data & facts gea close control - delta gcideltagci.com/pdf/dencotrangedatafacts.pdfgea close...
TRANSCRIPT
Air Treatment Division
DATA & FACTS
GEA Close ControlT-Range – Aerial values always on the level
Description GEA Close Control T-Range
2 PR-2006-0295-GB Subject to modifications Status 10/2007
The T-Range .......................................................................................3
Upflow and Downflow Versions Direct Expansion and Chilled Water Units .............................................................3
Key to Type Codes .................................................................................................3
Energy Saving Options .....................................................................4 Dimensions and Weights ...................................................................5
Dimensions and Weights – D/U 3 – 42 ...................................................................5
Dimensions and Weights – D/U 48 - 83 ..................................................................6
Service Entry / Access ......................................................................5 Guide Specification ...........................................................................8 Typical Airflow Arrangements ........................................................11 General Details ................................................................................11 Cooling Performance ......................................................................15
Cooling Performance – Models 3 – 19 ..................................................................15
Cooling Performance – Models 21 – 42 ................................................................16
Cooling Performance – Models 48 – 83 ................................................................17
Electrical Details ..............................................................................18 "X" Version.............................................................................................................18
"A" Version.............................................................................................................19
"W" and "F" Versions.............................................................................................20
"C" Version ............................................................................................................21
Schematic Diagrams .......................................................................22 "X" Version.............................................................................................................22
"A" Version.............................................................................................................23
"W" Version............................................................................................................24
"F" Version.............................................................................................................25
"C" Version ............................................................................................................26
Ancillaries and Options ...................................................................27
GEA Close Control The Range T-Range Key to Type Codes
PR-2006-0295-GB Subject to modifications Status 10/2007 3
Upflow and Downflow Versions Direct Expansion and Chilled Water Units
The “T” Range comprises nineteen (19) models, in six (6) cabinet sizes, with nominal capacities from 3 kW to 80 kW in the following versions: -
- X: Split System using Denco Condensing Units. - A: Air Cooled DX System with inbuilt compressor(s) and using Denco DCRA
Condensers. - W: Water Cooled DX System with inbuilt compressor(s) and Water Cooled
Condensers. - F: Ambicool System. - C: Chilled Water System.
Key to Type Codes Example: U 28 A V G H
H = Humidifier fitted G = Front Grille Return [Upflow only – not on U48 - U83]
(as opposed to underfloor return) V = Variable Refrigerant Flow (VRF)
A = X - Split System A - Air Cooled System W - Water Cooled System F - Ambicool System D - Combicool system C - Chilled Water System
28 = Unit Size: 3, 4, 5, 8, 10, 12, 17, 19, 21, 23, 28, 32, 37, 42 48, 53 63, 73 and 83 (models available dependent on System)
U = Upflow (D = Downflow)
Energy Saving Options GEA Close Control T-Range
4 PR-2006-0295-GB Subject to modifications Status 10/2007
“T” Range air conditioning units incorporate all of the energy/cost saving benefits for which Denco products are renowned. These include:
Ambicool (Glycol freecooling system) - "F" Version (not available on models 48 – 83) This substantially reduces annual energy consumption, and consequently costs, by exploiting low average ambient temperatures to provide partial or full freecooling. It is very unusual to experience the design summer ambient for any length of time, and external temperatures are generally considerably less for much of the year. This allows the drycooler to produce glycol at lower temperatures.
When the glycol is colder than the room air, it is passed through the economy coil before reaching the condenser, picking up some heat directly from the room rather than via the refrigeration system. Under conditions such as this, the compressor run time is reduced, thereby saving energy. As an example, some degree of freecooling is usually available for 70% of the year in northern Europe, giving very substantial running cost savings.
Variable Refrigerant Flow (VRF) - "V" Option This provides various compressor options for efficient part-load performance, with exceptional economy.
Full Cooling Load Both compressors running to circulate the full design refrigerant flow in order to achieve specified maximum cooling capacity. The scroll compressor coefficient of performance (COP) is typically 3.5.
Part Load Operation Lead compressor only running to circulate approximately 60% of the refrigerant flow. Evaporator and condenser are both oversized under this condition, causing increase in suction pressure and a reduction in discharge pressure. Resultant part-load COP increases to typically 5.0.
Secondary benefits include reduced temperature swing and increased compressor reliability caused by reduced cycling and an optional two-stage high-pressure trip. Lower inrush current and inbuilt redundancy is also provided by dual compressors and reduced humidifier run time – due to the very high sensible heat ratio achieved at the higher evaporating temperatures. Payback period is typically less than one year.
GEA Close Control Dimensions and Weights – D/U 3 - 42 T-Range
PR-2006-0295-GB Subject to modifications Status 10/2007 5
Unit Weights - kgs
Model "X" "A" "W" "F" "C"
D / U 3 - 5 135 165 175 N/A 140
D / U 8 - 12 210 255 270 305 215
D / U 17 - 28 345 445 460 505 355
D / U 32 - 42 420 520 535 590 430
Dimensions and Weights – D/U 48 - 83 GEA Close Control T-Range
6 PR-2006-0295-GB Subject to modifications Status 10/2007
Unit Weights - kgs
Model "X" "A" "W" "F" "C"
D / U 48 - 53 660 860 890 N/A 680
D / U 63 - 83 810 1010 1040 N/A 830
GEA Close Control Service Entry / Access T-Range
PR-2006-0295-GB Subject to modifications Status 10/2007 7
The “T” Range of air conditioning units has been designed to be completely front access for service/maintenance via the front hinged/removable doors. Therefore, no allowance for access to the ends or back is necessary, although the end panels can be removed in-situ if required.
Guide Specification GEA Close Control T-Range
8 PR-2006-0295-GB Subject to modifications Status 10/2007
Cabinet The cabinets shall be attractively designed having bevelled corners with flush fitting curved panels. Units shall have a rigid frame, manufactured from non corroding Aluzink, with hinged curved front panel(s) to provide access for installation and servicing. Panels shall be lined with class "O" non eroding insulation material with both thermal and acoustic properties. External panels shall be manufactured from pre-coated steel, colour Grey (RAL number 7024).
Cooling Coil The coils shall be multi row constructed from 3/8" O/D copper tubes with mechanically bonded aluminium fins. Direct expansion coils shall have internal grooving for optimum heat transfer. The coil face area shall be maximised to ensure high sensible heat ratio and low airside pressure drop, thereby minimising fan power and noise level. A stainless steel drain tray shall be included to ensure efficient removal of the condensate, via a factory fitted trap.
