Cat ® C18 DIESEL GENERATOR SETS LEHE1772-04 1/2 Standby & Prime: 60Hz PACKAGE PERFORMANCE Image shown might not reflect actual configuration Engine Model Cat ® C18 ATAAC™ In-line 6, 4-cycle diesel Bore x Stroke 145mm x 183mm (5.7in x 7.2in) Displacement 18.13 L (1106.3 in³) Compression Ratio 14:1 Aspiration Turbocharged Air-to-Air Aftercooled Fuel Injection System Electronic Unit Injection Governor Electronic ADEM™ A4 Model Standby Prime Emission Strategy C18 750 ekW, 938 kVA 680 ekW, 850 kVA EPA TIER II Performance Standby Prime Frequency 60 Hz Genset Power Rating 938 kVA 850 kVA Genset power rating with fan @ 0.8 power factor 750 ekW 680 ekW Emissions EPA TIER II Performance Number EM3842 EM3843 Fuel Consumption 100% load with fan, L/hr (gal/hr) 205.5 (54.2) 188.5 (49.7) 75% load with fan, L/hr (gal/hr) 164.3 (43.4) 146.3 (38.6) 50% load with fan, L/hr (gal/hr) 108.9 (28.7) 100.3 (26.5) 25% load with fan, L/hr (gal/hr) 63.5 (16.7) 59.4 (15.6) Cooling System 1 Radiator air flow restriction (system), kPa (in. Water) 0.12 (0.48) 0.12 (0.48) Radiator air flow, m 3 /min (cfm) 900 (31783) 900 (31783) Engine coolant capacity, L (gal) 20.8 (5.5) 20.8 (5.5) Radiator coolant capacity, L (gal) 77 (20.3) 77 (20.3) Total coolant capacity, L (gal) 97.8 (25.8) 97.8 (25.8) Inlet Air Combustion air inlet flow rate, m³/min (cfm) 67.3 (2376) 65.6 (2316) Max. Allowable Combustion Air Inlet Temp, °C (°F) 49 (120) 49 (120) Exhaust System Exhaust stack gas temperature, °C (°F) 452.9 (847.2) 432.9 (811.2) Exhaust gas flow rate, m³/min (cfm) 170.7 (6028) 161 (5686) Exhaust system backpressure (maximum allowable) kPa (in. water) 10.0 (40.0) 10.0 (40.0) Heat Rejection Heat rejection to jacket water, kW (Btu/min) 225 (12795) 208 (11828) Heat rejection to exhaust (total) kW (Btu/min) 714 (40604) 664 (37761) Heat rejection to aftercooler, kW (Btu/min) 272 (15468) 253 (14387) Heat rejection to atmosphere from engine, kW (Btu/min) 142 (8075) 123 (6995)

Upload: others

Post on 05-Mar-2021

11 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

Cat® C18 DIESEL GENERATOR SETS

LEHE1772-04 1/2

Standby & Prime: 60Hz

PACKAGE PERFORMANCE

Image shown might not reflect actual configuration

Engine Model Cat® C18 ATAAC™ In-line 6, 4-cycle diesel

Bore x Stroke 145mm x 183mm (5.7in x 7.2in)

Displacement 18.13 L (1106.3 in³)

Compression Ratio 14:1

Aspiration Turbocharged Air-to-Air Aftercooled

Fuel Injection System Electronic Unit Injection

Governor Electronic ADEM™ A4

Model Standby Prime Emission Strategy

C18 750 ekW, 938 kVA 680 ekW, 850 kVA EPA TIER II

Performance Standby Prime

Frequency 60 Hz

Genset Power Rating 938 kVA 850 kVA

Genset power rating with fan @ 0.8 power factor 750 ekW 680 ekW

Emissions EPA TIER II

Performance Number EM3842 EM3843

Fuel Consumption

100% load with fan, L/hr (gal/hr) 205.5 (54.2) 188.5 (49.7)

75% load with fan, L/hr (gal/hr) 164.3 (43.4) 146.3 (38.6)

50% load with fan, L/hr (gal/hr) 108.9 (28.7) 100.3 (26.5)

25% load with fan, L/hr (gal/hr) 63.5 (16.7) 59.4 (15.6)

Cooling System1

Radiator air flow restriction (system), kPa (in. Water) 0.12 (0.48) 0.12 (0.48)

Radiator air flow, m3/min (cfm) 900 (31783) 900 (31783)

Engine coolant capacity, L (gal) 20.8 (5.5) 20.8 (5.5)

Radiator coolant capacity, L (gal) 77 (20.3) 77 (20.3)

Total coolant capacity, L (gal) 97.8 (25.8) 97.8 (25.8)

Inlet Air

Combustion air inlet flow rate, m³/min (cfm) 67.3 (2376) 65.6 (2316)

Max. Allowable Combustion Air Inlet Temp, °C (°F) 49 (120) 49 (120)

Exhaust System

Exhaust stack gas temperature, °C (°F) 452.9 (847.2) 432.9 (811.2)

Exhaust gas flow rate, m³/min (cfm) 170.7 (6028) 161 (5686)

Exhaust system backpressure (maximum allowable) kPa (in. water) 10.0 (40.0) 10.0 (40.0)

Heat Rejection

Heat rejection to jacket water, kW (Btu/min) 225 (12795) 208 (11828)

Heat rejection to exhaust (total) kW (Btu/min) 714 (40604) 664 (37761)

Heat rejection to aftercooler, kW (Btu/min) 272 (15468) 253 (14387)

Heat rejection to atmosphere from engine, kW (Btu/min) 142 (8075) 123 (6995)

Page 2: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

Cat® C18 DIESEL GENERATOR SETS

Emissions (Nominal)2 Standby Prime

NOx, mg/Nm³ (g/hp-hr) 2468 (5.42) 2213 (4.91)

CO, mg/Nm³ (g/hp-hr) 100.1 (0.22) 75.6 (0.17)

HC, mg/Nm³ (g/hp-hr) 23.5 (0.06) 24.1 (0.06)

PM, mg/Nm³ (g/hp-hr) 11.7 (0.03) 10.6 (0.03)

WEIGHTS & DIMENSIONS

APPLICABLE CODES AND STANDARDS:AS1359, CSA C22.2 No100-04, UL142, UL489, UL869, UL2200, NFPA37, NFPA70, NFPA99, NFPA110, IBC, IEC60034-1, ISO3046, ISO8528, NEMA MG1-22, NEMA MG1-33, 2006/95/EC, 2006/42/EC, 2004/108/EC. Note: Codes may not be available in all model configurations. Please consult your local Cat Dealer representative for availability.

STANDBY: Output available with varying load for the duration of the interruption of the normal source power. Average power output is 70% of the standby power rating. Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year.

PRIME: Output available with varying load for an unlimited time. Average power output is 70% of the prime power rating. Typical peak demand is 100% of prime rated ekW with 10% overload capability for emergency use for a maximum of 1 hour in 12. Overload operation cannot exceed 25 hours per year

RATINGS: Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard conditions.

DEFINITIONS AND CONDITIONS1 For ambient and altitude capabilities consult your Cat dealer. Air flow restriction

(system) is added to existing restriction from factory.2 Emissions data measurement procedures are consistent with those described

in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77° F, 28.42 in HG and number 2 diesel fuel with 35° API and LHV of 18,390 BTU/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values based on a weighted cycle.

3 UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting characteristics. Generator temperature rise is based on a 40° C ambient per NEMA MG1-32.

LEHE1772-04 (05/20)

www.Cat.com/electricpowerAll rights reserved.

