Level 0: Information
Data SheetD184S073U02
Function– Electromagnetic flowmeters ca
measure the flowrate of liquids,sludges with an electrical condu(opt. 0.5 µS/cm).
Applications– The SM4000 is specially design
pulp & paper and food & beverato measure pulp stocksflows, faphase liquids, mining slurries anpump application).
Instrument Advantages– Digital Signal Processing (DSP)
and accuracy in both flow direcstability.
– Integrated diagnostic tools incluwith the error analysis displayedcontact output for increased op
– Easy to use menudriven operaapplication the configuration. Edisplay is backlighted.
Important Instrument Featu– flowmeter primary designed pe– diameter range from DN 1 to D– accuracy < ± 0.5 of rate– fluid temperatures 40 °C to 13– Hygienic Certification 3A, FML,– liners, PFA, PTFE, hard rubber – standardized installation lengths– Power supply voltage AC/DC
FieldIT
Electromagnetic Flowmeter FSM4000
n be used to accurately slurries, pastes and ctivity of at least 20 µS/cm
ed to measure liquids in the ge industry. It can be used st changing process, two d pulsating flows (piston
assures long term stability tions with absolute zero
ding system monitoring and signalled over a erational reliability.ting structure for asy to read the fullgraphic
resr PEDGuideline 97/23 ECN 1000 [1/25” to 40”]
0 °C (opt. 180 °C) EHEDG
for DIN or ANSI flanges
Electromagnetic Flowmeter FSM4000D184S073U02
Accuracy, Reference Conditions and Operating Principle
Reference Conditions per EN 29104
Fluid Temperature
20 °C ± 2 K
Ambient Temperature
20 °C ± 2 K
Supply Power
Nominal voltage per name plate UN ± 1 %
Reference installation conditions
Upstream > 10 x D, Downstream > 5 x D, D = nominal size of the flowmeter primary
Warm-up Time
30 min
Analog Output Effects
Same as pulse output plus ± 0.1 % of rate ± 0.01 mA
Operating PrincipleFaraday’s Laws of Induction form the basis for the electromagnetic flowmeters. It states that a voltage is induced in a conductor as it moves through a magnetic field.This principle is applied to a conductive fluid which flows through a magnetic field generated perpendicular to the flow direction (see Schematic).The voltage induced in the fluid is maesured at two electordes, installed diametrically opposed. This signal voltage UE is proportional to the magnetic induction B, the electrode spacing D and the average flow velocity v.Noting that the magnetic induction B and the electrode spacing D are constants, a proportionality exists between the signal voltage UE and the average flow velocity v. The equation for the volume flow shows that the signal voltage UE is linear and proportional to the volume flowrate.The induced signal voltage is processed in the converter into scaled, analog and digital signals.
0
0
5
0.5
10
1
20
2
90
9
100 %
10
Acc
urac
y
%
Q
mvs0.5
Range max
789
6
54321
0.5
Pulse Output Q> 0.05 Rangemax ± 0.5 % of rateQ< 0.05 Rangemax ± 0.00025 Rangemax
Fig. 1 Accuracy
UE
y
z
x
BD
E
v
Magnet Coil
Meter Tube inElectrode Plane
Signal electrode
Signal voltage
UE = Signal voltage B = Magnetic induction D = Electrode spacing v = Average flow velocity qv = Volume flowrate
UE ~
qv =
UE ~ qv
B D v⋅ ⋅
D2 π4
v⋅
Fig. 2 Electromagnetic Flowmeter Schematic
2
Electromagnetic Flowmeter FSM4000D184S073U02
Overview, Flowmeter Primary and Converter Design
Weld stubs
Pipe fittingFood industry fitting
Tri-Clamp
External threads
Rigid Flanges Rigid FlangesWafer DesignVariable Connections
DN 3–DN 40 1/10”–11/2”
DN 50–DN 100 2”–4”
DN 3–DN 40 1/10”–11/2”
DN 50–DN 100 2” – 4”
Connection Types
Additional, see Dimensions, Others upon request
Accuracy 0.5 % of rateFlowmeter primary hsg. material Complete stainless steel housing Series 2000 Alum. Series 4000
Flowmeter PrimaryModel Number SE21* SE21F SE21W SE41F
Process Connections DN Inch PN * DN PN DN Inch PN PNWafer Design 3–100 1/104 – W – 3–50 1/102 10–40
65–100 21/2–4 10–16–
Flanged DIN 2501 3–100 1/10–4 – F 3–100 10–40 – DN3–DN1000 10–40Flanged ASME B16.5 3–100 1/104 – F 1/10”–4”150–300 CL/JIS 350 1/102 CL300/JIS
65100 21/24 CL150/JIS1/10”–40” CL150 1/10”–12” CL 300
Food Industry Fitting DIN 11851 3–40 1/101 1/2 40 S 50, 80 2, 3 16 S 65, 100 2 1/2, 4 10 S
– – –
Weld stubs DIN 11850 3–40 1/101 1/2 40 R 50, 80 2, 3 16 R 65, 100 2 1/2, 4 10 R
– – –
Weld stubs DIN 2463 3–40 1/101 1/2 40 Q 50, 80 2, 3 16 Q 65, 100 2 1/2, 4 10 Q
– – –
Weld stubs ISO 2037 25–40 11 1/2 40 P 50, 80 2, 3 16 P 65, 100 2 1/2, 4 10 P
– – –
TriClamp DIN 32676 3–50 1/102 16 T 65, 100 2 1/24 10 T
– – –
External threads ISO 228 3–25 1/101 10 E – – –1/8” Sanitary connectors 1–2 1/251/12 10 B – – –Liner PEEK, Torlon (<DN 3[1/10”])
PFA (>DN 2 [1/12”])PFA PFA Hard rubber, soft rubber,
PTFE, PFA, othersConductivity ≥ 20 S/cm Option ≥ 0.5 µS/cmElectrodes SST No. 1.4571 [316Ti], 1.4539, Hastelloy B2/C4, PlatinumIridium, Tantalum, TitaniumProcess connection material SST1.4404[316L] SST No. 1.4571 [316Ti] – Steel,SSTNo.1.4571[316Ti]Protection Class per EN 60529 IP 67/ IP 68 IP 67 / IP 68 IP 67/ IP 68 IP 67 / IP 68Fluid temperature 25 to 130 °C 40 to 130 °C 25 to 130 °C 25 to 130 °C / 180 °C
ApprovalsHygienic & sterile requirements CIP/SIPcapable FML, 3A, EHEDG CIPcapable
ConverterModel Number S4Supply power 85 – 253 V AC, 24 V AC/DCCurrent output standard 0/2–10 mA, 0/4–20 mAPulse output, 1channel std. active (24 V), optocoupler (220 mA)Ext. Zero return yesExt. Totalizer reset yesForward/reverse metering yesCommunication HARTProtocol® (PROFIBUS PA, FF in preparation)Fluid monitor std. yes, from DN 10 [3/8”] and ≥ 20 S/cmDetection empty pipe yesLocal indicator/totalizer yesAuto. density correction yes, manual entry (totalize and indicate in mass units)Protection Class / EN 60529 IP 67, NEMA 4XHousing Field mount housing
µ
µ
3
Electromagnetic Flowmeter FSM4000D184S073U02
Specifications: Flowmeter Primary
Flow Ranges, Meter Sizes and Pressure Ratings
Information:
When a preamplifier is installed for low conditivity applications and the fluid has a high εr (e.g. demineralized water εr = 78) the fluid velocity is limited < 1 m/s.
Flange Designs and Pressure Ratings
Other meter sizes, press. ratings, temperature classes upon request.
Designs
Meter tube
Stainless steel No. 1.4301 [304]
DN 3 to DN 300 [1/10” to 12”]
Two piece housing: Cast Alum., painted1)
Flanges
Steel, zinc plated, standard Stn. stl 1.4571[316Ti] (≤ DN15[1/2”] standard)
DN 350 to DN 1000 [14” to 40”]
Steel, welded design, painted1)
Flanges
Steel, painted, standard,stn. stl. 1.4571[316Ti]
Connection Box
Body: RAL 70122)
Cover: RAL 90021)
1) Paint coat 80 µm thick, RAL 9002 (white grey), painting see page 8 2) Paint coat 80 µm thick, RAL 7012 (Basalt grey)
Meter Size
Dn Inch
Std. Pressure Rating
PN
Min. Flow RangeFlow Velocity0 to 0.5 m/s
Max. Flow RangeFlow Velocity0 to 10 m/s
1 1/25 1.5 1/17 2 1/12
101010
0 to 0.03 l/min 0 to 0.06 l/min 0 to 0.1 l/min
0 to 0.6 l/min 0 to 1.2 l/min 0 to 2 l/min
3 1/10 4 5/32 6 1/4
404040
0 to 0.2 l/min 0 to 0.4 l/min 0 to 1 l/min
0 to 4 l/min 0 to 8 l/min 0 to 20 l/min
8 5/16 10 3/8 15 1/2
404040
0 to 1.5 l/min 0 to 2.25 l/min 0 to 5 l/min
0 to 30 l/min 0 to 45 l/min 0 to 100 l/min
20 3/4 25 1
4040
0 to 7.5 l/min 0 to 10 l/min
0 to 150 l/min 0 to 200 l/min
32 11/440 11/2
4040
0 to 20 l/min 0 to 30 l/min
0 to 400 l/min 0 to 600 l/min
50 2 65 21/2 80 3
404040
0 to 3 m3/h 0 to 6 m3/h 0 to 9 m3/h
0 to 60 m3/h 0 to 120 m3/h 0 to 180 m3/h
100 4 125 5 150 6
161616
0 to 12 m3/h 0 to 21 m3/h 0 to 30 m3/h
0 to 240 m3/h 0 to 420 m3/h 0 to 600 m3/h
200 8 250 10 300 12
10/1610/1610/16
0 to 54 m3/h’ 0 to 90 m3/h 0 to 120 m3/h
0 to 1080 m3/h 0 to 1800 m3/h 0 to 2400 m3/h
350 14 400 16 450 18 500 20
10/1610/16Cl150
10
0 to 165 m3/h 0 to 225 m3/h 0 to 300 m3/h 0 to 330 m3/h
0 to 3300 m3/h 0 to 4500 m3/h 0 to 6000 m3/h 0 to 6600 m3/h
600 24 700 28 800 32
101010
0 to 480 m3/h 0 to 660 m3/h 0 to 900 m3/h
0 to 9600 m3/h 0 to 13200 m3/h 0 to 18000 m3/h
900 36 100040
1010
0 to 1200 m3/h 0 to 1350 m3/h
0 to 24000 m3/h 0 to 27000 m3/h
Meter Size Flanges Material Press. Rating PED
3 – 251/10” – 1”
DINASME
JIS
SS1.4571[316Ti]or Steel
40 barCL 150, CL 300
10 bar
SEPArt.3Par. 3
3211/4”
DINASME
JIS
SS1.4571[316Ti]or Steel
40 barCL 150, CL 300
10 bar
Con
form
ity E
valu
atio
n pe
r C
ateg
ory
III, M
odul
e B
1 +
D, F
luid
Gro
up 140
11/2”DIN
ASMEJIS
SS1.4571[316Ti]or Steel
40 barCL 150, CL 300
10 bar
502”
DINASME
JIS
SS1.4571[316Ti]or Steel
40 barCL 150, CL 300
10 bar
6521/2”
DINASME
JIS
SS1.4571[316Ti]or Steel
16, 40 barCL 150, CL 300
10 bar
803”
DINASME
JIS
SS1.4571[316Ti]or Steel
40 barCL 150, CL 300
10 bar
1004”
DINASME
JIS
SS1.4571[316Ti]or Steel
16, 40 barCL 150, CL 300
10 bar
1255”
DINASME
SS1.4571[316Ti]or Steel
16, 40 barCL 150, CL 300
1506”
DINASME
SS1.4571[316Ti]or Steel
16, 40 barCL 150, CL 300
2008”
DINASME
SS1.4571[316Ti]or Steel
10, 16, 25, 40 barCL 150, CL 300
25010”
DINASME
SS1.4571[316Ti]or Steel
10, 16, 25, 40 barCL 150, CL 300
30012”
DINASME
SS1.4571[316Ti]or Steel
10, 16, 25, 40 barCL 150, CL 300
350 – 100014” – 40”
DINASME
SS1.4571[316Ti]or Steel
10, 16, 25, barCL 150
4
Electromagnetic Flowmeter FSM4000D184S073U02
Installation Length, Flanged (Short Design)
Meter sizes DN 10 – DN 400 [3/8”–16”] correspond to DIN/ANSI Flanged design VDE/VDI 2641 and the installation lengths defined in DVGW Working Paper, W420 f (Water Totalizers, Design WP ISO 4064 Short as well as ISO 13359).
