determination of critical clearing time in transient

5
Determination of Critical Clearing Time in Transient Stability Analysis Yurika School of Electrical Engineering and Informatics Institut Teknologi Bandung Bandung, Indonesia [email protected] Gibson HM Sianipar School of Electrical Engineering and Informatics Institut Teknologi Bandung Bandung, Indonesia [email protected] Janson Naiborhu Faculty of Mathematics and Natural Sciences Institut Teknologi Bandung Bandung, Indonesia [email protected] Suwarno School of Electrical Engineering and Informatics Institut Teknologi Bandung Bandung, Indonesia [email protected] Abstract— Transient stability analysis is important in planning and operating on power system. Several methods or approaches have been taken to analyze transient stability. One approach to determining the transient stability of a power system is critical clearing time. It provides information about the level of stability of the existing system. When a disturbance occurs, the power system must be able to maintain stable conditions. Therefore in this paper, analysis of critical clearing time calculation is needed as an alternative to determine the transient stability of power system. For 9 buses and 3 machines, the critical clearing time of the system will vary depending on the location of the disturbance. Keywords— transient stability, stable, critical clearing time I. INTRODUCTION An electric power system aims to maintain continuity and availability of electric power to the increasing needs of the load. The more developed the electric power system can lead to increasingly complex systems when experiencing disturbance. In a power system, generally the disturbance that occurs can be divided into two parts, namely small disturbances and large disturbances. Small disturbances are disturbances due to changes in load that occur at the side of the load or generator randomly and slowly. These disturbances can be analyzed using linear equations or using small signal analysis. Whereas a large disturbance is a disturbance that occurs suddenly on the system and must be eliminated as quickly as possible because it can affect the stability of an existing system. Stability in the power system can be affected by the size of disturbance and the duration of disturbance that occurs in a power system. The stability of the electric power system is the ability of the system to return to normal operation after the system is subject to a disturbance [1]. Instead the instability of an electric power system is a condition where the system losses synchronization. Stability analysis has an important role in the power system. The more complex a system, the more complex the ability to maintain synchronism between parts of the system. For large systems with interconnections, power system results in changes in electrical parameters, including voltage, current, power, rotor speed, frequency and power angle. To analyze changes in these parameters to the length of the disturbance, from the beginning of the disturbance until the system becomes stable again, it is necessary to calculate when the disturbance is decided without losing the simultaneity of the generator. System stability depends on the load used, increasing the load can trigger instability. The stability of the power system can be classified into several parts. Transient or large signal rotor angle stability is one of most important types of stability phenomena. Transient stability is the ability of power system to maintain its synchronism under a severe fault such as three phase short circuit [1]. Due to changes in the system conditions immediately, the state of the system can change from the old state to the new state. The short period between the two conditions is called a transient period. Therefore an electrical power system analysis is needed to determine whether the system is stable or unstable when experiencing interference. II. TRANSIENT STABILITY ASSESSMENT A. Energi Function Based on the references [2]–[4] that the energy function method is the result of the transformation of the Lyapunov function into the energy function. This method is closely related to the kinetic energy and potential energy of the generator, with kinetic energy strongly related to the relative motion of the generator while potential energy is strongly related to network elements. The most critical energy is determined by the closest potential energy between the unstable equilibrium point and the stable equilibrium point. Energy function theory in the analysis of multi-machine transient stability can be analogous to a ball rolling in a bowl where the coordinate is the generator rotor angle. The area in a bowl is a region of stability while the area outside the bowl is an unstable area (region of instability). At the initial position or normal conditions, the ball is at the bottom of the bowl and this state is called Stability Equilibrium Point (SEP). The surface inside the bowl expresses potential energy while the peak of the bowl states Potential Energy Boundary Surface (PEBS). If the kinetic energy is converted to potential energy before reaching the top, then the ball will return back to the starting position (bottom of the bowl), this condition is called a stable condition. But if the kinetic energy is too large and has not been completely converted to potential energy, the ball will pass through the top of the bowl and enter the unstable region, this condition is called unstable. Reference [5] also shows the application of the energy function for the generator in a balanced condition and when the generator is subject to a disturbance as shown in Fig. 1. It 2018 International Conference on Electrical Engineering and Computer Science (ICEECS) 115

