DEMOSS AND
ASSOCIATES
LLC
NO.
REVISION
DESCRIPTION Date
ARCHITECT
MEP
DEMOSS AND ASSOCIATES LLC1188 AMSTERDAM AVENUEATLANTA, GA 30308
ISSUANCE
SHEET TITLE
PERRYCRABB2970 CLAIRMONT ROAD, #850ATLANTA, GA 30329
11/3
/2017 2
:40:4
6 P
M
MP0.01
MECHANICAL/PLUMBINGSCHEDULES AND
LEGEND
2017_ESJ_CON_PT_RMS
100% CONSTRUCTIONDOCUMENTS
NOVEMBER 3, 2017
Author
EM
OR
Y S
AIN
T J O
SE
PH
'S H
OS
PIT
AL
PA
T IE
NT
RO
OM
RE
NO
VA
TIO
NS
LAVATORIESLAVATORIESLAVATORIESLAVATORIESMARKMARKMARKMARK MANUFACTURERMANUFACTURERMANUFACTURERMANUFACTURER MODELMODELMODELMODEL
DIMENSIONS, INCHESDIMENSIONS, INCHESDIMENSIONS, INCHESDIMENSIONS, INCHES
ADAADAADAADA MOUNTMOUNTMOUNTMOUNT MATERIALMATERIALMATERIALMATERIALFAUCETFAUCETFAUCETFAUCET
MOUNTMOUNTMOUNTMOUNTDRAINDRAINDRAINDRAIN COLORCOLORCOLORCOLOR
ACCESSORIESACCESSORIESACCESSORIESACCESSORIES FAUCETFAUCETFAUCETFAUCET ROUGH-IN, NOMINAL INCHESROUGH-IN, NOMINAL INCHESROUGH-IN, NOMINAL INCHESROUGH-IN, NOMINAL INCHES
NOTESNOTESNOTESNOTESOVERALLOVERALLOVERALLOVERALL
L x W x HL x W x HL x W x HL x W x H
BASINBASINBASINBASIN
L x W x DEPTHL x W x DEPTHL x W x DEPTHL x W x DEPTHRIM HEIGHTRIM HEIGHTRIM HEIGHTRIM HEIGHT FAUCET TO BASIN, MINFAUCET TO BASIN, MINFAUCET TO BASIN, MINFAUCET TO BASIN, MIN P-TRAPP-TRAPP-TRAPP-TRAP
INSULATED SUPPLY &INSULATED SUPPLY &INSULATED SUPPLY &INSULATED SUPPLY &
DRAINDRAINDRAINDRAINMANUFACTURERMANUFACTURERMANUFACTURERMANUFACTURER MODELMODELMODELMODEL TYPETYPETYPETYPE HANDLESHANDLESHANDLESHANDLES FINISHFINISHFINISHFINISH MOUNTMOUNTMOUNTMOUNT OUTLETOUTLETOUTLETOUTLET GPMGPMGPMGPM OPERATIONOPERATIONOPERATIONOPERATION HOTHOTHOTHOT COLDCOLDCOLDCOLD WASTEWASTEWASTEWASTE VENTVENTVENTVENT
LAV-1 INTEGRAL -- -- -- 34 10 Y INTEGRAL CORIAN 4" CENTERSPERFORATED
STRAINERWHITE 1.25 x 1.5 Y T&S B-2866-05-LF15
GOOSENECK
RIGID/SWING
CONVERTIBLE4" WRIST BLADES
POLISHED
CHROMEDECK LAMINAR 2 MANUAL 1/2" 1/2" 2" 2"
LAV-3 INTEGRAL -- -- -- 34 10 Y INTEGRAL CORIAN 4" CENTERS
PERFORATED
STRAINER,
OFFSET
WHITE 1.25 x 1.5 Y T&S B-0892-01CR-L22
GOOSENECK
RIGID/SWING
CONVERTIBLE
4" WRIST BLADESPOLISHED
CHROMEDECK LAMINAR 1 MANUAL 1/2" 1/2" 2" 2"
LAV-4 KOHLER KINGSTON K2006 21 x 18 x 12 16 x 10 x 3.125 34 10 YCOUNTER,
SELF-RIMCHINA SINGLE
PERFORATED
STRAINERWHITE 1.25 x 1.5 Y T&S B-0892-01CR-L22
GOOSENECK
RIGID/SWING
CONVERTIBLE
4" WRIST BLADESPOLISHED
CHROMEDECK LAMINAR 1 MANUAL 1/2" 1/2" 2" 2"
MARK MFTR MODEL TYPE NECK SIZE DIMENSIONS MAX CFM MAX
A.P.D.
MAX
N.C.NOTES
S1 PRICE SCD LOUVER FACE 12 24x24 550 10.05 21
10 380 0.05 18
8 245 0.05 15
14 750 0.05 22
15 860 0.06 23
S2 PRICE SCD LOUVER FACE 12x12 10.078
6
245
135
17
15
S3 PRICE 620 SIDEWALL SEE PLANS SEE PLANS SEE PLANS 1,80.10 25
S4 PRICE SPD SQUARE PANEL 12 24x24 550 10.05 21
10 380 0.05 18
8 245 0.05 15
14 750 0.05 22
15 860 0.06 23
S5 PRICE TDB 3 PLENUM SLOT SEE PLANS SEE PLANS SEE PLANS 1,20.10 25
S6 PRICE LFD LAMINAR 10 48x24 240 10.05 22
S7 PRICE LFD LAMINAR 8 24x24 140 10.08 22
S8 FLANDERS CH-22 LAMINAR HEPA SEE PLANS SEE PLANS SEE PLANS 10.50 22
S9 PRICE RFD RADIAL 12 48x24 700 10.05 27
S10 PRICE LBP 15A LINEAR BAR SEE PLANS SEE PLANS SEE PLANS 1,20.10 25
S11 PRICE RVD VORTEX 10 24x24 200 10.26 28
S12 PRICE PDN PERFORATED 14 24x24 970 10.10 25
R1/E1 PRICE 80 EGG CRATE 24x24 30.10 2514
12
10 320
16
18
R2/E2 PRICE 80 EGG CRATE 8 24x12 200 30.10 25
460
640
830
1060
130020
6
10
110
320
PRICE 0.10 25
PRICE 0.10 25
PRICE 0.10 25
PRICE 0.10 25
PRICE 0.10 25
PRICE 0.10 25
3,4
3,5
3,6
3,7
3
3
SEE PLANS
SEE PLANS
SEE PLANS
NOTE 4
2200
970
12x12
24x24
24x24
24x24
SEE PLANSSEE PLANS
SEE PLANS
SEE PLANS
PLENUM
-
NOTE 4
PERFORATED
EGG CRATE
FILTER RETURN
LOW SIDEWALL
HIGH SIDEWALL
EGG CRATER3/E3
R4/E4
R5/E5
R6/E6
R7
R8
80
635
635
80FF
80
PDDR
1 S = SUPPLY AIR FROM COOLING/HEATING AIR SYSTEM, V = SUPPLY AIR FROM
DEDICATED VENTILATION SYSTEM (IF APPLICABLE).
2 INFORMATION REGARDING LENGTH, NUMBER OF SLOTS, WIDTH OF SLOTS, ETC. TO BE
OBTAINED FROM DUCT PLANS.
3 R = RETURN AIR TO COOLING / HEATING AIR SYSTEM, E = EXHAUST AIR.
4 SEE R2 FOR SIZING CRITERIA FOR MARK R3.
5 MOUNT TOP OF HIGH SIDEWALL RETURN 12" FROM TOP OF WALL. FRONT BLADES
PARALLEL TO THE FLOOR. ARRANGE TO BLOCK LINE OF SIGHT.
6 MOUNT BOTTOM OF LOW SIDEWALL RETURN 6" ABOVE FINISHED FLOOR. FRONTBLADES
PARALLEL TO THE FLOOR. ARRANGE TO BLOCK LINE OF SIGHT.
7 NECK SIZING FOR FILTER GRILLES ARE SIMILAR TO R1/E1. SEE PLANS FOR NECK SIZE.
8 MOUNT TOP OF HIGH SIDEWALL SUPPLY 12" FROM TOP OF WALL. FRONT BLADES
SHALL BE VERTICAL.
SEE PLANS
DIFFUSERS, REGISTERS, AND GRILLES
S EXISTING EXISTING EXISTING EXISTING SEE PLANS SEE PLANS 10.05 23
R/E EXISTING EXISTING EXISTING EXISTING SEE PLANS SEE PLANS 30.10 25
MITERED ELBOW WITH TURNING VANES
RADIUS ELBOW WITH NO. OF TURNING VANES INDICATED
VOLUME DAMPER
ACCESS PANELA.P.
SHADED AREAS INDICATE QUADRANTS OF DIFFUSER TO BE BLANKED OFF
CEILING DIFFUSER - TYPE & CFM GIVEN
EXISTING DUCT TO BE REMOVED
SUPPLY AIR DUCT - RISE OR DROP
EXHAUST, RETURN OR O.A. INTAKE DUCT - RISE OR DROP
STEAM SUPPLY MAIN - PRESSURE SHOWN (LPS, MPS, HPS)
CONDENSATE RETURN MAIN - (LPC, MPC, HPC)MPC
70#
24x12
24x12
24x12
24x12
P
24x12
12"Ø
23x10Ø
RECTANGULAR AIR DUCT - FIRST DIMENSION IS SIDE SHOWN
AIR DUCT WITH INTERNAL INSULATION
AIR DUCT WITH ACOUSTICAL VINYL WRAP
ROUND DUCT
FLAT OVAL DUCT
EXISTING DUCT TO REMAIN
FIRE DAMPER
FLEXIBLE DUCT-SAME SIZE AS DIFFUSER INLET
AIR DISTRIBUTION VANES AT SUPPLY GRILLE
TRANSFER GRILLE
TRANSFER GRILLE WITH SOUND TRAP IN WALL
THREE-WAY MIXING OR DIVERTING VALVE
2-WAY THROTTLING VALVE
GATE VALVE
GLOBE VALVE
BALANCING VALVE
BALL VALVE
BUTTERFLY VALVE
BUTTERFLY VALVE
CHECK VALVE
FLOW CONTROL ORIFICE
STRAINER
CONCENTRIC REDUCER
ECCENTRIC REDUCER-FLAT ON BOTTOM
ECCENTRIC REDUCER-FLAT ON TOP
UNION
THERMOMETER
PRESSURE GAUGE
DRIP POINT
VENT
DRAIN
HOT WATER SUPPLY
HOT WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
ARROW INDICATES DIRECTION OF FLOW
GRADE ARROW - GRADE DOWN IN DIRECTION OF ARROW
PUMPED STEAM CONDENSATE RETURN
THERMOSTAT
HUMIDISTAT
MOTOR OPERATED DAMPER
INDICATES NEW DUCTWORK OR EQUIPMENT
INDICATES EXISTING DUCTWORK OR EQUIPMENT TO REMAIN
INDICATES EXISTING DUCTWORK OR EQUIPMENT TO BE REMOVED
(R)
(D)
(E)
(N)
M.O.D.
CR
CS
HS
HR
D
V
DESCRIPTIONSYMBOL
HVAC SYMBOLS
D
24x12
TFR. GR.
24x12
TFR. GR.
