db50 storm louvre - heating appliances & spares · 2016. 5. 12. · fax: 01746 766450 the...

8
There’s a much bigger picture to be found at Ruskin Air Management. www.naco.co.uk Ruskin Air Management actionair Air Diffusion naco June 2014 DB50 Storm Louvre Excellent Performance Optimum Blade Pitch Class Leading Pressure Drop Slim 51mm Section Aluminium Construction Range of Finish Options naco

Upload: others

Post on 30-Mar-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DB50 Storm Louvre - Heating Appliances & Spares · 2016. 5. 12. · Fax: 01746 766450 The statements made in this brochure or by our representatives in consequence of any enquiries

There’s a much bigger picture to be found at Ruskin Air Management.

www.naco.co.uk

Ruskin Air

Managementactionair Air Diffusion naco

June 2014

DB50 StormLouvre

● Excellent Performance

● Optimum Blade Pitch

● Class Leading Pressure Drop

● Slim 51mm Section

● Aluminium Construction

● Range of Finish Options

naco

Page 2: DB50 Storm Louvre - Heating Appliances & Spares · 2016. 5. 12. · Fax: 01746 766450 The statements made in this brochure or by our representatives in consequence of any enquiries

DB50 Storm Louvres

2

Our ideas built with you in mind

Learning to harnessnature’s elements

When someone says it can’t be done, they’veobviously not spoken to us. So if anyone inthe industry suggests that you are asking forthe impossible, it will always be our privilegeto prove them wrong yet again.

From start to finish

Because unlike most UK louvre companies, we design,detail, supply and install. So not only do our productsmatch your requirements precisely in terms of function butalso in style, finish and colour.This determination to see things through to the finishedresult gives architects and designers a unique opportunityto create outstanding ventilation features or screeningcontrols within the external cladding. And our can-doattitude makes those satisfied clients come back to ustime and time again.

Past, present and future

Since the early sixties this customer-first philosophy hasbeen enshrined in all our activities. Blended withmanufacturing experience and practical expertise honedover almost half a century, it has seen Naco defineeverything from metal and glass louvres, natural air andsmoke ventilators to mist separators, sunscreens andbrise soleil.It even instigated a no-nonsense software program on ourwebsite to take the hassle out of sizing louvres andunscrambling such things as face, jet or core velocitiesand free areas.

An ideal environment

But user friendliness isn’t the only challenge facing buildingdesign today. Increasingly environmental friendliness is nowa design pre-condition, reflecting a growing duty to protectthe natural environment whilst controlling our own internalenvironments.Learning to harness nature’s elements to our advantagerather than simply fighting against them is now drivingforward our engineering and design teams more than ever.

Page 3: DB50 Storm Louvre - Heating Appliances & Spares · 2016. 5. 12. · Fax: 01746 766450 The statements made in this brochure or by our representatives in consequence of any enquiries

naco

DB50 Storm Louvres

3

● Sub cill if required

● Glazing channels

● Insect screen

● Non insulated or insulated blanking panels

● Triangular and bespoke shapes available exceptcircular.

Finishes

● Mill

● Polyester powder - coated to BS6496

● Clear and colour anodising to BS3987

● Consult Ruskin for other special requirements.

Options

80mm 51mm

Comparison between 75s and DB50

● Optimum blades pitch minimises thepenetration of wind-driven rain, reducingdamage and additional operating expenses

● Tested in the AMCA 500-L Wind-Driven RainPenetration test

● Published performance ratings based on testingin accordance with AMCA Publication 511.

● Cd figure of 0.39

● 43% nominal Free Area

● Class leading pressure drop performance.

● Aluminium construction for low maintenanceand high resistance to corrosion

● Tested under extreme weather conditions, seepage 5.

Features

Page 4: DB50 Storm Louvre - Heating Appliances & Spares · 2016. 5. 12. · Fax: 01746 766450 The statements made in this brochure or by our representatives in consequence of any enquiries

DB50 Storm Louvres

4

StandardConstruction

Frame51mm deep 6063T6 extruded aluminium with a1.5mm nominal wall thickness.