Materials and specifications are subject to change without notice.The International System of Units (SI) is used in this publication.© 2020 Caterpillar. All Rights Reserved. CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, “Caterpillar Corporate Yellow”, the “Power Edge” and

Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission

Dim “A” mm (in) Dim “B” mm (in) Dim “C” mm (in) Dry Weight kg (lb)

3512 (138) 1746 (69) 2322 (92) 4863 (10721)

C

A

2/2

B

Alternator3

Voltages 208V 220V 240V 480V 600V

Motor starting capability @ 30% Voltage Dip 1917 skVA 2129 skVA 2501 skVA 2512 skVA 2512 skVA

Current 2602.2 amps 2460.3 amps 2512 amps 1127.6 amps 902.1 amps

Frame Size LC7224N LC7224L LC7224L LC7224L LC7224L

Excitation AREP AREP AREP AREP AREP

Temperature Rise 130 °C 130 °C 130 °C 105 °C 130 °C

Page 3: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

1

Attachment

EMCP 4.2B GENERATOR SET CONTROLLER

The Cat® EMCP 4.2B offers fully featured power metering, protective relaying and engine and generator control and monitoring. Engine and generator controls, diagnostics, and operating information are accessible via the control panel keypads; diagnostics from the EMCP 4 optional modules can be viewed and reset through the EMCP 4.2B.

• Wide range of system expansion attachments, designed specifically to work with the EMCP 4

• Flexible packaging options for easy

and cost effective installation

World wide product support

• Cat dealers provide extensive pre and post sale support

• Cat dealers have over 1,600 dealer branch stores operating in 200 countries

• A 33 x 132 pixel, 3.8 inch, white backlit graphical

display denotes text alarm/event descriptions,

set points, engine and generator monitoring, and

is visible in all lighting conditions.

• Textual display with support for 26 languages

• Advanced engine monitoring is available on systems with an ADEM™ controller.

• Integration with the CDVR and IVR provides enhanced system performance

• Fully featured power metering, protective relaying, engine and generator parameter viewing, and expanded AC metering are all integrated into this controller.

• Real-time clock allows for date and time stamping of diagnostics and events in the control’s logs as well as service maintenance reminders based on engine operating hours or calendar days. Up to 40 diagnostic events are stored in the non-volatile memory

LEHE1208-01

Features

• Ability to view and reset diagnostics on EMCP

4 optional modules via the control panel

removes the need for a separate service tool

for troubleshooting

• Set points and software stored in non-volatile

memory, preventing loss during a power

outage

• Five levels of security allow for configurable

operator privileges

• Programmable security levels for groups of

setpoints.

• Programmable kW Relays (3)

• Programmable weekly exerciser timer• Dealer configurable resistive maps• Default overview screen• Real (kW) Load histogram• Auto mains failure• Programmable logic functionality• Selectable units

o Temperature: °C or °Fo Pressure: psi, kPa, baro Fuel Consumption: Liter/hr or Gal/hr

(U.S. or U.K.)

Full range of attachments Features

Pi cture shown may not reflect actual configuration

Page 4: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

2

Attachment

Standard Features

• Voltage (L-L, L-N)

• Current (Phase)

• Average Volt, Amp, Frequency

• kW, kVAr, kVA (Average, Phase, %)

• Power Factor (Average, Phase)

• kW-hr, kVAr-hr (total)

• Excitation voltage and current (with

CDVR)

• Desired Voltage, Excitation Command, Operating Mode (with IVR)

• Generator stator and bearing temp (with optional module)

• kW load histogram

Generator Protection

• Generator phase sequence

• Over/Under voltage (27/59)

• Over/Under frequency (81 O/U)

• Reverse Power (kW) (32)

• Reverse Reactive Power (kVAr) (32RV)

• Overcurrent (50/51)

• Thermal Damage Curve

Engine Monitoring

• Coolant temperature

• Oil pressure

• Engine speed (RPM)

• Battery voltage

• Run hours

• Crank attempt and successful start counter

• Enhanced engine monitoring (with electronic engines)

Engine Protection

• Control switch not in auto (alarm)

• High coolant temp (alarm and shutdown)

• Low coolant temp (alarm)

• Low coolant level (alarm)

• High engine oil temp (alarm and shutdown)

• Low, high, and weak battery voltage

• Overspeed

• Overcrank

• Low Oil Pressure

Control

• Run / Auto / Stop control

• Speed and voltage adjust

• Local and remote emergency stop

• Remote start/stop

• Cycle crank

Inputs & Outputs

• Two dedicated digital inputs

• Three analog inputs

• Six programmable digital inputs

• Eight relay out

• Two programmable digital outputs

Communications

• Primary and accessory CAN data links

• RS-485 annunciator data link

• Modbus RTU (RS-485 Half duplex)

Language Support

Environmental

LEHE1208-01

Arabic, Bulgarian, Czech, Chinese, Danish, Dutch, English, Estonian, Finnish, French, German, Greek, Hungarian, Italian, Icelandic, Japanese, Latvian, Lithuanian, Norwegian, Polish, Portuguese, Romanian, Russian, Spanish, Swedish, Turkish

• Control module operating temperature:

-40°C to 70°C

• Display operating temperature: -20°C to 70°C

• Humidity: 100% condensing 30°C to 60°C

• Storage temperature: -40°C to 85°C

• Vibration: Random profile, 24-1000 Hz, 4.3G rms

Standards• UL Recognized• CSA C22.2 No.100,14, 94• Complies with all necessary standards for CE

Certificationo 98/37/EC Machinery Directiveo BS EN 60204-1 Safety of Machinery

89/336/EEC EMC Directiveo BS EN 50081-1 Emissions Standardo BS EN 50082-2 Immunity Standard

73/23/EEC Low Voltage Directiveo EN 50178 LVD Standard

• IEC529, IEC60034-5, IEC61131-3• MIL STND 461

Page 5: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

ATTACHMENTS

ULCERT

UL 2200 LISTING

ELECTRICAL OPTIONS

The table below shows electrical options that meet UL requirements:

MECHANICAL OPTIONS

Mechanical options do not require UL Listing and, therefore, are not affected. The exceptions to this are:

FUEL TANKS

If a fuel tank is ordered with the unit, it must be UL Listed. Two versions are available: 24 hour integral (FCUL2) and 24/48 hour sub-base (FSBT)

ENCLOSURES

Factory installed enclosures meet UL requirements. Weatherproof and sound attenuated versions are available.

Materials and specifications are subject to change without notice. CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow,” the “Power Edge” trade dress as well as corporate

and product identity used herein, are trademarks of Caterpillar and may not be used without permission. www.Cat-ElectricPower.com

©2013 Caterpillar All Rights Reserved

LEHEXXXXXX (01/13) Printed in U.S.A.

INCLUDES THE FOLLOWING:

ALTERNATOR

Alternator insulation system is UL Recognized (UL 1446). PMG and AREP alternators are available. Automatic voltage regulators are UL Recognized.

WIRE HARNESS

AC, DC, and power harnesses are made with UL Listed wire and UL Listed terminals.

CONTROL PANEL

Control panels are comprised of UL Listed and UL Recognized components. EMCP is UL Recognized.

CIRCUIT BREAKER

Output circuit breaker is 100% rated and UL Listed.

TESTING

All UL Listed sets are designed and rigorously tested in accordance with UL Standard for Safety, UL 2200.

LABELING

Labeling meets UL requirements.

