databook - daikin · 2020. 12. 8. · databook 25/06/2015 . low operating cost and extended...

47
www.eurovent-certification.com www.certiflash.com Air Cooled Scroll Chillers EWAQ~G SS (Standard Efficiency - Standard Noise) - Cooling Capacity from 75 to 154 kW SR (Standard Efficiency - Reduced Noise) - Cooling Capacity from 69 to 143 kW XS (High Efficiency - Standard Noise) - Cooling Capacity from 80 to 149 kW XR (High Efficiency - Reduced Noise) - Cooling Capacity from 76 to 141 kW Performance according to EN14511. EWAQ Code: Printing Date: R3.7.2 CSS - Rev. 9.4 25/06/2015 Databook

Upload: others

Post on 27-Feb-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

www.eurovent-certification.com www.certiflash.com

Air Cooled Scroll Chillers

EWAQ~G

SS (Standard Efficiency - Standard Noise) - Cooling Capacity from 75 to 154 kW SR (Standard Efficiency - Reduced Noise) - Cooling Capacity from 69 to 143 kW

XS (High Efficiency - Standard Noise) - Cooling Capacity from 80 to 149 kW XR (High Efficiency - Reduced Noise) - Cooling Capacity from 76 to 141 kW

Performance according to EN14511.

EWAQ

Code:

Printing Date:

R3.7.2

CSS - Rev. 9.4

25/06/2015

Databook

Page 2: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the energy

efficiency of the chillers, with the objective of bringing down operating costs and improving installation profitability, effectiveness and economical management. The chillers feature a high efficiency scroll compressors, large condenser coil surface area for maximum heat transfer and low discharge pressure, continuous fan speed modulation, and a 'plate to plate' evaporator with low refrigerant pressure drops. Low operating sound levels Very low sound levels both at full load and part load conditions are achieved by the latest

compressor design and by a unique new fan that moves large volume of air at exceptionally low sound levels and by the virtually vibration-free operation. Outstanding reliability The chillers have one refrigerant circuit. The unit is equipped with hermetic orbiting scroll compressor

complete with motor over-temperature and over-current devices and protection against excessive gas discharge temperature, a proactive control logic and are full factory-run-tested to optimized trouble-free operation. Superior control logic The new controller provides an easy to use control environmental. The control logic is designed to

provide maximum efficiency, to continue operation in unusual operating conditions and to provide a history of unit operation. One of the greatest benefits is the easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications. Code requirements – Safety and observant of laws/directives Units are designed and in accordance with applicable selections of the following:

Construction of pressure vessel 97/23/EC (PED) Machinery Directive 2006/42/EC Low Voltage 2006/95/EC Electromagnetic Compatibility 2004/108/EC Electrical& Safety codes EN 60204–1 / EN 60335-2-40 Manufacturing Quality Stds UNI – EN ISO 9001:2004

Certifications Units are CE marked, complying with European directives in force, concerning manufacturing and safety. On

request units can be produced complying with laws in force in non European countries (ASME, GOST, etc.), and with other applications. Versions This range is available in two different versions: STANDARD EFFICIENCY 7 sizes to cover a range from 75 up to 154 Kw with an EER up to 2.76 and an ESEER up to 4.23 (data referred to Standard

Noise). HIGH EFFICIENCY 6 sizes to cover a range from 80 up to 149 Kw with an EER up to 3.12 and an ESEER up to 4.36 (data referred to Standard Noise). The EER (Energy Efficiency Ratio) is the ratio of the Cooling Capacity to the Power Input of the unit. The Power Input includes: the power input for operation of the compressor, the power input of all control and safety devices, the power input for fans. The ESEER (European Seasonal Energy Efficiency Ratio) is a weighed formula enabling to take into account the variation of EER with the load rate and the variation of air inlet condenser temperature. ESEER = A x EER100% + B x EER75% + C x EER50% + D x EER25%

K = Coefficient; T = Air inlet condenser temperature. Sound configurations Standard and reduced sound configurations available as follows: STANDARD SOUND Condenser fan rotating at 1360 rpm, rubber antivibration under compressor. REDUCED SOUND Condenser fan rotating at 1108 rpm, rubber antivibration under compressor, compressors acoustic insulation.

2/47

FEATURES AND BENEFITS

Page 3: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

Cabinet and structure The cabinet is made of galvanized steel sheet and painted to provide a high resistance to

corrosion. Colour Ivory White (Munsell code 5Y7.5/1) (±RAL7044).The base frame has an eye - hook to lift the unit with ropes

for an easy installation. The weight is uniformly distributed along the profiles of the base and this facilitates the arrangement

of the unit.

Compressor The compressor is hermetic orbiting scroll compressor complete with motor over - temperature and over -

current devices. An oil heater, which starts automatically, keeps the oil from being diluted by the refrigerant when the

compressor stops. The compressors are connected in Tandem on a single refrigerating circuit and are fitted on rubber

antivibration mounts and complete with oil charge.

Refrigerant Units have been optimized to operates with R - 410A, refrigerant with zero ODP (Ozone Depletion Potential).

R - 410A has been the logical choice for our multiple scroll chiller because today it is one of the most promising refrigerants in

terms of efficiency, stability and environmental impact. R - 410A offers a small swept volume, a good heat exchange capacity

and leads to reduced component sizes of items such as heat exchangers and tubing.

Evaporator (Plate Heat Exchanger) The unit is equipped with a direct expansion plate to plate type evaporator.

This heat exchanger is made of stainless steel brazed plates and is covered with a 20mm closed cell insulation material. The

exchanger is equipped with an electric heater for protection against freezing. The evaporator is manufactured in accordance

to PED approval.

Condenser The condenser is made entirely of aluminum with flat tubes containing small channels. Full - depth louvered

aluminum fins are inserted between the tubes maximizing the heat exchange. The Microchannel technology ensures the

highest performance with the minimum surface for the exchanger. The quantity of refrigerant is also reduced compared to

Cu/Al condenser. Special treatment ensure resistance to the corrosion by atmospheric agents extending the life time.

Note: for application in industrial and costal environment contact factory in order to evaluate if, for the specific environment,

special protections measures are needed.

Condenser fans (ø 450 mm) The condenser fans are propeller type with high efficiency design blades to maximize

performances. The material of the blades is glass reinforced resin and each fan is protected by a guard. Fan motors are

internally protected from overtemperature and are IP54.

Electronic expansion valve The unit is equipped with the most advanced electronic expansion valves to achieve

precise control of refrigerant mass flow. As today’s system requires improved energy efficiency, tighter temperature control,

wider range of operating conditions and incorporate features like remote monitoring and diagnostics, the application of

electronic expansion valves becomes mandatory.

Electronic expansion valves possess unique features: short opening and closing time, high resolution, positive shut - off

function to eliminate use of additional solenoid valve, continuous modulation of mass flow without stress in the refrigerant

circuit and corrosion resistance stainless steel body.

Electronic expansion valves are typically working with lower difference between high and low pressure side, than a

thermostatic expansion valve. The electronic expansion valve allows the system to work with low condenser pressure (winter

time) without any refrigerant flow problems and with a perfect chilled water leaving temperature control.

Refrigerant circuit Each unit has 1 refrigerant circuit that includes:

• Compressors

• Refrigerant

• Evaporator

• Air Cooled Condenser

• Electronic expansion valve

• Charging valves

• High pressure switch

• High pressure transducers

• Low pressure transducers

• Suction temperature sensor

Electrical control panel Power and control are located in the main panel that is manufactured to ensure protection

against all weather conditions. The electrical panel is IP54 and (when opening the doors) internally protected against possible

accidental contact with live parts. The main panel is fitted with a main switch interlocked door that shuts off power supply

when opening.

Power Section

The power section includes compressors and fans protection devices, compressors and fans starters and control circuit power

supply.

Unit controller

Unit controller is installed as standard; it can be used to modify unit set - points and check control parameters. A built - in

display shows chiller operating status plus temperatures of water, refrigerant, programmable values, set - points. A

sophisticated software with predictive logic, selects the most energy efficient combination of compressors and EEXV to keep

stable operating conditions to maximise chiller energy efficiency and reliability.

The unit controller is able to protect critical components based on external signs from its system (such as motor

3/47

GENERAL CHARACTERISTICS

Page 4: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

The unit controller is able to protect critical components based on external signs from its system (such as motor temperatures, refrigerant gas and oil pressures, pressure switches and evaporator). The input coming from the high pressure

switch cuts all digital output from the controller in less than 50ms, this is an additional security for the equipment.

Fast program cycle (200ms) for a precise monitoring of the system. Floating point calculations supported for increased

accuracy in Pressure / Temperature conversions.

Control section main features

Control Section has the following feature.

• Management of the refrigerant circuit capacity

• Full routine operation at condition of:

- high thermal load

- high evaporator entering water temperature (start - up)

• Display of evaporator entering/leaving water temperature.

•Display of condensing - evaporating temperature and pressure, suction superheat.

• Leaving water evaporator temperature regulation .

• Compressor and pumps hours counter.

• Display of Status Safety Devices.

• Number of starts and compressor working hours.

• Re - start in case of power failure (automatic / manual).

• Soft Load (optimized management of the compressor load during the start - up).

• OAT (Outside Ambient temperature) Reset.

• Start at high evaporator water temperature.

• Return Reset (Set Point Reset based on return water temperature).

• Set point Reset (optional).

• Application and system upgrade with commercial SD cards.

Safety device / logic for each refrigerant circuit

The following devices / logics are available.

• High pressure (pressure switch).

• High pressure (transducer).

• Low pressure (transducer).

• High motor winding temperature.

• No pressure change at start

System security

The following securities are available.

• Under/over voltage (available as option)

• Freeze protection.

Unit controller

Unit controller built - in terminal has the following features.

• 164x44 dots liquid crystal display with white back lighting. Supports Unicode fonts for multi - lingual.

• Key - pad consisting of 3 keys.

• Push’n’Roll control for an increased usability.

• Memory to protect the data.

• General faults alarm relays.

• Password access to modify the setting.

• Application security to prevent application tampering or hardware usability with third party applications.

• Service report displaying all running hours and general conditions.

• Alarm history memory to allow an easy fault analysis.

Supervising systems (on request) Unit controller remote communication

Unit controller is able to communicate to BMS (Building Management System) based on the most common

protocols as:

• ModbusRTU

• LonWorks, now also based on the international 8040 Standard Chiller Profile and LonMark Technology.

• BacNet BTP certifief over IP and MS/TP (class 4).

• Ethernet TCP/IP.

4/47

GENERAL CHARACTERISTICS

Page 5: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

Additional information related to F - GAS Regulation (EU) No 517/2014 OF THE European Parliament and of the

Council of 16 April 2014 on fluorinated greenhouse gases and repealing Regulation (EC) No 842/2006

5/47

GENERAL CHARACTERISTICS

Page 6: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

Standard Options (supplied on basic unit)

Direct on line starter (DOL)

Double setpoint - Dual leaving water temperature setpoints.

20mm evaporator insulation - The external shell is covered with a 20mm closed cell insulation material.

Evaporator electric heater - Electric heater (controlled by a thermostat) to protect the evaporator from freezing down to -

28°C ambient temperature, providing the power supply is on.

Electronic expansion valve

Ambient outside temperature sensor and setpoint reset

General fault contactor

Hour run meter

Main switch interlock door

Master / Slave – sequencing control that allow to connect up to 4 units in order to coordinate the operation of the chillers

working as a bigger unit with multiple circuits.

Options (on request)

MECHANICAL

Evaporator flow switch* - Supplied separately to be wired and installed on the evaporator water piping (by the customer).

Water filter* - Supplied separately, the water filter removes impurities from water by means of a fine physical barrier.

Evaporator victaulic kit - Hydraulic joint with gasket for an easy and quick water connection.

Partial heat recovery - Plate to plate heat exchangers for hot water production.

Total heat recovery - Plate to plate heat exchangers for hot water production.

Brine version - Allows the unit to operate down to - 10°C leaving liquid temperature (antifreeze required). Required below

+4°C

Coil guards

Suction and Discharge line shut - off valve - Installed to facilitate maintenance operation.

High and low pressure side manometers

One centrifugal pump (low lift) - Hydronic kit consists of: single direct driven centrifugal pump, pressure gauge, safety

valve, drain valve. The motor pump is protected by a circuit breaker installed in control panel. The kit is assembled and

wired to the control panel. The pipe and pump are protected from freezing with an additional electrical heater.

One centrifugal pump (high lift) Hydronic kit consists of: single direct driven centrifugal pump, pressure gauge, safety

valve, drain valve. The motor pump is protected by a circuit breaker installed in control panel. The kit is assembled and

wired to the control panel. The pipe and pump are protected from freezing with an additional electrical heater.

Two centrifugal pump (low lift) - Hydronic kit consists of: twin direct driven centrifugal pumps, pressure gauge, safety

valve, drain valve. The motor pump is protected by a circuit breaker installed in control panel. The kit is assembled and

wired to the control panel. The pipe and pumps are protected from freezing with an additional electrical heater.

Two centrifugal pump (high lift) Hydronic kit consists of: twin direct driven centrifugal pumps, pressure gauge, safety

valve, drain valve. The motor pump is protected by a circuit breaker installed in control panel. The kit is assembled and

wired to the control panel. The pipe and pumps are protected from freezing with an additional electrical heater.

