defining size and location of capacitor in electrical system (1) _ eep
TRANSCRIPT
2/1/2014 Defining Size and Location of Capacitor in Electrical System (1) | EEP
http://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 1/9
Energy & Power For All !
Home
Technical Articles
Categories
Electrica l Spreadsheets
Engineering Guides
EE Resources
Contact
Defining Size and Location of Capacitor in
Electrical System (1)
+ Share with engineers
Defining Size and Location of Capacitor in Electrical System (1)
2/1/2014 Defining Size and Location of Capacitor in Electrical System (1) | EEP
http://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 2/9
Content
Type of Capacitor Bank as per Its Application:
1. Fixed type capacitor banks
2. Automatic type capacitor banks
3. Types of APFC – Automatic Power Factor Correction
Type of Capacitor as per Construction
Selecting Size of Capacitor Bank
Selection of Capacitor as per Non Liner Load
Configuration of Capacitor:
1. Star-Solidly Grounded
2. Star-Ungrounded
3. Delta-connected Banks
Effect of series and Parallel Connection of capacitor:
1. Parallel Connection
2. Series Connection
Type of Capacitor Bank as per Its Application
1. Fixed type capacitor banks
The reactive power supplied by the fixed capacitor bank is constant irrespective of any variat ions
in the power factor and the load of the receivers. These capacitor banks are switched on either
manually (ci rcui t breaker / switch) or semi automatically by a remote-controlled contactor.
This arrangement uses one or more capacitor to provide a constant level of compensation.
These capacitors are applied at the terminals of inductive loads (mainly motors), a t bus bars.
Disadvantages:
Manual ON/OFF operation.
Not meet the require kvar under varying loads.
Penalty by electricity authority.
Power factor a lso varies as a function of the load requirements so it is difficult to maintain a
consistent power factor by use of Fixed Compensation i.e . fixed capacitors .
Fixed Capacitor may provide leading power factor under l ight load conditions, Due to this
result in overvoltages, saturation of transformers, mal-operation of diesel generating sets,
penalt ies by electric supply authorit ies.
Application:
2/1/2014 Defining Size and Location of Capacitor in Electrical System (1) | EEP
http://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 3/9
Where the load factor is reasonably constant.
Electrical insta llations with constant load operating 24 hours a day
Reactive compensation of transformers.
Individual compensation of motors.
Where the kvar rating of the capacitors is less than, or equal to 15% of the supply
transformer rating, a fixed value of compensation is appropriate.
Size of Fixed Capacitor bank Qc ≤ 15% kVA transformer
Go to Content ↑
2. Automatic type capacitor banks
The reactive power supplied by the capacitor bank can be adjusted according to variat ions in the
power factor and the load of the receivers.
These capacitor banks are made up of a combination of capacitor steps (step = capacitor +
contactor) connected in parallel. Switching on and off of all or part of the capacitor bank is
controlled by an integrated power factor controller.
The equipment is applied at points in an installation where the active-power or reactive power
variations are relatively large , for example:
At the bus bars of a main distribution switch-board,
At the terminals of a heavily-loaded feeder cable.
Where the kvar rating of the capacitors is less than, or equal to 15% of the supply transformer
rating, a fixed value of compensation is appropriate.
Above the 15% level, it is advisable to install an automatically-controlled bank of capacitors.
Control is usually provided by contactors. For compensation of highly fluctuating loads, fast and
highly repetitive connection of capacitors is necessary, and static switches must be used.
Go to Content ↑
Types of APFC – Automatic Power Factor Correction
Automatic Power Factor correction equipment is divided into three major categories:
1. Standard = Capacitor + Fuse + Contactor + Controller
2. De tuned = Capacitor + De tuning Reactor + Fuse + Contactor + Controller
3. Filtered = Capacitor + Filter Reactor + Fuse + Contactor + Controller.
2/1/2014 Defining Size and Location of Capacitor in Electrical System (1) | EEP
http://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 4/9
Advantages:
Consistently high power factor under fluctuating loads.
Prevention of leading power factor.
Eliminate power factor penalty.
