data center design guide featuring - utah...

35
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling

Upload: phamthu

Post on 17-Mar-2018

227 views

Category:

Documents


14 download

TRANSCRIPT

Page 1: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Data Center Design GuidefeaturingWater-Side Economizer Solutionswith Dynamic Economizer Cooling

Page 2: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Presenter:Jason Koo, P.EngSr. Field Applications EngineerSTULZ Air Technology Systems

jkoo@stulz‐ats.com

Page 3: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Water‐Side Economizer Solutions

OutlineASHRAE Standards and Guidelines relative to Precision Cooling

– ASHRAE 127‐2012– CEC Requirements– ASHRAE TC 9.9 – 2011– ASHRAE 90.1 ‐ 2010

Air & Water‐Side Economizers

Page 4: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

ASHRAE 127‐2012

New Test Standards• ASHRAE 127‐2012 Method for Testing for Rating Computer and Data

Processing Room Unitary Air Conditioners defines performance teststandards

• The purpose is to establish a uniform set of requirements for ratingprecision cooling equipment

• Significant changes in the 2012 edition1. Higher return air temperatures, thus increasing efficiency

• 75, 85, 95, 105 degrees F DB2. Higher chilled‐water entering temperatures3. A testing/rating procedure for equipment4. A testing/rating procedure for the newer technologies

a. Row based cooling systemsb. Containment systems

Page 5: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Raising return air temperature using containment• With a raised floor (Figure 1)

– Raised floor is pressurized with cold air from the precision cooling units

– Cold air passes through perforated floor tiles, taken into the servers, heated and exhausted into the contained hot aisle

– Hot air is directed back to the ceiling plenum, then returned to the CRAH units

• With a slab floor (Figure 2)– Utilizes server racks that have a top 

ducted chimney connection– A CRAH with front discharge floods 

the space with cold air, allowing the servers to take cold air in from the front 

– Hot air is discharged out to the chimney and returned to the CRAH unit via a return duct or ceiling plenum

Page 6: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Update of CEC Requirements 

On July 1st 2014• Adopting the SCOP requirements of ASHRAE 90.1‐2010 which are based

on the ASHRAE 127‐2007 test standard (75°F and 52° DP EAT’s)

• Requires 100% testing of a representative of each unit that will be offeredfor sale in the state of California

• Elimination of non‐adiabatic humidification and reheat

Page 7: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Adiabatic cooling provided (BTU/h)

Total KW/H per year*

Cost Per KWH

Annual Cost of 

Electricity

Ultrasonic 2,095,200 799,973 x $0.11  $87,997 

Feature Infrared Humidifier STULZ UltrasonicTechnology Infrared Ultrasonics

Capacity (lbs./hr.) 22 18

Energy Consumption (Watts) 9,600 585

Water Requirements Non‐conditioned city water

Demineralized water using RO and DI 

Maintenance Requirements ½ hour to remove mineral buildup in pan

No cleaning of ultrasonic required

Humidification Improves Efficiency

*KWH based on 1.23 KW/Ton for air cooled chiller

HumidificationTechnology

Number of Humidifiers Required

Watts Consumed

Annual Hours Of Operation

KW/H per year Cost Per KWH

Annual Cost of 

Electricity

Annual Savings

Infrared 98 x 9,600 x 3,725 x 3,504,480 x $0.11  x $385,493 

Ultrasonic 120 x 585 x 3,725 x 261,495 x $0.11  x $28,764  $356,728 

Humidification Energy Comparison

Free Cooling Energy SavingsHumidification

and Free Cooling Energy 

Savings$444,725 

Combined

Page 8: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

STULZ Ultrasonic Humidifier

DRH –Direct Room Humidifier

• Mounts below the ceiling in a conditioned space• On wall or column with factory furnished mounts• Suspended from above in open space • Integral blower and washable filter • Absorption distance determined by RH of room

Page 9: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Ultrasonic Humidifier in Space

Page 10: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

STULZ Ultrasonic Humidifier

DAH –Ducted Air Humidifier

• Mounts in moving air stream of AHU or ductwork• Multiple humidifiers assembled on factory rack system• Air velocity design similar to heating/cooling coils • Factory accessories for optimized airflow and mist control• Absorption distance determined by RH of airstream

Page 11: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Ultrasonic Humidifier in Duct

Page 12: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

ASHRAE Standards and GuidelinesASHRAE TC9.9 2011• Allowance for increased delta‐

T across server equipment• Offers an opportunity to raise 

the return air temperatures to the cooling equipment 

• Current trend for maximum efficiency in the data center – isolate the hot return air 

from the cold supply – prevent air mixing

• Opportunity to raise the delta‐T between the supply air temperature from the cooling equipment to the IT equipment and the return air temperature from the IT equipment to the cooling equipment 

What Has Changed  Inlet Air Temperature 

Moisture Content 

2004 Recommended (old) 

68‐77.0°F DB  40% RH to 55% RH 

2011 Recommended (new) 

64‐80.6°F DB  41.9°F DP to 60% RH & 59°F DP

2011 Allowable (A1)  59‐89.6°F DB  20‐80% RH up to 62.1°F DP 

Page 13: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Coil Calculations and Optimization• Higher return air 

temperature to the CRAC/CRAH equipment increases cooling efficiencies

• Increase Entering Air (to CRAH)

– Improve Net Sensible Capacity

– Decrease CRAH Unit Power– Decrease Chiller Power– Mix and match to achieve 

optimal conditions– More economizer hours, 

lower PUE, and lower energy costs

Page 14: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

ASHRAE 90.1 – 2010• Since data centers have been 

identified to consume ~3% of the total energy produced in the U.S., the former process cooling exemption is gone. 

