design column

Upload: aziah-amir

Post on 04-Jun-2018

262 views

Category:

Documents


2 download

TRANSCRIPT

  • 8/13/2019 design column

    1/33

    REINFORCED CONCRETE

    COLUMN

  • 8/13/2019 design column

    2/33

    Column Design Procedures:

    A procedure for carrying out the detailed

    design of braced columns (i.e. columns that do

    not contribute to resistance of horizontal

    actions) is shown in Table 1. This assumesthat the column dimensions have previously

    been determined during conceptual design or

    by using quick design methods. Column sizes

    should not be significantly different from thoseobtained using current practice.

  • 8/13/2019 design column

    3/33

  • 8/13/2019 design column

    4/33

    Column can be classified as:

    Braced where the lateral loads are resisted byshear wall or other form of bracing capable oftransmitting all horizontal loading to the foundations;and

    Unbraced where horizontal load are resisted bythe frame action of rigidity connected columns,beams and slabs.

    With a braced structure, the axial forces and moments in the columns arecaused the vertical permanent and variation action only, whereas with anunbraced structure, the loading arrangement which include the effects of

    lateral load must also be considered

  • 8/13/2019 design column

    5/33

    Loading and Moments

    For a braced structure, the critical arrangement of the ultimate loadis usually that which causes the largest moment in the column

    together with a larger axial load. Figure 2 shows the critical loading

    arrangement for design of its centre column at the first floor level

    and also the left-hand column at all floor levels.

    1.35 Gk + 1.5 Qk

    1.35 Gk + 1.5 Qk

    1.35 Gk + 1.5 Qk

    1.35 Gk

    Figure. 2: A critical loading arrangement

  • 8/13/2019 design column

    6/33

    Slenderness ratio of a column

    Eurocode 2 states that second order effects may be ignored if theyare less than 10% of the first order effects. As an alternative, if theslenderness () is less than the slenderness limit ( lim), then secondorder effects may be ignored.

    The slenderness ratio of a column bent about an axis is given by:

    Where:

    lo - effective height of the columni - radius of gyration about the axis

    I - the second moment of area of the section about the axis

    A - the cross section area of the column

    A

    I

    li

    l 00

  • 8/13/2019 design column

    7/33

    Effective height lo

    of a column lo is the height of a theoretical column of equivalent section but pinned at both ends. This depends on the degree of fixity at each end and of the column.

    Depends on the relative stiffness of the column and beams connected to either end of

    the column under consideration.

    Two formulae for calculating the effective height:

    Figure 3: Different

    buckling modes and

    corresponding effective

    height for isolated column

  • 8/13/2019 design column

    8/33

    i) For braced member

    ii) For unbraced member the larger of:

    And

    2

    2

    1

    10

    45.0

    1

    45.0

    15.0

    k

    k

    k

    kll

    kk

    xkkll

    1

    21

    0 101

    2

    2

    1

    10

    11

    11

    k

    k

    k

    kll

  • 8/13/2019 design column

    9/33

    Where

    k1 and k2relative flexibility of the rotational restrains at end 1 and 2 of thecolumn respectively. At each end k1 and k2can be taken as:

    k = column stiffness/ beam stiffness

    =

    =

    For a typical column in a symmetrical frame with span approximately equal

    length, k1 and k2can be calculated as:

    beam

    column

    lEI

    lEI

    )/(2

    )/(

    beam

    column

    lI

    lI

    )/(2

    )/(

    beam

    column

    lI

    lIkkk

    )/(

    )/(

    4

    121

  • 8/13/2019 design column

    10/33

    Limiting Slenderness Ratio short or slender columnsEurocode 2 states that second order effects may be ignored if they are less than 10% of the first

    order effects. As an alternative, if the slenderness () is less than the slenderness limit (lim), then

    second order effects may be ignored. Slenderness,

    = lo/i

    where i= radius of gyration

    Slenderness limit:

    Where:

    A = 1/(1+0.2ef) (if ef is not known,A = 0.7 may be used)

    B =

    w= (if w, reinforcement ratio, is not known, B = 1.1 may be used)

    C = 1.7 rm (if rm is not known, C = 0.7 may be used see below)

    n =

    rm =

    M01, M02 are the first order end moments, | M02| | M01|

    If the end moments M01 and M02 give tension on the same side, rm should be taken positive.

    w21

    cdc

    Ed

    fA

    N

    02

    01

    M

    M

  • 8/13/2019 design column

    11/33

    ** Of the three factorsA, B and C, C will have

    the largest impact on lim and is the simplest to

    calculate. An initial assessment of lim can

    therefore be made using the default values

    for A and B, but including a calculation for

    C. Care should be taken in determining Cbecause the sign of the moments makes a

    significant difference. For unbraced

    members C should always be taken as0.7.

