d iscrimination of magnetic inrush current from fault
TRANSCRIPT
Discrimination of magnetic inrush current from fault
current in transformer
- A new approach
Yashasvi Tripathi 1, Kushagra Mathur 2, Dr S.V.N.L. Lalitha 3,
Dr M. Ramamoorty 4
Department of EEE, KL University Green fields, Vaddeswaram, Guntur, AP,
522502, INDIA
[email protected],[email protected],
[email protected], [email protected]
Abstract
It is a challenge for the power engineers all around the globe to find a fast and accurate method
of discriminating magnetic inrush currents from fault currents in Power Transformers.
Though the previously known inrush current detection techniques are able to do it but they
are less reliable and slow to respond due to use of filter. A new approach of discriminating
inrush current from fault current in a fast and precise manner is developed. Based on the
asymmetry of inrush current waveform, a unique criteria for discrimination is established.
MATLAB coding is developed to model a transformer for the analysis. Various switching
instants on the supply voltage waveform have been considered at intervals of 900 from 00 to
3600 with different residual flux in magnetic core.
Keywords: Inrush current, Power transformers, Discrimination, Asymmetry, Residual flux.
1. Introduction
Transformer is a static device which transfers power from one electrical circuit to another at a
constant frequency. It is a valuable electrical component in power system both at transmission
as well as distribution end. The power is transmitted at a very high voltage by using step up
transformers to reduce the transmission line losses in the power system which improves the
overall efficiency of the transmission. At the distribution end step down transformers are used
to get the voltage at distribution level, so transformer is having dual action.
International Journal of Pure and Applied MathematicsVolume 114 No. 12 2017, 615-625ISSN: 1311-8080 (printed version); ISSN: 1314-3395 (on-line version)url: http://www.ijpam.euSpecial Issue ijpam.eu
615
Due to the above properties Transformers are one of the most important part of Power System.
So it is anticipated from the power engineers to have a proper and fast protective scheme for
its safety and to ensure its hassle free operation.
Among many one of the most common reason for mal operation of differential relays used for
transformer protection is high magnetic inrush current. The relay sometimes is unable to
discriminate between an inrush current and fault current within the first cycle hence it issues a
trip signal to the circuit breaker which causes an unwanted interruption in power.
When a transformer is energized at no load or lightly loaded condition for the first few cycles
it draws a very high amount of current known as magnetic inrush current. Magnetising current
is the one which is responsible for the development of rated flux in the transformer. Inrush
current peak is in the order of 5 to 10 times of the full load current. Due to this high current
magnitude it becomes difficult for a relay to distinguish between inrush and fault current which
causes its mal operation by giving tripping signal which causes discontinuity in power
transmission.
So an accurate identification of currents in a transformer is the key necessity for preventing
mal-operation of the protection system under different high current conditions which include
magnetising inrush current, external and internal fault current, etc. The requirement for
transformer protection has become major issue due to the need for precise, quick, and reliable
distinction between magnetic inrush current and internal fault current.
The magnetic inrush current has a good percentage of second harmonics unlike this fault do
not have large second harmonic. The percentage of second harmonic component of the current
to its fundamental component is utilized (also known as SHR) for discriminations .In this
method the relay should block the current when its ratio exceeds the pre-set value [1]. Most of
the viable differential relays are provided by the SHR method to prevent tripping due to inrush
current conditions. The ratio has been usually set in the range of 12–20%. But this method may
fail to differentiate high inrush currents when transformers are energized with some significant
residual flux.
The next method utilises the duration of gap between the zero crossing instants of the current
which is known as gap detection technique [2] is being used by some relays to identify the fault
and inrush currents. But, this gap detection method is liable to mal-operate when saturation of
CT takes place which in general is caused by high DC component present in the inrush current.
A number of algorithms have also been developed to overcome this serious problem which
consists of Wavelet Transform [3], ANN [4] and fuzzy logic [5]. Yet some of these methods
require a huge data for online training purpose, computational liability on the relay is
increased, and are difficult to predict counter to high frequency noise signal [6].
Due to the above mentioned drawbacks these methods have not reached a practical level yet.
So the SHR and gap detection are widely used methods in practise in spite of their limitations
of detecting high inrush currents till date.
