Page 1: Daikin Altherma™  Troubling Shooting

Daikin Altherma™ Troubling Shooting

Page 2: Daikin Altherma™  Troubling Shooting

2

• Code: 81

• Part: Outlet water thermistor

• Location:

• Activation failure:

• Possible action to resolve the problem:

– Check connector– Check resitance value– Replace thermistor

Outlet thermistor failure

R3T

Page 3: Daikin Altherma™  Troubling Shooting

3

Freeze up problem

• Code: 89

• Part: Heat exchanger freez-up

• Activation failure: Outlet water temp. too low

• Location:

• Possible action to resolve the problem:

– Check water flow in the system. Minimum water flow system 9liter / min.

R3T

Page 4: Daikin Altherma™  Troubling Shooting

5

Flow failure

• Code: 7H• Part: Flow failure• Location:• Activation failure: Flow switch

open during operation (no signal)• Possible action to resolve the

problem:– Check water flow in the system.

(Minimum water flow system 20liter / min.)– Check water pressure in the

installation. (Minimum 0.3 bar)– Check shutt OFF valves– Is water system purged– Check pressure drop and speed of

the waterpump– Check pump operation

R3T

Page 5: Daikin Altherma™  Troubling Shooting

6

Outlet water temperture too high

• Code: 8H

• Part: Outlet water thermistor

• Location: Outlet back up heater

• Activation failure: If outlet water > 65°C

• Possible action to resolve the problem:

– Check if contactor(s) back up heater is not welded

– Check if thermistor is not damaged

– Check if correct resistor value of thermistor

• Procedure :Refer to service manual

R3T

Page 6: Daikin Altherma™  Troubling Shooting

7

Indoor PCB failure

• Code: A1

• Part: Indoor PCB

• Location: Switchbox

• Activation failure:

• Possible action to resolve the problem:

– Replace PCB

Page 7: Daikin Altherma™  Troubling Shooting

8

Insufficient cooling or heating

• Code: A5• Part: Liquid sensor hydrobox• Location: • Possible action to resolve the problem:

– Check water flow in the system. (Minimum water flow system

9liter / min.)– Check water pressure in the

installation. (Minimum 0.3 bar)– Check shutt OFF valves– Is water system purged– Check pressure drop and speed of the

waterpump– Check refrigerant charge– Check thermistor

• Procedure: refer to service manual R3T

Page 8: Daikin Altherma™  Troubling Shooting

9

Booster heater thermal protector

• Code: AA• Part: Thermal protector

booster heater or back up heater *

• Location: • Possible action to resolve

the problem:– Check if thermal protection is not

damaged.– Check contactor of the electric

BUH / BSH

Page 9: Daikin Altherma™  Troubling Shooting

10

Stucked flow switch

• Code: CO

• Part: Flow switch failure

• Activation failure: Flow swith remains closed when pump is not operating

• Location:

• Possible action to resolve the problem:

– Check for dirt in flow switch– Replace part is required

R3T

Page 10: Daikin Altherma™  Troubling Shooting

11

Heat exchanger thermistor failure

• Code: C4

• Part: Liquid sensor

• Activation failure: Sensor broken or out of range

• Location:

• Possible action to resolve the problem:

– Check connector– Check resistance of the sensor– Procedure: refer to servicemanual

for procedure– If damaged replace part

R3T

Page 11: Daikin Altherma™  Troubling Shooting

12

Outdoor PCB failure

• Code: E1

• Part: Outdoor PCB failure

• Activation failure:

• Location:

• Possible action to resolve the problem:

– Out of control of CPU• Voltage drop

• Power loss

• Noise on power supply

– Defect outdoor PCB

Page 12: Daikin Altherma™  Troubling Shooting

13

Overload activation of compressor

• Code: E5

• Part: Overload protector compressor

• Activation failure: Failure If overload protector ( >130°C) is activated twice in one hour

• Location: Outdoor unit

• Possible action to resolve the problem:

– Refrigerant shortage.– Malfunction four way valve.– Outdoor PCB failure.– Electronic expansion valve

defective.

