Data sheet 3VA2225-4HL42-0AA0 CIRCUIT BREAKER 3VA2 IEC FRAME 250 BREAKING CAPACITY CLASS S ICU=36KA @ 415 V 4POLE, LINE PROTECTION ETU320, LI, IN=250A OVERLOAD PROTECTION IR=100A ...250A SHORT CIRCUIT PROTECTION II=1,5...12 X IN NEUTRAL PROTECTION ADJUSTABLE(OFF,50%,100%) BUSBAR CONNECTION Model product brandname SENTRON Product designation Molded case circuit breaker Design of the product Line protection Type of load switch / according to UL 489 / Heating, Air Conditioning, and Refrigeration circuit breaker (HACR Type) Yes Design of the overcurrent release ETU320 Protective function of the overcurrent release LI Number of poles 4 General technical data Tension assignée d'isolement Ui 800 V Max. rated operational voltage Ue with AC 50/60Hz 690 V Active power loss / for rated value of the current / at AC / in hot operating state / per pole 0W Mechanical service life (switching cycles) / typical 20 000 Electrical endurance (switching cycles) / at AC-1 / at 380/415 V 50/60 Hz 10 000 Neutral conductors / upgradeable/retrofittable No 3VA2225-4HL42-0AA0 Subject to change without notice Page 1/ 5 11/28/2016 © Copyright Siemens AG

Upload: others

Post on 15-Sep-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Data sheet 3VA2225-4HL42-0AA0...(HACR Type) Yes Design of the overcurrent release ETU320 Protective function of the overcurrent release LI Number of poles 4 General technical data

Data sheet 3VA2225-4HL42-0AA0CIRCUIT BREAKER 3VA2 IEC FRAME 250 BREAKING CAPACITYCLASS S ICU=36KA @ 415 V 4POLE, LINE PROTECTIONETU320, LI, IN=250A OVERLOAD PROTECTION IR=100A ...250ASHORT CIRCUIT PROTECTION II=1,5...12 X IN NEUTRALPROTECTION ADJUSTABLE(OFF,50%,100%) BUSBARCONNECTION

Modelproduct brandname SENTRONProduct designation Molded case circuit breakerDesign of the product Line protectionType of load switch / according to UL 489 / Heating,Air Conditioning, and Refrigeration circuit breaker(HACR Type)

Yes

Design of the overcurrent release ETU320Protective function of the overcurrent release LINumber of poles 4

General technical dataTension assignée d'isolement Ui 800 VMax. rated operational voltage Ue with AC 50/60Hz 690 VActive power loss / for rated value of the current / atAC / in hot operating state / per pole

0 W

Mechanical service life (switching cycles) / typical 20 000Electrical endurance (switching cycles) / at AC-1 / at380/415 V 50/60 Hz

10 000

Neutral conductors / upgradeable/retrofittable No

3VA2225-4HL42-0AA0 Subject to change without noticePage 1/5 11/28/2016 © Copyright Siemens AG

Page 2: Data sheet 3VA2225-4HL42-0AA0...(HACR Type) Yes Design of the overcurrent release ETU320 Protective function of the overcurrent release LI Number of poles 4 General technical data

Ground fault monitoring version WithoutProduct function

● communication function No

● other measurement function No

Net weight 2.7 kg

ElectricityMarking / according to UL 489 / 100%-rated breaker NoMax. rated operational voltage of the size of thecircuit-breaker

250 A

Courant permanent assigné Iu 250 AOperating current

● at 40 °C 250 A

● at 45 °C 250 A

● at 50 °C 250 A

● at 55 °C 241 A

● at 60 °C 232 A

● at 65 °C 222 A

● at 70 °C 213 A

Switching capacity according to IEC 60947Switching capacity class of the circuit breaker SMaximum short-circuit current breaking capacity (Icu)

● at 240 V 55 kA

● at 415 V 36 kA

● at 440 V 36 kA

● at 500 V 25 kA

● at 690 V 3 kA

Operational short-circuit current breaking capacity(Ics)