EBH Battery Heater

EOS Lube Oil Sump Heater

WCA1 Low Coolant Level Shutdown

WSS1 Low Coolant Temperature Alarm

AH1H Anti-Condensation Heater

WHH Coolant Heater

GOVE5 Electronic Governor (Fully Adjustable)

FSS1 Critical Low Fuel Level Shutdown

FSS2 Low Fuel Level Alarm

FSS5 Critical High Fuel Alarm

PBC5UL UL Listed Battery Charger

PBC10NU NFPA Battery Charger, UL Listed

UL Listing is available on all diesel fuelled generator sets up to 175 kW at 60 Hz, 600 vac maximum.

LEHE0410-00 (01/13)

Page 6: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

Enclosures

LEHE0465-09 1/7

C13/C15/C18 SOUND ATTENUATED ENCLOSURESUS Sourced Diesel Generator Set 350 - 750 ekW 60 Hz

FeaturesRobust/Highly Corrosion Resistant Construction• Factory installed on skid base• Environmentally friendly, polyester powder baked paint• 14 gauge steel• Interior zinc plated fasteners• Exterior stainless steel fasteners• Internally mounted exhaust silencing system• Designed and tested to comply with UL 2200 Listed generator set

package• Compression door latches providing solid door seal

Excellent Access• Large cable entry area for installation ease• Accommodates side mounted single or multiple breakers• Three doors on both sides• Vertically hinged allow 180° opening rotation and retention with

door stays• Lube oil and coolant drains piped to the exterior of the enclosure

base• Radiator fill cover

Security and Safety• Lockable access doors which give full access to control panel and

breaker• Cooling fan and battery charging alternator fully guarded• Fuel fill, oil fill and battery can only be reached via lockable access• Externally mounted emergency stop button• Designed for spreader bar lifting to ensure safety• Stub-up area is rodent proof

TransportabilityThese enclosures are of extremely rugged construction to withstand outdoor exposure and rough handling common on many construction sites.

Options• Enclosure constructed with 14 gauge steel• Enclosure constructed with 12 gauge aluminum (5052 grade)• Caterpillar yellow or white paint• Control panel viewing window• UL Listed integral fuel tank with 670, 400, and 300 gallon

capacities• UL Listed sub base fuel tank with 660, 1000, 1900, and 2200

gallon capacities.• Seismic certification per applicable building codes: IBC 2000, IBC

2003, IBC 2006, IBC 2009, IBC 2012, IBC 2015 CBC 2007, CBC 2010• IBC Certification for 150 mph wind loading• AC/DC lighting package• 5 kW Canopy space heater to facilitate compliance with NFPA 110• Motorized louvers and gravity discharge damper• 125A Load Center• GFCI outlets*Not available with aluminum enclosures.

Picture shown may not reflect actual configuration

Page 7: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

Enclosures

LEHE0465-09 2/7

Level 1 Sound Attenuated Enclosure (Steel) Sound Levels

Sound Attenuated Enclosure (Aluminum) Sound Levels

Model Standby eKWCooling Air Flow Rate Ambient Capability* Sound Pressure Levels

(dBA) at 7m (23 ft)

m3/s cfm ˚C ˚F 100% Load

C13350 8.5 18010 57 135 74

400 8.5 18010 56 133 75

C15

350 10.4 22072 59 138 73

400 10.4 22072 51 124 73

450 10.4 22072 46 115 74

500 12.5 26415 48 118 75

C18

550 8.1 17234 45 113 75

600 8.1 17234 43 109 75

650 12.7 26909 51 123 75

700 12.7 26909 48 118 75

750 12.7 26909 48 118 75

Model Standby eKWCooling Air Flow Rate Ambient Capability* Sound Pressure Levels

(dBA) at 7m (23 ft)

m3/s cfm ˚C ˚F 100% Load

C13350 8.5 - 57 135 75

400 8.5 - 56 133 75

C15

350 10.4 22072 59 138 72

400 10.4 22072 51 124 73

450 10.4 22072 46 115 74

500 12.5 26415 48 118 75

C18

550 8.1 17234 45 113 76

600 8.1 17234 43 109 76

650 12.7 26909 51 123 76

700 12.7 26909 48 118 76

750 12.7 26909 48 118 76

magriesti
Highlight
magriesti
Highlight
Page 8: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

Enclosures

LEHE0465-09 3/7

Level 2 Sound Attenuated Enclosure (Steel) Sound Levels

Component Weights to Calculate Package Weight

Sound Attenuated Enclosure on Skid Base

Model Standby eKWCooling Air Flow Rate Ambient Capability* Sound Pressure Levels

(dBA) at 7m (23 ft)

m3/s cfm ˚C ˚F 100% Load

C13350 7.2 15256 50 122 70

400 7.2 15256 50 122 70

C15

350 10.4 22071 50 122 72

400 10.4 22071 50 122 72

450 10.4 22071 50 122 72

500 12.5 26415 50 122 72

Model Standby eKW

Narrow Skid Base Wide Skid Base Sound Attenuated Enclosure (Steel)

Sound Attenuated Enclosure (Aluminum)

kg lb kg lb kg lb kg lb

C13350

253 578 579 1276 1245 2745 765 1687400

C15

350

273 602 465 1025 1245 2745 765 1687400

450

500

C18

550301 664 466 1027 1301 2868 817 1801

600

650

286 630 637 1404 1393 3071 887 1955700

750

Model Standby eKWLength “L” Width “W” Height “H”

mm in mm in mm in

C13350

4948 194.8 2014 79.3 2320 91.3400

C15

350

4948 194.8 2014 79.3 2320 91.3400

450

500

C18

5505183 204.0 2014 79.3 2262 89.0

600

650

5230 205.9 2315 91.1 2253 88.7700

750

*Cooling system performance at sea level. Consult your Cat® dealer for site specific ambient and altitude capabilities.Note: Sound level measurements are subject to instrumentation, installation and manufacturing variability, as well as ambient site conditions.

magriesti
Highlight
magriesti
Highlight
magriesti
Highlight
magriesti
Highlight
magriesti
Highlight
Page 9: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

Enclosures

LEHE0465-09 4/7

Sound Attenuated Enclosure on a UL Listed Integral Fuel Tank Base

Model Standby eKWLength “L” Width “W” Height “H”

mm in mm in mm in

C13350

5461 215.0 2014 79.3 2743 108.0400

C15

350

4948 194.8 2014 79.3 2619 103.0400

450

500

C18

5505187 204.2 2014 79.3 2561 101.0

600

650

6977 274.7 2315 91.1 2675 105.3700

750

magriesti
Highlight
magriesti
Highlight
magriesti
Highlight
magriesti
Highlight
Page 10: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

ATTACHMENTS

Picture shown may not represent actual package

C13 / C15 / C18 Integral and Sub-Base Fuel Tanks

US Sourced Diesel Generator Set

350 - 750 ekW 60 Hz

Features

• UL Listed for United States (UL 142) and Canada (CAN/ULC S601)• Facilitates compliance with NFPA 30 code, NFPA 37 and 110 standards and CSA C282 code• Dual wall• Lockable fuel fill cap, 4" (101.6 mm) NPT• Low fuel level warning standard, customer configurable warning or shutdown• Primary tank leak detection switch in containment basin• Tank design provides capacity for thermal expansion of fuel• Fuel supply dip tube is positioned so as not to pick up fuel sediment• Fuel return and supply dip tube is separated by an internal baffle to prevent immediate re-supply of

heated return fuel• Pressure washed with an iron phosphate solution• Interior tank surfaces coated with a solvent-based thin-film rust preventative• Heavy gauge steel gussets with internal lifting rings• Primary and secondary tanks are leak tested at 20.7 kPa (3 psi) minimum• Compatible with open packages and enclosures• Gloss black polyester alkyd enamel exterior paint• Welded steel containment basin (minimum of 110% of primary tank capacity)• Direct reading fuel gauge with variable electrical output• Emergency vents on primary and secondary tanks are sized in accordance with NFPA 30