ANSI CL 150/CL 300
With PFA, installation length, flanged to ISO 13359with PTFE, Hard/soft rubber Installation length, flanged to ISO 13359 or ABB (Installation length Series 1000)
Pipeline Vibrations
Max. allow. 15 m/s2 (10 – 150 Hz)
Temperature Diagram
60
50
10
0
130
Standard Flanges
Ambient Temperature °C
High Temperature Design
Stn. Stl. may be used for the entire range
180 Fluid Temp.°C
25
25
Note: Max. measuring temperature for hard/soft rubber ≤ 90 °C
Fig. 3 Fluid Temperature as a Function of the Ambient Temperature
Max. Allowable Cleaning Temperatures PTFE, PFA Designs
If the ambient temperature >25 °C, the difference must be subtracted from the max. cleaning temperature. Tmax – ∆ °C. ∆ °C = (TAmb. 25 °C [13 °F])
Weight
See Dimensions
Min. allowable Pressure and Fluid Temperature
Other meter sizes, pressure ratings and Temperature Classes upon request
Material strength for Model SE41F
Attention:
Limits for the allowable fluid temperature (TS) and allowable pressure (PS) are a function of the liner and flange materials of the flowmeter (see instrument Name Plate).
Material Strength Curves
Liner: PTFE, hard/soft rubber (limited to 90 °C, 194 °F)
Liner: PTFE, hard/soft rubber (limited to 90 °C, 194 °F)
Liner: PTFE, hard/soft rubber (limited to 90 °C, 194 °F)
CIPCleaning LinerPrimary
Tmax °C tmaxMinutes
TAmb. °C
Steam cleaning PTFE, PFA,PEEK, Torlon
150 60 25
Liquid cleaning PTFE, PFA,PEEK, Torlon
140 60 25
Liner material Meter size TOperationmbar abs
at TOperation
DN inch °C °FHard rubber 15 – 1000 1/2–40 0 < 90 < 194Soft rubber 50 – 1000 2–40 0 < 90 < 194PTFE 10 – 600 3/8–24 270
500< 20< 130
< 68< 266
PFA 3 – 100 1/10–4 0 < 130 < 266
Temperatur / Temperature (TS) [°C]
Dru
ck /
Pre
ssur
e (P
S) [
bar]
High temperature range
PN 40
PN 25
PN 16
PN 10
0
5
10
15
20
25
30
35
40
45
-30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120130140150160170180190
Fig. 4 DINFlanges SST No. 1.4571[316Ti] to DN 600 [24”]
Temperatur / Temperature (TS) [°C]
Dru
ck /
Pre
ssur
e (P
S) [
bar]
300lb
150lb
High temperature range
0
5
10
15
20
25
30
35
40
45
50
55
-30 -10 10 30 50 70 90 110 130 150 170 190
psi
0
72.5
145
217.5
290
362.5
435
507.5
580
652.5
725
797.5
-22 °F 14 °F 50 °F 86 °F 122 °F 158 °F 194 °F 230 °F 266 °F 302 °F 338 °F 374 °F
0.01 bar = 1 kPa
Fig. 5 ANSIFlanges SST No. 1.4571[316Ti] to DN 600 [24”]
PN 40
PN 25
PN 16
PN 10
Temperatur / Temperature (TS) [°C]
Dru
ck /
Pre
ssur
e (P
S) [
bar]
High temperature range
0
5
10
15
20
25
30
35
40
45
-30 -10 10 30 50 70 90 110 130 150 170 190
Fig. 6 DINFlanges Steel to DN 600 [24”]
5
Electromagnetic Flowmeter FSM4000D184S073U02
Liner: PTFE, hard/soft rubber (limited to 90 °C, 194 °F)
JIS 10K-B2210 Flanges SS No. 1.4571 [316Ti] or Steel
Liner: PTFE, hard/soft rubber (limited to 90 °C)
Liner: Hard/soft rubber ≤ 90 °C (≤194 °F)
Liner: Hard/soft rubber ≤ 90 °C (≤194 °F)
Specifications: Stainless Steel Flowmeter Primaries, Model SE21_, DN 1 to DN 100 [1/25“ to 4“]
Connection Overview Series 2000
Material Strength Curves for Flanged Flowmeters Model SE21F
Liner: PFA
Meter SizeDN Inch
Material PN TS [°C] PS [bar]
32–100 11/4 4 SST 1.4571[316Ti] 10 25 to +180 10
32–100 11/4 4 Steel 10 10 to +180 10
300lb
150lb
P/T-Ratings
Temperatur / Temperature (TS) [°C]
Dru
ck /
Pre
ssur
e (P
S) [
bar
]
HochtemperaturbereichHigh temperature range
0
5
10
15
20
25
30
35
40
45
50
55
-30 -10 10 30 50 70 90 110 130 150 170 190
psi
0
72.5
145
217.5
290
362.5
435
507.5
580
652.5
725
797.5
-22 °F 14 °F 50 °F 86 °F 122 °F 158 °F 194 °F 230 °F 266 °F 302 °F 338 °F 374 °F
0.01 bar = 1 kPa
Fig. 7 ANSIFlanges Steel to DN 600 [24”]
6
7
8
9
10
11
12
13
14
15
16
17
DN 700 PN 16
DN 900 PN 16DN 800 PN 16
DN 1000 PN 16
DN 900 PN10DN 800 PN 10DN 700 PN 10
DN 1000 PN 10
Temperatur / Temperature (TS) [°C]
Dru
ck /
Pre
ssur
e (P
S) [
bar]
-30 -20 -10 0 10 20 30 40 50 60 70 80 90
Fig. 8 DINFlange SST No. 1.4571 [316Ti] DN 700 [28“]−DN 1000 [40”]
DN 700 PN 16
DN 900 PN 16DN 800 PN 16
DN 1000 PN 16
DN 900 PN 10DN 800 PN 10DN 700 PN 10
DN 1000 PN 10
Temperatur / Temperature (TS) [°C]
Dru
ck /
Pre
ssur
e (P
S) [
bar]
6
7
8
9
10
11
12
13
14
15
16
17
-10 0 10 20 30 40 50 60 70 80 90
Fig. 9 DINFlanges Steel DN 700 [28“]−DN 1000 [40”]
Model: SE21
B E T R Q P S F W
Met
er S
ize
P
roce
ss C
onne
ctio
ns
1/8“
San
itary
Con
nect
ors
Ext
erna
l Thr
eads
TriC
lam
p D
IN 3
2676
Wel
d S
tubs
D
IN 1
1850
Wel
d S
tubs
D
IN 2
463
Wel
d S
tubs
IS
O 2
037
Food
Indu
stry
Fitt
ing
DIN
118
51
Flan
ge
Waf
er D
esig
n
DN 1 1/25” x PED
DN 2 1/12” x
SE
PA
rt. 3
,P
ar. 3
DN 3 1/10” x x x x x x
DN 4 5/32” x x x x x x
DN 6 1/4” x x x x x x
DN 8 5/16” x x x x x x
DN 10 3/8” x x x x x x
DN 15 1/2” x x x x x x
DN 20 3/4” x x x x x x
DN 25 1” x x x x x x x
DN 32 11/4” x x x x x x
Con
form
ity.
Eva
luat
ion
per
Cat
egor
y III
Mod
ule
B1+
D, F
luid
Gro
up 1
DN 40 11/2” x x x x x x
DN 50 2“ x x x x x x
DN 65 21/2” x x x x x x
DN 80 3” x x x x x x
DN 100 4“ x x x x x x
Temperatur / Temperature (TS) [°C]
Dru
ck /
Pre
ssur
e (P
S) [
bar] PN 40
PN 25
PN 16
PN 10
0
5
10
15
20
25
30
35
40
45
30 20 10 0 10 20 30 40 50 60 70 80 90 100 110 120130 *)
Fig. 10 DINFlanges SS 1.4571 [316Ti] to DN 100, 4“
6
Electromagnetic Flowmeter FSM4000D184S073U02
Liner: PFA
Material Strength Curve for Wafer Design Model SE21W
Liner: PFA
JIS 10K-B2210 Wafer Design
*) Higher temperature are allowed for CIP/SIP cleaning for limited time periods, see Table „Maximum Allowable Cleaning Temperature“
Ambient Conditions
Ambient Temperature
25 °C to + 60 °C [13 °F to +140 °F]
Fluid Temperature DN 3−100
40 °C to +130 °C, CIPcapable, see Temperature Diagram and max. allowable cleaning temperature.The maximum allowable ambient temperature as a function of the fluid temperature for stainless steel process connections and the Wafer Design
Fluid Temperature DN 1−2 [1/25”−1/12”]
10 °C to +120 °C [14 °F to 248 °F], CIPcapable to max. 120 °C.
