
1.21.8.2 type
1.21.9 Gland plate
1.21.9.1 material
1.21.1.1 hot-dip galvanised steel yes/no
1.21.1.1.1 min. thickness mm 3
1.21.1.2 aluminium yes/no
1.21.1.2.1 min. thickness mm 4
1.21.9.2 length mm
1.21.9.3 width mm
1.21.10 Gland
1.21.10.1 material brass
1.21.10.2 grade
1.21.11 MCB`s (supervised) provided for:
1.21.11.1 AC
1.21.11.1.1 each Panel Nos. 1
1.21.11.2 DC
1.21.11.2.1 each Panel at Main DC Board Nos. 1
1.21.11.2.2 alarm / supervision Nos. 1
1.21.11.2.3 each DC supply unit inside the Panel Nos. 1
1.21.12 Reset button
1.21.12.1 location outside the access door
1.21.13 Alarm Annunciators installed
1.21.13.1 16 windows for each bay yes/no yes
1.21.14 Weight kg
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 12 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.21.15 Floor load (maximum) 600
1.21.16 Heater with thermostat provided yes/no yes
1.21.17 Earth plate with screw terminal connection yes/no yes
1.21.18 Lifting lugs yes/no yes
1.21.19 Electrical interference environment
1.21.19.2 insulation class
1.21.19.3 insulation resistance
1.21.19.4 dielectric strength, 50Hz, 1min.
1.22 Cubicles mounted at transformers
1.22.1 manufacturer
1.22.1.1 name
1.22.1.2 country of manufacturing
1.22.2 applicable standards IEC
1.22.3 color RAL 7032
1.22.4 dimensions
1.22.4.1 height mm 800
1.22.4.2 width mm 600
1.22.4.3 depth mm 250
1.22.5 cable entries No.
1.22.6 gland plate
1.22.6.1 material Hot-Dip galcanised steel
1.22.6.2 length mm
1.22.6.3 width mm
1.22.6.4 min. thickness mm 3
1.22.7 gland
1.22.7.1 material brass
1.22.7.2 grade
1.22.8 MCB`s provided for transformer control equipment yes/no yes
daN/m2
M
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 13 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.22.9 reset button
1.22.9.1 location outside the access door
1.22.10 Alarm Annunciators installed yes/no yes
1.22.11 weight kg
D. Tele-Communication Panels/Cubicles, incl. Optic Heads/Termination Boxes
1.23 Free-standing
1.23.1 Manufacturer
1.23.1.1 name
1.23.1.2 country of manufacturing
1.23.2 Applicable standards IEC
1.23.3 Housing material type
1.23.3.1 protection class (IEC 60529) IP 54
1.23.3.2 anti-corrosion treatment
1.23.3.2.1 hardware and metallic parts
1.23.3.2.2 walls
1.23.3.2.2. inside
1.23.3.2.2 color RAL
1.23.3.2.2 thickness mm
1.23.3.2.2. outside
1.23.3.2.2 color RAL 7032/7035
1.23.3.2.2 thickness mm
1.23.4 Swing frame provided yes/no yes
1.23.5 Heat dissipation
1.23.5.1 natural convection yes/no
1.23.5.2 air flow yes/no
1.23.6 Panel access
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 14 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.23.6.1 front yes/no yes
1.23.6.2 rear (if applicable) yes/no yes
1.23.6.3 front door
1.23.3.1 opening minimum angle deg 120
1.23.3.2 door switch yes/no yes
1.23.6.4 Internal lighting with socket yes/no yes
1.23.7 Dimensions
1.23.7.1 height mm 2200
1.23.7.2 width mm 800
1.23.7.3 depth mm 800
1.23.7.4 wall thickness mm
1.23.8 Cable entries
1.23.8.1 numbers No.
1.23.8.2 type
1.23.9 Gland plate
1.23.9.1 material
1.23.1.1 hot-dip galvanised steel yes/no
1.23.1.1.1 min. thickness mm 3
1.23.1.2 aluminium yes/no
1.23.1.2.1 min. thickness mm 4
1.23.9.2 length mm
1.23.9.3 width mm
1.23.10 Gland
1.23.10.1 material brass
1.23.10.2 grade
1.23.11 MCB`s (supervised) provided for:
1.23.11.1 AC
1.23.11.1.1 each Panel Nos. 1
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 15 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.23.11.2 DC
1.23.11.2.1 each Panel at Main DC Board Nos. 1
1.23.11.2.2 alarm / supervision Nos. 1
1.23.11.2.3 each DC supply unit inside the Panel Nos. 1
1.23.12 Reset button
1.23.12.1 location outside the access door
1.23.13 Weight kg
1.23.14 Floor load (maximum) 600
1.23.15 Heater with thermostat provided yes/no yes
1.23.16 Earth plate with screw terminal connection yes/no yes
1.23.17 Lifting lugs yes/no yes
1.23.18 Electrical interference environment
1.23.18.2 insulation class
1.23.18.3 insulation resistance
1.23.18.4 dielectric strength, 50Hz, 1min.