2. Transformer Protection
Transformer is a static device which can transfer power from one electrical circuit to another
maintaining constant frequency. It is an important electrical component used in power system
to reduce the transmission losses.
We know from Faraday’s 2nd law emf equation,
E = N 𝒅ɸ
𝒅𝒕 ...( 2.1)
Where, N= number of turns , ɸ= flux linkage ,
E= Em sin 𝝎t , Em = Peak value of voltage, 𝝎 = Angular frequency.
International Journal of Pure and Applied Mathematics Special Issue
616
Flux linkage is,
ɸ = 𝑬𝒎 𝒔𝒊𝒏 𝝎𝒕
𝑵 𝒅𝒕 ...(2.2)
Applying KVL in primary loop,
Em sin 𝝎t – i*r1 – L1 𝒅𝒊
𝒅𝒕 =0 …(2.3)
So current through transformer ,
i = 𝑬𝒎
𝒁{sin (𝝎t +) – α} + c 𝒆(
−𝒓𝟏∗𝒕
𝑳𝟏) ….(2.4)
where α = 𝝎𝐿1
𝑟1 , r1= Primary winding resistance , L1 = Primary winding reactance.
If the magnetic core is not saturated, then the inductance L1 is high and constant. The current
‘i’ is magnetising current with small amplitude. If the core gets saturated then the inductance
L1 is very low and current ‘i’ will have very large amplitude.
Fig. 1: Transformer under no load
The above fig. represents a transformer under no load condition with sinusoidal supply.
The equivalent circuit of transformer is shown in the figure below.
where, N1 = Primary turns , N2 = Secondary turns
Fig. 2: Transformer equivalent circuit
A. Transformer protection using differential relay: In general, for transformer protection differential relays are popularly used. The differential
relay works on the principle of difference current flowing through primary and secondary coils.
If the differential current also known as spill current is zero then the relay does not operate or
remains in the blocking region but if the spill current is non-zero then the relay operates.
Differential relay only works for internal faults and remains un-operative for external (through)
faults. Fig. 2.3 shows a typical differential relay scheme for transformer protection against
internal fault.
Fig. 3: A differential relay for transformer protection
International Journal of Pure and Applied Mathematics Special Issue
617
In differential protection the difference of two currents is fed to the relay operating coil. So for
the external faults the currents in the two C.Ts must be equal in magnitude and opposite in
phase hence the spill current becomes zero.
B. Cause for mal operation of differential relay:
Differential Relays are widely used in the transformer protection but may maloperate due to
system disturbances, such as:
1. Over excitation: Over excitation [7] of transformer implies the level of magnetic flux is higher than the
designed level. This leads to saturation of the core drawing large current. This can leads
to severe fault and mal-operation of the differential relay.
2. CT saturation: It is a physical phenomenon that happens when all magnetic domain on ferromagnetic
material are already aligned and further flux increment does not takes place. The current
transformer [8] implication on secondary current may be different. Saturated core does not
imply constant flux increase or high current on secondary. Generally improper selection of
CT ratio and high DC offset in line current under fault current result in saturation of CTs.
3. Large magnetizing inrush current:
The large current drawn by transformer on no load when the transformer is energised and
will last only for few cycles. The magnitude of inrush[9] is generally several times more
than rated current .As its magnitude is near to fault current so there is a chance of tripping
of over current relay.
3. Inrush currents and types
A. Inrush current and its types: Magnetic inrush currents are the transient no load current which has high magnitude (5 to 10
times full load current) drawn by the primary winding of transformer. As discussed earlier
primary current develops rated flux in the transformer core rate of change generates counter
emf in the winding. But sometimes its magnitude becomes comparable to the fault current and
hence the relay is unable to discriminate between the inrush and fault current. A typical inrush
current waveform is shown in fig. 3.1.
Fig. 4: An inrush current waveform
International Journal of Pure and Applied Mathematics Special Issue
618
The inrush currents are mainly classified in three types:
(i) Inrush current during energisation
It occurs when transformer is brought from off state to energised state.
(ii) Inrush current during recovery
It occurs when the voltage is recovered after a small dip or disruption is restored.
(iii) Inrush current during operation or Sympathetic inrush current
It occurs when transformer is energised which is in parallel to an already excited
transformer. The sudden drop in voltage caused due to energisation can cause inrush current
in already excited transformer.
