Digital InverterQuick reference Card

4-Way Air Discharge Cassette TypeRAV-SM560UT-E RAV-SM800UT-E

Concealed Duct TypeRAV-SM560BT-E RAV-SM800BT-E

Indoor Units

High-Wall TypeOutdoor UnitsRAV-SM560KRT-E RAV-SM800KRT-E

RAV-SM560AT-E RAV-SM800AT-E

1 1 Refrigerant HFC (R410A)This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.

1. Required ToolsThe service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut of the refrigerant piping are lengthened. Tools exclusive for R410A (The following tools for R410A are required.) Tools whose specifications are changed for R410A and their interchangeabilityR410A air conditioner installation Whether Existence of conventional new equipment equipment for R410A can be used Yes Yes Yes Yes Yes Yes Yes Yes (Note 2) *(Note 1) *(Note 1) *(Note 1) Conventional air conditioner Whether new equipment can be used with conventional refrigerant

No

Used tool

Usage

1 2 3 4 5 6 7 8 9 10

Pipe flaring Flate tool Copper pipe gauge Flaring by for adjusting conventional flare tool projection margin Torque wrench Gauge maniford Charge hose Vacuum pump adapter Connection of flarenut Evacuating,refrigerant charge,run check,etc. Vacuum evacuating

Electronic balance for Refrigerant charge refrigerant charging Refrigerant cylinder Leakage detector Charging cylinder Refrigerant charge Gas leakage check Refrigerant charge

(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary. (Note 2) Charging cylinder for R410A is being currently developed.

2. Refrigerant chargeUp to 20m piape length, no need to add refrigerant. Exceed 20m, add the specified amount of the refrigerant.

Refrigerant adding procedure1) After vacuuming the pipe, charge the refrigerant with the valve close. 2) When the specified amount of the refrigerant cannot be charged, add the remained refrigerant from charging port of the valve at gas side with cooling operation. Record the added amount of the refrigerant in the site.(Note) Charge the refrigerant as liquid state. Otherwise the component of the refrigerant varies and the normal operation is disabled.

Additional charging amountCapacity rank 56 type 80 type Additional charging amount 20g/m 40g/m Max. Pipe Length 30 m 50 m

2

Systematic Diagram of Refrigerating CycleRAV-SM560AT-ETS sensor TD sensor 4-way valve (STF-0108G) Muffler 19 L160 Rotary compressor (DA130A1F-23F)Pressuare (MPa) Pd Ps (kg/cm2G) Pd Ps

Refrigerant pipe at gas side 12.7 Packed valve

Refrigerant pipe at liquid side 6.4 Packed valvePulse motor valve (PMV) (SKV-18D26)

Muffler 25 L80 TO sensor

Strainer TE sensor Heat exchanger 8 multiple thread ripple (1 row 22 stages) FP1.3 flat fin DistributorIn cooling operation In heating operation

Frequency of comp (rps)*

Pipe surface temp. (C)Indoor Outdoor Disheat charge Suction heat exchanger exchanger (TD) (TS) (TC) (TE)

Indoor fan

Indoor/Outdoor temp. conditions (DB/WB) (C) Indoor Outdoor

COOL

Standard 3.13 0.87 31.9

8.9 85 93 7.1 20 6.2 71 78 2.5 69

15 20 7 1 20 -14

10 15 3 39 54 31

50 57 5 3 19

74 72 28 84 47

HIGH 27/19 HIGH 32/24 LOW 18/15.5 HIGH LOW 20/30/15/-

35/43/-5/7/6 24/18 -10/(70%)

Over load 3.64 1.02 37.1 10.4 Low load 0.89 0.70

9.1

HEAT

Standard 2.31 0.61 23.6

Over load 3.26 1.16 33.2 11.8 Low load 1.86 0.25 19.0

-15 107 HIGH

* This compressor is provided with 4-pole motor. The frequency value of the comp shows two times as actual one by a clamp meter.RAV-SM800AT-ETS sensor TD sensor 4-way valve Muffler (STF-0213G) TE sensor Capillary 3 2 L530In cooling operation In heating operationIndoor/Outdoor temp. conditions (DB/WB) (C) Indoor Outdoor

Refrigerant pipe at gas side 15.9 Packed valve

Refrigerant pipe at liquid side 9.5 Packed valvePulse motor valve (PMV) (SKV-18D26)

Strainer

TO sensor

Strainer

25 L210 Heat exchanger 8 multiple thread 25 L160 ripple (1 tow 30 stages) FP1.3 flat fin Rotary compressor (DA220A2F-20L) AccumulatorPressuare (MPa) Pd Ps (kg/cm2G) Pd Ps Pipe surface temp. (C)Indoor Outdoor Disheat charge Suction heat exchanger exchanger (TD) (TS) (TC) (TE)

Frequency of comp (rps)*

Indoor fan

COOL

Standard 3.28 0.86 33.4

8.8 86 90 7.9 19 6.3 67 85 2.3 89

11 21 4 6 23 -16

9 18 4 42 55 34

44 54 8 2 16 -18

64 52 27 65 31 90

HIGH HIGH HIGH LOW HIGH

27/19 32/24 20/30/15/-

35/43/-5/7/6 24/18 -10/(70%)

Over load 3.71 1.12 37.8 11.4 Low load 0.98 0.77 10.0 Standard 2.53 0.62 25.8

LOW 18/15.5

HEAT

Over load 3.40 1.13 34.7 11.5 Low load 1.99 0.23 20.3

* This compressor is provided with 4-pole motor. The frequency value of the comp shows two times as actual one by a clamp meter.