E. Fire Fighting System Panels/Cubicles
1.24 Free-standing
1.24.1 Manufacturer
1.24.1.1 name
1.24.1.2 country of manufacturing
1.24.2 Applicable standards IEC
1.24.3 Housing material type
1.24.3.1 protection class (IEC 60529) IP 54
1.24.3.2 anti-corrosion treatment
1.24.3.2.1 hardware and metallic parts
1.24.3.2.2 walls
1.24.3.2.2. inside
daN/m2
M
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 16 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.24.3.2.2 color RAL
1.24.3.2.2 thickness mm
1.24.3.2.2. outside
1.24.3.2.2 color RAL 7032/7035
1.24.3.2.2 thickness mm
1.24.4 Swing frame provided yes/no yes
1.24.5 Heat dissipation
1.24.5.1 natural convection yes/no
1.24.5.2 air flow yes/no
1.24.6 Panel access
1.24.6.1 front yes/no yes
1.24.6.2 rear (if applicable) yes/no yes
1.24.6.3 front door
1.24.3.1 opening minimum angle deg 120
1.24.3.2 door switch yes/no yes
1.24.6.4 Internal lighting with socket yes/no yes
1.24.7 Dimensions
1.24.7.1 height mm 2200
1.24.7.2 width mm 800
1.24.7.3 depth mm 800
1.24.7.4 wall thickness mm
1.24.8 Cable entries
1.24.8.1 numbers No.
1.24.8.2 type
1.24.9 Gland plate
1.24.9.1 material
1.24.1.1 hot-dip galvanised steel yes/no
1.24.1.1.1 min. thickness mm 3
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 17 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.24.1.2 aluminium yes/no
1.24.1.2.1 min. thickness mm 4
1.24.9.2 length mm
1.24.9.3 width mm
1.24.10 Gland
1.24.10.1 material brass
1.24.10.2 grade
1.24.11 MCB`s (supervised) provided for:
1.24.11.1 AC
1.24.11.1.1 each Panel Nos. 1
1.24.11.2 DC
1.24.11.2.1 each Panel at Main DC Board Nos. 1
1.24.11.2.2 alarm / supervision Nos. 1
1.24.11.2.3 each DC supply unit inside the Panel Nos. 1
1.24.12 Reset button
1.24.12.1 location outside the access door
1.24.13 Weight kg
1.24.14 Floor load (maximum) 600
1.24.15 Heater with thermostat provided yes/no yes
1.24.16 Earth plate with screw terminal connection yes/no yes
1.24.17 Lifting lugs yes/no yes
1.24.18 Electrical interference environment
1.24.18.2 insulation class
1.24.18.3 insulation resistance
1.24.18.4 dielectric strength, 50Hz, 1min.
F. Air Conditioning System Panels/Cubicles
1.25 Free-standing
daN/m2
M
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 18 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.25.1 Manufacturer
1.25.1.1 name
1.25.1.2 country of manufacturing
1.25.2 Applicable standards IEC
1.25.3 Housing material type
1.25.3.1 protection class (IEC 60529) IP 54
1.25.3.2 anti-corrosion treatment
1.25.3.2.1 hardware and metallic parts
1.25.3.2.2 walls
1.25.3.2.2. inside
1.25.3.2.2 color RAL
1.25.3.2.2 thickness mm
1.25.3.2.2. outside
1.25.3.2.2 color RAL 7032/7035
1.25.3.2.2 thickness mm
1.25.4 Swing frame provided yes/no yes
1.25.5 Heat dissipation
1.25.5.1 natural convection yes/no
1.25.5.2 air flow yes/no
1.25.6 Panel access
1.25.6.1 front yes/no yes
1.25.6.2 rear (if applicable) yes/no yes
1.25.6.3 front door
1.25.3.1 opening minimum angle deg 120
1.25.3.2 door switch yes/no yes
1.25.6.4 Internal lighting with socket yes/no yes
1.25.7 Dimensions
1.25.7.1 height mm 2200
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 19 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.25.7.2 width mm 800
1.25.7.3 depth mm 800
1.25.7.4 wall thickness mm
1.25.8 Cable entries
1.25.8.1 numbers No.