Among the above three types of inrush currents [10] energisation is the most common
which generates the largest current magnitude.. To understand inrush analytically we have
to recognize the relationship between voltage applied to transformer and transformer’s
magnetic core flux .That relation is
E= dλ(t) / dt
Or λ (t) = ∫ e(t) dt + λ (0) ….(3.1)
Where λ = Flux linkage and E =Induced emf λ (0) =Residual flux
It is observed that the extreme possible value of λ after energisation is 2 λm + λ (0). The relation
between inrush current and λ is given by the saturation characteristics of transformer core.
The protection system must be able to discriminate between the inrush current and actual short
circuit.
B. Methods for Discrimination of inrush current from fault current: 1. Second harmonic Restraint Method Inrush current is dominated by second harmonic which is used in most of the differential relays
for transformer, to discriminate inrush current and fault current. The harmonic sensing relays
most commonly block operation if the harmonic(s) exceed a given percentage of the
fundamental component. Some relays use the harmonic to increase the restraint current.
Generally differential relays are aided by second harmonic restraint to block tripping due to
magnetic inrush current. Pickup ratio is in range of nearly 12 to 20 %. An S.H.R. relay is shown
in the figure below.
Rest
rain
ing
coil
Operation coil
Harmonic bias
Through bias
Transformer
High Set Unit
XLXC
Fig. 5: S.H.R. Relay circuit
2. Gap Detection Approach As shown in the figure below, the time difference in each cycle is called as dwell time [11] in
this region differential current is almost zero. So to identify the inrush current check where
current is becoming less then even 5% of the rated current.
International Journal of Pure and Applied Mathematics Special Issue
619
This criterion is known as the gap detection approach. CT saturation due to both the short
circuit fault and inrush currents adversely affects the detection criteria. When CT saturation
happens after a small period subsequent to an internal fault, output currents of CT may be
distorted so huge harmonic components are also present. Consequently, there is possibility that
second harmonic criteria operates inaccurately and blocking of differential relay takes place.
Fig. 6: Gap detection technique
Following observations about the two methods discussed above,
CT saturation due to both short circuit fault and inrush currents adversely affects inrush current
detection.
3 A variety of algorithms recently presented include artificial neutral network (ANN), fuzzy logic and wavelet analysis ANN is a novel approach which is used in online detection to discriminate the inter turn fault
and magnetizing inrush current, and also the fault location i.e., whether the turn to turn fault
lies in secondary winding or primary winding through the use of discrete wavelet transform
and artificial neural networks.
Wavelet Transform [12] is used to analyse the signal for short duration for its spectral contents.
Another method using operational matrices and Hartley transform [13] is proposed for
evaluation of inrush current and its simulation.
Following observations are made,
These methods need a large data set for training.
Impose a high computational burden on relay.
Depend on the transformer parameters or initial conditions.
Seem to be unpredictable against high frequency noise.
C. Proposed strategy: A new approach of discriminating inrush current from fault current in fast and precise manner
is developed. Based on the asymmetry of inrush current waveform a unique criteria for
discrimination is established.
It is observed that the instant at which the switching takes place with respect to voltage
waveform has a significant role on the peak value of current. Several case studies have been
conducted for various switching instants such as when the voltages waveform crosses zero, at
its positive peak, at its negative peak, etc. Intermediate switching instants have also been
considered at an interval of 900 from 00 to 3600 on the supply voltage waveform which are
thoroughly discussed in results and conclusions.
International Journal of Pure and Applied Mathematics Special Issue
620
4. Output Waveforms
For the proposed approach single phase transformer is modelled for two different conditions
which are Inrush current with open secondary, Short circuit at secondary with fault resistance
and Internal fault for primary turns shorted. The tool used is MATLAB 2011 version to carry
out all the simulations.
A. Parameters:
1 ɸ Saturable Transformer having 2 winding with following parameters,
Power Rating: 9.6 KVA
Voltage Rating: 300 V/ 150 V
Primary Winding: r1= 0.06 Ω x1 = 0.3 Ω
Secondary winding: r2= 0.03 Ω x2 = 0.15 Ω
Core loss resistance: Rc = 1200 Ω
Unsaturated magnetizing reactance: Xm = 600 Ω
Unsaturated inductance: Lu = 1.91 H
Saturated inductance: Ls = 0.191 H
Peak value of rated magnetising current in steady state: im = 0.452 A
Frequency: 50 Hz
3 separate conditions are considered for various phase angles:
Condition 1: Inrush current with open secondary.
