Fire Protection Div. Dorot Fire Protection Division Deluge Valves Deluge Valves Certification & Compliance by Design Typical Applications Automatic or Manual actuated Fire Suppression Systems Hangars & Airport terminals Flammable Storage Power Generation, Transformer & Transmission Plants Tunnels Petrochemical, Oil & Gas Installations Onshore-offshore Mining Model 68 DE/EL-MR Electrically Actuated, Manual-reset, Deluge Valve ANSI FCI 70-2 Class VI seat leakage class UL listed under VLFT category Fire tested to EN ISO 6182-5:2006 SIL 3-4 to IEC 65508/65111 in redundant system configuration Lloyd’s & ABS type approvals Designed for • High Pressure (PN25/375psi), high flow deluge systems • Automated remote or local manual emergency actuation and local manual reset • Hazardous flammable and explosion classified area fire suppression Onshore & Offshore, Naval, Industrial & Building fire suppression Features Superior design featuring exceptionally low pressure losses at high flow rates Low to negligible lifelong maintenance costs thanks to no wet metallic mechanical moving parts design Simple, no expertise required for maintenance Fresh or Brackish water, seawater and foam • Out of box fully assembled & tested valves Extensive valve & trim materials selection and corrosion protection coating to EN12944 C4, C5 & C5M 1

Upload: vuque

Post on 19-Mar-2018

319 views

Category:

Documents


17 download

TRANSCRIPT

Page 1: DE/EL-MR - GPM · PDF fileModel 68 DE/EL-MR Electrically Actuated, Manual-reset, Deluge Valve ... corrosion protection coating to EN12944 C4, C5 & C5M 1. Deluge Valve Model 68 DE/EL-MR

Fire Protection Div.

Dorot Fire Protection Division

Deluge Valves

Deluge Valves

Certification & Compliance by Design

Typical Applications

Automatic or Manual actuated Fire Suppression Systems

Hangars & Airport terminals

Flammable Storage

Power Generation, Transformer & Transmission Plants

Tunnels

Petrochemical, Oil & Gas Installations

CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.

The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.

The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.

Please Note:The word "MARINE" should only be used for UL Classified marine products.

200-195D 20M/11/97

Onshore-offshore

Mining

Model 68 DE/EL-MR

Electrically Actuated, Manual-reset, Deluge Valve

• ANSI FCI 70-2 Class VI seat leakage class • UL listed under VLFT category • Fire tested to EN ISO 6182-5:2006 • SIL 3-4 to IEC 65508/65111 in redundant system

configuration • Lloyd’s & ABS type approvals

Designed for• High Pressure (PN25/375psi), high flow deluge

systems• Automated remote or local manual emergency

actuation and local manual reset• Hazardous flammable and explosion classified

area fire suppression• Onshore & Offshore, Naval, Industrial & Building

fire suppression

Features• Superior design featuring exceptionally low

pressure losses at high flow rates• Low to negligible lifelong maintenance costs

thanks to no wet metallic mechanical moving parts design

• Simple, no expertise required for maintenance• Fresh or Brackish water, seawater and foam• Out of box fully assembled & tested valves• Extensive valve & trim materials selection and

corrosion protection coating to EN12944 C4, C5 & C5M

1

Page 2: DE/EL-MR - GPM · PDF fileModel 68 DE/EL-MR Electrically Actuated, Manual-reset, Deluge Valve ... corrosion protection coating to EN12944 C4, C5 & C5M 1. Deluge Valve Model 68 DE/EL-MR

Deluge Valve

Model 68 DE/EL-MRFire Protection Div.

General Description

This electrically actuated, local manual-reset deluge valve is designed for fire protection systems controlled by a Fire Alarm Control Panel and actuated by a solenoid valve as the automatic release device. The basic control valve type used in this deluge system is a direct-sealing elastomeric diaphragm, hydraulically operated control valve engineered specifically for Fire Protection systems. The system includes a 2 way solenoid valve as the interface between the Fire Alarm Control Panel - monitoring heat, smoke or flames - and the deluge valve. The deluge valve opens instantly when the control chamber is vented, under one of the following conditions:• The normally closed solenoid valve is

energized, (or the coil of a continuously energized ED 100% normally open solenoid is de-energized for SIL 3-4 rated systems)

• Opening the manual emergency release valve.In both instances the valve will open, allowing

water to spray from all open sprinklers and/or nozzles over the protected area.Once the valve opens, the DMR (Dorot Manual Reset) pilot latches hydraulically, causing the deluge valve to remain in a fully opened position, isolating the control chamber from the upstream water supply. After the solenoid is reset, closing the Dorot deluge valve model DE/EL-MR is only possible by pressing the local manual-reset knob until the valve shuts. Following resetting, the deluge valve closes drip-tight and returns to its standby position without requiring the valve to be physically open or performing other complex reset procedures by qualified or skilled personnel.Resetting, maintenance and periodic testing instructions must be followed as described in detail in the relevant Dorot DE/RC-MR model's IOM (Installation, Operation & Maintenance Manual).