6/47

OPTIONS

Page 7: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

Inertial tank (installed on board) All the Hydronic kit are available with inertial tank installed on board.

The tank capacities are the follow:

Standard efficiency version

size from 075 to 085 – tank volume 70 liters size from 100 to 120 - tank volume 145 liters size from 140 to 155 – tank volume 190 liters

High efficiency version

size from 080 to 090 – tank volume 145 liters

size from 105 to 150 – tank volume 190 liters

Double pressure relief valve with diverter

(*) Note: the installation is mandatory

ELECTRICAL / CONTROL

Controller expansion pack including :

Under / Over voltage control - Electronic device that monitors and displays input voltage, and stops the chiller in case of

phase loss, wrong phase sequence, or voltage exceeding minimum and maximum allowed values.

Setpoint reset, Demand limit and Alarm from external device, Setpoint Reset : The leaving water temperature set -

point can be overwritten with an external 4 - 20mA, through the ambient temperature, or through the evaporator water

temperature deltaT. Demand Limit: Chiller capacity can be limited through an external 4 - 20mA signal or via network. Alarm

from external device: The unit controller is able to receive an external alarm signal. The user can decide whether this alarm

signal will stop the unit or not.

Capacitors for power factor correction - Devices that increase the power factor of the unit. The capacitors are “dry” self -

regenerating type with over pressure disconnecting safety device insulated with a no toxic dielectric mix without PCB or PCT.

Compressors circuit breakers - Safety devices that include in a single device all safety functions otherwise provided by

standard fuses and optional thermal relays, such as protection against overcurrent, overload, current unbalance.

Fans circuit breakers - Safety devices that, added to the standard protection devices. One circuit breaker protects

all

the fan motors against overload and overcurrent.

INSTALLATION

Rubber anti vibration mounts - Supplied separately, these are positioned under the base of the unit during installation.

Ideal to reduce the vibrations when the unit is floor mounted.

Spring anti vibration mounts - Supplied separately, these are positioned under the base of the unit during installation.

Ideal for dampening vibrations for installation on roofs and metallic structures.

External tank without cabinet (500 L)

External tank without cabinet (1000 L)

External tank with cabinet (500 L)

External tank with cabinet (1000 L)

OTHER

Container Kit

Witness test

Acoustic test

7/47

OPTIONS

Page 8: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWA Q 120 G - S S

Machine type

Refrigerant

Capacity class in kW (Cooling)

Model series

Inverter

Efficiency level

Sound level

EWA = Air Cooled chiller cooling only

Q = R410a

Always 3-digit code

G = single circuit

- = no Inverter

S X

= Standard Efficiency = High efficiency

S R

= Standard noise = Reduced noise

8/47

NOMENCLATURE

Page 9: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-SS

2"1/2 2"1/2 2"1/2 2"1/2 2"1/2 2"1/2 mm Evaporator water inlet/outlet

PIPING CONNECTIONS

1 1 1 1 1 1 No. N. of circuits

12 10 10 10 8 8 kg Refrigerant charge

R410A R410A R410A R410A R410A R410A Refrigerant type

REFRIGERANT CIRCUIT

71 71 71 69 68 66 dB(A) Sound pressure - Cooling

89 89 89 87 85 83 dB(A) Sound power - Cooling(8)

SOUND LEVEL

2 2 2 2 2 2 No. Quantity

13.6 13.6 11.4 9.34 8.05 6.76 l Oil charge

Scroll Scroll Scroll Scroll Scroll Scroll Type

COMPRESSOR

3.6 2.7 2.7 2.7 1.8 1.8 kW Motor input

1360 1360 1360 1360 1360 1360 rpm Speed

8 6 6 6 4 4 No. Quantity

12008 9029 9029 9029 6444 6017 l/s Nominal air flow

450 450 450 450 450 450 mm Diameter

DOL DOL DOL DOL DOL DOL Drive(7)

DPT DPT DPT DPT DPT DPT Type(6)

FAN

microchannel microchannel microchannel microchannel microchannel microchannel Type(5)

AIR HEAT EXCHANGER

CC CC CC CC CC CC Insulation material(4)

27.5 36.0 31.6 36.9 27.3 15.5 kPa Nominal Water pressure drop

6.7 5.6 5.1 4.6 4.0 3.6 l/s Nominal water flow rate

8.10 5.60 5.60 4.90 4.90 5.60 l Water Volume

BPHE BPHE BPHE BPHE BPHE BPHE Type(3)

WATER HEAT EXCHANGER

1054 993 963 934 802 692 kg Operating Weight

1037 982 953 923 792 681 kg Unit Weight

WEIGHT

3200 3200 2680 2680 2680 2140 mm Length

1195 1195 1195 1195 1195 1195 mm Width

1800 1800 1800 1800 1800 1800 mm Height

DIMENSIONS

GPSS GPSS GPSS GPSS GPSS GPSS Material(2)

IW IW IW IW IW IW Colour(2)

CASING

4.92 4.66 4.86 4.78 4.97 4.79 IPLV

4.20 3.91 4.12 4.04 4.23 4.11 ESEER

2.73 2.70 2.70 2.76 2.70 2.70 EER(1)

51.1 43.4 39.5 35.0 31.2 27.7 kW Unit power input - Cooling(1)

43 50 44 50 44 50 % Capacity Control - Minimum capacity

Step Step Step Step Step Step Capacity Control - Type

139 117 107 96.7 84.2 74.7 kW Capacity - Cooling(1)

COOLING PERFORMANCE

140 120 110 100 085 075 MODEL

Fluid: Water

(1) Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation;

(2) IW: Ivory White; GPSS: Galvanized and Painted Steel Sheet; (3) PHE: Plate Heat Exchanger --- S&T: Single Pass Shell & Tube

(4) CC: Closed Cell; (5) HFP: High efficiency fin and tube type with integral subcooler

(6) DPT: Direct Propeller Type; (7) DOL: Direct On Line - VFD: Inverter - BRS: Brushless

(8)Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are mesuared in accordance with ISO 9614 and Eurovent 8/1 for Eurovent

certified units. The certification refers only to the overall sound power level, the sound pressure is calculated from the sound power level and are for information only

and not cosidered bounding

9/47

TECHNICAL SPECIFICATIONS

Page 10: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-SS

2"1/2 mm Evaporator water inlet/outlet

PIPING CONNECTIONS

1 No. N. of circuits

12 kg Refrigerant charge

R410A Refrigerant type

REFRIGERANT CIRCUIT

71 dB(A) Sound pressure - Cooling

89 dB(A) Sound power - Cooling(8)

SOUND LEVEL

2 No. Quantity

13.6 l Oil charge

Scroll Type

COMPRESSOR

3.6 kW Motor input

1360 rpm Speed

8 No. Quantity

12008 l/s Nominal air flow

450 mm Diameter

DOL Drive(7)

DPT Type(6)

FAN

microchannel Type(5)

AIR HEAT EXCHANGER

CC Insulation material(4)

25.8 kPa Nominal Water pressure drop

7.4 l/s Nominal water flow rate

9.40 l Water Volume

BPHE Type(3)

WATER HEAT EXCHANGER

1085 kg Operating Weight

1066 kg Unit Weight

WEIGHT

3200 mm Length

1195 mm Width

1800 mm Height

DIMENSIONS

GPSS Material(2)

IW Colour(2)

CASING

4.78 IPLV

4.06 ESEER

2.70 EER(1)

57.2 kW Unit power input - Cooling(1)

50 % Capacity Control - Minimum capacity

Step Capacity Control - Type

154 kW Capacity - Cooling(1)

COOLING PERFORMANCE

155 MODEL

Fluid: Water

(1) Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation;

(2) IW: Ivory White; GPSS: Galvanized and Painted Steel Sheet; (3) PHE: Plate Heat Exchanger --- S&T: Single Pass Shell & Tube

(4) CC: Closed Cell; (5) HFP: High efficiency fin and tube type with integral subcooler

(6) DPT: Direct Propeller Type; (7) DOL: Direct On Line - VFD: Inverter - BRS: Brushless

(8)Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are mesuared in accordance with ISO 9614 and Eurovent 8/1 for Eurovent

certified units. The certification refers only to the overall sound power level, the sound pressure is calculated from the sound power level and are for information only and not cosidered bounding

10/47

TECHNICAL SPECIFICATIONS

Page 11: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-SR

2"1/2 2"1/2 2"1/2 2"1/2 2"1/2 2"1/2 mm Evaporator water inlet/outlet

PIPING CONNECTIONS

1 1 1 1 1 1 No. N. of circuits

12 10 10 10 8 8 kg Refrigerant charge

R410A R410A R410A R410A R410A R410A Refrigerant type

REFRIGERANT CIRCUIT

68 68 68 66 65 62 dB(A) Sound pressure - Cooling

86 86 86 84 82 79 dB(A) Sound power - Cooling(8)

SOUND LEVEL

2 2 2 2 2 2 No. Quantity

13.6 13.6 11.4 9.34 8.05 6.76 l Oil charge

Scroll Scroll Scroll Scroll Scroll Scroll Type

COMPRESSOR

2.7 2.0 2.0 2.0 1.4 1.4 kW Motor input

1108 1108 1108 1108 1108 1108 rpm Speed

8 6 6 6 4 4 No. Quantity

9023 6787 6787 6787 5046 4523 l/s Nominal air flow

450 450 450 450 450 450 mm Diameter

DOL DOL DOL DOL DOL DOL Drive(7)

DPT DPT DPT DPT DPT DPT Type(6)

FAN

microchannel microchannel microchannel microchannel microchannel microchannel Type(5)

AIR HEAT EXCHANGER

CC CC CC CC CC CC Insulation material(4)

24.1 31.1 27.6 32.6 24.0 13.3 kPa Nominal Water pressure drop

6.2 5.2 4.8 4.4 3.8 3.3 l/s Nominal water flow rate

8.10 5.60 5.60 4.86 4.86 5.58 l Water Volume

BPHE BPHE BPHE BPHE BPHE BPHE Type(3)

WATER HEAT EXCHANGER

1084 1023 993 964 832 722 kg Operating Weight

1067 1012 983 953 822 711 kg Unit Weight

WEIGHT

3200 3200 2680 2680 2680 2140 mm Length

1195 1195 1195 1195 1195 1195 mm Width

1800 1800 1800 1800 1800 1800 mm Height

DIMENSIONS

GPSS GPSS GPSS GPSS GPSS GPSS Material(2)

IW IW IW IW IW IW Colour(2)

CASING

4.85 4.50 4.78 4.71 4.85 4.67 IPLV

4.12 3.74 4.02 3.94 4.12 3.94 ESEER

2.42 2.35 2.38 2.47 2.38 2.36 EER(1)

54.0 46.3 42.0 36.8 33.1 29.4 kW Unit power input - Cooling(1)

43 50 44 50 44 50 % Capacity Control - Minimum capacity

Step Step Step Step Step Step Capacity Control - Type

130 109 99.7 91.0 78.9 69.3 kW Capacity - Cooling(1)

COOLING PERFORMANCE

140 120 110 100 085 075 MODEL

Fluid: Water

(1) Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation;

(2) IW: Ivory White; GPSS: Galvanized and Painted Steel Sheet; (3) PHE: Plate Heat Exchanger --- S&T: Single Pass Shell & Tube

(4) CC: Closed Cell; (5) HFP: High efficiency fin and tube type with integral subcooler

(6) DPT: Direct Propeller Type; (7) DOL: Direct On Line - VFD: Inverter - BRS: Brushless

(8)Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are mesuared in accordance with ISO 9614 and Eurovent 8/1 for Eurovent

certified units. The certification refers only to the overall sound power level, the sound pressure is calculated from the sound power level and are for information only and not cosidered bounding

11/47

TECHNICAL SPECIFICATIONS

Page 12: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-SR

2"1/2 mm Evaporator water inlet/outlet

PIPING CONNECTIONS

1 No. N. of circuits

12 kg Refrigerant charge

R410A Refrigerant type

REFRIGERANT CIRCUIT

68 dB(A) Sound pressure - Cooling

86 dB(A) Sound power - Cooling(8)

SOUND LEVEL

2 No. Quantity

13.6 l Oil charge

Scroll Type

COMPRESSOR

2.7 kW Motor input

1108 rpm Speed

8 No. Quantity

9023 l/s Nominal air flow

450 mm Diameter

DOL Drive(7)

DPT Type(6)

FAN

microchannel Type(5)

AIR HEAT EXCHANGER

CC Insulation material(4)

22.2 kPa Nominal Water pressure drop

6.9 l/s Nominal water flow rate

9.36 l Water Volume

BPHE Type(3)

WATER HEAT EXCHANGER

1115 kg Operating Weight

1096 kg Unit Weight

WEIGHT

3200 mm Length

1195 mm Width

1800 mm Height

DIMENSIONS

GPSS Material(2)

IW Colour(2)

CASING

4.61 IPLV

3.88 ESEER

2.34 EER(1)

61.2 kW Unit power input - Cooling(1)

50 % Capacity Control - Minimum capacity

Step Capacity Control - Type

143 kW Capacity - Cooling(1)

COOLING PERFORMANCE

155 MODEL

Fluid: Water

(1) Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation;

(2) IW: Ivory White; GPSS: Galvanized and Painted Steel Sheet; (3) PHE: Plate Heat Exchanger --- S&T: Single Pass Shell & Tube