3

Check Code ListTable (Cassette / Duct type)

: Go on : Flash : Go of ALT : Two LED flash alternately. SAME : Two LED flash at the same time.Sensor Check Check code code Indoor display panel (Central) (Individual) Flash Failed position Detection

19 18 1b 1F 1d 17 1C 46 1E 21 1A 14 16 97 97 04 96 99 CF

F04 F06 F08 H01 H02 H03 L29 L31 P03 P04 P22 P26 P29 E01 E02 E03 E04 E08 E09 E10

ALT Outdoor, TD sensor error ALT Outdoor, TE, TS sensor error ALT Outdoor, TO sensor error Compressor breakdown Compressor lock ALT Outdoor, current detection error SAME Other outdoor error SAME Phase order error, etc ALT Outdoor, discharge gas temp error ALT Outdoor, high-pressure error ALT Outdoor, outdoor FM error ALT Outdoor, inverter ldc operation ALT Outdoor, position detect error Remote controller No master or No communication Remote controller signal sending error Indoor /remote controller communication error Indoor/Outdoor serial communication error Duplicated indoor addresses* Duplicated master remote controllers Communication error between CPU Master/Sub Indoor communication error SAME Duplicated master indoor units* SAME Group wiring in individual indoor unit SAME Unset indoor group address SAME Unset indoor capacity SAME Abnormal input to indoor unit ALT 4-way valve error ALT Indoor TCJ sensor error ALT Indoor TC sensor error ALT Indoor TA sensor error

Outdoor Outdoor Outdoor Outdoor Outdoor Outdoor Outdoor Outdoor Outdoor Outdoor Outdoor Outdoor OutdoorRemote controller Remote controller

Indoor Indoor IndoorRemote controller

Indoor Indoor Indoor Indoor Indoor Indoor Indoor Indoor Indoor Indoor Indoor

97,99 E18 96 99 99 46 b6 08 0F 0d 0C 12 11 0b 11 47 b7 97 98 99 L08 L07 L08 L09 L30 P19 F01 F02 F10 F29 P01 P10 P12 P31 L20

SAME Indoor, other indoor P.C. board error Indoor ALT Indoor, indoor FM error ALT Indoor, overflow detected ALT Indoor, indoor FM error ALT Other indoor unit error Up to the unit type ALT Indoor Error among group LAN communication error SAME LAN communication error Adapter Duplicated error Indoor Indoor Indoor Indoor Network adapterNetwork adapter, central Network adapter, central

Network adapter

*Group organization when the power supply is turned on.

Auto Restart

Description

Open or short of TD sensor was detected. Open or short of TE.TS sensor was detected. Open or short of TO sensor was detected. After current control , short-circuit current (ldc) was detected Locked compressor was detected. Abnormal current in AC-CT or phase missing was detected. Other outdoor unit error 1) MCU Communication error between IPDU and CDB. 2) Abnormal temperature was detected in temp sensor of IGBT heat sink. Phase order error of 3-phase power supply and others. Abnormal TD temp. was detected. High-pressure switch IOL worked. Abnormal TE temp was detected. Over-current, lock, etc. was detected on drive circuit of outdoor FM. Short-circuit protection of G-Tr, IGBT worked. Position detection error of compressor. No Signal from indoor (No master) Signal could not send to indoor. No signal from remote controller or network adapter. Indoor/Outdoor serial communication error. The same address with the one was detected. Both 2 remote controller were set as master in 2 controllers. Master unit stop. Communication error between main and motor control MCU. No communication between Master and Sub Indoor unit in the Gr. Multiple master units in a group. Group wiring is connected to the individual indoor units. Indoor address group was unset. Indoor unit capacity was unset. CN80 abnormal input and unit stop. In heating temp down of indoor heat exchanger. Open/short of TCJ sensor was detected. (TC) Open/short of TCJ sensor was detected. (TC) Open/short of TA sensor was detected. EEPROM error (Other error may be detected. Otherwise AUTO address is repeated.) Indoor AC FM error was detected. (Fan motor thermal relay worked) Float switch worked. Indoor DC FM error (over-current, lock, etc.) was detected. Another indoor unit in the group alert. (E03/L07/L03/L08 alarm) Indoor error found in the Group of central remote controller. Communication error of the central control system. *No displayed on the remote controller. Indoor addresses duplicated in the central control system . Multiple adapters in the wiring of the remote controller.

