ddc controller - dsl · pdf filewill be easy to communicate with modbus master such as...
TRANSCRIPT
DDC Controller Remote I/O Module Human Machine Controller
PEITAN TECHNOLOGY CO., LTD Mail:[email protected] :www.peitan.com TEL:886-2-22183491 FAX:886-2-22185595 ADDRESS:4F,NO.501-18,CHUNG-CHENG,ROAD HSIN-TIEN CITY TAIPEI HSIEN, 231 TAIWAN R.O.C
Introduction : A new line of Modbus based IO modules, Smart module for data acquisition and other applications are available now. These IO modules offer good reliability, low-cost solution for distributed IO applications. They are portable, easy integrated with existing Modbus network, and simple to use for end users. Various types of IO modules are available for different kinds of requirements.
All IO modules have LED indications for visualization of IO status (Digital) and diagnostic analysis. Some smart modules is useful for sequence control, DDC control applications. All IO modules have 3 wire RS485 interface with Modbus RTU Protocol.
S-100m software is used to setup communication of IO modules and checks the IO status in PC for diagnosis purpose. With Modbus RTU protocol, these IO modules configured as slaves will be easy to communicate with Modbus master such as SCADA/PLC/HMI. Features :
Portable Modubs connectivity Simple setup and easy handling Upto 240 Modules on RS485 network Smart modules available for special application. Low-cost IO modules addition to existing PLC system Versatile network topology—Bus, Star and daisy-chain. Different types of IO Modules Ai, Ao, Di, Do, Pi all available Free software for module configuration and trouble shooting IO modules used with the third party software via Modbus RTU protocol Intuitive and user friendly software for data monitoring and control on PC Interface with field devices to provide real-time data for SCADA/PLC/HMI LEDs on every module for digital IO status, communication and power supply
Product Category RS-485 adapter
Description Model
Repeater RS232 RS485 TCP
PT-C485 1 1
PT-IPG 1 1
PT-HUB V 1+ 1
PT-ISO V 1+ 4
Remote IO Module & DDC Controller
Description Model RS-485 Digital
input Digital output
Relay output
Analog input
Analog output
Programmable
PT-801M 1 8 0 0 0 0 N
PT-802M 1 16 0 0 0 0 N
PT-811M 1 8 8 0 0 0 N
PT-812M 1 16 8 0 0 0 N
PT-830M 1 0 24 0 0 0 N
PT-844M 1 4 0 4 0 0 N
PT-601M 1 0 0 0 4 0 N
PT-645M 1 4 4 0 4 0 N
PT-610M 1 0 0 0 0 4 N
PT-703M 1 6 4 0 0 0 Y
PT-1000M4 2 *1 *1 *1 *1 *1 Y
EMS Human-Machine Controller
Description Model
Firmware Display interface Keypad interface Mouse interface Ethernet
PT-EMS800 Elite2100 VGA USB USB 1
PT-EMS800C Intra2100C VGA USB USB 1
Software
Description Model
Monitoring & Control Access Server Client
Elite2100 V
Intra2100S V V
Intra2100C V V
Elite4100 V V
Product Introduction
1. Isolated RS232 to RS485 converter( PT-C485)
PT-C485 specification Description Specification
7
Indicating Status Label Power ON Run
RS485 TXD, RXD
LED Indicators
RS232 CTS, RXD, TXD, RTS
1 transformer-couple isolated three wires (with earth) RS485
Interface
1 RS232
RS485 Line Standby Voltage
. 4V minimum without line terminator,
. 0.22V to 0.4V with 120 ohm terminator
Format N81/N82, 9600bps
Communication
Data loop back NO
Power requirement 11-14V DC, 300mA
Storage Temperature -20 to 70 degree C
Operation Temperature 0 to 50 degree C
Humidity 5% to 95% (non-condensing)
Dimension 132mm(W)*138mm(H)*41mm(D)
Weight 260g
Mounting Din rail or wall mount
2. 1 channel RS485 repeater (PT-HUB)
PT-HUB specification Description Specification
High (ON) 2 to15 V or floating, sink current 10μA (max.) Communication control Input Low (Cut) -0.3 to 0.4V, source current 5 mA (max.)