- DX: Units shall have one, two or four refrigeration circuits (dependent upon model), inclusive of liquid distributor, expansion valve, solenoid valve, sight glass and filter drier, and these components shall be housed in the cabinet.
- C: Units shall be fitted with a modulating 3 way valve having manual override facility with water pressure / temperature test points, and these components shall be housed in the cabinet.
Fans “T” Range models 3 to 5 shall be fitted with one fan, which shall be single inlet backward curved centrifugal, and shall be direct driven by an integral motor. A differential pressure switch shall be fitted to monitor airflow, failure of which shall result in an alarm and automatic disabling of all functions. The fan motor shall be single speed, the final airflow therefore depending on exact static pressure requirements.
“T” Range models 8 to 42 shall be fitted with one, two or three fans, whilst models 48 to 83 shall be fitted with four or six fans, depending on unit size. The fans shall be double inlet, double width with forward curved impeller, and shall be direct driven by an integral motor. A differential pressure switch (8-42) and current monitoring relay (48-83) shall be fitted to monitor airflow, failure of which shall result in an alarm and automatic disabling of all functions. Fan motors shall be three speed. HIGH or MEDIUM speed shall be factory selected, depending on airflow and static pressure requirement, and LOW speed shall be assigned for dehumidification mode.
GEA Close Control Guide Specification T-Range
PR-2006-0295-GB Subject to modifications Status 10/2007 9
Electric Heaters Electric heaters shall have rigid Incoloy sheathed elements with stainless steel finning balanced over three phases and rated to operate at black heat. Control shall be in one or two stages, each stage being protected by a high temperature safety cut-out.
Filtration The filters shall have an efficiency of 30 % ASHRAE 52/76 Eurovent 4/5 arrestance value 90 % (G4). They shall be fitted in the return air stream, held by quick release retaining clips, and be accessible from the front of the unit. A differential pressure switch shall be fitted which, through the alarm facility in the microprocessor controller, shall indicate when the filters need changing.
Water Cooled Condensers The condenser shall be a compact brazed plate heat exchanger having a multiplicity of parallel stainless steel pressed plates. The construction shall give high turbulent flows resulting in a compact heat exchanger form with low pressure drops.
Humidifier The humidifier shall be of the electrode boiler type, located in the bottom of the unit. Features shall include proportional steam output and microprocessor control with alarms and diagnostic facilities. The control system shall allow the use of a wide range of mains water conditions and optimise drain down frequency for maximum operational economy.
Compressor and Safety Controls Robust fully hermetic scroll compressor(s) shall be located either in the base of the unit on "A", "W" and "F" systems or the outdoor condensing unit on "X" systems. The compressor(s) shall be resiliently mounted on a robust frame, which assists to minimise noise and vibration transmission to the structure. The compressor(s) shall be fitted with back seating isolating valves together with crankcase heater ("X" systems only) and oil level sight glass on larger models. Protection shall be provided by an internal self-setting overload device and pressure relief valve.
An external adjustable high pressure cut off switch, with manual reset facility shall be provided for high pressure protection, in addition to the internal devices. To protect primarily against loss of refrigerant charge, an adjustable low pressure switch shall also be provided, which includes an automatic reset facility.
A low pressure Alarm delay function is fitted to facilitate low ambient start condition as standard.
Dehumidification This shall be achieved by switching on a single stage of cooling and automatic selection of low fan speed (models 8 to 42).
Guide Specification GEA Close Control T-Range
10 PR-2006-0295-GB Subject to modifications Status 10/2007
Electrical Panel The electrical switchgear shall be contained in a cubicle located in the top of the unit, and shall include: - Controller baseboard and modules (if applicable) - MCB's and contactors for fans, heaters, humidifier and compressors as
appropriate - MCB's for remote condensing units (if applicable) - MCB's plus pressure operated on off switches for remote condensers (if
applicable)
Cabling shall be colour coded and numbered, and neatly run in trunking segregating high and low voltages. All wiring shall comply with BS EN 60204 Part 1.
Microprocessor Controls All units shall be fitted, as standard, with a C3-05 advanced microprocessor controls system, designed by Denco. This shall provide maximum economy of operation, a comprehensive intelligent alarm system and a wide range of information for operators and service engineers. All information shall be presented in a user friendly format with tamper proof setting up arrangements.
In addition to precise control of temperature and humidity, the system shall include the following features: - A liquid crystal semi - graphical display indicating unit function via icons,
displaying control conditions and historic logging of temperature and humidity conditions.
- Coded security access for set point parameter adjustment - Programmable stage delays, to minimise inrush currents - A comprehensive alarm system. Alarms shall be memorised and displayed in the
order in which they occur in order to aid fault diagnosis - Programmed set points and parameters shall be held in a non volatile memory,
therefore being safeguarded upon power failure - Denco Net functions are a standard feature within the controller. - Various third party communication and interface options are available which
connect direct to the C3-05 controller.
GEA Close Control Typical Airflow Arrangements T-Range General Details
PR-2006-0295-GB Subject to modifications Status 10/2007 11
Section "A" Downflow, into raised floor. Return from room or ceiling. Section "B" Upflow, with horizontal discharge plenum (as shown) or room/ceiling discharge, and front grille return (not available on models 48 – 83). Section "C" Upflow, with ceiling duct extension and underfloor return.