T
H
SMOKE DETECTOR, DUCT MOUNTED
CEILING RETURN OR EXHAUST AIR GRILLE
14x8
14x8
SIDEWALL SUPPLY GRILLE,
FACE DIMENSIONS
INDICATED
SIDEWALL RETURN OR EXHAUST
GRILLE,
FACE DIMENSIONS INDICATED
CONNECT TO EXISTING
(RB)
INDICATES EXISTING DUCTWORK OR EQUIPMENT; TO BE RELOCATED (DEMO PLAN) / RELOCATED (NEW PLAN)
INDICATES EXISTING DUCTWORK OR EQUIPMENT; TO BE REBALANCED (DEMO PLAN) / REBALANCED WITH NEW QUANTITIES
SHOWN (NEW PLAN)
S1250
S1250
S1250
S1250
S1250
F
SMOKE DAMPERS
THROUGH PENETRATION FIRE STOPX
COMBINATION FIRE AND SMOKE DAMPERC
WATER CLOSETSWATER CLOSETSWATER CLOSETSWATER CLOSETS
MARKMARKMARKMARKBOWLBOWLBOWLBOWL
FLUSH VALVEFLUSH VALVEFLUSH VALVEFLUSH VALVE SEATSEATSEATSEATROUGH-IN, NOMINALROUGH-IN, NOMINALROUGH-IN, NOMINALROUGH-IN, NOMINAL
INCHESINCHESINCHESINCHESNOTESNOTESNOTESNOTES
MANUFACTURERMANUFACTURERMANUFACTURERMANUFACTURER MODELMODELMODELMODEL ADAADAADAADA MOUNTMOUNTMOUNTMOUNT SPUDSPUDSPUDSPUD MATERIALMATERIALMATERIALMATERIAL RIM HEIGHTRIM HEIGHTRIM HEIGHTRIM HEIGHT COLORCOLORCOLORCOLORBEDPANBEDPANBEDPANBEDPAN
LUGSLUGSLUGSLUGSMANUFACTURERMANUFACTURERMANUFACTURERMANUFACTURER MODELMODELMODELMODEL GPFGPFGPFGPF OPERATIONOPERATIONOPERATIONOPERATION BEDPAN WASHERBEDPAN WASHERBEDPAN WASHERBEDPAN WASHER OFFSETOFFSETOFFSETOFFSET
OPENOPENOPENOPEN
FRONTFRONTFRONTFRONTCOVERCOVERCOVERCOVER COLDCOLDCOLDCOLD WASTEWASTEWASTEWASTE VENTVENTVENTVENT
WC-1 KOHLERKINGSTON
K-4325Y WALL TOP CHINA 17 WHITE N SLOAN ROYAL 111 1.28 MANUAL N N Y N 1 1/4" 4" 2"
SINKSSINKSSINKSSINKSMARKMARKMARKMARK TYPETYPETYPETYPE MANUFACTURERMANUFACTURERMANUFACTURERMANUFACTURER MODELMODELMODELMODEL
DIMENSIONS, INCHESDIMENSIONS, INCHESDIMENSIONS, INCHESDIMENSIONS, INCHES
ADAADAADAADA MOUNTMOUNTMOUNTMOUNT CARRIERCARRIERCARRIERCARRIER MATERIALMATERIALMATERIALMATERIAL DRAINDRAINDRAINDRAINFAUCETFAUCETFAUCETFAUCET
MOUNTMOUNTMOUNTMOUNTCOLORCOLORCOLORCOLOR
ACCESSORIESACCESSORIESACCESSORIESACCESSORIES FAUCETFAUCETFAUCETFAUCET ROUGH-IN, NOMINAL INCHESROUGH-IN, NOMINAL INCHESROUGH-IN, NOMINAL INCHESROUGH-IN, NOMINAL INCHES
NOTESNOTESNOTESNOTESOVERALLOVERALLOVERALLOVERALL
L x W x HL x W x HL x W x HL x W x H
BASINBASINBASINBASIN
L x W x DEPTHL x W x DEPTHL x W x DEPTHL x W x DEPTHP-TRAPP-TRAPP-TRAPP-TRAP
INSULATED SUPPLY &INSULATED SUPPLY &INSULATED SUPPLY &INSULATED SUPPLY &
DRAINDRAINDRAINDRAINMANUFACTURERMANUFACTURERMANUFACTURERMANUFACTURER MODELMODELMODELMODEL TYPETYPETYPETYPE HANDLESHANDLESHANDLESHANDLES FINISHFINISHFINISHFINISH MOUNTMOUNTMOUNTMOUNT OUTLETOUTLETOUTLETOUTLET GPMGPMGPMGPM OPERATIONOPERATIONOPERATIONOPERATION HOTHOTHOTHOT COLDCOLDCOLDCOLD WASTEWASTEWASTEWASTE VENTVENTVENTVENT
MSB-1 MOP SINK BASIN STERN WILLIAMS HL 1800 24 x 24 x 12 21 x 21 x 10 N FLOOR ---TERRAZO WITH
STAINLESS STEEL CAPSDOME WALL WHITE 3" N FIAT 830-AA
FAUCET WITH HOSE &
BRACKET & MOP HANGERCROSS
ROUGH
CHROMEWALL
MALE HOSE
THREAD3 MANUAL 1/2" 1/2" 2" 2"
BLOCKING IN WALL FOR FAUCET. STAINLESS STEEL GUARD ON DROP
EDGE. VACUUM BREAKER.
-
GALLEY PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
MED
STORAGE
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
NURSE STATION
1140.01
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
5E 5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E5E
5E
5E
TREATMENT
GALLEY
NURSE STATION
1141.01
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
STORAGE
MED
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
B5-12
B5-13
B5-11
B5-10
B5-9
B5-7
B5-8
B5-5
B5-6
B5-3
B5-4
B5-1
B5-2
B5-25
B5-24
B5-23
B5-22
B5-21
B5-20
B5-51
B5-19
B5-18
B5-17
B5-16
B5-15
B5-14
B5-52
B5-61
B5-60
B5-62
B5-30
B5-31
B5-28
B5-29
B5-26
B5-27
B5-49
B5-50
B5-48
B5-47
B5-46
B5-45
B5-44
B5-43
B5-42
B5-41
B5-40
B5-39
B5-38
B5-37
B5-36
B5-34
B5-35
B5-32
B5-33
Scale
Project number
Date
Drawn by
DEMOSS AND
ASSOCIATES
LLC
NO.
REVISION
DESCRIPTION Date
ARCHITECT
MEP
DEMOSS AND ASSOCIATES LLC1188 AMSTERDAM AVENUEATLANTA, GA 30308
ISSUANCE
SHEET TITLE
PERRYCRABB2970 CLAIRMONT ROAD, #850ATLANTA, GA 30329
1/8" = 1'-0"
11/3
/2017 2
:13:3
6 P
M
MP1.05
MECHANICAL/PLUMBINGPLANS - EAST &
WEST
2017_ESJ_CON_PT_RMS
100% CONSTRUCTIONDOCUMENTS
NOVEMBER 3, 2017
Author
EM
OR
Y S
AIN
T J O
SE
PH
'S H
OS
PIT
AL
PA
T IE
NT
RO
OM
RE
NO
VA
TIO
NS
1/8" = 1'-0"MP1.051 FIFTH FLOOR - EAST MECHANICAL/ PLUMBING PLAN
1/8" = 1'-0"MP1.052 FIFTH FLOOR - WEST MECHANICAL/PLUMBING PLAN
SHEET NOTES:SHEET NOTES:SHEET NOTES:SHEET NOTES:1 PROVIDE NEW LAV-1. LAV-1 IS A SOLID SURFACE, INTEGRAL BOWL LAVATORY. REFER TO PLUMBING FIXTURE
SCHEDULE. CONNECT NEW 2” DRAIN AND NEW 2” VENT TO EXISTING UTILITIES FROM THE DEMOLISHED
LAVATORY. CONNECT ½” HW AND ½” CW TO EXISTING UTILITIES FROM THE DEMOLISHED LAVATORY.
2 EXISTING WATER CLOSET TO REMAIN. VERIFY PROPER OPERATION. PROVIDE A UNIT PRICE TO REPLACE THE
EXISTING FLUSH VALVE AND TO REPLACE THE EXISTING WATER CLOSET.
3 EXISTING SHOWER TO REMAIN. VERIFY PROPER OPERATION. PROVIDE UNIT PRICE TO REPLACE EXISTING
SHOWER VALVES.
4 PROVIDE NEW LAV-3. LAV-3 IS A SOLID SURFACE, INTEGRAL BOWL LAVATORY. REFER TO PLUMBING FIXTURE
SCHEDULE. CONNECT NEW 2” DRAIN AND NEW 2” VENT TO EXISTING UTILITIES FROM THE DEMOLISHED
LAVATORY. CONNECT ½” HW AND ½” CW TO EXISTING UTILITIES FROM THE DEMOLISHED LAVATORY.
5 REMOVE EXISTING HEADWALLS. INSTALL NEW MEDICAL GAS OUTLETS IN WALL TO REPLACE EXISTING OUTLETS.
6 EXISTING VAV TERMINAL UNIT TO REMAIN. REPLACE ALL CONTROLLERS WITH DDC. REPLACE THERMOSTATS
AND UPDATE GRAPHICS TO BAS.
1
2
3
4
44
4
1
1
1
1
1
1
1
1
1
1
1
2
3
2
3
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
2
2
2
2
2
2
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
5
5
5
5
5
5
5
5
5
5
5
5
5
5
1
2
3
1
1
1
1
1
1
1
1
1
1
1
2
3
2
3
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
2
2
2
2
2
2
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5 5
5
5
5
55
5
5
5
5
5
5
5
5
5
5
5
5
5
6
6
6
6
6
6
6
6
6
6
6
6
66
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
66
66
6
66
6
6
6
6
6
6
6
6
6
6
6
6
6
6
N N0 1' 2' 4' 8' 16' 32'0 0 1' 2' 4' 8' 16' 32'0
6
-
REF.
NIC.
GALLEY
TREATMENT
GALLEY
OFFICEOFFICEOFFICE
SOILED UTILITY
HYDRO STORAGE
4230.07
CONSULT
113.06
WAITING
0.00
CONFERENCE
0.00
TOILET
0.00
LOCKERS
0.00
BATH
0.00
TOILET
TOILET
0.00
JANITOR
0.00
STAFF WORK
4230.06
HYDRO 03
4230.10
HYDRO 02
4230.09
HYDRO 01
4230.08
5E
5W
5W
555
55
729
5
5
55
5
5
5
5
729.06
729.10729.09729.08
86.81 SF
126.14 SF
85.97 SF
111.89 SF111.89 SF111.89 SF
137.17 SF153.29 SF
79.03 SF
112.93 SF
171.97 SF32.81 SF
51.55 SF
47.08 SF
24.89 SF
24.89 SF
22.17 SF
216.64 SF
80.63 SF102.75 SF103.66 SF
8'-10"
8"
8'-10"
8"
8'-10"
8"
8"
9'-8 1
/2 "
1'-0"
8"
3'-0" 2'-4" 8" 9'-6" 8" 10'-0" 8" 12'-8" 8" 11'-0" 8" 10'-0" 8" 12'-8" 8"8" 1"
FF
FF
REF.
NIC.
GALLEY
TREATMENT
GALLEY
OFFICEOFFICEOFFICE
CONSULT
113.06
WAITING
T.
JAN
IT
5E
5W
5W
555
5
FF
FF
B5-59
B5-58
B5-55
B5-54
B5-56
B5-53
B5-57
B5-52
14x5
8x5
8x5
12x4
8x5
R3510 R3
75
R375
12x6
R375
12x6
46x18
28x32 28x32
36x24
46x16
8x5
S175
R375
S1155
S1160
B5-52
B5-53
B5-57
B5-56
B5-55
B5-54
B5-58
B5-59
B5-61
B5-60
46x18
12x6
14x5
8x5
8x5S1
160
S1155
12x4
R375
28x32 28x32
36x24
46x168x5
12x4
8x5
R3510
S175
6ø
R375
R375
S2100
R3100
Scale
Project number
Date
Drawn by
DEMOSS AND
ASSOCIATES
LLC
NO.
REVISION
DESCRIPTION Date
ARCHITECT
MEP
DEMOSS AND ASSOCIATES LLC1188 AMSTERDAM AVENUEATLANTA, GA 30308
ISSUANCE
SHEET TITLE
PERRYCRABB2970 CLAIRMONT ROAD, #850ATLANTA, GA 30329
1/8" = 1'-0"
11/3
/2017 3
:08:0
2 P
M
MP2.05
MECHANICAL/PLUMBINGPLANS - CORE
2017_ESJ_CON_PT_RMS
100% CONSTRUCTIONDOCUMENTS
NOVEMBER 3, 2017
Author
EM
OR
Y S
AIN
T J O
SE
PH
'S H
OS
PIT
AL
PA
T IE
NT
RO
OM
RE
NO
VA
TIO
NS
1/8" = 1'-0"MP2.051 FIFTH FLOOR - MECHANICAL/PLUMBING DEMOLITON PLAN - CORE
1/8" = 1'-0"MP2.052 FIFTH FLOOR - MECHANICAL/PLUMBING PLAN - CORE
SHEET NOTES (DEMO):SHEET NOTES (DEMO):SHEET NOTES (DEMO):SHEET NOTES (DEMO):1 EXTEND EXISTING SA DUCT AND RELOCATE ASSOCIATED DIFFUSER. SEE NEW PLAN.
2 REMOVE BRANCH DUCT AND ASSOCIATED GRILLE. CAP BACK AT MAINS.
3 REMOVE EXISTING FIXTURES AND ASSOCIATED PIPING ABOVE CEILING/BELOW FLOOR. PREPARE
UTILITIES FOR FUTURE CONNECTIONS.
SHEET NOTES:SHEET NOTES:SHEET NOTES:SHEET NOTES:1 EXISTING VAV TERMINAL UNIT TO REMAIN. REPLACE ALL CONTROLLERS WITH DDC. REPLACE
THERMOSTATS AND UPDATE GRAPHICS TO BAS.
2 COORDINATE LOCATION OF DIFFUSER/GRILLE WITH NEW CEILING GRID.
3 PROVIDE NEW WC-1/LAV-4. CONNECT 1 1/4” CW, 2" V, 4" W TO EXISTING UTILITIES FROM THE
REMOVED WATER CLOSET. PROVIDE 1/2" CW, HW 2"V,W FOR LAV-4
4 PROVIDE NEW MSB-1. CONNECT 1/2" CW,HW 2" V,WTO EXISTING UTILITIES FROM THE REMOVED
FIXTURE.
5 AREA PROTECTED AS LIGHT HAZARD UNLESS OTHERWISE INDICATED. JANITOR CLOSET AND
STORAGE PROTECTED AS ORDINARY HAZARD GROUP 1.
6 RELOCATE EXISTING VAV TERMINAL UNIT TO ALLOW ACCESS TO CONTROLS FROM LAY-IN CEILING
AREA. CUT/EXTEND DUCT AND HW COIL PIPING AS REQUIRED AND RECONNECT TO RELOCATED
TERMINAL UNIT.
7 RELOCATE EXISTING SA DIFFUSER AS REQUIRED TO FIT INTO NEW LAY-IN CEILING GRID.
REBALANCE TO CFM QUANTITY INDICATED.
11
1
1
1
1
1
11
1
N0 1' 2' 4' 8' 16' 32'0
0 1' 2' 4' 8' 16' 32'0
N
2
1
1
1
2
2
2
2
2
3
3
3
3 3
4
5
6 6
7
-
T TFIFTH FLOOR
5LC 5LB 5LA 5EC 5EA
5NH 5NL
5ED 5EB 5LD 5LE 5LF112KVA
400A/3P
C.B.
112KVA
3-3/0&1#6 IN 2-1/2''C.
4-500 MCM
IN 3 1/2''C.
4-500 MCM IN 3 1/2''C.
4LB 4LA 4EA
4-4/0 IN 2 1/2''C.4-500 MCM IN 3 1/2''C.
NDPB
6NH
4-500 MCM&1#2 IN 4''C.
3#1+1#6(G) IN 2''C.
4DP
3-3/0&1#6 IN 2-1/2''C. 4LD
6LF
4-500 MCM IN 3 1/2''C.
4EB
4-500 MCM IN 3 1/2''C.
