danfoss refrigeration thermostats...464 refrigeration thermostats danfoss refrigeration thermostats...
TRANSCRIPT
463
REFRIGERATION THERMOSTATS
DANFOSS REFRIGERATION THERMOSTATSINTRODUCTION
KP thermostats are temperature-controlled electrical switches.
All KP thermostats have a single pole double throw (SPDT) changeover switch. The position of the switch depends on the thermostat setting and the bulb temperature.
A KP thermostat can be directly connected to single-phase a.c. motors of up to about 2.7 hp, or installed in the control current circuit of d.c. motors and large a.c. motors.
FEATURES• Wide regulating range.
• Can be used for deep freeze, refrigeration and air conditioning systems.
• Welded bellows elements mean increased reliability.
• Small dimensions — Easy to install in refrigerated counters or cold rooms.
• Ultra-short bounce times. Long operating life. Unnecessary cut-in and cut-out of control equipment is avoided.
• Standard versions with changeover switch. Possible to obtain opposite switch function or to connect a signal.
• Electrical connection at the front of the unit facilitates rack mounting. Saves space.
• Suitable for alternating and direct current.
• No spade or lug terminals required.
• Integral 1/2 NPSM swivel cable connector. Allows direct attachment of 1/2 in. male pipe thread connector.
• Extensive and wide range.
APPROVALSUL listed, file E31024.CSA certified, LR 27339.
P636
P636C
464
REFRIGERATION THERMOSTATS
DANFOSS REFRIGERATION THERMOSTATSORDERING
*Bulb must be installed in colder position than thermostat housing and capillary tube.†Bulb can be placed warmer or colder than thermostat housing.
**On manual minimum reset units the set value is equal to the cut-out value (lowest activating temperature).Reset is possible after a temperature rise of 5.4° F.
††Factory setting:Cut-In: 60° FCut-Out: 25° F
THEMOSTAT BULB TYPES
CHARGE TYPEBULBTYPE
REGULATIONRANGE
DIFFERENTIAL t
RESET
CAPILLARY TUBE LENGTH
P/NAt Lowest Temperature
Setting °F
At Highest Temperature
Setting °Fin. ft
Vapour*
KP 61 B -20 → 55 8 → 40 2.2 → 13 Auto. 80 6.5 60L2002KP 62 C -20 → 60 10 → 40 2.7 → 13 Auto. 60L2015KP 63 A -60 → 15 18 → 125 4.9 → 15 Auto. 80 6.5 60L2007KP 69 B 25 → 95 8 → 45 3.2 → 13 Auto. 80 6.5 60L2009
Adsorption†
KP 71 E 2 25 → 70 4.5 → 18 4 → 18 Auto. 80 6.5 60L2010KP 71 E 2 25 → 70 Fixed 5.4 Fixed 5.4 Man., Min.** 80 6.5 60L2011KP 73 D -15 → 60 8 → 36 6.3 → 36 Auto. 80 6.5 60L2017KP 73 E 1 0 → 80 10 → 35 10 → 35 Auto. 80 6.5 60L2029††
KP 98 E 2Oil: 30 to 90
HT: 210 to 350Oil: fixed 22HT: fixed 45
Oil: fixed 22HT: fixed 45
Man., Max.4080
3.26.5
60L2025
A
Straight capillary tubeSensing Length: 15 in. of 80 in.
B
Dia. 3/8 in. x 2-3/4 in. remote air coil
C
Dia. 1-9/16 in. x 1 in. air coil (integral with thermostat)
D
Dia. 3/8 in. x 2-3/4 in. double contact remote bulbNOTE: Cannot be used in sensor (bulb) pocket.
E
E1: Dia. 1/4 in. x 3-3/8 in. remote bulbE2: Dia. 3/8 in. x 4 in. remote bulb
465
TEMPERATURE & PRESSURE CONTROLS
ALCO TF115 TEMPERATURE CONTROLSThe TF115 Temperature Controls are designed to sense space or surface temperatures in cooling or heating applications for cycling and alarm applications. Maximum application flexibility is pro-vided by using a heavy-duty 24 amp single pole double throw SPDT switch and temperature ranges and power elements designed for specific applications.
*The controls listed replace many other temperature controls than just those shown in this table.†Limited Range — check application.
**Functional replacement.
TF115 ELECTRICAL RATINGS
PART NUMBER*RANGE
IN °FDIFFERENTIAL
IN °FSWITCH
CAPILLARY& BULB
REPLACESRanco Penn White-Rodgers Honeywell
REMOTE COILED BULB — VAPOR CHARGEDTF115-S1 AA10Low Temp
-60 to +15
3 to 30 SPDT10′ Capillarywith 3/8 x 2″coiled bulb
O10-1433 — 1609-100† —
TF115-S2 AA10Refrigerator/Freezer Control
-20 to +60O10-1408O10-1409O16-104
— 1609-90 T4031A1008
AIR COIL — ROOM SENSINGTF115-S2 AE00Walk-inCoolers/Freezers
-20 to +603 to 30 SPDT
Air Coilfor
spacetemperature
sensing
O10-1072O10-1418O16-594
A19BBC-2† 201-20† T6054A†
TF115-S3 AE00Ventilating/A.C./ Heat
+15 to +95O10-301O16-165
A19BAB-3A19BAC-1
201-8 T6054B
WIDE RANGE — BULB SENSINGTF115-S4 AF10Wide RangeTemperature Control
-20 to +95 5 to 35 SPDT10′ Capillary
with 3/8 x 2-3/4″solid bulb
O60-100F25-107**
A19ABC-24A19ZBC-2**
1609-1011609-1021609-103
T6031A1029
MAXIMUM LOAD 120 VAC 240 VACFull Load Amps 24 FLA 24 FLALocked Rotor Amps 144 LRA 144 LRAHorsepower 2 HP 3 HPPilot Duty 720 VA 720 VANoninductive 24 amps 24 amps
TF115 DIMENSIONAL DRAWINGS
SETTINGS & ADJUSTMENTS: TF115/FF115/FF215
ADJUSTABLE RANGE & DIFFERENTIAL CONTROLS
Procedure
1. Adjust the Range Screw/Pointer to the desired “High Event” setting.
2. Adjust the Differential Screw to the desired differential.
Low Event = High Event – Differential
• Adjustment of the Range Screw changes both high and low events
• Adjustment of the Differential Screw changes the “Low Event” only.
P1026
ADJUSTABLE RANGE FIXED DIFFERENTIAL CONTROLS OR HIGH SIDE DUAL PRESSURE
Procedure
1. Adjust the Range Screw to the desired “High Event” setting.
Low Event = High Event – Fixed Differential
• Adjustment of the Range Screw changes both the high and low events.
P1026A
P1025
P1024
466
TEMPERATURE & PRESSURE CONTROLS
RANCO LUBE OIL PROTECTION CONTROLSThese lube oil protection controls guard pressure-lubricated refrigeration compressors against major damage due to loss of oil pressure. If adequate oil pressure is lost, the built-in S30 Time Delays Switch starts timing. If the oil pressure does not recover within the set period, the control circuit is opened, stopping the compressor.
P1123
MODEL SELECTION CHART
NOTE: The range is the difference between the crankcase pressure and the oil pump pressure that will energize the time delay switch and lead to shut down. The difference in oil pressure needs to rise 7 P.S.I. above the range to de-energize the time delay switch and prevent eventual shutdown.
P30
PRESSURERANGEP.S.I.D.
VOLTAGEA.C.