Storage Temperature
25 °C to +70 °C [13 °F to +158 °F]
Minimum Allowable Absolute Pressure
Maximal Allowable Fluid Temperature and Pressure
Process Connections
DN 1−2 [1/25”−1/12”]
1/8“Sanitary connectors with 2 grounding electrodes in the same material as the signal electrodes, standard
DN 3−100 [1/10”−4”]
Wafer Design, TriClamp, Food Industry Fittings, External threads. Others upon request
Meter SizeDN
Material PN TS [°C] PS [bar]
32–10011/4” 4”
1.4404[316L]1.4435[316L]1.4301[304]
10145 psi
40 to +13040 to +266 °F
10145 psi
Temperatur / Temperature (TS) [°C]
Dru
ck /
Pre
ssur
e (P
S) [
bar] 300lb
150lb
0
5
10
15
20
25
30
35
40
45
50
55
30 10 10 30 50 70 90 110 130 *)
Fig. 11 ANSIFlanges SS 1.4571 [316Ti] to DN 100, 4“
P/TRatings
Temperatur / Temperature (TS) [°C]
Dru
ck /
Pre
ssur
e (P
S) [
bar]
PN 40/CL 300
PN 25
PN 16/CL 150
PN 10
0
5
10
15
20
25
30
35
40
45
60 50 40 30 20 10 0 10 20 30 40 50 60 70 80 90 100110120130*)
40 22 4 14 32 50 68 86 104 122 140 151 176 194 212 230 248 266 284 °F
psi
0
72.5
145
217.5
290
362.5
435
507.5
580
652.5
Fig. 12
Liner Meter SizeDN Inch
POperatembar abs
at TOperate°C
PFA 3–100 1/104 0 ≤ 130*)Peek/Torlon 1–2 1/251/12 0 ≤ 120
Process Connections Liner PFA
Meter SizeDN Inch
PSbar
at TS°C
Wafer Design 3–50 1/10−265–100 21/2−4
4016
≤≤
130*)130*)
Weld stubs 3–40 1/10−1 1/250, 80 2, 3 65, 100 2 1/2, 4
401610
≤≤≤
130*)130*)130*)
TriClamp 3–50 1/10−265–100 2 1/2−4
1610
≤≤
121121
Food Industry fittings 3–40 1/10−1 1/250, 80 2, 3 65, 100 2 1/2, 4
401610
≤≤≤
130*)130*)130*)
External threads 3–25 1/10−1 10 ≤ 130*)1/8”Sanitary connectorsLinerPeek/Torlon
1–2 1/25−1/12 10 ≤ 120
0
60
25
40 130 *)FluidTemp. °C
Ambient Temperature °C
50
Fig. 13 Temperature Diagram
7
Electromagnetic Flowmeter FSM4000D184S073U02
Maximal Allowable Cleaning Temperature
If the ambient temperature >25 °C, the difference must be subtracted from the max. cleaning temperature. Tmax °C, °C = (TAmb. 25 °C) [13 °F].
Maximal Allowable Temperature Shock
Specifications Flowmeter Primary
Flowmeter Primary Materials
Protection Class
IP 67 Standard IP 68 with connector Pg 13.5 and PU resin compound
Pipeline Vibration
Maximum allowable 15 m/s2 (10−150 Hz)
Specification for painting
Type of painting
Epoxy powder coating
Priming coat
No priming coating
Preparing of the surface
Cleaning in a high alkaline bath, Alodine procedure conversion layer for a better adherion of the painting
Thickness of painting
80 µm
Color
RAL 9002 (White grey)RAL 7012 (Basalt grey)
CIPCleaning Liner Tmax°C
TmaxMinutes
TAmb°C
Steam Liquid cleaning
PFA/PeekPFA/Peek/Torlon
150140
6060
2525
Liner Temp.Shockmax. Temp.Diff. °C
Temp.Gradient°C/min
PFA, Peek, Torlon arbitrary arbitrary
Liner Materials
Electrode Materials Electrode DesignStandard Others Standard Others
PFA, Peek, Torlon
Hast.C4 (1.4539 for Food Ind. fittings and TriClamp)
Hast.B2 SST 1.4539 SST 1.4571[316Ti] Tantalum, Titanium, PlatinumIridium
Flat head Conical head (≥ DN10 [3/8”]) SST No. 1.4539
Process Connection Materials
Standard Option
Flange SST 1.4571 [316Ti] upon req.Wafer Design noneWeld stubs SST 1.4404 [316L] upon req.Food Ind. fittings SST 1.4404 [316L] upon req.TriClamp SST 1.4404 [316L] upon req.External threads SST 1.4404 [316L] upon req.1/8”Sanitary connectors SST 1.4571 [316Ti] POM, Brass, PVCConnection Box Stainless Steel –Meter tube SST 1.4301 [304] –Cable connector Polyamide PVDFPrimary housing Deep drawn housing SST No. 1.4301[304]
Process Connection Material Gasket MaterialsWafer Design, noneWeld stubs, Food Ind. fittingTriClampExternal threads
EPDM (EthylenePropylene) std. with FDAApproval (CIP capable, no oil or grease) Silicone with FDAApproval (option, suitable for oil and grease)
Flat housing gaskets Silicone (suitable for oil and grease)
∆ ∆
8
Electromagnetic Flowmeter FSM4000D184S073U02
Specifications: Flowmeter Primary, Flowrate NomographsFlowrate Nomograph
Flowrate Nomographs
The volume flowrate is a function of the flow velocity and the flowmeter size. The Flowrate Nomographs, Fig. 14 and Fig. 15 indicate the flowrate range for a specific flowmeter size and which flowmeter sizes are suitable for a specific flowrate.
Example:
Flowrate = 7 m3/h (Maximum value = range end value). Suitable are flowmeter sizes DN 20 to DN 65 [3/4” to 2/12”] for a flow velocity between 0.5 and 10 m/s.
l/min l/s3/hm
54
3
2
103
102
8
654
3
2
Exam
ple
8
654
3
2
10-1
108
654
3
8
654
3
2
2
1
8
654
3
2
8
654
3
2
8
654
3
2
8
654
3
10-1
10-2
10-3
108
654
3
2
18
654
3
2
8
654
3
2
DN 100
DN 80
DN 65
DN 50
DN 40
DN 32
DN 25
DN 20
DN 15
DN 10
DN 8
DN 6
DN 4
DN 3
DN 2
DN 1.5
DN 1
32 4 5 6 8 1010.80.60.5m/s
10-3
10-1
10-2
8
654
3
2
8
654
3
2
8
654
3
2
1
108
654
3
2
102
8
654
3
2
3
2
Fig. 14 Flowrate Nomograph DN 1 to DN 100 [1/25” to 4”]
l/min 3/hm l/s
103
8
6
54
3
2
108
6
54
4
3
3
2
2
108
6
54
3
2
4
5
104
8
654
3
3
2
2
103
8
654
3
2
10
108
654
3
2
2
32 4 5 6 8 1010.80.60.5m/s
108
654
3
2
8
654
3
2
10
3
8
654
3
2
10
654
3
2
DN 250DN 300DN 350DN 400
DN 500DN 600DN 700DN 800DN 900DN 100
0
DN 125DN 150
DN 200
DN 450
Fig. 15 Flowrate Nomograph DN 125 to DN 1000 [5” to 40”]
9
Electromagnetic Flowmeter FSM4000D184S073U02
Specifications: Flowmeter Primary, Installation Requirements and GroundingUp- and Downstream Straight Sections
Flowmeter installation is the key to an accurata flow measurement system. As a rule of thump, generally 3 pipe diameters uystream and 2 pipe diameters downstream are sufficient. Other upstream obstructions however, such as double elbows out of plane, control valves and nonconcentric pipe reducers etc. may require longer lengths.
Grounding
Grounding the flowmeter primary is necesary not only for safety reasons but also to assure proper opration of the electromagnetic flowmeter. The grouding screws on the flowmeter primary, which correspond to VDE 0100, Part 540, are to be connected to earth potential. For measurement reasons this potential should be identical to the fluid potential if at all possible.In applications using plastic or insulating lined pipelines the ground connections are made utilizing grouding plates or grounding electrodes. If stray currents are present in the pipeline, grounding plates up and downstream of the flowmeter primary are recommended.
Electrode Axis
Neither electrode should be positioned at the highest pont in the pipeline in horizontal installations. Gas bubbles, which may be present in the fluid, could interrupt the electrical connection between the electrodes and the fluid. An ideal installation is shown in Fig. 16. Assure that the meter tube is always completely filled with fluid. Instrument designs with removable electrodes for cleaning are available upon request.
Installations in Larger Size Pipelines
The flowmeter can be installed in larger size pipelines without problems using reducer sections. The pressure drop when reducers are used can be determined from the Nomograph Fig. 17. The procedure for determining the pressure drop is as follows:1. Determine the diameter ratio d/D.2. Calculate the flow velocity as a function of the flowmeter size
and the flowrate:
v =
The flow velocity can also be determined from the Flowrate Nomographs, Fig. 14 and Fig. 15.
3. In Fig. 17 read the “Pressure drop” value, yaxis, at the intersection of the “Diameter Ratio”, xaxis, and the “Flow Velocity” curve.
Electrode Axis
Fig. 16 Electrode Axis
Q (flowrrate)Primary Constant----------------------------------------------
D d
8°
Flanged Reducer
100
10
1
0.5 0.6 0.7 0.8 0.9
v=8m/s
7m/s
6m/s
5m/s
4m/s
3m/s
2m/s
d = EMF inside diameter D = Pipe inside diameter v = Flow velocity in m/s ∆p = Pressure drop in mbar
Pressure Drop Nomograph for EMF Flanged reducers with α/2 = 8°
Diameter Ratio d/D
Pre
ssur
e D
rop
∆p [m
bar]
Fig. 17 Pressure Drop Nomograph
10
Electromagnetic Flowmeter FSM4000D184S073U02
Dimensions: Flowmeter Primary DN 3 to DN 300 [1/10“–12“], DIN Flanges
Model SE41F
1) Other pressure ratings upon request.2) Standard with one grounding plate mounted on one flange SST No. 1.4571 [316Ti]. Other materials upon request.
See also Information “Grounding”. DN 3–100 L + 3 mm, DN 125–300 L + 5 mm.3) With protection flanges. Protection flanges replace grounding plates. DN 3–100 L + 6 mm, DN 125–300 L + 10 mm.
Series 1000 (for replacement only) also available with protection flanges, Dimensions see page 16.4) For high temperature design + 120 mm.
Flange Dimensions Instrument Dimensions Weight
DN PN1) D/H d4 b k d2 N A L* L2) L3) E4) F G4) kg lb (pound)
3−8 10 15 20
10−4010−4010−4010−40
90 90 95105
40 40 45 58
18181820
60 60 65 75
14141414
4 4 4 4
67 67 67 87
130200200200
133203203203
136206206206
101101101112
62 62 62 73
129129129140
2.533
3.5
5.51 6.61 6.61 7.72
25 32 40
10−4010−4010−40
115140150
68 78 88
202020
85100110
141818
4 4 4
87 95100
200200200
203203203
206206206
112117121
73 78 82
140145149
456
8.82 11.02 13.23
50 10−40 165 102 21 125 18 4 116 200 203 206 129 90 157 8 17.64
65 10−1625−40
185185
122122
2125
145145
1818
4 8
100100
200200
203203
206206
153153
104104
171171
1212
26.45 26.45
80 10−40 200 138 27 160 18 8 100 200 203 206 159 110 177 16 35.27
100 10−1625−40
220235
158162
2327
180190
1822
8 8
130130
250250
253253
256256
179179
130130
197197
1515
33.07 33.07
125 10−1625−40
250270
188188
2529
210220
1826
8 8
124124
250250
255255
260260
170170
127127
195195
2330
50.71 66.14
150 10−1625−40
285300
212218
2531
240250
2226
8 8
170170
300300
305305
310310
190190
148148
216216
2834
61.73 74.96
200 1016
340340
268268
2828
295295
2222
812
195195
350350
355355
360360
222222
179179
248248
5454
119.05119.05
250 1016
395405
320320
3030
350355
2226
1212
250250
450450
455455
460460
250250
207207
276275
8080
176.37176.37
300 1016
445460
370378
3133
400410
2226
1212
250250
500500
505505
510510
293293
250250
318318
8392
182.98202.82
Projektion nach ISO Methode E
H
d2
k
Number of Holes N
Cable Connector M20 x 1.5
FE G
88
A b
L*
d4 D
Cable ConnectorM20 x 1,5
Number ofHoles N
All dim’s in mm
Tolerances L*
DN 3−200 1/10”−8”
+ 0
– 3
DN 250−300 10”−12”
+ 0
– 5
Fig. 18 Flowmeter Primaries DN 3 to DN 300 [1/10: to 12”]
11
Electromagnetic Flowmeter FSM4000D184S073U02
Dimensions: Flowmeter Primary DN 3 to DN 300 [1/10“–12“], ANSI Flanges
Model SE41F
H
d2
k
Number of Holes N
Cable Connector M20 x 1.5
FE G
88
A b
L*
d4 D
88
Number ofHoles N
Cable ConnectorM20 x 1.5
35
d2
EF
G
k
1) Standard with one grounding plate mounted on one flange SST No. 1.4571[316Ti]. Other materials upon request. See also Information “Grounding”. DN 3–100 L + 3 mm, DN 125–300 L + 5 mm
2) With protection flanges. Protection flanges replace grounding plates. DN 3–100 L + 6 mm, DN 125–300 L + 10 mm Series 1000 ( for replacement only) also available with protection flanges, Dimensions see page 16.