4-500 MCM IN 3 1/2''C.
3#1+1#6(G) IN 2''C.
4-4/0 IN 2 1/2''C.
100100
CONDUIT
KEY:
---400--- FEEDER. FEEDERS ARE 4 - WIRE PLUS
GROUND UNLESS NOTED OTHERWISE.
---G--- INDICATES #10 AWG PANELBOARD
BONDING CONDUCTOR IN 1/2" CONDUIT.
TERMINATE THE CONDUCTOR ON THE
EQUIPMENT GROUNDING BAR OF EACH
PANELBOARD.
20
30
40
50
60
70
80
90
100
125
#12
FEEDER
DESIGN
COPPER AWG SIZES
PHASE &
NEUTRALGROUND
#12 1/2"
FEEDER LEGEND
150
175
200
225
250
300
350
400
500
600
700
800
1000
1200
1600
2000
2500
3000
#10
#8
#6
#4
#4
#3
#2
#1
#1/0
#1/0
#2/0
#3/0
#4/0
#250
#350
#500
(2)#3/0
(2)#250
(2)#350
(2)#400
(2)#500
(3)#400
(3)#600
(4)#600
(5)#500
(6)#600
(8)#500
#10
#10
#10
#10
#8
#8
#8
#6
#6
#6
#6
#4
#4
#4
#3
#3
(2)#3
(2)#2
(2)#1
(2)#1/0
(2)#1/0
(3)#2/0
(3)#3/0
(4)#4/0
(5)#250
(6)#350
(8)#400
3/4"
1"
1-1/4"
1-1/4"
1-1/4"
1-1/2"
1-1/2"
2"
2"
2"
2-1/2"
2-1/2"
3"
3"
3-1/2"
4"
(2)2-21/2"
(2)3"
(2)3-1/2"
(2)3-1/2"
(2)4"
(3)3-1/2"
(3)4"
(4)4"
(5)4"
(6)4"
(8)4"
5000 (12)#600 (12)2#350 (12)4"
4000 (10)#600 (10)#500 (10)4"
110 #1 #6 2"
RG-6 COAXIAL CABLE
TO TELECOMM. ROOM
LABEL PER
SPECIFICATIONS
DUPLEX
RECEPTACLE
PROVIDED
UNDER SAME
COVER
PROVIDE TWO-GANG COMMERCIAL METAL TV BOX LEGRAND MODEL #TV2MW
SYMBOL:
LIGHTING FIXTURESLIGHTING FIXTURESLIGHTING FIXTURESLIGHTING FIXTURESTYPETYPETYPETYPE DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTION MTGMTGMTGMTG VOLTAGEVOLTAGEVOLTAGEVOLTAGE LAMPSLAMPSLAMPSLAMPS MANUFACTURERMANUFACTURERMANUFACTURERMANUFACTURER
A ARCHITECTURAL LED SCONCE, 3500K COLOR TEMPERATURE, COORDINATE FINISH AND SIZE WITH OWNER/ARCHITECT. TYPE TO MATCH 7TH FLOOR PATIENT ROOM SCONCE. W 120 V LED
14W
SCOTT ARCH LIGHTING #S3000
B 2’X4’ RECESSED LED TROFFER, FROSTED #12 ACRYLIC PRISMATIC .125 LENS, CRS HOUSING, FLAT STEEL DOOR WITH REINFORCED MITERED CORNERS, HINGE/LATCH ON BOTH SIDES OF DOOR,
WHITE ENAMEL FINISH, 5000 DELIVERED LUMENS, 4000K COLOR TEMPERATURE, L90 AT 60,000 HOURS, 80+ CRI.
R 120/277 V LED
36W
METALUX #24GR
LITHONIA #2GTL
OR PRE-APPROVED EQUAL
C 2’X2’ RECESSED LED TROFFER, FROSTED #12 ACRYLIC PRISMATIC .125 LENS, CRS HOUSING, FLAT STEEL DOOR WITH REINFORCED MITERED CORNERS, HINGE/LATCH ON BOTH SIDES OF DOOR,
WHITE ENAMEL FINISH, 2400 DELIVERED LUMENS, 4000K COLOR TEMPERATURE, L90 AT 60,000 HOURS, 80+ CRI.
R 120/277 V LED
20W
METALUX #22GR
LITHONIA #2GTL
OR PRE-APPROVED EQUAL
D 6’’ LED DOWNLIGHT, 1500 DELIVERED LUMENS, 0-10V DIMMING DRIVER, 90CRI MINIMUM, 4000K COLOR TEMPERATURE, MEDIUM BEAM DISTRIBUTION, SEMI-SPECULAR CLEAR FINISH. R 120/277 V LED
16W
PORTFOLIO #LD6B
PEACHTREE LIGHTING #6BLRD
INDY #L6
OR PRE-APPROVED EQUAL
F 2’X2’ RECESSED LED TROFFER, ACRYLIC FROSTED LENS, CRS HOUSING, FLAT STEEL DOOR WITH REINFORCED MITERED CORNERS, WHITE ENAMEL FINISH, 3500 DELIVERED LUMENS, 4000K COLOR
TEMPERATURE, L80 AT 60,000 HOURS, 85+ CRI.
R 120/277 V LED
30W
METALUX #22CZ
PHILIPS #DAY-BRITE 2EVG
OR PRE-APPROVED EQUAL
G LED STRIP LIGHT TO FIT IN EXISTING LIGHTING FIXTURE PROVISION, 1500 DELIVERED LUMENS, 4000K COLOR TEMPERATURE, FIELD VERIFY LENGTH AND CONFIGURATION WITH OWNER/ARCHITECT. R 120/277 V LED
46W
FOCAL POINT #FSM4L
AXIS #BBR
COORDINATE WITH OWNER/ARCHITECT
H 6’’ LED DOWNLIGHT, 1500 DELIVERED LUMENS, 0-10V DIMMING DRIVER, 90CRI MINIMUM, 4000K COLOR TEMPERATURE, SINGLE WALL WASH DISTRIBUTION, SEMI-SPECULAR CLEAR FINISH. R 120/277 V LED
16W
PORTFOLIO #LD6B
OR PRE-APPROVED EQUAL
J 2’ DIAMETER ROUND ARCHITECTURAL RECESSED FIXTURE, 2200 DELIVERED LUMENS, 82 CRI, 4000K COLOR TEMPERATURE, 0-10V DIMMING DRIVER, FROSTED CONCAVE ACRYLIC LENS. R 120/277 V LED
38W
H.E. WILLIAMS #RND
OR PRE-APPROVED EQUAL
L 2’ DIAMETER ROUND ARCHITECTURAL RECESSED FIXTURE TO FIT IN EXISTING LIGHTING FIXTURE PROVISION, 2200 DELIVERED LUMENS, 82 CRI, 3500K COLOR TEMPERATURE, 0-10V DIMMING
DRIVER, COORDINATE FEATURES WITH OWNER/ARCHITECT.
R 120/277 V LED
38W
H.E. WILLIAMS #RND
COORDINATE WITH OWNER/ARCHITECT
M 2’X4’ RECESSED MULTIFUNCTION PATIENT CARE LED TROFFER, READING, AMBIENT, AND EXAMINATION LIGHT DISTRIBUTION, CLEAR LENS, 13000 DELIVERED LUMENS WITH ALL LIGHTS ON, 2-LOW
VOLTAGE CONTROLLERS: 1 = AMBIENT, 1 = READING. 0.156’’ MIN. A19 PRISMATIC ACRYLIC LENS, DOOR SECURED BY CAPTIVE SCREWS, WET LOCATION-COVERED CEILING LABEL, SEAL AND
GASKET LENS TO DOOR, DOOR TO FRAME, AND FRAME TO CEILING, INSET DOOR WITH WHITE FINISH.
90W LED EXAM
25W LED READING
45W LED AMBIENT
R 120/277 V LED
25W
45W
90W
KENALL #MPC24
H.E. WILLIAMS #MDB
FOCAL POINT #APOLLO 8
FAIL SAFE #MAE LED
N 8’’ LED DOWNLIGHT TO FIT IN EXISTING LIGHTING FIXTURE PROVISION, MATCH EXISTING TYPE AND CONFIGURATION, 3000 DELIVERED LUMENS, 3500K COLOR TEMPERATURE, 0-10V DIMMING
DRIVER, COORDINATE FEATURES WITH OWNER/ARCHITECT.
R 120/277 V LED
35W
PORTFOLIO #LD8A
COORDINATE WITH OWNER/ARCHITECT
O LED MODULE COVE LIGHT, FIELD CURVABLE, 2.5" O.C. LED SPACING. PROVIDE POWER SUPPLIES, POLYCARBONATE MOUNTING CLIPS AND END CAPS AS REQUIRED FOR A COMPLETE INSTALLATION,
COORDINATE FEATURES WITH OWNER/ARCHITECT.
S 120/277 V 3.6W/FT
LED
TIVOLI #CLL-SF-2.5-WH-12
COORDINATE WITH OWNER/ARCHITECT
P 6’’ LED DOWNLIGHT, 2000 DELIVERED LUMENS, 0-10V DIMMING DRIVER, 90CRI MINIMUM, 3500K COLOR TEMPERATURE, MEDIUM BEAM DISTRIBUTION, SEMI-SPECULAR CLEAR FINISH,
COORDINATE CONFIGURATION WITH OWNER/ARCHITECT.
R 120/277 V LED
16W
PORTFOLIO #LD6B
PEACHTREE LIGHTING #6BLRD
COORDINATE WITH OWNER/ARCHITECT
LIGHTING FIXTURE NOTES:LIGHTING FIXTURE NOTES:LIGHTING FIXTURE NOTES:LIGHTING FIXTURE NOTES:MOUNTING LEGENDMOUNTING LEGENDMOUNTING LEGENDMOUNTING LEGEND: P-PENDANT S-SURFACE
R- RECESSED W-WALL
1. ALL FLUORESCENT BALLAST SHALL BE ELECTRONIC AND FACTORY INSTALLED.
MAXIMUM 0.78 BALLAST FACTOR. PROVIDE FOR ALL FLUORESCENT ELECTRONIC
BALLASTS.
2. PLASTIC LENS SHALL BE "APPROVED LIGHT TRANSMITTING PLASTIC", SEE
SPECIFICATIONS.
3. PROVIDE LIGHTING FIXTURE WITH NECESSARY FRAME, FLANGE, END PLATES,
ETC. AFTER VERIFICATION OF CEILING CONSTRUCTION (EXPOSED GRID, GYPBOARD,
ETC.)
4. PRISMATIC ACRYLIC LENSES SHALL BE A19, 0.156" MINIMUM.
5. PRIOR TO OWNER OCCUPANCY, CONTRACTOR SHALL "BURN-IN" FLUORESCENT
LAMPS IN DIMMING FLUORESCENT FIXTURES FOR A MINIMUM OF 100 HOURS
CONTINUOUSLY.
6. PROVIDE PROGRAMMABLE RAPID START ELECTRONIC BALLAST AND DRIVERS
WITH LESS THAN 10% THD.
Scale
Project number
Date
Drawn by
DEMOSS AND
ASSOCIATES
LLC
NO.
REVISION
DESCRIPTION Date
ARCHITECT
MEP
DEMOSS AND ASSOCIATES LLC1188 AMSTERDAM AVENUEATLANTA, GA 30308
ISSUANCE
SHEET TITLE
PERRYCRABB2970 CLAIRMONT ROAD, #850ATLANTA, GA 30329
12" = 1'-0"
11/3
/2017 2
:27:2
7 P
M
E0.01
ELECTRICALSCHEDULES
2017_ESJ_CON_PT_RMS
100% CONSTRUCTIONDOCUMENTS
NOVEMBER 3, 2017
PEB
EM
OR
Y S
AIN
T J O
SE
PH
'S H
OS
PIT
AL
PA
T IE
NT
RO
OM
RE
NO
VA
TIO
NS
AN
NM
OS
ELECTRICAL SYMBOLS
ABOVE FINISHED FLOORAFF
LIGHT FIXTURE.
SEE LIGHTING FIXTURE SCHEDULE
LIGHT FIXTURE CONNECTED TO
EMERGENCY CIRCUIT.
SEE LIGHTING FIXTURE SCHEDULE
VOICE/DATA OUTLET ABOVE CASE WORK OR IF NO CASEWORK 48" AFF WITH 3/4"C. STUBBED TO ACCESSIBLE CEILING
SPACE UNLESS OTHERWISE NOTED
VOICE
DATA
VOICE / DATA
VOICE/DATA OUTLET 18" AFF WITH 3/4"C. STUBBED TO ACCESSIBLE CEILING SPACE
UNLESS OTHERWISE NOTED
VOICE
DATA
VOICE/DATA
AMPLIFIERA
DUPLEX RECEPTACLE UNDER COMMON COVER, 125V, 42"AFF
DUPLEX RECEPTACLE, 125V, 18" AFF
MONITOR OUTLET : 2-GANG BOX WITH BLANK COVER IN PATIENT CONSOLE OR AT HEIGHT NOTED. PROVIDE 1-1/4"C. TO CEILING, UNLESS
OTHERWISE NOTED. PROVIDE A LEGRAND #TV2MW OR EQUAL. COORDINATE EXACT HEIGHT WITH ARCHITECTURAL DRAWINGS
SPECIAL POWER RECEPTACLE, 18" AFF
TELEPHONE EQUIPMENT BACKBOARD, 3/4" THICK PLYWOOD, SIZE AS INDICATED ON DRAWINGS
EXIT SIGN, CEILING MOUNTED, DIRECTIONAL
ARROWS AS SHOWN, SHADING INDICATES
FACE OF SIGN. ALL FIXTURES TYPE X,
UNLESS OTHERWISE NOTED
TV ANTENNA OUTLET, CONTROL OUTLET AND 15V, 120V, DUPLEX RECEPTACLE. 8" BELOW FINISHED CEILING, UNLESS
OTHERWISE NOTED. PROVIDE A LEGRAND #TV2MW OR EQUAL. COORDINATE EXACT HEIGHT WITH ARCHITECTURAL DRAWINGS
TV ANTENNA OUTLET AND 15V, 120V, DUPLEX RECEPTACLE. 8" BELOW FINISHED CEILING, UNLESS OTHERWISE NOTED. PROVIDE
A LEGRAND #TV2MW OR EQUAL. COORDINATE EXACT HEIGHT WITH ARCHITECTURAL DRAWINGS
EXIT SIGN, WALL MOUNTED, DIRECTIONAL
ARROWS AS SHOWN, SHADING INDICATES
FACE OF SIGN. ALL FIXTURES TYPE X,
UNLESS OTHERWISE NOTED
TIC MARKS INDICATE NUMBER OF PHASE AND NEUTRAL CONDUCTORS IN CONDUIT. IN ADDITION,
EACH CONDUIT SHALL HAVE AN EQUIPMENT GROUNDING CONDUCTOR SIZED PER NEC 250-122.
