Floor Heating History:
Floor Heating System goes
back more than 2000 years;
ROMAN AGE
-
7/29/2019 Design Presentation [Compatibility Mode]
3/28
we have it all
2 reasons:
-
7/29/2019 Design Presentation [Compatibility Mode]
4/28
we have it all
Ideal Heating Floor Heating Ceiling Heating Radiator HeatingOuter Wall
Radiators HeatingInner Wall
-
7/29/2019 Design Presentation [Compatibility Mode]
5/28
Design Process:we have it all
Design Process:Heat Load Calculations:
Heat load is ;
=
Where Q = U A (T in - T out)
Q infiltration + Q ventilation
And U = 1/Sum R ; where R is thermal resistance
=
k is the thermal conductivity.
ere s t e area w ere eat s trans erre t roug .
T in; is the room temperature.
T out; is the outside temperature (fixed value for each city).
-
7/29/2019 Design Presentation [Compatibility Mode]
6/28
Design Process:we have it all
Design Process:Heat Load Calculations:
Then;
= * *
Q ceiling = U ceiling * Aceiling * (T in T out)
* *oor oor n ou
Qwindow= U window* Awindow* (T in T out)
oor = door door in out
Note that the U-value for windows & doors are obtainedfrom the manufacturer.
-
7/29/2019 Design Presentation [Compatibility Mode]
7/28
Design Process:we have it all
Design Process:Heat Load Calculations:
But;
= * * *
QVentilation = f * V * Number of air change per hour * (T in T out)
Where;
Vis the volume
F factor = 12 0 600Rooms in
Resedential No of A-Ch
No External Windows,doors 0.50
As for ventilation the air changevalues are according to required.
One Side External Windows,doors 1.00
Two Sides External Windows,doors 1.50
ree es x erna n ows, oors .
Entrance Halls 2.00
-
7/29/2019 Design Presentation [Compatibility Mode]
8/28
Design Process:we have it all
Design Process:Heat Load Calculations:
Note: when calculating the thermal resistance the air films
that are in touch with the wall, ceiling or floor are takennto cons erat on as a convect ona res stance.
Wall Ceiling Floor
Heat transfer Horizantal Upword Downword
Wall Ceiling
Exposed
floor
Wind Speed at 5 m/s at 5 m/s at 0.5 m/s
Ri (m2K/W) 0.12 0.10 0.15Ro (m2K/W) 0.03 0.02 0.09
R = Ri + x1/k1 + x2/k2 + x3/k3 ++ Ro
-
7/29/2019 Design Presentation [Compatibility Mode]
9/28
we have it all
The final result is the heat load for each room
Room
No.
Q. Wall
Ext.
Q.
Window
Q.
Door
Q.
Infltrtion
Q.
Infltrtion Q. Floor Q. Ceiling
Q. Total
(kcal/h)
Q. Total/A.
(kcal/h.m^2)
Q.total/A(W/
m^2)
Gr 01 551.43 1324.40 385 1.50 2629.83 1644.62 1644.62 7052.93 107.56 125.1
Gr 02 303.60 385.00 0 1.00 1110.48 1041.70 1041.70 3347.83 80.60 93.7
. . . . . . . . .
Gr 04 76.82 36.96 0 1.00 206.94 194.12 194.12 612.03 180.01 209.3
Gr 05 240.90 481.25 0 1.00 1309.53 1228.42 1228.42 3870.28 161.26 187.5
Gr 06 69.96 77.00 0 1.00 197.31 185.09 185.09 616.77 83.57 97.2
Gr 07 687.72 1108.80 385 1.50 2807.29 1755.60 1755.60 7328.89 348.99 405.8
. . . . . . . . .
Gr 09 646.80 0.00 1732.5 1.50 7700.00 2407.68 2407.68 12841.52 133.77 155.5
Gr 10 366.96 554.40 0 1.00 1366.22 1281.59 1281.59 4182.54 81.85 95.2
Gr 11 125.40 77.00 0 1.00 162.82 152.74 152.74 579.05 26.32 30.6
Gr 12 256.08 770.00 0 1.50 707.04 442.16 442.16 2257.70 128.06 148.9
-
7/29/2019 Design Presentation [Compatibility Mode]
10/28
we have it all
Design Process:
28C - 29C --- Live area inside the room.
31C -
32C --- Surrounding areas and bathrooms.
-
7/29/2019 Design Presentation [Compatibility Mode]
11/28
we have it all
Design Process:
.
Accordingly, we obtainQ/A(watt/m2 )
From Under Floor Heating Tables wecan then choose the right spacing
Heat Pipe diameter
W/m2 0.16 m 0.20 m 0.25 m
choosing the pipe diameter for the
required system.
0-60 0.30 m 0.30 m 0.40 m
60-70 0.25 m 0.25 m 0.30 m
70-80 0.25 m 0.30m 0.30 m
Note: if the heat is more than UFHsystem can give, then auxiliary heating
80-90 0.20 m 0.25m 0.25 m
90-100 0.20 m 0.20 m 0.25 m
.
is required.
- . . .
110-120 0.10 m 0.10 m 0.15 m
120-130 0.10 m 0.10 m 0.15 m
-
7/29/2019 Design Presentation [Compatibility Mode]
12/28
we have it all
Design Process:
L length = Aavailable area / S spacing
The length from the beginning of the room to the cabinet isalso measured and added to the length inside the room.