1.25.8.2 type
1.25.9 Gland plate
1.25.9.1 material
1.25.1.1 hot-dip galvanised steel yes/no
1.25.1.1.1 min. thickness mm 3
1.25.1.2 aluminium yes/no
1.25.1.2.1 min. thickness mm 4
1.25.9.2 length mm
1.25.9.3 width mm
1.25.10 Gland
1.25.10.1 material brass
1.25.10.2 grade
1.25.11 MCB`s (supervised) provided for:
1.25.11.1 AC
1.25.11.1.1 each Panel Nos. 1
1.25.11.2 DC
1.25.11.2.1 each Panel at Main DC Board Nos. 1
1.25.11.2.2 alarm / supervision Nos. 1
1.25.11.2.3 each DC supply unit inside the Panel Nos. 1
1.25.12 Reset button
1.25.12.1 location outside the access door
1.25.13 Weight kg
1.25.14 Floor load (maximum) 600daN/m2
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 20 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.25.15 Heater with thermostat provided yes/no yes
1.25.16 Earth plate with screw terminal connection yes/no yes
1.25.17 Lifting lugs yes/no yes
1.25.18 Electrical interference environment
1.25.18.2 insulation class
1.25.18.3 insulation resistance
1.25.18.4 dielectric strength, 50Hz, 1min.
1.26 Wall-mounted (if applicable)
1.26.1 manufacturer
1.26.1.1 name
1.26.1.2 country of manufacturing
1.26.2 applicable standards NFPA
1.26.3 color RAL 7032
1.26.4 dimensions
1.26.4.1 height mm 800
1.26.4.2 width mm 600
1.26.4.3 depth mm 250
1.26.5 cable entries No.
1.26.6 gland plate
1.26.6.1 material Hot-Dip galcanised steel
1.26.6.2 length mm
1.26.6.3 width mm
1.26.6.4 min. thickness mm 3
1.26.7 gland
1.26.7.1 material brass
1.26.7.2 grade
1.26.8 MCCB`s provided for HVAC equipment yes/no yes
1.26.9 reset button
M
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 21 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.26.9.1 location outside the access door
1.26.9 weight kg
G. Interface Panels/Cubicles
1.27 Free-standing
1.27.1 Manufacturer
1.27.1.1 name
1.27.1.2 country of manufacturing
1.27.2 Applicable standards IEC
1.27.3 Housing material type
1.27.3.1 protection class (IEC 60529) IP 54
1.27.3.2 anti-corrosion treatment
1.27.3.2.1 hardware and metallic parts
1.27.3.2.2 walls
1.27.3.2.2. inside
1.27.3.2.2. color RAL
1.27.3.2.2. thickness mm
1.27.3.2.3 outside
1.27.3.2.3. color RAL 7032/7035
1.27.3.2.3. thickness mm
1.27.4 Swing frame provided yes/no yes
1.27.5 Heat dissipation
1.27.5.1 natural convection yes/no
1.27.5.2 air flow yes/no
1.27.6 Panel access
1.27.6.1 front yes/no yes
1.27.6.2 rear (if applicable) yes/no yes
1.27.7 front door
1.27.7.1 opening minimum angle deg 120
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 22 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.27.7.2 door switch yes/no yes
1.27.8 Internal lighting with socket yes/no yes
1.27.9 Dimensions
1.27.9.1 height mm 2200
1.27.9.2 width mm 800
1.27.9.3 depth mm 800
1.27.9.4 wall thickness mm
1.27.10 Cable entries
1.27.10.1 numbers No.
1.27.10.2 type
1.27.11 Gland plate
1.27.11.1 material
1.27.11.1.1 hot-dip galvanised steel yes/no
1.27.11.1.1 min. thickness mm 3
1.27.11.1.2 aluminium yes/no
1.27.11.1. min. thickness mm 4
1.27.11.2 length mm
1.27.11.3 width mm
1.27.12 Gland
1.27.12.1 material brass
1.27.12.2 grade
1.27.13 Weight kg
1.27.14 Floor load (maximum) 600
1.27.15 Heater with thermostat provided yes/no yes
1.27.16 Earth plate with screw terminal connection yes/no yes
1.27.17 Lifting lugs yes/no yes
1.27.18 Electrical interference environment
1.27.18.1 insulation class
1.27.18.2 insulation resistance
daN/m2
M
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 23 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.27.18.3 dielectric strength, 50Hz, 1min.
1.28 Wall-mounted
1.28.1 manufacturer
1.28.1.1 name
1.28.1.2 country of manufacturing
1.28.2 applicable standards IEC
1.28.3 color RAL 7032
1.28.4 dimensions
1.28.4.1 height mm 800
1.28.4.2 width mm 600
1.28.4.3 depth mm 250
1.28.5 cable entries No.