• Water‐side economizers must meet 100% of the expected load with cooling towers when operating at or above 40°F dry bulb / 35°F wet bulb and with dry coolers when operating at or below 35°F dry bulb. 

• Evolution of Measuring Efficiency– ASHRAE 127 – 2007 guideline for 

Sensible Coefficient of Performance (SCOP)

– ASHRAE 90.1 – 2010 guideline for SCOP (used for this presentation)

– ASHRAE 127 – 2012 guideline for Net Sensible Coefficient of Performance (NSenCOP) 

The DOE is mandating that all states adopt ASHRAE 90.1‐2010, or a more stringent standard, for new data center design and construction by October 2013. 

Page 15: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Direct Free Cooling System, butcustomer provides dampersystem and filtration, andcontrols its operation.

Air Side Economizers

Outside Air & Moisture OperationWarmer / High Humidity Dampers close & the CRAC/CRAH revert to traditional operation

Within Proper Range Outside air is directly introduced through the dampers in the mixing box

Colder than Desired Dampers mix outside air & return air to achieve desired temperature

Air Side Economizers

Page 16: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Vertical and horizontal mixing boxes for air-side economizer options using floor-standing CRAC’s or CRAH’s

• CRACs or CRAHs with an integrated mixing box and damper controls provide direct free cooling

• Units attached to the top of a CRAC or CRAH in a vertical or horizontal position

• Pre-filter and freeze protection damper options

• Mixes outside and return air depending on outside air conditions

• Full economizer controls provided by the CRAC or CRAH

Air‐Side Economzer

Vertical & Horizontal Mixing Boxes

Page 17: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Air‐Side Economzer

Page 18: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Direct Air-Side Economizer • Outside air (less than supply air

temp) is directly introduced into the data center

Direct Adiabatic Cooling• The outside air is cooled with an

adiabatic system and directly introduced into the data center

Direct DX Cooling• The outside and/or return air is

cooled with a DX evaporator coil and directly introduced into the data center

Air‐Side Economizer

CyberHandler (AHU) with Direct Air Economizer, Direct Adiabatic Cooling, and DX for trim

Page 19: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Direct Air-Side Economizer • Outside air (less than supply air

temp) is directly introduced into the data center

Direct Adiabatic Cooling• The outside air is cooled with an

adiabatic system and directly introduced into the data center

Direct DX Cooling• The outside and/or return air is

cooled with a DX evaporator coil and directly introduced into the data center

Air‐Side Economizer

CyberCon (Modular/Container) with Direct Air Economizer, Direct Adiabatic Cooling, and DX for trim

Page 20: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

DX Cooling Section with Humidification

Ex. Nortec V‐Profile Evaporative Pad

• An option is to add an adiabatic pad for direct adiabatic cooling before the DX Coil

• DX Coil used for trim capacity

• Ultrasonic Humidifier used for humidification

DX CoilUltrasonicHumidifier

Air‐Side Economizer

Page 21: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Indirect Air-Side Economizer• Outside Air (less than supply air temp) passes through an air-to-air heat exchanger

to indirectly cool the data center return air

Indirect Adiabatic Cooling• The return air is indirectly cooled via an air-to-air heat exchanger that has an

adiabatic spray applied to it

Air‐Side Economizer

CyberHandler with Indirect Air Economizer, Indirect Adiabatic Cooling, and DX for trim Indirect Adiabatic

Cooling Module

Page 22: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

DX CRAC with Economizer Coil and Condenser Loop• Used with the following Water‐Side 

Economizers:– Traditional Economizer Cooling– Variable Economizer Cooling– Evaporative Tower Economizer 

Cooling

Page 23: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Types of Water Side Economizers

• DX Economizer Solutions– Traditional Economizer– Variable Economizer– Evaporative Tower Economizer

• CW Economizer Solutions– Dual‐Source Chilled Water 

Economizer– Dynamic Economizer Cooling

• Standard• Optimized

Page 24: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Traditional Economizer Cooling Comparison• Traditional Economizer 

Cooling– Constant fan speed dry 

cooler • fans cycled on and off based 

on fluid temperature

– Constant speed pumps– Water/glycol cooled free 

cooling CRACs • DX cooling coil and 

water/glycol free cooling coil

• Comparison of a CRAC to a CRAC with Free Cooling Coupled with a Constant Speed Fan Dry Cooler– Baltimore, MD– Salt Lake City, UT (4,500 ft 

altitude)– Portland, OR

Page 25: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Variable Economizer Cooling Comparison• Variable Economizer Cooling

