~$ ~~~~~,- ;:.,-;-:,. Product Services lEG 60614-2-1 :1993 The complete detail of the tests performed and the results are recorded in asl Test Report No: 286/4271935 Dated: 4 September 2002 Description of item tested: 20mm diameter Galvanised Steel Conduit 25mm diameter Galvanised Steel Conduit 32mm diameter Galvanised Steel Conduit Tamco Electrical & Electronics (HK) Ltd 1701-2 Top Glory Tower 262 Gloucester Road Causeway Bay Hong Kong r- C 7-~ ~ft S~a--G REssam Title Principal Engineer Date 4 September 2002 Attention is drawn to the conditions upon which this declaration is issued, namely: 2. This Declaration applied only to the particular sample tested and to the specific tests carried out as detailed in the Report refe"ed to above. 1. This declaration does not indicate provide or imply any measure of Approval, Certification, Supervision, Control or Surveillance by asl to this or any related product. 3. The general and specific conditions of the asl Product Services, Test Leaflet 1 apply in all respects. Copies of this leaflet are available on request. BSI Product Services, Maylands Avenue, Hemel Hempstead, Hertfordshire HP2 4SQ

Upload: others

Post on 11-Mar-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

~$ ~~~~~,- ;:.,-;-:,.

Product Services

lEG 60614-2-1 :1993

The complete detail of the tests performedand the results are recorded in

asl Test Report No: 286/4271935 Dated: 4 September 2002

Description of item tested: 20mm diameter Galvanised Steel Conduit25mm diameter Galvanised Steel Conduit32mm diameter Galvanised Steel Conduit

Tamco Electrical & Electronics (HK) Ltd1701-2 Top Glory Tower262 Gloucester Road

Causeway BayHong Kong

r-C 7-~ ~ft S~a--G R Essam

Title Principal Engineer

Date 4 September 2002

Attention is drawn to the conditions upon which this declarationis issued, namely:

2. This Declaration applied only to the particular sample testedand to the specific tests carried out as detailed in theReport refe"ed to above.

1. This declaration does not indicate provide or imply anymeasure of Approval, Certification, Supervision, Control orSurveillance by asl to this or any related product.

3. The general and specific conditions of the asl ProductServices, Test Leaflet 1 apply in all respects. Copies of thisleaflet are available on request.

BSI Product Services, Maylands Avenue, Hemel Hempstead, Hertfordshire HP2 4SQ

Page 2: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

Product Services

as! Product SelVices hereby declares that theitem described below has been tested

by as! and complies with the requirements of

BS 4568:Part 1: 1970

The complete detail of the tests peliormedand the results are recorded in

asl Test Report No: 286/4271935 Dated: 4 September 2002)

20mm diameter Galvanised Steel Conduit25mm diameter Galvanised Steel Conduit32mm diameter Galvanised Steel Conduit

Tamco Electrical & Electronics (HK) Ltd1701-2 Top Glory Tower262 Gloucester Road

Causeway BayHong Kong

,----:S.RC...Y.S'a.- G R Essam

Title Principal Engineer

Date 4 September 20Q2 II

2. This Declaration applied only to the particular sample testedand to the specific tests carried out as detailed in theReport referred to above.

Attention is drawn to the conditions upon which this declarationis issued, namely:

1. This declaration does not indicate provide or imply anymeasure of Approval, Certification, Supervision, Control orSurveillance by asl to this or any related product.

3. The general and specific conditions of the asl ProductServices, Test Leaflet 1 apply in all respects. Copies of thisleaflet are available on request.

BSI Product Services, Maylands Avenue, Hemel Hempstead, Hertfordshire HP2 4SQ

Page 3: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

--~--"",Product Services

as! Product Services hereby declares that theitem described below has been tested

by asl and complies with the requirements of

BS EN 50086-2-1 :1996

The complete detail of the tests performedand the results are recorded in

asl Test Report No: 286/4271935 Dated: 4 September 2002

20mm diameter Galvanised Steel Conduit

25mm diameter Galvanised Steel Conduit32mm diameter Galvanised Steel Conduit

Tamco Electrical & Electronics (HK) Ltd1701-2 Top Glory Tower262 Gloucester Road

Causeway BayHong Kong

r--~..~'t::SS'o.-- .G REssam

Title Principal Engineer, .

Date 4 September 2002 I!

Attention is drawn to the conditions upon which this declarationis issued, namely:

2. This Declaration applied only to the particular sample testedand to the specific tests carried out as detailed in theReport referred to above.