TIME DELAY(Seconds)
P/N
36″″″″ CapillaryWith Flare Nut
Male FlareMale Flare
With24″″″″ Ref. Hose
9 Fixed
120 or 240
120 RAN-P30-5826 RAN-P30-5827 RAN-P30-5827H5 Fixed 60 RAN-P30-5629 RAN-P30-5628 RAN-P30-5628H8 to 60
Adjustable120 RAN-P30-3801 — RAN-P30-3803H
90 RAN-P30-3701 — —
RANCO REFRIGERANT HOSERefrigerant hose is a heavy duty hose designed for critical appli-cations like commercial refrigeration. It is designed to resist breakage from compressor vibration. The refrigerant hose is made of teflon tubing, surrounded by a braided 304 stainless steel wire.
P1127
1290132P/N OVERALL HOSE LENGTH FITTINGS (1/4″″″″ SAE)
RAN-1290132-B18 18″
Straight 7/16 - 20 Female Flare ConnectionRAN-1290132-B24 24″RAN-1290132-B36 36″RAN-1290132-B48 48″RAN-1290132-A18 18″
One Straight And One 90° ElbowBoth Ends Have 7/16 - 20 Female Flare Connection
RAN-1290132-A24 24″RAN-1290132-A36 36″RAN-1290132-A48 48″
467
TEMPERATURE & PRESSURE CONTROLS
RANCO MINI PRESSURE CONTROLSLOW, HIGH PRESSURE AND FAN CYCLING CONTROLS
Ranco Mini Pressure, fixed setting controls are used on refrigera-tion or air conditioning systems.
P1125
P1126
MODEL SELECTION CHART
MP
APPLICATION P/NSETTINGS P.S.I.G. LEADS,
COLOR CODESETTING TOLERANCE
PSICut-Out Cut-In
Low PressureCut-Out
RAN-MPL-7001 5 20
Blue(Cut-Out On
Pressure Drop)
Cut-Out +/-5Cut-In +/-6 (RAN-MPL-7003 is -12)
RAN-MPL-7002 15 35RAN-MPL-7003 25 80RAN-MPL-7004 35 60RAN-MPL-7005 45 60RAN-MPL-7011 10 25RAN-MPL-7012 20 45RAN-MPL-7014 40 80
Condenser FanCycling
RAN-MPF-7006 75 120
Cut-Out +/-15 (RAN-MPF-7006 is +/-10)
Cut-In +/-10
RAN-MPF-7007 110 170RAN-MPF-7008 150 225RAN-MPF-7009 190 275RAN-MPF-7010 300 400
High PressureCut-Out
RAN-MPH-7101 250 180
Black(Cut-Out On
Pressure Rise)
Cut-Out +/-10Cut-In +/-15 (RAN-MPH-7101 is +/-20)
RAN-MPH-7102 270 200RAN-MPH-7103 300 200RAN-MPH-7104 325 225RAN-MPH-7105 350 250RAN-MPH-7106 375 275RAN-MPH-7107 400 300RAN-MPH-7108 425 325
High PressureManual Reset
RAN-MPH-7109 375Lockout
Manual ResetSPDT
Terminals1 & 2 Open On Rise1 & 4 Signal/Alarm;
Close On Rise
RAN-MPH-7110 410
RAN-MPH-7111 475
468
TEMPERATURE & PRESSURE CONTROLS
JOHNSON CONTROLS A19 REMOTE BULB CONTROL
P4411
DESCRIPTIONThe A19 Series are single stage temperature controls that incorporate liquid filled sensing elements.
SELECTION CHART
*Replaces White-Rodgers 1609-101.†Replaces White-Rodgers 1609-12, -13; Ranco O10-1408, -1409, -1410, -1490, O60-110;
Honeywell L6018C-1006, L6021A-1005, T675-1011, -1508, -1516, -1821, T4301A-1008, T6031A-1011, T6031A-1029.**Case-Compensated.
����Universal Replacement.
P/NSWITCHACTION
RANGE°F (°C)
DIFF F°(C°)
BULB ANDCAPILLARY
BULB WELL NO.(Order
Separately)
RANGEADJUSTER
MAX. BULBTEMP °F (°C)
Wide Range — Adjustable Differential
A19ABA-40C*SPST
Open Low–30 to 100 (–34 to 38) 3 to 12 (1.7 to 6.7) 3/8 in. x 4 in., 6 ft Cap. WEL14A-602R Screwdriver Slot 140 (60)
A19ABC-4C SPDT 50 to 130 (10 to 55) 3-1/2 to 14 (1.9 to 8) 3/8 in. x 5 in., 8 ft Cap. WEL14A-603R Knob 170 (77)���� A19ABC-24C† SPDT –30 to 100 (–34 to 38) 3 to 12 (1.7 to 6.7) 3/8 in. x 4 in., 8 ft Cap. WEL14A-602R Convertible 140 (60)���� A19ABC-36C SPDT –30 to 100 (–34 to 38) 3 to 12 (1.7 to 6.7) 3/8 in. x 4 in., 20 ft Cap. WEL14A-602R Convertible 140 (60)A19ABC-37C SPDT –30 to 100 (–34 to 38) 3 to 12 (1.7 to 6.7) 3/8 in. x 4 in., 10 ft Cap. WEL14A-602R Screwdriver Slot 140 (60)A19ABC-74C SPDT –30 to 100 (–34 to 38) 3 to 12 (1.7 to 6.7) 3/8 in. x 4 in., 6 ft Cap. WEL14A-602R Screwdriver Slot 140 (60)
Fixed DifferentialA19AAF-12C SPDT 25 to 225 (–4 to 107) 3-1/2 (1.9) 3/8 in. x 3 in., 10 ft Cap. WEL14A-602R Screwdriver Slot 275 (135)
CASE COMPENSATED — FIXED DIFFERENTIALA19AAC-4C SPDT 0 to 80 (–18 to 27) 5 (2.8) 3/8 in. x 4 in., 6 ft Cap. WEL14A-602R Screwdriver Slot 140 (60)
A19AAD-12CSPST
Open Low–30 to 50 (–34 to 10) 2-1/2 (1.4) 3/8 in. x 4 in., 7 ft Cap. WEL14A-602R Screwdriver Slot 140 (60)
Close Differential
A19AAD-5C**SPST
Open Low30 to 50 (–1 to 10)(Bulk Milk Cooler)
2-1/2 (1.4) 3/8 in. x 2-5/8 in., 6 ft Cap. WEL16A-601R Screwdriver Slot 190 (88)
A19AAF-20C SPDT –30 to 100 (–34 to 38) 2-1/2 (1.4) 3/8 in. x 4 in., 6 ft Cap. WEL14A-602R Screwdriver Slot 140 (60)A19AAF-21C SPDT 40 to 90 (4 to 32) 1-1/2 (0.8) 3/8 in. x 5-3/4 in., 6 ft Cap. WEL14A-603R Screwdriver Slot 140 (60)
Manual Reset
A19ACA-14CSPST
Open Low–30 to 100 (–34 to 38) Manual Reset 3/8 in. x 4 in., 6 ft Cap. WEL14A-602R Screwdriver Slot 140 (60)
A19ACA-15CSPST
Open Low–30 to 100 (–34 to 38) Manual Reset 3/8 in. x 4 in., 10 ft Cap. WEL14A-602R Screwdriver Slot 140 (60)
A19ADB-1CSPST
Open High100 to 240 (38 to 116) Manual Reset 3/8 in. x 3-1/2 in., 6 ft Cap. WEL14A-602R Knob 290 (143)
A19ADN-1CSPST
Open HIgh100 to 240 (38 to 116) Manual Reset 3/8 in. x 4 in., 6 ft Cap. WEL14A-602R Screwdriver Slot 290 (143)
469
TEMPERATURE & PRESSURE CONTROLS
JOHNSON CONTROLS A419 ELECTRONIC TEMPERATURE CONTROL
JOHNSON CONTROLS A319 ELECTRONIC TEMPERATURE CONTROL
DESCRIPTIONThe A419 Series control is a line voltage, single-stage, elec-tronic temperature control with a Single-Pole, Double-Throw (SPDT) output relay. It has heating or cooling modes of operation with an adjustable set point and differential, a lockable keypad, an adjustable anti-short cycle delay, and binary input for temperature offset. The A419 combines remote sensing capability and interchangeable sensors with electronic accuracy, all in a NEMA 1 high-impact plastic enclosure that is suitable for surface-mounting or DIN-rail mounting.