3) For high temperature design + 120 mm.
MeterSize
Instrument Dimensions ANSI CL 150/CL 300 Flange Dimensions ANSI CL 150
Flange Dimensions ANSI CL 300
Weight
L1)2) *
DN Inch A ISO13359
ABB(Ser.1000)
E3) F G D/H d4 b k d2 N D/H d4 b k d2 N kgCL150/300
lb (pound)
3−810, 15
20 25
1/10−5/163/8, 1/2
3/41
67 67 87 87
130200200200
130270270270
101101112112
62 62 73 73
129129140140
89 89 99108
35 35 43 51
13131416
60 60 70 80
16161616
4 4 4 4
9595
117124
35 35 43 51
16161820
67 67 83 89
16161919
4 4 4 4
2.53
3.54
5.516.617.728.82
32 40 50
1 1/41 1/2
2
95100116
200200200
280280280
117121129
78 82 90
145149157
117127152
64 73 92
182021
89 99121
161619
4 4 4
134156165
64 73 92
212324
99115127
192319
4 4 8
568
11.0213.2317.64
65 80100
2 1/2 3 4
100100130
200200250
330340400
153159179
104110130
171177197
178191229
105127157
252626
140153191
191919
4 4 8
191210254
105127157
273034
150168200
232322
8 8 8
121615
26.4535.2733.07
125150200250
5 6 810
124170195250
250300350450
450450500550
169190222250
127148179207
195216248276
254279343406
186216270324
28303435
216241298362
22222225
8 8 812
280318381445
186216270324
39414753
235270330387
22222528
8121216
36/38386698
79/8483.77
145.50216.05
300 12 250 500 620 293 250 319 483 381 37 432 26 12 521 381 56 451 32 16 124/181 273/399
Tolerances L*
DN 3−200 1/10”−8”
+ 0
– 3
DN 250−300 10”−12”
+ 0
– 5
Projektion nach ISO Methode EAll dim’s in mm
Fig. 19 Flowmeter Primaries DN 3 to DN 300 [1/10: to 12”], ANSI Flanges
12
Electromagnetic Flowmeter FSM4000D184S073U02
Dimensions: Flowmeter Primary DN 350 to DN 1000 [14“–40“], DIN Flanges
Model SE41F
A
d4
EG
F
L*
b
Cable Connector M20 x 1.5Number ofHoles N
kD
d4
d2
Tolerances L*
DN 350−500 14”−20”
0
– 5
DN 600−1000 24”−40”
0
– 10
1) Other pressure ratings upon request.2) One grounding plate mounted on one flange SST No. 1.4571[316Ti].
Other materials upon request. L + 5 mm.3) With protection plates mounted on both flanges, grounding plate not required L + 10 mm.
Series 1000 (for replacement only) also available with protection flanges, Dimensions see page 16.
DIN Flange Dimensions Instrument Dimensions Weight
DN PN1) D k d4 d2 N b A L * L2) L3) G E F appr. kg lb (pound)
350 350
1016
505 520
460 470
430 438
2226
1616
3135
322322
550 550
555 555
560 560
341341
313313
250250
126140
278 309
400 400
1016
565 580
515 525
482 490
2630
1616
3137
370370
600 600
605 605
610 610
367367
339339
275275
155175
342 386
500 500
1016
670 715
620 650
585 610
2633
2020
3339
407407
650 650
655 655
660 660
403403
375375
310310
191235
421 518
600 600
1016
780 840
725 770
685 725
3036
2020
3341
469469
780 780
785 785
790 790
454454
426426
361361
243302
536 666
700 700
1016
895 910
840 840
800 795
3036
2424
3541
537537
910 910
915 915
920 920
495495
469469
405405
315340
694 750
800 800
1016
10151025
950 950
905 900
3339
2424
3743
605605
10401040
10451045
10501050
545545
519519
455455
405467
8931030
900 900
1016
11151125
10501050
10051000
3339
2828
3945
671671
11701170
11751175
11801180
595595
569569
505505
483567
10651250
100010001000
61016
117512301255
112011601170
108011101115
303642
282828
313947
739739739
130013001300
130513051305
131013101310
645645645
619619619
555555555
475575764
104712681684
Projektion nach ISO Methode EAll dim’s in mm
Fig. 20 Flowmeter Primaries DN 350 to DN 1000 [14” to 40”], DIN Flanges
13
Electromagnetic Flowmeter FSM4000D184S073U02
Dimensions: Flowmeter Primary DN 350 to DN 1000 [14“–40“], ANSI Flanges
Model SE41F
Ad4
EG
F
L*
b
Cable Connector M20 x 1.5Number ofHoles N
kD
d4
d2
1) Other pressure ratings upon request.2) One grounding plate mounted on one flange SST No. 1.4571[316Ti].
Other materials upon request. L + 5 mm.3) With protection plates mounted on both flanges, grounding plate not required L + 10 mm.
Series 1000 (for replacement only) also available with protection flanges, Dimensions see page 16.
Meter Size Instrument Dimensions Flange Dimensions ANSI CL 150 1)
Weight
L2)3) * appr. kgCL150
appr. lb(pound)DN Inch A ISO
13359ABB
(ser.1000)E F G D k d4 d2 N b
350 400 450 500
14161820
322370407416
550600686762
650 700
– 780
313329375375
250275310310
341367403403
534 597 635 699
476 540 578 635
413 470 533 584
28.628.631.731.7
12161620
40424548
178 225 230 263
392496507580
600 700
2428
469537
914–
850 910
423469
361405
454495
813 837
749 749
692 762
34.934.9
2020
5350
327 385
721849
800 9001000
323640
605671739
–––
104011701300
519569619
455505555
545595645
94210571380
90010101210
864 9721140
22.225.456
484428
515763
513 6621132
113114592496
Tolerances L*
DN 350 –500 14”–20”
0
– 5
DN 600 –1000 24”−40”
0
– 10
Projektion nach ISO Methode EAll dim’s in mm
Fig. 21 Flowmeter Primaries DN 350 to DN 1000[14” to 40”], ANSI Flanges
14
Electromagnetic Flowmeter FSM4000D184S073U02
Ordering information: Flanged Instruments, Model SE41FIn addition to the Ordering Number please supply the following information: Fluid, fluid temperature, operating pressure, flow range, pipeline type (grounding plate, grounding electrodes)1)
Continued on next page1) If a grounding plate is required (see Part No.) The standard grounding plate is made of SST No. 1.4571[316Ti]. Others upon request.2) From DN 125 [5”] a conductive grounding surface is integrated in the hard/soft rubber liners, standard.3) For Food Industry applications.
Ordering Number SE41FLiner MaterialHard rubber (DN15DN1000 [1/2”40”]) KTW approved Soft rubber (DN50DN1000 [2”40”]) PTFE (DN10DN600 [3/8”24”]) FDA approved PFA (DN3DN 8 [1/10”5/16“”]) FDA approved Others
HSTPZ
Meter Size InchDN 3 1/10 DN 4 5/32 DN 6 1/4 DN 8 5/16
03040608
DN 10 3/8 DN 15 1/2 DN 20 3/4 DN 25 1
10152025
DN 32 11/4 DN 40 11/2 DN 50 2 DN 65 21/2
32405065
DN 80 3 DN 100 4 DN 125 5 DN 150 6
801H1Q1F
DN 200 8 DN 250 10 DN 300 12 DN 350 14
2H2F3H3F
DN 400 16 DN 450 18 (only ANSI Cl150/300 ISO 13359 Installation length) DN 500 20 DN 600 24
4H4F5H6H
DN 700 28 DN 800 32 DN 900 36 DN 1000 40
7H8H9H1T
Measuring Grounding Electrode Material 2)
SST No. 1.4571[316Ti] none Hastelloy B2 none Hastelloy C4 none standard Titanium none Tantalum none SST No. 1.45393) none PlatinumIridium none
SBHMTFP
SST No. 1.4571[316Ti] with Hastelloy B2 with Hastelloy C4 with Titanium with Tantalum with SST No. 1.45393) with PlatinumIridium with Others
ENOIQRGZ
Pressure RatingDIN PN 10 DIN PN 16 DIN PN 25 DIN PN 40
CDEF
JIS K10 ANSI CL 150 (Installation length Series 1000 only for replacement)ANSI CL 300 (Installation length Series 1000 only for replacement)ANSI CL 150 (ISO 13359 Installation length)ANSI CL 300 (ISO 13359 Installation length)Others
KPQRSZ
15
Electromagnetic Flowmeter FSM4000D184S073U02
4) Only with Installation Length Series 1000 Short and ANSI/DINFlanges. Installation length ≤ DN 80[3] L + 20 mm, from DN 100[4”] L + 25 mm.
5) Notes on design
Max. cable lenght without preamplifier 50 mMax. cable lenght with preamplifier 200 m (Empty pipe detection not possible)
Additional Ordering Information may be provided in writing:
Name Plate (also available in Stainless Steel, option)
German EnglishFrench
Electrode Design
Standard Conical head (from DN 10 [3/8”] material SST No. 1.4539 used for high grease content fluids)
Ordering NumberFlange MaterialSteel (standard from DN 20[3/4”]) SS No. 1.4571[316Ti] (standard for DN3DN15[1/10”1/2”], option from DN 20[3/4”]) Others upon request
139
Flange AccessoriesNone Protection plates SST 1.4571[316Ti] (mounted one side) Grounding plate SST 1.4571[316Ti] (mounted one side) Protection flanges SST 1.4571[316Ti] (mounted both sides)4)
Only PTFE/PFA Only PTFE/PFA Only PTFE
ABCD
Temperature RangeStandard (see Specifications, Liner Materials) ≤ 130 °CHigh temperature design ≤ 180 °C (only PTFE/PFA)
SH
CertificationsNoneMaterial certified per EN 10204 Par. 3.1B and pressure test per AD2000Inspection Certificate EN 102043.1BPressure test per AD2000Others
ADFGZ
Calibration CertificatesStandardOthers
AZ
Protection Class per EN 60529IP 67 (connection box with M20 x 1.5 cable connector)IP 68 (connection box with M20 x 1.5 cable connector) and PU resin compoundIP 67 (connection box with NPTthreads)Others
2349
Design5)
Without preamplifier (Standard DN 10 [3/8“] to DN 1000 [4“])Preamplifier Typ A (Standard DN 3 [1/10“] to DN 8 [5/16“])Preamplifier Typ B
124
Design Minimum Conductivity
DN 3 [1/10“] to DN 8 [5/16“] DN 10 [3/8“] to DN 1000 [4“]
without preamplifier not possible = > 20 µS/cm
Preamplifier Typ A = > 20 µS/cm = > 5 µS/cm
Preamplifier Typ B = > 5 µS/cm = > 0,5 µS/cm
16
Electromagnetic Flowmeter FSM4000D184S073U02
Dimensions: Stainless Steel Flowmeter Primaries DN 3 to DN 40 [1/10“ to 1-1/4“], Flanged
Model SE21F
103
L
A
FE
G
b
Dd4
83Cable ConnectorPg 13.5
Number of Holes N
41
kD
FE
G
d2
DIN Flange Dimensions
ANSI Flange Dimensions
1) If a grounding plate is required, L + 3 mm, materials upon request. With 2 grounding plates (protection plates) L + 6 mm, materials upon request.