(4) CC: Closed Cell; (5) HFP: High efficiency fin and tube type with integral subcooler

(6) DPT: Direct Propeller Type; (7) DOL: Direct On Line - VFD: Inverter - BRS: Brushless

(8)Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are mesuared in accordance with ISO 9614 and Eurovent 8/1 for Eurovent

certified units. The certification refers only to the overall sound power level, the sound pressure is calculated from the sound power level and are for information only and not cosidered bounding

12/47

TECHNICAL SPECIFICATIONS

Page 13: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-XS

2"1/2 2"1/2 2"1/2 2"1/2 2"1/2 2"1/2 mm Evaporator water inlet/outlet

PIPING CONNECTIONS

1 1 1 1 1 1 No. N. of circuits

12 10 10 10 8 8 kg Refrigerant charge

R410A R410A R410A R410A R410A R410A Refrigerant type

REFRIGERANT CIRCUIT

71 71 71 69 68 66 dB(A) Sound pressure - Cooling

71 89 89 87 85 84 dB(A) Sound power - Cooling(8)

SOUND LEVEL

2 2 2 2 2 2 No. Quantity

13.6 13.6 11.4 9.34 8.05 6.76 l Oil charge

Scroll Scroll Scroll Scroll Scroll Scroll Type

COMPRESSOR

4.5 4.5 3.6 3.6 2.7 2.7 kW Motor input

1360 1360 1360 1360 1360 1360 rpm Speed

10 10 8 8 6 6 No. Quantity

15046 15046 12008 12008 9498 9029 l/s Nominal air flow

450 450 450 450 450 450 mm Diameter

DOL DOL DOL DOL DOL DOL Drive(7)

DPT DPT DPT DPT DPT DPT Type(6)

FAN

microchannel microchannel microchannel microchannel microchannel microchannel Type(5)

AIR HEAT EXCHANGER

CC CC CC CC CC CC Insulation material(4)

20.6 25.4 19.9 20.3 32.7 25.7 kPa Nominal Water pressure drop

7.1 6.3 5.6 5.0 4.3 3.8 l/s Nominal water flow rate

8.10 5.60 5.60 4.86 4.86 5.58 l Water Volume

BPHE BPHE BPHE BPHE BPHE BPHE Type(3)

WATER HEAT EXCHANGER

1144 1102 1040 1002 860 744 kg Operating Weight

1123 1086 1024 987 850 734 kg Unit Weight

WEIGHT

3800 3800 3200 3200 3200 2680 mm Length

1195 1195 1195 1195 1195 1195 mm Width

1820 1820 1800 1800 1800 1800 mm Height

DIMENSIONS

GPSS GPSS GPSS GPSS GPSS GPSS Material(2)

IW IW IW IW IW IW Colour(2)

CASING

5.05 4.92 5.02 4.96 5.04 4.82 IPLV

4.36 4.22 4.34 4.28 4.30 4.20 ESEER

3.10 3.10 3.10 3.12 3.11 3.10 EER(1)

48.1 42.3 37.7 33.8 29.0 25.8 kW Unit power input - Cooling(1)

43 50 44 50 44 50 % Capacity Control - Minimum capacity

Step Step Step Step Step Step Capacity Control - Type

149 131 117 105 90.3 79.8 kW Capacity - Cooling(1)

COOLING PERFORMANCE

150 130 115 105 090 080 MODEL

Fluid: Water

(1) Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation;

(2) IW: Ivory White; GPSS: Galvanized and Painted Steel Sheet; (3) PHE: Plate Heat Exchanger --- S&T: Single Pass Shell & Tube

(4) CC: Closed Cell; (5) HFP: High efficiency fin and tube type with integral subcooler

(6) DPT: Direct Propeller Type; (7) DOL: Direct On Line - VFD: Inverter - BRS: Brushless

(8)Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are mesuared in accordance with ISO 9614 and Eurovent 8/1 for Eurovent

certified units. The certification refers only to the overall sound power level, the sound pressure is calculated from the sound power level and are for information only and not cosidered bounding

13/47

TECHNICAL SPECIFICATIONS

Page 14: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-XR

2"1/2 2"1/2 2"1/2 2"1/2 2"1/2 2"1/2 mm Evaporator water inlet/outlet

PIPING CONNECTIONS

1 1 1 1 1 1 No. N. of circuits

12 10 10 10 8 8 kg Refrigerant charge

R410A R410A R410A R410A R410A R410A Refrigerant type

REFRIGERANT CIRCUIT

67 67 68 66 65 62 dB(A) Sound pressure - Cooling

86 86 86 84 82 80 dB(A) Sound power - Cooling(8)

SOUND LEVEL

2 2 2 2 2 2 No. Quantity

13.6 13.6 11.4 9.34 8.05 6.76 l Oil charge

Scroll Scroll Scroll Scroll Scroll Scroll Type

COMPRESSOR

3.4 3.4 2.7 2.7 2.0 2.0 kW Motor input

1108 1108 1108 1108 1108 1108 rpm Speed

10 10 8 8 6 6 No. Quantity

11309 11309 9023 9023 7356 6787 l/s Nominal air flow

450 450 450 450 450 450 mm Diameter

DOL DOL DOL DOL DOL DOL Drive(7)

DPT DPT DPT DPT DPT DPT Type(6)

FAN

microchannel microchannel microchannel microchannel microchannel microchannel Type(5)

AIR HEAT EXCHANGER

CC CC CC CC CC CC Insulation material(4)

18.4 23.0 17.8 18.4 29.6 23.3 kPa Nominal Water pressure drop

6.7 6.0 5.3 4.8 4.1 3.6 l/s Nominal water flow rate

8.10 5.60 5.60 4.86 4.86 5.58 l Water Volume

BPHE BPHE BPHE BPHE BPHE BPHE Type(3)

WATER HEAT EXCHANGER

1174 1132 1070 1032 890 774 kg Operating Weight

1153 1116 1054 1017 880 764 kg Unit Weight

WEIGHT

3800 3800 3200 3200 3200 2680 mm Length

1195 1195 1195 1195 1195 1195 mm Width

1820 1820 1800 1800 1800 1800 mm Height

DIMENSIONS

GPSS GPSS GPSS GPSS GPSS GPSS Material(2)

IW IW IW IW IW IW Colour(2)

CASING

5.03 4.89 4.99 4.93 4.99 4.85 IPLV

4.33 4.21 4.31 4.27 4.29 4.18 ESEER

2.83 2.88 2.83 2.89 2.88 2.88 EER(1)

49.8 43.3 39.0 34.7 29.9 26.4 kW Unit power input - Cooling(1)

43 50 44 50 44 50 % Capacity Control - Minimum capacity

Step Step Step Step Step Step Capacity Control - Type

141 125 110 100 86.0 76.0 kW Capacity - Cooling(1)

COOLING PERFORMANCE

150 130 115 105 090 080 MODEL

Fluid: Water

(1) Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation;

(2) IW: Ivory White; GPSS: Galvanized and Painted Steel Sheet; (3) PHE: Plate Heat Exchanger --- S&T: Single Pass Shell & Tube

(4) CC: Closed Cell; (5) HFP: High efficiency fin and tube type with integral subcooler

(6) DPT: Direct Propeller Type; (7) DOL: Direct On Line - VFD: Inverter - BRS: Brushless

(8)Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are mesuared in accordance with ISO 9614 and Eurovent 8/1 for Eurovent certified units. The certification refers only to the overall sound power level, the sound pressure is calculated from the sound power level and are for information only

and not cosidered bounding

14/47

TECHNICAL SPECIFICATIONS

Page 15: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-SS

DOL Starting method

114 A Maximum running current

10% % Voltage tollerance maximum

-10% % Voltage tollerance minimum

400 V Voltage

3 No. Phases

COMPRESSORS

7 A Nominal running current cooling

FANS

134 A Maximum current for wires sizing

122 A Maximum running current

102 A Nominal running current cooling

374 A Maximum starting current

UNIT

10% % Voltage tollerance maximum

-10% % Voltage tollerance minimum

400 V Voltage

50 Hz Frequency

3 No. Phases

POWER SUPPLY

155 MODEL

DOL DOL DOL DOL DOL DOL Starting method

100 86 79 71 65 60 A Maximum running current

10% 10% 10% 10% 10% 10% % Voltage tollerance maximum

-10% -10% -10% -10% -10% -10% % Voltage tollerance minimum

400 400 400 400 400 400 V Voltage

3 3 3 3 3 3 No. Phases

COMPRESSORS

7 6 6 6 4 4 A Nominal running current cooling

FANS

118 101 93 84 76 70 A Maximum current for wires sizing

108 92 84 77 69 64 A Maximum running current

89 79 70 62 58 54 A Nominal running current cooling

361 321 313 266 259 208 A Maximum starting current

UNIT

10% 10% 10% 10% 10% 10% % Voltage tollerance maximum

-10% -10% -10% -10% -10% -10% % Voltage tollerance minimum

400 400 400 400 400 400 V Voltage

50 50 50 50 50 50 Hz Frequency

3 3 3 3 3 3 No. Phases

POWER SUPPLY

140 120 110 100 085 075 MODEL

Fluid: Water

Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.

Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of

inverter driven units, no inrush current at start up is experienced.

Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.

Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current

Maximum unit current for wires sizing is based on minimum allowed voltage

Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.

15/47

ELECTRICAL SPECIFICATIONS

Page 16: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-SR

DOL Starting method

114 A Maximum running current

10% % Voltage tollerance maximum

-10% % Voltage tollerance minimum

400 V Voltage

3 No. Phases

COMPRESSORS

7 A Nominal running current cooling

FANS

133 A Maximum current for wires sizing

121 A Maximum running current

109 A Nominal running current cooling

374 A Maximum starting current

UNIT

10% % Voltage tollerance maximum

-10% % Voltage tollerance minimum

400 V Voltage

50 Hz Frequency

3 No. Phases

POWER SUPPLY

155 MODEL

DOL DOL DOL DOL DOL DOL Starting method

100 86 79 71 65 60 A Maximum running current

10% 10% 10% 10% 10% 10% % Voltage tollerance maximum

-10% -10% -10% -10% -10% -10% % Voltage tollerance minimum

400 400 400 400 400 400 V Voltage

3 3 3 3 3 3 No. Phases

COMPRESSORS

7 5 5 5 3 3 A Nominal running current cooling

FANS

118 101 92 84 76 70 A Maximum current for wires sizing

107 91 84 76 69 63 A Maximum running current

93 84 74 65 61 57 A Nominal running current cooling

360 320 313 266 258 207 A Maximum starting current

UNIT

10% 10% 10% 10% 10% 10% % Voltage tollerance maximum

-10% -10% -10% -10% -10% -10% % Voltage tollerance minimum

400 400 400 400 400 400 V Voltage

50 50 50 50 50 50 Hz Frequency

3 3 3 3 3 3 No. Phases

POWER SUPPLY

140 120 110 100 085 075 MODEL

Fluid: Water

Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.

Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of

inverter driven units, no inrush current at start up is experienced.

Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.

Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current

Maximum unit current for wires sizing is based on minimum allowed voltage

Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.

16/47

ELECTRICAL SPECIFICATIONS

Page 17: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-XS

DOL DOL DOL DOL DOL DOL Starting method

100 86 79 71 65 60 A Maximum running current

10% 10% 10% 10% 10% 10% % Voltage tollerance maximum

-10% -10% -10% -10% -10% -10% % Voltage tollerance minimum

400 400 400 400 400 400 V Voltage

3 3 3 3 3 3 No. Phases

COMPRESSORS

9 9 7 7 6 6 A Nominal running current cooling

FANS

120 105 95 86 78 72 A Maximum current for wires sizing

109 96 86 78 71 65 A Maximum running current

87 76 69 61 56 52 A Nominal running current cooling

362 324 315 268 261 210 A Maximum starting current

UNIT

10% 10% 10% 10% 10% 10% % Voltage tollerance maximum

-10% -10% -10% -10% -10% -10% % Voltage tollerance minimum

400 400 400 400 400 400 V Voltage

50 50 50 50 50 50 Hz Frequency

3 3 3 3 3 3 No. Phases

POWER SUPPLY

150 130 115 105 090 080 MODEL

Fluid: Water

Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.

Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of

inverter driven units, no inrush current at start up is experienced.

Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.

Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current

Maximum unit current for wires sizing is based on minimum allowed voltage

Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.

17/47

ELECTRICAL SPECIFICATIONS

Page 18: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-XR

DOL DOL DOL DOL DOL DOL Starting method

100 86 79 71 65 60 A Maximum running current

10% 10% 10% 10% 10% 10% % Voltage tollerance maximum

-10% -10% -10% -10% -10% -10% % Voltage tollerance minimum

400 400 400 400 400 400 V Voltage

3 3 3 3 3 3 No. Phases

COMPRESSORS

9 9 7 7 5 5 A Nominal running current cooling

FANS

120 104 94 86 78 71 A Maximum current for wires sizing

109 95 85 78 71 65 A Maximum running current

90 78 71 63 58 54 A Nominal running current cooling

362 324 314 267 260 209 A Maximum starting current

UNIT

10% 10% 10% 10% 10% 10% % Voltage tollerance maximum

-10% -10% -10% -10% -10% -10% % Voltage tollerance minimum

400 400 400 400 400 400 V Voltage

50 50 50 50 50 50 Hz Frequency

3 3 3 3 3 3 No. Phases

POWER SUPPLY

150 130 115 105 090 080 MODEL

Fluid: Water

Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.

Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of

inverter driven units, no inrush current at start up is experienced.

Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.

Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current

Maximum unit current for wires sizing is based on minimum allowed voltage

Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.

18/47

ELECTRICAL SPECIFICATIONS

Page 19: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-SS

89 71 49,0 56,0 62,0 66,0 70,0 68,0 71,0 80,0 155

89 71 49,0 56,0 62,0 66,0 70,0 68,0 71,0 80,0 140

89 71 49,0 56,0 63,0 67,0 70,0 69,0 71,0 80,0 120

89 71 49,0 56,0 62,0 66,0 70,0 69,0 71,0 80,0 110

87 69 47,0 54,0 61,0 65,0 68,0 67,0 69,0 78,0 100

85 68 46,0 53,0 59,0 63,0 67,0 65,0 68,0 77,0 085

83 66 44,0 51,0 57,0 61,0 65,0 63,0 66,0 75,0 075

db(A) 8000 Hz 4000 Hz 2000 Hz 1000 Hz 500 Hz 250 Hz

125 Hz 63 Hz

MODEL

Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)

Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are mesuared in accordance with ISO 9614 and Eurovent

8/1 for Eurovent certified units. The certification refers only to the overall sound power level, the sound pressure is calculated from the sound

power level and are for information only and not cosidered bounding

Power db(A)

19/47

SOUND LEVELS

Page 20: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-SR

86 68 42,0 51,0 59,0 63,0 67,0 64,0 65,0 73,0 155

86 68 42,0 51,0 59,0 63,0 67,0 64,0 65,0 73,0 140

86 68 43,0 51,0 59,0 63,0 67,0 65,0 65,0 74,0 120

86 68 42,0 51,0 59,0 63,0 67,0 65,0 65,0 73,0 110

84 66 41,0 49,0 58,0 61,0 65,0 63,0 63,0 72,0 100

82 65 39,0 48,0 56,0 60,0 64,0 61,0 62,0 70,0 085

79 62 37,0 45,0 53,0 57,0 61,0 59,0 59,0 68,0 075

db(A) 8000 Hz 4000 Hz 2000 Hz 1000 Hz 500 Hz 250 Hz

125 Hz 63 Hz

MODEL

Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)

Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are mesuared in accordance with ISO 9614 and Eurovent

8/1 for Eurovent certified units. The certification refers only to the overall sound power level, the sound pressure is calculated from the sound

power level and are for information only and not cosidered bounding

Power db(A)

20/47

SOUND LEVELS

Page 21: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-XS

71 71 48,0 55,0 62,0 66,0 69,0 68,0 70,0 80,0 150

89 71 48,0 55,0 62,0 66,0 69,0 68,0 70,0 80,0 130

89 71 49,0 55,0 62,0 66,0 69,0 68,0 71,0 80,0 115

87 69 47,0 54,0 60,0 64,0 68,0 67,0 69,0 78,0 105

85 68 45,0 52,0 59,0 63,0 66,0 65,0 67,0 77,0 090

84 66 44,0 50,0 57,0 61,0 64,0 63,0 66,0 75,0 080

db(A) 8000 Hz 4000 Hz 2000 Hz 1000 Hz 500 Hz 250 Hz

125 Hz 63 Hz

MODEL

Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)

Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are mesuared in accordance with ISO 9614 and Eurovent

8/1 for Eurovent certified units. The certification refers only to the overall sound power level, the sound pressure is calculated from the sound

power level and are for information only and not cosidered bounding

Power db(A)

21/47

SOUND LEVELS

Page 22: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-XR

86 67 42,0 51,0 59,0 63,0 66,0 64,0 65,0 73,0 150

86 67 42,0 51,0 59,0 63,0 66,0 64,0 65,0 73,0 130

86 68 42,0 51,0 59,0 63,0 66,0 64,0 65,0 73,0 115

84 66 41,0 49,0 57,0 61,0 65,0 63,0 63,0 72,0 105

82 65 39,0 48,0 56,0 60,0 63,0 61,0 62,0 70,0 090

80 62 37,0 45,0 53,0 57,0 61,0 59,0 59,0 68,0 080

db(A) 8000 Hz 4000 Hz 2000 Hz 1000 Hz 500 Hz 250 Hz

125 Hz 63 Hz

MODEL

Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)

Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are mesuared in accordance with ISO 9614 and Eurovent

8/1 for Eurovent certified units. The certification refers only to the overall sound power level, the sound pressure is calculated from the sound

power level and are for information only and not cosidered bounding

Power db(A)

22/47

SOUND LEVELS

Page 23: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

Operating Limits

EWAQ G SS (Standard efficiency, Standard Noise)

EWAQ G SR (standard efficiency, Reduced Noise)

Ref. A: Operation with glycol

Ref. B: operation with fan speed modulation (fan speed modulation provided as standard)

Ref. C: in this area the fan speed increase in order to ensure the functioning of the unit.

Note: The above graphic represents a guidelines about the operating limits of the range. Please refer to Chiller Selection

Software (CSS) for real operating limits working conditions for each size.

23/47

OPERATING LIMITS

Page 24: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ G XS (High efficiency, Standard Noise)

EWAQ G XR (High efficiency, Reduced Noise)

Ref. A: Operation with glycol

Ref. B: operation with fan speed modulation (fan speed modulation provided as standard)

Ref. C: in this area the fan speed increase in order to ensure the functioning of the unit.

Note: The above graphic represents a guidelines about the operating limits of the range. Please refer to Chiller Selection

Software (CSS) for real operating limits working conditions for each size.

24/47

OPERATING LIMITS

Page 25: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

Table 1 - Water heat exchanger - Minimum and maximum water deltaT

Legend: A = Max evaporator water deltaT

B = Min evaporator water deltaT

Table 2 - Water heat exchanger - Fouling factors

Legend: A = Fouling factors (m2 °C / kW)

B = Cooling capacity correction factor

C = Power input correction factor

D = EER correction factor

Table 3 - Air heat exchanger - Altitude correction factors

Legend: A = Elevation above sea level (m)

B = Barometric pressure (mbar)

C = Cooling capacity correction factor

D = Power input correction factor

- Maximum operating altitude is 2000 m above sea level

- Contact factory in case the unit has to be installed at altitudes between 1000 and 2000 m above sea level

Table 4 - Minimum glycol percentage for low air ambient temperature

Legend: AAT = Air Ambient Temperature (°C) (2)

A = Ethylene glycol (%) (1)

B = Propylene glycol (%) (1)

(1) Minimum glycol percentage to prevent freezing of water circuit at indicated air ambient temperature

(2) Air ambient temperature do exceed the operating limits of the unit, a protection of water circuit may be needed in winter

season at non - working conditions.

25/47

OPERATING LIMITS

Page 26: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

Water content in cooling circuits The cooled water distribution circuits should have minimum water content to

avoid excessive compressors start and stop. In fact, each time the compressor starts up, an excessive quantity of oil goes

from the compressor sump and simultaneously there is a rise in the temperature of the compressor motor’s stator due to the

inrush current during the start - up. To prevent damage to the compressors, have been envisaged the application of a device

to limit frequent stops and restarts.

During the span of one hour there will be no more than 6 starts of the compressor. The plant side should therefore ensure

that the overall water content allows a more constant functioning of the unit and consequently greater environmental

comfort. The minimum water content per unit should be calculated with a certain approximation using this simplified formula:

For 2 compressors unit

M (liters) = (12.153 x DT(°C) - 22.168) x P(kW)