Upload: others

Post on 02-Oct-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Determination of Critical Clearing Time in Transient

Determination of Critical Clearing Time in Transient Stability Analysis

Yurika School of Electrical

Engineering and Informatics Institut Teknologi Bandung

Bandung, Indonesia [email protected]

Gibson HM Sianipar School of Electrical

Engineering and Informatics Institut Teknologi Bandung

Bandung, Indonesia [email protected]

Janson Naiborhu Faculty of Mathematics and Natural

Sciences Institut Teknologi Bandung

Bandung, Indonesia [email protected]

Suwarno School of Electrical

Engineering and Informatics Institut Teknologi Bandung

Bandung, Indonesia [email protected]

Abstract— Transient stability analysis is important in planning and operating on power system. Several methods or approaches have been taken to analyze transient stability. One approach to determining the transient stability of a power system is critical clearing time. It provides information about the level of stability of the existing system. When a disturbance occurs, the power system must be able to maintain stable conditions. Therefore in this paper, analysis of critical clearing time calculation is needed as an alternative to determine the transient stability of power system. For 9 buses and 3 machines, the critical clearing time of the system will vary depending on the location of the disturbance.

Keywords— transient stability, stable, critical clearing time

I. INTRODUCTION

An electric power system aims to maintain continuity and availability of electric power to the increasing needs of the load. The more developed the electric power system can lead to increasingly complex systems when experiencing disturbance. In a power system, generally the disturbance that occurs can be divided into two parts, namely small disturbances and large disturbances. Small disturbances are disturbances due to changes in load that occur at the side of the load or generator randomly and slowly. These disturbances can be analyzed using linear equations or using small signal analysis. Whereas a large disturbance is a disturbance that occurs suddenly on the system and must be eliminated as quickly as possible because it can affect the stability of an existing system. Stability in the power system can be affected by the size of disturbance and the duration of disturbance that occurs in a power system.

The stability of the electric power system is the ability of the system to return to normal operation after the system is subject to a disturbance [1]. Instead the instability of an electric power system is a condition where the system losses synchronization. Stability analysis has an important role in the power system. The more complex a system, the more complex the ability to maintain synchronism between parts of the system. For large systems with interconnections, power system results in changes in electrical parameters, including voltage, current, power, rotor speed, frequency and power angle. To analyze changes in these parameters to the length of the disturbance, from the beginning of the disturbance until the system becomes stable again, it is necessary to calculate when the disturbance is decided without losing the simultaneity of the generator.

System stability depends on the load used, increasing the load can trigger instability. The stability of the power system can be classified into several parts. Transient or large signal rotor angle stability is one of most important types of stability phenomena. Transient stability is the ability of power system to maintain its synchronism under a severe fault such as three phase short circuit [1]. Due to changes in the system conditions immediately, the state of the system can change from the old state to the new state. The short period between the two conditions is called a transient period. Therefore an electrical power system analysis is needed to determine whether the system is stable or unstable when experiencing interference.

II. TRANSIENT STABILITY ASSESSMENT

A. Energi Function

Based on the references [2]–[4] that the energy functionmethod is the result of the transformation of the Lyapunov function into the energy function. This method is closely related to the kinetic energy and potential energy of the generator, with kinetic energy strongly related to the relative motion of the generator while potential energy is strongly related to network elements. The most critical energy is determined by the closest potential energy between the unstable equilibrium point and the stable equilibrium point.

Energy function theory in the analysis of multi-machine transient stability can be analogous to a ball rolling in a bowl where the coordinate is the generator rotor angle. The area in a bowl is a region of stability while the area outside the bowl is an unstable area (region of instability). At the initial position or normal conditions, the ball is at the bottom of the bowl and this state is called Stability Equilibrium Point (SEP). The surface inside the bowl expresses potential energy while the peak of the bowl states Potential Energy Boundary Surface (PEBS). If the kinetic energy is converted to potential energy before reaching the top, then the ball will return back to the starting position (bottom of the bowl), this condition is called a stable condition. But if the kinetic energy is too large and has not been completely converted to potential energy, the ball will pass through the top of the bowl and enter the unstable region, this condition is called unstable.