General Details
U / D - All Versions 3 - 5 8 - 12 17 - 28 32 - 42 48 - 53 63 - 83
Coil Face Area m2 0.200 0.414 0.864 1.382 1.728 2.764
No. of Fans Air Volume Fan Heat Absorbed
- m3/s m3/hr kW
1 0.415 1490 0.27
1 1.00 3600 1.17
2 2.17 7810 2.86
3 3.3
11880 4.37
4 4
14400 5.37
6 6.1
21960 8.24
Electric Reheat: No. of Steps Capacity
- kW
1
3.0
1
6.0
2
12.0
2
12.0
2
12.0
2
12.0
Humidifier Capacity Power
kg/hr kW
3.0 2.3
3.0 2.3
3.0 2.3
3.0 2.3
3.0 2.3
3.0 2.3
Filters (Standard G4): No. of Pieces Length Width Depth
- mm mm mm
1
455 455 50
2
442 505 50
2
885 505 50
3
885 540 50
4
885 505 50
6
885 540 50
General Details GEA Close Control T-Range
12 PR-2006-0295-GB Subject to modifications Status 10/2007
3 4 5 8 10 12 17 19 "X" Versions
Suction Line Liquid Line Humidifier Feed Drain
ins ins mm mm
3/4 3/8 15 22
3/4 3/8 15 22
3/4 3/8 15 22
7/8 1/2 15 22
7/8 1/2 15 22
1-1/8 1/2 15 22
1-1/8 5/8 15 22
1-1/8 5/8 15 22
C.U. Type No. fitted
- -
CT18 1
CT18 1
CT22 1
CS40 1
CM48 1
CM61 1
CP72 1
CP81 1
"A" Versions
Discharge Line Liquid Line Humidifier Feed Drain
ins ins mm mm
N/A N/A 1/2 3/8 15 22
3/4 1/2 15 22
3/4 1/2 15 22
3/4 1/2 15 22
7/8 5/8 15 22
7/8 5/8 15 22
Compressor No. fitted A/C Condenser * No. fitted
ZR - DCRA -
N/A N/A 22 1
08-6 1
34 1
13-6 1
48 1
21-6 1
61 1
21-6 1
61 1
26-6 1
72 1
26-6 1
"W" Versions
Cond Water In Cond Water Out Humidifier Feed Drain
mm mm mm mm
N/A N/A 22 22 15 22
28 28 15 22
28 28 15 22
28 28 15 22
35 35 15 22
35 35 15 22
Compressor Compr. Type No. fitted W/C Condenser No. fitted
ZR - - -
N/A N/A 22 Scroll
1 B8/20
1
34 Scroll
1 B8/30
1
48 Scroll
1 B8/30
1
61 Scroll
1 B8/30
1
61 Scroll
1 B10/30
1
72 Scroll
1 B10/30
1
“F" Versions
Coolant In Coolant Out Humidifier Feed Drain
mm mm mm mm
N/A N/A N/A 28 28 15 22
28 28 15 22
28 28 15 22
35 35 15 22
35 35 15 22
Compressor No. fitted W/C Condenser No. fitted
ZR - -
N/A N/A N/A 34 1
B8/30 1
48 1
B8/30 1
61 1
B8/30 1
61 1
B10/30 1
72 1
B10/301
"C" Versions
Chilled Water In Chilled Water Out Humidifier Feed Drain
mm mm mm mm
N/A N/A 22 22 15 22
N/A N/A 28 28 15 22
N/A N/A
Valve Size Valve kv
ins m3/hr
N/A N/A 1/2" 2.5
N/A N/A 3/4" 6.3
N/A N/A
Note: Variable Refrigerant Flow option NOT available on models 3 - 19. * - Quiet / Residential Condensers are available as an alternative to the Standard versions stated.
GEA Close Control General Details T-Range
PR-2006-0295-GB Subject to modifications Status 10/2007 13
21 23 28 32 37 42 "X" Versions
Suction Line Liquid Line Humidifier Feed Drain
ins ins mm mm
1-1/8 5/8 15 22
1-1/8 5/8 15 22
1-3/8 5/8 15 22
1-3/8 3/4 15 22
1-3/8 3/4 15 22
1-3/8 3/4 15 22
C.U. Type No. fitted
- -
CL90 1
CL11 1
CL12 1
CL12 1
CL16 1
CL19 1
"A" Versions
Discharge Line Liquid Line Humidifier Feed Drain
ins ins mm mm
7/8 5/8 15 22
7/8 5/8 15 22
1-1/8 5/8 15 22
1-1/8 3/4 15 22
1-1/8 3/4 15 22
1-1/8 3/4 15 22
Compressor No. fitted A/C Condenser * No. fitted
ZR - DCRA -
81 1
32-6 1
48 2 **
32-6 1
61 2 **
32-6 1
61 2 **
50-6 1
72 2 **
50-6 1
81 2 **
50-6 1
"W" Versions
Cond Water In Cond Water Out Humidifier Feed Drain
mm mm mm mm
35 35 15 22
35 35 15 22
35 35 15 22
42 42 15 22
42 42 15 22
42 42 15 22
Compressor No. fitted W/C Condenser No. fitted
ZR - -
81 1
B10/30 1
48 2 **
B10/30 1
61 2 **
B10/30 1
61 2 **
B10/40 1
72 2 **
B10/40 1
81 2 **
B10/40 1
"F" Versions
Coolant In Coolant Out Humidifier Feed Drain
mm mm mm mm
35 35 15 22
35 35 15 22
35 35 15 22
42 42 15 22
42 42 15 22
42 42 15 22
Compressor No. fitted W/C Condenser No. fitted
ZR - -
81 1
B10/30 1
48 2 **
B10/30 1
61 2 **
B10/30 1
61 2 **
B10/40 1
72 2 **
B10/40 1
81 2 **
B10/40 1
"C" Versions
Chilled Water In Chilled Water Out Humidifier Feed Drain
mm mm mm mm
N/A N/A 35 35 15 22
N/A N/A 42 42 15 22
Valve Size Valve kv
ins m3/hr
N/A N/A 1" 10
N/A N/A 1¼" 16
Note: Variable Refrigerant Flow option NOT available on model 21. * Quiet / Residential Condensers are available as an alternative to the Standard versions stated. ** - Variable Refrigerant Flow as Standard
General Details GEA Close Control T-Range
14 PR-2006-0295-GB Subject to modifications Status 10/2007
48 53 63 73 83 "X" Versions
Suction Line Liquid Line Humidifier Feed Drain
ins ins mm mm
1-1/8 5/8 15 22
1-1/8 5/8 15 22
1-3/8 3/4 15 22
1-3/8 3/4 15 22
1-3/8 3/4 15 22
C.U. Type No. fitted
- -
CL11 2
CL12 2
CL12 2
CL16 2
CL19 2
"A" Versions
Discharge Line Liquid Line Humidifier Feed Drain
ins ins mm mm
1-1/8 5/8 15 22
1-1/8 5/8 15 22
1-1/8 3/4 15 22
1-1/8 3/4 15 22
1-1/8 3/4 15 22
Compressor No. fitted A/C Condenser * No. fitted
ZR - DCRA -
48 4 **
32-6 2
61 4 **
32-6 2
61 4 **
32-6 2
72 4 **
50-6 2
81 4 **
50-6 2
"W" Versions
Cond Water In Cond Water Out Humidifier Feed Drain
mm mm mm mm
2 x 35 2 x 35
15 22
2 x 35 2 x 35
15 22
2 x 42 2 x 42
15 22
2 x 42 2 x 42
15 22
2 x 42 2 x 42
15 22
Compressor No. fitted W/C Condenser No. fitted
ZR - -
48 4 **
B10/30 2
61 4 **
B10/30 2
61 4 **
B10/40 2
72 4 **
B10/40 2
81 4 **
B10/40 2
"C" Versions
Chilled Water In Chilled Water Out Humidifier Feed Drain
mm mm mm mm
N/A 54 54 15 22
N/A N/A 54 54 15 22
Valve Size Valve kv
ins m3/hr
N/A 1½" 25
N/A N/A 2" 40
Note: * Quiet / Residential Condensers are available as an alternative to the Standard versions stated. ** Variable Refrigerant Flow as Standard
GEA Close Control Cooling Performance – Models 3 to 19 T-Range
PR-2006-0295-GB Subject to modifications Status 10/2007 15
All the cooling performances below are based on Standard EU4 filtration and with a minimum of 50 Pa external static and Air On at 24 °C, 45 %RH.