  • 8/13/2019 design column

    12/33

    Example:

    Determine if the column in the braced frame shown in

    Figure 4 is short or slender. The concrete strength fck =

    25 N/mm2 and the ultimate axial load = 1280 kN

    Hcol=3.5m

  • 8/13/2019 design column

    13/33

    Effective column height lo

    Icol = 400 x 3003/12 = 900 x 106 mm4

    Ibeam = 300 x 5003/12 = 3125 x 106 mm4

    k1 = k2= =0.096

    = 0.59 x 3.0 = 1.77 m

    Slenderness ratio :Radius of gyration, i=

    Slenderness ratio

    3636

    104/1031252(2

    103/10900

    /2

    /

    xxx

    xx

    lI

    lI

    beambeam

    colcol

    2

    2

    1

    10

    45.01

    45.015.0

    k

    k

    k

    kll

    mmh

    bh

    bh

    A

    I

    col

    col 6.8646.3

    12/3

    4.206.86

    1077.1 30 x

    i

    l

  • 8/13/2019 design column

    14/33

    For braced column,

    > 20.4

    )/(/2.26lim cdcED fAN

    866.05.1/2585.0300400

    101280)/(

    3

    xxx

    xfAN cdcED

    25.30866.02.26lim x

  • 8/13/2019 design column

    15/33

    REINFORCEMENT DETAILS

    Longitudinal steelA minimum of four bars is required in the

    rectangular column (one bar in each corner) and

    six bars in circular column. Bar diameter should

    not be less than 12 mm.

    The minimum area of steel is given by:c

    yk

    Eds A

    f

    NA 002.0

    87.0

    10.0

  • 8/13/2019 design column

    16/33

    Links

    The diameter of the transverse reinforcement should not

    be less than 6 mm or one quarter of the maximumdiameter of the longitudinal bars.

    Spacing requirements

    The maximum spacing of transverse reinforcement(i.e.links) in columns (Clause 9.5.3(1)) should not

    generally exceed:

    20 times the minimum diameter of the longitudinalbars.

    the lesser dimension of the column.

    400 mm.

  • 8/13/2019 design column

    17/33

    DESIGN MOMENTFor braced slander column, the design bending moment is illustrated

    in Figure 5 and defined as:MEd = max {M02, M0e + M2, M01 + 0.5 M2, NEd.e0}

    For unbraced slender column:

    MEd = max {M02 + M2, NEd.e0}

    Where:M01 = min {|Mtop|, |Mbottom|} + ei NEdM02 = max {|Mtop|, |Mbottom|} + ei NEde0 = max {h/30, 20 mm}

    ei = lo/400Mtop, Mbottom = Moments at the top and bottom of the

    column

  • 8/13/2019 design column

    18/33

    Figure 5: Design bending moment

  • 8/13/2019 design column

    19/33

    M0e = 0.6 M02 + 0.4 M01 0.4 M02

    M01 and M02 should be positive if they give tension on thesame side.

    M2 = NEd x e2 = The nominal second order moment

    Where:

    NEd = the design axial loade2 = Deflection due to second order effects =

    lo = effective length

    c = a factor depending on the curvature distribution,normally

    1/r = the curvature = Kr . K . 1/r0

    c

    l

    r

    01

    102

  • 8/13/2019 design column

    20/33

    Kr = axial load correction factor =

    Where, n =

    K = creep correction factor =

    Where:

    ef= effective creep ratio =

    = 0, if ( < 2, M/N > h, 1/r0 < 75)

    = 0.35 + fck/200 /150

    1/r0 =

    A non-slender column can be designed ignoring secondorder effects and therefore the ultimate design moment,

    MEd = M02.

    4.0,1,/ balucdcEd nwnfAN

    1/ baluu nnnn

    cdcyds fAfAw /

    11 ef

    EdEqp MjM 00 /

    dEfd sydyd 45.0//)45.0/(

  • 8/13/2019 design column

    21/33

    SHORT COLUMN RESISTING MOMENTS AND

    AXIAL FORCES

    The area of longitudinal reinforcement isdetermined based on:

    Using design chart or construction M-Ninteraction diagram.

    A solution a basic design equation.