This declaration does not indicate provide or imply anymeasure of Approval, Certification, Supervision, Control orSurveillance by asl to this or any related product.

3. The general and specific conditions of the asl ProductSeNices, Test Leaflet 1 apply in all respects. Copies of thisleaflet are available on request.

BSI Product Services, Maylands Avenue, Hemel Hempstead, Hertfordshire HP2 4SQ

Page 4: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

':";:~""l:::

: ':"="":::;",0';"."""'"2 ,

Product Services

Report No 286/4271935 This Report consists of 16 pages

Client Tamco Electrical & Electronics (HK) Ltd1701-2 Top Glory Tower262 Gloucester Road

Causeway BayHong Kong

Authority & date Fax from client dated 20 December 2001

)Items tested Steel Conduits

Specification BS 4568: Part 1: 1970 Clauses 5.1, 5.3.. 5.4, 6.1, 7, 8, 9 and 10BS EN 50086-2-1:1996 Clauses 7.1,7.5,8.1,9.1,10..2,10.3,10.4,11.5,and 14.2.2.3IEC 60614-2-1:1993 Clauses 6.1,6.2,6.3,7.1,8.1,9.2,9.3,9.4,12.1.2and 13.4.5Independent Test

Results See summary of results on page 2

)

Prepared by Engineer

Authorized by G R Essam,~:1~~E~ so-- Principal Engineer

Issue Date

Conditions of issue This Test Report is issued subject to the conditions stated in current issue of Test Leaflet 1'Genera! conditions relating to acceptance of testing'. The results contained herein apply only tothe particular sample/s tested and to the specific tests carried out, as detailed in this Test Report.The Issuing of this Test Report does not indicate any measure of Approval, Certification,Supervision, Control or Surveillance by BSI of any product. No extract, abridgement orabstraction from a Test Report may be published or used to advertise a product without the writtenconsent of the General Manager, BSI Product Services, who reserves the absolute right to agreeor reject all or any of the details of any items or publicity for which consent may be sought.

851 PrOOud Ser.;res ~ A~ue I-EmeI Hem~tead Hertfadshire HP2 4SQ Telepnc:.1e:(O1442) 230442

Page 5: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

Report No 286/4271935

Page 2 of 16

TESTING, EXAMINATION AND ASSESSMENT OF STEEL CONDUITS SUBMITTED ASINDEPENDENT TEST SAMPLES

INTRODUCTION

At the request of Tamco Electrical & Electronics (HK) Ltd the steel conduits detailed below,received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1 :1993 from 23 May 2002, as indicated onthe following pages of this Report. This request was made in a Fax from client dated 20December 2001. It is emphasized that assessments were not made against the other clausesof the Specification.

I his Report only relates to the actual samples which have been tested and assessed. The,esults obtained do not necessarily relate to samples from the production line and in no wayimply that the performance or quality of the continuing production will be maintained.

TEST ITEMS

15 off 1 metre lengths 20mm diameter Galvanised Steel Conduit15 off 1 metre lengths 25mm diameter Galvanised Steel Conduit15 off 1 metre lengths 32mm diameter Galvanised Steel Conduit

SUMMARY OF RESULTS

)5 4568: Part 1: 1970

The Galvanised steel conduits met the requirements of those clauses, or parts thereof, of theSpecification against which assessments were made.

BS EN 50086-2-1 :1996

The Galvanised steel conduits met the requirements of those clauses, or parts thereof, of theSpecification against which assessments were made.

Page 6: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

Report No 286/4271935

Page 3 of 16SUMMARY OF RESULTS (Continued)

I EC 60614-2-1 : 1993

The Galvanised steer conduits met the requirements of those clauses, or parts thereof, of theSpecification against which assessments were made.

The potential variability in, both the items tested and the method of measurement used,. meansthat for measurements close to a specified limit, the level of confidence in a compliancestatement mayor may not be reduced.

Further advice on the specific measurements in this report that may be affected can beobtained from the report authoriser shown on the front cover.

Page 7: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

Report No 286/4271935

Page 4 of 16EXAMINATION AND TEST

BS 4568:Part 1:1970

CLAUSE

4.ASSESSMENT

CLASSIFICATION

The Galvanised steel conduits were classified as screwedconduits.

The Galvanised steel conduits were further classified as having aClass 4, heavy protection both inside and outside. Pass

5.