Blades6063T6 extruded aluminium with 1.1mm nominalwall thickness. Double drainable blades are sightproof.

FinishesPolyester powder - coated to BS6496

Minimum Size152mm x 152mm

Maximum Factory Assembly sizeSingle sections shall not exceed 1500mm maxwidth by 2500mm max height. Louvres larger thanthe maximum single size will require on siteassembly.

Approximate Shipping Weight19.4 kg/m Sq

Supports (Standard louvre)Louvres may be provided with rear mounted bladesupports that increase overall louvre depthdepending on louvre size, assembly configurationor wind load.

Louvres in excess of max factory assembly sizewill require additional support.

Jamb Section

Head and Cill Section

Blade Section

51mm

25.4

mm

38.1

mm

19.1

mm

23.3

mm

Page 5: DB50 Storm Louvre - Heating Appliances & Spares · 2016. 5. 12. · Fax: 01746 766450 The statements made in this brochure or by our representatives in consequence of any enquiries

naco

DB50 Storm Louvres

5

Wind-Driven Rain Performance

Pressure Drop

Test size is 1m x 1m core area, (1.04m x 1.12m nominal ).

Normal weather conditions 29 mph (75 mm/h) wind and 76mm per hour rain conditions

Extreme weather conditions 50 mph (202 mm/h) wind and 203mm per hour rain conditions

Pressure Drop testing performed on1219 x 121mm unit.

Ratings do not include the effect of a bird screen

Air Velocity in meters per minute through Free Area

Notes:

1. Core area is the open area of the louvre face (face area lesslouvre frames). Core Velocity is the airflow velocity through thecore area of the louvre (1m x 1m).

2. Free area of test size is calculated per AMCA standard 500-L.

3. Wind Driven Rain Penetration Classes:Class EffectivenessA 1 to .99B 0.989 to 0.95C 0.949 to 0.80D Below 0.8

4. Entry/Discharge Loss Class 2 Discharge Loss Coefficient is calculated by dividing a louvre’sactual airflow rate vs. a theoretical airflow for the opening. Itprovides an indication of the louvres’ airflow characteristics.

Discharge Loss Classes:Class Discharge Loss Coefficient1 0.4 and above2 0.3 to 0.3993 0.2 to 0.2994 0.199 and below

(The higher the coefficient, the less resistance to airflow.)

5. The AMCA Wind Driven Rain Test is performed in a laboratoryenvironment and incorporates controlled wind, water and systemairflow effects. In actual field installations, storms may createconditions not considered by the AMCA test. Penthouse and similarapplications where wind can pass through multiple louvres in anenclosure is another condition that is not simulated by AMCA tests.These applications can create elevated water penetration ratesthrough any louvre. Because of these uncontrolled situations, it isrecommended that provisions to manage water penetrationthrough louvres be included in the building design.

Core Airflow Free Area Effectiveness ClassVelocity m3/min Velocity Ratiom/s m/sec

0 0 0 99.9 A

0.7 1421 383 99.9 A

1.0 2120 505 99.9 A

1.4 3068 730 99.9 A

1.9 4031 960 99.9 A

2.4 5077 1209 99.3 A

3.0 6277 1495 97.1 B

3.5 7373 1755 96.1 B

Core Airflow Free Area Effectiveness ClassVelocity m3/min Velocity Ratiom/s m/sec