APPLICATIONSThe A419 can be used to control a wide variety of sin-gle-stage refrigeration or HVAC equipment. Typical applica-tions include:
• freezer control in convenience stores• reach-in coolers• supermarket display cases for produce or meats• restaurant or convenience store walk-in coolers• boiler control• compressor lockout (disables the compressor when tem-
perature exceeds limits)• condenser fan cycling• pump control for cooling towers• space and return-air temperature
P4412
SELECTION CHART
P/N DESCRIPTION
A419ABC-1C A419 Electronic Temperature Control with Display and Sensor (120/240 VAC model)
A419GBF-1C A419 Electronic Temperature Control with Display and Sensor (24 VAC model)
A99BB-200C PTC Sensor with 6.5 ft (1.98 m) LeadsBKT287-1R 35 x 7.5 mm, 0.305 m (12 in.) long DIN RailBKT287-2R 35 x 7.5 mm, 0.914 m (36 in.) long DIN RailPLT344-1R Two End Clamps, for DIN Rail MountingCLK350-2 7-Day Programmable Digital Clock; Electronic Switch Output
WEL11A-601R Immersion Well (Use with Thermal Compound)
DESCRIPTIONThe A319 Series is a line voltage, single-stage electronic temperature control with Single-Pole, Double-Throw (SPDT) relay output and LED indication. The A319 features heating or cooling modes of operation, adjustable cut-in, adjustable differential, and an interchangeable temperature sensor. The A319 couples electronic accuracy with remote sensing capability in a NEMA 1 high-impact plastic enclosure suitable for surface or DIN rail mounting.
P4415
SELECTION CHART
ITEM P/N DESCRIPTIONA319 Temperature Control with Sensor A319ABC-12-01 Cut-in Range: 100 to 220° F (38 to 105° C)
Differential: 1 to 30° F (0.5 to 17° C)Sensor Lead Length: 8 ft (2.4 m)
A319 Temperature Control With Sensor A319ABC-24-01 Cut-in Range: –20 to 100° F (–30 to 38° C)Differential: 1 to 30° F (0.5 to 17° C)Sensor Lead Length: 8 ft (2.4 m)
A319 Temperature Control With Sensor A319ABC-07-01 Cut-in Range: –25 to 50° F (–32.5 to 10° C)Differential: 1 to 15° F (0.5 to 8° C)Sensor Lead Length: 8 ft (2.4 m)
A319 Temperature Control Without Sensor A319ABC-12-02 Cut-in Range: 100 to 220° F (38 to 105° C)Differential: 1 to 30° F (0.5 to 17° C)
A319 Temperature Control Without Sensor A319ABC-24-02 Cut-in Range: –20 to 100° F (–30 to 38° C)Differential: 1 to 30° F (0.5 to 17° C)
A319 Temperature Control Without Sensor A319ABC-07-02 Cut-in Range: –25 to 50° F (–32.5 to 10° C)Differential: 1 to 15° F (0.5 to 8° C)
470
TEMPERATURE & PRESSURE CONTROLS
JOHNSON CONTROLS A28 SERIES TWO-STAGE FLANGE MOUNTED DUCT THERMOSTAT
JOHNSON CONTROLS P70 SERIES SINGLE-POLE DUAL PRESSURE CONTROL
DESCRIPTIONThe A28AK is a two-stage temperature control with special air coil sensing element and adjustable mounting flange.
P4408
SELECTION CHART
P/N NUMBER OFSTAGES
SWITCHACTION
RANGE°F (°C)
DIFFERENTIAL F° (C°)FIXED
MAXIMUM ALLOWABLETEMPERATURE AT BULB
°F (°C)Each Stage Between StageA28AK-1C 2 2-SPDT Switches 30 to 110 (–1 to 43) 2 (1.1) 3 (1.7) 140 (60)A28AK-2C 2 2-SPDT Switches 60 to 130 (16 to 54) 2 (1.1) 3 (1.7) 200 (93)
P4410
DESCRIPTIONThis P70 Series of dual pressure controls employs a SPST switch, that is opened when either high pressure or low pressure beyond the control set-tings is sensed at the control’s two bellows sensing elements. The load-carrying contacts provide direct control of AC motors within the con-trol’s rating. These controls provide close high-open low (low pressure) or open high-close low (high pressure) contact action.
SELECTION CHART
� � � � Universal Replacement.
P/N SWITCHACTION
LOW PRESSUREpsig (kPa)
HIGH PRESSUREpsig (kPa) PRESSURE
CONNECTORLMITED
KNOB ADJ.
MAXIMUMOVERPRESSURE
psig (kPa)Range Diff Range Diff (Non-Adj)MICRO-SET™ FOR R-12, R-22, R-134a, R-500, R-502 (R)
P70LB-6CSPST
12 in. to 80(–41 to 552)
Min 5 (34)Max 35 (241)
100 to 500(690 to 3447)
65 psi at < 300 psig75 psi at 300-400 psig95 psi at > 400 psig
36 in. Cap. with1/4 in. Flare Nut Cut-out 325 Low
525 High(2241 Low)(3620 High)P70MA-18C Lockout
(Requires Manual Reset)36 in. Cap. with1/4 in. Flare Nut None
“ALL RANGE” FOR R-12, R-22, R-134a, R-500, R-502 (R)
� � � � P70LB-1C
SPST20 in. to 100(–68 to 690)
Min 7 (48)Max 50 (345) 100 to 500
(690 to 3447)
65 psi < 300 psig75 psi 300-400 psig95 psi > 400 psig
36 in. Cap. with1/4 in. Flare Nut
Cut-out325 Low525 High(2241 Low)(3620 High)
� � � � P70MA-1C Lockout(Requires Manual Reset)
36 in. Cap. with1/4 in. Flare Nut
None� � � � P70NA-1C Lockout
(Manual Reset)Lockout(Requires Manual Reset)
36 in. Cap. with1/4 in. Flare Nut
P70SA-1C Two Independent SPDT Switches
12 in. to 80(–41 to 552)
Min 5 (34)Max 35 (241)
100 to 500(690 to 3445)
Switchable Between Manual and Automatic Reset
36 in. Cap. with1/4 in. Flare Nut
None 525 Low525 High
FOR AMMONIA
P70LA-2CSPST
20 in. to 100(–68 to 690)
Min 7 (48)Max 50 (345)
100 to 500(690 to 3445)
65 psi < 300 psig75 psi 300-400 psig95 psi > 400 psig
1/4 in. FemaleNPT Conn.
None
325 Low525 High(2241 Low)(3620 High)P70MA-2C Lockout
(Requires Manual Reset)1/4 in. FemaleNPT Conn.
471
TEMPERATURE & PRESSURE CONTROLS
JOHNSON CONTROLS P72 SERIES TWO-POLE LOW-PRESSURE CONTROL
JOHNSON CONTROLS P70 SERIES SINGLE-POLE LOW-PRESSURE CONTROL
DESCRIPTIONThe P72 Series of controls employs a set of DPST contacts that are opened and closed by the pres-sure actuated bellows. The heavy duty load-carrying contacts provide direct control of motors having integral line-interrupting overload protectors up to three horsepower, 240 volt, single phase. Starter is unnecessary. Primarily used on air-conditioning and refrigeration applications but also used to con-trol air, water, and lube oil pressure.