NO TIC MARKS INDICATES 2#12+#12G
CONDUIT, WITH WIRING AS INDICATED, CONCEALED IN CEILING, WALL OR FURRED SPACE
CONDUIT, WITH WIRING AS INDICATED. RUN EXPOSED
SINGLE RECEPTACLE, 125V, 18" AFF
NOTES:
GF :20A RECEPTACLE WITH INTEGRAL GROUND FAULT CIRCUIT
INTERRUPTER
TWO DUPLEX RECEPTACLE ABOVE CASEWORK OR IF NO CASEWORK 18" AFF
TWO DUPLEX RECEPTACLE UNDER COMMON COVER, 125V, 42"AFF
20A GFTAMPER
PROOF
SINGLE POLE SWITCH, 48" AFF
D DIMMER SWITCH, 48" AFF
THREE - WAY SWITCH, 48" AFF
RECEPTACLES
CONDUIT, WITH WIRING AS INDICATED, HOMERUN TO PANEL OR EQUIPMENT.
HOMERUNS TO EXISTING PANELS ARE DESIGNATED WITH BREAKER SIZES (AMPS/POLE)
EMERGENCY BATTERY PACK LIGHT FIXTURE
CONDUIT, WITH WIRING AS INDICATED, CONCEALED IN FLOOR, WALL OR UNDERGROUND
SWITCHES
CONDUIT
EXIT SIGNS
LIGHT FIXTURES
VOICE & DATA SYSTEMS
3
POWER
ABBREVIATIONS
NEW ITEM
NEW and EXISTING LINE STYLES
EXISTING ITEM
DENOTES AREA OUTSIDE SCOPE OF WORK
DEMO and SCOPE REGIONS
INDICATES AREA OF DEMOLITION
DEMOLITION ITEM
OUTLET BOX FOR CARD READER WITH 3/4" C. STUBBED TO ACCESSIBLE CEILING SPACE. MAKE 120V CONNECTION TO DOORS ELECTRIC
STRIKE, 48" AFFCR
OUTLET BOX FOR KEY PAD WITH 3/4" C. STUBBED TO ACCESSIBLE CEILING SPACE.
MAKE 120V CONNECTION TO DOORS ELECTRIC STRIKE, 48" AFFK
WIRELESS ACCESS POINT
MOTOR (HP / VOLTS / PHASE)
JUNCTION BOX, 18" AFFJ
DRY TYPE TRANSFORMERT
JUNCTION BOX ABOVE CEILING. INSTALL IN ACCESSIBLE LOCATION OR
SURFACE MOUNT ON CEILING IN EXPOSED CONDUIT INSTALLATIONJ
PUSH PAD
480Y / 277V, PANELBOARD AS SCHEDULED
208Y / 120V, PANELBOARD AS SCHEDULEDLOW VOLTAGE SWITCHLV
OS OCCUPANCY SENSOR SWITCH, 48" AFF
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANT SENSOR.
(WATTSTOPPER LMDC-100 OR EQUIVALENT BY LEVITON OR
HUBBELL)
OUTLET OR OTHER DEVICE CONNECTED TO EMERGENCY POWER CIRCUITE
EXISTING RELOCATEDER
EXISTINGEX
USB RECEPTACLE, HUBBELL #USB8300W OR EQUALUSB
WEATHERPROOF DEVICE. PROVIDE HINGED GASKETED COVERWP
FIRE ALARM SYSTEMS FIRE ALARM SPEAKER AND STROBE, 80"AFF
FIRE ALARM VISUAL ONLY, 80" AFF
FIRE ALARM MANUAL STATION, 48" AFFF
SMOKE DETECTOR SURFACE MOUNTED ON CEILINGS
NURSE CALL AUDIO / VISUAL PATIENT STATION HEADWALL
NURSE CALL AUDIO / VISUAL MASTER STATION
NURSE CALL VISUAL PATIENT STATION HEADWALL
NURSE CALL DOME LIGHT
NURSE CALL SYSTEMSNURSE STATION VISUAL SYSTEM ANNUNCIATOR
BATHROOM PULL STATION
NURSE CALL EMERGENCY ASSIST STATION
PERIPHERAL STATION
NURSE CALL BED INTERFACE UNIT, IN BED DOCKER OR WALL
T TIMER SWITCH, 48" AFF
E0.01
1 RISER DIAGRAM
ELECTRICAL SPECIFICATIONSELECTRICAL SPECIFICATIONSELECTRICAL SPECIFICATIONSELECTRICAL SPECIFICATIONS
2. USE IMC OR UL LISTED EMT OF CONCRETE ENCASEMENT WHEN EMBEDDED IN SLABS OF BUILDING STRUCTURE.
E. MINIMUM RACEWAY SIZE: 1/2-INCH TRADE SIZE EXCEPT RNC FOR OUTDOORS; 1-INCH MINIMUM.
F. VIBRATING EQUIPMENT: USE LIQUID TIGHT FLEXIBLE CONDUIT FOR FINAL TERMINATIONS TO MOTORS, TRANSFORMERS, OR OTHER VIBRATING EQUIPMENT.
G. USE GROUND BUSHINGS ON ALL FEEDER TERMINATIONS AND CRITICAL PANEL BRANCH CIRCUIT TERMINATIONS. CONNECT EACH BUSHING WITH BONDING WIRE AND TERMINATE TO ENCLOSURE
OR GROUND BUS.
1.8 WIRING DEVICES
A. PROVIDE DIMMING BALLAST OR 0-10V DIMMING DRIVER IN FIXTURES CONNECTED TO DIMMERS.
B. USE 20A, 120/277V SWITCHES AND 20A RECEPTACLES UNLESS OTHERWISE NOTED.
C. USE HOSPITAL GRADE RECEPTACLES AND SPECIFICATION GRADE SWITCHES.
D. DO NOT USE WIRING DEVICES MANUFACTURED WITH MULTICONDUCTOR SNAP-IN PIG TAILS OR MANUFACTURED WITH PRE-TERMINATED WIRING LEADS.
E. LOCATIONS:
1. PEDIATRIC AREA: USE TAMPER RESISTANT RECEPTACLES IN PEDIATRIC AREA, CORRIDORS, WAITING ROOMS, GENERAL CARE PATIENT AREAS, AND EXAM ROOMS.
2. SINKS: USE GFCI RECEPTACLES WITHIN 6’ OF ALL SOURCES OF WATER SUCH AS SINKS AND TUBS.
F. AFTER INSTALLING WIRING DEVICES AND AFTER ELECTRICAL CIRCUITRY HAS BEEN ENERGIZED, TEST FOR PROPER POLARITY, GROUND CONTINUITY, AND COMPLIANCE WITH REQUIREMENTS.
G. CONNECT BONDING JUMPER AND INSTALL FACEPLATE NAMEPLATE.
1.9 SURGE PROTECTION DEVICES (SPD)
A. COMPLY WITH ANSI/IEEE C62.41.1, C62.41.2, C62.33 AND C62.45, NEC ARTICLE 285. PROVIDE DEVICES LISTED UNDER UL 1449 3RD EDITION.
B. MOUNT EXTERNAL SPD AS IN CLOSE PROXIMITY TO THE PANELBOARD AND PROTECTED BY A CIRCUIT BREAKER.
C. SUBMIT PRODUCTS BY CURRENT TECHNOLOGY, EMERSON, OR SSI MEETING THIS SPECIFICATION.
1.10 SWITCHBOARDS AND PANELBOARDS
A. SUBMIT SHOP DRAWINGS AND DATA SHEETS.
1. ENGAGE FACTORY TO TEST AND SUBMIT REPORT RESULTS PER NFPA 99.
B. MAKE SERVICE ENTRANCE EQUIPMENT SE RATED.
C. IDENTIFY EACH CIRCUIT AND CIRCUIT MODIFICATION WITH ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE ON PANEL SCHEDULE PER NEC 408.4.
D. USE DOOR-IN-DOOR CONTINUOUS HINGE COVER FOR PANELBOARDS.
E. USE ELECTRONIC ADJUSTABLE LSIG (LSIA ON EMERGENCY POWER DEVICES) WHEN DEVICE RATING IS ABOVE 400A.
F. COMPLY WITH NEMA PB 2.
G. USE MOLDED CASE, THERMAL MAGNETIC, GROUP MOUNTED DEVICES. PROVIDE AMPERE INTERRUPTING AND WITHSTAND RATING TO MATCH EXISTING EQUIPMENT.
H. USE TIN PLATED ALUMINUM PHASE AND NEUTRAL BAR AND COPPER GROUND BAR.
I. USE HINGED FRONT PANELS. USE MECHANICAL LUG TERMINATIONS EXCEPT ON GENERATOR PARALLELING GEAR USE COMPRESSION LUG TERMINATIONS.
J. SEPARATE MAIN DEVICE SECTION FROM BRANCH DEVICE SECTIONS WITH METAL BARRIER.
K. ANCHOR TO WALLS OR CONCRETE PAD.
L. PERFORM LOAD BALANCING.
1.11 LOW VOLTAGE DRY TYPE TRANSFORMERS (600V AND LESS)
A. USE HIGH EFFICIENCY TRANSFORMERS.
B. USE ALUMINUM WINDINGS.
C. INSULATION CLASS: 220 DEG C, UL-COMPONENT-RECOGNIZED INSULATION SYSTEM WITH A MAXIMUM OF 150 DEG C RISE ABOVE 40 DEG C AMBIENT TEMPERATURE.
D. PROVIDE A TOTAL OF 6 TAPS, ABOVE AND BELOW, NORMAL FULL CAPACITY.
E. SUPPORT FROM STRUCTURE. ANCHOR TO BASE OR TRAPEZE SUPPORT. USER VIBRATION PADS OR SPRINGS.
F. SOUND LEVELS: NEMA ST 20 STANDARD
G. LOOSEN SHIPPING BOLTS AT TIME OF INSTALLATION.
H. KEEP 6 INCH CLEARANCE AROUND TRANSFORMER FOR HEAT RELEASE.
1.12 LIGHTING
A. USE 0.156 INCH THICK ACRYLIC LENSES WHEN LENSES ARE SPECIFIED.
B. USE 0-10V DIMMING DRIVER IN LED FIXTURES CONNECTED TO DIMMERS.
C. PROVIDE LAMPS THAT ARE OPERABLE AT THE TIME OF FINAL COMPLETION.
1.18 FIRE ALARM SYTEMS
A. PROVIDE A COMPLETE AND OPERATING SYSTEM IN COMPLIANCE WITH NFPA 101, NFPA 70, NFPA 90A, AND NFPA 72.
B. INCLUDE SMOKE SENSORS, HEAT SENSORS, SENSOR BASES, CONTROL MODULES, MONITOR MODULES, ADDRESSABLE MANUAL PULL STATIONS, VOICE EVACUATION, DOOR MAGNETS, DUCT
SMOKE SENSOR PROBES, ETC; THAT IS IN KEEPING WITH CODE AND THE EXISTING INSTALLATION. PROVIDE ITEMS AS INDICATED IN CONTRACT DOCUMENTS.
C. SUBMIT DATA SHEETS AND SHOP DRAWINGS WITH DEVICE AND WIRING DIAGRAM FOR REVIEW. USE SHOP DRAWINGS FOR INSTALLATION.
D. SUBMIT PLANS, DETAILS, AND VOLTAGE DROP CALCULATIONS FOR NOTIFICATION APPLIANCE CIRCUITS, BATTERY SIZE CALCULATIONS AND INPUT/OUTPUT MATRIX. PROVIDE FLOOR PLANS
INDICATING DEVICE LOCATIONS SHOWING THE ADDRESS OF EACH ADDRESSABLE DEVICE.
E. ENGAGE MANUFACTURER TO TEST AND CERTIFY INSTALLATION.
F. COORDINATE AND PROVIDE SUBMITTALS AND INSPECTIONS BY THE AUTHORITY HAVING JURISDICTION.
G. PROVIDE POWER SUPPLIES, BATTERIES, BATTERY CHARGER, CONTROL PANELS, ADDRESSABLE POINTS, PRINTER AND DISPLAY AS REQUIRED TO MAKE A COMPLETE AND OPERABLE SYSTEM.
H. UPDATE ENERGY PLANT CENTRAL COMMAND ANNUNCIATOR TO REFLECT FIRE ALARM CHANGES.
I. HVAC: LOCATE DETECTORS NOT CLOSER THAN 3 FEET FROM AIR-SUPPLY DIFFUSER OR RETURN-AIR OPENING.
J. DUCT SMOKE DETECTORS: COMPLY WITH NFPA 72 AND NFPA 90A. INSTALL SAMPLING TUBES SO THEY EXTEND THE FULL WIDTH OF THE DUCT.