26/47

OPERATING LIMITS

Page 27: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-SS

15.3 16.9 40.7 47.1 54.4 62.4 15.0 43.9 47.9 55.6 64.2 73.4 kPa dpw

3.6 3.7 5.8 6.2 6.7 7.2 3.0 5.1 5.3 5.7 6.1 6.5 l/s qw

25.9 24.6 46.4 42.6 39.3 36.4 21.1 43.6 41.2 37.7 34.8 32.3 kW Pa

74.1 77.8 121 130 139 149 61.5 105 110 118 127 136 kW Pf 15

13.7 15.1 36.8 42.8 49.6 57.0 13.3 39.6 43.3 50.4 58.3 66.9 kPa dpw

3.4 3.5 5.5 6.0 6.4 6.9 2.8 4.8 5.0 5.4 5.8 6.2 l/s qw

25.6 24.4 45.6 41.8 38.5 35.6 20.8 42.8 40.4 37.0 34.1 31.6 kW Pa

70.1 73.7 115 124 133 143 58.1 99.9 104 113 121 130 kW Pf 13

12.2 30.3 33.2 38.8 45.1 51.9 11.8 35.5 39.0 45.5 52.9 60.8 kPa dpw

3.2 5.0 5.2 5.7 6.1 6.6 2.6 4.6 4.8 5.2 5.6 5.9 l/s qw

25.3 47.4 44.8 41.0 37.7 34.9 20.6 42.1 39.7 36.3 33.4 31.0 kW Pa

66.2 104 109 118 127 136 54.8 94.8 99.2 107 115 124 kW Pf 11

10.8 27.2 29.9 35.1 40.9 47.2 29.1 31.8 35.0 41.0 47.8 55.0 kPa dpw

3.0 4.7 5.0 5.4 5.8 6.2 4.1 4.3 4.5 4.9 5.3 5.7 l/s qw

25.0 46.5 44.0 40.3 37.0 34.3 44.0 41.3 39.0 35.6 32.8 30.4 kW Pa

62.5 99.0 104 112 121 130 85.8 89.8 94.1 102 110 118 kW Pf 9

9.60 24.4 26.8 31.6 37.0 42.7 25.9 28.4 31.3 36.9 43.1 49.7 kPa dpw

2.8 4.5 4.7 5.1 5.5 5.9 3.9 4.1 4.3 4.6 5.0 5.4 l/s qw

24.8 45.8 43.2 39.5 36.4 33.6 43.3 40.7 38.3 35.0 32.2 29.8 kW Pa

58.9 93.7 98.4 107 115 124 81.0 84.9 89.2 96.7 104 112 kW Pf 7

8.50 21.7 24.0 28.4 33.3 38.6 22.9 25.3 28.0 33.0 38.7 44.7 kPa dpw

2.6 4.2 4.5 4.8 5.2 5.6 3.7 3.8 4.0 4.4 4.7 5.1 l/s qw

24.5 45.0 42.5 38.9 35.7 33.0 42.6 40.0 37.7 34.4 31.6 29.3 kW Pa

55.4 88.7 93.2 101 110 118 76.4 80.2 84.3 91.6 99.1 107 kW Pf 5

46 43 40 35 30 25 46 43 40 35 30 25 Tain Twout

110 100

13.6 15.0 35.0 40.7 47.2 54.3 6.20 6.80 19.6 22.9 26.7 30.8 kPa dpw

2.8 3.0 4.6 4.9 5.3 5.7 2.3 2.4 4.0 4.4 4.7 5.0 l/s qw

20.9 19.8 36.9 33.8 31.1 28.8 16.0 15.3 32.3 29.8 27.6 25.6 kW Pa

59.3 62.2 95.0 102 110 118 47.1 49.6 83.8 90.7 97.8 105 kW Pf 15

12.2 13.4 31.7 37.0 43.0 49.5 5.50 6.10 17.8 20.9 24.3 28.1 kPa dpw

2.7 2.8 4.3 4.7 5.1 5.4 2.1 2.2 3.8 4.2 4.5 4.8 l/s qw

20.6 19.5 36.2 33.1 30.5 28.2 15.8 15.1 31.8 29.2 27.0 25.1 kW Pa

56.1 58.9 90.4 97.7 105 113 44.5 46.9 79.8 86.5 93.4 100 kW Pf 13

10.8 26.1 28.6 33.5 39.1 45.1 4.90 14.5 16.1 18.9 22.1 25.6 kPa dpw

2.5 3.9 4.1 4.5 4.8 5.2 2.0 3.5 3.6 4.0 4.3 4.6 l/s qw

20.3 37.6 35.5 32.4 29.8 27.6 15.7 32.9 31.2 28.7 26.5 24.6 kW Pa

52.9 82.1 86.0 93.1 100 108 42.0 72.3 76.0 82.5 89.2 95.9 kW Pf 11

9.60 23.4 25.8 30.3 35.4 41.0 4.40 13.1 14.5 17.1 20.1 23.3 kPa dpw

2.4 3.7 3.9 4.2 4.6 4.9 1.9 3.3 3.5 3.8 4.1 4.4 l/s qw

20.0 36.9 34.8 31.8 29.2 27.0 15.5 32.4 30.7 28.2 26.0 24.1 kW Pa

49.9 77.8 81.7 88.6 95.7 103 39.6 68.6 72.2 78.5 85.0 91.5 kW Pf 9

8.50 20.9 23.1 27.3 32.0 37.1 3.90 11.7 13.0 15.5 18.2 21.1 kPa dpw

2.2 3.5 3.7 4.0 4.4 4.7 1.8 3.1 3.3 3.6 3.9 4.2 l/s qw

19.8 36.3 34.2 31.2 28.7 26.5 15.3 31.9 30.2 27.7 25.5 23.6 kW Pa

47.0 73.7 77.5 84.2 91.1 98.0 37.4 65.0 68.6 74.7 81.0 87.2 kW Pf 7

7.50 18.7 20.7 24.5 28.9 33.5 3.40 10.5 11.7 13.9 16.4 19.1 kPa dpw

2.1 3.3 3.5 3.8 4.1 4.5 1.7 2.9 3.1 3.4 3.7 4.0 l/s qw

19.5 35.6 33.6 30.6 28.1 26.0 15.2 31.4 29.7 27.2 25.1 23.2 kW Pa

44.1 69.7 73.4 79.9 86.6 93.3 35.2 61.5 65.0 71.0 77.0 83.0 kW Pf 5

46 43 40 35 30 25 46 43 40 35 30 25 Tain Twout

085 075

27/47

PERFORMANCE IN COOLING MODE

Page 28: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-SS

10.7 11.8 32.9 38.3 44.4 51.1 kPa dpw

4.8 5.0 8.4 9.0 9.7 10 l/s qw

33.3 31.6 67.8 62.1 57.2 53.0 kW Pa

99.2 104 174 188 202 217 kW Pf 15

9.50 10.6 29.8 34.8 40.5 46.7 kPa dpw

4.5 4.7 8.0 8.6 9.3 10 l/s qw

32.8 31.2 66.3 60.8 56.0 51.8 kW Pa

93.8 98.8 166 179 193 207 kW Pf 13

8.50 9.40 27.0 31.6 36.8 42.6 kPa dpw

4.2 4.5 7.6 8.2 8.8 9.5 l/s qw

32.4 30.8 65.0 59.5 54.8 50.7 kW Pa

88.6 93.4 158 171 184 198 kW Pf 11

7.50 8.40 24.3 28.6 33.4 38.7 kPa dpw

4.0 4.2 7.2 7.8 8.4 9.1 l/s qw

32.0 30.4 63.8 58.3 53.7 49.6 kW Pa

83.5 88.1 150 162 176 189 kW Pf 9

6.70 19.8 21.8 25.8 30.2 35.1 kPa dpw

3.8 6.5 6.8 7.4 8.0 8.6 l/s qw

31.6 66.3 62.6 57.2 52.6 48.6 kW Pa

78.6 136 142 154 167 180 kW Pf 7

5.90 17.7 19.5 23.2 27.3 31.7 kPa dpw

3.5 6.1 6.4 7.0 7.6 8.2 l/s qw

31.3 65.2 61.5 56.2 51.6 47.6 kW Pa

73.9 128 135 147 159 172 kW Pf 5

46 43 40 35 30 25 Tain Twout

155

13.3 14.8 35.4 41.2 47.7 54.8 15.3 16.9 46.0 53.2 61.4 70.5 kPa dpw

4.6 4.9 7.6 8.2 8.8 9.4 3.7 3.8 6.3 6.8 7.3 7.8 l/s qw

34.2 32.5 59.8 55.0 50.8 47.1 25.0 23.8 50.8 46.7 43.1 39.9 kW Pa

96.9 102 158 170 183 196 76.0 79.9 132 142 152 163 kW Pf 15

11.9 29.2 32.0 37.4 43.5 50.0 13.7 15.1 41.7 48.4 56.1 64.5 kPa dpw

4.4 6.9 7.2 7.8 8.4 9.0 3.5 3.6 6.0 6.5 7.0 7.5 l/s qw

33.8 62.0 58.7 53.9 49.8 46.1 24.7 23.5 49.9 45.8 42.2 39.1 kW Pa

91.6 143 150 162 175 187 72.0 75.7 125 135 145 156 kW Pf 13

10.6 26.3 28.9 33.9 39.5 45.5 12.2 13.5 37.7 44.0 51.1 59.0 kPa dpw

4.1 6.5 6.8 7.4 8.0 8.6 3.3 3.4 5.7 6.2 6.7 7.2 l/s qw

33.3 60.9 57.7 52.9 48.8 45.2 24.4 23.2 49.0 44.9 41.4 38.4 kW Pa

86.6 136 143 154 167 179 68.0 71.6 119 129 139 149 kW Pf 11

9.40 23.6 26.0 30.6 35.7 41.3 10.8 12.0 34.0 39.8 46.5 53.7 kPa dpw

3.9 6.2 6.5 7.0 7.6 8.2 3.1 3.2 5.4 5.9 6.4 6.8 l/s qw

32.9 59.9 56.7 52.0 47.9 44.3 24.1 23.0 48.1 44.1 40.7 37.6 kW Pa

81.7 129 135 147 159 170 64.2 67.6 114 123 133 143 kW Pf 9

8.30 21.1 23.3 27.5 32.3 37.4 9.60 27.8 30.6 36.0 42.1 48.8 kPa dpw

3.7 5.8 6.1 6.7 7.2 7.8 2.9 4.9 5.2 5.6 6.1 6.5 l/s qw

32.5 58.9 55.8 51.1 47.1 43.5 23.9 50.0 47.3 43.4 39.9 36.9 kW Pa

76.9 122 128 139 151 162 60.5 103 108 117 126 136 kW Pf 7

17.0 18.8 20.9 24.7 29.1 33.7 8.50 24.9 27.5 32.4 38.1 44.2 kPa dpw

5.3 5.5 5.8 6.3 6.9 7.4 2.7 4.7 4.9 5.3 5.8 6.2 l/s qw

61.5 58.0 54.9 50.3 46.3 42.7 23.6 49.2 46.5 42.6 39.2 36.2 kW Pa

110 115 122 132 143 154 56.9 97.4 102 111 120 130 kW Pf 5

46 43 40 35 30 25 46 43 40 35 30 25 Tain Twout

140 120

28/47

PERFORMANCE IN COOLING MODE

Page 29: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-SR

13.9 15.3 16.9 40.8 47.0 54.1 13.8 15.3 16.8 48.7 56.3 64.6 kPa dpw

3.4 3.6 3.7 5.8 6.2 6.7 2.8 3.0 3.1 5.3 5.7 6.1 l/s qw

26.5 25.2 24.0 45.7 42.0 38.8 21.3 20.2 19.2 40.1 36.8 34.0 kW Pa

70.7 74.2 77.8 121 130 139 59.2 62.1 65.2 111 119 127 kW Pf 15

12.5 13.8 15.2 37.1 43.0 49.6 12.4 13.6 38.2 44.3 51.3 59.1 kPa dpw

3.2 3.4 3.5 5.5 6.0 6.4 2.7 2.8 4.7 5.1 5.5 5.9 l/s qw

26.2 24.9 23.7 44.7 41.0 37.9 21.0 19.9 43.2 39.2 36.0 33.2 kW Pa

67.0 70.3 73.9 115 124 133 55.9 58.8 98.2 106 114 122 kW Pf 13

11.1 12.3 13.6 33.7 39.2 45.3 11.0 12.2 34.5 40.1 46.6 53.8 kPa dpw

3.0 3.2 3.4 5.3 5.7 6.1 2.5 2.7 4.5 4.8 5.2 5.6 l/s qw

25.8 24.5 23.3 43.8 40.1 37.0 20.7 19.6 42.3 38.4 35.2 32.5 kW Pa

63.4 66.6 70.0 110 119 127 52.8 55.5 93.4 101 108 116 kW Pf 11

9.90 11.0 26.2 30.5 35.6 41.3 9.70 10.8 31.0 36.2 42.3 48.9 kPa dpw

2.9 3.0 4.7 5.0 5.4 5.8 2.4 2.5 4.3 4.6 5.0 5.3 l/s qw

25.5 24.2 47.1 42.8 39.3 36.2 20.5 19.4 41.4 37.6 34.4 31.7 kW Pa

59.8 63.0 97.1 105 113 122 49.8 52.4 88.6 95.8 103 111 kW Pf 9

8.80 9.80 23.5 27.6 32.3 37.6 8.60 25.4 27.8 32.6 38.2 44.3 kPa dpw

2.7 2.8 4.4 4.8 5.2 5.6 2.2 3.8 4.0 4.4 4.7 5.1 l/s qw

25.2 23.9 46.1 42.0 38.4 35.4 20.2 43.2 40.6 36.8 33.7 31.1 kW Pa

56.4 59.5 92.2 99.7 108 116 46.8 80.3 84.0 91.0 98.4 106 kW Pf 7

7.80 8.70 21.1 24.8 29.2 34.1 7.60 22.6 24.9 29.3 34.4 40.1 kPa dpw

2.5 2.7 4.2 4.5 4.9 5.3 2.1 3.6 3.8 4.1 4.5 4.8 l/s qw

24.9 23.6 45.2 41.1 37.6 34.7 20.0 42.4 39.8 36.1 33.0 30.4 kW Pa

53.2 56.1 87.3 94.7 103 111 44.0 75.9 79.5 86.3 93.5 101 kW Pf 5

46 43 40 35 30 25 46 43 40 35 30 25 Tain Twout

110 100

12.5 13.7 15.1 35.4 41.0 47.3 5.60 6.20 6.90 19.5 22.7 26.3 kPa dpw

2.7 2.9 3.0 4.6 4.9 5.3 2.2 2.3 2.4 4.0 4.3 4.7 l/s qw

21.6 20.4 19.3 36.2 33.2 30.7 16.3 15.5 14.8 32.0 29.5 27.3 kW Pa

56.8 59.5 62.4 95.5 103 110 44.9 47.3 49.7 83.7 90.3 97.1 kW Pf 15

11.2 12.3 13.5 32.3 37.5 43.3 5.00 5.60 6.20 17.8 20.8 24.1 kPa dpw

2.6 2.7 2.8 4.4 4.7 5.1 2.0 2.1 2.3 3.8 4.1 4.5 l/s qw

21.2 20.0 19.0 35.4 32.4 29.9 16.1 15.3 14.6 31.3 28.8 26.7 kW Pa

53.8 56.4 59.2 91.2 98.3 106 42.5 44.8 47.2 80.0 86.4 93.0 kW Pf 13

10.0 11.0 12.1 29.3 34.2 39.6 4.50 5.00 5.50 16.2 19.0 22.1 kPa dpw

2.4 2.6 2.7 4.2 4.5 4.9 1.9 2.0 2.1 3.7 4.0 4.3 l/s qw

20.9 19.7 18.6 34.6 31.7 29.2 15.9 15.1 14.4 30.6 28.2 26.1 kW Pa

50.8 53.3 56.0 87.0 93.9 101 40.2 42.4 44.7 76.3 82.6 89.1 kW Pf 11

8.80 9.80 10.8 26.5 31.1 36.1 4.00 4.50 5.00 14.7 17.3 20.2 kPa dpw

2.3 2.4 2.5 4.0 4.3 4.6 1.8 1.9 2.0 3.5 3.8 4.1 l/s qw

20.6 19.4 18.3 33.8 31.0 28.5 15.7 14.9 14.2 30.0 27.6 25.5 kW Pa

47.9 50.4 53.0 82.9 89.6 96.6 38.0 40.1 42.3 72.8 78.9 85.2 kW Pf 9