3 4 5 8 10 12 17 19
Airflow m3/s m3/hr
0.30 1080
0.35 1260
0.415 1490
0.70 2520
0.80 2880
1.00 3600
1.40 5040
1.60 5760
"X" Version 1
Total Sensible S.H.R.
kW kW -
4.6 4.1 0.89
4.8 4.4 0.93
5.6 5.1 0.92
9.5 8.7 0.92
11.6 10.0 0.88
13.4 11.6 0.87
17.6 16.7 0.95
19.4 18.4 0.95
"A" Version 2
Total Sensible S.H.R.
kW kW -
N/A N/A 5.6 5.1 0.91
8.7 8.3 0.95
12.1 10.2 0.86
14.1 11.9 0.85
16.1 15.6 0.86
18.3 17.6 0.96
"W" Version 3
Total Sensible S.H.R.
kW kW -
N/A N/A 5.7 5.2 0.90
8.7 8.3 0.95
11.7 10.1 0.86
13.9 11.7 0.85
15.7 15.2 0.97
18.0 17.3 0.96
"F" Version 4
Total Sensible S.H.R.
kW kW -
N/A N/A N/A 7.9 7.6 0.97
10.7 9.7 0.90
12.6 11.1 0.88
14.1 14.0 0.99
16.3 16.0 0.98
"C" Version 5
Total Sensible S.H.R. CW Flow Rate Unit P.D
kW kW - l/s kPa
N/A N/A 5.8 5.4 0.92
0.279 49.7
N/A N/A 13.9 12.5 0.90
0.664 57.8
N/A N/A
Refrigerant R407C used as standard on DX units. Notes: 1. "X" performances are NETT and based on: (a) Standard matching Condensing Units (alternatives available, enquire for details). (b) 1.0 °C suction line loss. (c) 32 °C ambient temperature. 2. "A" performances are NETT and based on: (a) Standard matching A/C Condensers (alternatives available, enquire for details). (b) 0.5 °C suction line loss. (c) 32 °C ambient temperature. 3. "W" performances are NETT and based on: (a) Standard matching W/C Condensers (alternatives available, enquire for details). (b) 0.5 °C suction line loss. (c) Condenser water in 30 °C, temperature rise 8 °C. 4. "F" performances are NETT and based on: (a) Standard matching W/C Condensers (alternatives available, enquire for details). (b) 0.5 °C suction line loss. (c) 25 % ethylene glycol solution coolant in 40 °C, temperature rise 6 °C. 5. "C" performances are GROSS and based on: (a) Standard coil with chilled water in 7°C, temperature rise 5 °C
Cooling Performance – Models 21 to 42 GEA Close Control T-Range
16 PR-2006-0295-GB Subject to modifications Status 10/2007
All the cooling performances below are based on Standard EU4 filtration and with a minimum of 50 Pa external static and Air On at 24 °C, 45 %RH.
21 23 28 32 37 42
Airflow m3/s m3/hr
1.80 6480
2.00 7200
2.17 7810
2.50 9000
2.90 10440
3.30 11880
"X" Version 1
Total Sensible S.H.R.
kW kW -
23.0 21.0 0.92
26.4 23.2 0.89
29.2 25.0 0.87
31.2 29.5 0.95
36.1 33.4 0.93
41.3 37.0 0.91
"A" Version 2
Total Sensible S.H.R.
kW kW -
20.7 19.7 0.95
23.8 22.1 0.93
27.2 24.1 0.89
31.5 29.7 0.94
35.7 33.2 0.93
39.2 36.2 0.92
"W" Version 3
Total Sensible S.H.R.
kW kW -
20.1 19.3 0.96
23.6 22.0 0.93
27.6 24.3 0.88
30.0 28.6 0.95
34.4 32.5 0.95
38.2 35.7 0.94
"F" Version 4
Total Sensible S.H.R.
kW kW -
18.1 17.7 0.98
21.2 20.4 0.96
24.9 23.0 0.92
27.0 26.3 0.97
31.2 30.1 0.96
34.4 32.9 0.96
"C" Version 5
Total Sensible S.H.R. CW Flow Rate Unit P.D
kW kW - l/s kPa
N/A N/A 28.7 26.4 0.92
1.372 65.6
N/A N/A 45.4 41.3 0.91 2.171 79.8
Refrigerant R407C used as standard on DX units. Notes: 1. "X" performances are NETT and based on: (a) Standard matching Condensing Units (alternatives available, enquire for details). (b) 1.0 °C suction line loss. (c) 32 °C ambient temperature. 2. "A" performances are NETT and based on: (a) Standard matching A/C Condensers (alternatives available, enquire for details). (b) 0.5 °C suction line loss. (c) 32 °C ambient temperature. 3. "W" performances are NETT and based on: (a) Standard matching W/C Condensers (alternatives available, enquire for details). (b) 0.5 °C suction line loss. (c) Condenser water in 30 °C, temperature rise 8 °C. 4. "F" performances are NETT and based on: (a) Standard matching W/C Condensers (alternatives available, enquire for details). (b) 0.5 °C suction line loss. (c) 25 % ethylene glycol solution coolant in 40 °C, temperature rise 6 °C. 5. "C" performances are GROSS and based on: (a) Standard coil with chilled water in 7 °C, temperature rise 5 °C. .
GEA Close Control Cooling Performance – Models 48 to 83 T-Range
PR-2006-0295-GB Subject to modifications Status 10/2007 17
All the cooling performances below are based on Standard EU4 filtration and with a minimum of 50 Pa external static and Air On at 24 °C, 45 %RH.