Sub Base • The sub-base fuel tank mounts below the generator set wide base

Integral • Integral diesel fuel tank is incorporated into the generator set base frame• Robust base design includes linear vibration isolators between tank base and engine generator

Options • Audio/visual fuel level alarm panel• 5 gal (18.9 L) spill containment• 5 gal (18.9 L) spill containment with fuel fill drop tube with in 6" (152 mm) from bottom of tank• 5 gal (18.9 L) spill containment with overfill prevention valve and fuel fill drop tube with in 6" (152 mm)

from bottom of tank• ULC Listed 7.5 gal (28.4 L) spill containment with vent extensions, vent whistle, and drop tube facilitating

compliance with CSA 8139-09• ULC Listed 7.5 gal (28.4 L) spill containment with overfill prevention valve, vent extensions, vent whistle

and drop tube facilitating compliance with CSA 8139-09LEHE0467-08 Page 1 of 5

Page 11: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

ATTACHMENTS

Integral & Sub-Base Fuel Tank Base Useable Capacities with

Fuel Tank Dimensions & Weights

Integral - Width (W) 2014 mm (79.3 in)

Sub-base - Width (W) 2056 mm (81.0 in)

Integral* - Width(W) 2315 mm (91.2 in)

Sub-base*-Width(W) 2357 mm (92.7in)

Open Set & Weather Protective Enclosure

C13 Tank

Design

Feature

Code

Total

Capacity

Useable

Capacity

Tank Only

Overall Package Height

with Tank

Dry Weight Height 'H' Length 'L' Open Enclosure

Liter Gallon Liter Gallon kg lb mm in mm in mm in mm in

Integral FTDW013 2646 699 2540 671 1569 3450 762 30.0 5461 215 2552 100.5 2743 108.0

Sub-Base FTDW005 3941 1041 3876 1024 1659 3657 635 25.0 5550 218.5 2763 108.8 2955 116.3

Sub-Base FTDW006 6980 1844 6818 1801 2228 4483 889 35.0 6184 243.5 3017 118.8 3209 126.3

Sub-Base FTDW007 8339 2203 8244 2178 2150 5052 889 35.0 7074 278.5 2291 117.8 3789 149.2

Sub-Base FTDW011 2476 654 2435 643 1468 3236 635 25.0 3810 150.0 2763 108.8 2955 116.3

C15 Tank

Design

Feature

Code

Total

Capacity

Useable

Capacity

Tank Only

Overall Package Height

with Tank

Dry Weight Height 'H' Length 'L' Open Enclosure

Liter Gallon Liter Gallon kg lb mm in mm in mm in mm in

Integral FTDW002 1283 339 1262 333 1015 2237 635 25.0 3814 150.1 2426 95.5 2619 103.0

Sub-Base FTDW005 3941 1041 3876 1024 1659 3657 635 25.0 5550 218.5 2763 108.8 2955 116.3

Sub-Base FTDW006 6980 1844 6818 1801 2228 4912 889 35.0 6184 243.5 3017 118.8 3209 126.3

Sub-Base FTDW008 2476 654 2435 643 1468 3236 635 25.0 3810 150.0 2763 108.8 2955 116.3

C18 Tank

Design

Feature

Code

Total

Capacity

Useable

Capacity

Tank Only

Overall Package Height

with Tank

Dry Weight Height 'H' Length 'L' Open Enclosure

Liter Gallon Liter Gallon kg lb mm in mm in mm in mm in

Integral FTDW004 1446 382 1422 376 1015 2237 635 25.0 3814 150.1 2426 95.5 2560 100.8

Integral* FTDW030 2498 660 2377 628 1681 3703 762 30.0 4995 196.6 2670 105.1 2675 105.3

Integral* FTDW031 5175 1367 4997 1320 2046 4510 762 30.0 6737 265.3 2670 105.1 2675 105.3

Sub-Base FTDW005 3941 1041 3876 1024 1659 3657 635 25.0 5550 218.5 2763 108.8 2955 116.3

Sub-Base FTDW007 8339 2203 8244 2178 2150 4134 889 35.0 7074 278.5 2291 117.8 3159 124.4

Sub-Base FTDW008 2476 654 2435 643 1468 3236 635 25.0 3810 150.0 2739 107.9 2905 114.4

Sub-Base* FTDW032 10228 2702 10112 2640 2638 5816 889 35.0 7368 290 3127 123.1 3132 123.3

LEHE0467-08 Page 2 of 5

Page 12: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

ATTACHMENTS

Integral & Sub-Base Fuel Tank Base Useable Capacities with

Fuel Tank Dimensions & Weights

Integral - Width(W) 2014 mm (79.3 in)

Sub-base - Width(W) 2056 mm (81 in)

Integral* - Width(W) 2315 mm (91.2 in)

Sub-base*-Width(W) 2357 mm (92.7in)

Sound Attenuated Enclosure

C13 Tank

Design

Feature

Code

Total

Capacity

Useable

Capacity

Tank Only

Overall Package Height

with Tank

Dry Weight Height 'H' Length 'L' Open Enclosure

Liter Gallon Liter Gallon kg lb mm in mm in mm in mm in

Integral FTDW013 2646 699 2540 671 1569 3450 762 30.0 5461 215.0 NA NA 2743 108.0

Sub-Base FTDW005 3941 1041 3876 1024 1659 3657 635 25.0 5550 218.5 NA NA 2955 116.3

Sub-Base FTDW006 6980 1844 6818 1801 2033 4483 889 35.0 6184 243.5 NA NA 3209 126.3

Sub-Base FTDW007 8339 2203 8244 2178 2292 5052 889 35.0 7074 278.5 NA NA 3209 126.3

Sub-Base FTDW011 2476 654 2435 643 1468 3236 635 25.0 3810 150.0 NA NA 2955 116.3

C15 Tank

Design

Feature

Code

Total

Capacity

Useable

Capacity

Tank Only

Overall Package Height

with Tank

Dry Weight Height 'H' Length 'L' Open Enclosure

Liter Gallon Liter Gallon kg lb mm in mm in mm in mm in

Integral FTDW001 1283 339 1262 333 1015 2237 639 25.0 4746 186.9 NA NA 2619 103.0

Sub-Base FTDW005 3941 1041 3876 1024 1659 3657 635 25.0 5550 218.5 NA NA 2955 116.3

Sub-Base FTDW006 6980 1844 6818 1801 2228 4912 889 35.0 6184 243.5 NA NA 3209 126.3

Sub-Base FTDW011 2476 654 2435 643 1468 3236 635 25.0 3810 150.0 NA NA 2955 116.3

C18 Tank

Design

Feature

Code

Total

Capacity

Useable

Capacity

Tank Only

Overall Package Height

with Tank

Dry Weight Height 'H' Length 'L' Open Enclosure

Liter Gallon Liter Gallon kg lb mm in mm in mm in mm in

Integral FTDW003 1446 382 1422 376 1015 2237 635 25.0 3814 150.1 NA NA 2560 100.8

Integral* FTDW030 2498 660 2381 629 1681 3703 762 30.0 4995 196.6 2670 105.1

2675 105.3

Integral* FTDW031 5175 1367 4997 1320 2046 4510 762 30.0 6737 265.3 NA NA 2675 105.3

Sub-Base FTDW005 3941 1041 3876 1024 1659 3657 635 25.0 5550 218.5 NA NA 2905 114.3

Sub-Base FTDW007 8339 2203 8244 2178 2150 4134 889 35.0 7074 278.5 NA NA 3209 126.3

Sub-Base FTDW011 2476 654 2435 643 1468 3236 635 25.0 3810 150.0 NA NA 2905 114.3

Sub-Base* FTDW032 10228 2702 9994 2640 2638 5816 889 35.0 7368 290 NA NA 3132 123.3

LEHE0467-08 Page 3 of 5

magriesti
Highlight
magriesti
Highlight
magriesti
Highlight
Page 13: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

ATTACHMENTS

The heights listed above do not include lumber used during manufacturing and shipping.