)

MARKING

Specified Marking.(1) The name or trademark of the manufacturer or responsible

Vendor.(2) BS 4568: Part 1: 1970(3) The Class of finish

Actual Marking

20 mm diameter Galvanised Steel Conduit:

RMG 20 G.E.-MARUIGHI5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan

25 mm diameter Galvanised Steel Conduit:

RMG 25 G.E.-MARUIGHI5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan Pass

32 mm diameter Galvanised Steel Conduit:

RMG 32 G.E.-MARUIGHI5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan

Page 8: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

Report No 286/4271935

Page 5 of 16EXAMINATION AND TEST (CONTINUED)

BS 4568:Part 1:1970 (CONTINUED)

CLAUSE ASSESSMENT

5.

5.4

MARKING (CONTINUED)

Marking durabilityMarking shall be checked by inspection and by rubbing themarking by hand, suitably protected, for 15 s with a piece ofcloth soaked with water and again for 15 s with a piece of clothsoaked with petroleum spirit. Pass

6.

6.1

6.1.1

DIMENSIONS

Conduit

Test

(1) External Diameter

The EXternal diameter of the 20mm, 25mm and 32mmDiameter Galvanised steel conduits was checked by means ofthe gauge according to figure 4 of the standard.

(2) Ovality

The Ovality of the 20mm, 25mm and 32mm DiameterGalvanised steel conduits was checked by means of the gaugeaccording to figure 5 of the standard. Pass

(3) Screw Threads

The Screw Threads of the 20mm, 25mm and 32mm DiameterGalvanised steel conduits were checked by means of thegauge according to figure 2 of the standard. Pass

(4) Wall ThicknessThe Wall thickness of the 20mm, 25mm and 32mm DiameterGalvanised steel conduits was tested in accordance to therequirements of the clause. Pass

7. CONSTRUCTION

The Galvanised steel conduits were seamed by welding. Pass7.1

The Galvanised steel conduits showed no appreciableunevenness and the interior and ends were free from burrs,fins and the like which may cause damage to cables.

7.2

8. MECHANICAL PROPERTIES OF CONDUIT

The Galvanised steel conduits were tested by the methoddescribed in the text of Appendix A.2. On completion of thetest it was possible to pass the appropriate steel balls throughthe conduits.

8.1

The Galvanised steel conduits when bent showed no signs ofcracking nor were they deformed to such an extent that theintroduction of cables became difficult or damaged when,.j~~...:~~ :~

Page 9: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

Report No 286/4271935

Page 6 of 16

EXAMINATION AND TEST (CONTINUED)

BS 4568:Part 1 :1970 (CONTINUED)

CLAUSE ASSESSMENT

9.

RESISTANCE AGAINST CORROSION

When tested in accordance with the method described inclause 9.1.1. and Appendix A.3.3. (Heavy protection)

The Galvanised steel conduits displayed no signs of corrosion. Pass

10. ELECTRICAL CONTINUITY

The Galvanised steel conduits met the requirements of theclause and Appendix A..5. Pass

Page 10: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

Report No 286/4271935

Page 7 of 16EXAMINATION AND TEST (CONTINUED)

BS EN 50086-2-1:1996

CLAUSE

6.ASSESSMENT

CLASSIFICATIONThe Galvanised steel conduits did not have a Classificationnumber marked. Therefore, it was assumed the samples had avery heavy mechanical strength, lower temperature range of -SoC.

7 MARKINGSpecified Marking(a) The name or trademark of manufacturer.(b) A product identification mark.

Actual Marking

20 mm diameter Galvanised Steel Conduit:

RMC 20 C.E.-MARUICHI 5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan Pass

25 mm diameter Galvanised Steel Conduit:

RMG 25 G.E.-MARUIGHI 5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan Pass

32 mm diameter Galvanised Steel Conduit:

RMC 32 C.E.-MARUICHI5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan Pass

The marking shall be shall be durable and easily legible. Pass7.5

Page 11: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

Report No 286/4271935

Page 8 of16EXAMINATION AND TEST {CONTINUED}

BS EN 50086.2.1 :1996 (CONTINUED)

CLAUSE ASSESSMENT

8.

DIMENSIONS

The outside diameters and threads shall comply withBS EN 60423:1995

The maximum outside diameter of the 20mm, 25mm and 32mmdiameter Galvanised steel conduits was checked by means ofthe gauge according to figure 2 of BS EN 60423: 1995

The minimum outside diameter of the 20mm, 25mm and 32mmdiameter Galvanised steel conduits was checked by means ofthe gauge according to figure 3 of BS EN 60423: 1995

The screw threads of the 20mm, 25mm and 32mm diameterGalvanised steel conduits was checked by means of the gaugeaccording to figure 4 of BS EN 60423: 1995

9.9.1

CONSTRUCTIONWithin the Conduit System there shall be no sharp edges, burrsor surface projections which are likely to damage insulatedconductors or cables or inflict injury to the installer or used.