Operation ON

4 Check Code List : Indoor Unit Detect (Cassette/Duct Type)Error to be detected by indoor unitOperation of diagnostic function

Check code

Cause

Unit status

Judgment and Action

E03

No communication from All off 1. Check wiring of remote controller and remote controller (includ- (Automatic communication adapter. ing wireless ) and comrestart ) Disconnection : controller display off munication adapter. [97] check code of central remote controller No serial signal from outdoor unit . Wrong wiring All off Serial sending circuit error on outdoor P.C. (Automatic restart ) board Serial receiving circuit error on indoor P.C. board Duplicated indoor unit addresses Duplicated master indoor unit Group line in individual indoor units Unset indoor group address Unset indoor capacity Abnormal input of outside interlock Fan motor thermal protection Float switch operation Disconnection/coming off of float circuit, switch contact error Indoor DC FM error All off All off All off All off All off All off All off 1. Set the indoor capacity. (DN = 11) 1. Outside devices check 2. Indoor P.C. board check 1. Thermal relay check of fan motor 2. Indoor P.C. board check 1. Defective drain pump 2. Stagnation of drain water 3. Float switch check 4. Indoor P.C. board check 1. Position detection error 2. Over-current protective circuit of indoor fan drive unit works. 3. Indoor FM lock 4. Indoor P.C. board check 1. Outdoor unit no operate wiring check, case thermo operation Outdoor P.C. board check 2. Outdoor unit normally operate. P.C. board (Indoor receiving/Outdoor sending) check

E04

E08 L03 L07 L08 L09 L30 P01 P10

1. Check connection change after power on firstly.

All off

P12

All off

P19

4-way valve failure

All off 1. 4-way valve check (Automatic 2. TC/TCJ sensor check restart ) 3. Indoor P.C. board check All off (Sub) (Automatic restart ) All off (Automatic restart ) All off (Automatic restart ) All off (Automatic restart ) All off (Automatic restart ) 1. Sub units judg while master unit is in [E03], [L03], [L07] or [L08]. 2. Indoor P.C. board check 1. Check for indoor TCJ sensor 2. Indoor P.C. board check 1. Check for indoor TC sensor 2. Indoor P.C. board check 1. Check for indoor temp sensor (TA) 2. Indoor P.C. board check 1. Check Indoor EEPROM (including socket insertion) 2. Indoor P.C. board check

P31

Alarm other indoor unit, own unit stops. Coming-off, disconnection or short of TCJ sensor Coming-off, disconnection or short of TC sensor Coming-off, disconnection or short of TA sensor Indoor EEPROM error EEPROM access error

F01 F02 F10 F29 E10

1. Indoor P.C. board check Communication error between indoor MCU All off Communication error (Automatic restart ) Between FM driving MCU and main MCU Communication error All off 1. Remote controller wiring check between master and (Automatic 2. Indoor power wiring check restart ) 3. Indoor P.C. board check sub indoor units

E18

5 Check Code List : Outdoor Unit Detect (Cassette/Duct Type)Error to be detected by outdoor unitOperation of diagnostic functionCheck code Cause Unit status Judgment and Action

H01

Compressor breakdown Compressor stopped due to lowering of operation frequency after operation had started. Compressor did not rotate. Over-current protective circuit operated when a constant time passed after compr essor had been activated. Current detection cir cuit error Current value at AC side is high even if compressor stops. Phase of power supply is missed. Error on outdoor unit, etc. Communication error between CDB and IPDU (Coming-off of connector) Heat sink temperature error (Temperature over specified value was detected.)

All off

1. Power voltage check AC200V20V 2. Overload operation of refrigerating cycle 3. Check for AC current detection cir cuit 1. Trouble on compr essor ( lock, etc.) Replace the compressor. 2. Cable trouble of compr essor (Phase missing) 3. Phase-missing operation of power supply ( 3phase model) 1. Start operating but soon stop IPDU check 2. Phase-missing operation of power supply Check for 3-phase power voltage, wiring cable check

H02

All off

H03

All off

L29

1. CDB and IPDU wiring cables check 2. Abnormal overload operation of r efrigerating cycle

All off

L31* Phase detection protective circuit operated. (Normal model) P03 Discharge temperature error Discharge temperature over the specified value was detected. High-pressure protection error by TE sensor (T emperature over the specified value was detected.) Outdoor DC FM error

Continuance 1. Phase order of power supply (Reverse phase) /Missing phase check (Compressor 2. Outdoor P.C. board check stop) All off1. Refrigerating cycle check (Gas leak) 2. Trouble on electric expansion valve 3. Td sensor check 1. Overload operation of refrigerating cycle 2. Check for outdoor temperatur e sensor (TE) 3. P.C. board check of outdoor CDB 1. Position detection err or 2. Over-current protective circuit of outdoor FM drive works. 3. Outdoor fan lock 4. Outdoor CDB P.C. board check 1. Start operating but soon stop Compressor motor short 2. IPDU check: Wiring check 1. Position detection cir cuit operates even if disconnecting 3P connector of the compressor. Replace IPDU. 1. Check for outdoor temp sensor (TD) 2. Outdoor CDB P.C. board check 1. Check for outdoor temp sensor (TE, TS) 2. Outdoor CDB P.C. board check 1. Check for outdoor temp sensor (TO) 2. Outdoor CDB P.C. board check

P04

All off

P22

All off

P26

Operation of inverter over-current protective circuit (In a short time) IPDU position detection circuit error Coming-of f, disconnection or short of outdoor temp sensor (TD) Coming-of f, disconnection or short of outdoor temp sensor (TE, TS) Coming-of f, disconnection or short of outdoor temp sensor (TO)

All off

P29

All off

F04

All off

F06

All off

F08

All off

* For the error mode detected by the outdoor unit, sub indoor units in a gr oup operation continues the fan the operation because no communicate with the outdoor units.