1.28.6 gland plate
1.28.6.1 material Hot-Dip galcanised steel
1.28.6.2 length mm
1.28.6.3 width mm
1.28.6.4 min. thickness mm 3
1.28.7 gland
1.28.7.1 material brass
1.28.7.2 grade
1.28.8 weight kg
H. Other Free-Standing Panels/Cubicles
1.29 Applicable standards IEC
1.30 Housing material type
1.30.1 protection class (IEC 60529) IP 54
1.30.2 anti-corrosion treatment
1.30.3 hardware and metallic parts
1.30.4 walls
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 24 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.30.4.1 inside
1.30.4.1.1 color RAL
1.30.4.1.2 thickness mm
1.30.4.2 outside
1.30.4.2.1 color RAL 7032/7035
1.30.4.2.2 thickness mm
1.31 Swing frame provided yes/no yes
1.32 Heat dissipation
1.32.1 natural convection yes/no
1.32.2 air flow yes/no
1.33 Panel access
1.33.1 front yes/no yes
1.33.2 rear (if applicable) yes/no yes
1.33.3 front door
1.33.3.1 opening minimum angle deg 120
1.33.3.2 door switch yes/no yes
1.34 Internal lighting with socket yes/no yes
1.35 Dimensions
1.35.1 height mm 2200
1.35.2 width mm 800
1.35.3 depth mm 800
1.35.4 wall thickness mm
1.35 Cable entries
1.35.1 numbers No.
1.35.2 type
1.36 Gland plate
1.36.1 material
1.36.1.1 hot-dip galvanised steel yes/no
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 25 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
1.36.1.1.1 min. thickness mm 3
1.36.1.2 aluminium yes/no
1.36.1.2.1 min. thickness mm 4
1.36.2 length mm
1.36.3 width mm
1.37 Gland
1.37.1 material brass
1.37.2 grade
1.38 MCB`s (supervised) provided for:
1.38.1 AC
1.38.1.1 each Panel Nos. 1
1.38.2 DC
1.38.2.1 each Panel at Main DC Board Nos. 1
1.38.2.2 alarm / supervision Nos. 1
1.38.2.3 each DC supply unit inside the Panel Nos. 1
1.39 Reset button
1.39.1 location outside the access door
1.39.1.1 Alarm Annunciators installed
1.39.2 16 windows for each bay yes/no yes
1.40 Weight kg
1.41 Floor load (maximum) 600
1.42 Heater with thermostat provided yes/no yes
1.43 Earth plate with screw terminal connection yes/no yes
1.44 Lifting lugs yes/no yes
1.45 Electrical interference environment
1.45.2 insulation class
1.45.3 insulation resistance
1.45.4 dielectric strength, 50Hz, 1min.
daN/m2
M
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 26 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
I. Other Wall-Mounted Cubicle / Marshalling Boxes
1.46 Application
1.47 Manufacturer
1.47.1 name
1.47.2 country of manufacturing
1.48 Applicable standards
1.49 Color RAL 7032
1.50 Dimensions
1.50.1 height mm 800
1.50.2 width mm 600
1.50.3 depth mm 250
1.51 Cable entries No.
1.52 Gland plate
1.52.1 material Hot-Dip galcanised steel
1.52.2 length mm
1.52.3 width mm
1.52.4 min. thickness mm 3
1.53 Gland
1.53.1 material brass
1.53.2 grade
1.54 Reset button
1.54.1 location outside the access door
1.54.2 Weight kg
2.00 CONSTRUCTION DATA
A. Indoor Type Panels/Cubicles, Marshalling Boxes
2.01 Degree of protection
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 27 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
2.01.1 Battery Chargers IP 41
2.01.2 LVAC Distribution Board IP 41
2.01.3 DC Distribution Board IP 41
2.02 Corner posts
2.02.1 material galvanised steel
2.02.2 grade
2.02.3 applicable standards IEC 60439-1
2.02.4 minimum thickness mm 2
2.03 Walls
2.03.1 material galvanised steel
2.03.1.1 grade
2.03.2 applicable standards IEC 60439-1
2.03.3 minimum thickness mm 2
2.04 Roof
2.04.1 material galvanised steel
2.04.1.1 grade
2.04.2 applicable standards IEC 60349-1
2.04.3 minimum thickness mm 2
2.05 Doors
2.05.1 material galvanised steel
2.05.1.1 grade
2.05.2 applicable standards IEC 6039-1
2.05.3 minimum thickness mm 2
2.05.4 transparent glass window provided yes
2.05.4.1 seize
2.05.4.1.1 length mm 1600
2.05.4.1.2 width mm 450
2.05.5 door stoppers provided yes
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 28 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
2.05.6 door opening minimum angle deg 120
2.06 Equipment mounting plates
2.06.1 material galvanised steel sheet
2.06.1.1 grade
2.06.2 applicable standards IEC 60439-1
2.06.3 minimum thickness mm 2
2.07 Partition (if applicable)
2.07.1 material galvanised steel sheet
2.07.1.1 grade
2.07.2 applicable standards IEC 60349-1
2.07.3 minimum thickness mm 2
2.08 Panel access
2.08.1 front yes/no yes