    An approximate method

    A column should not be designed for a momentless than NEdx emin where emin has a gratervalue of h/300 or 20 mm

  • 8/13/2019 design column

    22/33

    DESIGN CHARTThe basic equation:

    NEd design ultimate axial load

    MEd design ultimate moment

    s the depth of the stress block = 0.8x(Figure 6)

    As the area of longitudinal reinforcement in the more highlycompressed face

    As the area of reinforcement in the other face

    fsc the stress in reinforcementAsfs the stress in reinforcementAs, negative when tensile

    sscccEd FFFN

    sssscck AfAfbsf '567.0

    2'222

    h

    dFd

    h

    F

    sh

    FM sscccEd

  • 8/13/2019 design column

    23/33

    Figure 6: Column section

    Figure 7: Example of

    column design chart

  • 8/13/2019 design column

    24/33

    Two expressions can be derived for the area of steel required,(based on a rectangular stress block, see Figure 8) one for the axialloads and the other for the moments:

    AsN/2 = (NEd fcd b dc) / [(sc st) c]

    Where:

    AsN/2 = Area of reinforcement required to resist axial load

    NEd = Axial load

    fcd = Design value of concrete compressive strengthsc (st) = Stress in compression (and tension) reinforcement

    b = Breadth of section

    c = Partial factor for concrete (1.5)

    dc = Effective depth of concrete in compression

    = x h = 0.8 for C50/60

    x = Depth to neutral axis

    h = Height of section

  • 8/13/2019 design column

    25/33

    AsM/2 = Total area of reinforcement required to resist moment

    = [M fcd b dc(h/2 dc/2)] / [(h/2d2) (sc+st) c]

    Example:

    Figure 8 shows a frame of heavily loaded industrial structure for which thecentre column along line PQ are to be designed in this example. The frameat 4m centres are braced against lateral forces and support the followingfloor loads:

    Permanent action, gk - 10 kN/m2

    Variable action, qk - 15 kN/m2

    Characteristic materials strength arefck= 25 N/mm2 and fyk= 500 N/mm2

    Maximum ultimate load at each floor:

    = 4.0 (1.35gk+ 1.5qk) per meter length of beam

    = 4.0 (1.35 x 10 + 1.5 x 15)

    = 144 kN/mMinimum ultimate load at each floor:

    = 4.0 x 1.35gk

    = 4.0 x (1.34 x 10)

    = 54 kN per meter length of beam

  • 8/13/2019 design column

    26/33

    Figure 8: Column structure

  • 8/13/2019 design column

    27/33

    Column load:

    1st floor = 144 x 6/2 + 54 x 4/2 = 540 kN

    2nd and 3rd floor = 2 x 144 x 10/2 = 1440 kN

    Column self weight = 2 x 14 = 28 kN

    NEd = 2008 kN

  • 8/13/2019 design column

    28/33

    Figure 10: Results summary

    Column moments

    Member stiffness:

    kBC= 1.07 x 10-3kcol= 0.53 x 10-3

    k = [0.71 + 1.07 + (2 x 0.53)]10-3 = 2.84 x 10-3

    333

    1071.0612

    7.03.0

    2

    1

    122

    1

    2

    AB

    AB

    L

    bhk

  • 8/13/2019 design column

    29/33

    Distribution factor for column =

    Fixed end moments at B are:

    F.E.MBA =

    F.E.MBC =

    Column moment MEd = 0.19 (432 72) = 68.4 kNm

    At the 3rd floor

    k = (0.71 + 1.07 + 0.53) 10-3 = 2.31 x 10-3

    Column moment MEd =

    19.084.2

    53.0

    k

    kcol

    kNm43212

    6144 2

    kNm7212

    454 2

    kNm6.82)72432(31.2

    53.0

  • 8/13/2019 design column

    30/33

    400

    300

    4H25 4H16

    H8 at 300

    H8 at 300

    Ground to 1st

    Floor 1st

    to 3rd

    Floor

    Figure 10: Column reinforcement details

  • 8/13/2019 design column

    31/33

    BIAXIAL BENDING

    The effects of biaxial bending may be checked using Expression

    (5.39), which was first developed by Breslaer.Where:

    Medz,y = Design moment in the respective direction including secondorder effects in a slender column

    MRdz,y = Moment of resistance in the respective directionA = 2 for circular and elliptical sections; refer to Table 1 for

    rectangular sections

    NRd =Acfcd +Asfyd

    Table 1: Value of a

    for a rectangular

    section

  • 8/13/2019 design column

    32/33

    Either or

    Where ey and ez are the first-order eccentricities in thedirection of the section dimensions b and h respectively.

    (a) If then the increased single axis design

    moment is

    (b) if then the increased single axis design

    moment is

    2.0/ b

    e

    h

    e yz 2.0/ b

    e

    b

    ezy

    ,'' b

    M

    h

    M yz

    yzz xMbhMM'''

    ,'' b

    M

    h

    M yz

    zyy xMbhMM'''

  • 8/13/2019 design column

    33/33

    The dimension hand bare defined in Figure 11 and the

    coefficient is specified as:ck

    Ed

    bhf

    N 1

    Figure 11: Section with biaxial

    bending