6 Check Code List : Remote Controller or Network Adapter Detect (Cassette/Duct Type)Error to be detected by remote controller or network adapterOperation of diagnostic function Check code Cause Unit status

Judgment and Action Power supply error of remote controller, indoor EEPROM error 1. Remote controller wiring check 2. Remote controller check 3. Indoor power wiring check 4. Indoor P.C. board check 5. Indoor EEPROM check (including socket insertion) automatic address repeat phenomenon

No display (No operation)

No communication with master unit of indoor units Wiring of remote controller is not correctly connected. Power of indoor unit is not turned on. Automatic address is not completed

All off

Remote controller receiving error E01 No communication with 1. Remote controller inter-unit wiring check *2 master unit of indoor All off 2. Remote controller check units (Automatic 3. Indoor power wiring check Wiring disconnection between remote control- restart ) 4. Indoor P.C. board check ler and master indoor unit (Remote controller detect ) All off 1. Check for sending circuit of remote E02 Error of signal sending to (Automatic indoor unit controller restart ) ( Remote controller deReplace remote controller. tect ) E09 There are multiple master All off 1. Check for multiple master for 2 remote remote controllers. controllers ( including wireless ): Only one (Sub units for master, and others are for sub. ( Remote controller detect ) keep operation ) L20 Duplicated indoor central 1. Check for network address setup (Network adapter SW01) Central addresses on central con- All off remote trol system (AI-NET) (Automatic 2. Network adapter P.C. board check. controller (Detected at central conrestart ) 98 *3 troller side) 1. Check for multiple network adapters There are multiple net2. Check for incorrect controller wrong wiring work adapters on comOnly one adapter on communication line of munication line of remote Continuation Central remote controller. controller. (Detected at of operation remote controller central controller side) 99 Interruption of communiContinuance cation on central control Continuation Central system (AI-NET) of operation remote (Detected at central con- (According to troller side) controller individual 97 remotecontroller)

*3

1. Check for communication wiring, and power supply of indoor unit. 2. Communication check (XY terminal) 3. Check for network adapter P.C. board 4. Check for central controller (central remote controller, etc.)

*2 Check code cannot be displayed by the wired remote controller. (Usual operation of the air conditioner cannot be performed.) For wireless models, an error is indicated by the display lamp. *3 This error is related to the remote controllers (A, B) and the central system (AI-NET, X, Y). On the individual remote controller, [E01], [E02], [E03] , [E09] or [E18] is displayed or check code is not displayed according to contents of the error.

7 Error Check Method by Outdoor PC board LEDSW800 : LED display while Bit 1, 2, and 3 set off When multiple errors are detected, the latest error is displayed. When LED display goes on, the main cause of trouble exist at CDB side, and the unit stops. When LED display flashes, the main cause of trouble exists at IPDU side, and the unit stops. When the case thermostat operates, the communication is interrupted on the serial circuit. If it continues, it cause a serial communication error.SW800 bit 1 bit 2 bit 3 No. Item Check code LED display

Handy Central D800 D801 D802 D803 remote controller control (Red) (Yellow) (Yellow) (Yellow)

1 TE sensor error 2 TD sensor error

F06 F04 F06 F08 F03 P22 L29 P04 E04 P26 P29 H03

18 19 18 1B 1E 1A 1C 21 04 14 16 17 17 1D 1F 1C : Light ON : Light OFF : Flash

3 TS sensor error 4 TO sensor errorCDB side

5 6

Discharge temp. error DC outdoor fan error

7 Communication error between IPDU OFF OFF OFF 8 High-pressure release operation

9 Case thermo. operation 10 EEPROM error 11 G-Tr short-circuit protection 12 Detection circuit errorIPDU side

13 Current sensor error

14 Phase-missing detection H03 15 Compressor lock error 16 Compressor breakdown 17 Tin sensor error H02 H01 L29

SW800

LED

8 Indoor unit PC board exchange method (Cassette & Duct Type)

In the failed PC board, an important data is memorized in the EEPROM (memory) part. The data is also needed for the exchanged PC board. So please follow procedure below. (Before exchanged) Case 1. You can check the memorized data by wired remote controller. Case 2. You can not check the memorized data by a EEPROM failure. Case 1. Read the data power OFF Change PC board power ON Write the read data Case 2. Change PC board power ON Write the data

Power reset

Power reset

*all indoor unit when Gr operation

1. How to read the set data in the EEPROMa. Push (SET)+(CL)+( ) button concurrently for more than 4sec. b. Push (UNIT) button to select the set unit when Gr operation. (selected unit start fan operation) c. Read the set data of each CODE by pushing "TEMP SET" / button. (The least data you must read is in the next table . DN=10-14)

2. How to change the PC boarda. Change the PC board with set the jumper wire and connector same state as before. b. In Gr all indoor Power on and wait for 5min until automatic address is set.