K. REMOTE STATUS AND ALARM INDICATORS: INSTALL IN NEAREST PUBLIC SPACE FOR EACH SMOKE DETECTOR AND EACH SPRINKLER WATER-FLOW SWITCH AND VALVE-TAMPER SWITCH THAT IS
NOT READILY VISIBLE FROM NORMAL VIEWING POSITION.
L. AUDIBLE ALARM-INDICATING DEVICES: INSTALL NOT LESS THAN 6 INCHES BELOW THE CEILING. INSTALL BELLS AND HORNS ON FLUSH-MOUNTED BACK BOXES WITH THE DEVICE-OPERATING
MECHANISM CONCEALED BEHIND A GRILLE.
M. VISIBLE ALARM-INDICATING DEVICES: INSTALL ADJACENT TO EACH ALARM BELL OR ALARM HORN AND AT LEAST 6 INCHES BELOW THE CEILING.
N. DEVICE LOCATION-INDICATING LIGHTS: LOCATE IN PUBLIC SPACE NEAR THE DEVICE THEY MONITOR.
O. POST INDICATOR VALVE: CONNECT TO POST INDICATE VALVE IN PROJECT SITE WITH A MONITOR MODULE.
P. SMOKE CONTROL: USE SMOKE DETECTORS AND CONTROL RELAY TO START FAN USED FOR SMOKE CONTROL IN ATRIUMS, OPERATING ROOMS, AND FOR STAIR PRESSURIZATION.
Q. ASSEMBLY OCCUPANCY: PROVIDE VOICE EVACUATION SYSTEM.
R. CONNECT 120V POWER TO FIRE ALARM CONTROL PANEL, POWER SUPPLIES, AND AMPLIFIERS.
S. INFRASTRUCTURE
1. UTILIZE FIRE ALARM CONTROL PANEL, REMOTE PANELS AND POWER SUPPLIES SO EACH UNIT HAS 30 PERCENT SPARE CAPACITY.
T. USE ADJUSTABLE HORNS OR CHIMES AND PROVIDE ADJUSTMENT AT TIME OF SUBSTANTIAL COMPLETION.
U. WIRING METHOD: INSTALL WIRING IN RACEWAY EXCEPT IN ACCESSIBLE CEILING SPACES AND IN GYPSUM BOARD PARTITIONS, WHERE CABLE WIRING METHOD MAY BE USED. USE UL-LISTED
PLENUM CABLE IN ENVIRONMENTAL AIR SPACES INCLUDING PLENUM CEILINGS. CONCEAL CABLE AND RACEWAY WIRING EXCEPT IN UNFINISHED SPACES.
1.19 NURSE CALL
A. SUBMIT DATA SHEETS AND SHOP DRAWINGS WITH DEVICE AND WIRING DIAGRAM FOR REVIEW. USE SHOP DRAWINGS FOR INSTALLATION.
B. ENGAGE MANUFACTURER TO TEST AND CERTIFY INSTALLATION.
C. PROVIDE PATIENT STATIONS, PATIENT CONTROL UNITS, STAFF STATIONS, DUTY STATIONS, DOME LIGHTS, MASTER STATION(S), CONTROL PANEL(S), EMERGENCY STATIONS, AND CODE BLUE
STATIONS; ARRANGED TO PROVIDE A COMPLETE AND OPERATING SYSTEM.
D. CONNECT TV CONTROL OUTLET TO PATIENT STATION CONTROL.
E. CONNECT BED OUTLET TO BED TO FACILITATE SIDE-COM BED CONTROLS.
F. MATCH EXISTING MANUFACTURER IF ANY, OTHERWISE; USE WESCOM, RAULAND, SIMPLEX, OR DUKANE.
G. CUSTOMIZE MASTER STATION DISPLAY TO SPECIFIC PROJECT ROOM NAMING AND NUMBER CONVENTION PER THE FACILITIES DIRECTIONS.
H. PROVIDE OWNER TRAINING.
I. WIRING METHOD: INSTALL WIRING IN RACEWAY EXCEPT WITHIN CONSOLES, DESKS, AND COUNTERS; AND EXCEPT IN ACCESSIBLE CEILING SPACES AND IN GYPSUM BOARD PARTITIONS, WHERE
CABLE WIRING METHOD MAY BE USED. USE UL-LISTED PLENUM CABLE IN ENVIRONMENTAL AIR SPACES INCLUDING PLENUM CEILINGS. CONCEAL CABLE AND RACEWAY WIRING EXCEPT IN
UNFINISHED SPACES.
ELECTRICAL SPECIFICATIONSELECTRICAL SPECIFICATIONSELECTRICAL SPECIFICATIONSELECTRICAL SPECIFICATIONS
1.1 GENERAL
A. DEFINITION
1. FURNISH: ITEM DELIVERED TO PROJECT SITE, STORED, PROTECTED, AND NOT INCORPORATED INTO WORK UNDER THIS DIVISION OF THE SPECIFICATIONS.
2. INSTALL: ITEM ALREADY ON SITE, FURNISHED BY ANOTHER ENTITY, OR FURNISHED BY THIS DIVISION OF THE SPECIFICATION; AND REQUIRED TO BE INCORPORATED IN WORK INDICATED BY THIS
DIVISION OF THE SPECIFICATION. RECEIVE, MOUNT AND CONNECT, COMPLETE, AND READY FOR OPERATION.
3. PROVIDE: ITEM PURCHASED AND DELIVERED TO PROJECT SITE AND INCORPORATED INTO WORK OR CONSTRUCTION ACTIVITY INDICATED BY THIS DIVISION OF THE SPECIFICATION, COMPLETE
AND READY FOR OPERATION.
4. SYSTEM: A COMPLETE FURNISHED AND INSTALLED ITEM OF FIRST CLASS WORKING ORDER, READY FOR OPERATION.
5. EXTEND: BEGINNING AT THE POINT OF ORIGIN, CONNECTING, OR INTERFACE USING COMPATIBLE EQUIVALENT MATERIAL AND EXTEND TO FINAL CONNECTION OR INTERFACE, COMPLETE AND
READY FOR OPERATION.
B. SUBMITTALS
1. SUBMIT SHOP DRAWINGS INDICATING COMPLIANCE WITH SPECIFIED FEATURES FOR EACH PRODUCT OR SYSTEM UNIQUE TO THIS PROJECT.
2. SUBMIT DATA SHEETS FOR LIGHT FIXTURES AND ELECTRICAL DISTRIBUTION ITEMS. SUBMIT SHOP DRAWINGS AND DATA SHEETS AS NOTED ELSEWHERE IN THE CONTRACT DOCUMENTS.
3. SUBMIT TEST REPORT DATA.
C. COORDINATION
1. COORDINATE ARRANGEMENT, MOUNTING, AND SUPPORT OF ELECTRICAL EQUIPMENT TO KEEP OTHER DIVISIONS WORK FROM CONFLICTING WITH WORKING CLEARANCE AROUND EQUIPMENT.
KEEP DUCTWORK AND PIPES AWAY FROM THE AREA ABOVE ELECTRICAL DISTRIBUTION EQUIPMENT.
2. COORDINATE POWER REQUIREMENTS FOR MECHANICAL EQUIPMENT INCLUDING VAV TERMINALS, DAMPERS, CONTROL PANELS, AND PRESSURE MONITORS. INSTALL UP TO SIX TERMINAL UNITS
ON ONE 120 VAC, 20 AMP CIRCUIT, AND PROVIDE WIRING, AND MAKE CONNECTION TO EACH TERMINAL UNIT. DIVISION 23 TO PROVIDE TRANSFORMER AND DISCONNECT AT TERMINAL UNITS.
3. NOTIFY ARCHITECT OF DEVIATIONS FROM INTENDED ELECTRICAL CHARACTERISTICS PRIOR TO EQUIPMENT PURCHASE, MATERIAL PURCHASE, OR CONSTRUCTION ACTIVITY RELATED TO
EQUIPMENT IN QUESTION.
4. PROVIDE, AT NO ADDITIONAL COST TO THE PROJECT, MATERIAL, AND WORK RELATED TO CONTRACTOR CHANGES OF ELECTRICAL CHARACTERISTICS SPECIFIED BY THIS AND OTHER DIVISIONS OF
THE SPECIFICATIONS.
D. PERMITS AND INSPECTION
1. OBTAIN PERMITS AND PAY INSPECTION FEES REQUIRED TO COMPLETE THE WORK AND RECEIVE A CERTIFICATE OF OCCUPANCY.
2. PERFORM OPERATION AND TESTING PROCEDURES REQUIRED BY AUTHORITIES HAVING JURISDICTION.
E. ELECTRICAL CONNECTIONS
1. MAKE ARRANGEMENTS FOR CONNECTION TO SERVICE, EXTENSION OF SERVICE AND METER INSTALLATION. PAY COSTS ASSOCIATED WITH PERMANENT SERVICE CONNECTION.
F. EXISTING CONDITION
1. VISIT THE PROJECT SITE AND BECOME THOROUGHLY FAMILIAR WITH EXISTING CONDITIONS PRIOR TO OFFERING A BID.
2. REPORT TO THE ARCHITECT UNFORESEEN SITE CONDITIONS THAT MAY AFFECT WORK AT THE TIME OF DISCOVERY.
G. MANUFACTURERS
1. MATCH PERFORMANCE SPECIFIED FOR EACH COMPONENT OR SYSTEM.
2. PROVIDE MATERIALS FOR A COMPLETE FUNCTIONING SYSTEM.
3. MANUFACTURERS LISTED ARE SUBJECT TO COMPLIANCE WITH REQUIREMENTS.
4. PROVIDE PRODUCTS BY THE MANUFACTURER(S) SPECIFIED.
5. PROVIDE PRODUCTS FROM ONE MANUFACTURER FOR SWITCHBOARD, SWITCHGEAR, PANELBOARDS, MOTOR CONTROL CENTERS, CIRCUIT BREAKERS, AND ENCLOSED SWITCHES; SWITCHES AND
RECEPTACLES.
6. HONOR FACILITIES PRODUCT OR MANUFACTURER PREFERENCES.
H. TESTING
1. PERFORM TEST APPROPRIATE FOR WORK INSTALLED TO VERIFY WORKING ORDER.
2. PERFORM CONTINUITY TESTS.
3. PERFORM PHASE ROTATION TEST FOR EACH SERVICE AND SEPARATELY DERIVED SYSTEM.
I. PENETRATIONS
1. USE SLEEVES FOR MASONRY WALL AND FLOOR PENETRATIONS. USE RATED SEALANT TO MAINTAIN PARTITION’S UL RATED ASSEMBLY. USE SLEEVE SEALS ON BELOW GRADE PENETRATIONS.
USE SEAL OFF FITTING ON ROOF PENETRATIONS. USE RAYCHEM RDSS ACCESSIBLE THROUGH A PULL BOX FOR BELOW GRADE CONDUIT PENETRATION.
J. OVERCURRENT DEVICES
1. PROVIDE FULLY PREPARED SPACE FOR MOUNTING OF FUTURE DEVICES INDICATED IN DOCUMENTS AS “SPACE”.
2. PROVIDE OVERCURRENT COORDINATION AND FAULT CURRENT STUDY.
K. MOUNTING HEIGHT
1. MEASURE INDICATED MOUNTING HEIGHTS TO BOTTOM OF UNIT FOR SUSPENDED ITEMS, TO BOTTOM OF OUTLET BOX FOR WALL-MOUNTED ITEMS BELOW 36”, TO TOP OF OUTLET BOX FOR
WALL-MOUNTED ITEMS ABOVE 36”. ARCHITECTURAL DOCUMENTS TAKE PRECEDENCE WHEN DETERMINING MOUNTING HEIGHTS. COORDINATE LOCATION AND HEIGHT WITH ARCHITECTURAL
ELEVATIONS.
L. METERING
1. METERING EQUIPMENT WILL BE PROVIDED FOR EACH ELECTRICAL SERVICE. COORDINATE METERING WITH THE UTILITY COMPANY AND PROVIDE METERING COMPONENTS IN ACCORDANCE WITH
THE UTILITY COMPANY'S REQUIREMENTS.
M. BRANCH CIRCUITS
1. PROVIDE BRANCH CIRCUITS AS EITHER TWO, THREE, AND FOUR WIRE CIRCUITS, RUN FROM THE PANELS TO OUTLETS AS INDICATED ON THE DRAWINGS. PROVIDE EACH 120V OR 277V CIRCUIT
WITH A NEUTRAL CONDUCTOR. USE ONE NEUTRAL FOR EVERY PHASE CONDUCTOR UNLESS OTHERWISE NOTED.
2. USE EMT FOR INTERIOR CIRCUITS AND FEEDERS EXCEPT IN BUSINESS OCCUPANCIES OF TENANT SPACES WHERE MC CABLE WITH FULL SIZE INSULATED GROUND IS ACCEPTABLE.
3. PROVIDE CONDUCTORS FOR 20A, 120V CIRCUITS LESS THAN 100 FEET AT MINIMUM OF #12 AWG. OTHERWISE, PROVIDE #10 MINIMUM CONDUCTORS FOR 20A, 120V CIRCUITS GREATER THAN
100 FEET.
N. LOW VOLTAGE CABLES
1. FROM OUTLET BOX WITH PLASTER RING STUB CONDUIT INTO ACCESSIBLE CEILING SPACE. INSTALL PULL STRING.
1.2 GROUNDING AND BONDING
A. USE INSULATED NO. 10 BONDING JUMPER CONNECTED TO GROUNDED TERMINAL OF EACH RECEPTACLE AND OUTLET BOX.
B. USE INSULATED NO. 10 BONDING JUMPER CONNECTED TO GROUNDED OUTLET AND METAL HOUSING OF WALL-MOUNTED LIGHT FIXTURES.
C. USE INSULATED NO. 10 BONDING JUMPER TO CONNECT METAL SURFACES NEAR OR ON HYDRO MASSAGE TUBS, POOLS, OR WHIRLPOOLS TO MOTOR HOUSING, COLD WATER PIPE, HOT WATER
PIPE, DRAIN PIPE, GRAB BARS, CAST IRON TUB, OTHER METAL SURFACES, AND THEN TO MOTOR’S EQUIPMENT GROUNDING TERMINAL.