Condition 2: Secondary short circuited with fault resistance.
Condition 3: Internal fault for some primary turns shorted.
300 V (rms) supply is given to the transformer under the conditions mentioned above and the
developed model is run for 0.2 seconds (10 cycles) for various phase angles. Based on that the
waveforms are obtained then FFT is performed to obtain fundamental, 2nd harmonic, 5th
harmonic and 7th harmonic components. On the basis of the results obtained, logic for the relay
is developed. For fault case the fault resistance is varied for 4 different values which are 𝝎𝑳
𝟏𝟎 ,
𝝎𝑳
𝟕 ,
𝝎𝑳
𝟓 and
𝝎𝑳
𝟑 .Where, 𝜔 = 314 𝑟𝑎𝑑/𝑠 and L=0.191 H then for internal fault two cases
were considered i.e., 5% and 10% primary turns were shorted.
B. Output waveforms:
For Magnetising current
For Residual flux = 0
International Journal of Pure and Applied Mathematics Special Issue
621
Fig. 7 : Magnetising current for zero residual flux
For Residual flux = 2.7 mWb
Fig. 8 : Magnetising current for 2.7 mWb residual flux
For Internal fault: For 5% turns shorted:
Fig. 9: Fault current for 5% turns shorted
International Journal of Pure and Applied Mathematics Special Issue
622
C. Observation Table : FFT analysis of the waveforms above is done and both +ve and –ve peaks for the first cycle
are noted and tabulated below for various switching instants :
For Residual flux =0
5. CONCLUSION
This paper highlights a simple, fast and cost effective way of distinguishing magnetising current from a fault
current just by checking the positive and negative peaks of the current waveform.
For inrush current case, its magnitude is always less than magnetising current peak value (i.e., 0.452 A) in one
of the half or in either of the halves for first few cycles.
In case of through fault current, its magnitude will be always greater than magnetising current peak value in
either of the halves for first few cycles. In case of an internal fault it takes 3 to 4 cycles for exceeding
magnetising current in both cycles. So for internal fault logic will be similar to external fault if both halves
For α = 900
Current Inrush Internal
Rf =
5.997
Rf =
8.567
Rf =
11.99
DC
comp
(%) 10.25 51.27 67.74 67.05 65.694
Fund
(%) 100 100 100 100 100
2nd (%) 26.51 42.85 50.57 50.69 50.65
5th (%) 11.58 22.14 22.06 22.18 22.18
7th (%) 9.22 17.57 18.05 17.63 17.58
1st peak 0.08 0.85 -3 -2.5 -2
2nd peak -0.4862 -14.42 -14 -13 -12
For α = 00
Current Inrush Internal
Rf =
5.997
Rf =
8.567
Rf =
11.99
DC
comp
(%) 0.23 0.51 0.461 0.463 0.467
Fund
(%) 100 100 100 100 100
2nd (%) 27.27 50 47.83 47.83 47.83
5th (%) 9.09 19.23 21.73 21.73 21.73
7th (%) 9.09 15.38 17.39 17.39 17.39
1st peak 1.4 15.41 12 11.5 10.5
2nd peak -3.9e-3 -0.07 -4 -4.7 -5
For α = 1800
Current Inrush Internal
Rf =
5.997
Rf =
8.567
Rf =
11.99
DC
comp
(%) 18.65 38.67 34.16 36.51 39.19
Fund
(%) 100 100 100 100 100
2nd (%) 26.44 50 50.56 50.71 50.6
5th (%) 11.51 22.05 22.13 22.13 22.13
7th (%) 9.17 17.54 17.61 17.58 17.62
1st peak 0.06 2.82 7 7 7
2nd peak -0.788 -12.42 -7 -6.5 -6
For α = 2700
Current Inrush Internal
Rf =
5.997
Rf =
8.567
Rf =
11.99
DC
comp
(%) 20.86 34.59 37.1 34.33 30.75
Fund
(%) 100 100 100 100 100
2nd (%) 26.26 50.83 50.69 50.96 50.89
5th (%) 11.11 22.5 22.22 21.93 22.15
7th (%) 9.99 17.5 17.36 17.42 17.36
1st peak 1.364 17.09 15 14 12.5
2nd peak -2e-3 1.25 -1.5 -2.5 -4.5
International Journal of Pure and Applied Mathematics Special Issue
623
exceed 0.452 A value otherwise both halves are of same polarity so it can be properly discriminated from
inrush current. This method can help fast detection of magnetising current whereas previously known methods
utilise filter which causes time delay and increases computational burden on the relay. So just by incorporating
comparator the fault and inrush currents can be discriminated.