3. How to write the data to the EEPROMa. Push (SET)+(CL)+( ) button all concurrently for more than 4sec. b. Push (UNIT) button to select the set unit when Gr operation. (selected unit start fan operation) c. Select the set CODE by pushing "TEMP SET" / button. d. Select the data to write by pushing "TIMER SET" / button. e. Push "SET" button to complete writing of each item. f. Repeat b.-e. Procedure until all the data written. g. Push ( ) button to get to a normal "Unit STOP" state. (It takes about a minute to ready to operate by remote controller) NOTE ) At least 1 wired remote controller is needed in the indoor group . Above procedure is followed when unit operation stop. When group operation, at first master unit No. is displayed. ex. "2-1"

Code

Item

Set Data

10

Indoor Unit type

0001 : 4way Casette Type 0006 : Duct Type

11

Capacity of Indoor Unit

0009 : 56 Type 0012 : 80 Type

12

System address (1 address/ outdoor unit )

0099 : Initial 0001-0030 : Set Address 0099 : Initial 0001-(0064) : Set Address 0099 : Initial 0000 : individual (No Group) 0001 : Master 0002 : Sub (In Group) (In Group)

13

Indoor Unit address (Max No indoor unit/ System)

14

Gr address *In Gr operation only 1 indoor unit : Master others : Sub (max 7units)

NOTE ) Max No. of System address is "8" in Gr operation. In single operation, Indoor Unit address is always "1".

Wired Remote controller display

CODE No.SET DATA

UNIT No.

R.C.

No.

Set Data

System address Indoor Unit address

CODE

Wired Remote controller operation button

UNIT

TIMER SETSETCL

TEMP SET

Set Mode

9 Monitoring function by wired remote controller

1. Cycle Temperatur e Monitoring a. Push (CL)+( ) button concurrently for more than 4sec. b. Push (UNIT) button to select unit when Gr operation. c. Read the cycle temperatur e by pushing " TEMP SET " /Indoor unit Code 00 01 02 03 04 Item 00 or 01 Code Remotecontroll Ta (room) TCJ (coil) TC (coil) Outdoor unit Code 60 61 62 63 64 65 TE (coil)

button.

Item

TO (outdoor) TD (discharge) TS (suction) THS (heat sink)

* 00 displayed center unit when Gr operation

2. Error History Check a. Push (SET)+( ) button concurr ently for more than 4sec. b. The latest error code is displayed as CODE No."01" c. Push " TEMP SET " / button to check the second - fourth latest error code. d. Push ( ) button to get to a normal state. * Do not push the "CL" button or all err or code will be clear ed.

Wired Remote contr oller display

Error check

Monitering

Wired Remote contr oller operation button

TEMP SET

Monitoring Mode

10

Self diagnostic Method (High Wall)

Rough diagnosis by indoor unit display panel (indicators)Check code rough Indoor panel indicators Contents Check code details

_ 00 01 02 03

"OPERATION" lamp flash

1Hz Failure of power supply (After power-on reset) "OPERATION" lamp flash 5Hz Indoor P.C. board "OPERATION"&"TIMER" lamp flash 5Hz Connecting cable & serial signal "OPERATION"&"PRE.DEF" lamp flash 5Hz outdoor P.C. board "OPERATION","TIMER"&"PRE.DEF" lamp flash 5Hz Others (including compressor)

_ 0b-0F,11,12 04 14-19,1A,1C 1B,1E,1F, 21

Display panelThe operating conditions ar e indicated below . 1 2 3 4 5 AUTO (green) PRE.DEF .lamp (orange) FILTER lamp (orange) TIMER lamp (yellow) OPERA TION lamp(green)

Self - diagnosis with wir eless remote contr oller(1). Selecting service mode: Push the button for selecting service mode for mor e than 3 sec. "00" display. (2). Self diagnosis method : Check receiving sound and indicator by each code. When code was set to the err or cause. "Pi" sound changes to "Pi,Pi,Pi," (continues for about 10 seconds) "OPERA TION" and other indicator flash. (5kHz) (3). Selecting normal mode: Push the "ACL" button for selecting normal mode for more than 3 sec.

Operating key

Indication after operation

ACL

CLOCK

1 is added to data befor e operation. (Example) 1 is subtracted fr om date before operation. (Example) 10 is added from date before operation. (Example)

ACL CLOCK

Date before operation is directly transferred (Example)

Location of service & ACL button

Method of changing set code

Self diagnosis with wir ed remote contr oller (High Wall Type only)(1). Selecting service mode: Push the "CHECK" button for selecting service mode for mor e than 0.5sec. (2). The latest 2 err codes are displayed on panel. or

Check code checked by indoor unit (High Wall Type)Indoor panel indicators"OPERATION" and "TIMER" lamp flash (5kHz)