P1019
SELECTION CHART
P/N SWITCHACTION
RANGEpsig (kPa)
DIFFERENTIAL(psi)
PRESSURECONNECTOR
KNOBADJUSTMENT
MAX BELLOWSOVERPRESSURE
psig (kPa)
P72AA-1C DPST: Close High,Open Low
20 in. to 100 psi(–68 to 690)
Min 7 (41)Max 50 (345)
36 in. Cap. with1/4 in. flare Nut None 325 (2241)
DESCRIPTIONThis P70 Series of controls employs a set of switch contacts that are opened and closed by the movement of pressure actuated bellows. The load-carrying contacts provide direct con-trol of AC motors within the control rating. Note the electrical rating chart for specific models. These controls are available with either close high-open low, open high-close low, or SPDT contact action.
SELECTION CHART
*Adjusting knob supplied on differential (cut-out setting) to limit adjustments to 5 psi (34 kPa) above or below normal setting.
� � � � Universal Replacement.
P/N SWITCHACTION
RANGEpsig (kPa)
DIFFERENTIALpsi (kPa)
PRESSURECONNECTOR
LIMITED KNOBADJUSTMENT
MAX BELLOWSOVERRUN
PRESSUREpsig (kPa)
MICRO-SET™ FOR R-12, R-22, R-134a, R-500, R-502 (R)
� � � � P70AB-12C Close HighOpen Low
12 in. to 80(–40 to 551)
Min 5 (34)Max 35 (241)
36 in. Cap. with1/4 in. Flare Nut Cut-out* 525 (3620)
“ALL RANGE” FOR R-12, R-22, R-134a, R-500, R-502 (R)
� � � � P70AA-1C
Close HighOpen Low
20 in. to 100(–68 to 690)
Min 7 (48)Max 50 (345)
36 in. Cap with1/4 in. Flare Nut None
325 (2241)
� � � � P70AB-1C 1/4 in. MaleFlared Conn. Cut-out*
� � � � P70AB-2C 36 in. Cap. with1/4 in. Flare Nut Cut-out*
� � � � P70CA-1C Open HighClose Low
36 in. Cap. with1/4 in. Flare Nut None
P70EA-10C SPDT 5 (34) Fixed 1/4 in. MaleFlared Conn. None
FOR AMMONIA
P70AA-5C Close HighOpen Low 20 in. to 100
(–68 to 690)Min 7 (48)
Max 50 (345)1/4 in. Female NPT None 325 (2241)
P70CA-4C Open HighClose Low
P1019
SPST ELECTRICAL RATINGS (P70A and P70C Models)
STANDARDSINGLE-PHASE RATINGS
HERMETICCOMPRESSOR SINGLE-PHASE
RATINGS120 VAC 208 VAC 240 VAC 208/240 VAC
Motor Horsepower 1.5 3 3 —Motor Full-Load Amp 20 18.7 17 20
Motor Locked Rotor Amp 120 112.2 102 120Non-Inductive Amp 22 22 22 —
Pilot Duty 125 VA at 120 to 600 VAC; 57.5 VA at 120 to 300 VDC
SPDT ELECTRICAL RATINGS (P70E Models)
STANDARDSINGLE-PHASE RATINGS
120 VAC 208 VAC 240 VACMotor Full-Load Amp 16.0 9.2 8.0
Motor Locked Rotor Amp 96.0 55.2 48.0Non-Inductive Amp 16.0 9.2 8.0
Pilot Duty 125 VA at 120 to 600 VAC
472
TEMPERATURE & PRESSURE CONTROLS
JOHNSON CONTROLS V46 SERIES PRESSURE ACTUATED WATER REGULATING VALVEDESCRIPTIONThe V46 is a pressure actuated, modulating valve that is suitable for use either on closed or open systems. Direct acting valves open on pressure increase. This type of valve is primarily used to regulate the flow of water or glycol to a water cooled condenser on a refrigeration system. Reverse acting valves open on pressure decrease and are generally used in paral-lel with a direct-acting valve or for bypass operation.
P4409
SELECTION CHART
P/N PIPE SIZE(in.)
INLET AND OUTLET
OPENING POINTRANGE
psig (kPa)
PRESSURE ELEMENT STYLE
SEAT REPAIRKIT
REPLACEMENTPOWER ELEMENTS
COMMERCIAL TYPE, STANDARD FLOW — NON-CORROSIVE REFRIGERANTS (R)V46AA-1C 3/8 NPT
Threaded 70 to 260(483 to 1793)
30 in. Capillary1/4 in. Flare Nut
(Style 45)
STT14A-600R SEP91A-600R and SEC37A-601RV46AB-1C 1/2 NPT STT15A-602R SEP91A-602R and SEC37A-602RV46AC-1C 3/4 NPT STT16A-601R SEP91A-601R and SEC37A-602RV46AD-1C 1 NPT STT17A-609R
SEP91A-603R and SEC37A-600RV46AE-1C 1-1/4 NPTSTT17A-610R
V46AR-1C 1-1/2
4 HoleASME Flange
V46AS-1C 2 70 to 170(483 to 1172)
1/4 in. Male Flare Fitting (Style 5)
STT18A-600RSEP81A-602R
V46AS-2C 2 160 to 260(1103 to 1793) SEP81A-601R
V46AT-1C 2-1/2 70 to 170(483 to 1172)
STT18A-601RSEP81A-602R
V46AT-2C 2-1/2 160 to 260(1103 to 1793) SEP81A-601R
473
PRESSURE CONTROLS
ALCO FF115 SINGLE LOW PRESSURE CONTROLSThe FF115 Low Pressure Controls are designed to sense the suction pressure in refrigeration systems for cycling, limit and alarm applications. Maximum application flexibility and accuracy are assured by using a heavy-duty 24 amp single pole double throw (SPDT) switch and customized pressure ranges for precise sensing.
P1019
*Controls have an extended range.†For applications where the condensing unit/control is exposed to temperatures below 20° F, 1/4″ lines are recommended.
ALCO FF115 SINGLE HIGH-PRESSURE CONTROLS
PART NUMBERPRESSURERANGE IN
PSIG
DIFFERENTIALRANGE IN PSI
SWITCHACTION
PRESSURECONNECTION
REPLACES
Penn Copeland Ranco
FF-115-S1-BAK 24 to 42 3 to 30
SPDTAuto Reset
36″ Capillary with
1/4″ Flare Nut
P70AB-12* 085-0098-21O10-1402O16-557
FF-115-S3-BAK
15 to 100 7 to 70
P70AB-2P70AB-12P70CA-1
085-0098-00O10-1483O11-3099O16-527
FF-115-S3-BAA1/4″ SAE†Male Flare
P70AB-1P170AB-2,-12*
P170CA-1—
O10-1831O11-1799O16-107
The FF115 High Pressure Controls are designed to sense the high side pressure in refrigeration systems for high pressure limit, alarm and condenser fan control. Maximum application flexibility is assured by using a heavy-duty 24 amp single pole double throw (SPDT) switch and wide range pressure setting capability.
P1020
*FF115-S5-BRK has common power feed for limit and alarm function.†48” capillary.