Page 12: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

Report No 286/4271935

Page 9 of 16EXAMINATION AND TEST (CONTINUED)

BS EN 50086-2-1:1996 (CONTINUED)

CLAUSE

10.10.2

ASSESSMENT

MECHANICAL PROPERTIES

Compression testThe Conduits were tested in accordance with the methoddescribed in this clause. When a force of 4000N (Very heavygrade) the sample shall not exceed 25% of the initial outsidediameter.

Nominal Size Sample Compression (%)20mm Conduit 1 3.8

2 3.93 3.9Mean 3.9

PassPassPass

25mm Conduit 3.53.52.83.3

123Mean

PassPassPass

3.23.23.23.2

PassPassPass

32mm Conduit 123Me

~an

Page 13: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

Report No 286/4271935

Page 10 of 16EXAMINATION AND TEST (CONTINUED)

BS EN 50086-2-1:1996 (CONTINUED)

CLAUSE

10.10.2

ASSESSMENT

MECHANICAL PROPERTIES (CONTINUED)

Compression test (Continued)The Force and the intermediate piece are then removed and, 60safter removal, the outside diameter of the samples, where theyhave flattened, shall be measured again.

The difference between the initial diameter and the diameter ofthe flattened samples shall not exceed 10% of the outsidediameter, measured before test.

Nominal Size20mm Conduit

Sample123Mean

Change in diameter (%)0.60.80.80.7

PassPassPass

25mm Conduit 123Mean

0.70.80.80.8

PassPassPass

32mm Conduit 123Mean

0.30.50.40.4

PassPassPass

Page 14: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

Report No 286/4271935

Page 11 of16EXAMINATION AND TEST (CONTINUED)

as EN 50086-2-1:1996 (CONTINUED)

CLAUSE ASSESSMENT10.10.3

MECHANICAL PROPERTIES (CONTINUED)

Impact testThe Conduits were tested at -5°C in accordance with themethod described in this clause. After the test, at least nineof the samples shall show no signs of disintegration, nor shallthere be any crack visible to normal or corrected visionwithout magnification and there shall be no deformationimpairing its normal use.

NominalSize

MassUsed

(kg)6.86.86.8

Dropheight(mm)300300300

No.failuresout of 12000

20mm Conduit25mm Conduit32mm Conduit

PassPassPass

10.4 Bending testThe Galvanised steel conduits were tested in accordance tothe method described in this clause.

After the test, the samples showed no cracks visible to normalor corrected vision without magnification. It was possible topass the appropriate gauges through the samples. Pass

1111.5

ELECTRICAL PROPERTIESElectrical Bonding

The Galvanised steel conduits were tested by the methoddescribed in the text of clause 11.5 of BS EN 50086-1 :1994.

The Galvanised steel conduits met the requirements of theclause Pass

14.

14.2

14.2.2

EXTERNALINFUUENCES

Resistance against corrosion

Tests for resistance to corrosion for steel conduit

systems

The Galvanised steel conduits were tested in accordance withJ.'-- -_J.L._-'d :L._-' :- _I_ U A 2 2 3 &_p h:~h P~~~~~~:~ nLilt:: IIICLIIUU t::;:II.,IIIUCU 1111...10 ;:It:: 1"1'. ..IVI III~II IU..t:;\.-~lul

The steel conduits displayed no signs of corrosion Pass

Page 15: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

Report No 286/4271935

Page 12of 16EXAMINATION AND TEST (CONTINUED)

lEG 60614.2.1:1993

CLAUSE6. ASSESSMENT

6.1

MARKING

Specified MarkingConduits shall be marked with:(.1) the name or trademark of the manufacturer or responsible

Vendor, trade mark, or other indentifying symbol.(2) a classification code .in accordance with clause A.1

of annex A..(3) any other mark or symbol required by the relevant section of

part 2 of this standard.