Interfaces 2 transformer-couple isolated three wires (with earth) RS485
Turn Direction Time 60 ns maximum
Direction Hold time 1.5 ms Typical
Disconnect Time 12 μsecond maximum after control Input low
Communication
Connection Time 100 μsecond maximum after control Input high
Power requirement 9-14 DC 90mA
Operation Temperature 0 to 50 degree C
Storage Temperature -20 to 70 degree C
Humidity 5% to 95% (non-condensing)
Dimension 120mm W X 125 mm D X 26 mm H
Weight 249 g
Mounting Din rail or wall mount
3. 4 channel RS485 repeater (PT-ISO)
PT-ISO specification Description Specification
High (ON) 2 to15 V or floating, sink current 10μA (max.) Communication control Input Low (Cut) -0.3 to 0.4V, source current 5 mA (max.) LED indicators 17
. 15 for five RS485 RXD, TXD and Fault
. One for power DC IN
. One for Control input CTRL1
Interface 5 transformer-couple isolated three wires (with earth) RS485
Turn Direction Time
60 ns maximum
Direction Hold time
1.5 ms Typical
Disconnect Time
12 μsecond maximum after control Input low
Communication
Connection Time
100 μsecond maximum after control Input high
Loop impedance to isolate 45 Ohm maximum
Line fault set up time 2 second
Line fault recover time 1 mS
Power requirement 10 to 14 V DC, 500 mA + power distributor output
Power distributor output Four, each 500mA maximum
Fuse of each Power distributor 750mA
Operation Temperature 0 to 50 ℃
Storage Temperature -20 to 70 ℃
Humidity 5% to 95% (non-condensing)
Dimension 120mm W X 134 mm D X 41 mm H
Weight 279 g
Mounting Din rail or wall mount
4. Analog input Module (PT-601M)
PT-601M specification Description Specification CPU 89C52, 18.432MHz Permanent memory size EPROM: 8K Bytes, EEPROM: 512 Bytes Watch-dog 1.5 Sec
No. of AI 4 single ended Signal Range 0 /1 to +5 V, or 0/4 to +20 mA Resolution 12-bit binary Accuracy +-0.5% of range Linearity +LSB Repeatability +LSB Max Input Voltage +6.5V Input Impedance .500K for voltage type .250 for current type
Analog Inputs
Current/Voltage One select jumper for each AI, Jumper on for current Digital outputs (PT641M, PT645M 4 open collector Digital Inputs( PT645M PT-605M 4 dry contact input
15 Indicated status Label Power RUN RS485 RXD,TXD Analog input High/Low AI1,AI2, AI3, AI4 Digital Input DI1, DI2, DI3, DI4
LED indicators
Digital output DO1, DO2, DO3, DO4 Interface One transformer-couple isolated three wires (with Format N81/N82, 9600 Baud, MODBUS RTU
Communication
Turn direction time 2.0-5mS from last bit of query command Power requirement 11-14V DC, 250mA Storage Temperature -20 to 70 degree C Operation Temperature 0 to 50 degree C Humidity 5% to 95% (non-condensing) Dimension 132mm W X 138mm H X 41mm D Weight 275g Mounting Din rail or wall mount
5. Analog output module (PT-610M)
PT-610M specification Description Specification CPU 89C52, 18.432MHz Permanent memory size EPROM: 8K Bytes, EEPROM: 128 Bytes Watch-dog 1.5 Sec
No. of AO 4 single ended Signal Range 0 /1 to +5 V, or 0/4 to +20 mA Resolution 12-bit binary Accuracy . +-0.5% of full scale for current mode. Output Impedance . 250 Ohms maximum for voltage output Burden . 480 Ohm maximum for current output at 12V power Output Load >20K(Voltage mode) Max Output Current 2 mA in voltage mode Output Overload Protection against short circuit condition not exceed Response Time 200msec maximum for a resistive load from 0 to Full
Analog Output
Current/Voltage One select jumper for each AO, Jumper on for Voltage 3 Indicated status Label Power RUN
LED indicators
RS485 RXD,TXD Interface One transformer-couple isolated three wires (with Format N81/N82, 9600bps, MODBUS RTU
Communication
Turn direction time 2.0-5mS from last bit of query command Power requirement 12V DC, 250mA Storage Temperature -20 to 70 degree C Operation Temperature 0 to 50 degree C Humidity 5% to 95% (non-condensing) Dimension 132mm W X 138mm H X 41mm D Weight 275g Mounting Din rail or wall mount
6. Digital input module (PT-801M)
PT-801M specification Description Specification CPU 89C51