7.80 8.70 20.4 24.0 28.2 32.8 3.50 4.00 11.2 13.3 15.7 18.4 kPa dpw

2.2 2.3 3.5 3.8 4.1 4.4 1.7 1.8 3.0 3.3 3.6 3.9 l/s qw

20.2 19.1 36.5 33.1 30.3 27.9 15.5 14.7 32.2 29.4 27.0 25.0 kW Pa

45.1 47.5 72.7 78.9 85.4 92.2 35.8 37.9 63.6 69.3 75.3 81.4 kW Pf 7

6.90 7.70 18.2 21.6 25.5 29.7 3.10 3.50 10.1 12.0 14.2 16.7 kPa dpw

2.0 2.1 3.3 3.6 3.9 4.2 1.6 1.7 2.9 3.2 3.4 3.7 l/s qw

20.0 18.8 35.7 32.4 29.6 27.3 15.4 14.6 31.6 28.8 26.5 24.4 kW Pa

42.5 44.7 68.9 74.9 81.3 87.9 33.7 35.7 60.3 65.9 71.8 77.7 kW Pf 5

46 43 40 35 30 25 46 43 40 35 30 25 Tain Twout

085 075

29/47

PERFORMANCE IN COOLING MODE

Page 30: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-SR

9.70 10.7 11.8 32.6 37.8 43.6 kPa dpw

4.5 4.8 5.0 8.3 9.0 9.6 l/s qw

34.1 32.4 30.8 67.3 61.7 56.9 kW Pa

94.6 99.4 104 173 186 200 kW Pf 15

8.70 9.60 10.6 29.8 34.6 40.0 kPa dpw

4.3 4.5 4.7 7.9 8.6 9.2 l/s qw

33.5 31.8 30.2 65.6 60.2 55.5 kW Pa

89.6 94.2 99.1 166 178 192 kW Pf 13

7.80 8.60 9.50 27.1 31.5 36.6 kPa dpw

4.1 4.3 4.5 7.6 8.2 8.8 l/s qw

33.0 31.3 29.8 64.0 58.7 54.1 kW Pa

84.7 89.2 93.9 158 171 184 kW Pf 11

6.90 7.70 8.50 24.5 28.7 33.4 kPa dpw

3.8 4.0 4.2 7.2 7.8 8.4 l/s qw

32.6 30.9 29.3 62.6 57.3 52.8 kW Pa

80.0 84.3 88.8 151 163 176 kW Pf 9

6.10 6.80 7.60 22.2 26.1 30.4 kPa dpw

3.6 3.8 4.0 6.9 7.4 8.0 l/s qw

32.1 30.4 28.9 61.2 56.0 51.6 kW Pa

75.4 79.5 83.9 143 155 168 kW Pf 7

5.40 6.00 17.0 20.0 23.6 27.6 kPa dpw

3.4 3.6 6.0 6.5 7.1 7.7 l/s qw

31.7 30.0 66.0 59.9 54.8 50.4 kW Pa

71.0 75.0 126 136 148 160 kW Pf 5

46 43 40 35 30 25 Tain Twout

155

12.2 13.4 14.8 35.6 41.3 47.6 13.9 15.3 16.9 19.7 52.5 60.3 kPa dpw

4.4 4.7 4.9 7.6 8.2 8.8 3.5 3.7 3.8 4.1 6.8 7.3 l/s qw

35.1 33.3 31.6 58.7 54.1 50.0 25.6 24.3 23.1 21.4 46.4 42.9 kW Pa

92.5 97.2 102 158 170 183 72.6 76.2 79.9 86.4 141 151 kW Pf 15

10.9 12.0 13.3 32.4 37.7 43.6 12.5 13.8 15.2 41.5 48.0 55.4 kPa dpw

4.2 4.4 4.6 7.2 7.8 8.4 3.3 3.5 3.6 6.0 6.5 7.0 l/s qw

34.5 32.7 31.1 57.4 52.8 48.9 25.2 24.0 22.8 49.3 45.4 41.9 kW Pa

87.6 92.1 96.8 151 163 175 68.8 72.2 75.9 125 135 145 kW Pf 13

9.70 10.8 25.2 29.4 34.3 39.8 11.1 12.3 13.6 37.8 43.9 50.8 kPa dpw

4.0 4.2 6.4 6.9 7.5 8.0 3.1 3.3 3.4 5.7 6.2 6.7 l/s qw

34.0 32.2 61.5 56.2 51.7 47.8 24.9 23.6 22.5 48.3 44.4 41.0 kW Pa

82.8 87.2 133 144 155 167 65.1 68.4 71.9 120 129 139 kW Pf 11

8.70 9.60 22.8 26.7 31.2 36.3 9.90 11.0 12.2 34.3 40.0 46.5 kPa dpw

3.7 3.9 6.1 6.6 7.1 7.7 2.9 3.1 3.3 5.5 5.9 6.4 l/s qw

33.5 31.8 60.3 55.1 50.6 46.7 24.6 23.3 22.2 47.3 43.4 40.0 kW Pa

78.2 82.4 127 137 148 160 61.4 64.7 68.1 114 123 133 kW Pf 9

7.70 8.50 20.5 24.1 28.3 32.9 8.80 9.80 10.9 31.1 36.4 42.4 kPa dpw

3.5 3.7 5.8 6.2 6.8 7.3 2.8 2.9 3.1 5.2 5.6 6.1 l/s qw

33.1 31.3 59.1 54.0 49.6 45.7 24.3 23.0 21.9 46.3 42.5 39.2 kW Pa

73.8 77.8 120 130 141 152 58.0 61.1 64.4 109 118 127 kW Pf 7

6.80 7.60 18.3 21.7 25.5 29.8 7.80 8.70 23.9 28.0 33.0 38.5 kPa dpw

3.3 3.5 5.4 5.9 6.4 6.9 2.6 2.8 4.6 4.9 5.4 5.8 l/s qw

32.7 30.9 58.0 53.0 48.6 44.8 24.0 22.7 49.7 45.4 41.6 38.3 kW Pa

69.4 73.3 114 124 134 145 54.6 57.6 95.5 103 112 121 kW Pf 5

46 43 40 35 30 25 46 43 40 35 30 25 Tain Twout

140 120

30/47

PERFORMANCE IN COOLING MODE

Page 31: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-XS

21.5 23.6 26.0 30.3 35.0 40.1 22.3 24.4 26.8 31.3 36.1 41.2 kPa dpw

5.8 6.1 6.4 6.9 7.4 7.9 5.3 5.5 5.8 6.3 6.7 7.2 l/s qw

48.5 46.0 43.6 40.2 37.2 34.6 43.6 41.2 39.1 36.0 33.3 31.1 kW Pa

121 127 133 144 155 165 110 115 121 130 140 149 kW Pf 15

19.3 21.2 23.4 27.4 31.7 36.4 19.9 21.9 24.1 28.2 32.7 37.3 kPa dpw

5.5 5.8 6.1 6.6 7.1 7.6 5.0 5.2 5.5 5.9 6.4 6.8 l/s qw

47.8 45.2 42.9 39.5 36.6 34.0 43.0 40.6 38.5 35.4 32.8 30.5 kW Pa

115 120 126 137 147 158 104 109 114 124 133 142 kW Pf 13

17.3 19.0 21.0 24.7 28.7 32.9 17.8 19.6 21.6 25.3 29.4 33.7 kPa dpw

5.2 5.5 5.7 6.2 6.7 7.2 4.7 5.0 5.2 5.6 6.1 6.5 l/s qw

47.1 44.6 42.3 38.9 36.0 33.4 42.3 40.0 37.9 34.8 32.2 30.0 kW Pa

109 114 120 130 140 150 98.4 103 108 117 126 135 kW Pf 11

15.4 17.0 18.8 22.2 25.8 29.7 15.8 17.5 19.3 22.7 26.5 30.4 kPa dpw

4.9 5.2 5.4 5.9 6.4 6.8 4.4 4.7 4.9 5.3 5.8 6.2 l/s qw

46.4 43.9 41.6 38.3 35.4 32.8 41.7 39.4 37.3 34.3 31.7 29.5 kW Pa

103 108 114 123 133 143 92.9 97.6 103 111 120 129 kW Pf 9

13.7 15.1 16.8 19.9 23.2 26.7 14.0 15.5 17.2 20.3 23.7 27.2 kPa dpw

4.6 4.9 5.1 5.6 6.0 6.5 4.2 4.4 4.6 5.0 5.4 5.8 l/s qw

45.8 43.3 41.0 37.7 34.8 32.3 41.2 38.9 36.8 33.8 31.2 29.0 kW Pa

97.0 102 107 117 126 135 87.6 92.1 97.0 105 114 122 kW Pf 7

12.1 13.4 14.9 17.7 20.8 24.0 12.4 13.8 15.3 18.1 21.2 24.4 kPa dpw

4.4 4.6 4.8 5.3 5.7 6.1 3.9 4.1 4.4 4.8 5.1 5.5 l/s qw

45.2 42.7 40.5 37.1 34.3 31.7 40.6 38.3 36.3 33.3 30.7 28.5 kW Pa

91.3 96.2 101 110 120 128 82.4 86.8 91.5 99.5 108 115 kW Pf 5

46 43 40 35 30 25 46 43 40 35 30 25 Tain Twout

115 105

35.3 38.7 42.6 49.6 57.2 65.2 27.4 30.2 33.3 39.0 45.1 51.4 kPa dpw

4.5 4.7 4.9 5.3 5.7 6.1 3.9 4.1 4.4 4.7 5.1 5.4 l/s qw

37.4 35.4 33.6 31.0 28.7 26.7 32.6 31.0 29.5 27.3 25.4 23.6 kW Pa

93.5 98.0 103 111 119 127 82.0 86.2 90.5 97.8 105 112 kW Pf 15

31.7 34.9 38.4 44.8 51.9 59.2 24.6 27.2 30.1 35.3 40.8 46.6 kPa dpw

4.3 4.5 4.7 5.1 5.5 5.8 3.7 3.9 4.1 4.5 4.8 5.1 l/s qw

36.8 34.9 33.1 30.5 28.2 26.2 32.1 30.5 29.1 26.9 25.0 23.2 kW Pa

88.7 93.0 97.6 105 113 121 77.8 81.9 86.0 93.1 100 107 kW Pf 13

28.4 31.3 34.5 40.4 46.9 53.6 22.1 24.5 27.1 31.8 36.9 42.2 kPa dpw

4.0 4.2 4.4 4.8 5.2 5.5 3.5 3.7 3.9 4.3 4.6 4.9 l/s qw

36.3 34.3 32.6 30.0 27.7 25.8 31.7 30.1 28.7 26.5 24.6 22.8 kW Pa

84.0 88.2 92.6 100 108 115 73.8 77.7 81.7 88.5 95.3 102 kW Pf 11

25.3 28.0 31.0 36.4 42.3 48.4 19.7 21.9 24.3 28.7 33.3 38.1 kPa dpw

3.8 4.0 4.2 4.6 4.9 5.3 3.3 3.5 3.7 4.0 4.3 4.6 l/s qw

35.8 33.9 32.1 29.5 27.3 25.3 31.4 29.8 28.3 26.1 24.2 22.5 kW Pa

79.5 83.5 87.8 95.2 103 110 69.8 73.6 77.5 84.1 90.6 96.9 kW Pf 9

22.5 25.0 27.7 32.7 38.0 43.6 17.6 19.6 21.8 25.7 30.0 34.2 kPa dpw

3.6 3.8 4.0 4.3 4.7 5.0 3.2 3.3 3.5 3.8 4.1 4.4 l/s qw

35.3 33.4 31.6 29.0 26.8 24.9 31.0 29.4 27.9 25.8 23.8 22.1 kW Pa

75.0 79.0 83.1 90.3 97.4 104 66.0 69.7 73.4 79.8 86.1 92.0 kW Pf 7

20.0 22.2 24.7 29.2 34.1 39.1 15.6 17.5 19.5 23.1 26.9 30.7 kPa dpw

3.4 3.6 3.8 4.1 4.4 4.7 3.0 3.1 3.3 3.6 3.9 4.2 l/s qw

34.9 32.9 31.2 28.6 26.4 24.5 30.6 29.0 27.6 25.4 23.5 21.8 kW Pa

70.7 74.6 78.6 85.5 92.3 98.8 62.3 65.8 69.5 75.6 81.6 87.3 kW Pf 5

46 43 40 35 30 25 46 43 40 35 30 25 Tain Twout

090 080

31/47

PERFORMANCE IN COOLING MODE

Page 32: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-XS

22.2 24.4 26.8 31.3 36.3 41.5 27.4 30.2 33.2 38.7 44.6 50.8 kPa dpw

7.4 7.8 8.1 8.8 9.5 10 6.5 6.8 7.2 7.7 8.3 8.9 l/s qw

61.7 58.6 55.7 51.3 47.5 44.2 53.5 50.8 48.4 44.7 41.5 38.6 kW Pa

154 162 169 183 197 211 136 142 149 161 173 185 kW Pf 15

19.9 21.9 24.1 28.3 32.9 37.7 24.6 27.1 29.9 34.9 40.4 46.1 kPa dpw

7.0 7.4 7.7 8.4 9.0 9.7 6.2 6.5 6.8 7.4 7.9 8.5 l/s qw

60.8 57.6 54.8 50.5 46.7 43.4 52.8 50.1 47.7 44.0 40.8 38.0 kW Pa

146 153 161 174 188 201 129 135 142 153 165 176 kW Pf 13

17.8 19.7 21.7 25.5 29.7 34.2 22.0 24.3 26.8 31.5 36.5 41.7 kPa dpw

6.6 7.0 7.3 7.9 8.6 9.2 5.8 6.1 6.5 7.0 7.5 8.0 l/s qw

59.9 56.8 53.9 49.6 45.9 42.6 52.1 49.5 47.1 43.4 40.2 37.4 kW Pa

138 145 153 166 179 191 122 128 135 146 157 167 kW Pf 11

15.9 17.6 19.5 23.0 26.8 30.8 19.6 21.7 24.0 28.3 32.9 37.6 kPa dpw

6.3 6.6 6.9 7.5 8.1 8.7 5.5 5.8 6.1 6.6 7.1 7.6 l/s qw

59.1 55.9 53.1 48.8 45.1 41.8 51.5 48.9 46.5 42.8 39.6 36.8 kW Pa

131 138 145 157 170 182 115 121 127 138 149 159 kW Pf 9

14.1 15.7 17.4 20.6 24.1 27.8 17.4 19.4 21.5 25.4 29.6 33.8 kPa dpw

5.9 6.2 6.6 7.1 7.7 8.3 5.2 5.5 5.8 6.3 6.8 7.2 l/s qw

58.3 55.2 52.3 48.1 44.4 41.1 50.9 48.3 45.9 42.3 39.1 36.2 kW Pa

124 130 137 149 161 173 109 114 121 131 141 151 kW Pf 7

12.5 13.9 15.5 18.4 21.6 24.9 15.4 17.2 19.1 22.7 26.5 30.3 kPa dpw

5.6 5.9 6.2 6.7 7.3 7.8 4.9 5.2 5.4 5.9 6.4 6.9 l/s qw

57.5 54.4 51.6 47.4 43.7 40.4 50.3 47.7 45.3 41.7 38.5 35.7 kW Pa

116 123 129 141 153 164 102 108 114 124 134 143 kW Pf 5

46 43 40 35 30 25 46 43 40 35 30 25 Tain Twout

150 130

32/47

PERFORMANCE IN COOLING MODE

Page 33: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-XR

8.30 9.20 23.0 26.8 31.1 35.8 7.20 22.0 24.1 28.0 32.5 37.2 kPa dpw

3.6 3.8 6.0 6.5 7.0 7.5 3.0 5.2 5.5 5.9 6.4 6.8 l/s qw

25.6 24.4 45.8 42.0 38.8 36.0 20.9 43.1 40.7 37.3 34.4 32.0 kW Pa

75.5 79.4 125 135 146 156 62.7 109 114 123 133 142 kW Pf 15

7.40 19.0 20.8 24.3 28.3 32.6 6.40 19.8 21.7 25.3 29.4 33.8 kPa dpw

3.4 5.5 5.7 6.2 6.7 7.2 2.8 5.0 5.2 5.6 6.1 6.5 l/s qw

25.3 47.5 44.9 41.2 38.0 35.2 20.7 42.3 40.0 36.6 33.8 31.3 kW Pa