**Limited to stock on hand.
PART NUMBER**PRESSURERANGE IN
PSIG
DIFFERENTIALRANGE IN PSI
SWITCHACTION
PRESSURECONNECTION
REPLACES
Penn Copeland Ranco
FF-115-S4-BAK 15 to 290 15 to 145
SPDTAuto Reset
36″ Capillary with
1/4″ Flare Nut
P70AA-2 085-0098-33O10-2000O16-593
FF-115-S5-BAK
90 to 450
30 to 220
P70AA-118P70CA-3
085-0098-08O10-2054O11-1711O16-108
FF-115-S5-BAA1/4″ SAE
Male Flare
P70CA-2P170AA-118P170CA-3
—
O10-1894O11-1713O16-503O16-570
FF-115-S5-BRK60 PSI fixed
SPDTManual Reset
Trips onpressure rise
36″ Capillary with
1/4″ Flare Nut
P70DA-1P70KA-1*
— O16-200†
FF-115-S5-BRA1/4″ SAE
Male FlareP170DA-1 — O16-209
FF115 ELECTRICAL RATINGS
MAXIMUM LOAD 120 VAC 240 VACFull Load Amps 24 FLA 24 FLALocked Rotor Amps 144 LRA 144 LRAHorsepower 2 HP 3 HPPilot Duty 720 VA 720 VANoninductive 24 amps 24 amps
FF115 DIMENSIONAL DRAWINGS
474
PRESSURE CONTROLS
ALCO PS1 SERIES SINGLE PRESSURE CONTROLS
NOMENCLATURE - EXAMPLE PS1-A5K
PS1 A 5 K
Product Name Function Pressure Range Pressure Connector Type
PS1 = Adjustable singlePressure Control
PSA = Customer specials
A = Pressure control, automatic reset,internal range & differential adjustments
B = Pressure cut out, external manualreset, DIN/TUV approved, internalrange and differential adjustments*, †
R = Pressure cut out, external manual reset,internal range and differential adjustments*, †
S = Safety pressure cut out, internal manual reset, DIN/TUV approved, internalrange & differential adjustments*, †
U = Convertible from R to AW = Pressure control, automatic reset,
DIN/TUV approved, internal range and differential adjustments
X = Pressure control, automatic reset, external range and differential adjustments
Y = Pressure cut out, external manual reset, external range and differential adjustments
*Function types B, R, S in combination with Pres-sure Range 1 or 3 have a low pressure manual reset function. (15 psi differential)
†Function types B, R, S in combination with Pres-sure Range 4 or 5 have a high pressure manual reset function. (60 psi diff.)
1 = 24″ Hg to 42 psi (-0.75 to 3 bar)2 = 26″ Hg to 21 psi (-0.8 to 1.5 bar)3 = 15″ Hg to 100 psi (-0.5 to 7 bar)4 = 15 to 290 psi (1 to 20 bar)5 = 90 to 450 psi (6 to 31 bar)
A = 7/16″-20 UNF male for 1/4″ SAE male flare
C = R 1/4″ stainless steel with steel bellows
F = 1/4-18 NPTF stainless steelwith steel bellows
K* = 7/16″ -20 UNF flare nut with1 meter (3 ft) cap tube
L = 1/4″ ODF solder with 1 meter (3 ft) cap tube
R = R 1/4″U = 6 mm ODF solder, 80 mm tube
lengthX = 1/4″ ODF solder, 80 mm tube length
*Controls with housing variant X/Y have extended copper ends, without Schrader valve depressor. All other housing variants have schrader valve depressor and brass end fitting with copper gasket.
PS1 Single Pressure Controls are designed for use on high and low pressure applications in refrigeration and heat pump systems. By operating a set of electrical contacts, a pressure is kept inside a certain limit.
FEATURES
• Adjustable pressures and differentials.• Narrow adjustable differential depending on model.• Range and differential pointer in units bar and psig.• Range and differential individually lockable by wire seal.• High rated SPDT contacts for all versions.• Captive terminal and cover screws.• Manual toggle for system checkout and override.• Factory installed wire bridge for reduced installation
effort.
OPTIONS
• Different pressure connections.• Automatic and manual reset versions.• Factory set to customer specifications.• Different types of mounting brackets.
SPECIFICATIONS
• SPDT switch rated for 120 VAC/240 VAC at 24 FLA and 144 LRA.
• Agency approvals include: UL/CUL file #E85974,VDE 0631/0660, TUV, CE 73/23/EWG, CE 93/68/EWG.
• Low pressure and high pressure versions available with TUV approval according to EN 12263 (supersedes DIN 32733) to meet requirements of DIN 8901 and EN378 (supercedes DIN 8975).
FF115 REPLACEMENT
475
PRESSURE CONTROLS
ALCO PS1 SERIES SINGLE PRESSURE CONTROLS
Standard Product Offering.
*Product Code Number.
P/NALCO U.S.
PCN
ALCOEUROPE
PCN
ADJUSTMENT RANGE FACTORYSETTIG
PSI (BAR)
PRESSURECONNECTIONUpper Setpoint
PSI (BAR)Diff. Setpoint
PSI (BAR)LOW PRESSURE CONTROLSTPC-PS1-X1K 097898 24″ Hg to 42 (-.75 to 3) 4 to 29 (.25 to 2) 7/15 (.5/1) Capillary/nut
PS1-A3A 4370700
15″ Hg to 100(-0.5 ... +7)
7 to 73(0.5 ... 5)
50/65(3.5/4.5)
7/16″ -20 UNFTPC-PS1-X3A 097914 7/16″ -20 UNF, 1/4″ SAE male
PS1-A3K 4370600 Capillary/nutTPC-PS1-X3K 097904 Capillary/nut
PS1-A3L 4714945 Capillary/solderPS1-A3U 4714945 Solder 6 mmPS1-A3X 4713430 Solder tube 1/4″PS1-R3A 4350100
15″ Hg to 100(-0.5 ... +7)
ExternalManual ResetLow Pressure
15 psi(1 bar) fixed
50 (3.5)
7/16″ -20 UNFPS1-R3K 4713431 Capillary/nutPS1-R3L 4715135 Capillary/solderPS1-R3U 4713432 Solder 6 mmPS1-R3X 4713433 Solder tube 1/4″
HIGH PRESSURE CONTROLSTPC-PS1-X4K 097901 15 to 290 (1 to 20) 15 to 100 (1 to 7) 145/115 (10/8) Capillary/nut
PS1-A5A 4350500
90 to 450(6 ... 31)
29 to 217(2 ... 15)
230/290 (16/20) 7/16″ -20 UNFTPC-PS1-X5A 097919 190/280 (10/19) 7/16″ -20 UNF
PS1-A5K 4370400230/290(16/20)
Capillary/nutTPC-PS1-X5K 097908 Capillary/nut
PS1-A5L 4715136 Capillary/solderPS1-A5U 4713325 Solder 6 mmPS1-A5X 4713434
90 to 450(6 ... 31)
Ext. Manual ResetHigh Pressure
60 psi(4 bar) fixed
290 (20) Solder tube 1/4″PS1-R5A 4350700 290 (20) 7/16″-20 UNF
TPC-PS1-Y5A 097923 390 (27) 7/16″-20 UNF, 1/4″ SAE malePS1-R5K 4370300
290 (20)
Capillary/nutTPC-PS1-Y5K 097911 Capillary/nut
PS1-R5L 4715137 Capillary/solderPS1-R5U 4713435 Solder 6 mmPS1-R5X 4713436 Solder tube 1/4″
PRESSURE LIMITER FOR LOW PRESSURE PROTECTIONPS1-W3A 4368300
15″ Hg to 100(-0.5 ... +7)
7 to 73(0.5 ... 5)
50/65(3.5/4.5)
7/16″-20 UNFPS1-W3K 4321400 Capillary/nutPS1-W3L 4715138 Capillary/solderPS1-W3U 4713437 Solder 6 mmPS1-W3X 4713438 Solder tube 1/4″
PRESSURE CUT OUT FOR LOW PRESSURE PROTECTIONPS1-B3A 4470400
15″ Hg to 100(-0.5 ... +7)
Ext. Manual ResetLow Pressure
15 psi(1 bar) fixed
65 (4.5)
7/16″-20 UNFPS1-B3K 4715139 Capillary/nutPS1-B3L 4715140 Capillary/solderPS1-B3U 4715141 Solder 6 mmPS1-B3X 4715142 Solder tube 1/4″
PRESSURE LIMITER FOR HIGH PRESSURE PROTECTIONPS1-W5A 4353200
90 to 450(6 ... 31)
29 to 217(2 ... 15)
230/290(16/20)
7/16″-20 UNFPS1-W5K 4359100 Capillary/nutPS1-W5L 4715143 Capillary/solderPS1-W5U 4713439 Solder 6 mmPS1-W5X 4713440 Solder tube 1/4″
476
PRESSURE CONTROLS
ALCO PS1 SERIES SINGLE PRESSURE CONTROLSORDERING INFORMATION FOR PS1 SINGLE PRESSURE CONTROLS
Standard Product Offering.*Product Code Number.