Reference [5] also shows the application of the energy function for the generator in a balanced condition and when the generator is subject to a disturbance as shown in Fig. 1. It

2018 International Conference on Electrical Engineering and Computer Science (ICEECS)

115

Page 2: Determination of Critical Clearing Time in Transient

shows also the trajectory for a stable and unstable area due to the movement of the ball in the bowl.

Mathematically the energy function can be written as in the equation below:

, = + (1)

The kinetic energy produced depends on the speed of the generator, while the potential energy depends on the angle of the generator. When described again, equation (1) will be: = ∑ − ∑ − −∑ ∑ cos − cos −

(2)

= cos − sin (3)

where is kinetic energy, is potential energy, and is the angle of the bus i post fault stable equilibrium point (SEP).

R R

θω θω

θωθω

θω

θω

θω

θω

SEPForward movement

Backward movement

θω

θω

θω

θω

SEPForward movement

Backward movement

θω

System is stable System is unstable

Fig. 1. Concept of energy function in the generator [5]

To conduct a transient stability analysis, the reference used is the difference between critical energy or critical unstable equilibrium point (Vcr) and energy when fault clearance (Vcl). If the fault clearing is negative then the system is declared to be in an unstable condition. Conversely, if the result is positive, the system is declared to be in a stable condition. The following equation shows the magnitude of the energy margin (ΔV) produced, namely:

∆ = − (4)

If the positive stability index can be said to be a stable

The steps in analyzing the stability of transients by using energy functions are: reading machine and network data to determine the power flow, determining the matrix admittance

network matrix Y before a pre-fault occurs, determining the Y matrix is reduced when fault on and after the pre-fault, determines the rotor angle when the fault is cleared for all generators, determines the value of SEP (stable equilibrium point) and UEP (unstable equilibrium point), and determines the energy margin (ΔV).

B. Critical Clearing Time

CCT (Critical Clearing Time) is the critical time ormaximum time needed by the synchronous generator to maintain the condition of the generator remains in synchronization. The electric power system becomes unstable when the rotor angle becomes larger. This increase in greatly affects the change in power so that, by obtaining the rotor angle, the critical clearing time can be determined. If a disturbance occurs and the system cannot handle it, so the system is declared unstable. This instability affects the entire system. Therefore, it is necessary to determine the critical clearing time to avoid any disturbances.

Various studies have been carried out in analyzing transient stability. Previously, transient stability analysis still used numerical integration of nonlinear differential equations. This method is quite accurate in calculating critical clearing time in a multi-machine power system and is able to provide an overview of the power system stability due to transient symptoms. However, numerical integration that is so long in the process of calculating critical clearing time causes this method to take a long time in the iteration process. This is very ineffective when applied to transient stability analysis. Because, the pattern of changes that occur due to disturbances that occur very quickly in the system. Therefore, we need a method that can calculate critical clearing time with a faster and more accurate iteration, so that it can be applied significantly to the system.

Determination of the critical clearing time in transient stability analysis through stages, namely: 1. The process of power flow, by calculating the internal

voltage of all generators, calculating the admittance matrixfor each network condition, before, during and after adisturbance.

2. Determine the location of the disturbance.3. Determine the critical termination time based on the critical

clearing angle.

III. CASE STUDY

The first step taken to determine the transient stability is to simulate the power flow in the system. In power system 9 buses and 3 machines, power flow simulations are carried out to determine the condition of the system before and after the disturbance occurs. The software used in this analysis is Digsilent Power Factory for manual analysis. Simulation is carried out in each line, to determine the stability level of the system. The critical clearing time can be determined in each line, for this case the line used in the analysis is six lines. The following will be discussed power system model and simulation results.

A. Power System Model

Fig. 2 shows a single line of power system that consist of9 buses and 3 machines.