71.3 114 119 129 139 149 59.2 103 109 117 126 135 kW Pf 13

6.60 17.0 18.7 21.9 25.6 29.6 16.2 17.7 19.5 22.9 26.6 30.7 kPa dpw

3.2 5.2 5.4 5.9 6.3 6.8 4.5 4.7 4.9 5.3 5.8 6.2 l/s qw

25.0 46.6 44.1 40.5 37.3 34.5 44.2 41.6 39.3 35.9 33.1 30.7 kW Pa

67.3 108 113 123 132 142 93.8 98.3 103 112 120 129 kW Pf 11

5.90 15.2 16.8 19.8 23.1 26.8 14.4 15.8 17.5 20.6 24.0 27.7 kPa dpw

3.0 4.9 5.1 5.6 6.0 6.5 4.2 4.5 4.7 5.1 5.5 5.9 l/s qw

24.8 45.9 43.4 39.7 36.6 33.9 43.4 40.9 38.6 35.3 32.5 30.1 kW Pa

63.4 102 107 116 126 135 88.7 93.0 97.6 106 114 123 kW Pf 9

5.20 13.6 15.0 17.8 20.9 24.2 12.8 14.1 15.6 18.4 21.6 25.0 kPa dpw

2.9 4.6 4.9 5.3 5.7 6.2 4.0 4.2 4.4 4.8 5.2 5.6 l/s qw

24.5 45.1 42.6 39.0 35.9 33.2 42.7 40.2 37.9 34.7 31.9 29.5 kW Pa

59.7 96.7 102 110 120 129 83.7 87.8 92.3 100 109 117 kW Pf 7

11.0 12.1 13.4 15.9 18.7 21.8 11.3 12.5 13.9 16.5 19.3 22.4 kPa dpw

4.2 4.4 4.6 5.0 5.4 5.9 3.8 4.0 4.2 4.5 4.9 5.3 l/s qw

47.1 44.4 41.9 38.4 35.3 32.6 42.1 39.6 37.3 34.1 31.3 29.0 kW Pa

86.9 91.3 96.1 105 114 122 78.8 82.8 87.2 94.9 103 111 kW Pf 5

46 43 40 35 30 25 46 43 40 35 30 25 Tain Twout

115 105

14.4 34.9 38.2 44.5 51.5 59.1 9.00 27.0 29.8 34.9 40.5 46.4 kPa dpw

2.9 4.5 4.7 5.1 5.4 5.8 2.3 3.9 4.1 4.5 4.8 5.1 l/s qw

20.3 37.0 35.0 32.2 29.7 27.6 15.7 32.1 30.6 28.2 26.2 24.3 kW Pa

59.8 93.0 97.3 105 113 121 47.1 81.5 85.6 92.5 99.7 107 kW Pf 15

12.8 31.4 34.6 40.4 46.8 53.8 8.00 24.4 26.9 31.6 36.8 42.3 kPa dpw

2.7 4.2 4.5 4.8 5.2 5.6 2.1 3.7 3.9 4.2 4.6 4.9 l/s qw

20.1 36.3 34.4 31.5 29.1 27.0 15.5 31.7 30.1 27.7 25.7 23.9 kW Pa

56.5 88.4 92.6 100 108 115 44.5 77.5 81.4 88.2 95.1 102 kW Pf 13

11.4 28.3 31.2 36.5 42.5 48.9 19.8 22.0 24.3 28.6 33.4 38.4 kPa dpw

2.6 4.0 4.2 4.6 4.9 5.3 3.4 3.5 3.7 4.0 4.4 4.7 l/s qw

19.8 35.7 33.8 31.0 28.6 26.5 32.9 31.2 29.6 27.3 25.3 23.4 kW Pa

53.3 83.9 88.0 95.3 103 110 70.0 73.6 77.4 84.0 90.7 97.2 kW Pf 11

23.0 25.4 28.0 32.9 38.4 44.3 17.8 19.7 21.9 25.9 30.2 34.8 kPa dpw

3.6 3.8 4.0 4.3 4.7 5.0 3.2 3.3 3.5 3.8 4.1 4.4 l/s qw

37.3 35.1 33.2 30.4 28.0 26.0 32.5 30.7 29.2 26.8 24.8 23.0 kW Pa

75.8 79.5 83.5 90.6 97.8 105 66.3 69.9 73.6 79.9 86.3 92.6 kW Pf 9

20.5 22.7 25.1 29.6 34.7 40.0 15.9 17.7 19.7 23.3 27.3 31.4 kPa dpw

3.4 3.6 3.8 4.1 4.5 4.8 3.0 3.2 3.3 3.6 3.9 4.2 l/s qw

36.7 34.6 32.7 29.9 27.5 25.5 32.0 30.3 28.7 26.4 24.4 22.6 kW Pa

71.6 75.3 79.2 86.0 93.0 99.8 62.7 66.2 69.8 76.0 82.1 88.1 kW Pf 7

18.2 20.2 22.4 26.6 31.2 36.0 14.1 15.8 17.6 20.9 24.6 28.3 kPa dpw

3.2 3.4 3.6 3.9 4.2 4.5 2.8 3.0 3.2 3.4 3.7 4.0 l/s qw

36.2 34.1 32.2 29.4 27.1 25.0 31.6 29.9 28.3 26.0 24.0 22.2 kW Pa

67.6 71.1 74.9 81.6 88.3 94.9 59.2 62.6 66.1 72.1 78.0 83.8 kW Pf 5

46 43 40 35 30 25 46 43 40 35 30 25 Tain Twout

090 080

33/47

PERFORMANCE IN COOLING MODE

Page 34: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

EWAQ~G-XR

8.80 9.70 23.7 27.6 32.1 36.9 9.00 27.1 29.8 34.7 40.2 46.1 kPa dpw

4.7 4.9 7.6 8.3 8.9 9.6 3.7 6.5 6.8 7.3 7.9 8.5 l/s qw

33.3 31.6 58.4 53.7 49.6 46.0 25.8 52.7 50.1 46.2 42.8 39.7 kW Pa

97.2 102 159 172 185 199 77.9 135 141 153 164 176 kW Pf 15

7.90 19.5 21.4 25.1 29.2 33.7 8.00 24.4 26.9 31.4 36.5 41.9 kPa dpw

4.4 6.9 7.3 7.9 8.5 9.1 3.5 6.2 6.5 7.0 7.5 8.1 l/s qw

32.8 60.5 57.3 52.7 48.6 45.1 25.6 51.9 49.3 45.4 42.0 39.0 kW Pa

91.9 145 152 164 177 190 73.5 128 135 145 157 168 kW Pf 13

7.00 17.5 19.3 22.7 26.5 30.6 19.9 21.9 24.2 28.4 33.1 38.0 kPa dpw

4.2 6.6 6.9 7.5 8.1 8.7 5.6 5.8 6.1 6.6 7.2 7.7 l/s qw

32.4 59.4 56.3 51.7 47.7 44.1 54.0 51.2 48.6 44.7 41.3 38.3 kW Pa

86.8 137 144 156 169 181 116 122 128 138 149 160 kW Pf 11

6.20 15.7 17.3 20.4 23.9 27.7 17.8 19.7 21.7 25.6 29.9 34.4 kPa dpw

3.9 6.2 6.5 7.1 7.7 8.3 5.3 5.5 5.8 6.3 6.8 7.3 l/s qw

32.0 58.4 55.3 50.7 46.8 43.3 53.2 50.4 47.8 44.0 40.6 37.6 kW Pa

81.8 130 137 148 161 173 110 115 121 131 142 152 kW Pf 9

5.50 14.0 15.5 18.4 21.6 25.1 15.9 17.5 19.4 23.0 26.9 31.1 kPa dpw

3.7 5.9 6.2 6.7 7.3 7.9 5.0 5.2 5.5 6.0 6.5 6.9 l/s qw

31.6 57.4 54.4 49.8 45.9 42.4 52.5 49.7 47.1 43.3 40.0 37.0 kW Pa

77.0 123 129 141 153 164 104 109 115 125 135 145 kW Pf 7

11.3 12.5 13.9 16.5 19.4 22.6 14.1 15.6 17.4 20.6 24.2 28.0 kPa dpw

5.3 5.6 5.9 6.4 6.9 7.5 4.7 4.9 5.2 5.7 6.1 6.6 l/s qw

59.9 56.5 53.5 49.0 45.1 41.6 51.8 49.0 46.5 42.7 39.3 36.3 kW Pa

111 116 122 134 145 156 98.0 103 109 118 128 138 kW Pf 5

46 43 40 35 30 25 46 43 40 35 30 25 Tain Twout

150 130

34/47

PERFORMANCE IN COOLING MODE

Page 35: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

Water Pump Kit for EWAQ~G SS/SR (standard efficiency version)

The above curves are representing the available static pressure external to the unit. The pressure drops of the

water filter (available as option) are not included.

- when using mixture of water and glycol please contact the factory as above specification can change

35/47

OPTIONS (TECHNICAL DATA)

Page 36: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

Water Pump Kit for EWAQ~G XS/XR (high efficiency version)

The above curves are representing the available static pressure external to the unit. The pressure drops of the

water filter (available as option) are not included.

- when using mixture of water and glycol please contact the factory as above specification can change

36/47

OPTIONS (TECHNICAL DATA)

Page 37: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

Water Pump Kit - Technical Information

EWAQ~G SS/SR (standard efficiency version)

EWAQ~G XS/XR (high efficiency version)

Filter pressure drops (size 2’ 2/12)

Note: to calculate the pressure drops values introduced by the water filter, refer to the above curve.

37/47

OPTIONS (TECHNICAL DATA)

Page 38: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

LEGEND 1. COMPRESSOR 2. EVAPORATOR 3. CONDENSER COIL 4. ELECTRICAL PANEL 5. FAN 6. EVAPORATOR WATER INLET 7. EVAPORATOR WATER OUTLET 8. SLOT FOR POWER AND CONTROL PANEL CONNECTION

1195 1800 519 189 238 74 152 1743 3200 EWAQ155G-SS

1195 1800 519 189 238 74 152 1714 3200 EWAQ140G-SS

1195 1800 519 189 238 74 152 1657 3200 EWAQ120G-SS

1195 1800 519 189 238 74 152 1657 2680 EWAQ110G-SS

1195 1800 519 189 238 74 152 1641 2680 EWAQ100G-SS

1195 1800 519 189 238 74 152 1641 2680 EWAQ085G-SS

1195 1800 519 189 238 74 152 1657 2140 EWAQ075G-SS

I H G F E D C B A MODEL

38/47

DIMENSIONAL DRAWING

Page 39: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

LEGEND 1. COMPRESSOR 2. EVAPORATOR 3. CONDENSER COIL 4. ELECTRICAL PANEL 5. FAN 6. EVAPORATOR WATER INLET 7. EVAPORATOR WATER OUTLET 8. SLOT FOR POWER AND CONTROL PANEL CONNECTION

1195 1800 519 189 238 74 152 1743 3200 EWAQ155G-SR

1195 1800 519 189 238 74 152 1714 3200 EWAQ140G-SR

1195 1800 519 189 238 74 152 1657 3200 EWAQ120G-SR

1195 1800 519 189 238 74 152 1657 2680 EWAQ110G-SR

1195 1800 519 189 238 74 152 1641 2680 EWAQ100G-SR

1195 1800 519 189 238 74 152 1641 2680 EWAQ085G-SR

1195 1800 519 189 238 74 152 1657 2140 EWAQ075G-SR

I H G F E D C B A MODEL

39/47

DIMENSIONAL DRAWING

Page 40: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

LEGEND 1. COMPRESSOR 2. EVAPORATOR 3. CONDENSER COIL 4. ELECTRICAL PANEL 5. FAN 6. EVAPORATOR WATER INLET 7. EVAPORATOR WATER OUTLET 8. SLOT FOR POWER AND CONTROL PANEL CONNECTION

1195 1820 519 189 238 74 152 1776 3800 EWAQ150G-XS

1195 1820 519 189 238 74 152 1714 3800 EWAQ130G-XS

1195 1800 519 189 238 74 152 1714 3200 EWAQ115G-XS

1195 1800 519 189 238 74 152 1693 3200 EWAQ105G-XS

1195 1800 519 189 238 74 152 1641 3200 EWAQ090G-XS

1195 1800 519 189 238 74 152 1641 2680 EWAQ080G-XS

I H G F E D C B A MODEL

40/47

DIMENSIONAL DRAWING

Page 41: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

LEGEND 1. COMPRESSOR 2. EVAPORATOR 3. CONDENSER COIL 4. ELECTRICAL PANEL 5. FAN 6. EVAPORATOR WATER INLET 7. EVAPORATOR WATER OUTLET 8. SLOT FOR POWER AND CONTROL PANEL CONNECTION

1195 1820 519 189 238 74 152 1776 3800 EWAQ150G-XR

1195 1820 519 189 238 74 152 1714 3800 EWAQ130G-XR

1195 1800 519 189 238 74 152 1714 3200 EWAQ115G-XR

1195 1800 519 189 238 74 152 1693 3200 EWAQ105G-XR

1195 1800 519 189 238 74 152 1641 3200 EWAQ090G-XR

1195 1800 519 189 238 74 152 1641 2680 EWAQ080G-XR

I H G F E D C B A MODEL

41/47

DIMENSIONAL DRAWING

Page 42: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

Warning Installation and maintenance of the unit must be performed only by qualified personnel who have knowledge

with local codes and regulations, and experience with this type of equipment. Must be avoided the unit installation in places

that could be considered dangerous for all the maintenance operations.