48 53 63 73 83
Airflow m3/s m3/hr
4.0 14400
4.34 15620
5.00 18000
5.80 20880
6.60 23760
"X" Version 1
Total Sensible S.H.R.
kW kW -
52.8 46.4 0.89
58.5 49.9 0.87
62.5 59.0 0.95
72.3 66.7 0.93
78.7 74.1 0.91
"A" Version 2
Total Sensible S.H.R.
kW kW -
47.7 44.3 0.94
54.6 48.3 0.90
63.3 59.4 0.95
71.5 66.4 0.94
78.7 72.4 0.93
"W" Version 3
Total Sensible S.H.R.
kW kW -
47.1 44.0 0.94
55.3 48.6 0.89
60.2 57.3 0.96
68.9 65.1 0.95
76.7 71.6 0.94
"C" Version 4
Total Sensible S.H.R. CW Flow Rate Unit P.D
kW kW - l/s kPa
N/A 57.3 52.8 0.92 2.743 56.8
N/A N/A 90.7 82.5 0.91 4.343 71.2
Refrigerant R407C used as standard on DX units. Notes: 1. "X" performances are NETT and based on: (a) Standard matching Condensing Units (alternatives available, enquire for details). (b) 1.0 °C suction line loss. (c) 32 °C ambient temperature. 2. "A" performances are NETT and based on: (a) Standard matching A/C Condensers (alternatives available, enquire for details). (b) 0.5°C suction line loss. (c) 32°C ambient temperature. 3. "W" performances are NETT and based on: (a) Standard matching W/C Condensers (alternatives available, enquire for details). (b) 0.5 °C suction line loss. (c) Condenser water in 30 °C, temperature rise 8 °C. 4. "C" performances are GROSS and based on: (a) Standard coil with chilled water in 7 °C, temperature rise 5 °C.
Electrical Details at 400 Volt / 3 Ph + N / 50 Hz GEA Close Control "X" Version T-Range
18 PR-2006-0295-GB Subject to modifications Status 10/2007
Models 3 4 5 8 10 12 17 19 21 23
Controls FLA 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Main Fan(s) OA CLA
0.7 0.9
0.7 0.9
0.7 0.9
4.0 5.0
4.0 5.0
4.0 5.0
4.0 5.0
4.0 5.0
4.0 5.0
4.0 5.0
Heaters FLA 13.0 13.0 13.0 8.7 8.7 8.7 17.4 17.4 17.4 17.4
Humidifier OA CLA
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
Condensing Unit OA CLA
6.7 8.2
6.7 8.2
3.8 4.2
6.4 7.3
7.4 8.4
9.2 10.5
10.1 12.0
11.9 14.1
14.9 16.8
17.019.4
Operating Amps FLA 16.3 16.3 16.3 19.1 20.1 21.9 31.5 33.3 36.3 38.4
Connected Load CLA 18.6 18.6 18.6 21.0 22.1 24.2 34.4 36.5 39.2 41.8
Maximum Inrush LRA 42.2 42.2 37.0 59.7 63.7 79.7 96.4 123 121 145
Operating kW kW 5.5 5.5 5.5 9.3 9.9 10.7 18.3 19.0 19.9 21.4
Connected Load kW kW 7.0 7.0 7.0 10.2 10.9 11.9 19.9 20.8 21.8 23.6
Models 28 32 37 42 48 53 63 73 83
Controls FLA 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Main Fan(s) OA CLA
4.0 5.0
4.0 5.0
4.0 5.0
4.0 5.0
8.0 10.0
8.0 10.0
8.0 10.0
8.0 10.0
8.0 10.0
Heaters FLA 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4
Humidifier OA CLA
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
Condensing Unit OA CLA
19.1 21.8
19.1 21.8
21.9 25.8
25.5 29.9
34.0 38.8
38.2 43.6
38.2 43.6
43.8 51.6
51.0 59.8
Operating Amps FLA 40.5 41.5 44.3 47.9 46.4 50.6 51.6 57.2 64.4
Connected Load CLA 44.2 45.2 49.2 53.3 55.0 59.8 60.8 68.8 77.0
Maximum Inrush LRA 149 149 189 220 159 165 166 210 245
Operating kW kW 22.5 23.1 25.2 27.8 22.6 23.7 24.9 28.5 33.7
Connected Load kW kW 25.0 25.8 28.4 31.5 26.2 29.0 30.5 35.7 41.9
Notes: Controls are 24 volt. “Operating Amps” (OA): worst case phase for components that can be selected to operate at any one time by the automatic control system, each component operating at “design conditions”, i.e. Compressors (based on saturated suction 5 °C, condensing 50 °C), Humidifier (100 %), Main Fans (80 % of rated kW) and Condenser Fans (100 % of rated kW). “Connected Load Amps” (CLA): worst case phase for components that can be selected to operate at any one time by the automatic control system at maximum load conditions for each component, i.e. Compressors (based on saturated suction 10 °C, condensing 60 °C), Humidifier (170 % Alarm Condition), Main Fans (100 % of rated kW), Condenser Fans (100 % of rated kW).
GEA Close Control Electrical Details at 400 Volt / 3 Ph + N / 50 Hz T-Range "A" Version
PR-2006-0295-GB Subject to modifications Status 10/2007 19
Models 5 8 10 12 17 19 21 23
Controls FLA 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Main Fan(s) OA CLA
0.7 0.9
4.0 5.0
4.0 5.0
4.0 5.0
4.0 5.0
4.0 5.0
4.0 5.0
4.0 5.0
Heaters FLA 13.0 8.7 8.7 8.7 17.4 17.4 17.4 17.4
Humidifier OA CLA
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
Compressors OA CLA
3.0 3.5
4.5 5.4
6.2 7.2
8.0 9.3
8.0 9.3
8.7 10.6
10.5 12.7
12.4 14.4
Condenser Fans FLA 0.9 1.7 3.3 3.3 3.3 3.3 3.3 3.3
Operating Amps FLA 17.3 17.2 18.9 20.7 30.4 31.1 32.9 34.8
Connected Load CLA 19.6 19.3 20.9 23.0 32.7 34.0 36.1 37.8
Maximum Inrush LRA 38.0 53.7 63.7 79.7 89.4 97.4 125 80.6
Operating kW kW 5.5 9.2 10.6 11.4 18.2 18.9 19.6 20.8
Connected Load kW kW 7.0 10.1 11.7 12.7 19.6 20.5 21.4 22.9
Models 28 32 37 42 48 53 63 73 83
Controls FLA 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Main Fan(s) OA CLA
4.0 5.0
4.0 5.0
4.0 5.0
4.0 5.0
8.0 10.0
8.0 10.0
8.0 10.0
8.0 10.0
8.0 10.0
Heaters FLA 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4
Humidifier OA CLA
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
Compressors OA CLA
16.0 18.6
16.0 18.6
17.4 21.2
21.0 25.4
24.8 28.8
32.0 37.2
32.0 37.2
34.8 42.4
42.0 50.8
Condenser Fans FLA 3.3 6.6 6.6 6.6 3.3 3.3 6.6 6.6 6.6
Operating Amps FLA 38.4 44.0 45.4 49.0 41.1 47.7 51.0 52.7 59.9
Connected Load CLA 42.0 47.6 50.2 54.4 47.7 56.1 59.4 64.6 73.0
Maximum Inrush LRA 98.7 105 114 143 90.5 112.4 116.4 129.4 162.4
Operating kW kW 22.4 23.8 25.2 26.6 22.0 31.1 24.3 28.7 31.5
Connected Load kW kW 24.9 26.5 28.3 30.1 25.6 29.6 32.7 36.3 39.9
Notes: Controls are 24 volt. “Operating Amps” (OA): worst case phase for components that can be selected to operate at any one time by the automatic control system, each component operating at “design conditions”, i.e. Compressors (based on saturated suction 5 °C, condensing 50 °C), Humidifier (100 %), Main Fans (80 % of rated kW) and Condenser Fans (100 % of rated kW). “Connected Load Amps” (CLA): worst case phase for components that can be selected to operate at any one time by the automatic control system at maximum load conditions for each component, i.e. Compressors (based on saturated suction 10 °C, condensing 60 °C), Humidifier (170 % Alarm Condition), Main Fans (100 % of rated kW), Condenser Fans (100 % of rated kW).