Check code

Primary cause

Unit status

Judgment and Action

04

Return serial signal is not sent to 1.Outdoor unit no operation indoor from outdoor. a).Correct mis-wiring (1) Mis-wiring b).Check outdoor P.C. board continu(2) send or receive circuit failure of c).Check case thermo of ance the outdoor P.C. board compressor (3) Compressor thermo detector start d).Check amount of charged gas gas shortage/gas leak 2.Outdoor unit normal operation a).Check P.C. board of in/outdoor 4-way valve inverse error (1) TC sensor value UP : Cooling, DOWN:Heating Other refrigerant cycle error (1) TC sensor value no change Cooling / Heating 1.Check 4way valve continu- 2.Check 2way and One way valve ance 3.Check TC sensor 4.Check indoor P.C. board 1.Check case thermo of compressor continu- 2.Check TC sensor attatchment ance 3.Check TC sensor 4.Check indoor P.C. board continu- 1.Check TA sensor ans 2.Check indoor P.C. board continu- 1.Check TC sensor ance 2.Check indoor P.C. board continu- 1.Check TCJ sensor ance 2.Check indoor P.C. board 1.Check indoor FM connector circuit All-off 2.Check indoor FM 3.Check indoor P.C. board continu- 1.Check indoor P.C. board (around ance EEPROM)

08

09

0C"OPERATION" lamp flash (5kHz)

TA (Room temp sensor) error TC (Room temp sensor) error TCJ (Room temp sensor) error Indoor fan error (Abnormal frequency) Trouble on other indoor P.C. boards

0d 0F

"OPERATION" lamp flash (5kHz)

11 12

Error code checked by outdoor unit (High Wall Type)Indoor panel indicators Check code Primary cause Inverter over-current protective circuit operates. (Short time) 14 Unit status Judgment and Action

1.Restart but stop. a).Check short circuit of compressor. b).Check IGBT. All-off c).Check P.C. board output. d).Check outdoor P.C. board. All-off 1.Restart but stop. a).Change outdoor P.C. board.

"OPERATION " and "PRE,DEF" lamp flash(5kHz)

17

Current-detect circuit error (1). High AC current when compressor OFF (2).Low DC current when compressor ON TE or TS sensor error TD(Discharge gas temp sensor) error TO (Out door temp sensor) error Compressor drive output error Compressor error (lock,missing,etc.) IPDU communication error Disconnection between CDB-IPDU Compressor does not rotate. (Over current protective device will operate after compressor ractivate) Discharge gas temp abnormally higher Break down of compressor

18 19 1b

1.Check TE TS sensor. All-off 2.Check outdoor P.C. board. All-off 1.Check TD sensor. 2.Check outdoor P.C. board.

continu- 1.Check TO sensor. ance 2.Check outdoor P.C. board. 1.Check over load operation. 2.Check Heat sink. 3.Check wiring between CDB and IPDU. 1.Trouble on compressor (lock etc.) Change compressor. 2.Trouble on wiring of compressor (Missed phase)

1C

All-off

1d

All-off

"OPERATION " and "TIMER" "PRE,DEF" lamp flash(5kHz)

1E

1.Check refrigerant leakage. All-off 2.Check PMV. 3.Check TD sensor. 1.Check poewr voltage. All-off 2.Check over load operation. 3.Check AC current detective circuit All-off 1.Check over load operation. 2.Check TE sensor. 1.If position tracking operation works after Compressor lead wire off @ Change IPDU.

1F High-pressure value (TE sensor) abnormal IPDU position tracking error (DC motor)

21

16

All-off

11

Wiring Diagram ( Outdoor Unit )

RAV-SM560AT-EQ200 BLU P17 P18 IGBT MODULE THERMOSTAT FOR COMPRESSOR BRW ORN 2 1 CN500 2 1 2 1 + ~ ~ A E G P10 P09 2 1 TE P20 P19 P08 P07 CN600 1 1 2 2 CONVERTER MODULE DB01 REACTOR

BZ BY BX EW BW EV BV EU BU

BLK P23 WHI P22 RED P21

ELECTRONIC STARTER P.C. BOARD (MCC-813)Q300

POWER RELAYC12 C13 3 C14

CT

CN601 2 2

1 1 3 3

TD TO TS

4

3 2 1 3 2 1

CN602 1 1 2 2

CMCOMPRESSOR

3 RELAY 1 CN701 2 3SURGE ABSORBER VARISTOR FUSE T25A F01 2 250V~

CN603 2 2

1 1 3 1 2 3

F04 FUSE 2 T3. 15A 250V~

+ + +

P06 BLKBLK YEL RED ORN RED GRY CN703

COIL FOR 4-WAY VALVE

1 2 3 4 5 6

1 2 3 4 5 6

PMVPULSE MODULATING VALVE

GRY PNK

BLK WHI RED

YEL

5 4 3 2 1

PUR

2 1 2 1

WHI ORN BLK

CN301 5 4 3 2 1

3 2 1 CN300 3 2 1

P14

P13 P12

P11

P02

P03 P01

FAN MOTOR TERMINAL OF COMPRESSOR BLACK(C) WHITE(S) The sign in ( ) is displayed in the terminal RED(R) cover