Lower energy consumption by reducing losses.
Continuously sense and monitor load.
Automatica lly switch on/off relevant capacitors steps for consistent power factor.
Ensures easy user interface.
Automatica lly variation, without manual intervention, the compensation to suit the load
requirements.
Application:
Variable load electrical instal lations.
Compensation of main LV distribution boards or major outgoing lines.
Above the 15% level, i t is advisable to insta ll an automatically-controlled bank of capacitors.
Size of Automatic Capacitor bank Qc > 15% kVA transformer.
Method Advantages Disadvantages
Individual capacitorsMost technically efficient, most
flexible
Higher insta llat ion & maintenance
cost
Fixed bankMost economical, fewer installations Less flexible, requires switches
and/or circuit breakers
Automatic bankBest for variable loads, prevents
over voltages, low installation cost
Higher equipment cost
CombinationMost practical for larger numbers of
motors
Least flexible
Go to Content ↑
Type of Capacitor as per Construction
1. Standard duty Capacitor
Construction: Rectangular and Cylindrical (Resin f illed / Resin coa ted-Dry)
Application:
1. Steady inductive load.
2/1/2014 Defining Size and Location of Capacitor in Electrical System (1) | EEP
http://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 5/9
2. Non linear up to 10%.
3. For Agriculture duty.
2. Heavy-duty
Construction: Rectangular and Cylindrical (Resin f illed / Resin coa ted-Dry/oil/gas)
Application:
1. Suitable for fluctuating load.
2. Non linear up to 20%.
3. Suitable for APFC Panel.
4. Harmonic fil tering
3. LT Capacitor
Application:
Suitable for fluctuating load.
Non linear up to 20%.
Suitable for APFC Panel & Harmonic fi lter application.
Go to Content ↑
Selecting Size of Capacitor Bank
The size of the inductive load is large enough to select the minimum size of capacitors that is
practical.
For HT capacitors the minimum ratings that are practical are as follows:
System VoltageMinimum rating of capacitor
bank
3.3 KV , 6.6KV 75 Kvar
11 KV 200 Kvar
22 KV 400 Kvar
33 KV 600 Kvar
2/1/2014 Defining Size and Location of Capacitor in Electrical System (1) | EEP
http://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 6/9
Unit sizes lower than above is not practica l and economical to manufacture.
When capacitors are connected directly across motors i t must be ensured that the rated current
of the capacitor bank should not exceed 90% of the no-load current of the motor to avoid self-
excitation of the motor and also over compensation.
Precaution must be taken to ensure the live parts of the equipment to be compensated should not
be handled for 10 minutes (in case of HT equipment) after disconnection of supply.
Crane motors or like , where the motors can be rotated by mechanica l load and motors with
electrical braking systems, should never be compensated by capacitors directly across motor
terminals.
For direct compensation across transformers the capacitor rating should not exceed 90 %
of the no-load KVA of the motor.
Go to Content ↑
Selection of Capacitor as per Non Liner Load
For power Factor correction it is need to first decide which type of capacitor is used.
Selection of Capacitor is depending upon many factor i.e . operating life, Number of Operation,
Peak Inrush current withstand capacity.
For selection of Capacitor we have to calculate Total Non-Liner Load like: UPS, Rectifier,
Arc/Induction Furnace, AC/DC Drives, Computer, CFL Blubs, and CNC Machines.
Calculation of Non l iner Load, Example: Transformer Rating 1MVA,Non Liner Load
100KVA
% of non Liner Load = (Non Liner Load/Transformer Capacity) x100 = (100/1000)
x100=10%.
According to Non Linear Load Select Capacitor as per Following Table.
% Non Liner
LoadType of Capacitor
<=10% Standard Duty
Up to 15% Heavy Duty
Up to 20% Super Heavy Duty
Up to 25% Capacitor +Reactor (Detuned)
Above 30%
2/1/2014 Defining Size and Location of Capacitor in Electrical System (1) | EEP
http://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 7/9
Go to Content ↑
Configuration of Capacitor
Power factor correction capacitor banks can be configured in the following ways:
1. Delta connected Bank.
2. Star-Solidly Grounded Bank.
3. Star-Ungrounded Bank.
Go to Content ↑
1. Star-Solidly Grounded
Initia l cost of the bank may be lower since the neutral does not have to be insulated from
ground.
