DIFFERENTIAL PROTECTION

Page 2: Differential Protection 8

Differential protection

Page 3: Differential Protection 8

Differential protection application

Page 4: Differential Protection 8
Page 5: Differential Protection 8
Page 6: Differential Protection 8
Page 7: Differential Protection 8
Page 8: Differential Protection 8
Page 9: Differential Protection 8
Page 10: Differential Protection 8

Differential Relay – Operating Principle

PLANT TO BE PROTECTED

I1 I2

I1 = I2 Healthy; no trip| I1 - I2 | > Limit Fault; trip

“Balanced beam” type of relay – difference current trips beam; through current restrains it.Modern relays do the comparison by microprocessor

Page 11: Differential Protection 8

Differential Relay Coil Connection

Page 12: Differential Protection 8

Differential Relay – Transformer Application

• Transformation ratio has to be taken into account. Trip if |aI1 – I2| > Limit, where a is trf. ratio (VP/VS)

• Three-phase delta-star or star-delta. The phase shift and 3 have to be taken into account

• Allow for inrush currents – suppress tripping (2nd harmonic restraint).

• Allow for ratio changes due to tap-changing (may be 10-15%)

Page 13: Differential Protection 8

Transformer Inrush Current-Full DC Offset

Page 14: Differential Protection 8

Differential Relay Set-up for Delta-Star Transformer

CTs in delta

CTs in star

DeltaStar

Page 15: Differential Protection 8

Transformer Differential Protection Example

• 33/11 kV, star-star transformer. Rating = 25 MVA

• Standard CT ratios available are 200:5, 400:5, 600:5, 800:5, 1000:5, 1600:5, 1800:5

• Allow for 15-20% unbalance

Page 16: Differential Protection 8

Transformer Differential Protection Example .. 2

• Full–load current = 437 A/ph (33kV side), =1312 A/ph (11kV side)• Allow 150% overload. Choose 600:5 CT for 33kV. • Transformation ratio = 3. Choose 1800:5 CT for 11kV

side• Set HV normal current In = 450 A say• Set bias to 20%.• If delta-star transformer, allow for 3 (in LV CT ratio for

old relays – Idelta = Iline/ 3; taken care of in setting for modern relays)

Page 17: Differential Protection 8

Busbar Differential Protection Scheme

Page 18: Differential Protection 8

Limitations with OC Protection in Transformers

• A simple overcurrent and earth fault relay will not provide adequate protection for winding earth faults.

• Need some earth fault protection.• Degree of earth fault protection is very

much improved by the application of unit differential or restricted earth fault systems.

Page 19: Differential Protection 8

Restricted Earth Fault Protection

Page 20: Differential Protection 8

Restricted Earth Fault - How it Works

• On the HV side, the residual current of the 3 line CT’s is balanced against the output current of the CT in the neutral conductor.

• For the LV side, earth faults occurring on the delta winding may also result in a level of fault current of less than full load. HV overcurrent relays will not provide adequate protection.

• A relay connected to monitor residual current will provide restricted earth fault protection since the delta winding cannot supply zero-sequence current to the system.

Page 21: Differential Protection 8

Restricted Earth Fault - How it Works .. 2

• Both windings of the transformer can thus be protected separately with restricted earth fault.

• Provide high speed protection against earth faults over the whole of the transformer windings.

• Relay used is an instantaneous high impedance type.

Page 22: Differential Protection 8

High Impedance Differential Scheme

Page 23: Differential Protection 8

High Impedance Scheme - How it WorksThe CTs generate currents that create a high voltage across the relay (which has a high burden).

CTs must generate 2 times the trip voltage to work on an internal fault

If one only CT saturates for through fault, not enough voltage is generated to trip relay.

Page 24: Differential Protection 8

High Impedance Scheme - Requirements

• CTs must have identical turns ratios, knee-point voltages 2 times relay operating voltage, high accuracy, low reactance (‘PX’ class)

• High internal faults can generate high voltage across relay - some form of voltage dependent resistor (“metrosil”) is required to avoid this.

Page 25: Differential Protection 8

High Impedance Scheme -

Example … 1

Page 26: Differential Protection 8

High Impedance Scheme - Example … 2

Page 27: Differential Protection 8
Page 28: Differential Protection 8
Page 29: Differential Protection 8
Page 30: Differential Protection 8
Page 31: Differential Protection 8
Page 32: Differential Protection 8