Electrical Details at 400 Volt / 3 Ph + N / 50 Hz GEA Close Control "W" and "F" Versions T-Range
20 PR-2006-0295-GB Subject to modifications Status 10/2007
Models 5*** 8 10 12 17 19 21 23
Controls FLA 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Main Fan(s) OA CLA
0.7 0.9
4.0 5.0
4.0 5.0
4.0 5.0
4.0 5.0
4.0 5.0
4.0 5.0
4.0 5.0
Heaters FLA 13.0 8.7 8.7 8.7 17.4 17.4 17.4 17.4
Humidifier OA CLA
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
Compressors OA CLA
3.0 3.5
4.5 5.4
6.2 7.2
8.0 9.3
8.0 9.3
8.7 10.6
10.5 12.7
12.4 14.4
Operating Amps OA 16.3 17.2 18.9 20.7 29.4 30.1 31.9 33.8
Connected Load CLA 18.6 19.3 20.9 23.0 31.7 33.0 35.1 36.8
Maximum Inrush LRA 37.0 53.7 63.7 79.7 88.4 96.4 124 79.6
Operating kW kW 5.5 8.8 9.8 10.6 17.4 18.1 18.8 19.6
Connected Load kW kW 7.0 9.7 10.9 11.9 18.8 19.7 20.6 22.1
Models 28 32 37 42 48*** 53*** 63*** 73*** 83***
Controls FLA 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Main Fan(s) OA CLA
4.0 5.0
4.0 5.0
4.0 5.0
4.0 5.0
8.0 10.0
8.0 10.0
8.0 10.0
8.0 10.0
8.0 10.0
Heaters FLA 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4
Humidifier OA CLA
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
Compressors OA CLA
16.0 18.6
16.0 18.6
17.4 21.2
21.0 25.4
24.8 28.8
32.0 37.2
32.0 37.2
34.8 42.4
42.0 50.8
Operating Amps OA 37.4 38.4 39.8 43.4 37.8 43.3 44.3 47.1 53.3
Connected Load CLA 41.0 42.0 44.6 48.8 44.4 52.8 53.8 58.0 66.4
Maximum Inrush LRA 97.7 98.7 108 137 87.8 110 111 123 156
Operating kW kW 21.6 22.2 23.6 25.0 21.2 22.8 24.0 25.4 28.3
Connected Load kW kW 24.1 24.9 26.7 28.5 23.6 28.0 29.5 33.1 36.7
Notes: *** “F” System not available for model 5 and models 48 to 83. Controls are 24 volt. “Operating Amps” (OA): worst case phase for components that can be selected to operate at any one time by the automatic control system, each component operating at “design conditions”, i.e. Compressors (based on saturated suction 5 °C, condensing 50 °C), Humidifier (100 %), Main Fans (80 % of rated kW) and Condenser Fans (100 % of rated kW). “Connected Load Amps” (CLA): worst case phase for components that can be selected to operate at any one time by the automatic control system at maximum load conditions for each component, i.e. Compressors (based on saturated suction 10 °C, condensing 60 °C), Humidifier (170 % Alarm Condition), Main Fans (100 % of rated kW), Condenser Fans (100 % of rated kW). .
GEA Close Control Electrical Details at 400 Volt / 3 Ph + N / 50 Hz T-Range "C" Version
PR-2006-0295-GB Subject to modifications Status 10/2007 21
Models 5 12 28 42 53 83
Controls FLA 1.0 1.0 1.0 1.0 1.0 1.0
Main Fan(s) OA CLA
0.7 0.9
4.0 5.0
4.0 5.0
4.0 5.0
8.0 10.0
8.0 10.0
Heaters FLA 13.0 8.7 17.4 17.4 17.4 17.4
Humidifier OA CLA
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
3.3 5.6
Operating Amps OA 16.3 16.0 24.7 25.7 28.7 29.7
Connected Load CLA 18.6 19.3 28.0 29.0 33.0 34.0
Maximum Inrush LRA 18.6 19.3 28.0 29.0 34.8 35.8
Operating kW kW 5.5 8.7 15.5 16.1 16.7 17.9
Connected Load kW kW 7.0 10.4 17.3 18.1 18.8 20.3
Notes: Controls are 24 volt. “Operating Amps” (OA): worst case phase for components that can be selected to operate at any one time by the automatic control system, each component operating at “design conditions”, i.e. Compressors (based on saturated suction 5 °C, condensing 50 °C), Humidifier (100 %), Main Fans (80 % of rated kW) and Condenser Fans (100 % of rated kW). “Connected Load Amps” (CLA): worst case phase for components that can be selected to operate at any one time by the automatic control system at maximum load conditions for each component, i.e. Compressors (based on saturated suction 10 °C, condensing 60 °C), Humidifier (170 % Alarm Condition), Main Fans (100 % of rated kW), Condenser Fans (100 % of rated kW).