Estimated Run Times (Hours) at 100% Load

C13 Tank

Design Feature Code

Standby Ratings (ekW) Prime Ratings (ekW)

400 350 – – 350 320 – –

Integral FTDW013 24 27 - - 25 29 - -

Sub-Base FTDW005 36 41 - - 38 43 - -

Sub-Base FTDW006 65 72 - - 72 77 - -

Sub-Base FTDW007 77 87 - - 81 93 - -

Sub-Base FTDW011 23 25 - - 24 27 - -

C15 Tank

Design Feature Code

Standby Ratings (ekW) Prime Ratings (ekW)

500 450 400 350 455 410 365 320

Integral FTDW001 / FTDW002 9 9 11 11 10 10 11 12

Sub-Base FTDW005 28 29 32 36 30 31 35 38

Sub-Base FTDW006 50 52 57 63 54 56 62 67

Sub-Base FTDW008 / FTDW011 17 18 20 22 19 20 22 24

C18 Tank

Design Feature Code

Standby Ratings (ekW) Prime Ratings (ekW)

750 700 650 600 550 680 635 600 545 500

Integral FTDW003 / FTDW004 - - - 8 9 - - - 9 10

Integral* FTDW030 11 12 13 - - 12 13 14 - -

Integral* FTDW031 24 25 27 - - 26 27 29 33 36

Sub-Base FTDW005 - - - 24 25 - - - 25 27

Sub-Base FTDW007 - - - 51 54 - - - 54 59

Sub-Base FTDW008 / FTDW011 - - - 15 16 - - - 16 17

Sub-Base* FTDW032 49 51 54 - - 53 55 58 - -

LEHE0467-08 Page 4 of 5

magriesti
Highlight
magriesti
Highlight
Page 14: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

ATTACHMENTS

Tanks with full electrical stub-up area include removable end channel. Tanks with RH stub-up include stub- up area directly below the circuit breaker or power terminal strips. Dimensions include weather-protective enclosure exhaust system.

Dual wall sub-base tanks are UL Listed and constructed in accordance with UL Standard for Safety UL 142, Steel Aboveground Tanks for Flammable and Combustible Liquids and Canada CAN/ULC S601, Standard for Shop Fabricated Steel Aboveground Horizontal Tanks for Flammable and Combustible Liquids.

Fuel tanks and applicable options facilitate compliance with the following United States NFPA Code and Standards:

NFPA 30: Flammable and Combustible Liquids Code

NFPA 37: Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines

NFPA 110: Standard for Emergency and Standby Power Systems

Fuel tanks and applicable options facilitate compliance with the following Canadian Standard and Code:

CSA C282 - Emergency Electrical Power Supply for Buildings

CSA B139-09 - Installation Code for Oil-Burning Equipment

The following sub-base fuel tanks meet Chicago code for containment and labelling:

FTDW005

FTDW008

FTDW011

LEHE0467-08 (03/20)

www.cat.com/electricpower ©2020 Caterpillar

All rights reserved.

Page 15: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

LEHE0942-01 Page 1 of 2

Construction robuste et durable

C9 ACERT™, C13 ACERT, C15 ACERT, C18 ACERT Circuit Breakers

Circuit Breakers

Manually Operated Circuit Breakers

Current(A) Frame

Number of Poles

Interrupting Ratings (kA rms) TripUnits

(Lugs) Cable Size Range / Phase Auxiliary Options240V 480V 600V

250 T4N 3 65 25 18

Electronic LS/I

(S or I)or

LSI

(1) 6 AWG – 350 kcmil 1 Form C + 1 Bell Alarm

250VAC/VDC

Shunt Trip 24VDC

400 T5N 3 65 25 18 (2) 3/0 – 250 kcmil

600 T6N 3 65 35 20 (3) 2/0 – 400 kcmil

800 T6N 3 65 35 20 (3) 2/0 – 400 kcmil

1 Form C + 1 Bell Alarm 400VAC / 250VDC

Shunt Trip 24VDC1200 T7S 3 65 50 25 (4) 4/0 – 500 kcmil

1600 R 3 65 35 18

Electronic LSI

BUS BARForm C (1NO + 1NC)

Shunt Trip 24VDC2000 R 3 65 35 18 BUS BAR

2500 R 3 65 35 18 BUS BAR

Electrically Operated Circuit Breakers

Current(A) Frame

Number of Poles

Interrupting Ratings (kA rms) TripUnits

(Lugs) Cable Size Range / Phase Auxiliary Options240V 480V 600V

800 T7M-S 3 65 50 25Electronic

LSI

(4) 4/0 – 500kcmil

2 Form C + 1 BellAlarm 24VDC

1200 T7M-S 3 65 50 25 (4) 4/0 – 500 kcmil

2 Form C + 1 BellAlarm 24VDC

magriesti
Highlight
magriesti
Highlight
magriesti
Highlight
Page 16: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

Circuit Breakers

LEHE0942-01 (04/16)

Materials and specifications are subject to change without notice.CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”,

the “Power Edge” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.

www.Cat-ElectricPower.com©2016 Caterpillar

All rights reserved.

Single Breaker Options (250 – 2500A)

Model Current (A) Operation

C9 ACERT™ 250 Manually Operated

C9 ACERT 400 Manually Operated

C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 600 Manually Operated

C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 800 Manually Operated or Electrically Operated

C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 1200 Manually Operated or Electrically Operated

C13 ACERT, C15 ACERT, C18 ACERT 1600 Manually Operated

C15 ACERT, C18 ACERT 2000 Manually Operated

C18 ACERT 2500 Manually Operated

Multiple Breaker Options

Model

Main Breaker Box Auxiliary Box

1st Breaker (Amps)

2nd Breaker (Amps)

Breaker(Amps)

ManuallyOperated

ManuallyOperated Manually Operated

C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 250

250, 400, 600, 800, or 1200

3rd Breaker:250 or 400

(Not available if1st & 2nd Breaker = 1200A)

C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 400

C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 600

C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 800

C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 1200

C13 ACERT, C15 ACERT, C18 ACERT 1600

Not Available2nd Breaker:250 or 400

C15 ACERT, C18 ACERT 2000

C18 ACERT 2500

magriesti
Highlight
magriesti
Highlight
magriesti
Highlight
Page 17: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

LEHE0141-05 Page 1 of 2

Battery Charger

Features ● Electronicallycurrentlimitedat105%ofrated

output● Alarmsystem● Digitaldisplay● Lightningandvoltagetransientprotection● Protectionofconnectedequipmentagainst

loaddumpprotection● Constantvoltage,currentlimited,4-rate

automaticequalization● IP20housing● Temperaturecompensation● Onboardtemperaturesensorwithremoteport● AutoAClinecompensation● Outputregulatedbysensedbatteryvoltage

Standards● C-ULlistedtoUL1236● NFPA70,NFPA110● CSA22.2No107certified● CEDOCtoEN60335● IBCSeismicCertification

UL 10 AmpBattery ChargerThisbatterychargeroffersaccurate,automaticchargingoflead-acidandnickelcadmiumbatteries.Theoutputvoltageautomaticallyadjuststochanginginput,load,batteryandambientconditions.Thispreventsbatteryover-chargingandconsequentlossofbatteryelectrolyte.