REFERENCES
[1] Pei L, Malik OP, Deshu C, Hope GS, Yong G. Improved operation of differential protection of power
transformers for internal faults. Power Deliv, IEEE Trans 1992;7:1912–9
[2] Mekic F, Girgis R, Gajic Z, teNyenhuis E. Power transformer characteristics and their effect on
protective relays. Presented at the 33rd Western protective relay conference, October 17–19, 2006.
[3] Rasoulpoor M, Banejad M. A correlation basedmethod for discrimination between inrush and short circuit
currents in differential protection of power transformer using discrete wavelet transform: theory,
simulation and experimental validation. Int J Electr Power Energy Syst October 2013; 51:168–77.
[4] Puneet Kumar Singh , D K Chaturvedi. Modeling and Simulation of Single-Phase Transformer Inrush
Current using Neural Network. Control Theory and Informatics Vol.3, No.2, 2013- National Conference
on Emerging Trends in Electrical, Instrumentation & Communication Engineering
[5] Wiszniewski A, Kasztenny B. A multi-criteria differential transformer relay based on fuzzy logic. Power
Deliv, IEEE Trans 1995;10:1786–92
[6] Hooshyar A, Afsharnia S, Sanaye-Pasand M, Ebrahimi BM. A new algorithm to identify magnetizing
inrush conditions based on instantaneous frequency of differential power signal. Power Deliv, IEEE Trans
2010;25:2223–33.
[7] https://electrical-engineeringportal.com %2F protection-against-overexcitation-of-a-
transformer&usg=AFQjCNEj7QJq.
[8] https://www.google.co.in/url?sa=t&rct=j&q=&esrc=s&source=web&cd=5&cad=rja&uact=8&ved=0ah
UKEwjrmfTo57bQAhXBv48KHfZ_A_sQFgg2MAQ&url=http%3A%2F%2Fwww.gohz.com%2Fwhat-
happens-in-current-transformer-core-during-ct- saturation &usg=AFQjCNGi 5p3ReC9A0uR5bJEnh-
GjnNi4cQ&sig2=cwniyL--lPm-gexXmTgeUQ
[9] http://www.google.com/url?q=http%3A%2F%2Fwww.ece.mtu.edu%2Ffaculty%2Fbamork%2Fee5220
%2FInrush.pdf&sa=D&sntz=1&usg=AFQjCNHcWsfLj7hHRHmh9V9oOMjTk1Lx0wnSKvx0w3RlUV
AdPtrK7EQ&sig2=6PZQp9z9_0cEhaJeG0RvTA.
[10] https://www.google.co.in/url?sa=t&rct=j&q=&esrc=s&source=web&cd=4&ved=0ahUKEwiRnZ7k_
LbQAhUErI8KHRvlATQQFggqMAM&url=http%3A%2F%2Fwww.electrical4u.com%2Fmagnetizingi
nrush-current-in-power-transformer%2F&usg=AFQjCNHVw6y-4T9pQp
AjymyL4HkpK56fMA&sig2=LXnJaAfouFiXDjpec2QhzQ.
[11] Dashti-Hamed , Mahdi Davarpanah, Majid Sanaye-Pasand, Hamid Lesani. Discriminating transformer
large inrush currents from fault currents electrical power and energy systems 75 (2016) 74-82
[12] Maya.P, S.Vidya shree, Roopasree.K, K.P.Soman. Discrimination of Internal Fault Current and
Inrush Current in a Power Transformer using Empirical Wavelet Transform
[13] M. A. Taghikhani, A. Sheikholeslami and Z. Taghikhani. Harmonic Modeling of Inrush Current in
Core Type PowerTransformers using Hartley Transform. Iranian Journal of Electrical & Electronic
Engineering, Vol. 11, No. 2, June 2015.
International Journal of Pure and Applied Mathematics Special Issue
624
625
626