FM

REACTOR

1 2 3 LNTO INDOOR UNIT POWER SUPPLY 220 to 240 50Hz

1

SIMPLE CHECK POINTS FOR DIAGNOSING FAULTSCheck items Diagnosis result

12

TERMINAL BLOCK There is no supply voltage (AC220 to 240V) between L - N , 1 - 2 There is no voltage (DC15 to 25V) 2 - 3 FUSE T25A 250V to fuse (F01) blown T3.15A 250V to fuse (F04) blown ELECTROLYTIC CAPACITOR VOLTAGE (C12, C13, C14) DC320V not available between + terminal of electrolytic capacitor

Power supply and connecting cable check Converter module (DB01) and electrolytic capacitor (C12 to C14) check IGBT module (Q200) check Fan motor check T25A fuse (F01) check P.C. board and converter module (DB01) check

3 4CM PMV FM TE TD TO TS IGBT DB01 CT Q300

INVERTER OUTPUT (Inverter and compressor connector out of position) (Please confirm within six minutes after instructing in the drive.) Voltage between each line of inverterside IGBT module and conector pins are not equal. P.C. board check

: Compressor : Pules modulating valve : Fan motor : Heat exchenger Temp. Sensor : Discharge Temp. Sensor : Outdoor Temp. Sensor : Suction Temp. Sensor : Insulated Gate Bipolar Transistor : Converter module : Curreut Transformer : Fan motor driver module

NOTE

Color Identification

BLK BLU RED GRY PNK GRN

: : : : : :

BLACK BLUE RED GRAY PINK GREEN

WHI : WHITE BRW : BROWN ORN : ORANGE YEL : YELLOW PUR : PURPLE

RAV-SM800AT-ET03 CT T04 CT

THERMOSTAT FOR COMPRESSOR ORN 2 2 CN500 ORN 1 1 4-WAY VALVE COIL 33 3 CN700 11 1

Compressor CN604 2 2 11 CN605 2 1 3 CN600 2 1 2 GRN 1 3 1

CMTE TS TD TO

RED WHI BLK

CN09 CN10 CN11

POWER SUPPLY CIRCUIT (FOR P.C. BOARD)F04 FUSE 3.15A

4

2C13 C12 C11 C10

BU EU BV EV IGBT BW module EW BX BY BZ Q200 P20 P19 P18 P17 YEL BLU

+

CN601 2 2 FAN MOTOR 5 5 11 44 Fan 3 3 CN300 FM circuit 22 11 33 2 CN302 1 1 33 2 2 CN301 F300 FUSE 11 55 T5A 44 66 CN800 3 3 55 22 11 PMV 4 4 CN702 33 22 CN04 2 2 11 11

3 2F02 FUSE 15A

BLU YEL BLK WHI BLU RED PNK ORN BLK WHI RED

33 CN04 11 5 4 3 2 1 5 4 3 2 1 5 4 3 CN06 2 1 P.C. BOARD

POWER RELAY

G E A ~ Converter

22 1 1 CN05

(MCC-1359)

RY01 R05 R06 T02 CT

PHOTO COUPLER 5 4 3 CN01 2 1

5 4 3 2 1

SUB P.C. BOARD (MCC-1398)

2CN02

F01 FUSE T3.15A123 1 2 3 GRY WHI REACTOR

5 4 3 2 1 CN13

ORN REACTOR 22 11 REACTOR 22 P08 1 1 P15 BRN P14 P11 P13 P12 P09

P10

module ~ + DB01

2

F01 VARISTOR SURGE FUSE ABSORBER 25A

CN01 RED

CN02 WHI

CN03 BLK

1

RED

TO POWER INDOOR SUPPLY UNIT 220-240V ~50Hz

1 23LN

TERMINAL OF COMPRESSOR BLACK(C) WHITE(S)

The sign in ( ) is displayed in the terminal RED(R) cover

SIMPLE CHECK POINTS FOR DIAGNOSING FAULTSCheck items Diagnosis result

12

3 4BLK BLU RED GRY PNK GRN

TERMINAL BLOCK There is no supply voltage (AC220 to 240V) between L - N , 1 - 2 There is no voltage (DC15 to 25V) 2 - 3 FUSE 25A fuse (F01) blown, 15A fuse (F02) blown 3.15A fuse (F04) blown, T5A fuse (F300) blown (SUB P.C. board) T3.15A fuse (F01) blown (SUB P.C. board) ELECTROLYTIC CAPACITOR VOLTAGE (C10, C11, C12, C13) DC320V not available between + terminal of electrolytic capacitor INVERTER OUTPUT (CN09, CN10, CN11) (Please confirm within six minutes after instructing in the drive.) Voltage between each line of inverterside conector pins are not equal.

Connecting cable check Converter module (DB01) and electrolytic capacitor (C10 to C13) check IGBT module (Q200) check, Fan motor check SUB P.C. board check 25A fuse (F01) check P.C. board and coverter module (DB01) check IGBT module and P.C. board check

Color Identification: : : : : : BLACK BLUE RED GRAY PINK GREEN WHI BRN ORN YEL PUR : : : : : WHITE BROWN ORANGE YELLOW PURPLE

NOTE An abnormal location can be judged by light of the led lamp of the Sub P.C. board assembly.