2.08.2 rear (if applicable) yes/no yes
2.09 Maximum inside temperature of cubicle 55
2.10 Lifting lugs provided yes/no yes
B. Outdoor Type Cubicles/Panels, Marshalling Boxes
2.10 Applicable Standards IEC 61069
2.11 Degree of protection IP 55W
2.12 Corner posts
2.11.1 material galvanised steel sheet
2.11.1.1 grade
2.11.2 minimum thickness mm 3
2.13 Walls
2.13.1 material stainless steel
2.13.1.1 grade 1.4301 (V2A)
2.13.2 minimum thickness mm 1.5
2.14 Roof
0C
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 29 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
2.14.1 material stainless steel
2.14.1.1 grade 1.4301 (V2A)
2.14.2 minimum thickness mm 1.5
2.15 Doors
2.15.1 material stainless steel
2.15.1.1 grade 1.4301 (V2A)
2.15.2 minimum thickness mm 2
2.15.3 door stoppers provided yes/no yes
2.15.4 door opening angle deg 120
2.16 Sun shade
2.16.1 material stainless steel
2.16.1.1 grade 1.4301 (V2A)
2.16.2 minimum thickness mm 2
2.16.3 minimum clearance to cubicle wall mm 15
2.17 Equipment mounting plates
2.17.1 material galvanised steel sheet
2.17.1.1 grade
2.17.2 applicable standards
2.17.3 minimum thickness mm 2
2.18 Partition (if applicable)
2.18.1 material galvanised steel sheet
2.18.1.1 grade
2.18.2 minimum thickness mm 1.5
2.19 Panel access
2.09.1 front yes
2.09.2 rear (if applicable) yes
2.20 Maximum inside temperature of cubicle 55
2.21 Lifting lugs provided yes/no yes
0C
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 30 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
C. Wiring
2.21 Material
2.21.1 stranded copper wires for cross-sections yes/no yes
2.22 Cross-sections
2.22.1 power circuits (min) 1.5
2.22.2 control circuits 1
2.22.3 CT circuits (min) 2.5
2.22.4 VT circuits (min) 1.5
2.22.5 Telecommunication/control/protection connections
2.22.5.1 external wiring 1.5
2.22.5.2 other wiring 0.5
2.23 Arrangement
2.23.1 Telecommunication/control/protection connections screened pairs
2.24 Colors
2.24.1 control circuits
2.24.1.1 black yes/no
2.24.1.2 grey yes/no
D. Terminal Blocks
2.25 Manufacturer
2.25.1 name
2.25.2 country of manufacturing
2.25.3 catalogue number
2.26 Applicable standards or equivalent IEC 60947-7-1
2.27 Type
2.27.1 clamping yoke yes/no
2.27.2 plu-in spring clamp yes/no
>2.5mm2 else solid copper wires
mm2
mm2
mm2
mm2
mm2
mm2
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 31 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
2.28 Color beige
2.29 Dimensions (of one terminal)
2.29.1 length mm
2.29.2 width mm
2.29.3 height
2.29.3.1 Type 1 mm
2.29.3.2 Type 2 mm
2.29.3.3 Type 3 mm
2.30 Material polyamide
2.30.1 type PA
2.30.2 UV stabilised
2.30.2.1 applicable standards IEEE G53/26/23
2.30.3 flammability grade
2.30.3.1 applicable standards UL 94
2.30.3.2 class 5V or V0
2.31 Maximum continuous working temperature 120
2.32 Short-time temperature rise (IEC 60216) 200
2.33 Cable size to be terminated
2.33.1 minimum 0.5
2.33.2 maximum 10
2.34 Spare terminals % 10
2.35 Terminal Marking
2.35.1 Color of letters black on white
2.35.2 Power Circuits (motors, etc.)
2.35.2.1 Phase R R on red ground
2.35.2.2 Phase Y Y on yellow ground
2.35.2.3 Phase B B on blue ground
2.35.2.4 Neutral NP on black ground
0C
0C
mm2
mm2
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 32 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
2.35.2.5 Earthing Conductor PE on green ground
2.35.3 Current Transformer Circuits (according to IEC)
2.35.3.1 Phase R on red ground
2.35.3.2 Phase Y on yellow ground
2.35.3.3 Phase B on blue ground
2.35.4 Voltage Transformer Circuits (according to IEC)
2.35.4.1 Phase R on red ground
2.35.4.2 Phase Y on yellow ground
2.35.4.3 Phase B on blue ground
2.35.5 110 Vdc Circuits
2.35.5.1 Positive P on green ground
2.35.5.2 Negative N on grey ground
2.36 Isolation links provided yes/no yes
2.37 Testing sockets provided yes/no yes
2.38 Arresters are provided
2.38.1 telephone cores yes/no yes
2.38.2 protection cores yes/no no
2.39 Isolation transformers provided
2.39.1 protection cores yes/no
2.39.2 control cores yes/no
2.40 Short-circuit facilities provided for CT terminals yes/no yes
2.41 Easily accessible from the floor level yes/no yes
2.42 Minimum numbers of terminals
2.42.1 protection cubicle
2.42.1.1 protection No.
2.40.1.2 control No.
2.42.2 local/remote control No.