Page 13: Daikin Altherma™  Troubling Shooting

14

Compressor start up failure

• Code: E6

• Part: Compressor locked

• Activation failure: : Failure, if error occurs 16 times, counter reset if compressor runs normal for 5 minutes

• Location: Outdoor unit

• Possible action to resolve the problem:

– Replace outdoor PCB– Replace compressor

Page 14: Daikin Altherma™  Troubling Shooting

15

Fan motor failure

• Code: E7

• Part: Outdoor fan motor

• Activation failure: Failure, if error occurs 16 times, counter reset if compressor runs normal for 5 minutes

• Location: Outdoor unit

• Possible action to resolve the problem:

– Fan motor breakdown– Bad contact between PCB and fan

motor– Blockage of the fan blades

Page 15: Daikin Altherma™  Troubling Shooting

18

Sanitary water too high

• Code: EC• Part: Sanitary tank temperature• Activation failure: If temperature

sanitary water > 89°C• Location: Sensor inside sanitary

tank• Possible action to resolve the

problem:– Check position of sensor in socket– Check if contactor(s) booster heater is

not welded– Check if thermistor is not damaged– Check if correct resistor value of

thermistor

Page 16: Daikin Altherma™  Troubling Shooting

19

Discharge temperature too high

• Code: F3

• Part: Discharge sensor

• Activation failure: Failure if discharge temperature > 120°C for 6 times

• Location: Sensor located on the discharge pipe of compressor

• Possible action to resolve the problem:

– Refrigerant shortage.– Malfunction four way valve.– Defective discharge sensor.– Defective EEV driver.

Page 17: Daikin Altherma™  Troubling Shooting

22

Voltage and current sensor failure

• Code: H0

• Part: Voltage / Current sensor

• Activation failure:

No measurement of current during compressor operation.

• Possible action to resolve the problem:

– Reactor disconnected– Compressor disconnection– Outdoor PCB failure– Compressor defective

Page 18: Daikin Altherma™  Troubling Shooting

25

Outdoor ambient thermistor

• Code: H9

• Part: Thermistor

• Location

• Activation failure: Resistance value out of range

• Possible action to resolve the problem:

– Check connector– Check resistance value– Replace thermistor.– Outdoor PCB

Page 19: Daikin Altherma™  Troubling Shooting

26

Discharge pipe thermistor

• Code: J3

• Part: Discharge pipe thermistor

• Location

• Activation failure: Resistance value out of range

• Possible action to resolve the problem:

– Check connector– Check resistance value– Replace thermistor.– Outdoor PCB

Page 20: Daikin Altherma™  Troubling Shooting

27

Outdoor heat exchanger

• Code: J6

• Part: Thermistor

• Location

• Activation failure: Resistance value out of range

• Possible action to resolve the problem:

– Check connector– Check resistance value– Replace thermistor.– Outdoor PCB

Page 21: Daikin Altherma™  Troubling Shooting

29

Electrical box temperature rise

• Code: L3

• Part: Radiation fin thermistor

• Location: Outdoor PCB

• Activation failure: failure if temperature > 85°C and compressor OFF

• Possible action to resolve the problem:

– Defective outdoor fan– Defective Fin thermistor– Defective Outdoor PCB– Heat conductive paste

Page 22: Daikin Altherma™  Troubling Shooting

30

Radiation fin temperature rise

• Code: L4

• Part: Radiation fin temperature rise

• Location: Outdoor PCB

• Activation failure: failure if temperature > 105°C and compressor ON for 4 times

• Possible action to resolve the problem:– Defective outdoor fan– Defective Fin thermistor– Defective Outdoor PCB– Heat conductive paste

Page 23: Daikin Altherma™  Troubling Shooting

36