D. USE INSULATED BONDING WIRE IN FLEXIBLE CONDUIT MORE THAN SIX FEET LONG, OR 1-1/4 INCH DIAMETER, OR NON-JACKETED FLEXIBLE CONDUIT CONTAINING CIRCUITS RATED MORE THAN 20
AMPS. BOND TO EACH END OF FLEXIBLE CONDUIT TERMINATION.
E. BOND TRANSFORMER CASES WITH EQUIPMENT GROUNDING CONDUCTOR ORIGINATING AT MAIN SWITCHBOARD.
F. BOND “XO” TERMINAL WITH GROUNDING ELECTRODE CONDUCTOR RUN TO EFFECTIVELY GROUNDED BUILDING STEEL OR TO DISTRIBUTED GROUNDING ELECTRODE SYSTEM GROUND BUS.
1.3 SESMIC RESTRAINT
A. SEISMIC CONSULTANT: HIRE A REGISTERED ENGINEER WITH LICENSURE IN THIS STATE TO PROVIDE SEISMIC SUPPORT ANCHORING METHODS AND SUPERVISE INSTALLATION OF ANCHORS.
B. REFER TO ARCHITECT OR STRUCTURAL DOCUMENTS FOR IBC SEISMIC DATA TO BE USED BY SEISMIC CONSULTANT.
C. USE CABLES, RODS, PIPES, OR STRUTS WITH DAMPING SPRINGS AS DIRECTED BY SEISMIC CONSULTANT TO REDUCE LATERAL MOVEMENT OF SUPPORTED ITEMS.
1.4 SUPPORTS
A. ALL SUPPORTS SHALL BE METALLIC.
B. USE MECHANICAL EXPANSION ANCHOR TO SUSPEND FROM CONCRETE SLABS OR ATTACH TO CONCRETE WALLS.
C. ATTACH EQUIPMENT TO CONCRETE PADS WITH ANCHOR BOLTS.
1.5 ELECTRICAL IDENTIFICATIONS
A. LABEL ALL ELECTRICAL EQUIPMENT WITH ENGRAVED PLASTIC NAMEPLATE TO MATCH FACILITY’S SIZE AND COLOR STANDARDS.
B. LABEL ALL DEVICE FACEPLATES WITH THE PANEL AND CIRCUIT NUMBER SERVING THE DEVICE. USE SIZE AND COLOR TO MATCH THE FACILITY’S STANDARDS.
C. USE PERMANENT MARKER TO IDENTIFY WIRING WITHIN CONCEALED OUTLET BOXES.
1.6 CONDUCTORS AND CABLES
A. USE COPPER CONDUCTORS.
B. USE XHHW WITHOUT PULLING COMPOUND FOR ISOLATED POWER SYSTEMS.
C. SERVICE ENTRANCE AND FEEDERS: USE TYPE XHHW-2, SINGLE CONDUCTORS IN RACEWAY.
D. USE PULL BOXES FOR EVERY 200 FEET OF CONDUCTOR LENGTH.
E. USE CABLE STRAIN RELIEF SUPPORTS IN KEEPING WITH MANUFACTURER AND NEC REQUIREMENTS.
F. ENERGIZE CIRCUITS THEN INFRARED SCAN AND DOCUMENT TEMPERATURE OF WIRE TERMINATIONS. TIGHTEN LOOSE TERMINATIONS.
1.7 RACEWAYS AND BOXES
A. GALVANIZED SHEET METAL OUTLET AND DEVICE BOXES:
1. 1-1/2 INCHES X 4 INCHES X 4 INCHES MINIMUM SIZE.
2. USE RAISED DEVICE COVER.
3. USE BOX SUPPORT FOR BRACING INSIDE HOLLOW STUD WALLS.
4. USE BOXES LISTED FOR CONTACT WITH CONCRETE WHERE INSTALLATION REQUIRES SAME.
B. INDOOR RACEWAYS: USE EMT WITH SET SCREW FITTINGS FOR DRY INDOOR LOCATIONS. USE COMPRESSION FITTINGS IN DAMP OR WET INDOOR LOCATIONS.
C. EMBEDDED IN CONCRETE:
1. EMBED SERVICE LATERALS IN CONCRETE DUCT BANK FROM THE SECONDARY OF THE UTILITY SOURCE UNTIL THEY ENTER THE SERVICE DISCONNECTING MEANS.
E0.01
3 TYPICAL TELEVISION OUTLET
-
LOBBY
PUBLIC
LOBBY
SERVICE
REF.
NIC.
GALLEY
TREATMENT
GALLEY
OFFICEOFFICEOFFICE
CONSULT
113.06
WAITING
ADA T. T.
JAN
IT
5E
5W
5W
555
5
86.81 SF
126.14 SF
85.97 SF
111.89 SF111.89 SF111.89 SF
112.93 SF
137.17 SF
137.17 SF 137.17 SF
137.17 SF
137.17 SF
OSOS
OS
T
D
D D D
LOBBY
PUBLIC
LOBBY
SERVICE
REF.
NIC.
GALLEY
TREATMENT
GALLEY
OFFICEOFFICEOFFICE
CONSULT
113.06
WAITING
ADA T. T.
JAN
IT
5E
5W
5W
555
5
86.81 SF
126.14 SF
85.97 SF
111.89 SF111.89 SF111.89 SF
112.93 SF
137.17 SF
137.17 SF 137.17 SF
137.17 SF
137.17 SF
S
S
F F
C
C
FF
J
HH
J
D D
J
DD
J
D D
J
HH
JF
JF
D D
J
D D
J
D
J
D
F
F
J
D D
5NH-13
G
5NL-25
5NL-26
EE
E
5EA-25
5EA-27
5EA-29
Scale
Project number
Date
Drawn by
DEMOSS AND
ASSOCIATES
LLC
NO.
REVISION
DESCRIPTION Date
ARCHITECT
MEP
DEMOSS AND ASSOCIATES LLC1188 AMSTERDAM AVENUEATLANTA, GA 30308
ISSUANCE
SHEET TITLE
PERRYCRABB2970 CLAIRMONT ROAD, #850ATLANTA, GA 30329
1/8" = 1'-0"
11/3
/2017 2
:27:2
9 P
M
E1.05
ELECTRICAL COREPLANS
2017_ESJ_CON_PT_RMS
100% CONSTRUCTIONDOCUMENTS
NOVEMBER 3, 2017
PEB
EM
OR
Y S
AIN
T J O
SE
PH
'S H
OS
PIT
AL
PA
T IE
NT
RO
OM
RE
NO
VA
TIO
NS
1/8" = 1'-0"E1.051 5TH FLOOR - LIGHTING PLAN - CORE
1/8" = 1'-0"E1.052 5TH FLOOR - POWER & SYSTEMS PLAN - CORE
SHEET NOTES:SHEET NOTES:SHEET NOTES:SHEET NOTES:1 CONNECT TO EXISTING LIFE SAFETY LIGHTING CIRCUIT SERVING THE AREA. VERIFY LIGHTING
LOADS DO NOT EXCEED BRANCH CIRCUIT OR PANEL AMPACITY.
2 COORDINATE MOUNTING HEIGHT AND LOCATION OF TV WITH OWNER PRIOR TO INSTALLATION.
1
GENERAL NOTES:GENERAL NOTES:GENERAL NOTES:GENERAL NOTES:1. PROVIDE A DEDICATED NEUTRAL FOR EACH CIRCUIT.
2. PROVIDE INSULATED EQUIPMENT GROUND TO EACH RECEPTACLE
CIRCUIT.
3. PROVIDE NEW EQUIPMENT GROUND AS REQUIRED.
4. PROVIDE INSULATED #10 GROUND BETWEEN NORMAL AND CRITICAL
PANEL SERVING THE SAME PATIENT AREA.
5. VERIFY RECEPTACLE LOADS DO NOT EXCEED BRANCH CIRCUIT OR
PANEL AMPACITY.
6. REUSE EXISTING CIRCUITS IN SPACE.
7. COORDINATE EXACT MOUNTING HEIGHT AND LOCATION OF ALL
DEVICES WITH ARCHITECTURAL PLANS PRIOR TO INSTALLATION.
8. CONNECT FIRE ALARM DEVICES TO EXISTING FIRE ALARM SYSTEM.
9. REFER TO PANEL SCHEDULES FOR NUMBER OF POLES AND PHASE
PER CIRCUIT.
10. CONNECT 120V TO EACH NEW VAV BOX. PROVIDE NO MORE THAN 20
BOXES ON ONE 120V CIRCUIT. COORDINATE THE EXACT LOCATION AND
QUANTITY WITH DIVISION 23 DRAWINGS. RECONNECT EXISTING VAV
CONTROL POWER IF EXISTING VAV BOXES ARE RELOCATED.
NN
2
-
CLOSET
ELECT
GALLEY PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
MED
STORAGE
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
NURSE STATION
1140.01
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
5E 5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E5E
5E
5E
86.81 SF
242.96 SF
213.48 SF
213.48 SF
213.48 SF
189.63 SF
189.57 SF
189.63 SF
213.48 SF
213.48 SF
189.57 SF
189.57 SF
838.49 SF
213.48 SF
228.57 SF
213.48 SF
213.48 SF
189.63 SF
189.57 SF
213.45 SF213.45 SF
189.57 SF
189.63 SF
LVLV
LV
LV
J
J
J
J
J
J
J
J
J
J
JJ
JJ
J
J
J
J
J
J
J
J
J
D
D
OS
OS
DDDD
CLOSET
ELECT
TREATMENT
GALLEY
NURSE STATION
1141.01
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
STORAGE
MED
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
126.14 SF
85.97 SF
836.43 SF
189.63 SF
213.48 SF
213.48 SF
189.63 SF
189.57 SF
213.45 SF
213.45 SF
213.48 SF
216.20 SF
242.96 SF
213.48 SF
189.57 SF
189.63 SF
213.48 SF
213.48 SF
189.63 SF
189.57 SF
213.48 SF
213.48 SF
189.57 SF
189.57 SF
213.48 SF
228.57 SF
JJ
J
JJ
J
J
J
J
J
J
JJ
JJ
J
J
J
J
J
J
J
J
OS
OS
D D D D
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
5E
5E
189.63 SF
189.57 SF
LV
LV
J
D
189.63 SF
189.57 SF
5E
5E
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.005E
213.48 SF
213.48 SF
LV
LV
J
213.48 SF
213.48 SF
5E
PATIENT ROOM AND TOILET
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
D
E2.053
E2.054
5ED-26
5ED-27
E
E
E
E
E
E
E E
E
EE
E
E
E
E
E
E
E
E
EE
E
E
MA
M
A
B
B
P P
P
P
P
P
P
P
P
LPPP
P
P
P
O
P
P
P
P
P
N N
N
N
NN
N
N
L
G
G
GGG
L
G
L
G
G
G
G
G
L
L
L
G
G
G
G
5EC-26
5EC-27
B
B
E E
E
E
EE
E
E
E
E
EE
EE
E
EE
E
E
E
E
E
E
N
N
NN
N
N
N N
P
P
P
P
PP
P
P
P
P
P
P
P
P
P
PP
P
P
P
L
L
L
L
L
L
L
G
G
G
G
G
G
G
G
G
G
G
G
G G G
O
M
LVC
E
277V CRITICAL
A
M
LVC
277V
CRITICAL
A
Scale
Project number
Date
Drawn by
DEMOSS AND
ASSOCIATES
LLC
NO.
REVISION
DESCRIPTION Date
ARCHITECT
MEP
DEMOSS AND ASSOCIATES LLC1188 AMSTERDAM AVENUEATLANTA, GA 30308
ISSUANCE
SHEET TITLE
PERRYCRABB2970 CLAIRMONT ROAD, #850ATLANTA, GA 30329
As indicated
11/3
/2017 2
:27:3
1 P
M
E2.05
LIGHTING PLAN
2017_ESJ_CON_PT_RMS
100% CONSTRUCTIONDOCUMENTS
NOVEMBER 3, 2017
PEB
EM
OR
Y S
AIN
T J O
SE
PH
'S H
OS
PIT
AL
PA
T IE
NT
RO
OM
RE
NO
VA
TIO
NS
1/8" = 1'-0"E2.051 5TH FLOOR - EAST LIGHTING PLAN
1/8" = 1'-0"E2.052 5TH FLOOR - WEST LIGHTING PLAN
1/4" = 1'-0"E2.053 5TH FLOOR - TYPICAL PATIENT ROOM - LIGHTING PLAN - TYPE 1
1/4" = 1'-0"E2.054 5TH FLOOR - TYPICAL PATIENT ROOM - LIGHTING PLAN - TYPE 2
N N
NN
1
GENERAL NOTES:GENERAL NOTES:GENERAL NOTES:GENERAL NOTES:1. PROVIDE A DEDICATED NEUTRAL FOR EACH CIRCUIT.
2. COORDINATE EXACT MOUNTING HEIGHT AND LOCATION OF ALL
DEVICES WITH ARCHITECTURAL PLANS PRIOR TO INSTALLATION.
3. CONNECT FIRE ALARM DEVICES TO EXISTING FIRE ALARM SYSTEM.
4. REFER TO PANEL SCHEDULES FOR NUMBER OF POLES AND PHASE
PER CIRCUIT.