Liner PFA WeightConnections DN PN L1) A D k d4 d2 b E F G appr. kg appr. lb
(pound)1/10−5/16“ 38
1040
130 37 90 60 42 14 18 108 62 134 3.5 7.723/8“, 1/2“ 10,15 200 37 95 65 36 14 18 108 62 134 3.5 7.72
3/4“ 20 200 42 105 75 41 14 20 120 66 136 3.5 7.721“ 25 200 54 115 85 54 14 20 127 73 143 4 8.82
1−1/4“ 32 200 62 140 100 64 14 20 132 78 148 5 11.021−1/2“ 40 200 67 150 110 74 14 20 136 82 152 5.5 12.13
Liner PFA WeightConnections DN PN L1) A D k d4 d2 b E F G appr. kg appr. lb
(pound)1/10”−5/16” 38
CL 150
130 37 88.9 60.3 42 15.9 18 108 62 134 3.5 7.723/8”, 1/2” 10,15 200 37 88.9 60.3 34.8 15.9 12.6 108 62 134 3.5 7.72
3/4“ 20 200 42 98.4 69.8 42.9 15.9 14.2 120 66 136 3.5 7.721“ 25 200 54 108 79.2 50.8 15.9 15.8 127 73 143 4 8.82
1−1/4“ 32 200 62 117.5 88.9 63.5 15.9 17.4 132 78 148 5 11.021−1/2“ 40 200 67 127 98.6 73.0 15.9 19 136 82 152 5.5 12.13
1/10”−5/16” 38
CL 300
130 37 95.2 66.7 42 15.9 18 108 62 134 3.5 7.723/8”, 1/2” 10,15 200 37 95.2 66.7 34.8 15.9 15.8 108 62 134 3.5 7.72
3/4“ 20 200 42 117.5 82.5 42.9 19 17.4 120 66 136 3.5 7.721“ 25 200 54 123.8 88.9 50.8 19 19.0 127 73 143 4 8.82
1−1/4“ 32 200 62 133.3 98.4 63.5 19 20.5 132 78 148 5 11.021−1/2“ 40 200 67 155.6 114.3 73.0 22.2 22.1 136 82 152 5.5 12.13
Projektion nach ISO Methode EAll dim’s in mm
Fig. 22 Flowmeter Primaries DN 3 to DN 40 [1/10” to 11/2”]
17
Electromagnetic Flowmeter FSM4000D184S073U02
Dimensions: Stainless Steel Flowmeter Primaries DN 50 to DN 100 [2“ to 4“], Flanged
Model SE21F
A
d2
L
EE
G
83
Cable Connector Pg 13.5
Number of Holes N
41
G
d4 D
b
DIN Flange Dimensions
ANSI Flange Dimensions
1) If a grounding plate is required, L + 3 mm, materials upon request. With 2 grounding plates (protection plates) L + 6 mm, materials upon request.
Liner PFA Weight
DN PN L1) A D k d4 d2 N b E G appr. kg appr. lb (pound)
50 10−40 200 100 165 125 104 18 4 24 135 161 8 17.64
65 10−1625−40
200200
107107
185185
145145
124124
1818
48
2626
149149
175175
1010
22.0522.05
80 10−40 200 107 200 160 139 18 8 28 155 181 12 26.45
100 10−1625−40
250250
159159
220235
180190
161167
1822
88
2428
175175
201201
1818
39.6839.68
Liner PFA Weight
Meter Size PN L1) A D k d4 d2 N b E G appr. kg appr. lb (pound)
2”
CL 150
200 100 152 121 99 19 4 23 135 163 8 17.64
2−1/2” 200 107 178 140 118 19 4 26 149 177 10 22.05
3” 200 107 191 152 131 19 4 28 155 183 12 26.45
4” 250 159 229 190 171 19 8 28 175 203 18 39.68
2”
CL 300
200 100 165 127 102 19 8 26 135 163 8 17.64
2−1/2” 200 107 191 149 124 22 8 29 149 177 10 22.05
3” 200 107 210 168 143 22 8 32 155 183 12 26.45
4” 250 159 254 200 177 22 8 36 175 203 18 39.68
Projektion nach ISO Methode EAll dim’s in mm
Fig. 23 Flowmeter Primaries DN 50 to DN 100
18
Electromagnetic Flowmeter FSM4000D184S073U02
Ordering Information: Stainless Steel Flowmeter Primaries DN 3 to DN 100 [1/10“ to 4“], FlangedIn addition to the Ordering Number please supply the following information: Fluid, fluid temperature, operating pressure, flow range, pipeline type (grounding plate)1)
Continued on next page1) Protection plates (2 grounding plates) mounted on both sides and grounding plate mounted on one side to flange,
material SST No. 1.4571 [316Ti]. Others upon request.
Ordering Number SE21F
Liner Material: PFA PMeter Size InchDN 3 1/10 DN 4 5/32 DN 6 1/4 DN 8 5/16 DN 10 3/8 DN 15 1/2 DN 20 3/4 DN 25 1 DN 32 11/4 DN 40 11/2 DN 50 2 DN 65 21/2 DN 80 3 DN 100 4
030406081015202532405065801H
Signal Electrode / Grounding Electrode MaterialSST No. 1.4571[316Ti] / none Hastelloy B2 / none Hastelloy C4 / none Titanium / none Tantalum / none SST No. 1.4539 / none (Food Ind. applications) PlatinumIridium / none
SBHMTFP
SST No. 1.4571[316Ti] / with Hastelloy Bs / with Hastelloy C4 / with Titanium / with Tantalum / with SST No. 1.4539 / with (Food Ind. applications) PlatinumIridium / withOthers
ENOIQRGZ
Pressure RatingPN 16 Standard DN 100 [4”] PN 40 Standard DN 3−80 [1/10”−3”]
DF
JIS K10 ANSI CL 150 (ISO 13359 Installation length) ANSI CL 300 (ISO 13359 Installation length)Others
KPQZ
Process Connection MaterialsSST No. 1.4571[316Ti] Others
39
Flange Accessories1)
NoneProtection Plates SST No. 1.4571 (mounted both sides)Grounding Plate SST No. 1.4571 (mounted one side)Others
ABCZ
Temperature RangeStandard design ≤ 130 °C (266 °F) S
19
Electromagnetic Flowmeter FSM4000D184S073U02
In addition to the Ordering Number please supply the following information: Fluid, fluid temperature, operating pressure, flow range, pipeline type (grounding plate))1)
1) Notes on design
Max. cable lenght without preamplifier 50 mMax. cable lenght with preamplifier 200 m (Empty pipe detection not possible)
Additional Ordering Information may be provided in writing:
Name Plate (also available in Stainless Steel, option)
German EnglishFrench
Electrode Design
Standard Conical head (from DN 10 [3/8”] material SST No. 1.4539 used for high grease content fluids)
Ordering Number SE21FCertificationsNoneMaterial certified per EN 10204 Par. 3.1B and pressure test per AD2000Inspection Certificate EN 10204 3.1BPressure test per AD2000Others
ADFGZ
Calibration CertificatesStandardOthers
AZ
Protection ClassIP 67 (connection box with Pg 13.5 cable connector)IP 68 (connection box with Pg 13.5 cable connector) and PU resin compoundIP 67 (connection box with NPTAdapter)
234
Design1)
Without preamplifier (Standard DN 10 [3/8“] to DN 1000 [4“])Preamplifier Typ A (Standard DN 3 [1/10“] to DN 8 [5/16“])Preamplifier Typ B
124
Design Minimum Conductivity
DN 3 [1/10“] to DN 8 [5/16“] DN 10 [3/8“] to DN 1000 [4“]
without preamplifier not possible = > 20 µS/cm
Preamplifier Typ A = > 20 µS/cm = > 5 µS/cm
Preamplifier Typ B = > 5 µS/cm = > 0,5 µS/cm
20
Electromagnetic Flowmeter FSM4000D184S073U02
Dimensions: Stainless Steel Flowmeter Primaries, DN 3 to DN 100 [1/10“ to 4“], Wafer Design
Model SE21W
A
83Cable Connector Pg 13.5
C
A*
B
G
EF
L
C D
Di
DN 3–DN 8 [1/10”–5/16”]
Di
13.6
41
#
1) Installation length with 2 grounding plates L + 3 mm# Mounting bracket optional
Meter Size DN Inch
PN
10–40CL 150/CL 300
JIS
L1) A* A B C C Di D E F G Weightappr. kg
Weightappr. lb (pound)
3 1/10 4 5/32 6 1/4 8 5/16 10 3/8 15 1/2
68 64 37 28 50 42
3 4 6 81015
45 108 62 197 1.5 3.31
20 3/4 78 74 42 28 50 50 20 54 112 66 205 2.0 4.4125 1 90 86 54 46 70 59 25 63 119 73 219 2.0 4.4132 11/4 98 94 62 46 70 69 32 73 124 78 229 2.5 5.5140 11/2 103 99 67 46 70 77 40 82 128 82 237 3.0 6.6150 2 117 112 – 60 110 95 47 100 136 50 213 4.0 8.8265 21/2 10–16
CL 150JIS
103 99 – 60 110 111 62 116 150 58 235 4.5 9.9280 3 103 99 – 60 110 128 74 133 157 66.5 250 6.5 14.33100 4 133 129 – 60 110 155 96 160 176 80 283 8.5 18.74
∅ ∅ ∅
Projektion nach ISO Methode EAll dim’s in mm
Fig. 24 Flowmeter Primaries DN 3 to DN 100 [1/10” to 4”], Wafer Design
21
Electromagnetic Flowmeter FSM4000D184S073U02
Dimensions: Flowmeter Primary, Variable Process Connections, DN 3 to DN 100 [1/10“ to 4“]
Model SE21_
3
2 1/2”–4”DN 65–100
A
B
83
103
G
EF
D
C#
2”DN 50
83Cable Connector Pg 13.5
Number of Holes N
83Cable ConnectorPg 13.5
C#
B
A
G
EF
103
83
RohrL
3D
For installation lengths with process connections, see Pages 23–24.1) For additional weight due to process connections, see Pages 23–24.2) With mounting bracket G and F + 10.5 mm# Mounting bracket optional
Meter Size DN Inch
A D B C E F2) G2) N Weightappr. kg1)
Weightappr. lb1) (pound)
3–10 1/10−3/8 37 44 28 50 108 62 197 – 1.5 3.31
15 1/2 37 44 28 50 108 62 197 – 1.5 3.31
20 3/4 42 63 28 50 112 66 205 – 2.0 4.41
25 1 54 63 46 70 119 73 219 – 2.0 4.41
32 11/4 62 78 46 70 124 78 229 – 2.5 5.51
40 11/2 67 78 46 70 128 82 237 – 3.0 6.61
50 2 128 100 60 110 136 50 213 4 4.0 8.82
65 21/2 114 116 60 110 150 58 235 6 4.5 9.92
80 3 114 133 60 110 157 66.5 250 6 6.5 14.33
100 4 144 160 60 110 176 80 283 6 9.0 19.84
∅
DN 3−DN 40[1/10“−11/2“]
DN 50−DN 100[2“–4“]
Projektion nach ISO Methode EAll dim’s in mm
Fig. 25 Flowmeter Primaries DN 3 to DN 100 [1/10” to 4”], Variable Process Connections
22
Electromagnetic Flowmeter FSM4000D184S073U02
Dimensions: Stainless Steel Flowmeter Primaries, Adapters for Various Process Connections
Model SE21_
L
Di
Da
L
Rd
Wgt
.