2.42.3 local/remote control (transformer) No.
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 33 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
2.42.4 marshalling cubicle for 17 pair protection/telephone cable
2.42.4.1 protection No. 12
2.42.4.2 telephone No. 30
2.42.5 AC Distribution No.
2.42.6 DC Distribution No.
2.42.7 battery chargers, voltage control units No.
2.42.8 uninterruptable power supply (UPS) No.
2.42.9 tele-communication No.
2.42.10 fire fighting No.
2.42.11 air conditioning No.
2.42.12 interfacings No.
2.42.13 other free-standing cubicle No.
2.42.14 other wall-mounted cubicle No.
2.43 Mounting rail
2.43.1 type TS 35 x 15mm
2.43.2 applicable standards DIN EN 46277
2.44 Min. clearances
2.44.1 between two rows of terminal blocks mm 150
2.44.2 between first row and the cable gland plate mm 250
E. Contactor
2.45 Manufacturer
2.45.1 name
2.45.2 country of manufacturing
2.45.3 catalogue number
2.46 Applicable standards or equivalent
2.47 Type
2.48 Number of poles No. 3
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 34 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
2.49 Lifetime operation under rated current switching No. 100,000
F. Auxiliary Contactor
2.50 Manufacturer
2.50.1 name
2.50.2 country of manufacturing
2.50.3 catalogue number
2.51 Applicable standards or equivalent
2.52 Type
2.53 Number of poles No.
2.54 Lifetime operation under rated current switching No. 100,000
G. MCB
2.55 Manufacturer
2.55.1 name
2.55.2 country of manufacturing
2.55.3 catalogue number
2.56 Applicable standards IEC 60947-2
2.57 Type molded case
H. Strip Fuse Ways
2.58 Manufacturer
2.58.1 name
2.58.2 country of manufacturing
2.58.3 catalogue number
2.59 Applicable standards or equivalent IEC 60269-1
2.60 Type
2.61 Fuses
2.61.1 Manufacturer
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 35 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
2.61.1.1 name
2.61.1.2 country of manufacturing IEC 60269-1
2.61.1.3 catalogue number
2.62 Applicable standards or equivalent
2.63 Type
2.64 Fuse supervision provided yes/no yes
I. Indicator Lamps
2.65 Manufacturer
2.65.1 name
2.65.2 country of manufacturing
2.65.3 catalogue number
2.66 Applicable standards or equivalent IEC 60983, 61554
2.67 Type
2.68 Minimum diameter mm 16
2.69 Lamps are panel mounting type yes/no yes
2.70 Lamps are filament type yes/no yes
2.71 Lamps have translucent covers yes/no yes
J. Push Buttons
2.72 Manufacturer
2.72.1 name
2.72.2 country of manufacturing
2.72.3 catalogue number
2.73 Applicable standards or equivalent IEC 60629, 61554
2.74 Type
2.75 Minimum diameter mm 16
2.76 Push button is push to actuate type yes/no yes
2.77 Contacts
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 36 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
2.77.1 silver yes/no
2.77.2 silver alloy yes/no
K. Selector Switch
2.78 Manufacturer
2.78.1 name
2.78.2 country of manufacturing
2.78.3 catalogue number
2.79 Applicable standards or equivalent IEC 61058, 61554
2.80 Type
2.81 Switch is panel mounted rotary type yes/no yes
2.82 Switch is with oval handle yes/no yes
2.83 Contacts are spring assisted yes/no yes
2.84 Voltmeter switch has 4 stayput positions yes/no yes
L. Ventilation *
2.85 Fans (if applicable)
2.85.1 manufacturer
2.85.1.1 name
2.85.1.2 country of manufacturing
2.85.1.3 catalogue number
2.85.2 applicable standards or equivalent IEC
2.85.3 type
2.85.4 MCB for fans
2.85.4.1 manufacturer
2.85.4.1.1 name
2.85.4.1.2 country of manufacturing
2.85.4.1.3 catalogue number
2.85.4.2 applicable standards or equivalent IEC
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 37 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
2.85.4.3 type molded case
2.85.4.4 no. of poles 1
2.86 Louvers (if applicable)
2.86.1 manufacturer
2.86.1.1 name
2.86.1.2 country of manufacturing
* heat dissipation calculation of equipment inside panel/cubicleshall be submitted for approval!