Actual Marking

20 mm diameter Galvanised Steel Conduit:

RMC 20 C.E.-MARUICHI 5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan Pass

25 mm diameter'Galvanised Steel Conduit

RMC 25 C.E.-MARUICHI 5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan Pass

32 mm diameter Galvanised Steel Conduit:

RMC 32 C.E.-MARUICHI 5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan Pass

)

Page 16: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

Report No 286/4271935

Page 13 of 16EXAMINATION AND TEST (CONTINUED)

IEC 60614-2-1:1993 (CONTINUED)

CLAUSE ASSESSMENT

6.6.2

MARKING (CONTINUED)

Marking of ConduitsRigid conduits shall be marked at least once on eachmanufacturing length, preferably 50mm from one end Pass

6.3 Marking shall be durable and easily legibleMarking according to 6.1 to 6.3 shall be checked by inspection,and by rubbing the marking by hand, suitably protected, for 15 swith a piece of cloth soaked with water and again for 15 s with apiece of cloth soaked with petroleum spirit Pass

DIMENSIONS

The outside diameters and threads shall comply with lEG 4237.1

The maximum outside diameter of the 20mm, 25mm and 32mmdiameter Galvanised steel conduits was checked by means of thegauge according to figure 2 of lEG 423

71 1

Pass

The minimum outside diameter of the 20mm, 25mm and 32mmdiameter Galvanised steel conduits was checked by means of thegauge according to figure 101 of this specification

7.1.2

Pass

7.2 The waH thickness of the 20mm, 25mm and 32mm diameterGalvanised steel conduits shaH comply to Standard sheet 2 of this

specification Pass

8.

CONSTRUCTION

The inside and outside surfaces of the conduits shall bereasonably free from burrs, flash and similar defects; in additionthe edges over which the conductors or cables are likely to bedrawn, shall not damage these conductors or cables

Compliance shall be checked by inspection, if necessary, after

cutting the samples apart Pass

Conduits shall be solid drawn or seam joined by welding Pass8.101

Page 17: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

Report No 286/4271935

Page 14 of 16EXAMINATION AND TEST (CONTINUED)

IEC 60614-2-1 :1993 (CONTINUED)

CLAUSE ASSESSMENT

9.

9.1MECHANICAL PROPERTIES

Conduits shall have adequate mechanical strength

Conduits according to their types, when bent or compressed, orexposed to shocks or extreme specified temperatures, eitherduring or after installation, shall show no cracks and shatl not bedeformed to such an extent that the introduction of the cablesbecomes difficult, or that the installed conductors or cables arelikely to be damaged, while being drawn in

Compliance shall be checked by the test specified in Sub-clauses9.2 and 9.3

9.2 Bending testThe 20mm, 25mm and 32mm diameter Galvanised steel conduitswere subjected to a bending test by means of a device as shownin figure 102 of this specification

After the test, the samples showed no cracks visible to normal orcorrected vision without magnification. It was possible to pass theappropriate gauges through the samples Pass

9.3 Compression testThe Conduits were tested in accordance with the methoddescribed in this clause. When a force of 4000N (very heavygrade) the sample shall not exceed 25% of the initial outsidediameter

Nominal Size Sample Compression (%)20mm Conduit 1 3.8

2 3.93 3.9Mean 3.9

PassPassPass

25mm Conduit 3.53.52.83.3

PassPassPass

123Mean

PassPassPass

32mm Conduit 123Me

3.23.23.23.2

.~an

Page 18: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

Report No 286/4271935

Page 15 of 16EXAMINATION AND TEST (CONTINUED)

IEC 60614-2-1 :1993 (CONTINUED)

CLAUSEASSESSMENT

9.

9.3MECHANICAL PROPERTIES (CONTINUED)

Compression test (Continued)The Force and the intermediate piece are then removed and, 60safter removal, the outside diameter of the samples, where theyhave flattened, shall be measured again

The difference between the initial diameter and the diameter ofthe flattened samples shall not exceed 10% of the outsidediameter, measured before test

Nominal Size20mm Conduit

Sample123Mean

Change in diameter (%)0..60.80.80.7

PassPassPass

25mm Conduit 123Mean

0.70.80.80.8

PassPassPass

32mm Conduit 123Me

0.30.50.40.4

PassPassPass

an

Page 19: Description of item tested - Nikcon · received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part 1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1

Report No 286/4271935

Page 16 of 16EXAMINATION AND TEST (CONTINUED)

IEC 60614-2-1 :1993 (CONTINUED)

CLAUSE

12.

12.1

ASSESSMENTELECTRICAL CHARACTERISTICS

Conduits with electrical continuity characteristics

12.1.1 Conduits shall be so constructed that they can be used in aninstallation system as an earthing or protective conductor Pass

12.1.2 Conduits shall have a resistance of not more than 5 x 10 -3.0. Pass

13.4 RESISTANCE AGAINST CORROSION

When tested in accordance with the method described in clause13.4.5 for conduits with High Protection

The Galvanised steel conduits displayed no signs of corrosion Pass

)