5. CONNECT 120V TO EACH NEW VAV BOX. PROVIDE NO MORE THAN 20
BOXES ON ONE 120V CIRCUIT. COORDINATE THE EXACT LOCATION AND
QUANTITY WITH DIVISION 23 DRAWINGS. RECONNECT EXISTING VAV
CONTROL POWER IF EXISTING VAV BOXES ARE RELOCATED.
6. COORDINATE MULTI-FUNCTION LIGHTING FIXTURE WITH BED
LOCATION AND ARCHITECT PRIOR TO INSTALLATION.
7. PROVIDE WIRING WITH REDUNDANT INSULATED GROUND IN ALL
PATIENT CARE AREAS.
8. MATCH ALL EXISTING LIGHTING WITH LED.
SHEET NOTES:SHEET NOTES:SHEET NOTES:SHEET NOTES:1 CONNECT TO AMBIENT AND READING LAMP BALLAST VIA LOW VOLTAGE CONTROLLER TO NURSE
CALL PILLOW SPEAKER.
2 CONNECT TO THE AMBIENT AND READING LIGHT PORTIONS OF THE FIXTURE.
3 CONNECT A RED SINGLE POLE SWITCH TO THE EXAM PORTION OF THE FIXTURE.
4 PROVIDE A 2-WAY/4-POSITION, 120/277V SEQUENTIALLY WIRED LOW VOLTAGE CONTROLLER.
CURBELL LVC-2000, COORDINATE WITH NURSE CALL MANUFACTURE. CONNECT THE NURSE CALL
SYSTEM 24VAC MOMENTARY CONTACT IN PARALLEL WITH THE MOMENTARY CONTACT “LV”
WALL SWITCH SO EITHER CONTACT PERFORMS THE FOLLOWING SEQUENCES:
1.AMBIENT ON/READING LIGHT ON.
2. AMBIENT ON/READING LIGHT OFF.
3.AMBIENT OFF/READING LIGHT ON.
4.AMBIENT OFF/READING LIGHT OFF.
5 REFER TO DETAIL 3/E2.05 FOR TYPICAL PATIENT ROOM LIGHTING PLAN – TYPE 1.
6 REFER TO DETAIL 4/E2.05 FOR TYPICAL PATIENT ROOM LIGHTING PLAN – TYPE 2.
7 REPLACE CENTRAL AREA LIGHTS WITH LED EQUIVALENTS TO FIT IN EXISTING LIGHT FIXTURE
PROVISIONS. RECONNECT TO EXISTING CIRCUITS AND SWITCHES. VERIFY IN FIELD SIZE AND TYPE
WILL FIT.
8 RECONNECT TO EXISTING LIGHTING CIRCUIT IN ROOM.
9 PROVIDE NEW DIMMER SWITCHES TO CONTROL EXISTING LIGHTING CIRCUITS.
2
3
4
2
3
14
5
5
6
6
6
5
6
6
6
5
5
6
6
5
6
6
5
5
6
6
6
66
6
5 5
6
6
55
6
6
5
6
6
5
5
6
6
5
5
6
6
6
6
5
7
7
8
8
8
8
7
7
9
9
-
CLOSET
ELECT
GALLEY PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
MED
STORAGE
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
NURSE STATION
1140.01
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
PATIENT ROOM AND TOILET
1140.00
5E 5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E
5E5E
5E
5E
86.81 SF
242.96 SF
213.48 SF
213.48 SF
213.48 SF
189.63 SF
189.57 SF
189.63 SF
213.48 SF
213.48 SF
189.57 SF
189.57 SF
838.49 SF
213.48 SF
228.57 SF
213.48 SF
213.48 SF
189.63 SF
189.57 SF
213.45 SF213.45 SF
189.57 SF
189.63 SF
CLOSET
ELECT
TREATMENT
GALLEY
NURSE STATION
1141.01
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
PATIENT ROOM AND TOILET
1141.00
STORAGE
MED
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
5W
126.14 SF
85.97 SF
836.43 SF
189.63 SF
213.48 SF
213.48 SF
189.63 SF
189.57 SF
213.45 SF
213.45 SF
213.48 SF
216.20 SF
242.96 SF
213.48 SF
189.57 SF
189.63 SF
213.48 SF
213.48 SF
189.63 SF
189.57 SF
213.48 SF
213.48 SF
189.57 SF
189.57 SF
213.48 SF
228.57 SF
5LF
5LE
5LD
5EB5ED
5LF - 31
5ED - 55ED - 6
5LF - 30
5LF - 29
5ED - 2
5LF - 32
5ED - 1
5ED - 25
5LF - 33
5ED - 24
5LF - 34
5ED - 23
5LD - 30
5LD - 29
5ED - 22
5ED - 21
5LD - 32
5ED - 20
5LD - 31
5ED - 19
5LD - 335ED - 18
5LD - 34
5ED - 17
5LD - 36
5ED - 16
5LD - 35
5LE - 37
5ED - 15
5ED - 14
5LE - 17
5ED - 13
5ED - 12
5LE - 19
5ED - 11
5LE - 20
5LE - 18
5ED - 10
5LE - 21
5LE - 33
5ED - 9
5LE - 35
5ED - 7 5LE - 34
5ED - 8
5EA 5NH
5LC
5LA
5LB
5EC
5EC - 9
5LB - 25
5LB - 33
5EC - 8
5LA - 29
5EC - 7
5LA - 30
5EC - 24
5LA - 31
5EC - 25
5LA - 32
5EC - 6
5LA - 33
5EC - 5
5LA - 34
5EC - 2
5LC - 29
5EC - 1
5EC - 23
5LC - 30
5EC - 22
5LC - 31
5LC - 32
5EC - 21
5LC - 33
5EC - 20
5EC - 19
5LC - 345LC - 35
5EC - 18
5EC - 17
5LB - 34
5EC - 16
5LB - 35
5EC - 15
5LB - 36
5LB - 37
5EC - 14
5LB - 38
5EC - 13
5LB - 39
5EC - 12
5LB - 40
5EC - 11
5LB - 41
5EC - 10 5NL
ACCESSIBLE CEILNG LINE
FLOOR
MONITOR OUTLET: 1 GANG BOX WITH BLANK COVER IN
PATIENT CONSOLE OR AT HEIGHT NOTED. GFCI TYPE.
37-PIN SIDE-COM OUTLET IN PATIENT BED LOCATOR.
E
HEADWALL LEGEND
DUPLEX RECEPTACLE.
EMERGENCY J-BOX CONNECTION FOR HEADWALL UNIT
NORMAL JUNCTION BOX CONNECTION FOR HEADWALL UNIT.
NURSE CALL PATIENT STATION WITH PILLOW
SPEAKER, STAFF EMERGENCY STATION AND
CODE BLUE CALL STATION, ALL UNDER A
COMMON FACEPLATE. PROVIDE ACRYLIC COVER
FOR CODE BLUE BUTTON.
PATIENT UP/DOWN LIGHT FIXTURE.
SIMPLEX BED RECEPTACLE.
NIGHT LIGHT: 7W, 120V.
2 AUX JACKS. PROVIDE 3/4"C. STUBBED ABOVE ACCESSIBLE CEILING.
NC/CB
1 CRITICAL CIRCUIT
2 NORMAL CIRCUITS
M
M
DATA OUTLET. 2 CAT 5E, RJ-45 RECEPTACLES.
VOICE/DATA OUTLET. 2 CAT 5E, RJ-45 RECEPTACLES.
NC
LIGHT SWITCH.
NOTE: PROVIDE GFCI RECEPTACLES ON HEADWALL.
CB
E
EM M
E
FRONT VIEW
LV
LOW-VOLTAGE LIGHT SWITCHLV
Scale
Project number
Date
Drawn by
DEMOSS AND
ASSOCIATES
LLC
NO.
REVISION
DESCRIPTION Date
ARCHITECT
MEP
DEMOSS AND ASSOCIATES LLC1188 AMSTERDAM AVENUEATLANTA, GA 30308
ISSUANCE
SHEET TITLE
PERRYCRABB2970 CLAIRMONT ROAD, #850ATLANTA, GA 30329
As indicated
11/3
/2017 2
:27:3
3 P
M
E3.05
POWER & SYSTEMSPLAN
2017_ESJ_CON_PT_RMS
100% CONSTRUCTIONDOCUMENTS
NOVEMBER 3, 2017
PEB
EM
OR
Y S
AIN
T J O
SE
PH
'S H
OS
PIT
AL
PA
T IE
NT
RO
OM
RE
NO
VA
TIO
NS
1/8" = 1'-0"E3.051 5TH FLOOR - EAST POWER & SYSTEMS PLAN
1/8" = 1'-0"E3.052 5TH FLOOR - WEST POWER & SYSTEMS PLAN
SHEET NOTES:SHEET NOTES:SHEET NOTES:SHEET NOTES:1 PROVIDE NEW HEADWALL. REFER TO DETAIL 3/E3.05 FOR TYPICAL PATIENT ROOM HEADWALL.
ALL OTHER POWER AND DATA DEVICES IN ROOM EXISTING TO REMAIN.
2 RE-USE EXISTING NORMAL CIRCUIT POLE SPACE IN ROOM AND PROVIDE ADDITIONAL CIRCUIT AS
SHOWN IN ROOM.
1
N
GENERAL NOTES:GENERAL NOTES:GENERAL NOTES:GENERAL NOTES:1. PROVIDE A DEDICATED NEUTRAL FOR EACH CIRCUIT.
2. PROVIDE INSULATED EQUIPMENT GROUND TO EACH RECEPTACLE
CIRCUIT.
3. PROVIDE NEW EQUIPMENT GROUND AS REQUIRED.
4. PROVIDE INSULATED #10 GROUND BETWEEN NORMAL AND CRITICAL
PANEL SERVING THE SAME PATIENT AREA.
5. VERIFY RECEPTACLE LOADS DO NOT EXCEED BRANCH CIRCUIT OR
PANEL AMPACITY.
6. REUSE EXISTING CIRCUITS IN SPACE.
7. COORDINATE EXACT MOUNTING HEIGHT AND LOCATION OF ALL
DEVICES WITH ARCHITECTURAL PLANS PRIOR TO INSTALLATION.
8. CONNECT FIRE ALARM DEVICES TO EXISTING FIRE ALARM SYSTEM.
9. REFER TO PANEL SCHEDULES FOR NUMBER OF POLES AND PHASE
PER CIRCUIT.
10. CONNECT 120V TO EACH NEW VAV BOX. PROVIDE NO MORE THAN 20
BOXES ON ONE 120V CIRCUIT. COORDINATE THE EXACT LOCATION AND
QUANTITY WITH DIVISION 23 DRAWINGS. RECONNECT EXISTING VAV
CONTROL POWER IF EXISTING VAV BOXES ARE RELOCATED.
N
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1 1
1
1
1
1 1
1
1
1
1
1
E3.05
3 TYPICAL PATIENT ROOM HEADWALL
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
22
2
2
2
2
22
22
22
2
2
2
2
2
1
-
Scale
Project number
Date
Drawn by
DEMOSS AND
ASSOCIATES
LLC
NO.
REVISION
DESCRIPTION Date
ARCHITECT
MEP
DEMOSS AND ASSOCIATES LLC1188 AMSTERDAM AVENUEATLANTA, GA 30308
ISSUANCE
SHEET TITLE
PERRYCRABB2970 CLAIRMONT ROAD, #850ATLANTA, GA 30329
11/3
/2017 2
:27:3
5 P
M
E6.05
PANEL SCHEDULES
2017_ESJ_CON_PT_RMS
100% CONSTRUCTIONDOCUMENTS
NOVEMBER 3, 2017
PEB
EM
OR
Y S
AIN
T J O
SE
PH
'S H
OS
PIT
AL
PA
T IE
NT
RO
OM
RE
NO
VA
TIO
NS
* INDICATES NEW/MODIFIED CIRCUIT.
- CRITICAL POWER PANEL.
Notes:Notes:Notes:Notes:
Total Est. Demand Current:Total Est. Demand Current:Total Est. Demand Current:Total Est. Demand Current: 66.04 A
Total Conn. Current:Total Conn. Current:Total Conn. Current:Total Conn. Current: 78.83 A
Total Est. Demand:Total Est. Demand:Total Est. Demand:Total Est. Demand: 23.79 kVA
Total Conn. Load:Total Conn. Load:Total Conn. Load:Total Conn. Load: 28.40 kVA
Panel TotalsPanel TotalsPanel TotalsPanel Totals
Total Amps:Total Amps:Total Amps:Total Amps: 74 A 86.99 A 77.15 A
Total Load:Total Load:Total Load:Total Load: 8.82 kVA 10.38 kVA 9.20 kVA
35 EXISTING LOAD 20 A 1 0.72 0.00 -- -- -- 36
33 EXISTING LOAD 20 A 1 0.72 0.00 -- -- -- 34
31 EXISTING LOAD 20 A 1 0.72 0.00 3 100 A MCB 32
* 29 IT CLOSET 20 A 1 0.18 0.00 1 20 A Spare 30
* 27 IT CLOSET 20 A 1 0.18 0.00 1 20 A Spare 28
* 25 IT CLOSET 20 A 1 0.18 0.00 1 20 A Spare 26
23 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 24
21 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 22
19 EXISTING LOAD 20 A 1 0.72 2.88 -- -- -- 20 *
17 EXISTING LOAD 20 A 1 0.72 3.26 -- -- -- 18 *
15 EXISTING LOAD 20 A 1 0.72 4.44 3 100 A 5EC 16 *
13 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 14
11 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 12
9 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 10
7 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 8
5 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 6
3 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 4
1 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 2
CKTCKTCKTCKT Circuit DescriptionCircuit DescriptionCircuit DescriptionCircuit Description TripTripTripTrip PolesPolesPolesPoles AAAA BBBB CCCC PolesPolesPolesPoles TripTripTripTrip Circuit DescriptionCircuit DescriptionCircuit DescriptionCircuit Description CKTCKTCKTCKT
Mounting:Mounting:Mounting:Mounting: Recessed Wires:Wires:Wires:Wires: 4 Mains Rating:Mains Rating:Mains Rating:Mains Rating: 100.00 A
Supply From:Supply From:Supply From:Supply From: 4EA Phases:Phases:Phases:Phases: 3 Mains Type:Mains Type:Mains Type:Mains Type: MCB
Volts:Volts:Volts:Volts: 120/208 Wye A.I.C. Rating:A.I.C. Rating:A.I.C. Rating:A.I.C. Rating: EXISTING
Existing Branch Panel:Existing Branch Panel:Existing Branch Panel:Existing Branch Panel: 5EA5EA5EA5EA
* INIDCATES NEW/MODIFIED CIRCUIT.