0 0 0 99.9 A

0.6 1228 292 99.8 A

0.9 2001 476 99.4 A

1.5 3181 757 99.3 A

2.0 4285 1020 97.8 B

2.5 5315 1265 96.2 B

2.9 6114 1456 95.4 B

3.5 7442 1772 90.9 C

1.00.90.80.70

.60

.50

.40

.30

.20

.10

.09

.08

.07

.06

.05

.04

.03

.02

.01

248.9224.01199.12174.23

149.34

124.45

99.56

74.67

49.78

24.8922.4019.9117.42

14.93

12.45

9.96

7.47

4.98

2.49

30 61 91 122

152

183

213

244

274

305

610

924

1219

1524

1829

2134

2438

2743

INTAKE

EXHAUST

Static Pressure Drop

Page 6: DB50 Storm Louvre - Heating Appliances & Spares · 2016. 5. 12. · Fax: 01746 766450 The statements made in this brochure or by our representatives in consequence of any enquiries

DB50 Storm Louvres

6

Installation Drawings

AC Fixing Method - Channel Frame Model

AC Fixing Method - Flange Frame

Curtain Wall Installation View

Framework location for multi panel solution

Horizontal Transom Detail

Vertical Mullion Fixing Details

Fixing Details Coupling Details

Page 7: DB50 Storm Louvre - Heating Appliances & Spares · 2016. 5. 12. · Fax: 01746 766450 The statements made in this brochure or by our representatives in consequence of any enquiries

Typical Installation Details

Louvres wider than the maximum single section width will be supplied in multiple sections andwill require site assembly.

Maximum Width - Unlimited

Visible Mullion Approx 51mm

MaximumHeight

2500mm

Maximum Single Width1500mm

DB50 LouvreSectionShip

The Naco Range

The Naco RangeYou’ll find our products in buildings around the world,from Hong Kong airport and the University of Cincinnatiin San Francisco, to the Channel Tunnel and WimbledonNumber 1 court closer to home.

With over 50 years’ experience, we’re the first choice forarchitects and specifiers everywhere. Part of Ruskin AirManagement Limited, our products and services include:

Metal LouvresOur comprehensive range of standard and high performancelouvres covers everything from simple screen work to specialistapplications, including acoustic, drainable and sandtrap louvres.

Natural Air VentilatorsA natural and practical alternative to openable windows androof mounted air systems, our range of natural air ventilators(NAVs) ensure consistent air flow while preventing carbondioxide build up.

naco 7

Solar ShadingSunscreens continue to be popular for many applications incommercial buildings, meeting the needs for control of solar gainand energy conservation while offering designers a palette ofpossible effects with the external cladding.

Vengen28 Thermal Break Double Glazed Louvre Windows

High quality, double glazed thermal break aluminium louvrewindow system offering high quality solutions for all your naturaland smoke ventilation needs. Available in bespoke sizes, and inan extensive range of colours and finishes, it's both fit forpurpose - and fits to your exact building requirements.

Weatherbeta Single GlazedOur Weatherbeta single glazed louvre is an exceptionally efficientglazed ventilator particularly effective when thermal properties arenot an issue, used widely in many countries around the world.

InstallationAll products are offered on a supply or supply and fix basis. Weoffer a full site survey, design and fixing service where required.

DB50 Storm Louvres

Page 8: DB50 Storm Louvre - Heating Appliances & Spares · 2016. 5. 12. · Fax: 01746 766450 The statements made in this brochure or by our representatives in consequence of any enquiries

10 Grange Road, Houstoun Industrial EstateLivingston West Lothian, EH54 5DETel: +44 (0)1506 438083Fax: +44 (0)1506 433441Email: [email protected]: www.hasl.co.uk

Distributor for Scotland

naco

Ruskin Air Management Limited,Stourbridge Road, Bridgnorth,Shropshire, WV15 5BB England.

Tel: 01746 761921Fax: 01746 766450

www.naco.co.uk

The statements made in this brochure or by our

representatives in consequence of any enquiries

arising out of this document are given for information

purposes only. They are not intended to have any

legal effect and the company is not to be regarded

as bound thereby. The company will only accept

obligations which are expressly negotiated for and

agreed and incorporated into a written agreement

made with its customers.

Due to a policy of continuous product development

the specification and details contained herein are

subject to alteration without prior notice.