Capacitor switch recovery voltages are reduced
High inrush currents may occur in the station ground system.
The grounded-Star arrangement provides a low-impedance fault path which may require
revision to the existing system ground protection scheme.
Typically not applied to ungrounded systems. When applied to resistance-grounded systems,
difficulty in coordination between capacitor fuses and upstream ground protection relays
(consider coordination of 40 A fuses with a 400 A grounded sys tem) .
Application: Typical for smaller installations (since auxil iary equipment is not required)
Go to Content ↑
2. Star-Ungrounded
Industrial and commercial capacitor banks are normally connected ungrounded Star, with
paralleled units to make up the total kvar.
It is recommended that a minimum of 4 paralleled units to be applied to limit the over voltage
on the remaining units when one is removed from the circuit.
If only one unit is needed to make the total kvar, the units in the other phases will not be
overloaded if it fails.
In industria l or commercial power systems the capacitors are not grounded for a variety of
reasons. Industrial systems are often resistance grounded. A grounded Star connection on the
2/1/2014 Defining Size and Location of Capacitor in Electrical System (1) | EEP
http://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 8/9
capacitor bank would provide a path for zero sequence currents and the possibil ity of a false
operation of ground fault relays.
Also, the protective relay scheme would be sensitive to system l ine-to-ground voltage Unbalance,
which could also result in false relay tripping.
Application: In Industria l and Commercia l.
Go to Content ↑
3. Delta-connected Banks
Delta-connected banks are generally used only at distributions voltages and are configured with a
Single series group of capacitors rated at line-to-line voltage. With only one series group of
units no overvoltage occurs across the remaining capacitor units from the isolation of a faulted
capacitor unit.
Therefore, unbalance detection is not required for protection and they are not treated further in
this paper.
Application: In Distribution System.
Go to Content ↑
Effect of series and Parallel Connection of capacitor
Parallel Connection
This is the most popular method of connection. The capacitor is connected in para llel to the
unit. The voltage rating of the capacitor is usually the same as or a li ttle higher than the system
voltage.
Go to Content ↑
Series Connection
This method of connection is not much common. Even though the voltage regulation is much
high in this method,
It has many disadvantages.
2/1/2014 Defining Size and Location of Capacitor in Electrical System (1) | EEP
http://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 9/9
© 2013 EEP - Electrica l Engineering Porta l. All Rights Reserved | Privacy Policy | 33 queries in
0.856 seconds.
Powered by CsanyiGroup
One is that because of the series connection, in a short circuit condit ion the capacitor should be
able to withstand the high current. The other is that due to the series connection due to the
inductivity of the line there can be a resonance occurring at a certain capacitive value.
This wil l lead to very low impedance and may cause very high currents to flow through the
lines.
Go to Content ↑
Recommended EE articles
jiguparmar - Jignesh Parmar has completed his B.E(Electrical) from Gujarat
University. He is member of Institution of Engineers (MIE),India. Membership
No:M-1473586.He has more than 12 years experience in Transmission -
Distribution-Electrical Energy theft detection-Electrical Maintenance-Electrical
Projects (Planning-Designing-Technical Review-coordination -Execution). He is
Presently associate with one of the leading business group as a Assistant Manager
at Ahmedabad,India. He has published numbers of Technical Articles in "Electrical Mirror",
"Electrica l India", "Lighting India", "Industria l Electrix"(Australian Power Publications) Magazines.
He is Freelancer Programmer of Advance Excel and design useful Excel base Electrica l Programs
as per IS, NEC, IEC,IEEE codes. He is Technical Blogger and Familiar with English, Hindi,
Gujarati, French languages. He wants to Share his experience & Knowledge and help technical
enthusiasts to find suitable solutions and updating themselves on various Engineering Topics.
Become EEP's Contributor and introduce yourself to 70k+ of our readers al l across the web.
TOP
Get