Schematic Diagram: "X" Version GEA Close Control T-Range
22 PR-2006-0295-GB Subject to modifications Status 10/2007
GEA Close Control RI-Schema: "A"-Version T-Range
PR-2006-0295-GB Subject to modifications Status 10/2007 23
Schematic Diagram: "W" Version GEA Close Control T-Range
24 PR-2006-0295-GB Subject to modifications Status 10/2007
GEA Close Control Schematic Diagram: "F" Version T-Range
PR-2006-0295-GB Subject to modifications Status 10/2007 25
Schematic Diagram: "C" Version GEA Close Control T-Range
26 PR-2006-0295-GB Subject to modifications Status 10/2007
GEA Close Control Ancillaries and Options T-Range
PR-2006-0295-GB Subject to modifications Status 10/2007 27
Plinth For upflow units, a standard plinth is available that raises the Air Handling Unit 200mm (or 400mm) from the floor level to facilitate services entry. It is a plain sheetmetal box supplied complete with gasket and fixing bolts, and finished to match the Air Handling Unit.
Base Stand When the Air Handling Unit is to be installed before the installation of a raised floor, a matching Base Stand should be used to support it. This consists of a rigid frame of 6mm thick MS angle complete with adjustable feet. The upper face of the frame is lined with 3mm semi hard gasket. When ordering, specify the nominal height required, which normally will be the same as the overall height of the raised floor. The feet have an adjustment of ± 25mm.
Ceiling Return Duct The Ceiling Return Duct is a rigid riveted sheetmetal assembly comprising of unit matched panels lined with 25mm thick insulation. The duct, which is suitable for downflow units only, is bolted to the top of the Air Handling Unit on site. When ordering, specify the height between the top of the Air Handling Unit and the under side of the suspended ceiling. The overall height of the duct will be this dimension plus 50mm.
Horizontal Discharge Section The Horizontal Discharge Section consists of a double deflection grille fitted into a rigid sheetmetal box. The complete assembly is bolted to the top of the Air Handling Unit on site. The grille has two sets of blades, which allow for both vertical and horizontal directional adjustment of airflow. The standard height for this section is 500 mm.
Ceiling Discharge Section For upflow units, where the Air Handling Unit is required to discharge into the ceiling void, a Ceiling Discharge Extension is available. This consists of a rigid riveted sheetmetal assembly comprising of unit matched front; rear and end panels lined with 25 mm thick insulation. The extension is bolted to the top of the Air Handling Unit on site. When ordering specify the height between the top of the Air Handling Unit and the underside of the suspended ceiling. The overall height of the duct will be this dimension plus 50 mm.
High Efficiency Filters Higher specification filtration can be provided in place of the standard filters having an efficiency of 80% ASHRAE 52/76 (Eurovent F7). Pre filters are fitted, before the main high efficiency filters, and are rated as G2. These filters are fitted in the return airside of the Air Handling Unit within the main cabinet.
Filter Gauge A dial type manometer can be installed to read the pressure drop across the filter to give an accurate indication of filter condition.
Ancillaries and Options GEA Close Control T-Range
28 PR-2006-0295-GB Subject to modifications Status 10/2007
Fresh Air Kit and Filter Units can be supplied with a fresh air inlet connection and disposable fresh air filter element. This will admit approximately 35 % of the recirculated air volume. One or two may be fitted depending on requirements.
Special Colours Special Colours must be specified when ordering the Air Handling Unit (quote British Standard number, RAL number, or other, if known). If more than one colour is specified then state the colour of each panel.
Double Skin Panels To reduce the sound "break out", Double Skin Panels comprise: - 20 swg steel sheet glued to the inner face of all outer panels then covered with standard 25mm class “O” insulation.
Without Electric Heating All equipment associated with electric heating is removed from the Air Handling Unit.
LPHW Heating (not available on models 48 – 83) Units may be fitted with a Low Pressure Hot Water heating coil in place of the standard electrical heating. Water flow through the coil is controlled by a modulating 3 way valve. Duties of these coils are nominally the same as standard electric heating, based on flow and return hot water temperatures of 82 °C and 71 °C respectively.
Water Detection Water Sensors, connected directly to the water detection module of the Air Handling Unit microprocessor control system, are located in: - - Condensate drain pan detecting undue water level. - Underfloor water tape, supplied loose with 5 metres of cable.
When water is detected, the Air Handling Unit's alarm system is activated and disables humidifier function.
Sump Pump Where, due to location, it is not possible to gravity drain units, a sump pump can be fitted to collect any condensate and pump it to the nearest convenient drain point (maximum available pump head 5.7 metres). For units fitted with humidifiers, a larger capacity sump pump is available to accommodate the additional discharge of hot water during humidifier drain down cycles (maximum available pump head 7 metres). Please note that when using a sump pump a minimum of a 200 mm high plinth is required.
GEA Close Control Ancillaries and Options T-Range
PR-2006-0295-GB Subject to modifications Status 10/2007 29
VRF System To provide energy saving and thereby limit emission of greenhouse gases that contribute to global warming, models 23 and above are supplied with the variable refrigerant flow (VRF) compressor configuration. By applying these models to smaller loads, even greater energy savings will be realised, due to the very high part load efficiency.
Electronically Controlled Fans For applications where high airflow is not required and noise is a major consideration, then fans with variable speed motors can be fitted. The motors are 3 phase variable frequency but only a single phase feed is provided. The airflow provided by the fan(s) is determined by a 0 – 10 Vdc signal that is generated from the cooling demand via the controls. The lower the cooling demand the lower the airflow and vice versa. For this option, a reduced heating capacity will be necessary.
Condenser Fan Pressure Switch A Condenser Fan Pressure Switch can be fitted to the Unit to replace the standard fan speed controller on "A" versions.
Screwed Water Connections BSP screwed fittings supplied instead of the standard copper solder connections on “W” and “C” versions.
Hot Gas By Pass "A" versions can be fitted with hot gas by pass compressor capacity control. This consists of a hot gas control valve in the by pass line between the discharge line of the compressor and the evaporator coil suction header, with the sensing line fitted in the suction line.
Refrigerants Alternative refrigerants R134a and R410A are available as standard options on request.
Hand/Auto Switches A hard wired switch assembly, fitted in the electrical control panel can be used as manual override or as automatic control function, and is intended as an aid to commissioning engineers.
Run Status Run Status is achieved by volt free terminals, located in the electrical box, for remote monitoring of the unit run (fans) operation.
Ancillaries and Options GEA Close Control T-Range
30 PR-2006-0295-GB Subject to modifications Status 10/2007
Controller Remote Display The C3-05 Controller Display can be supplied remote from the Air Handling Unit, complete with interconnecting cable up to 1 kilometre.
Monitoring Display The Monitoring Display can be connected to a network of C3-05 Controllers to enable complete Air Handling Unit monitoring.
Electronic Expansion Valve (EEV) On DX units the EEV option can be fitted to replace the standard TEV. This consists of a valve, electronic driven module, pressure transducer and temperature sensor per refrigerant circuit.