Permanent memory size EPROM: 4K Bytes, EEPROM: 128 Bytes
Watch-dog 2 Sec
Digital Inputs 8 dry contact or TTL signal input Accept signal frequency < 7.5Hz Loop impedance less than 150 Ohm
11
Indicated status Label Power RUN
RS485 RXD,TXD
LED indicators
Input signal DI1 to DI8
Interface One transformer-couple isolated three wires (with earth) RS485
Format N81/N82, 9600bps, MODBUS RTU
Communication
Turn direction time 2.0 mS from last bit of query command
Power requirement DC 12V +- 12%, 100mA
Storage Temperature -20 to 70 degree C
Operation Temperature 0 to 50 degree C
Humidity 5% to 95% (non-condensing)
Dimension 132mm W X 138mm H X 41mm D
Weight 280g
Mounting Din rail or wall mount
7. Digital input module (PT-802M)
PT-802M specification Description Specification CPU 89C51
Permanent memory size EPROM: 4K Bytes, EEPROM: 128 Bytes
Watch-dog 2 Sec
Digital Inputs 16 dry contact or TTL signal input Accept signal frequency < 7.5Hz Loop impedance less than 150 Ohm
19
Indicated status Label Power RUN
RS485 RXD,TXD
LED indicators
Input signal DI1 to DI16
Interface One transformer-couple isolated three wires (with earth) RS485
Format N81/N82, 9600bps, MODBUS RTU
Communication
Turn direction time 2.0 mS from last bit of query command
Power requirement DC 12V +- 12%, 100mA
Storage Temperature -20 to 70 degree C
Operation Temperature 0 to 50 degree C
Humidity 5% to 95% (non-condensing)
Dimension 132mm W X 138mm H X 41mm D
Weight 280g
Mounting Din rail or wall mount
8. Digital input and output module (PT-811M)
PT-811M specification Description Specification CPU 89C51 Permanent memory size EPROM: 4K Bytes, EEPROM: 128 Bytes Watch-dog 2 Sec Digital Inputs 8 dry contact or TTL signal input
Quantity 8 Open Collect output Voltage Range 0 to 12V Voltage of Low 0.4V at Sink current 40 mA (max)
Digital Outputs
Voltage of High 12V DC max. 19 Indicated status Label Power RUN RS485 RXD,TXD Input signal DI1 to DI8
LED indicators
Output Signal DO1 to DO8 Interface One transformer-couple isolated three wires (with Format N81/N82, 9600bps, MODBUS RTU
Communication
Turn direction time 2.0 mS from last bit of query command Power requirement DC 12V +- 12%, 350mA Storage Temperature -20 to 70 degree C Operation Temperature 0 to 50 degree C Humidity 5% to 95% (non-condensing) Dimension 132mm W X 138mm H X 41mm D Weight 280g Mounting Din rail or wall mount
9. Digital input and output module (PT-812M)
PT-812M specification Description Specification CPU 89C51 Permanent memory size EPROM: 4K Bytes, EEPROM: 128 Bytes Watch-dog 2 Sec Digital Inputs 16 dry contact or TTL signal input
Quantity 8 Open Collect output Voltage Range 0 to 12V Voltage of Low 0.4V at Sink current 40 mA (max)
Digital Outputs
Voltage of High 12V DC max. 27 Indicated status Label Power RUN RS485 RXD,TXD Input signal DI1 to DI16
LED indicators
Output Signal DO1 to DO8 Interface 1 transformer-couple isolated three wires (with earth) Format N81/N82, 9600bps, MODBUS RTU
Communication
Turn direction time 2.0 mS from last bit of query command Power requirement DC 12V +- 12%, 350mA Storage Temperature -20 to 70 degree C Operation Temperature 0 to 50 degree C Humidity 5% to 95% (non-condensing) Dimension 132mm W X 138mm H X 41mm D Weight 280g Mounting Din rail or wall mount
10. Digital output module (PT-830M)
PT-830M, PT830MCC, PT830MCA specification Description Specification
CPU 89C51
Permanent memory size EPROM: 4K Bytes, EEPROM: 128 Bytes
Watch-dog 2 Sec
Digital Outputs PT830M PT830MCC PT830MCA
Quantity 24 Open Collect 24 Open Collect 24 Open Collect
Voltage Range 0 to 12V 0 to 30V 0 to (DCIN – 1)V
Active state Low Low High
Voltage of Low 0.4V 40 mA max. 4V 150mA max. Floating
Digital Outputs
Voltage of High Floating Floating (DCIN – 1)V,
27
Indicated status Label
Power RUN
RS485 RXD,TXD
LED indicators
Output Signal DO1 to DO24
Interface 1 transformer-couple isolated three wires (with earth)
Format N81/N82, 9600bps, MODBUS RTU
Communication