L
Di
1) Weight per pair
Meter Size DN Inch
Weld Stubs
ISO 2037 DIN 11850 DIN 2463
∅ Di ∅ Da LWeight1)
∅ Di ∅ Da LWeight1)
∅ Di ∅ Da LWeight1)
kg lb kg lb kg lb
310 1/103/8 10.0 13.0 127 0.4 0.88 10.3 13.5 127 0.4 0.88
15 1/2 16.0 19.0 127 0.4 0.88 18.1 21.3 127 0.4 0.88
20 3/4 20.0 23.0 132 0.7 1.54 23.7 26.9 132 0.7 1.54
25 1 22.6 25.0 149 0.7 1.54 26.0 29.0 149 0.7 1.54 25 28 149 0.7 1.54
32 11/4 31.3 33.7 166 1.0 2.20 32.0 34.0 166 1.0 2.20 32 35 166 1.0 2.20
40 11/2 35.6 38.0 171 1.0 2.20 38.0 41.0 171 1.0 2.20 36.8 40 171 1.0 2.20
50 2 48.6 51.0 173 1.0 2.20 50.0 54.0 173 1.0 2.20 49 52 173 1.0 2.20
65 21/2 60.3 63.5 165 1.4 3.09 66.0 70.0 165 1.4 3.09 66 70 165 1.4 3.09
80 3 72.9 76.1 169 2.0 4.41 81.0 85.0 169 2.0 4.41 81 85 169 2.0 4.41
100 4 97.6 101.6 199 2.6 5.73 100.0 104.0 199 2.6 5.73 100 104 227 3.0 6.61
Meter Size DN Inch
Food Industry Fittings Tri-Clamp
DIN 11851 DIN11864-1 (Form B) DIN 32676
Rd. Thds. LWeight1)
Rd. Thds. LWeight1)
∅ Di LWeight1)
kg lb kg lb kg lb
310 1/103/8 28 x 1/8” 169 0.5 1.10 34 x 1/8” 161 0.5 1.10 10.0 163 0.5 1.10
15 1/2 34 x 1/8” 169 0.5 1.10 44 x 1/6” 161 0.5 1.10 16.0 163 0.5 1.10
20 3/4 44 x 1/6” 180 0.9 1.98 44 x 1/6” 170 0.9 1.98 20.0 168 0.7 1.54
25 1 52 x 1/6” 207 0.9 1.98 52 x 1/6” 197 0.9 1.98 26.0 192 0.8 1.76
32 11/4 58 x 1/6” 230 1.4 3.09 58 x 1/6” 220 1.4 3.09 32.0 209 1.5 3.31
40 11/2 65 x 1/6” 237 1.4 3.09 65 x 1/6” 227 1.4 3.09 38.0 214 1.4 3.09
50 2 78 x 1/6” 243 1.4 3.09 78 x 1/6” 233 1.4 3.09 50.0 216 1.2 2.65
65 21/2 95 x 1/6” 245 2.2 4.85 95 x 1/6” 233 2.2 4.85 66.0 221 1.6 3.53
80 3 110 x 1/4” 259 3.2 7.05 110 x 1/4” 245 3.2 7.05 81.0 225 2.4 5.29
100 4 130 x 1/4” 307 4.4 9.70 130 x 1/4” 291 4.4 9.70 100.0 255 3.1 6.83
Weld Stubs perDIN 11850 or ISO 2037 or DIN 2463
Food Industry Fittingper DIN 11851
TriClamp perDIN 32676
Projektion nach ISO Methode EAll dim’s in mm
Fig. 26 Dimensions DN 3 to DN 100 [1/10” to 4”], Adapters for Variable Process Connections
23
Electromagnetic Flowmeter FSM4000D184S073U02
Model DS21
Weld Stubs
FoodIndustryFitting
a
L
R
L
DIN 11850, ISO 2037
∅D
i
DIN 11851
L
ExternalThreads
Meter Size Weld Stubs Food Industry Fittings
DIN 11850L
Weight1)DIN 11851
L
Weight1)
DN Inch
kg lb kg lb
3−10 1/10−3/8 127 0.4 0.88 169 0.5 1.1015 1/2 127 0.4 0.88 169 0.5 1.1020 3/4 132 0.7 1.54 180 0.9 1.9825 1 149 0.7 1.54 207 0.9 1.9832 11/4 166 1.0 2.20 230 1.4 3.0840 11/2 171 1.0 2.20 237 1.4 3.0850 2 173 1.0 2.20 243 1.4 3.0865 21/2 165 1.4 3.08 245 2.2 4.8580 3 169 2.0 4.41 259 3.2 7.05100 4 199 2.6 5.73 307 4.4 9.70
1) Weight per pair
Meter Size External Threads ISO 228 / DIN 2999
R a LWeight 1)
DN Inch kg lb3−10 1/10−3/8 3/8” 18 139 0.4 0.8815 1/2 1/2” 18 139 0.4 0.8820 3/4 3/4” 25 164 0.8 1.7625 1 1” 25 179 0.8 1.76
Projektion nach ISO Methode EAll dim’s in mm
Fig. 27 Dimensions, Model SE21, DN 3 to DN 100 [1/10” to 4”], Adapters for Variable Process Connections
24
Electromagnetic Flowmeter FSM4000D184S073U02
Dimensions: Stainless Steel Flowmeter Primaries, 1/8“-Sanitary Connectors, DN 1 to DN 2 [1/25“ to 1/12“]
Model SE21B
118
9248
10
26
40
25
69
2
60
90
64
(135)
41
83Cable Connector Pg 13.5
4 x ∅ 5.5
1
2
Note:
Connection dimension for G 1/8” coupling, internal threads
Mounting bracket optional
Information:Grounding electrodes are integrated in the flowmeter primary as standard and are made of the same material as the signal electrodes.
1) For hose 6 x 4 mm
Process Connections DN Inch PNWeight
kg lb
1/8” Sanitary connection1) 1 2 1/25 1/12 10 1.5 3.31
2
1
Projektion nach ISO Methode EAll dim’s in mm
Fig. 28 Flowmeter Primaries DN 1 to DN 2 [1/25” to 1/12”]
25
Electromagnetic Flowmeter FSM4000D184S073U02
Ordering Information: Stainless Steel Flowmeter PrimariesIn addition to the Ordering Number please supply the following information: Fluid, fluid temperature, operating pressure, flow range, pipeline type (grounding plate, grounding electrode)1)
Continued on next page 1) Only required for Wafer Design and pipelines with insulating liners. 2) DN 1−2 [1/25”−1/12”] always order with same material as signal electrodes, standard.
Ordering Number SE21Process ConnectionsWafer Design DN 3–100 [1/10–4“] Weld stubs DIN 11850 DN 3–100 [1/10–4“] Weld stubs DIN 2463 DN 3–100 [1/10–4“] Weld stubs ISO 2037 DN 25–100 [1–4“] Food Industry fitting DIN 11851 DN 3–100 [1/10–4“] TriClamp DIN 32676 DN 3–100 [1/10–4“] External threads ISO 228/DIN 2999 DN 3– 25 [1/0”1”] No adapter 1/8”Sanitary connectors DN 12 [1/25”3/32”] Others
WRQPSTEVBZ
Liner MaterialPFA (DN 3 100 [1/10”4”]) Peek (DN 12 [1/25”1/12”]) Torlon (DN 12 [1/25”1/12”])
PKN
Meter Size InchDN 1 1/25 DN 1.5 1/17 DN 2 1/12 DN 3 1/10 DN 4 5/32 DN 6 1/4 DN 8 5/16
011S0203040608
DN 10 3/8 DN 15 1/2 DN 20 3/4 DN 25 1
10152025
DN 32 11/4 DN 40 11/2 DN 50 2 DN 65 21/2 DN 80 3 DN 100 4
32405065801H
Measuring Electrode /Grounding Electrode Material2)
SST No. 1.4571[316Ti] /none Hastelloy B2 /none Hastelloy C4 /none standard Titanium /none Tantalum /none SST No. 1.4539 /none (Food Industry applications) PlatinumIridium /none
SBHMTFP
SST No. 1.4571[316Ti] /with Hastelloy B2 /with Hastelloy C4 /with Standard Titanium /with Tantalum /with SST No. 1.4539 /with (Food Industry applications) PlatinumIridium /withOthers
ENOIQRGZ
Pressure RatingPN 10 TriClamp (DN 65–100); external threads, Food Ind. fitting, weld stubs (DN 65, 100) PN 16 Wafer Design, TriClamp DN (3–50); Food Ind. fitting, weld stubs DN 50, 80) PN 40 Wafer Design (DN 3–50); Food Ind. fitting, weld stubs (DN 3–40) JIS K10 Wafer Design DN 3–100 [1/10”4”] ANSI CL 150 Wafer Design DN 3–100 [1/10”4”] ANSI CL 300 Wafer Design DN 3–50 [1/10”2”] Others
CDFKPQZ
26
Electromagnetic Flowmeter FSM4000D184S073U02
1) Notes on design
Max. cable lenght without preamplifier 50 mMax. cable lenght with preamplifier 200 m (Empty pipe detection not possible)
Additional Ordering Information may be provided in writing:
Name Plate (also available in Stainless Steel, option)
German EnglishFrench
Electrode Design
Standard Conical head (from DN 10 [3/8”] material SST No. 1.4539 used for high grease content fluids) Others
Gasket Materials
EPDM with FDAApproval (CIP capable, no oil or grease) Silicone with FDAApproval (suitable for oil and grease) PTFE (Teflon) None
Ordering Number SE21Process Connection MaterialsNone (only Wafer Design) SST No. 1.4571 [316Ti] (only DN 1–2 [1/25”−1/12”]) SST No. 1.4404 [316L] standard POM (DN 1−2 [1/25”−1/12”]) Others
03489
Instrument Mounting BracketNoneWithOthers
ACZ
Temperature RangeStandard design ≤ 130 °C (DN 1–2 [1/25”1/12”] max. 120 °C) SCertificationsNoneMaterial certified per EN 10204 Par. 3.1B and pressure test per AD2000Inspection Certificate EN 10204 3.1BPressure test per AD2000
ADFG
Calibration CertificatesStandardOthers
AZ
Protection ClassIP 67 (connection box with Pg 13.5 cable connector)IP 68 (connection box with Pg 13.5 cable connector) and PU resin compoundIP 67 (connection box with NPTAdapter)
234
Design1)
Without preamplifier (Standard DN 10 [3/8“] to DN 1000 [4“])Preamplifier Typ A (Standard DN 3 [1/10“] to DN 8 [5/16“])Preamplifier Typ B
124
Design Minimum Conductivity
DN 3 [1/10“] to DN 8 [5/16“] DN 10 [3/8“] to DN 1000 [4“]
without preamplifier not possible = > 20 µS/cm
Preamplifier Typ A = > 20 µS/cm = > 5 µS/cm
Preamplifier Typ B = > 5 µS/cm = > 0,5 µS/cm
27
Electromagnetic Flowmeter FSM4000D184S073U02
Installation Accessories
Fig. 29 Protection Plates/Grounding Plates
The loose grounding plates are installed between the flowmeter flange and the mating flange.