Operation Modes

2

Manually Actuated Reset to Close

Ready Position Electrically Actuated

Manually Actuated

Electrically ActuatedReady Position

68-DE\EL-MR

Reset To CloseManually Actuated

Electrically ActuatedReady Position

68-DE\EL-MR

Reset To Close

Manually Actuated

Electrically ActuatedReady Position

68-DE\EL-MR

Reset To CloseManually Actuated

Electrically ActuatedReady Position

68-DE\EL-MR

Reset To Close

Water Water

Control(By others)

Sensor Line

Control(By others)

To System

Control(By others)

Sensor Line

Control(By others)

Sensor LineSensor Line

Water To System Water

Press

Page 3: DE/EL-MR - GPM · PDF fileModel 68 DE/EL-MR Electrically Actuated, Manual-reset, Deluge Valve ... corrosion protection coating to EN12944 C4, C5 & C5M 1. Deluge Valve Model 68 DE/EL-MR

Deluge Valve

Model 68 DE/EL-MR

Typical control trim materials for POG (1) applications

3

2

7

3

4

1

9

8

5

6

2

7

3

4

1

9

8

5

6

68-DE\EL-MRID Description1 S-68 Control Valve2 Ball Valve3 Y Control Filter4 Check Valve5 Dorot Latching & Manual Reset device6 Emergency manual activation Valve7 1/2" Drip Valve8 Pressure Gauge9 2way, 1/2" Solenoid Valve

ID Description Material

1 Dorot deluge valve body See Engineeering data model (2b)

2 Ball Valve SST

3 Y Control Filter SST

4 Check Valve SST

5 DMR See Engineering data model (2)

6 Manual Emergency Valve See engineering data accessories

7 1/2” Drip Valve SST

8 Pressure Gauge SST, glycerin filled 2 ½”

9 2/2, 1/2” Solenoid Valve See engineering data solenoids (3)

• Temperature: Media up to 80°C = 176°F

(1) Petrochemical, Oil & Gas(2) Refer to material selection guidelines,

Engineering Data - Valves & Control Trims(2b) Basic Valve material options:

Ductile Iron A-536 65-45-12; Cast Steel WCB A-216;Cast Steel A-352 LCB; Austenitic Stainless Steel A-351/CF8M; Super Duplex 2507; Nickel-Aluminium-Bronze B-148 UNS C95800

(3) Refer to solenoid selection guidelines

Page 4: DE/EL-MR - GPM · PDF fileModel 68 DE/EL-MR Electrically Actuated, Manual-reset, Deluge Valve ... corrosion protection coating to EN12944 C4, C5 & C5M 1. Deluge Valve Model 68 DE/EL-MR

Deluge Valve

Model 68 DE/EL-MRFire Protection Div.

Valve Dimensions

Valve 2 (50) 3 (80) 4 (100) 6 (150) 8 (200) 10 (250)inch mm inch mm inch mm inch mm inch mm inch mm

A 10.00 254 12.20 310 13.98 355 17.44 443 20.87 530 25.00 635B 6.61 168 7.87 200 9.37 238 12.05 306 14.17 360 16.93 430C 4.78 122 6.10 155 6.04 154 7.78 198 9.37 238 11.28 287D 5.71 145 5.71 145 5.71 145 6.28 160 7.87 200 9.78 249E 9.72 247 12.32 313 12.17 309 15.43 392 16.22 412 17.13 435F 6.50 165 9.09 231 8.94 227 12.20 310 12.99 330 13.90 353G 2.17 55 3.03 77 3.43 87 4.49 114 5.47 139 6.26 159H 3.27 83 3.27 83 3.27 83 3.78 96 3.78 96 3.78 96I 10.31 262 10.31 262 10.31 262 10.31 262 10.43 265 12.48 317L 2.48 63 2.48 63 2.48 63 2.48 63 2.48 63 2.48 63K 2.44 10 2.44 62 2.44 62 2.44 62 2.44 62 2.44 62

Approx. Weight

Ibs kg Ibs kg Ibs kg Ibs kg Ibs kg Ibs kg29 13 73 33 90 41 172 78 278 126 425 193

4

CONTROL VALVES

SST

190

CONTROL VALVES

Brass

247

CONTROL VALVES

K

HA

I

G

E

F

B

K

L

DC

I

HA

G

DE-EL-MR

CONTROL VALVES

K

HA

I

G

E

F

B

K

L

DC

I

HA

G

DE-EL-MR

CONTROL VALVES

K

HA

I

G

E

F

B

K

L

DC

I

HA

G

DE-EL-MR

Optional Upstream Drain Valve

Page 5: DE/EL-MR - GPM · PDF fileModel 68 DE/EL-MR Electrically Actuated, Manual-reset, Deluge Valve ... corrosion protection coating to EN12944 C4, C5 & C5M 1. Deluge Valve Model 68 DE/EL-MR

Deluge Valve

Model 68 DE/EL-MRFire Protection Div.