M. Anticondensing Heater
2.87 Manufacturer
2.87.1 name
2.87.2 country of manufacturing
2.87.3 catalogue number
2.88 Applicable standards or equivalent IEC
2.89 Type
2.90 Control system
2.90.1 thermostat yes/no yes
2.90.1.1 setting 20 to 80
2.90.2 humidistat yes/no yes
2.90.2.1 setting
2.91 MCB for anticondensing heater
2.91.1 manufacturer
2.91.1.1 name
2.91.1.2 country of manufacturing
2.91.1.3 catalogue number
2.91.2 applicable standards or equivalent IEC
2.91.3 type molded case
2.91.4 no. of poles 1
0C
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 38 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
N. Lighting (if applicable)
2.92 Manufacturer
2.92.1 name
2.92.2 country of manufacturing
2.92.3 catalogue number
2.93 Applicable standards or equivalent IEC
2.94 Type florescent
2.94.1 electronic/HF switched type yes/no yes
2.95 Door switch provided yes/no yes
2.96 MCB for lighting yes/no yes
2.96.1 manufacturer
2.96.1.1 name
2.96.1.2 country of manufacturing
2.96.1.3 catalogue number
2.96.2 applicable standards or equivalent IEC
2.96.3 type molded case
2.96.4 no. of poles 1
O. Socket (if applicable)
2.97 Manufacturer
2.97.1 name
2.97.2 country of manufacturing
2.97.3 catalogue number
2.98 Applicable standards or equivalent BS 1363
2.99 Type cubicle mounted
2.100 RCCB for socket yes/no yes
2.100.1 manufacturer
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 39 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
2.100.1.1 name
2.100.1.2 country of manufacturing
2.100.1.3 catalogue number
2.100.2 applicable standards or equivalent BS
2.100.3 type molded case
2.100.4 no. of poles 1
P. Cubicle Vermin Proof? yes/no yes
Q. Corrosion Protection Details as per requirement specified in standard technical specification
part: D-AA-CORR
R. Earthing Arrangement
2.101 Earth bar of each compartment
2.101.1 material copper
2.101.2 minimum cross-section
2.101.3 dimension
2.101.3.1 width mm 5
2.101.3.2 height mm 40
2.102 Interconnection between compartments, etc.
2.102.1 material stranded copper
2.102.2 minimum cross-section 70
2.103 Door earthing
2.103.1 material highly flexiblestranded copper
2.103.2 cross-section 16
2.103.3 color green-yellow
2.104 Number of connections for external earthing No. 1
2.105 Gland earthing
mm2
mm2
mm2
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 40 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
2.105.1 material stranded copperconductor
2.105.2 minimum cross-section 120
S. Danger Sign Details
2.106 Material stainless steel
2.106.1 grade 1.4301 (V2A)
2.107 Width mm
2.108 Height mm
2.109 Language
2.109.1 Arabic and English yes/no yes
2.110 Letters
2.110.1 quality of paint sun light proof, no fading
2.110.2 height of letters mm 75
2.111 Colors
2.111.1 MV cubicles
2.111.1.1 background red
2.111.1.2 letters white
2.111.2 AC distribution cubicles
2.111.2.1 background yellow
2.111.2.2 letters black
2.111.3 DC distribution cubicles
2.111.3.1 background white
2.111.3.2 letters black
2.111.4 protection cubicles
2.111.4.1 background white
2.111.4.2 letters red
2.111.5 emergency system cubicles
2.111.5.1 background red
mm2
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 41 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
2.111.5.2 letters white
2.112 Fixing bolts
2.112.1 material stainless steel
2.112.1.1 grade 1.4301 (V2A)
2.113 Numbers No.
T. Identification Sign Details
2.114 Material stainless steel
2.114.1 grade 1.4301 (V2A)
2.115 Width mm
2.116 Height mm
2.117 Language
2.117.1 Arabic and English yes
2.118 Letters
2.118.1 quality of paint sun light proof, no fading
2.118.2 height of letters mm 75
2.119 Colors
2.119.1 MV cubicles
2.119.1.1 background red
2.119.1.2 letters white
2.119.2 AC distribution cubicles
2.119.2.1 background yellow
2.119.2.2 letters black
2.119.3 DC distribution cubicles
2.119.3.1 background white
2.119.3.2 letters black
2.119.4 protection cubicles
2.119.4.1 background white
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 42 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
2.119.4.2 letters red
2.119.5 emergency system cubicles
2.119.5.1 background red
2.119.5.2 letters white
2.120 Fixing bolts
2.120.1 material stainless steel
2.120.1.1 grade 1.4301 (V2A)