P/N ALCO U.S.PCN
ALCO EUROPEPCN
ADJUSTMENT RANGEFACTORY SETTING
PSI (BAR)PRESSURE
CONNECTIONUpper SetpointPSI (BAR)
Diff. SetpointPSI (BAR)
PRESSURE CUT OUT FOR HIGH PRESSURE PROTECTIONPS1-B5A 4353300
90 to 450(6 ... 31)
Ext. Manual ResetHigh Pressure
60 psi(4 bar) fixed
290 (20)
7/16″-20 UNF
PS1-B5K 4359200 Capillary/nutPS1-B5L 4715144 Capillary/solderPS1-B5U 4712332 Solder 6 mmPS1-B5X 4713441 Solder tube 1/4″
SAFETY PRESSURE CUT OUT FOF HIGH PRESSURE PROTECTIONPS1-S5A 4368400
90 to 450(6 ... 31)
Int. Manual ResetHigh Pressure
60 psi (4 bar) fixed304 (21)
7/16″-20 UNF
PS1-S5K 4359400 Capillary/nutPS1-S5L 4715145 Capillary/solderPS1-S5U 4711591 Solder 6 mmPS1-S5X 4713442 Solder tube 1/4″
*The Alco control may be used with bracket (PCN 097221) to allow placement of the Copeland control with the same mounting configuration.
OLD TO NEW CROSS REFERENCE (TF115 TO TS1) REPLACES THE COMPETITIONOLD MODEL OLD PCN NEW MODEL NEW PCN COPELAND* RANCO PENN DANFOSS SAGINOMIYA
FF115-S1-BAK 097450 PS1-X1K 7/15 097898085-0098-21985-CP1A-1K
O10-1402O16-557 P70AB-12
FF115-S4-BAK 097565 PS1-X4K 115/145 097901 085-0098-33 O10-2000O16-593
P70AA-2
FF115-S3-BAK 097451 PS1-X3K 50/65 097904 085-0098-00985-CP1A3K
O10-1483O11-3099O16-527
P70AB-12P70AB-2P70CA-2
FF115-S5-BAK 097452 PS1-X5K 230/290 097908085-0098-08985-CP1A-5K
O10-2054, O11-1711O16-108, O20-7006
P70AA-118P70CA-3
FF115-S5-BRK 097453 PS1-Y5K 230/290 097911 O16-200P70DA-1P70KA-1
FF115-S3-BAA 097459 PS1-X3A 50/65 097914 985-CP1A-3AO10-1401, O10-1831O11-1799, O16-106
O16-107
P170AB-12P170AB-2
KP1 60-1101 SNS-C106X
FF115-S5-BAA 097460 PS1-X5A 140/280 097919 985-CP1A-5AO10-1894, O11-1713
O16-503, O16-570O16-106
P170AA-118P170CA-3
P77AAA-9350P77AAA-9370
KP5 60-1171SNS-C130XSNS-C135X
FF115-S5-BRA 097462 PS1-Y5A 330/390 097923 O16-209, O16-106P170DA-1
P77BEA-9350P77BEA-9370
KP 60-1173
PS1-U5A 385 985-CP1U-5APS1-U5K 385 985-CP1U-5K
PS1 DIMENSIONAL DIAGRAM
DIMENSIONS SHOWN ARE IN INCHES.
477
PRESSURE CONTROLS
ALCO PS1 SERIES SINGLE PRESSURE CONTROLSPS1 PARTS/ACCESSORIES
UNIVERSAL ANGLE BRACKETAlco U.S. PCN #097064, KB-00026
Alco Europe PCN #0153962
ANGLED MOUNTING BRACKETAlco U.S. PCN #097215, KB-00028
Alco Europe PCN #0411746
MOUNTING BRACKET Z TYPEAlco U.S. PCN #097063, KB-00025
Alco Europe PCN #0411759
KNOB AND LOCK PLATE KITAlco U.S. PCN #097061, KB-00024
Alco Europe PCN #0163191
Kit consists of adjustment knob, lockplate (2),pan-head screw (1) and fillister head screw
with lock-wire hole (2).
478
PRESSURE CONTROLS
ALCO FF215 DUAL PRESSURE CONTROLS
*Controls have an extended range.†For applications where the condensing unit/control is exposed to temperatures below 20° F, 1/4” lines are recommended.
**Limited to stock on hand.
FF215 DIMENSIONAL DRAWINGS
PART NUMBER**LOW PRESSURERANGE IN PSIG
LO PRESS. DIFF.RANGE IN PSI
HIGH PRESSURERANGE IN PSIG
HI PRESS. DIFF.RANGE IN PSI
SWITCHACTION
PRESSURECONNECTION
FF-215-S9-BAUK 24 to 42 3 to 30
90 to 450 60 fixed
LP SPDT Auto Reset
HP SPDTConvertible—User Selects
Auto or Manual Reset
(2) 48″ Capillarywith
1/4″ Flare NutFF-215-S7-BAUK
15 to 100 7 to 70FF-215-S7-BAUA
1/4″ SAE Male Flare†
PART NUMBERREPLACES ALCO
PART NUMBERREPLACES
PENN COPELAND RANCO PENN COPELAND RANCO
FF-215-S9-BAUKP70LB-6*
P70MA-18*085-0098-22085-0098-23
O12-1502O12-1506O12-1554O12-4833
FF215-S7 BAUK P70LB-1,-6085-0098-02085-7000-00
O12-1549O12-4834
FF215-S7 BAUAP170LB-1P170MA-1
— O12-1550
FF215 ELECTRICAL RATINGS
MAXIMUM LOAD 120 VAC 240 VACFull Load Amps 24 FLA 24 FLALocked Rotor Amps 144 LRA 144 LRAHorsepower 2 HP 3 HPPilot Duty 720 VA 720 VANoninductive 24 amps 24 ampsP1021
P1022
479
PRESSURE CONTROLS
ALCO PS2 SERIES DUAL PRESSURE CONTROLSPS2 Dual Pressure Controls are designed for use on high and low pressure applications in refrigeration and heat pump sys-tems. By operating a set of electrical contacts, a pressure is kept inside certain limits.
FEATURES
• Adjustable pressures and differentials.• Narrow adjustable differential depending on model.• Range and differential pointer in units bar and psig.• Range and differential individually lockable by wire seal.• High rated SPDT contacts for all versions.• Captive terminal and cover screws.• Manual toggle for system checkout and override.• Factory-installed wire bridge for reduced installation effort.
OPTIONS• Different pressure connections.• Automatic and manual reset versions.• Factory set to customer specification.• Different types of mounting brackets.
SPECIFICATIONS• SPDT switch rated for 120 VAC/240 VAC at 24 FLA and
144 LRA.• Agency approvals include: UL/CUL file #E85974, VDE
0631/0660, TÜV, CE 73/23/EWG, CE 93/68/EWG.• Low pressure and high pressure versions available with TÜV
approval according to DIN 32733 to meet requirements ofDIN 8901and DIN 8975.