Turn direction time 2.0 mS from last bit of query command
Power requirement(DCIN) DC 12V +- 12%, 820mA
Storage Temperature -20 to 70 degree C
Operation Temperature 0 to 50 degree C
Humidity 5% to 95% (non-condensing)
Dimension 132mm W X 138mm H X 41mm D
Weight 280g
Mounting Din rail or wall mount
Note 1: Apply separate power supply for load of digital output if load current is larger than 40mA
11.Relay output converter (PT-908M)
PT-908 specification
a、 Conjunction with PT-811M, PT-812M, PT-830M digital output
b、 Relay capacitor: AC 220V/1A,DC 50V/6A resistive load
c、 Relay On Time: 3ms
d、 Relay Off Time: 5ms
e、 Power consumption: 12V DC,350 mA(Max)
f、 Size: 132 x 125 x 42 mm
12. Digital input and relay output module (PT-844M)
PT-844M specification Description Specification CPU 89C51
Permanent memory size EPROM: 4K Bytes, EEPROM: 128 Bytes
Watch-dog 2 Sec
Digital Inputs 4 dry contact or TTL signal input Accept signal frequency < 7.5Hz Loop impedance less than 150 Ohm
Quantity 4 RO
Contact Capacity AC 110/220V 0.2A, DC 12V,2A
Relay Outputs
Active state Relay close
11
Indicated status Label
Power RUN
RS485 RXD,TXD
Input signal IN1 to IN4
LED indicators
Output Signal RLY to RLY4
Interface 1 transformer-couple isolated three wires (with earth) RS485
Format N81/N82, 9600bps, MODBUS RTU
Communication
Turn direction time 2.0 mS from last bit of query command
Power requirement DC 12V +- 12%, 350mA
Storage Temperature -20 to 70 degree C
Operation Temperature 0 to 50 degree C
Humidity 5% to 95% (non-condensing)
Dimension 132mm W X 138mm H X 41mm D
Weight 280g
Mounting Din rail or wall mount
13. pulse accumulator controller (PT-304M, PT-308M)
PT-304M, PT-308M specification Description Specification
CPU 89C51
Permanent memory size EPROM: 4K Bytes, EEPROM: 256 Bytes
Maximum value of Counter 65,535
Maximum value of counter
accumulator
4,294,967,295 (optional)
Memory type of counter Permanent memory
Watch-dog 2 Sec
Counter Inputs 4 (8 for PT-308M) Dry contact or TTL signal input
Accept signal frequency < 25Hz
Loop impedance less than 150 Ohm
Counter stop control input 4 (8 for PT-308M) Dry contact or TTL signal input
Accept signal frequency < 25Hz
Loop impedance less than 150 Ohm
19
Indicated status Label
Power RUN
RS485 RXD,TXD
Counter Input IN1 to IN8
LED indicators
Control input IN9 to IN16 (note 1)
Interface 1 transformer-couple isolated three wires (with earth) RS485
Format N81/N82, 9600bps, MODBUS RTU
Communi
cation
Turn direction time 2.0 mS from last bit of query command
Power requirement DC 12V +- 12%, 350mA
Storage Temperature -20 to 70 degree C
Operation Temperature 0 to 50 degree C
Humidity 5% to 95% (non-condensing)
Dimension 132mm W X 138mm H X 41mm D
Weight 280g
Mounting Din rail or wall mount
note 1: The #1 one counter (IN1) will stop if #1 counter control input (IN9) was inactive, and so on.
14. Sequential on/off controller (PT-703M)
PT-703M specification Description Specification CPU 89C51 Permanent memory size EPROM: 4K Bytes, EEPROM: 128 Bytes Watch-dog 2 Sec Digital Inputs 6 dry contact, 2 for manual Start and stop,
Quantity 4 Open Collect output Voltage Range 0 to 12V Voltage of Low 0.4V at Sink current 40 mA (max)
Digital Outputs
Voltage of High 12V DC max. Sequencer time pitch 5 to 1800 seconds, Programmable Expand connection In cascade Starter Manual start or remote start by communication
13 Indicated status Label Power RUN RS485 RXD,TXD Input signal DI1 to DI6
LED indicators
Output Signal DO1 to DO4 Interface 1 transformer-couple isolated three wires (with earth) Format N81/N82, 9600bps, MODBUS RTU
Communication
Turn direction time 2.0 mS from last bit of query command Power requirement DC 12V +- 12%, 300mA Storage Temperature -20 to 70 degree C Operation Temperature 0 to 50 degree C Humidity 5% to 95% (non-condensing) Dimension 132mm W X 138mm H X 41mm D Weight 270g Mounting Din rail or wall mount
15. EMS DDC controller (PT-1000M4)
a、 Standalone, programmable by menu-driven setting and down load directly .