L length = (Aavailable area / S spacing) + L1
Where L1 is the distance from room to cabinet multipliedy
And since it is recommended that;
The length of a single loop is less than 120m.
The difference between loops lengths are not high.
-
7/29/2019 Design Presentation [Compatibility Mode]
13/28
we have it all
Design Process:
Since it is always recommended that the spacing at the,two areas;
1 is for reduced s acin S1 near external walls
A1 = 0.6 * B
A 2 is for normal spacing S2;
=
where A is the total area for the room
en length = 1 1 + 2 2
-
7/29/2019 Design Presentation [Compatibility Mode]
14/28
we have it all
-
7/29/2019 Design Presentation [Compatibility Mode]
15/28
Design Processwe have it all
Design Process:The average water temperature Tavg for the system isthen calculated for each zone after according to thelayers above the UFH pipes (the thermal resistances forthese layers)
Chose the designT = TS - TR Normally taken as 8 C
Where:TS
is water supply temperature.
TRis water return temperature.
-
7/29/2019 Design Presentation [Compatibility Mode]
16/28
we have it all
10mm Ceramic Tiles
20mm Morter
40mm Sand
20mm Screed
Pipes
Layer X (m) K (w/mK) R (m2K/W) T1 T2
. . . . .
Morter 0.025 1.400 0.018 29.67 31.45
Sand 0.032 0.700 0.046 31.45 36.02
Screed 0.030 1.200 0.025 36.02 38.52. . . . .
Tsup Tret
0.097 0.100 42.99 34.99
0.179
resistivity) 0.100 m2K / W
U (overall heat
transfer coeff.)
10.011 W / m2K
-
7/29/2019 Design Presentation [Compatibility Mode]
17/28
we have it all
14 mm Solid wood
3 mm Airgap
20 mm morter
20 mm sand
20 mm Screed
0.002mm Pipes
Layer X (m) K (w/mK) R (m2K/W) T1 T2
Solis wood 0.014 0.150 0.093 29.00 39.73
airgap 0.003 0.100 39.73 51.23
Terrazo 0.025 1.200 0.021 51.23 53.63
Morter 0.020 1.400 0.014 53.63 55.27
Sand 0.020 0.700 0.029 55.27 58.56Screed 0.020 0.870 0.023 58.56 61.20
Pipe 0.002 0.430 0.005 61.20 61.74
Tsup Tret
0.104 65.74 57.74
R (thermal
resistivity) 0.285 m2K / W
U (overall heat
transfer coeff.)
3.513 W / m2K
-
7/29/2019 Design Presentation [Compatibility Mode]
18/28
we have it all
es gn rocess:
The flow rate for each zone is calculated and also theflow rate for each branch;
Q = m * Cp * T
Then the pressure drop is calculated for each branchand for the main pipe for each zone.
Where:
Pmain is found according to m main
rom e pressure rop curves.
P branch is found according to m branch
-
7/29/2019 Design Presentation [Compatibility Mode]
19/28
we have it all
-
7/29/2019 Design Presentation [Compatibility Mode]
20/28
we have it all
Design Process:
- = a
-T = 8 C
Then:
TR = 40 - 8/2 = 36 C
S
-
7/29/2019 Design Presentation [Compatibility Mode]
21/28
we have it all
In order to calculate the pressure drop
known.
Diameter of main pipe must be known
-
7/29/2019 Design Presentation [Compatibility Mode]
22/28
we have it all
Heat load for the zone must be calculated Q (Watts)
Temperature difference for the system must be defined (T)
Mass flow rate is then calculated from equation
M = C * T
Diameter of the main pipe must be defined
Pressure drop per meter length is then found from pipe chart.
s va ue s t en mu t p e y t e engt o t e p pe.
-
7/29/2019 Design Presentation [Compatibility Mode]
23/28
we have it all
-
7/29/2019 Design Presentation [Compatibility Mode]
24/28
we have it all
Heat load for each branch must be defined Q (Watts).
Temperature difference for the branch must be defined (T).
Mass flow rate is then calculated for each branch from theequation: M = Q / (Cp* T)
The critical branch must be defined. Which is the one withhighest pressure drop.
Diameter for each branch must be defined.
ressure rop s t en oun rom p pe c art or eac rancand multiplied by the length of the pipe.
.
-
7/29/2019 Design Presentation [Compatibility Mode]
25/28
we have it all
Pressure drop for fittings such as manifolds, elbows,etc. is
Pressure drop for other parts of the system must be calculated.
also calculated (detailed or approximate).
t ree way va ves, stra ners,..
The total pressure drop then is;
The flow rate is known.P = P
(main)
+ P(branch)
+ P(fittings & parts)
The pump is then selected, by finding one that covers therequired flow and pressure drop (head).
-
7/29/2019 Design Presentation [Compatibility Mode]
26/28
we have it all
Pump Curve;
The total pressure drop:
P (mbar)
The total flow rate:
m (l/s).
h it ll
-
7/29/2019 Design Presentation [Compatibility Mode]
27/28
Design Processwe have it all
Design Process:
Calculate the total heat load forunder floor heating.
Add other extra loads such as;domestic hot water, other heatingnetworks, swimming pools, etc.
Safety factor should be addeddepending on the boiler efficiency.
h it ll
-
7/29/2019 Design Presentation [Compatibility Mode]
28/28
Design Processwe have it all
Design Process:
balanced UFH system.