- CRITICAL POWER PANEL.
Notes:Notes:Notes:Notes:
Total Est. Demand Current:Total Est. Demand Current:Total Est. Demand Current:Total Est. Demand Current: 68.74 A
Total Conn. Current:Total Conn. Current:Total Conn. Current:Total Conn. Current: 83.33 A
Total Est. Demand:Total Est. Demand:Total Est. Demand:Total Est. Demand: 24.76 kVA
Total Conn. Load:Total Conn. Load:Total Conn. Load:Total Conn. Load: 30.02 kVA
Panel TotalsPanel TotalsPanel TotalsPanel Totals
Total Amps:Total Amps:Total Amps:Total Amps: 91 A 81.65 A 78.00 A
Total Load:Total Load:Total Load:Total Load: 10.92 kVA 9.74 kVA 9.36 kVA
35 EXISTING LOAD 20 A 1 0.72 0.00 -- -- -- 36
33 EXISTING LOAD 20 A 1 0.72 0.00 -- -- -- 34
31 EXISTING LOAD 20 A 1 0.72 0.00 3 100 A MCB 32
29 Spare 20 A 1 0.00 0.72 1 20 A EXISTING LOAD 30
27 Spare 20 A 1 0.00 0.72 1 20 A EXISTING LOAD 28
25 Spare 20 A 1 0.00 0.72 1 20 A EXISTING LOAD 26
23 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 24
21 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 22
19 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 20
17 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 18
15 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 16
13 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 14
11 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 12
9 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 10
7 EXISTING LOAD 20 A 1 0.72 0.72 1 20 A EXISTING LOAD 8
* 5 -- -- -- 2.88 0.72 1 20 A EXISTING LOAD 6
* 3 -- -- -- 3.26 0.72 1 20 A EXISTING LOAD 4
* 1 5ED 100 A 3 4.44 0.72 1 20 A EXISTING LOAD 2
CKTCKTCKTCKT Circuit DescriptionCircuit DescriptionCircuit DescriptionCircuit Description TripTripTripTrip PolesPolesPolesPoles AAAA BBBB CCCC PolesPolesPolesPoles TripTripTripTrip Circuit DescriptionCircuit DescriptionCircuit DescriptionCircuit Description CKTCKTCKTCKT
Mounting:Mounting:Mounting:Mounting: Recessed Wires:Wires:Wires:Wires: 4 Mains Rating:Mains Rating:Mains Rating:Mains Rating: 100.00 A
Supply From:Supply From:Supply From:Supply From: 4EB Phases:Phases:Phases:Phases: 3 Mains Type:Mains Type:Mains Type:Mains Type: MCB
Volts:Volts:Volts:Volts: 120/208 Wye A.I.C. Rating:A.I.C. Rating:A.I.C. Rating:A.I.C. Rating: EXISTING
Existing Branch Panel:Existing Branch Panel:Existing Branch Panel:Existing Branch Panel: 5EB5EB5EB5EB
- CRITICAL POWER PANEL.
Notes:Notes:Notes:Notes:
Miscellaneous 0 VA 0.00% 0 VA
X-Ray 0 VA 0.00% 0 VA
Motors 0 VA 0.00% 0 VA Total Est. Demand Current:Total Est. Demand Current:Total Est. Demand Current:Total Est. Demand Current: 30.96 A
Motor (largest) 0 VA 0.00% 0 VA Total Conn. Current:Total Conn. Current:Total Conn. Current:Total Conn. Current: 29.37 A
Dedicated 0 VA 0.00% 0 VA Total Est. Demand:Total Est. Demand:Total Est. Demand:Total Est. Demand: 11.16 kVA
Receptacle 8280 VA 100.00% 8280 VA Total Conn. Load:Total Conn. Load:Total Conn. Load:Total Conn. Load: 10.58 kVA
Lighting 2300 VA 125.00% 2875 VA
Load ClassificationLoad ClassificationLoad ClassificationLoad Classification Connected LoadConnected LoadConnected LoadConnected Load Demand FactorDemand FactorDemand FactorDemand Factor Estimated DemandEstimated DemandEstimated DemandEstimated Demand Panel TotalsPanel TotalsPanel TotalsPanel Totals
Total Amps:Total Amps:Total Amps:Total Amps: 37 A 27.65 A 24.00 A
Total Load:Total Load:Total Load:Total Load: 4.44 kVA 3.26 kVA 2.88 kVA
41 Spare 20 A 1 0.00 0.00 1 20 A Spare 42
39 Spare 20 A 1 0.00 0.00 1 20 A Spare 40
37 Spare 20 A 1 0.00 0.00 1 20 A Spare 38
35 Spare 20 A 1 0.00 0.00 1 20 A Spare 36
33 Spare 20 A 1 0.00 0.00 1 20 A Spare 34
31 Spare 20 A 1 0.00 0.00 1 20 A Spare 32
29 Spare 20 A 1 0.00 0.00 1 20 A Spare 30
27 PATIENT ROOM LIGHTING 20 A 1 1.10 0.00 1 20 A Spare 28
25 HEADWALL 20 A 1 0.36 1.20 1 20 A PATIENT ROOM LIGHTING 26
23 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 24
21 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 22
19 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 20
17 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 18
15 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 16
13 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 14
11 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 12
9 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 10
7 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 8
5 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 6
3 Spare 20 A 1 0.00 0.00 1 20 A Spare 4
1 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 2
CKTCKTCKTCKT Circuit DescriptionCircuit DescriptionCircuit DescriptionCircuit Description TripTripTripTrip PolesPolesPolesPoles AAAA BBBB CCCC PolesPolesPolesPoles TripTripTripTrip Circuit DescriptionCircuit DescriptionCircuit DescriptionCircuit Description CKTCKTCKTCKT
Mounting:Mounting:Mounting:Mounting: Recessed Wires:Wires:Wires:Wires: 4 Mains Rating:Mains Rating:Mains Rating:Mains Rating: 100.00 A
Supply From:Supply From:Supply From:Supply From: 5EA Phases:Phases:Phases:Phases: 3 Mains Type:Mains Type:Mains Type:Mains Type: MLO
Volts:Volts:Volts:Volts: 120/208 Wye A.I.C. Rating:A.I.C. Rating:A.I.C. Rating:A.I.C. Rating: MATCH FEEDER AIC
Branch Panel: Branch Panel: Branch Panel: Branch Panel: 5EC5EC5EC5EC
- CRITICAL POWER PANEL.
Notes:Notes:Notes:Notes:
Miscellaneous 0 VA 0.00% 0 VA
X-Ray 0 VA 0.00% 0 VA
Motors 0 VA 0.00% 0 VA Total Est. Demand Current:Total Est. Demand Current:Total Est. Demand Current:Total Est. Demand Current: 30.96 A
Motor (largest) 0 VA 0.00% 0 VA Total Conn. Current:Total Conn. Current:Total Conn. Current:Total Conn. Current: 29.37 A
Dedicated 0 VA 0.00% 0 VA Total Est. Demand:Total Est. Demand:Total Est. Demand:Total Est. Demand: 11.16 kVA
Receptacle 8280 VA 100.00% 8280 VA Total Conn. Load:Total Conn. Load:Total Conn. Load:Total Conn. Load: 10.58 kVA
Lighting 2300 VA 125.00% 2875 VA
Load ClassificationLoad ClassificationLoad ClassificationLoad Classification Connected LoadConnected LoadConnected LoadConnected Load Demand FactorDemand FactorDemand FactorDemand Factor Estimated DemandEstimated DemandEstimated DemandEstimated Demand Panel TotalsPanel TotalsPanel TotalsPanel Totals
Total Amps:Total Amps:Total Amps:Total Amps: 37 A 27.65 A 24.00 A
Total Load:Total Load:Total Load:Total Load: 4.44 kVA 3.26 kVA 2.88 kVA
41 Spare 20 A 1 0.00 0.00 1 20 A Spare 42
39 Spare 20 A 1 0.00 0.00 1 20 A Spare 40
37 Spare 20 A 1 0.00 0.00 1 20 A Spare 38
35 Spare 20 A 1 0.00 0.00 1 20 A Spare 36
33 Spare 20 A 1 0.00 0.00 1 20 A Spare 34
31 Spare 20 A 1 0.00 0.00 1 20 A Spare 32
29 Spare 20 A 1 0.00 0.00 1 20 A Spare 30
27 PATIENT ROOM LIGHTING 20 A 1 1.10 0.00 1 20 A Spare 28
25 HEADWALL 20 A 1 0.36 1.20 1 20 A PATIENT ROOM LIGHTING 26
23 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 24
21 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 22
19 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 20
17 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 18
15 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 16
13 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 14
11 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 12
9 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 10
7 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 8
5 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 6
3 Spare 20 A 1 0.00 0.00 1 20 A Spare 4
1 HEADWALL 20 A 1 0.36 0.36 1 20 A HEADWALL 2
CKTCKTCKTCKT Circuit DescriptionCircuit DescriptionCircuit DescriptionCircuit Description TripTripTripTrip PolesPolesPolesPoles AAAA BBBB CCCC PolesPolesPolesPoles TripTripTripTrip Circuit DescriptionCircuit DescriptionCircuit DescriptionCircuit Description CKTCKTCKTCKT
Mounting:Mounting:Mounting:Mounting: Recessed Wires:Wires:Wires:Wires: 4 Mains Rating:Mains Rating:Mains Rating:Mains Rating: 100.00 A
Supply From:Supply From:Supply From:Supply From: 5EB Phases:Phases:Phases:Phases: 3 Mains Type:Mains Type:Mains Type:Mains Type: MLO
Volts:Volts:Volts:Volts: 120/208 Wye A.I.C. Rating:A.I.C. Rating:A.I.C. Rating:A.I.C. Rating: MATCH FEEDER AIC
Branch Panel:Branch Panel:Branch Panel:Branch Panel: 5ED5ED5ED5ED
* INDICATES NEW/MODIFIED CIRCUIT
Notes:Notes:Notes:Notes:
Total Est. Demand Current:Total Est. Demand Current:Total Est. Demand Current:Total Est. Demand Current: 43.88 A
Total Conn. Current:Total Conn. Current:Total Conn. Current:Total Conn. Current: 60.12 A
Total Est. Demand:Total Est. Demand:Total Est. Demand:Total Est. Demand: 15.81 kVA
Total Conn. Load:Total Conn. Load:Total Conn. Load:Total Conn. Load: 21.66 kVA
Panel TotalsPanel TotalsPanel TotalsPanel Totals
Total Amps:Total Amps:Total Amps:Total Amps: 80 A 57.54 A 46.00 A
Total Load:Total Load:Total Load:Total Load: 9.42 kVA 6.72 kVA 5.52 kVA
35 Spare 20 A 1 0.00 0.00 1 20 A Spare 36
* 33 Receptacle 20 A 1 0.36 0.36 1 20 A Receptacle 34 *
* 31 Receptacle 20 A 1 0.36 0.36 1 20 A Receptacle 32 *
* 29 Receptacle 20 A 1 0.36 0.36 1 20 A Receptacle 30 *
27 EXISTING LOAD 20 A 1 0.90 0.30 1 20 A EXISTING LOAD 28
25 EXISTING LOAD 20 A 1 0.90 0.30 1 20 A EXISTING LOAD 26
23 EXISTING LOAD 20 A 1 0.90 0.30 1 20 A EXISTING LOAD 24
21 EXISTING LOAD 20 A 1 0.90 0.30 1 20 A EXISTING LOAD 22
19 EXISTING LOAD 20 A 1 0.90 3.00 1 20 A EXISTING LOAD 20
17 EXISTING LOAD 20 A 1 0.90 0.30 1 20 A EXISTING LOAD 18
15 EXISTING LOAD 20 A 1 0.90 0.30 1 20 A EXISTING LOAD 16
13 EXISTING LOAD 20 A 1 0.90 0.30 1 20 A EXISTING LOAD 14
11 EXISTING LOAD 20 A 1 0.90 0.30 1 20 A EXISTING LOAD 12
9 EXISTING LOAD 20 A 1 0.90 0.30 1 20 A EXISTING LOAD 10
7 EXISTING LOAD 20 A 1 0.90 0.30 1 20 A EXISTING LOAD 8
5 EXISTING LOAD 20 A 1 0.90 0.30 1 20 A EXISTING LOAD 6
3 EXISTING LOAD 20 A 1 0.90 0.30 1 20 A EXISTING LOAD 4
1 EXISTING LOAD 20 A 1 0.90 0.30 1 20 A EXISTING LOAD 2
CKTCKTCKTCKT Circuit DescriptionCircuit DescriptionCircuit DescriptionCircuit Description TripTripTripTrip PolesPolesPolesPoles AAAA BBBB CCCC PolesPolesPolesPoles TripTripTripTrip Circuit DescriptionCircuit DescriptionCircuit DescriptionCircuit Description CKTCKTCKTCKT
Mounting:Mounting:Mounting:Mounting: Recessed Wires:Wires:Wires:Wires: 4 Mains Rating:Mains Rating:Mains Rating:Mains Rating: 150.00 A
Supply Fro