b、 Non-pc base, Low power consumption, no need fan or heat sink.
c、 Down connect 32 pcs remote module and supervise 512 IO point.
d、 Monitor alarm, Inquiry device status, Remote device Control.
e、 Inquiry environment value – temperature, humidity, voltage, pressure.
f、 Display alarm message when event trigger.
g、 Made 4 different alarm sound depend on alarm priority.
h、 Driven Mimic Panel when alarm trigger.
i、 Save latest 100 alarm records.
j、 Weekly schedule control.
k、 Build-in human interface --16*1 LCD, 4*4 Membrane Keypad & Speaker.
l、 Built-in battery back-up real time clock (RTC).
PT-1000M4 specification
Description Specification CPU 77E58 or ARM7( PT-1000MT)
EPROM 32 Bytes
FRAM 32KB
Backup RAM 128K to 512K Bytes
Memory
EEPROM 256 bytes
RTC (Real Time Clock) Battery backup
Display One row, 16 character, back light
Keyboard Membrane, 16 keys
Speaker Internal 1/4W
Peripheral CPLD
Watch-dog 2 Sec
3
Indicated status Label
Power RUN
LED indicators
RS485 RXD,TXD
Interface 2 transformer-couple isolated three wires (with earth) RS485 or RS485 x 1, Ethernet x 1
Format N81/N82, 9600bps, MODBUS RTU
Communication
Turn direction time 2.0 mS from last bit of query command
Power requirement DC 12V +- 12%, 250mA (PC-1000M4) DC 12V +- 12%, 800mA (PT-1000MT)
Storage Temperature -20 to 70 degree C
Operation Temperature 0 to 50 degree C
Humidity 5% to 95% (non-condensing)
Dimension 260mm(L) x 193mm(w) x 75mm(D)
Weight 270g
Mounting wall mount
16. EMS Human-Machine controller (PT-EMS800)
PT-EMS800 is a embedded EMS client or workstation, build-in EMS software. When it be defined a client (PT-EMS800C), It can easily accept real time message from EMS server. Only need pug in Ethernet port.
When it be defined a workstation, It integrate HMI and Main controller function. It can endure worse environment than P.C, because it’s low power consumption, no moving parts, small size and embedded design. PT-EMS800 workstation can conjunction with PEITAN all remote IO module and DDC controller, Execute security management, environment monitoring and control function. PT-EMS800 specification CPU 32 bits, 800MHZ
Main memory SRAM 256MB
Flash Memory 1GB
O.S XP Embedded
VGA 1,280 x 1,024
Serial RS-232 x 1
LAN 10/100 M Ethernet
Peripheral USB 2.0 x 2
Keyboard PS/2
Mouse PS/2
Parallel Printer port x 1
Size 170 x 124 x 55 mm
Weight 0.92kg
Power 5V ~ 5.25V @4A
Operating temperature 0~60OC
Operating Humidity 0~90%, non-condensing.
17. EMS Software (Elite2100) The Elite2100 is intuitive and user friendly security management, environment monitoring
and control software. It is used conjunction with DDC controller and remote IO module.
Windows XP/2000. Graphic Man-Machine Interface. Supervise 253 DDC controller, 129,536 IO points. 2 serial and 253 IP communication channel. Customers map, icon, device category and alarm voice. Analog level monitoring. Time internal event monitoring. Alarm popup map of event. Alarm trigger event voice. Alarm trigger 1 or more output setting. Inquiry event history by date, time, alarm priority and device name. Inquiry real time device status by category and map. Day schedule security or device control. On-screen device control by device category and map. 3 different management architecture –
Single P.C supervise --- Elite 2100 Server/ client supervise— Intra2100S/ Intra2100C. Web-control interface – web 2100.
Option Integrated digital video--- Live video verification, e-map live video. Weekly schedule device control.
18. EMS integrated ACS software( Elite4100) The Elite4100 is fully integrated Access Control, Security Management, Environment
Monitoring and Control Software. It has not only Elite2100 function but following features.
Supervise 1,024 doors, 3,584 I/O points.(expandable) Real time access controller status display. Real time access controller parameter setting. Elevator floor control setting. Real time card transaction and people picture display. 12 time zone per door site. 1 year holiday per door site. Anti pass back setting. Time and attendance report. Remote open door lock. Inquire card transition by date, time, staff id, card id, door id. Day and month access transaction .txt file for 3’rd party software. Legal card trigger device control.
Option Integrated digital video--- Live video verification, e-map live video. Weekly schedule device control. On-line guard tour.