description purpose - mylinkdrive · pdf filethe suction line filter assembly will enhance...

2
Description This suction line filter / refrigerant cleaning assembly provides a replaceable pleated media filter core in a bypass arrangement from main suction flow to allow for preventative system cleanup following original installation, system repair, or rework associated with renovation. The assembly is integral with bypass and main flow full port shut off ball valves, as well as a filter inlet check valve to prevent reverse flow and back flushing of contaminants in the event ball valves are not positioned correctly. An integral pressure relief device is also included to prevent over pressurization failure of assembly components and filter housing. PAC-SPRFCS SYSTEMS REFRIGERANT FILTER / CLEANING SYSTEM © 2015 Mitsubishi Electric US, Inc. Purpose The suction line filter assembly will enhance quality assurance on VRF project installations, minimizing potential migration of contaminants introduced during installation of field piping that may lead to long term damage of the compressor and other critical components. Mitsubishi Electric VRF systems already have integral strainers located upstream of major system components; however, finer particles associated with improper nitrogen purge during brazing as well as other sediment / debris not properly removed from field piping prior to installation can pass through the mesh of built in system strainers and lead to potential wear and premature failure of certain components. By providing a suction line filter of higher filtration efficiency during initial startup will ensure such foreign debris is not migrating to the compressor or other critical parts after startup. The filter assembly can also enhance success of compressor replacements on existing projects to ensure contaminants in the piping system associated with original failure are properly removed. Use The filter assembly would be installed in the main suction pipe ahead of the main suction connections on the Mitsubishi VRF outdoor units. For systems with one or more outdoor modules twinned together, the suction filter would be installed in the main suction pipe prior to any twinning. During initial startup, before compressor are run for the first time, the suction line filter would be opened and the main bypass line closed to force 100% of suction line refrigerant flow through the filter media. Following the included filter assembly startup procedure, a portion of the system’s indoor units are run in increments of approximately 1/3 the connected capacity, to flush all system refrigerant

Upload: duongkhanh

Post on 16-Feb-2018

275 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: Description Purpose - MyLinkDrive · PDF fileThe suction line filter assembly will enhance quality assurance on VRF project ... efficiency during initial startup will ... REQUIREMENTS

Description

This suction line filter / refrigerant cleaning assembly provides a replaceable pleated media filter core in a bypass arrangement from main suction flow to allow for preventative system cleanup following original installation, system repair, or rework associated with renovation.

The assembly is integral with bypass and main flow full port shut off ball valves, as well as a filter inlet check valve to prevent reverse flow and back flushing of contaminants in the event ball valves are not positioned correctly. An integral pressure relief device is also included to prevent over pressurization failure of assembly components and filter housing.

PAC-SPRFCS SYSTEMS REFRIGERANT FILTER / CLEANING SYSTEM

© 2015 Mitsubishi Electric US, Inc.

Purpose

The suction line filter assembly will enhance quality assurance on VRF project installations, minimizing potential migration of contaminants introduced during installation of field piping that may lead to long term damage of the compressor and other critical components.

Mitsubishi Electric VRF systems already have integral strainers located upstream of major system components; however, finer particles associated with improper nitrogen purge during brazing as well as other sediment / debris not properly removed from field piping prior to installation can pass through the mesh of built in system strainers and lead to potential wear and premature failure of certain components.

By providing a suction line filter of higher filtration efficiency during initial startup will ensure such foreign debris is not migrating to the compressor or other critical parts after startup. The filter assembly can also enhance success of compressor replacements on existing projects to ensure contaminants in the piping system associated with original failure are properly removed.

Use

The filter assembly would be installed in the main suction pipe ahead of the main suction connections on the Mitsubishi VRF outdoor units. For systems with one or more outdoor modules twinned together, the suction filter would be installed in the main suction pipe prior to any twinning.

During initial startup, before compressor are run for the first time, the suction line filter would be opened and the main bypass line closed to force 100% of suction line refrigerant flow through the filter media.

Following the included filter assembly startup procedure, a portion of the system’s indoor units are run in increments of approximately 1/3 the connected capacity, to flush all system refrigerant

Page 2: Description Purpose - MyLinkDrive · PDF fileThe suction line filter assembly will enhance quality assurance on VRF project ... efficiency during initial startup will ... REQUIREMENTS

© 2015 Mitsubishi Electric US, Inc.

through the suction filter assembly. This process is repeated in increments of 1/3 of the indoor units until all system components have been thoroughly cleaned.