Available for sizes DN 3–DN 600 [1/10“–24“]. Mat. SS 1.4571[316Ti] other materials upon request .
Protection Flanges
Protection flanges protect the liner from abrasive fluids and are centered in the pipeline using a groove or spring. Protection flanges are available in 2 thicknesses and are mounted on the intrument. Added installation length for Series 1000 and DIN/ANSI flanges ≤ DN 80 [3“] L + 20 mm, from DN 100 [4“] L + 25 mm.
Gaskets for Protection Plates/Grounding Plates
Only one gasket at the mating flange is required for PTFE/PFA lined instruments installed with metal grounding plates. A gasket should be placed on either side of the grounding plate for hard/soft rubber lined instruments. Commercially available gaskets made of a material (rubber, lt, PTFE, etc) compatible with the fluid and the operating temperatures should be used.
Chemical Applicationd (Grounding)
For plastic pipelines or pipelines with insulating liners, protection/grounding plates made of conductive PTFE (patent applied for), replace the expensive special materials (Platinum, Tantalum etc.) presently used. Succesfully tested in numerous applications.
Wafer Design Accessories for Model SE21W
The following accessories are available as a function of the meter size and the pressure rating: Bolts, nuts, lockwasher, centering elements Gaskets are not included ion the accessories.
Material: SS
DN (inch) PN T=Thick3–80 1/10–3 10–40 1,5
100–150 4–6 25–40 1,5100–250 4–10 10–16 1,5300–600 12–24 10–16 3
∅A
∅B
C
6.4
20
10
T
Groundconnection 1)
Grounding Plate, Loose (Centeredby Mounting Bolts)
R8
16
6,6
R2 R2
R8
16
∅B
Groundconnection 1)
Protection Plate/Grounding PlateMounted on Flowmeter 2)
1) Attach ground cable with a M6 screw, lock washer and nut to the plate. ∅B = Inside diameter of the lining
2) Grounding plate mounted directly on the instrument DN 10 to DN 600 [3/8“ to 24“] Material: Stn. stl. 1.4571 [316Ti] Thickness ≤ DN 100 [4“] = 3 mm, ≥ DN 125 [5“] = 5 mm ∅B = Inside diameter of the lining
Fig. 30 Grounding plate
Nennweite (inch) PN ThicknessDN 10–100 3/8“–4“ 10–40 4 mm< DN 200 upon request
Meter Size Pressure Rating Part NumberDN 3 to 101/10“ to 3/8“
PN 10 40 D614L265U03150 lb D614L265U03300 lb D614L265U04
DN 151/2“
PN 10 40 D614L265U03150 lb D614L266U05300 lb D614L266U06
DN 203/4“
PN 10 40 D614L267U04150 lb D614L267U05300 lb D614L267U06
DN 251“
PN 10 40 D614L268U04150 lb D614L268U05300 lb D614L268U06
DN 321 1/4“
PN 10 40 D614L269U04150 lb D614L269U05300 lb D614L269U06
DN 401 1/2“
PN 10 40 D614L270U04150 lb D614L270U05300 lb D614L270U06
DN 502“
PN 10 40 D614L296U04150 lb D614L296U05300 lb D614L296U06
DN 652 1/2“
PN 10 16 D614L297U08150 lb D614L297U10
DN 803“
PN 10 40 D614L298U08150 lb D614L298U09
DN 1004“
PN 10 16 D614L299U07150 lb D614L299U09
R8 R2
d2
di
Dk
6.6
16
4±0.5l1
N Holes at scale
Fig. 31 PTFE Protection/Ground Plates
28
Electromagnetic Flowmeter FSM4000D184S073U02
Specifications: Converter
Fig. 32 Converter FSM4000S4
Flow Range
Any flow range whose 100 % value corresponds to a flow velocity between 0.5 m/s and 10 m/s can be selected.
Minimum Conductivity
≥ 20 µS/cm standard DN 3–1000 [1/10”–40”] ≥ 5 µS/cm with preamplifier DN >8 [ 5/16”] ≥ 0.5 µS/cm with preamplifier DN 10–1000 [3/8”–40”]
Reproducibility
≤ ± 0.2 % of rate
Response Time
1τ = 70 ms (0–66 %) in Operation mode „Fast“ 1τ = 200 ms (0–66 %) in Operation mode (Standard)
Supply Power
Unom = 115–230 V 50/60 Hz Urat = 85–253 V 50/60 Hz 50/60 Hz ± 6 % 20,4–26,4 V AC, 20,4–31,2 V DC Ripple ≤ 5 %
Power
S ≤ 45 VA (flowmeter primary including converter)
Ambient Temperature
20 to +60 °C [4 to +140 °F]
Storage Temperature
20 to +80 °C [4 to +176 °F]
Relatively humidity
Acc. to IEC 6006821
Vibration
Acc. to DIN EN 6006826 (10–55 Hz: amplitude = 0.15 mm)
Protection Class per EN 60529
IP 67 for field mount housing and NEMA 4X
Design
Field Mount Housing made of cast Alum. per DIN 1725, painted. Paint coat 60 µm thick. Lower section (RAL 7012), upper section (RAL 9002). Dimensions Page 35. Weight appr. 3.3 kg (7.28 pound).
Electrical Connections
Cable entry M20 x 1.5, NPT, PF with adapter (upon request), screw terminals
Damping
Selectable from 0.1 to 99.0 s
Zero Return
Selectable from 0 to 10 % of range end value
Signal Cable
Max. cable length between flowmeter primary and converter is: 50 m for the standard design and versions with automatic zero return, from DN 10 [3/8”] and from 20 µS/cm. 200 m for designs with preamplifiers. A 10 m long signal cable is included with flowmeter. If a longer cable is required, see Footnote on Page 35, Ordering Information, Converter.
Magnet Coil Supply Cable
Is required for connecting the flowmeter primary to the converter. For EMCreasons the 2 wire cable is shielded. A 10 m long cable is included with flowmeter. If a longer cable is required, see Footnote on Page 35, Ordering Information, Converter.
Forward/Reverse Flow Metering
The flow direction is indicated in the display by direction arrows. It is also possible to transmit the flow direction information over the contact output.
Display
4line, lighted, graphic display. To improve the readability, the flow information can be displayed on two lines with larger characters. The individual flowrate and output values can be displayed. Nonswitching dotmatrix display with max. 4 x 16 characters. An clear text error diagnosis is displayed when the system monitor detects an error condition. The alarm condition can also be signaled over the alarm output.
Data Security
All data is stored in a FRAM (Ferroelectric Nonvolatile Random Access Memory) for a 10 year period without requiring power during a power outage or when the main supply power is turned off. Additional security is provided by a serial FRAM installed in the converter and on the external connection board in which the parameter settings and process information are stored. The data in the external FRAM can be uploaded into the converter. Thereby an easy converter exchange is possible without reconfiguration by simply uploading the stored data from the external FRAM into the new converter.
29
Electromagnetic Flowmeter FSM4000D184S073U02
Flow Totalization
The flow is totalized in engineering units. The pulse factor, pulses per unit, can be set between 0.001 and 1000. The totalizer values for the forward and reverse flow directions can be displayed simultaneously. Display selections are made in the submenu "Display".
Parameter Settings
Entries are made using menus displayed in a number of languages (German, English, French, Finnish, Swedish, Italian, Spanish and Dutch) using 3 keys in dialog with the display or by communication over a data link, using a PC, HARTProtocol or Profibus (in preparation).A Magnet Stick can be used for configuration without opening the front door. Position the Magnet Stick over the magnet symbols on the cover over the display.
Alarm Signals
The converter can incorporate a max/minalarm. The alarm limits can be set anywhere within the range of 0–105 % of the flow range end value. When the flowrate is outside of the alarm limits set, an error message is displayed in the upper line. It is also possible to transmit a signal over the contact output.
Upgrade
The converter with all its functions can also be used with older model electromagnetic flowmeters. The appropriate model number must be selected in the converter. It is also possible to use the converter with flowmeters Model 10D1422. A special converter version is required when updating an older model (see Ordering Information, Converter) and is applicable to the meter size range DN 3 to DN 1000 [1/10" to 40"] only in the low voltage design.
Isolation In-/Output
The current output, pulse output and the contact input and contact output are galvanically isolated from the input circuit and from each other.
In-/Output Signals
Current Output (terminals 31, 32)
The following functions are available in the software:0 to 20 mA load ≤ 560 Ohm4 to 20 mA load ≤ 560 Ohm0 to 10 mA load ≤ 1120 Ohm2 to 10 mA load ≤ 1120 Ohm
Contact Output (terminals 41,42)
The following functions are available in the software:– Forward/reverse flow direction signal– Flowrate alarm (max. or min.)– General alarm– Empty pipeThe output contact can be configured as normally open or normally closed.
Optocoupler specifications16 V ≤ UCEH ≤ 30 V, 2 mA ≤ ICEL ≤ 220 mA
Scaled Pulse Output (terminals 51, 52)
Maximum count frequency 5 kHz. Pulse factor per engineering unit from 0.001 to 1000/unit selectable in the software. The pulse width can be set from 0.100 ms to 2000 ms.The design (active, passive) can be selected using jumpers.
Active
Voltage pulse 24 V rectangular, – Load ≥ 150 Ohm,
Pulse width ≤ 50 ms, count frequency ≤ 3 Hz,– Load ≥ 500 Ohm,
Pulse width ≥ 0.1 ms, max. count frequency: 5 kHz.
Passive
Optocoupler"closed ": 0V ≤ UCEL ≤ 2 V, 2 mA ≤ ICEL ≤ 220 mA"open": 16 V ≤ UCEH ≤ 30 V, 0 mA ≤ ICEH ≤ 2 mA
Contact Input (terminals 81/82)Passive contact (normally open). The following functions are available in the software:
External Zero Return
When the pipeline empties all output signals can be turned off. The current output can be set to 0 mA or 2/4 mA dependent on the current output range selection.
External Totalizer Reset
Resets the internal totalizer value in the display and the pulse counter for both flow directions.
Design Passive (optocoupler)
„ON“: 16 V ≤ UKL ≤ 30 V „OFF“: 0 V ≤ UKL ≤ 2 V Ri: 2 kΩ
30
Electromagnetic Flowmeter FSM4000D184S073U02
HART
FlowmeterPrimary
Hand TerminalPC
Converter
4-20 mA
Bell 202Modem Box
R min = 250 Ohmb
Fig. 33 HARTProtocol
HART®-Protocol Version 5.xThe HART®Protocol provides for communication between a process control system, Hand Terminal and the EMF field instrument. The communication signals, which are superimposed as an AC voltage on the current output, do not affect any other instruments connected to the current output. This option is only available with a 420 mA current output.
Transmission Type
FSKModulation on the current output 420 mA per Bell 202 Standard.