12

Wiring Diagram ( indoor Unit )

4-Way Air Discharge Cassette Type RAV-SM560UT-E/RAV-SM800UT-E

TA FS 5 4 3 2 1 5 4 3 2 1 5 4 2 1 5 4 3 2 1 5 4 3 2 1 5 4 2 1CN333 (WHI) CN34 (RED) CN104 (YEL)

TCJCN102 (RED)

TC 1 1CN101 (BLK)

12 12

12 12

2 2

123CN80 (GRN)

33 22 11

CN73 (RED)

12

(EXCT)

CN70 (WHI)

1 2

LM1

MCC-1402 Control P.C. Board for Indoor UnitPower supply circuitDC20V DC15V DC12V DC7V

5 4 CN620 3 (BLU) 2 1 6 5 4 CN60 3 (WHI) 2 1CN32 2 (WHI) 1 (FAN DRIVE)

CN33 (WHI)

5 4 3 2 1

5 4 3 2 1

LM2 3 3

Fuse F302 T3.15A 250V~ Motor drive circuit

6 5 4 CN61 3 (YEL) 2 1 5 4 CN50 3 (WHI) 2 1 3 CN309 2 (YEL) 1 3 3 BLK 2 2 BLK 11CN41 (BLU)

FM

5 4 3 2 1 1 2 3 4 5

5 4 3 2 1 1 2 3 4 5

BLK WHI

CN334 (WHI)

Motor drive circuit

2 2 CN001 1 1 (WHI)

Adapter for Wireless Remote Controller

RY 302

RY 303 CN304 (GRY)

CN68 1 2 3 (BLU) 1 2 3

123

CN67 1 2 3 4 5 (BLK) 1 2 3 4 5 RED WHI BLK

Fuse F301 250V~ T6.3A

P301 BLK 1 2 CN66 (WHI) RED Closed-end connector

B A

BLK WHI

2 2 CN1 1 1 (WHI)

Wired Renote Controller

DP

WHI

1 2 3 1 2 3Serial signal Single phase 220 to 240V 50Hz

Indoor unit earth screw Outdoor unit earth screw

L N

FM : TA : TC : TCJ : LM1,LM2 : DP : FS : RY302 :

Fan motor Indoor temp. sensor Temp. sensor Temp. sensor Louver motor Drain pump motor Float switch Drain control relay

NOTE

Color IdentificationBLK BLU RED GRY PNK GRN : : : : : : BLACK BLUE RED GRAY PINK GREEN WHI BRN ORN YEL : : : : WHITE BROWN ORANGE YELLOW

1. indicates the terminal block. 2. A dotted line and broken line indicate the wiring at site.

Concealed Duct Type RAV-SM560BT-E/RAV-SM800BT-E

TAFS CN030 (RED) 33 22 11 LM CN033 (GRN) 3 2 1 CN068 (BLU) 33 22 11 1 2 3 4 5 6 7 1 2 3 4 5 6 7 YEL 1 1 BLU 2 2 33 44 55 ORN 6 6 BLK 7 7 88 RED 9 9 CN083 (WHI) 1 2 3 4 5 6 7 8 9 UL L M H

TCJ

TC12 12 CN101 (BLK)

12 12 CN104 (YEL)

12 12 CN102 (RED)

RY001

DP1 RED 2 YEL 3 BLU 4 OPN 5 BLK 6 7 BRW 8 9 1 2 3 4 5 6 7 8 9

RY002

FMRC

RY007

FM

1 RED 2 YEL 3 BLU 4 OPN 5 BLK 6 7 BRW 8 9

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7

1 2 3 4 5 6 7

RY 004 123 CN304 (GRY)

(When selecting high-static pressure)

6 5 4 OPTION 3 2 1 CN032 2 FAN (WHI) 1 DRIVE 6 5 CN061 4 (YEL) 3 2 1 33 22 11 CN074 (WHI) TR 66 55 Power 44 RY005 supply RY006 33 circuit 22 11 CN075 (WHI) 6 5 4 3 2 1 CN050 (WHI) Fuse F001 2 2 CN1 33 B T5A 22 A 11 250V~ 11 CN041 Remote (BLU) 123 12345 12 Controller 1 2 3 4 5 CN067 CN066 CN309 (BLK) (WHI) (YEL) RED WHI BLK RED Closed-end connector WHI

123 CN080 (GRN)

PNL

EXCT 1 2

12 12 CN073 CN070 (RED) (WHI) CN060 (WHI)

Indoor unit earth screw

1 2 3 1 2 3 L N

Outdoor unit earth screw

FM : RC : TR : LM : TA : TC,TCJ : : RY001 : RY002 RY005~007 : : DP

Fan motor Running capacitor Transformer Louver motor Indoor temp. sensor Inddor heat exchanger sensor Louver control relay Drain control relay Air volume control relay Drain pump motor

NOTE

Color IdentificationBLK BLU RED GRY PNK GRN : : : : : : BLACK BLUE RED GRAY PINK GREEN WHI BRN ORN YEL : : : : WHITE BROWN ORANGE YELLOW

1. indicates the terminal block. 2. A dotted line and broken line indicate the wiring at site.