After completion of the startup cleaning, the suction filter assembly is isolated by closing the integral ball valves and bypass ball valve opened to allow for full unrestricted flow to the outdoor unit and the rest of the system for normal operation.

PAC-SPRFCS Refrigerant Filter / Cleaning System

System Model NumberValve Assembly / Outdoor Unit Suction

Pipe Size

PAC-SPRFCS-118 1-1/8" *

PAC-SPRFCS-138 1-3/8"

PAC-SPRFCS-158 1-5/8"

* 1-1/8” System also includes 7/8” reducers (2) for use with Outdoor Units with 7/8” Suction Lines

THIS DOCUMENT CONTAINS INFORMATION THAT IS CONFIDENTIAL AND PROPRIETARY TO PARKER HANNIFINCORPORATION ("PARKER"). IT IS NOT TO BE COPIED OR DISCLOSED TO OTHERS OR USED FOR ANY PURPOSE OTHER THAN CONDUCTING BUSINESS WITH PARKER, AND WILL BE RETURNED AND ALL FURTHER USE DISCONTINUED UPON REQUEST BY PARKER. THE RECIPIENT OF THIS DOCUMENT, THROUGH ITS OWN ANALYSIS AND TESTING, IS SOLELY RESPONSIBLE FOR MAKING THE FINAL SELECTION OF THE APPLICABLESYSTEM AND COMPONENTS AND ASSURING THAT ALL PERFORMANCE, ENDURANCE, MAINTENANCE, SAFETYAND WARNING REQUIREMENTS OF THE APPLICATION ARE MET. COPYRIGHT PARKER. YEAR OF COPYRIGHTIS FIRST YEAR INDICATED ON THIS DOCUMENT. ALL RIGHTS RESERVED.

DR

AW

ING

NU

MB

ER:

SH.

REV

.1

A07

1790

-118

PARKER HANNIFIN CORPORATIONSPORLAN DIVISION

GREENFIELD, TENNESSEE, U.S.A. 38230

UNLESS OTHERWISE SPECIFIEDDIMENSIONS ARE IN INCHESDIMENSIONS ARE AFTER PLATINGTOLERANCE ON:

.XX� .03

.XXX� .005

ANGLES� 2�

FINISH PER ANSI Y14.36REMOVE ALL BURRS

DIMENSIONING PER ANSI Y14.5WORK TO DIMENSIONS

DO NOT SCALE

ALL DIAMETERS MUST BECONCENTRIC WITHIN T.I.R.

ALL CORNERS .015/.005 R. OR BREAK

DATE:

DATE:

DATE:

DATE:DRAWN BY:

CHECKED BY:

APPROVED BY:

RELEASE ECN:

REFERENCE:

CUSTOMER:

CUSTOMER PART NO.:

DRAWING TITLE:

DRAWING NUMBER:SIZE M/P REV.

SCALE SHEET1 /2

1 1/8 ASSEMBLY

M

1 : 2

AD 071790-118

PBR 6/18/2014

Q15022GF

MITSUBISHI ELEC

PAC-SPRFCS118

REDUCER 1 1/8 X 7/8 W01337 212RPE-48-BD FILTER40455511156% BRAZE ALLOYAR10BRAZE ALLOYBLOCKADEAR9SPORLAN EBVT-109050204238ATM RELIEF VALVE17STRAIGHT TUBE1 1!8 TUBE 4 BRASS CV26CATCH-ALL - RSF-489-T 1-1/8 ODF800501-000154 BOLT CHECK VALVE141 1/8 SWAGE TUBE1 1/8 TUBE 3231 1/8 TUBE1 1/8 TUBE 2221 1/8 BENT TUBE11

Parts ListDESCRIPTIONPART NUMBERQTYITEM

REVISION HISTORYREV DESCRIPTION ECN NO. BY DATE

A DRAWN PBR 6/18/2014

5.9919.41

24.1320.85

510

1

8 10

6

410

3 9

839

2

810

6

2

12PLACE 2 FITTINGS

IN PLASTIC BAG ANDINCLUDE WITH ASSEMBLY

PRESSURERELIEF VALVE

BALL VALVE

BALL VALVE

BA

LL V

ALV

E

CHECK VALVETO PREVENT

REVERSE FLOW