Baudrate
1200 Baud
Format
Logic 1: 1200 Hz Logic 0: 2200 Hz
Cable
Max. 1500 m AWG 24 twisted and shielded
Max. Signal Amplitude
1.2 mApp
Load Current Output
min.: 250 Ω, max.: 560 ΩThe digital communication on the current output does not affect any other connected instruments.To configure using SmartVision a DTM (Device Type Manager) is required.
System Connections
In conjunction with the DTM (Device Type Manager) available of the instrument (Software Revision from B.10) the communication (Configuration, Parameter Settings) can be activated using the appropriate applications per FDT 0.98 or 1.2 (SMART VISION 4.01 R2).
AMS
in preparation
PROFIBUS PA
in preparation
FOUNDATION Fieldbus FF
in preparation
31
Electromagnetic Flowmeter FSM4000D184S073U02
Connection Examples for Peripherals
* RB ≥ UCEICE
+31
32
0/4–20 mA
0/2–10 mA
externalinternal
Current Output active with/without HART-Protocol (4–20) mA
externalinternal
Scaled Pulse Output passive, optocoupler
52
51+16–30 V DC
RB*
52
+24 V DC
–
externalinternal
Scaled Pulse Output active
51
41
42
externalinternal
RB*+U 0 V
+24 V DC
externalinternal
82
81+16–30 V DC
0 V
RI
Contact output for system monitor, max.min.alarm, empty pipe or forward/reverse flow direction signal. Function software selectable
Contact input for external totalizer reset and external zero return Function software selectable
Fig. 34 Connection Examples for Peripherals
32
Electromagnetic Flowmeter FSM4000D184S073U02
Interconnection Diagram: Flowmeter Primary DN 1 to DN 1000 [1/25“–40“], Converter Field Mount Housing
2
LM3 M1323151 52 41 N
1+
1)2)3)4)
8212S 2 161S3
8) UU+
42
6)7)
UU+
2S3 1S 163
1633
SE
SE
M3 M1 SE
M3 M1 SE
3 81
24 V +
5)
12
12
Functional Earth
Functional Earth
Converter S4Field Mount Housing
Flowmeter Primary
With preamplifier(always at DN1[1/25”] DN8 [5/16”])
Comment:We recommend that the output cables be shielded with the shield at one end connected to functional earth.
1) Supply power High voltage:
Low voltage:
Frequency:
Urat = 85 V AC to 253 V AC / Unom = 115 to 230 V AC Terminals L, N, 20.4 to 26. V AC, 20.4 to 31.2 V DC Terminals 1+, 2, 47 Hz ≤ f ≤ 53 Hz; 50 Hz Supply power 56 Hz ≤ f ≤ 64 Hz, 60 Hz Supply power
2) Magnet coil supply: Shielded 2 x 1 mm² CE Type 227 TEC 74 ABB Part No. D173D147U01 10 m included with shipment standard
3) Current output:Function:
Software selectableActive 0/4–20 mA, 0/2−10 mA,0 Ω ≤ RB ≤ 560 Ω Terminals: 31, 32
4) Contact output:Function:
Software selectable Passive„closed“: 0V ≤ UCEL ≤ 2 V, 2 mA ≤ ICEL ≤ 220 mA „open“: 16 V ≤ UCEH ≤ 30 V, 0 mA ≤ ICEH ≤ 2 mA Terminals: 41, 42
5) Contact input:Function:
Software selectable Passive„On“: 16 V ≤ UKL ≤ 30 V „Off“: 0 V ≤ UKL ≤ 2 V Ri = 2 kΩ Terminals: 81, 82
6) Pulse output:Function:
SelectableActive/Passive fmax: 5 kHz, pulse width 0.1 ms–2000 ms Setting range:0.001–1000 pulses/units „closed“: 16 V ≤ UCEH ≤ 30 V, 2 mA ≤ ICEH ≤ 220 mA „open“: 0 V ≤ UCEL ≤ 2 V, 0 mA ≤ ICEL ≤ 2 mA Terminals: 51, 52
7) Shielded signal cable: ABB Part No. D173D018U02, 10 m included with shipment.
8) Shielded signal cable: Voltage supply for flowmeter primary with preamplifier Terminals +U, U instead of on 2S and 1S in the standard instrument.
Attention!Is the flowmeter primary includes a preamplifier either for low conductivity applications or for flowmeter sizes DN 1 to DN 8 [1/25“ to 5/16“], the supply voltage ± 12 V DC must be connected to terminals U+ and U at both the flowmeter primary and at the converter.
Fig. 35 Interconnection Converter S4
33
Electromagnetic Flowmeter FSM4000D184S073U02
Interconnection Diagram: Upgrade Flowmeter Primary DN 3 to DN 1000 [1/10“–40“], Converter Field Mount Housing, Model 10D1422 (10DI1425, 10DS3111A-C DN 500–1000 [20“–40“])
LM3 M1323151 52 41 N
1)
2)
3)4)
8212S 2 161S3
8)
42
6)7)
3 67SE L N
673 81
24
V +
5)
12
Functional Earth
Functional Earth
Converter S4Field Mount Housing
Flowmeter Primary
Comment:We recommend that the output cables be shielded with the shield at one end connected to functional earth.
1) Supply Power High voltage:
Frequency:
Urat = 85 V AC to 253 V AC / Unom = 115 to 230 V AC Terminals L, N, 47 Hz ≤ f ≤ 53 Hz; 50 Hz Supply power 56 Hz ≤ f ≤ 64 Hz, 60 Hz Supply power
2) Magnet coil supply: Magnet coil supply from Supply power3) Current output:
Function:Software selectableActive 0/4–20 mA, 0/2−10 mA, 0 Ω ≤ RB ≤ 560 Ω Terminals: 31, 32
4) Contact output:Function:
Software selectable Passive„closed“: 0V ≤ UCEL ≤ 2 V, 2 mA ≤ ICEL ≤ 220 mA „open“: 16 V ≤ UCEH ≤ 30 V, 0 mA ≤ ICEH ≤ 2 mA Terminals: 41, 42
5) Contact input:Function:
Software selectable Passive„On“: 16 V ≤ UKL ≤ 30 V „Off“: 0 V ≤ UKL ≤ 2 V Ri = 2 kΩ Terminals: 81, 82
6) Pulse output:Function:
SelectableActive/Passive fmax: 5 kHz, pulse width 0.1 ms–2000 ms Setting range: 0.001–1000 pulses/units „closed“: 16 V ≤ UCEH ≤ 30 V, 2 mA ≤ ICEH ≤ 220 mA „open“: 0 V ≤ UCEL ≤ 2 V, 0 mA ≤ ICEL ≤ 2 mA Terminals: 51, 52
7) Shielded signal cable: ABB Part No. D173D018U02 using this signal cable or use the available installation8) Reference cable: Only for connecting to reference cable terminals: Terminals: 6, 7 in Model 10D1422
Attention!Supply power see name plate primary
Terminal board: D685A1020U03 Switch S903 must be closed
Fig. 36 Interconnection Upgrade Converter S4
34
Electromagnetic Flowmeter FSM4000D184S073U02
Ordering Information: Converter S4In addition to the Ordering Number please supply the following information: Flow range, if applicable current output, pulse output active/passive, pulse factor and pulse width. These selections can be factory preset.
Ordering Number S4
External Converter S4 ± 0.5 % v. M.
HousingField mount housing (with cable connector M20x1.5), standardField mount housing (with adapter for cable connector NPT 1/2“)
AB
Supply PowerHigh voltage 85–253 V ACLow voltage 20.4–26.4 V AC, 20.4–31.2 V DC
GK
DisplayMagnet Stick operation and graphic display, lighted A
In-/Output OptionsCurrent output + Pulse output active + Contact input + Contact outputCurrent output + Pulse output active + Contact input + Contact output + HARTCurrent output + Pulse output passive + Contact input + Contact outputCurrent output + Pulse output passive + Contact input + Contact output + HARTContact output + PROFIBUS PAContact output + FOUNDATION Fieldbus FFContact output + PROFIBUS PA with M12 plug
1)
1)
01020304070810
in preparationin preparationin preparation
ApplicationStandard 0
For Flowmeter PrimaryFlowmeter Primary Type SE2_, SE4_, standardFlowmeter Primary Type DS2_, DS4_, 10DS3111, 10DI1425Flowmeter Primary Type 10D1422, 10DI1425 (≥ DN 500)2)
Others
1239
ApprovalsNone 0
Name PlateGermanEnglishFrenchStainless Steel GermanStainless Steel EnglishStainless Steel French
GEFGNENFN
Design Level *
Software Level *
1) Option not available for Supply power „Low voltage“Shielded signal cable, 10 m included with each flowmeter. For longer cables order Part No. D173D018U02.Shielded coil supply cable, 10 m included with each flowmeter. For longer cables order Part No. D173D147U01.
2) The connection board for the reference cable includes a voltage splitter, magnet coil supply for the flowmeter primary from a separate external power supply. FRAMVariant Cs = 100 % and Cz = 0 % required.
35
Electromagnetic Flowmeter FSM4000D184S073U02
265
198
10
14.5
132
66
139.7
38
83.5
167
249
7
Min
.175
min. 62
Field Mount Housing with Window Cable Connector M20 x 1.5 Mounting Dimensions
1) 1)
1)1)
1) Mounting holes for 2” pipe mounting kit
Mounting kit upon request
Projektion nach ISO Methode EAll dim’s in mm
Opening the Housing Cover
– Loosen the cover screws.– Remove cover or flip open the cover with a
window.
Closing the Housing Cover
– Press the cover with window on its closure side against the gasket surface and install and tighten the cover screws.
– Set the small cover in the frame and install and tighten the cover screws.
Fig. 37 Dimensions, Converter Housing and Installation proposal
Dimensions: Field Mount Housing
36
Electromagnetic Flowmeter FSM4000D184S073U02
Ordering Number: Test simulator
1) Supply power must correspond to value listed on the converter Name Plate.2) The adapter listed above for Converters 50XM2000/50XE4000/E4 can also be used for existing simulators 55XC2000.
If two adapters are required, then the Ordering Number for each adapter type is to be used.
SoftwareMeter parameter documentation software for PC upon request. SMART VISION Communication tool for HART ® No charge for 90 day evaluation version.DTM‘s are included in SMART VISION Tool.
Flowmeter Primary Simulator 55XC4
Setting the Flow SignalNone (adapter only)3position Digiswitch with 1000 steps
01
Supply power 1)
None (Adapter orders only)110 V–240 V (50/60 Hz) with Schuko plug24 V/48 V (AC/DC) with 4 mm plug110 V–240 V (50/60 Hz) with USA plugOthers
01239
AccessoriesNoneAdapter for converter 50XM2000/50XE4000/E4/50XF4000Adapter for simulator 55XC2000 2)
Adapter plate for converter S4Others
01259
Design Level(Specified by ABB) *
Name PlateGermanEnglishFrench
123
37
Electromagnetic Flowmeter FSM4000D184S073U02
38
Electromagnetic Flowmeter FSM4000D184S073U02
39
U02
Rev
. 03
The IndustrialIT wordmark and all mentioned product names in the form XXXXXXIT are registered or pending trademarks of ABB.
ABB has Sales & Customer Supportexpertise in over 100 countries worldwide.
www.abb.com
The Company’s policy is one of continuous productimprovement and the right is reserved to modify the
information contained herein without notice.
Printed in the Fed. Rep. of Germany (10.03)
© ABB 2003
D18
4S07
3