Discharge Pressure Transducer On DX units a pressure transducer can be fitted to monitor the discharge pressure. It is recommended that the EEV option it fitted with the Discharge Pressure Transducer.
Remote Temperature and Humidity Sensor The temperature and humidity sensors Unit, fitted with the required length of cable (up to a maximum of 25 metres), can be supplied remote from the Air Handling.
Winter Start Kit (ELATE) Generally recommended for temperatures between –25 °C and –40 °C, and comprises horizontal type liquid receiver with trace heater and pressure relief valve situated in a special section below the air cooled Condensing Unit / Condenser. However a base section will be required and will increase the overall height of the horizontal blow Condensing Units / Condensers by 400 mm.
Trend Interface Card The Trend interface is a small pcb which can be plugged into the C3-05 controller to provide it with Trend network capability.
The interface needs to be configured in order that the required controller variables are linked to appropriate Trend parameters; these then become accessible via the Trend network using standard Trend (text) communications. The interface provides CNC functionality.
- Flexible number of configuration modules - Peer to peer communications (IC Comms) - Suitable for field installation - Display and directory modules
GEA Close Control Ancillaries and Options T-Range
PR-2006-0295-GB Subject to modifications Status 10/2007 31
RS232 Serial Card The RS232 Serial Card is used to interface the C3-05 controller directly to a standard HAYES modem. The following hardware signals can be managed: - Output, “request to send” (RTS) in parallel to “data terminal ready” (DTR). - Input, “carrier detected” (CD).
The maximum baud rate is 19200.
RS485 Serial Card The RS485 Serial Card is used to interface the C3-05 controller to an RS485 network.
The card guarantees the optical isolation of the controller from the RS485 serial network. The maximum baud rate is 19200 (adjustable in software).
Lonworks Serial Card
The LonWorks Serial Card is used to interface the C3-05 controller to a Lonworks network.
The type of interface on the LonWorks network side is: - PCO20000F0 – interface to FTT-10A 78 Kbs (TP/FT-10).
The baud rate of the C3-05 controller must be set to 4800.
PCOWEB Interface The pCOWeb Interface allows connection to TCP/IP and SNMP protocols on the Ethernet standard and BACnet both on the Ethernet and EIA485 standards.
Due to our policy of continuous development and improvement, the specifications and data herein are subject to change without notice. We must therefore reserve the right to supply equipment that may differ from that described and illustrated herein. All information, including illustrations, contained in this brochure, is believed to be accurate and reliable. Users, however, should independently evaluate the suitability of each product for their own application. GEA makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use.
GB Denco Ltd.UK-HR4 8DS HerefordTel. +44 / 1432 / 277 277
N GEA Klimaprodukter ASN-0484 OsloTel. +47 / 220 / 27990
UA GEA Ukraina t.o.v.UA-01135 KyivTel. +38 / 044 / 4619356
TR ISISANTR-80700 BalmumcuIstanbulTel. +90 / 212 / 2757171
SLO GEA KlimatizacijskaTehnika d.o.o.SI-1000 LjubljanaTel. +386 / 1 / 2573850
SK GEA Klimatizácia s.r.o.SK-83104 BratislavaTel. +421 / 7 / 44457917
GEA KlimatehnikaRS-11070 Novi BeogradTel. +381 / 11 / 3193955
SRB
S GEA EXOSVentilation ABS-74528 EnköpingTel. +46 / 171 / 85530
RUS GEA KondicionerMoskvaRU-105094 MoskvaTel. +7 / 495 / 9566674
P Nónio, Lda.P-1269-090 LisboaTel. +351 / 21 / 3826160
LV GEA Klimatechnik UABLT-01141 VilniusTel. +370 / 5 / 2106060
LT GEA Klimatechnik UABLT-01141 VilniusTel. +370 / 5 / 2106060
L GEA Happel LuxembourgL-4940 BascharageTel. +352 / 26 / 502970
IS Rafn JenssonIS-110 ReykjavikTel. +354 / 56 / 780-30
PL GEAKlimatyzacja Sp. z o.o.PL-54610 WroclawTel. +48 / 71 / 3737952
HR GEA Klima-rashladnatehnika d.o.o.HR-10000 ZagrebTel. +385 / 1 / 6064900
FIN OY TEKNOCALOR ABFIN-01300 VantaaTel. + 358 / 9 / 82546020
F GEA Happel France sarlF-59436 Roncq CedexTel. +33 / 3 / 20689020
EST GEA Klimatechnik UABLT-01141 VilniusTel. +370 / 5 / 2106060
E GEA Air TreatmentMarketing ServicesInt. GmbH - oficina EspañaE-28036 MadridTel. +34 / 91 / 3837701
DK GEA Klimateknik ApSDK-2610 RødovreTel. +45 / 38 / 887070
H GEA Klimatechnika KftH-1037 BudapestTel. +36 / 1 / 4393200
D GEA HappelKlimatechnik GmbHD-44625 HerneTel. +49 / 2325 / 468-00
CZCZ-46312 LiberecTel. +420 / 48 / 5225-111GEA Klimatizace spol. s r.o.CZ-46312 LiberecTel. +420 / 48 / 5225-303
GEA LVZ, a.s.
CH GEA KlimatecSchweiz AGCH-3065 Bolligen-StationTel. +41 / 31 / 9171919
BY GEA Klimatechnik UABLT-01141 VilniusTel. +370 / 5 / 2106060
BIH GEA KlimatehnikaRS-11070 Novi BeogradTel. +381 / 11 / 3193955
BG EVISS Ltd.BG-7000 RousseTel. +359 / 82 / 81000
B GEA Happel Belgium N.V.B-1130 BrusselsTel. +32 / 2 / 2406161
A GEAKlimatechnik GmbHA-4673 GaspoltshofenTel. +43 / 7735 / 8000-0
NL GEA HappelNederland B.V.NL-2909 LLCapelle a/d IjsselTel. +31 / 10 / 2350606
RO GEA Klimatechnik s.r.l.RO-300222 TimisoaraTel. +40 / 356 / 423703
GEA KlimatehnikaRS-11070 Novi BeogradTel. +381 / 11 / 3193955
MWE
Our Market in Europe
Air Treatment Division For detailed information on all corporate areas,go to www.gea-airtreatment.com or contactus by email [email protected] company of GEA Group
PR-2
006-
0295
-GB
• S
ub
ject
to
mo
dif
icat
ion
s •
Stat
us
10/2
007
• C
op
yrig
ht
GEA
Air
Tre
atm
ent