116

Page 3: Determination of Critical Clearing Time in Transient

2 3

1

4

98

7

65

32

1

Load A

Load C

Load B

18 kV 230 kV 230 kV 13.8 kV

18 kV

230 kV

Fig. 2. IEEE 9 buses and 3 machines system

Table I, II, and III show generator data, machine data, and load data for 9 buses and 3 machines.

TABLE I. GENERATOR DATA

Parameter G1 G2 G3

Rated MVA 247.5 192 128

KV 16.5 18 13.8

pf 1 0.85 0.85

Bus type SL PV PV

TABLE II. MACHINE DATA

Parameter G1 G2 G3

xd (pu) 0.36 1.72 1.68

xq (pu) 0.24 1.66 1.61

xd' (pu) 0.15 0.23 0.23

xq' (pu) 0 0.378 0.32

xd" (pu) 0.1 0.2 0.2

xq" (pu) 0.1 0.2 0.2

Td' (s) 3.73 0.8 0.806

Tq' (s) 0 0.12 0.12

Td" (s) 0.05 0.05 0.05

Tq" (s) 0.05 0.05 0.05 H (s) 9.55 4.165 2.765

TABLE III. LOAD DATA

Bus Load Active Power (MW) Reactive Power (MVAR)

5 A 125 50

6 B 90 30

8 C 100 35

B. Simulation Results

For 9 buses and 3 machines, the location of thedisturbance is determined to vary on the transmission line. There are 6 disturbance locations on the transmission line, namely point D, E, F, G, H, and I.

Table IV shows the critical clearing times for various fault locations in the 9 buses and 3 machines systems.

TABLE IV. CRITICAL CLEARING TIME WITH VARIOUS FAULT LOCATIONS

No Fault Line (Fault) CCT (sec) D 4 – 5 0.22 – 0.23

E 4 – 6 0.24 – 0.25

F 5 – 7 0.13 – 0.14

G 6 – 9 0.19 – 0.20

H 7 – 8 0.14 – 0.15

I 8 - 9 0.20 – 0.21

Based on Table IV above it can be concluded that: • Among the disturbances that occur, disturbance that

occur between bus 5 and bus 7 (F) have the fastest clearing time.

• When the line between bus 4 and bus 5 is given adisturbance (D), the critical clearing time is between0.22 to 0.23 seconds. If the clearing time is set to morethan 0.23 seconds, the existing generator 2 andgenerator 3 will be released from the system.

• When the line between bus 4 and bus 6 is given adisturbance (E), the clearing time is between 0.24 to0.25 seconds. If the clearing time is set to more than0.25 seconds, the existing generator 2 and generator 3will be released from the system.

• When the line between bus 5 and bus 7 is given adisturbance (F), the clearing time is between 0.13 to0.14 seconds. If the clearing time is set to more than0.14 seconds then the existing generator 2 andgenerator 3 will be released from the system.

• When the line between bus 6 and bus 9 is given adisturbance (H), the clearing time is between 0.19 to0.20 seconds. If the clearing time is set to more than0.20 seconds, the existing generator 2 and generator 3will be released from the system.

• When a line between bus 7 and bus 8 is given adisturbance (G), the clearing time is between 0.14 to0.15 seconds. If the clearing time is set to more than0.15 seconds, the existing generator 2 and generator 3will be released from the system.

• When the line between bus 8 and bus 9 is given adisturbance (I), the clearing time is between 0.20 to0.21 seconds. If the clearing time is set to more than0.21 seconds then the existing generator 2 andgenerator 3 will be released from the system.

Fig. 3. Rotor angle response for CCT= 0.22 sec

117

Page 4: Determination of Critical Clearing Time in Transient

Fig. 4. Rotor angle response for CCT= 0.23 sec

Fig. 5. Rotor angle response for CCT= 0.13 sec

Fig. 6. Rotor angle response for CCT= 0.14 sec

Fig. 7. Rotor angle response for CCT= 0.24 sec

Fig. 8. Rotor angle response for CCT= 0.25 sec

Fig. 9. Rotor angle response for CCT= 0.19 sec

Fig. 10. Rotor angle response for CCT= 0.20 sec

Fig. 11. Rotor angle response for CCT= 0.14 sec

118

Page 5: Determination of Critical Clearing Time in Transient

Fig. 12. Rotor angle response for CCT= 0.15 sec

Fig. 13. Rotor angle response for CCT= 0.20 sec

Fig. 14. Rotor angle response for CCT= 0.20 sec

Based on Fig. 3, Fig. 5, Fig. 7, Fig. 9, Fig. 11 and Fig. 13 show rotor angle response for stable case. Fig. 4, Fig. 6, Fig. 8, Fig. 10, Fig. 12 and Fig. 14 show rotor angle response for unstable case.