FF215 REPLACEMENTNOMENCLATURE — Example PS2-G8A
PS2 G 8 AProduct Name
PS2 = Adjustable DualPressostat
PSB = Customer SpecialVersion
FunctionA = Both sides: Pressure controls, automatic reset,
internal range and differential adjustmentsB = Both sides: Pressure cut out, external manual
reset, DIN/TÜV approved, internal range anddifferential adjustments
C = Left side: Pressure control, automatic reset,DIN/TÜV approved, internal range and differentialadjustments. Right side: Safety cut out, externalmanual reset, DIN/TÜV approved, internal rangeand differential adjustments.
G = Left side: Pressure control, automatic reset,DIN/TÜV approved, internal range and differentialadjustments. Right side: Safety limiter, internalmanual reset, DIN/TÜV approved, internal rangeand differential adjustments.
L = Left side: Pressure control, automatic reset,internal range and differential adjustments.Right side: Pressure cut out, external manualreset, internal range and differential adjustments.
M = Left side: Pressure control, automatic reset,internal range and differential adjustments.Right side: Convertible reset from R to A, internalrange and differential adjustments.
R = Both sides: Pressure cut out, external manualreset, internal range and differential adjustments.
S = Both sides: Pressure safety cut out, internalmanual reset, DIN/TÜV approved, internal rangeand differential adjustments.
T = Left side: Pressure control, automatic reset,DIN/TÜV approved, internal range and differentialadjustments. Right side: Safety limiter, internalmanual reset, DIN/TÜV approved, internal rangeand differential adjustments.
U = Both sides: Convertible from R to A.W = Both sides: Pressure control, automatic reset,
TÜV approved, internal range and differentialadjustments.
X = Both sides: Pressure controls, automatic reset,external range and differential adjustments.
Y = Left side: Pressure control, automatic reset,external range and differential adjustments.Right side: Convertible from external manual resetto automatic reset, external range and differentialadjustments.
Z = Both sides: Convertible from external manual resetto automatic reset, external range and differentialadjustments.
LOW PRESSURE MANUAL RESET: Cut outs with manual reset function and in combination with the low pressure side of Pressure Ranges 7 and 9 have a low pressure manual reset function (15 psi differential).HIGH PRESSURE MANUAL RESET: Cut outs with manual reset function and in combination with the high pressure side of Pressure Ranges 7 and 9 have a high pressure manual reset function (60 psi differential).
Pressure Ranges7 = Left side: 15″ Hg to 100 psi
(-0.5 to 7 bar)Right side: 90 to 450 psi(6 to 31 bar)
8 = Left side: 90 to 450 psi(6 to 31 bar)Right side: 90 to 450 psi(6 to 31 bar)
9 = Left side: 24″ Hg to 45 psi(-0.75 to 3 bar)Right side: 90 to 450 psi(6 to 31 bar)
Pressure Connector TypeA = 7/16″ -20 UNF male for
1/4″ SAE flare fitting C = R 1/4″ stainless steel with
steel bellowsF = 1/4″ -18 NPTF stainless steel
with steel bellowsK* = 7/16″ -20 UNF flare nut with
1 meter (3 ft) cap tubeL = 1/4″ ODM solder with
1 meter (3 ft) cap tubeR = R 1/4″U = 6 mm ODF solder,
80 mm tube lengthX = 1/4″ ODF solder, 80 mm tube
length
*Controls with housing variants X/Y/Z have extended copper ends, without schrader valve depressor and brass end fitting with copper gasket
480
PRESSURE CONTROLS
ALCO PS2 SERIES DUAL PRESSURE CONTROLSORDERING INFORMATION FOR PS2 DUAL PRESSURE CONTROLS
Standard Product Offering.
*Product Code Number.
P/NALCO U.S.
PCN
ALCOEUROPE
PCN
ADJUSTMENT RANGEFACTORY SETTING
PRESSURE CONNECTION
Upper Setpoint DifferentialLeft
PSI (BAR)Right
PSI (BAR)Left
PSI (BAR)Right
PSI (BAR)Left
PSI (BAR)Right
PSI (BAR)COMBINED LOW AND HIGH PRESSURE CONTROLSTPC-PS2-A7A 097874 4353400
15″ Hg to 100(-0.5...7)
90 to 450(6...31)
7 to 72(0.5...5)
29 to 217(2...5)
50/65(3.5/4.5)
230/290(16/20)
7/16″ -20 UNFTPC-PS2-A7K 097875 4350900 Capillary/nutTPC-PS2-A7L 097876 4713565 Capillary/solder
PS2-A7U 4713415 Solder 6 mmPS2-A7X 4713416 Solder tube 1/4″
TPC-PS2-L7A 097877 4351100
15″ Hg to 100(-0.5...7)
90 to 450(6...31)
7 to 72(0.5...5)
External Manual ResetHigh Press.60 (4) fixed
50/65(3.5/4.5)
290(20)
7/16″ -20 UNFPS2-L7K 4370500 Capillary/nut
TPC-PS2-L7L 097878 4440800 Capillary/solderPS2-L7U 4713417 Solder 6 mmPS2-L7X 4713418 Solder tube 1/4″PS2-R7A 4351300
15″ Hg to 100(-0.5...7)
90 to 450(6...31)
External Manual ResetLow Press.15 (1) fixed
External Manual ResetHigh Press.60 (4) fixed
50(3.5)
290(20)
7/16″ -20 UNFPS2-R7K 4713421 Capillary/nutPS2-R7L 4715134 Capillary/solderPS2-R7U 4713419 Solder 6 mmPS2-R7X 4713420 Solder tube 1/4″
COMBINED PRESSURE LIMITER FOR LOW PRESSURE/HIGH PRESSURE PROTECTIONPS2-W7A 4360100
15″ Hg to 100(-0.5...7)
90 to 450(6...31)
7 to 72(0.5...5)
29 to 217(2...5)
50/65(3.5/4.5)
230/290(16/20)
7/16″ -20 UNFPS2-W7K 4450200 Capillary/nutPS2-W7L 4450300 Capillary/solderPS2-W7U 4712436 Solder 6 mmPS2-W7X 4713429 Solder tube 1/4″
COMBINED PRESSURE LIMITER/PRESSURE CUT OUT FOR LOW PRESSURE/HIGH PRESSURE PROTECTIONPS2-C7A 4353500
15″ Hg to 100(-0.5...7)
90 to 450(6...31)
7 to 72(0.5...5)
External Manual ResetHigh Press.60 (4) fixed 50/65
(3.5/4.5) 290(20)
7/16″ -20 UNFPS2-C7K 4348400 Capillary/nutPS2-C7L 5715131 Capillary/solderPS2-C7U 4713422 Solder 6 mmPS2-C7X 4713423 Solder tube 1/4"
TPC-PS2-Y7A 097954Convertible Auto/Manual
Reset
7/16″ -20 UNTPC-PS2-Y7K 097943 Capillary/nut
TPC-PS2-Y9K 09795024″ Hg to 45
(-0.8...3)90 to 450(6...31)
4 to 29(.25...2)
7/15 Capillary/nut
481
PRESSURE CONTROLS
ALCO PS2 SERIES DUAL PRESSURE CONTROLSORDERING INFORMATION FOR PS2 DUAL PRESSURE CONTROLS
Standard Product Offering.
*Product Code Number.
*The Alco control may be used with bracket (PCN 097221) to allow replacement of the Copeland control with the same mounting configuration.
P/NALCO U.S.