5

Typical electric actuated, local manual-reset system layoutDorot’s DE/EL-MR electrically actuated, local manual-reset deluge valve is held shut drip-tight in its stand-by set position. When the solenoid valve is actuated, the deluge valve's control chamber is vented through the ½” solenoid. The deluge valve latches open, allowing water to flow into all of the open sprinklers and/or nozzles over the protected area.

13

DMR

2

Fire Alarm Control Panel3

Dorot electrically actuated, local manual-reset deluge valve

1

DMR hydraulic latching pilot2

Page 6: DE/EL-MR - GPM · PDF fileModel 68 DE/EL-MR Electrically Actuated, Manual-reset, Deluge Valve ... corrosion protection coating to EN12944 C4, C5 & C5M 1. Deluge Valve Model 68 DE/EL-MR

Deluge Valve

Model 68 DE/EL-MRFire Protection Div.

Ordering Guide

Specification for Engineers The Deluge valve shall be hydraulically operated, direct elastomeric diaphragm-seal, single chamber globe weir type. The valve shall consist of three major components: the body, cover and the diaphragm assembly. The diaphragm shall be the only moving part. The diaphragm forms a sealed control chamber in the upper portion of the valve, separating operating pressure from line pressure. Packing glands and/or stuffing boxes are not permitted and there shall be no shafts, discs, bearings or pistons operating the main valve. No hourglass-shaped disc retainers shall be permitted and no V-type, U-type or other slotted type disc guides shall be used. The valve shall contain a nylon reinforced rubber diaphragm elastic & resilient through its entire surface without vulcanized radial discs and/or reinforcements The diaphragm shall not be guided by any shafts or bearings and shall not be in close contact with other valve parts except for its sealing surface. Maintenance, disassembly and reassembly of all the valve’s components shall be made possible on site and in-line, without the need to remove the valve from the line. The electric actuated control trim should contain a push button local manual-reset hydraulic latching pilot to ensure the Deluge valve remains fully open even when the release device (solenoid or any other release device type) is reset to its initial standby position.Standard material valves such as Ductile Iron (ASTM A-536 65-45-12) and Cast Steel (WCB A-216) should be coated with zinc-enriched, high-built fusion-bonded epoxy (FBE) and a UV protective topcoat conforming to EN12944 C4 & C5 high & very high corrosivity protection grades. Naval quality / very high corrosivity protection grade conforming to EN12944 C5M is available upon request. Other coating standards such as NORSOK or ANSI/NACE as well as coatings for special material valves such as austenitic Stainless Steel (CF8M/ASTM A-316 ) and Nickel Aluminum Bronze (ASTM B-148) can be supplied upon request. The valve should be UL listed under category VLFT for fire protection service.

Ed

itio

n 1

0.11

.201

6

6

Dorot Control Valves www.dorot.come-mail: [email protected]

Please specify in addition to the above:• Electrical features other than standard (24VDC, IP65/Nema4) • Control trim material other than standard (brass/copper) • Required standard/certifications and approva

Dorot & Dorot companies worldwide reserve the right to make changes without notice including product specification and configuration, content, description(s), dimensions etc. The Information herein is subject to change without notice. Dorot shall not be held liable for any errors. All rights reserved. © Copyright by Dorot.

68 - SS - - 3 - AN150RF - DE/EL-MR - /PI/HA/...

Model 68 68 Optional add-on

Material UV Upstream drain valve

Dutile Iron - HA Hydraulic alarm loop

Cast Steel CS LS Limit switch

SST316 SS Ex Explosion-proof ***

NAB NAB PI Pressure switch

Optional add-on Control Function

Indicator rod I End connection standard

Size (inch) ** 2”-24” AN15RF ANSI #150 (FF or RF)

AN30RF ANSI #300 (FF or RF)

V Grooved

ISO16 ISO PN16

ISO25 ISO PN25

xxx Other (specify)

Notes:

* Grooved end-connection available in straight-flow: S-300 Sizes 2”-6” and model 68 sizes 2”-10”

** UL listed sizes: S-300 Sizes 2”-12” and model 68 sizes 2”-10”

*** If explosion-proof accessories are required such as solenoid, pressure switches or trans-mitters, please define classification