IV. FUTURE RESEARCH

The electric power system consists of many elements. The most important element in controlling the transient characteristics of a machine is the synchronous machine. To be able to analyze transients quickly requires proper synchronous machine modeling. In addition to engine modeling, overall system modeling also influences the transient stability analysis. Transient stability analysis is carried out individually where each existing machine views

the system in front of it as a constant impedance. For this reason, the superposition principle can be used to simplify the modeling of existing systems. Based on previous research and based on papers, the possible opportunity for further research is to reverse the method used by researchers so far. Completion in analyzing modeling dq0 was done with the help of Closed Form method to analyze machines individually [13].

V. CONCLUSION

Calculation of critical clearing time for 9 buses and 3 machine is known. Disturbance that occurs in transmission line provides the results of calculating different critical clearing time. The critical clearing time determines the condition of the electric power system will be able to return to a stable or unstable condition. If the disturbance is disconnected more than the critical time, the system will be unstable.

REFERENCES

[1] P. Kundur et al., “Definition and classification of power system

stability,” IEEE Trans. Power Syst., vol. 19, pp. 1387–1401, 2004.

[2] a. Fouad and S. Stanton, “Transient Stability of a Multi-Machine

Power System. Part II: Critical Transient Energy,” IEEE Trans. Power

Appar. Syst., vol. PAS-100, no. 7, pp. 3417–3424, 1981.

[3] A. Michel, A. Fouad, and V. Vittal, “Power system transient stability

using individual machine energy functions,” IEEE Trans. Circuits

Syst., vol. 30, no. 5, pp. 266–276, 1983.

[4] H.-D. Chang, C.-C. Chu, and G. Cauley, “Direct stability analysis of

electric power systems using energy functions: theory, applications,

and perspective,” Proc. IEEE, vol. 83, no. 11, pp. 1497–1529, 1995.

[5] X. Kong, H. Jia, Y. Jiang, S. Zhao, and D. Fang, “Criterion to evaluate

power system online transient stability based on adjoint system energy

function,” IET Gener. Transm. Distrib., vol. 9, no. 1, pp. 104–112,

2015.

[6] E. W. Kimbark, Power System Stability Volume I. 1995.

[7] U. Karaagac, J. Mahseredjian, O. Saad, and S. Dennetière,

“Synchronous machine modeling precision and efficiency in

electromagnetic transients,” IEEE Trans. Power Deliv., vol. 26, no. 2,

pp. 1072–1082, 2011.

[8] L. Wang, J. Jatskevich, C. Wang, and P. Li, “A voltage-behind-

reactance induction machine model for the EMTP-type solution,”

IEEE Trans. Power Syst., vol. 23, no. 3, pp. 1226–1238, 2008.

[9] J. Marti and K. Louie, “A phase-domain synchronous generator model

including saturationeffects,” IEEE Trans. Power Syst., vol. 12, no. 1,

pp. 222–229, 1997.

[10] L. Wang, J. Jatskevich, and H. W. Dommel, “Re-examination of

synchronous machine modeling techniques for electromagnetic

transient simulations,” IEEE Trans. Power Syst., vol. 22, no. 3, pp.

1221–1230, 2007.

[11] G. H. M. Sianipar, “Closed Form Solution of Synchronous Machine

Short Circuit Transients,” vol. 42, no. 1, pp. 91–102, 2010.

[12] G. H.M. Sianipar, “The All-DQ-Domain EMTP,” ITB J. Eng. Sci.,

vol. 43, no. 1, pp. 11–26, 2011.

119