StandardfeaturesincludeAClinecompensation,precisionvoltageregulation,currentlimiting,automatic2-ratecharging,voltmeterandammeter,temperaturecompensationandULListing.

Theuserinterfaceiseasytounderstandwithdigitalmetering,NFPA110alarmsandabatteryfaultalarm.

ImageShownmaynotReflectActualPackage.

Page 18: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

Battery Charger

Informationcontainedinthispublicationmaybeconsideredconfidential.Discretionisrecommendedwhendistributing.Materialsandspecificationsaresubjecttochangewithoutnotice.

CAT,CATERPILLAR,LET’SDOTHEWORK,theirrespectivelogos,“CaterpillarYellow,”the“PowerEdge”andCat“ModernHex”tradedressaswellascorporateandproductidentityusedherein,aretrademarks

ofCaterpillarandmaynotbeusedwithoutpermission.

www.cat,com/electricpower©2019CaterpillarAllrightsreserved.

Specifications Inputsupply 110 – 120 V

208 – 240 V

ACandDCfuses 2inputand2output)

Outputvoltage 24V

Outputamps 10

Frequency 50/60Hz

Operatingtemperature -20°C(-4°F)to+60°C(140°F)

HousingconstructedofrustproofanodizedAluminum

Dimensions

Width Depth Height Weight

195mm(7.66in) 165mm(6.5in) 318mm(12.5in) 10.4kg(23lb)

NFPA110alarmpackageasfollows:

● ACon Greenled(indication)● ACfail RedledandformCcontact(2A)● Floatmode LED● Fastcharge LED● Tempcompactive LED● Lowbatteryvolts RedledandFormCconta● HighBatteryVolts RedledandFormCconta● Chargerfail RedledandFormCconta● Batteryfault RedledandFormCconta● Batterydisconnected● Batterypolarityreversed● Mismatchedchargerbatteryvoltage● Openorhighresistancechargertobatteryconnection● Openbatterycellorexcessiveinternalresistance

Feature Codes:BTC1024BTC1028BTC1035BTC1025BTC1032

LEHE0141-05 (02/19)

Page 19: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

ATTAC

LEHE0

FEATURE

FACTORY

Comple

Isolatedextreme

Optimizfor max

Remoteoptimize100° F (

Automavia a depanel.

Supplie

Compat

All parts

Incoloy

Ima

CHMENT

0297-01

ES

INSTALLED

ete with silicon

d tank heater e limits to gua

zed location oimum coolant

e pilot thermosed power cyc(37.8°C)

atically disconedicated heate

d with UL rec

tible with Cat®

s are servicea

heater eleme

age Shown may n

TS

ne hoses

vibration andarantee durab

f the heater ot flow

stat located ole efficiency i

nected whener relay locate

cognized com® ELC and all

able and field

ent for longer

not Reflect Actua

shock testedbility

on the genset

on the engine s factory set t

engine is runed in the cont

ponents

l chemicals

replaceable

service life

al Package

d to

base

forto

nningtrol

Ro1

Ar

S

C1He

Factostartimetaremosilicocommheatemaxi

Remote pilot optimized pow100° F (37.8°

Automaticallyrunnune cont

Rating

Frequency

Phase

Amps

Feature Code

SPECIFICAT

15 and eater

ory installed jing capability

al heater with ote engine moone hoses andmon connectier and thermomum coolant

thermostat lower cycle effic°C

y disconnectetrol panel

Unit Spe

208

2250

50/60 Hz

1

10.82

IONS

C18 Ja

acket water h. The system an integral hi

ounted controd heater contion point in thostat locationt flow and hea

ocated on the ciency is facto

ed when the e

ecifications

Design Vo

220

2520

z 50/60 H

1

11.45

JWH005JWH005JWHD03

acket W

heater for incrincludes a ta

igh limit thermol thermostat, trol relay wirehe control pan is optimized ating power e

engine for ory set to

engine is

ltage

240

3000

Hz 50/60 H

1

12.5

585932

Water

reased cold-ank-stylemostat and a

durabled to a

nel. The for

efficiency.

0

Hz

C15 and C18 Jacket Water Heater . Factory installed jacket water heater for increased

cold-starting capability. The system includes a tank-

style metal heater with an integral high limit

thermostat and a remote engine mounted control

thermostat, durable silicone hoses and heater control

relay wired to a common connection point in the

control panel. The heater and thermostat location is

optimized for maximum coolant flow and heating

power efficiency.

Page 20: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

ATTACHMENTS

LEHE0297-01 2

WIRING DIAGRAMS

Wiring diagram reference for 240V Line to Neutral power connection

Wiring diagram reference for 240V or 208V Line to Line and 120V Line to Neutral power connection (Note: Including Optional Space Heater and Battery Charger)

Page 21: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

ATTACHMENTS

LEHE0297-01 3

HEATER OPERATION

The heater uses compliant components to UL and CSA, and is both CSA and UL approved.

When the generator set is not running, the heater is automatically connected to the AC supply through a power relay mounted in the control panel. Upon receiving a start signal, the AC supply is automatically disconnected by the power relay and automatically reconnected when the start signal is removed and the engine has stopped.

Pilot thermostat located on the engine precisely monitors and controls the engine coolant temperature and is wired to energize and de-energize heater power cycles.

A high-limit thermostat is built into the heater to regulate the output temperature to within safe limits.

HEATER DETAIL

Materials and specifications are subject to change without notice. CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow,” the “Power Edge” trade dress as well as corporate

and product identity used herein, are trademarks of Caterpillar and may not be used without permission.

www.Cat-ElectricPower.com

LEHE0297-01 (05/13) ©2013 Caterpillar All Rights Reserved.

Printed in U.S.A.

Page 22: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

G E N E R A T O R S

www.cat-ElectricPower.comMarket: N. America

Information contained in this publication may be considered confidential. © 2005 Caterpillar LEHE4017 (01-05) Discretion is recommended when distributing. All Rights Reserved.

Materials and specifications are subject to change without notice. Printed in U.S.A.

GENERATOR ANTI-CONDENSATIONHEATER AH1H

Appropriate when the generator set is to be sited ina low ambient and/or high humidity environment,the heater maintains the AC generator at a suitabletemperature to prevent winding corrosion dueto condensation.

The heater itself is powered by a 110/120 volt(VAC 120) or 208/240 volt (VAC 240) AC auxiliarysupply protected by a fuse inside the main controlpanel. When the generator set is not running theheater is automatically connected to the AC supplythrough a power relay mounted in the controlpanel. Upon receiving a start signal the AC supplyis automatically disconnected by the power relayand automatically reconnected when the startsignal is removed and the engine has stopped.

Page 23: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •
Page 24: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •
Page 25: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •
Page 26: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •
Page 27: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •
Page 28: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •
Page 29: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •
Page 30: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •
Page 31: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •
Page 32: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •
Page 33: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •
Page 34: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •
Page 35: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •
Page 36: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •
Page 37: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

SELF5709

Effective with sales to the first user on or after August 1, 2016

CATERPILLAR LIMITED WARRANTYIndustrial, Petroleum, Locomotive, and Agriculture Engine Products and Electric Power

Generation ProductsWorldwide

Caterpillar Inc. or any of its subsidiaries (“Caterpillar”) warrants new and

remanufactured engines and new and rebuild electric power generation

products sold by it (including any products of other manufacturers

packaged and sold by Caterpillar), to be free from defects in material

and workmanship.