– Variable fan speed dry cooler 

• fan speed controlled based on fluid temperature

– Variable speed pumps • controlled based on fluid 

temperature– Water/glycol cooled free 

cooling CRACs• DX and water/glycol free 

cooling coil

• Comparison of a CRAC to a CRAC with Free Cooling Coupled with a Variable Speed Fan Dry Cooler– Baltimore, MD– Salt Lake City, UT (4,500 ft 

altitude)– Portland, OR

Page 26: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Evaporative Tower Economizer Cooling Comparison• Evaporative Tower 

Economizer Cooling– Closed loop evaporative 

cooling tower • Controlled based on fluid 

temperature

– Constant speed pump– Water/glycol cooled free 

cooling CRACs• DX and water/glycol free 

cooling coil

• Comparison of a CRAC to a CRAC with Free Cooling Coupled with an evaporative cooling tower– Baltimore, MD– Salt Lake City, UT (4,500 ft 

altitude)– Portland, OR

Page 27: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Comparison of DX Economizer Cooling% Reduced Energy• Baltimore MD 

– Traditional Economizer Cooling verses DX Cooling ‐13%

– Variable Economizer Cooling verses DX Cooling ‐31%

– Evaporative Cooling Tower Economizer Cooling verses DX Cooling ‐32%

Page 28: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Dual‐Source Chilled Water Economizer Cooling• Dual‐Source Chilled Water 

Economizer Cooling– Evaporative cooling tower and 

pump• controlled based on fluid 

temperature– Air‐Cooled Chiller  and pump

• controlled based on fluid temperature

– CRAH units• dual circuited interlaced chilled 

water cooling coil

• Comparison of a CRAH Coupled with an Air‐Cooled Chiller to a CRAH with Dual Coils Coupled to an Air‐Cooled Chiller and Evaporative Cooling Tower– Baltimore, MD– Salt Lake City, UT (4,500 ft 

altitude)– Portland, OR

Page 29: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Dynamic Economizer Cooling (DEC)• A Dynamic Economizer Cooling 

(DEC) system (state‐of‐the‐art water‐side economizer solution)– Evaporative cooling tower– Air‐ cooled chiller– Cooling tower and chiller pumps– Control mixing valves– CRAH units

• Required cooling fluid temp < ambient conditions = operates in the cooling tower mode

• Required cooling fluid temp > ambient conditions = operates in the “chiller assisted cooling©” mode

• System minimizes hours of chiller operation and optimizes opportunity for economization

Page 30: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Warm Water Cooling 

Page 31: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Power Usage Effectiveness (PUE)Evaluating Power Usage Effectiveness• Power Usage Effectiveness (PUE) 

– Measurement of data center efficiency (by The Green Grid)

• PUE = (IT Load + Total Power) / IT Load– IT Load is the effective processing equipment power of the data center– Total Power includes security, cooling, lighting, fire monitoring, etc. 

• Industry Benchmarks– PUE < 1.6 considered very good– PUE < 1.2 is state‐of‐the‐art

Page 32: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Latest News  

Page 33: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Outdoor Cooling Indoor Cooling Retrofit and Conditioning

Utility Rebates Further Improve ROI

Utility Rebates Further Improve ROI

• Many utility companies are running out of capacity

• Most utility companies are offering incentive programs for:

• Retrofitting existing cooling equipment

• Replacing cooling equipment

• Installing new energy efficient cooling equipment

• Most energy efficient solutions available

• Sales Rep and Applications Engineering can:

• Help calculate the energy savings for STULZ solutions

• Provide you with an energy analysis report

• Sales Rep can:

• Introduce you to your local utility

• Initiate the rebate process by starting the paperwork

Customers have received hundreds of thousands of

$’s in rebates

Page 34: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Conclusions

• By providing an economizer, power usage is significantly reduced during cooling ambient conditions.

• By elevating return air temperature and elevating water temperatures, effective economizer hours are increased.

• Increase in effective economizer hours will reduce energy consumption of the cooling equipment.

• Reduction of energy by cooling equipment equates to smaller PUE values. 

• Additional Savings Potential (Energy and Capital)– Eliminate the raised floor by utilizing CRAH’s with front discharge and 

racks with integrated hot air containment (entire white space used as a cold aisle)

– Reduce chiller requirements and related maintenance, by specifying/sizing only for the minimum trim capacity required 

– Reduce gen‐set requirements and related maintenance, by specifying/sizing for the much lower energy required by the system

Page 35: Data Center Design Guide featuring - Utah ASHRAEutahashrae.org/wp-content/uploads/2015/04/Water-Side_Economizer...Data Center Design Guide featuring Water-Side Economizer Solutions

Presenter:Jason Koo, P.EngSr. Field Applications EngineerSTULZ Air Technology Systems

jkoo@stulz‐ats.com