● at 240 V 55 kA

● at 415 V 36 kA

● at 440 V 36 kA

● at 500 V 25 kA

● at 690 V 3 kA

Short-circuit current making capacity (Icm)

● at 240 V 121 kA

● at 415 V 76 kA

● at 440 V 76 kA

● at 500 V 53 kA

● at 690 V 4.5 kA

Adjustable parametersAdjustable response value current / lg min. 100 A

3VA2225-4HL42-0AA0 Subject to change without noticePage 2/5 11/28/2016 © Copyright Siemens AG

Page 3: Data sheet 3VA2225-4HL42-0AA0...(HACR Type) Yes Design of the overcurrent release ETU320 Protective function of the overcurrent release LI Number of poles 4 General technical data

Adjustable response value current / lg min. 250 AAdjustable response value current / lg min. 0.5Adjustable response value current / lg min. 15Short-term delayed / tripping switchable /I2t=ON/OFF

No

Adjustable response value current / li min. 375 AAdjustable response value current / li max. 2 500 ADesign of the N-conductor protection adjustable OFF; 50%; 100%Ground fault protection / tripping switchable /I2t=ON/OFF

No

Mechanical DesignHeight [in] 7.1 inHeight 181 mmWidth [in] 5.5 inWidth 140 mmDepth [in] 4.2 inDepth 107 mm

ConnectionsArrangement of electrical connectors / for maincurrent circuit

Front terminal

Type of electrical connection / for main current circuit Lug terminalType of connectable conductor cross-section,connection screw, width x thickness , min.

13 x 1 mm

Auxiliary circuitNumber of CO contacts / for auxiliary contacts 0

AccessoriesProduct extension / optional / motor drive Yes

Environmental conditionsProtection class IP / on the front IP40Ambient temperature

● during operation / minimum -25 °C

● during operation / maximum 70 °C

● during storage / minimum -40 °C

● during storage / maximum 80 °C

CertificatesEquipment marking / acc. to DIN EN 81346-2 QCertificate of suitability / as approval for NAVAL (nocombat vessels) / Supplement SB

No

3VA2225-4HL42-0AA0 Subject to change without noticePage 3/5 11/28/2016 © Copyright Siemens AG

Page 4: Data sheet 3VA2225-4HL42-0AA0...(HACR Type) Yes Design of the overcurrent release ETU320 Protective function of the overcurrent release LI Number of poles 4 General technical data

EMC Declaration ofConformity

Test Certificates other

Typprüfbescheinigung/Werkszeugnis

sonstig sonstig

Further informationInformation- and Downloadcenter (Catalogs, Brochures,…)http://www.siemens.com/lowvoltage/catalogs

Industry Mall (Online ordering system)https://eb.automation.siemens.com/mall/en/WW/Catalog/Product/3VA2225-4HL42-0AA0

Service&Support (Manuals, Certificates, Characteristics, FAQs,...)http://support.automation.siemens.com/WW/view/en/3VA2225-4HL42-0AA0/all

Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3VA2225-4HL42-0AA0

CAx-Online-Generatorhttp://www.siemens.com/cax

Tender specificationshttp://www.siemens.com/specifications

52.5

140

181

157

35

3535

1212

20

18

18

83

93

107

70

81

22.5

136

22.523

22.6

17.5

35

70

73

146

17.5

4.5

19

38

3VA2225-4HL42-0AA0 Subject to change without noticePage 4/5 11/28/2016 © Copyright Siemens AG

Page 5: Data sheet 3VA2225-4HL42-0AA0...(HACR Type) Yes Design of the overcurrent release ETU320 Protective function of the overcurrent release LI Number of poles 4 General technical data

SIEMENS

L

ETU320

I>>

N

I

N

-Q

I> I> I> I>

-X2 -X3

1 3 5 N

2 4 6 N.EFB RCD

last modified: 10/29/2016

3VA2225-4HL42-0AA0 Subject to change without noticePage 5/5 11/28/2016 © Copyright Siemens AG