Handling Care should be taken to avoid rough handling or shock due to dropping the unit. Do not push or pull the unit

from anything other than the base frame. Never allow the unit to fall during unloading or moving as this may result in

serious damage. To lift the unit, rings are provided in the base frame of the unit. Spreader bar and cables should be

arranged to prevent damage to the condenser coil or unit cabinet.

Location The units are produced for outdoor installation on roofs, floors or below ground level on condition that the area

is free from obstacles for the passage of the condenser air. The unit should be positioned on solid foundations and perfectly

leveled; in the case of installation on roofs or floors, it may be advisable to arrange the use of suitable weight distribution

beams. When the units are installed on the ground, a concrete base at least 250 mm wider and longer than the unit’s

footprint should be laid. Furthermore, this base should withstand the unit weight mentioned in the technical data table.

Space requirements The units are air - cooled, then it is important to respect the minimum distances which

guarantee the best ventilation of the condenser coils. Limitations of space reducing the air flow could cause significant

reductions in cooling capacity and an increase in electricity consumption.

To determinate unit placement, careful consideration must be given to assure a sufficient air flow across the condenser heat

transfer surface. Two conditions must be avoided to achieve the best performance: warm air recirculation and coil starvation.

Both these conditions cause an increase of condensing pressures that results in reductions in unit efficiency and

capacity. Moreover the unique microprocessor has the ability to calculate the operating environment of the air cooled chiller

and the capacity to optimize its performance staying on - line during abnormal conditions.

Each side of the unit must be accessible after installation for periodic service. 'Fig.1 and Fig.2' shows you minimum

recommended clearance requirements.

Vertical condenser air discharge must be unobstructed because the unit would have its capacity and efficiency

significantly reduced. If the units are positioned in places surrounded by walls or obstacles of the same height as the units,

the units should follow the minimum recommended clearance requirements shown in 'Fig.3 and Fig.4'. In the event the

obstacles are higher than the units, the minimum recommended clearance requirements are shown in 'Fig.5 and Fig.6'. Units

installed closer than the minimum recommended distance to a wall or other vertical riser may experience a combination of

coil starvation and warm air recirculation, thus causing reduction in unit capacity and efficiency reductions. The

microprocessor control is proactive in response “of design condition”. In the case of single or compounded influences

restricting airflow to the unit, the microprocessor will act to keep the compressor(s) running (at reduced capacity) rather

than allowing a shut - off on high discharge pressure.

When two or more units are positioned side by side it is recommended that the condenser coils are at a minimum

distance from one another as shown in 'Fig.7 and Fig.8'; strong wind could be the cause of air warm recirculation.

For other installation solutions, consult our technicians.

The above recommended information are representative of general installation. A specific evaluation should be done by

contractor depending on the case.

c

42/47

INSTALLATION NOTES

Page 43: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

Acoustic protection

When noise level must meet special requirements, it is necessary to pay the maximum attention to ensure the perfect

insulation of the unit from the support dampening devices on the unit, on the water pipes and on the electrical connections.

Storage The environment conditions have to be in the following limits:

43/47

INSTALLATION NOTES

Page 44: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

Warning Installation and maintenance of the unit must to be performed only by qualified personnel who have knowledge

with local codes and regulations, and experience with this type of equipment. Must be avoided the unit installation in places

that could be considered dangerous for all the maintenance operations.

General The chiller will be designed and manufactured in accordance with the following European directives:

• Construction of pressure vessel 97/23/EC (PED)

• Machinery Directive 2006/42/EC

• Low Voltage 2006/95/EC

• Electromagnetic Compatibility 2004/108/EC

• Electrical & Safety codes EN 60204 – 1 / EN 60335 - 2 - 40

• Manufacturing Quality Standards UNI – EN ISO 9001:2004

To avoid any losses, the unit will be tested at full load in the factory (at the nominal working conditions and water

temperatures). The chiller will be delivered to the job site completely assembled and charged with refrigerant and oil.

The installation of the chiller must comply with the manufacturer’s instructions for rigging and handling equipment.

The unit will be able to start up and operate (as standard) at full load with:

- outside air temperature from ............... °C to ............... °C

- evaporator leaving fluid temperature between ............... °C and ............... °C

Refrigerant Only HFC 410A can be used.

Performance Chiller shall supply the following performances:

• Number of chiller(s) : ............... unit(s)

• Cooling capacity for single chiller : ............... kW

• Power input for single chiller in cooling mode : ............... kW

• Heat exchanger entering water temperature in cooling mode : ............... °C

• Heat exchanger leaving water temperature in cooling mode : ............... °C

• Heat exchanger water flow : ............... l/s

• Nominal outside working ambient temperature in cooling mode : ............... °C

Operating voltage range should be 400V ±10%, 3ph, 50Hz, voltage unbalance maximum 3%, without neutral conductor

and shall only have one power connection point.

Unit description Chiller shall include as standard not less than: hermetic type rotary scroll compressors, electronic

expansion device (EEXV), refrigerant direct expansion plate to plate heat exchanger, air - cooled condenser section, R - 410A

refrigerant, motor starting components, control system and all components necessary for a safe and stable unit operation.

The chiller will be factory assembled on a robust base frame made of galvanized steel, protected by an epoxy paint.

Sound level and vibrations Sound pressure level at 1 meter distance in free field, semispheric conditions, shall

not exceed ………dB(A). The sound power levels must be rated in accordance to ISO 9614 (other types of rating can

not be used).

Vibration on the base frame should not exceed 2 mm/s.

Dimensions Unit dimensions shall not exceed following indications:

- Unit length ............... mm

- Unit width ............... mm

- Unit height ............... mm

Compressors The units shall be equipped with:

• High performance hermetic scroll compressors optimized to work with R410a, with reduced vibration and sound emissions.

High efficiency values shall be guaranteed:

- by high volumetric efficiency in the whole range of application, through the continuous contact between the fixed and the

orbiting scroll deleting the dead space and the re - expansion of the refrigerant gas;

- by low pressure drops due to the absence of inlet and discharge valves and to the uniform compression cycle;

- reduction of the heat exchange between the gas during suction and discharge due to the separation of gas flows;

•The reduced noise shall be obtained: - for the absence of the inlet and discharge valves

- for the uniform compression cycle

- for the absence of pistons which ensures reduced vibration and pulsation of the refrigerant

• The engine shall be cooled by the suction refrigerant fluid.

• The terminal shall be contained in a casing with protection degree IP 54.

• The compressors shall be provided with crankcase heater to prevent the dilution of refrigerant and oil the during the stops

of the unit;

• Shall be present an electronic thermal protection for the three phases complete with sensors on the stator windings to

avoid overheating caused by lack of phase, insufficient cooling, mechanical locks, power supply out of tolerance;

•The compressors shall be connected in Tandem on a single refrigerating circuit.

•The compressors shall be fitted on rubber antivibration mounts.

•The compressors shall be provided complete with oil charge.

Evaporator (PHE) The units shall be equipped with a direct expansion plate to plate type evaporator.

• The evaporator will be made of of stainless steel brazed plates and shall be linked with an electrical heater to prevent

freezing down to - 28°C ambient temperature, controlled by a thermostat and shall be insulated with flexible, closed cell

polyurethane insulation material (20 - mm thick).

• The evaporator will have 1 refrigerant circuit.

• The water connections shall be treated type connections as standard to ensure quick mechanical disconnection between the

unit and the hydronic network.

44/47

TECHNICAL SPECIFICATIONS

Page 45: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

unit and the hydronic network. • The evaporator will be manufactured in accordance to PED approval.

Condenser coil The condenser is made entirely of aluminum with flat tubes containing small channels. Full - depth

louvered aluminum fins are inserted between the tubes maximizing the heat exchange. The Microchannel technology ensures

the highest performance with the minimum surface for the exchanger. The quantity of refrigerant is also reduced compared

to Cu/Al condenser. Special treatment ensure resistance to the corrosion by atmospheric agents extending the life time.

Condenser fans The condenser fans used in conjunction with the condenser coils, shall be propeller type with glass

reinforced resin blades for higher efficiencies and lower sound. Each fan shall be protected by a fan guard.

• The air discharge shall be vertical and each fan must be coupled to the electrical motor, supplied as standard to IP54 and

capable to work to ambient temperatures of - 20°C to + 65°C.

• The condenser fans shall have as a standard an internally protection from overtemperature.

Refrigerant circuit The unit shall have one refrigerant circuit.

• The circuit shall include as standard: electronic expansion device piloted by unit’s microprocessor control, sight glass with

moisture indicator, charging valves, high pressure switch, high and low pressure transducers and insulated suction line.

Condensation control The units will be provided with an automatic control for condensing pressure which ensures the

working at low external temperatures down to - …………… °C, to maintain condensing pressure.

• The unit automatically unloads when abnormal high condensing pressure is detected. This to prevent the shutdown of the

refrigerant circuit (shutdown of the unit) due to a high - pressure fault.

Low sound unit configurations (on request) The unit compressor shall be connected with unit’s metal base

frame by rubber antivibration supports to prevent the transmission of vibrations to all metal unit structure, in order to

control the unit sound.

• The chiller shall be provided with an acoustical compressor enclosure. The compressor sound - proof enclosure shall be

internally fitted with flexible, multi - layer, high density materials.

Hydronic kit options (on request) The hydronic module shall be integrated in the chiller chassis without

increasing its dimensions and includes the following elements: centrifugal pump with motor protected by a circuit breaker

installed in control panel, pressure gauge, safety valve, drain valve.

• The hydronic module shall be assembled and wired to the control panel.

• The water piping shall be protected against corrosion and freezing and insulated to prevent condensation.

• A choice of two pump types shall be available:

- in - line single pump

- in - line twin pumps

- in - line single pump with tank

- in - line twin pumps with tank.

Electrical control panel Power and control shall be located in the main panel that will be manufactured to ensure

protection against all weather conditions.

• The electrical panel shall be IP54 and (when opening the doors) internally protected against possible accidental

contact with live parts.

• The main panel shall be fitted with a main switch interlocked door that shuts off power supply when opening.

• The power section will include compressors and fans protection devices, compressors and fans starters and control circuit

power supply.

Controller The controller will be installed as standard and it will be used to modify unit set - points and check control

parameters.

• A built - in display will shows chiller operating status plus temperatures of water, refrigerant and air, programmable values,

set - points.

• A sophisticated software with predictive logic, will select the most energy efficient combination of compressors, EEXV and

condenser fans to keep stable operating conditions to maximize chiller energy efficiency and reliability.

• The controller will be able to protect critical components based on external signals from its system (such as motor

temperatures, refrigerant gas and oil pressures, correct phase sequence, pressure switches and evaporator). The input

coming from the high pressure switch cuts all digital output from the controller in less than 50ms, this will be an additional

security for the equipment.

• Fast program cycle (200ms) for a precise monitoring of the system.

• Floating point calculations supported for increased accuracy in P/T conversions.

Controller main features: Controller shall grantee the following minimum functions • Management of the refrigerant circuit capacity

• Full routine operation at condition of:

- high thermal load

- high evaporator entering water temperature (start - up)

• Display of evaporator entering/leaving water temperature.

•Display of condensing - evaporating temperature and pressure, suction superheat for each circuit.

• Leaving water evaporator temperature regulation .

• Compressor and pumps hours counter.

• Display of Status Safety Devices.

• Number of starts and compressor working hours.

• Optimized management of compressor load.

45/47

TECHNICAL SPECIFICATIONS

Page 46: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the

• Optimized management of compressor load. • Re - start in case of power failure (automatic / manual).

• Soft Load (optimized management of the compressor load during the start - up).

• OAT (Outside Ambient temperature) Reset.

• Start at high evaporator water temperature.

• Return Reset (Set Point Reset based on return water temperature).

• Set point Reset (optional).

• Application and system upgrade with commercial SD cards.

High Level Communications Interface (on request) The chiller shall be able to communicate to BMS

(Building Management System) based on the most common protocols as:

- ModbusRTU

- LonWorks, now also based on the international 8040 Standard Chiller Profile and LonMark Technology

- BacNet BTP certifief over IP and MS/TP (class 4)

- Ethernet TCP/IP.

46/47

TECHNICAL SPECIFICATIONS

Page 47: Databook - Daikin · 2020. 12. 8. · Databook 25/06/2015 . Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the