demve a multi-vendor laboratory environment for research ... · pdf filedemve – a...

Download DEMVE a Multi-Vendor Laboratory Environment for Research ... · PDF fileDEMVE – a Multi-Vendor Laboratory Environment for Research and Education ... ABB Terminals Switch & Mervento

If you can't read please download the document

Upload: nguyennga

Post on 07-Feb-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • DEMVE a Multi-Vendor Laboratory Environment for Research and Education

    Related to IEC 61850

    21.3.2012 1

    Renewable Efficient Energy II Conference

    Vaasa 21.3.2012

    Reino Virrankoski

    University of Vaasa

    Department of Computer Science

    Communications and Systems Engineering Group

  • DEMVE

    Coordinated by Merinova, funded organizations the University of Vaasa

    Vaasa University of Applied Sciences (VAMK)

    Novia University of Applied Sciences

    Duration 24 months on 1.8.2011-31.7.2013

    Building up a multi-vendor environment under IEC 61850 to Technobothnia for research and education purposes IEC 61850 training can then be offered in the context of Vaasa Energy

    Institute (VEI)

    21.3.2012 2

  • Companies Participating to DEMVE-project

    21.3.2012 3

  • IEC 61850

    A standard for electrical substation automation; extended also for communication between substations An important enabler of local electricity production

    An important enabler of monitoring and control soutions required for Smart Grid

    Object oriented monitoring and control information for substation control and protection

    The abstract data models defined in IEC 61850 can be mapped to a number of communication protocols

    21.3.2012 4

  • 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009

    WG 10 System Overview

    WG 11 Coding and Mapping

    WG 12 Process Interfaces

    WG 10

    WG 11

    IEC 61850

    Part 1 Introduction and Overview

    Part 2 Glossary

    Part 3 General requirements

    Part 4 System and project management

    Part 5 Communication requirements for functions and device models

    Part 6 Configuration description language

    Part 7 Basic communication structure, Principles and models

    Part 8 Mappings to MMS

    Part 9 Specific communication service mapping (SCSM)

    Part 10 Conformance testing

    Part 90-1 FOR THE COMMUNICATION BETWEEN SUBSTATIONS

    IEC 61850 Development History

    Committee draft

    Committee draft for voting

    Final draft International Standard in Nimes 2004

    International Standard

    Process continues by technical issues - TISSUES

    Baden November 1995 Around 65 persions First interoperability

    tests of bay devices

    FDFV Standard

    2009-05-11

    21.3.2012 5

  • Application Areas of IEC 61850 Standard

    Industrial Bus

    Process Bus

    IEC 61850-9-2

    Station Bus

    IEC 61850-8-1

    Cyber Security

    Application

    WAN

    Multi Vendor Environment

    M

    Station Bus

    IEC 61850-8-1

    G

    Station Bus

    IEC 61850-8-1

    Distributed

    Power Plan

    Control Centers

    21.3.2012 6

  • IEC 61850 Multi-Vendor Environment

    Siemens Terminals

    VAMP Terminals

    ABB Terminals

    Switch & Mervento Wind Turbines

    Vacon Terminals Schneider

    Electric Terminals

    21.3.2012 7 Erkki Antila, University of Vaasa

  • Challenges Related to IEC 61850

    The standard enables distributed packet-connected control architecture, which is necessary to be able to enable local electricity production. It can also increase the system reliability. However, it is a big technological step for the automation systems.

    The standard allows many different options. As a consequence, the vendor spesific solutions can still be an issue and the compatibility between different vendors is currently not fully guaranteed.

    21.3.2012 8

  • 21.3.2012 9

    IEC 61850/Ethernet

    Fibre

    Optic

    Test Rack 1

    Distribution Network 1

    2 pcs ABB REF630

    2 pcs SE MiCOM P139

    2 pcs Siemens 7SJ6311

    IEC 61850/Ethernet

    RJ45/CAT6

    Control Center Rack 1 (Schneider Electric)

    System Configuration Editor (SCE)

    System Management Tool (SMT)

    MiCOM S1 Studio

    Workstation 1

    Workstation 3

    Control Center Rack 2 (ABB)

    IEC 61850/Ethernet

    Backbone-fibre optic

    Waveform recording tool

    VAMPSET ICD-file, IED Capab. Descr.

    IID-file, IED Description

    SCD EDITOR SCD-file, Substation Conf. Descr.

    ICD-file of IED -> CID/IID, SCD & txt files

    COM600

    Communication

    Gateway

    System

    Diagnostics

    PCM600 Ver. 2.4 Engineering Pro + IET600

    SAB600 Ver. 3.5

    Workstation 2

    Test Rack 2

    Distribution Network 2

    2 pcs ABB REF615

    2 pcs VAMP 255

    2 pcs Siemens 7SJ8011

    IEC 61850/Ethernet

    RJ45/

    CAT6

    Test Rack 3

    Subtransmission Network

    ABB RET630 & REF630

    VAMP 265 & VAMP 255

    2 pcs Siemens 7SJ6311

    IEC 61850/Ethernet

    Fibre

    Optic

    Protection Relay Test Set

    and Commissioning Tool

    Test Rack 4

    Distributed Power Generation

    2 pcs eroonkytkentyksikk (ABB & VAMP)

    2 pcs Power Converter (ABB & Vacon)

    Option for line differential relays (2 pcs ABB RED615)

    IEC 61850/Ethernet

    RJ45/

    CAT6

    IEC 60870-5-104/

    Ethernet

    RJ45/CAT6

    MicroSCADA Pro Ver. 9.3

    Substation Control System PACiS

    Substation Control System

    IEC 61850 Multi-Vendor Environment in Technobothnia

    Building up to be

    completed during

    Q2/2012

  • Research Issues Related to IEC 61850 Multi-Vendor Environment in Technobothnia

    21.3.2012 10

    Creation of core criterias to enable the compatibility between different vendors.

    Classification and instruction of interface requirements such that the automation requirements are filled.

    Reasearch regarding the compatibility of the files created by the software tools of different vendors.

    A simple conversion middleware will be made for the most important interfaces, if needed.

    Interfacing with wireless communication (long distance links, wireless sensor networks, etc.)

  • Possible Training Courses based on IEC 61850 Multi-Vendor Environment in Technobothnia

    21.3.2012 11

    The Basics of IEC 61850

    How to Implemant IEC 61850 Based System

    IEC 61850 Configuration Programs

    GOOSE Configuration For one vendor devices

    For multi-vendor devices

    Remote Terminal Unit (RTU) Configuration Adding single vendor devices to RTU

    Adding multi-vendor devices to RTU

    Implementing a Control Center in IEC 61850 Environment

    Wireless Automation Under IEC 61850

  • 12

    Questions?

    Remember 3rd Workshop on Wireless Communication and Applications

    in Vaasa on 25.-26.4.2012

    Day 1 (25.4.): Wireless Automation

    Day 2 (26.4.): Tactical Communication Systems

    Registration is mandatory, but free of charge.

    See http://cs.uwasa.fi/wowca2012/ for further details

    http://cs.uwasa.fi/wowca2012/