2.121 Numbers No. 1
U. Lifting Devices Details (if applicable)
2.122 Free-standing cubicle
2.122.1 number 4
V. Provision of Safety Equipment
2.123 Shock treatment chart yes/no yes
W. Pocket on Door for Drawings yes/no yes
2.124 Material galvanised steel
X. Door Fixing Devices Provided (to keep door in yes/no yesopen position in case of maintenance)
Y. Door Locks and Keys yes/no yes
2.125 Manufacturer
2.125.1 name YALE or equivalent
2.125.2 country of manufacturing
2.126 Keys numbers for any lock or padlock No. 6
Z. Stainless steel used for handles, hinges, signs,bolts, nuts, etc.
2.127 Grade 1.4301 (V2A)
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 43 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
3.00 ELECTRICAL DATA
A. Wiring
3.01 Power frequency withstand voltage 2
B. Terminal Blocks
3.02 Material
3.02.1 applicable standards IEC 60093IEC 60167IEC 60112DIN VDE 0303-2
3.02.2 dielectric strength kV/cm 8
3.02.3 surface resistance x cm 10^12
3.03 Nominal Voltage
3.03.1 type 1 V 800
3.03.2 type 2 V 400
3.03.3 type 3 V 800
3.03.4 type 4 V 400
3.03.5 type 5 V 800
3.03.6 type 6 V 800
3.04 Nominal Currents
3.04.1 type 1 A 41
3.04.2 type 2 A 16
3.04.3 type 3 A 76
3.04.4 type 4 A 57
3.04.5 type 5 A 57
3.04.6 type 6 A 101
3.05 Rated surge voltage
3.05.1 type 1 8
kV ac/1min
kVac
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 44 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
3.05.2 type 2 6
3.05.3 type 3 8
3.05.4 type 4 6
3.05.5 type 5 8
3.05.6 type 6 8
3.06 Power frequency withstand voltage between terminals
3.06.1 protection cubicle 15
3.06.2 marshalling cubicle for 17 pair protection/telephone cable
3.06.2.1 protection terminals 15
3.06.2.2 telephone terminals 15
3.06.2.3 surge arrester magazine base and terminals 15without arresters
3.06.3 local/remote control cubicle 2
3.06.4 local/remote control (transformer) cubicle 2
3.06.5 AC distribution cubicle 2
3.06.6 DC distribution cubicle 2
3.06.7 battery chargers, voltage control cubicle 2
3.06.8 uninterruptable Power Supply (UPS) cubicle 2
3.06.9 tele-communication cubicle 2
3.06.10 fire fighting cubicle 2
3.06.11 air conditioning cubicle 2
3.06.12 interfacings cubicle 2
3.06.13 other free-standing cubicle 2
3.06.14 other wall-mounted cubicle 2
C. Contactor
3.07 Rated voltages
kVac
kVac
kVac
kVac
kVac
kVac
kVac
kVac
kVac
kVac
kVac
kVac
kVac
kVac
kVac
kVac
kVac
kVac
kVac
kVac
kVac
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 45 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
3.07.1 main contacts 400
3.07.2 control contacts 110
3.08 Limits of operation
3.08.1 supply voltage variation % +/- 10
3.08.2 supply frequency variation % +/- 5
3.08.3 drop out voltage %
3.09 Rated breaking capacity kA
3.10 Rated making capacity kA
3.11 Rated thermal capacity kA
3.12 Coil
3.12.1 rated voltage
3.12.2 burden VA
D. Auxiliary Contactor
3.13 Coil
3.13.1 rated voltage
3.13.2 burden VA
3.14 Number of contacts 2NO+2NC
E. MCB
3.15 Rated voltage 230
3.16 A
3.17 Rated short-circuit current, 1s kA
3.18 Rated breaking current A
3.19 Rated making current A
F. Fuses
3.20 Rated voltage 230
3.21 Rated minimum breaking current
Vac
Vdc
Vdc
Vdc
Vac
Rated current carrying at max. 500C
Vac
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 46 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
3.21.1 type 1 A
3.21.2 type 2 A
3.21.3 type 3 A
G. Indicator Lamps
3.22 Rated voltage V 110 +10%-15%
H. Push Buttons
3.23 Rated voltage
3.23.1 AC V 230
3.23.2 DC V 220
3.24 Rated make, continuously, break current
3.24.1 AC, pf = 0.5 A 10
3.24.2 DC A 10
I. Selector Switch
3.25 Contact ratings for continuos duty, pf = 0.5 A 10
3.26 Rated voltage 230
J. Ventilation Motor (if applicable)
3.27 Rated voltage
3.27.1 AC V 230
3.27.2 DC V 110
3.28 Rated power W
3.29 MCB for fans
3.29.1 rated current A
K. Anticondensing Heater
3.30 Rated voltage 230
3.31 Rated current A
Vac
Vac
-
305661956.xls
___________________________________________________________________________________________________________________
TENDERER`s STAMP SIGNATURE
Page 47 of 45
PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURESPanels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No. REQUIRED TENDERED
3.32 Power W 70
3.33 MCB for anticondensing heater
3.33.1 rated current A
L. Lighting (if applicable)
3.34 Rated voltage 230
3.35 Rated power W 40
3.36 MCB for lighting yes/no yes
3.36.1 rated current A 6
M. Socket (if applicable)
3.37 Rated voltage 230
3.38 RCCB for socket yes/no yes
3.38.1 rated current A 16
4.00 SUPPORTING DOCUMENTS
4.01 Technical literature enclosed yes/no yes
4.02 Standard conditions of installation enclosed yes/no yes
4.03 Relevant drawings enclosed yes/no yes
Vac
Vac
CSToCDS