Introduction
Pacific Crest Grounding transformers are used to provide a ground path to either an ungrounded or a
delta connected system and are used...
1. Provide a relatively low impedance path to ground, thereby maintaining the system neutral at or nearground potential.
2. Limit the magnitude of transient over voltages when re-striking ground faults occur.
3. Provide a source of ground fault current during line to ground faults.
4. Permit the connection of secondary loads if desired.
All ratings are designed in accordance with applicable ANSI, NEMA and IEEE standards.
Ratings
Primary Voltage - all voltages through 46 kV - 250 kV BIL
Secondary Voltage - when required all voltages through 15 kV
Frequency - 60Hz
Temperature rise 65 C
Consult factory for ratings not shown
Standard Features
Secondary spade connectors when required
Primary clamp type eyebolt connectors
Combination drain and sampler
Pressure test and upper filter press connection - 1 pipe plug
NEMA two hole ground pad
Corrosion resistant nameplate
Provisions for jacking and lifting
Base suitable for rolling or skidding
Pressure relief valve
Rugged steel plate tank reinforced with steel channel selections for strength and rigidity
Undercoated base
Door has three-point locking mechanism
Externally clamped bushings
-
8/14/2019 Datasheet of Grounding Transformer
3/4
Pacific Crest Transformers
300 West Antelope Road Medford, Oregon 97503Tel : (541) 826 2113 Fax : (541) 826 - 8847
3
When secondary bushings are provided, primary compartment accessible only after low voltage dooris opened
1/2 liquid level plug
Welded cover with handhole
Standard Tests
Each unit is subjected to the following tests:
Resistance
Ratio
Polarity
Phase relation
Core loss
Exciting current
Impedance
Load loss
Applied potential test
Induced potential test
Quality control impulse test
Pressure leak test
Optional Features
Five-legged core for wye-wye connections
50 cycles
55/65 C temperature rise
High fire point liquid
Loop feed construction
Dead front construction
Lightning arrestors
Dial type thermometer
Liquid level gauge
-
8/14/2019 Datasheet of Grounding Transformer
4/4
Pacific Crest Transformers
300 West Antelope Road Medford, Oregon 97503Tel : (541) 826 2113 Fax : (541) 826 - 8847
4
Pressure vacuum gauge
Pressure vacuum bleeder
Combination drain and sampler
Pressure relief device
Bay-o-net fuses
Weak links
Current limiting fuses
Loadbreak oil switch (es)
Primary current transformers
Gauges furnished with alarm contacts
Bolted cover with handhole
Zigzag designs