This warranty does not apply engines sold for use in on-highway vehicle or

marine applications; engines in machines manufactured by or for Caterpillar;

C175, 3500 and 3600 series engines used in locomotive applications; 3000

Family engines, C0.5 through C4.4 and ACERT™ (C6.6, C7, C7.1, C9,

C9.3, C11, C13, C15, C18, C27, and C32) engines used in industrial, mobile

agriculture and locomotive applications; or Cat®

batteries; or Electric Power

Generation Products manufactured or assembled in India. These products

are covered by other Caterpillar warranties.

This warranty is subject to the following:

Warranty Period

• For industrial engines, engines in a petroleum applications

or Petroleum Power Systems (excluding petroleum fire

pump application), or engines in a Locomotive application, or

Uninterruptible Power Supply (UPS) systems, the warranty period

is 12 months after date of delivery to the first user.

• For engines used in petroleum fire pump and mobile agriculture

applications the warranty period is 24 months after date of delivery

to the first user.

• For controls only (EPIC), configurable and custom switchgear

products, and automatic transfer switch products, the warranty

period is 24 months after date of delivery to the first user.

• For new CG132, CG170 and CG260 series power generation

products the warranty period is 24 months/16,000 hours, whichever

comes first, after date of delivery to first user.

• For electric power generation products other than CG132, CG170

and CG260 series in prime or continuous applications the warranty

period is 12 months. For standby applications the warranty period

is 24 months/1000 hours. For emergency standby applications the

warranty period is 24 months/400 hours. All terms begin after date

of delivery to the first user.

• For Caterpillar rebuild electric power generation products the

warranty period is 12 months, but not to exceed 24 months

from shipment of rebuilt electric power generation product from

Caterpillar.

• For all other applications the warranty period is 12 months after

date of delivery to the first user.

Caterpillar Responsibilities

If a defect in material or workmanship is found during the warranty

period, Caterpillar will, during normal working hours and at a place of

business of a Cat dealer or other source approved by Caterpillar:

• Provide (at Caterpillar’s choice) new, Remanufactured, or

Caterpillar approved repaired parts or assembled components

needed to correct the defect.

Note: New, remanufactured, or Caterpillar approved repaired parts or

assembled components provided under the terms of this warranty

are warranted for the remainder of the warranty period applicable

to the product in which installed as if such parts were original

components of that product. Items replaced under this warranty

become the property of Caterpillar.

• Replace lubricating oil, filters, coolant, and other service items

made unusable by the defect.

• Provide reasonable and customary labor needed to correct

the defect, including labor to disconnect the product from and

reconnect the product to its attached equipment, mounting, and

support systems, if required.

For new 3114, 3116, and 3126 engines and, new and Caterpillar rebuild

electric power generation products (which includes the following: any

new products of other manufacturers packaged and sold by Caterpillar)

• Provide travel labor, up to four hours round trip, if in the opinion

of Caterpillar, the product cannot reasonably be transported to

a place of business of a Cat dealer or other source approved by

Caterpillar (travel labor in excess of four hours round trip, and any

meals, mileage, lodging, etc. is the user’s responsibility).

For all other products:

• Provide reasonable travel expenses for authorized mechanics,

including meals, mileage, and lodging, when Caterpillar chooses

to make the repair on-site.

User Responsibilities

The user is responsible for:

• Providing proof of the delivery date to the first user.

• Labor costs, except as stated under “Caterpillar Responsibilities,”

including costs beyond those required to disconnect the product

from and reconnect the product to its attached equipment,

mounting, and support systems.

• Travel or transporting costs, except as stated under “Caterpillar

Responsibilities.”

• Premium or overtime labor costs.

• Parts shipping charges in excess of those that are usual and

customary.

• Local taxes, if applicable.

• Costs to investigate complaints, unless the problem is caused by a

defect in Caterpillar material or workmanship.

• Giving timely notice of a warrantable failure and promptly making

the product available for repair.

• Performance of the required maintenance (including use of proper

fuel, oil, lubricants, and coolant) and items replaced due to normal

wear and tear.

• Allowing Caterpillar access to all electronically stored data.

Limitations

Caterpillar is not responsible for:

• Failures resulting from any use or installation that Caterpillar

judges improper.

• Failures resulting from attachments, accessory items, and parts

not sold or approved by Caterpillar.

• Failures resulting from abuse, neglect, and/or improper repair.

• Failures resulting from user’s delay in making the product available

after being notified of a potential product problem.

• Failures resulting from unauthorized repairs or adjustments, and

unauthorized fuel setting changes.

• Damage to parts, fixtures, housings, attachments, and accessory

items that are not part of the engine, Cat Selective Catalytic

Reduction System or electric power generation product (including

any products of other manufacturers packaged and sold by

Caterpillar).

• Repair of components sold by Caterpillar that is warranted directly

to the user by their respective manufacturer. Depending on type of

application, certain exclusions may apply. Consult your Cat dealer

for more information.

(Continued on reverse side…)

magriesti
Highlight
Page 38: DIESEL GENERATOR SETS · 2020. 10. 26. · • Generator stator and bearing temp (with optional module) • kW load histogram . Generator Protection • Generator phase sequence •

SELF5709

This warranty covers every major component of the products. Claims under this warranty should be submitted to a

place of business of a Cat dealer or other source approved by Caterpillar. For further information concerning either

the location to submit claims or Caterpillar as the issuer of this warranty, write Caterpillar Inc., 100 N. E. Adams St.,

Peoria, IL USA 61629.

Caterpillar’s obligations under this Limited Warranty are subject to, and shall not apply in contravention of, the laws,

rules, regulations, directives, ordinances, orders, or statutes of the United States, or of any other applicable jurisdiction,

without recourse or liability with respect to Caterpillar.

A) For products operating outside of Australia, Fiji, Nauru, New Caledonia, New Zealand, Papua New Guinea, the Solomon Islands and Tahiti, the following is applicable:

NEITHER THE FOREGOING EXPRESS WARRANTY NOR ANY OTHER WARRANTY BY CATERPILLAR,

EXPRESS OR IMPLIED, IS APPLICABLE TO ANY ITEM CATERPILLAR SELLS THAT IS WARRANTED DIRECTLY

TO THE USER BY ITS MANUFACTURER.

THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED,

INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE,

EXCEPT CATERPILLAR EMISSION-RELATED COMPONENTS WARRANTIES FOR NEW ENGINES, WHERE

APPLICABLE. REMEDIES UNDER THIS WARRANTY ARE LIMITED TO THE PROVISION OF MATERIAL AND

SERVICES, AS SPECIFIED HEREIN.

CATERPILLAR IS NOT RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES.

CATERPILLAR EXCLUDES ALL LIABILITY FOR OR ARISING FROM ANY NEGLIGENCE ON ITS PART

OR ON THE PART OF ANY OF ITS EMPLOYEES, AGENTS OR REPRESENTATIVES IN RESPECT OF THE

MANUFACTURE OR SUPPLY OF GOODS OR THE PROVISION OF SERVICES RELATING TO THE GOODS.

IF OTHERWISE APPLICABLE, THE VIENNA CONVENTION ON CONTRACTS FOR THE INTERNATIONAL SALE

OF GOODS IS EXCLUDED IN ITS ENTIRETY.