PCN
ALCOEUROPE
PCN
ADJUSTMENT RANGEFACTORY SETTING
PRESSURE CONNECTION
Upper Setpoint DifferentialLeft
PSIG (BAR)Right
PSIG (BAR)Left
PSIG (BAR)Right
PSIG (BAR)Left
PSIG (BAR)Right
PSIG (BAR)COMBINED PRESSURE LIMITER/SAFETY PRESSURE CUT OUT — FOR LOW PRESSURE/HIGH PRESSURE PROTECTION
PS2-T7A 4368500
15″ Hg to 100(-0.5...7)
90 to 450(6...31)
7 to 72(0.5...5)
Internal Manual ResetHigh Press.60 (4) fixed
50/65(3.5/4.5)
290(20)
7/16″ -20 UNFPS2-T7K 4448000 Capillary/nutPS2-T7L 4715132 Capillary/solderPS2-T7U 4713424 Solder 6 mmPS2-T7X 4713425 Solder tube 1/4″
COMBINED PRESSURE CUT OUT — FOR LOW PRESSURE/HIGH PRESSURE PROTECTIONPS2-B7A 4360200
15″ Hg to 100(-0.5...7)
90 to 450(6...31)
External Manual Reset
Low Press.15 (1) fixed
External Manual ResetHigh Press.60 (4) fixed
65 (4.5)
290(20)
7/16″ -20 UNFPS2-B7K 4446600 Capillary/nutPS2-B7L 4446700 Capillary/solderPS2-B7U 4449400 Solder 6 mmPS2-B7X 4713426 Solder tube 1/4″
COMBINED PRESSURE CUT OUT — FOR HIGH PRESSURE/HIGH PRESSURE PROTECTIONPS2-G8A 4368600
15″ Hg to 100(-0.5...7)
90 to 450(6...31)
External Manual Reset
Low Press.15 (1) fixed
Internal Manual ResetHigh Press.60 (4) fixed
65 (4.5)
290(20)
7/16″ -20 UNFPS2-G8K 4445500 Capillary/nutPS2-G8L 4715133 Capillary/solderPS2-G8U 4713427 Solder 6 mmPS2-G8X 4713428 Solder tube 1/4″
OLD TO NEW CROSS REFERENCE (FF215 TO PS2) REPLACES THE COMPETITIONOLD MODEL OLD PCN NEW MODEL NEW PCN COPELAND* RANCO PENN DANFOSS SAGINOMIYA
FF215-S7-BAUK 097454PS2-Y7K 50/65*
230/290097943
085-0098-02085-7000-00
985-CP2M-7K
O12-1549O12-4834
P70LB-1P70LB-6P70MA-1P70MA-18
FF215-S9-BAUK 097455PS2-Y9K 7/15*
230/290097950
085-0098-22085-0098-23
O12-1502O12-1506O12-1554O12-4833
P70LB-1P70LB-6P70MA-1P70MA-18
FF215-S7-BAUA 097463PS2-Y7A 50/65*
230/290097954 985-CP2M-7A O12-1550
P170LB-1P170MA-1
FF215-S7-BAAA 097006PS2-A7A 50/65*
230/290097874 O17-108
P78LCA-9300P78LCA-9320
KP15 60-1241KP15 60-1265
DNS-D304XDNS-D306XDNS-D604XDNS-D606XDNS-D706X
FF215-S7-BAAK 097261PS2-X7K 50/65*
230/290097875
FF215-S7-BAAL 097145PS2-A7L 50/65*
230/290097876
FF215-S7-BARA 097034PS2-L7A 50/65*
290097877 O17-108
P78MCA-9300P78MCA-9320
KP15 60-1243KP15 60-1264
DNS-D304XMDNS-D304XMLDNS-D306XM
DNS-D306XMLDNS-D604XMDNS-D606XM
DNS-D606XMM
FF215-S7-BARL 097344PS2-L7L 50/65*
290097878
FF215-S7-BAUL 097057PS2-Y7L 50/65*
290097896
482
PRESSURE CONTROLS
ALCO PS2 SERIES DUAL PRESSURE CONTROLSPS1 DIMENSIONAL DIAGRAM
UNIVERSAL ANGLE BRACKETAlco U.S. PCN #097064, KB-00026
Alco Europe PCN #0153962
ANGLED MOUNTING BRACKETAlco U.S. PCN #097215, KB-00028
Alco Europe PCN #0411746
MOUNTING BRACKET Z TYPEAlco U.S. PCN #097063, KB-00025
Alco Europe PCN #0411759
KNOB AND LOCK PLATE KITAlco U.S. PCN #097061, KB-00024
Alco Europe PCN #0163191
Kit consists of adjustment knob, lockplate (2),pan-head screw (1) and fillister head screw
with lock-wire hole (2).
PS2 PARTS/ACCESSORIES
DIMENSIONS SHOWN ARE IN INCHES.
483
PRESSURE CONTROLS
ALCO FD113-ZU(K) OIL PRESSURE SAFETY CONTROLS
FEATURES
• Pressure range adjustable from 4 to 65 PSID; Timer startpressure-timer stop pressure is 3 PSID above timer start pressure.
• A SPDT switch is used in the pressure portion of the control which allows the addition of a “safe light” if desired.
• Electronic timer is Timer-Adjustable from 20 to 150 seconds.• Supply voltage - 24 to 240 Volt AC/DC. Timing unaffected by voltage or ambi-
ent temperature variations.• A SPDT Manual Reset Switch is used in the Timer Module. Upon time-out,
the compressor is stopped and an alarm circuit is energized. To restart the compressor and de-energize the alarm circuit, the reset button is pushed.
• A factory installed jumper allows the FD113 to be powered from a single power source. Should separate circuits be desired for the timer and “Lockout” switch, the jumper can be removed.
ORDERING INFORMATION FOR FD113-ZU(K) OIL PRESSURE SAFETY CONTROLS
*For applications where the condensing unit/control is exposed to temperatures below 20° F, 1/4″ lines are recommended.
P/N PCNADJUSTABLE
PRESSURE RANGEADJUSTABLE
TIMESUPPLY
VOLTAGEPRESSURE
CONNECTIONREPLACES
PENN COPELAND RANCO
TPC-FD-113-ZUK 097456
4-65 PSID20 to 150seconds
24 to 240VAC/DC
(2) 36″capillary with1/4″ flare nut
P45NCA-12P45NCA-82P28AA-1,-2
P28AA-17,-18P28DA-1P28GA-2P28NA-5
085-0062-00
P30-5826P30-3601P30-3701P30-3801
TPC-FD-113-ZU 097464 (2) 1/4″ male flare*P128AA-1,-2,-3
P145NCA-12,-82P145NCB-12,-82
P30-5827
FD113 DIMENSIONAL DATA
A typical 3 wire hookup with the factory installed jumper.
P1023AP1023B
P1023
The FD113 Oil Pressure Safety Control senses the effective oil pressure on pressure lubricate compressors. If inadequate oil pressure exists, a time delay is energized. If the oil pressure does not recover to safe levels within the time delay setting, the compressor is shut down. The time delay allows the compressor adequate time to establish oil pressure on start up and avoids nuisance shutdowns on pressure drop of short duration during the run cycle.
Maximum application flexibility is assured by providing an adjustable differential pressure switch which can be adjusted to the compressor’s minimum required oil pressure needs and an adjust-able electronic time delay which allows you to select the length of time the compressor runs below the minimum pressure before shutdown. The minimum pressure setting and time delay values specified by the compressor manufacturer should be used when installing the FD113 control.
DIMENSIONS SHOWN ARE IN INCHES.
SPECIFICATIONS
• Agency approvals include: UL/CUL file#E85974, VDE 0631/0660, TUV, CE 73/23/EWG, CE 93/68/EWG.