For personal or family use engines or electric power generation products, operating in the USA, its territories and

possessions, some states do not allow limitations on how long an implied warranty may last nor allow the exclusion

or limitation of incidental or consequential damages. Therefore, the previously expressed exclusion may not apply to

you. This warranty gives you specific legal rights and you may also have other rights, which vary by jurisdiction. To

find the location of the nearest Cat dealer or other authorized repair facility, call (800) 447-4986. If you have questions

concerning this warranty or its applications, call or write:

In USA and Canada: Caterpillar Inc., Engine Division, P. O. Box 610, Mossville, IL 61552-0610, Attention: Customer

Service Manager, Telephone (800) 447-4986. Outside the USA and Canada: Contact your Cat dealer.

B) For products operating in Australia, Fiji, Nauru, New Caledonia, New Zealand, Papua New Guinea, the Solomon Islands and Tahiti, the following is applicable:

THIS WARRANTY IS IN ADDITION TO WARRANTIES AND CONDITIONS IMPLIED BY STATUTE AND OTHER

STATUTORY RIGHTS AND OBLIGATIONS THAT BY ANY APPLICABLE LAW CANNOT BE EXCLUDED,

RESTRICTED OR MODIFIED (“MANDATORY RIGHTS”). ALL OTHER WARRANTIES OR CONDITIONS, EXPRESS

OR IMPLIED (BY STATUTE OR OTHERWISE), ARE EXCLUDED. WITHOUT LIMITING THE FOREGOING

PROVISIONS OF THIS PARAGRAPH, WHERE A PRODUCT IS SUPPLIED FOR BUSINESS PURPOSES, THE

CONSUMER GUARANTEES UNDER THE CONSUMER GUARANTEES ACT 1993 (NZ) WILL NOT APPLY.

NEITHER THIS WARRANTY NOR ANY OTHER CONDITION OR WARRANTY BY CATERPILLAR, EXPRESS

OR IMPLIED (SUBJECT ONLY TO THE MANDATORY RIGHTS), IS APPLICABLE TO ANY ITEM CATERPILLAR

SELLS THAT IS WARRANTED DIRECTLY TO THE USER BY ITS MANUFACTURER.

IF THE MANDATORY RIGHTS MAKE CATERPILLAR LIABLE IN CONNECTION WITH SERVICES OR GOODS,

THEN TO THE EXTENT PERMITTED UNDER THE MANDATORY RIGHTS, THAT LIABILITY SHALL BE LIMITED

AT CATERPILLAR’S OPTION TO (a) IN THE CASE OF SERVICES, THE SUPPLY OF THE SERVICES AGAIN OR

THE PAYMENT OF THE COST OF HAVING THE SERVICES SUPPLIED AGAIN AND (b) IN THE CASE OF GOODS,

THE REPAIR OR REPLACEMENT OF THE GOODS, THE SUPPLY OF EQUIVALENT GOODS, THE PAYMENT OF

THE COST OF SUCH REPAIR OR REPLACEMENT OR THE ACQUISITION OF EQUIVALENT GOODS.

CATERPILLAR EXCLUDES ALL LIABILITY FOR OR ARISING FROM ANY NEGLIGENCE ON ITS PART

OR ON THE PART OF ANY OF ITS EMPLOYEES, AGENTS OR REPRESENTATIVES IN RESPECT OF THE

MANUFACTURE OR SUPPLY OF GOODS OR THE PROVISION OF SERVICES RELATING TO THE GOODS.

CATERPILLAR IS NOT LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES UNLESS IMPOSED UNDER

MANDATORY RIGHTS.

IF OTHERWISE APPLICABLE, THE VIENNA CONVENTION ON CONTRACTS FOR THE INTERNATIONAL SALE

OF GOODS IS EXCLUDED IN ITS ENTIRETY.

C) For products supplied in Australia:

IF THE PRODUCTS TO WHICH THIS WARRANTY APPLIES ARE:

I. PRODUCTS OF A KIND ORDINARILY ACQUIRED FOR PERSONAL, DOMESTIC OR HOUSEHOLD USE

OR CONSUMPTION; OR

II. PRODUCTS THAT COST AUD 40,000 OR LESS,

WHERE THOSE PRODUCTS WERE NOT ACQUIRED FOR THE PURPOSE OF RE-SUPPLY OR FOR THE

PURPOSE OF USING THEM UP OR TRANSFORMING THEM IN THE COURSE OF PRODUCTION OR

MANUFACTURE OR IN THE COURSE OF REPAIRING OTHER GOODS OR FIXTURES, THEN THIS SECTION

C APPLIES.

THE FOLLOWING MANDATORY TEXT IS INCLUDED PURSUANT TO THE AUSTRALIAN CONSUMER LAW

AND INCLUDES REFERENCES TO RIGHTS THE USER MAY HAVE AGAINST THE DIRECT SUPPLIER OF

THE PRODUCTS: OUR GOODS COME WITH GUARANTEES THAT CANNOT BE EXCLUDED UNDER THE

AUSTRALIAN CONSUMER LAW. YOU ARE ENTITLED TO A REPLACEMENT OR REFUND FOR A MAJOR

FAILURE AND COMPENSATION FOR ANY OTHER REASONABLY FORESEEABLE LOSS OR DAMAGE. YOU

ARE ALSO ENTITLED TO HAVE THE GOODS REPAIRED OR REPLACED IF THE GOODS FAIL TO BE OF

ACCEPTABLE QUALITY AND THE FAILURE DOES NOT AMOUNT TO A MAJOR FAILURE. THE INCLUSION

OF THIS TEXT DOES NOT CONSTITUTE ANY REPRESENTATION OR ACCEPTANCE BY CATERPILLAR OF

LIABILITY TO THE USER OR ANY OTHER PERSON IN ADDITION TO THAT WHICH CATERPILLAR MAY HAVE

UNDER THE AUSTRALIAN CONSUMER LAW.

TO THE EXTENT THE PRODUCTS FALL WITHIN THIS SECTION C BUT ARE NOT OF A KIND ORDINARILY

ACQUIRED FOR PERSONAL, DOMESTIC OR HOUSEHOLD USE OR CONSUMPTION, CATERPILLAR LIMITS

ITS LIABILITY TO THE EXTENT IT IS PERMITTED TO DO SO UNDER THE AUSTRALIAN CONSUMER LAW

TO, AT ITS OPTION, THE REPAIR OR REPLACEMENT OF THE PRODUCTS, THE SUPPLY OF EQUIVALENT

PRODUCTS, OR THE PAYMENT OF THE COST OF SUCH REPAIR OR REPLACEMENT OR THE ACQUISITION

OF EQUIVALENT PRODUCTS.

THE WARRANTY SET OUT IN THIS DOCUMENT IS GIVEN BY CATERPILLAR INC. OR ANY OF ITS

SUBSIDIARIES, 100 N. E. ADAMS ST, PEORIA, IL USA 61629, TELEPHONE 1 309 675 1000, THE USER IS

RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH MAKING A CLAIM UNDER THE WARRANTY SET

OUT IN THIS DOCUMENT, EXCEPT AS EXPRESSLY STATED OTHERWISE IN THIS DOCUMENT, AND THE

USER IS REFERRED TO THE BALANCE OF THE DOCUMENT TERMS CONCERNING CLAIM PROCEDURES,

CATERPILLAR RESPONSIBILITIES AND USER RESPONSIBILITIES.

TO THE EXTENT PERMISSIBLE BY LAW, THE TERMS SET OUT IN THE REMAINDER OF THIS WARRANTY

DOCUMENT (INCLUDING SECTION B) CONTINUE TO APPLY TO PRODUCTS TO WHICH THIS SECTION C

APPLIES.

©2016 Caterpillar All Rights Reserved.

CAT, CATERPILLAR, their respective logos, "Caterpillar Yellow" the "Power Edge" trade dress as well as corporate and

product identity used herein, are trademarks of Caterpillar and may not be used without permission.