2
Ingenieurbüro für Prozessautomatisierung Friedrich Werber Str. 44 · D-78315 Digital Output Board Digital Output Board Power connection layout for Digout-Aqua-PWM1A/16-Aqua on ISSMB1-4IO and Phoenix UM45-FLK40 cable connector adapter (terminal strip)

Upload: debra-joseph

Post on 31-Dec-2015

19 views

Category:

Documents


4 download

DESCRIPTION

Digital Output Board. Power connection layout for Digout-Aqua-PWM1A/16-Aqua on ISSMB1-4IO and Phoenix UM45-FLK40 cable connector adapter (terminal strip). - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Digital Output Board

Ingenieurbüro für ProzessautomatisierungFriedrich Werber Str. 44 · D-78315 Radolfzell/Germany

Digital Output Board Digital Output Board

Power connection layout for Digout-Aqua-PWM1A/16-Aqua on ISSMB1-4IO and

Phoenix UM45-FLK40 cable connector adapter (terminal strip)

Page 2: Digital Output Board

Ingenieurbüro für ProzessautomatisierungFriedrich Werber Str. 44 · D-78315 Radolfzell/Germany

40

38

34

32

30

28

26

24

22

20

18

16

14

12

10

8

6

36

4

2

39

37

33

31

29

27

25

23

21

19

17

15

13

11

9

7

5

35

3

1

1

40

UM 45-FLK40

1

40

Dig

out-

Aqu

a-P

WM

1A/1

6-A

qua

V1.

0

1234

5 - 35 VDC

5 - 35 VDC

GND

GND

} Switch 01 _______________________________________________________________

} Switch 02 _______________________________________________________________

} Switch 03 _______________________________________________________________

} Switch 04 _______________________________________________________________

} Switch 05 _______________________________________________________________

} Switch 06 _______________________________________________________________

} Switch 07 _______________________________________________________________

} Switch 08 _______________________________________________________________

} Switch 09 _______________________________________________________________

} Switch 10 _______________________________________________________________

} Switch 11 _______________________________________________________________

} Switch 12 _______________________________________________________________

} Switch 13 _______________________________________________________________

} Switch 14 _______________________________________________________________

} Switch 15 _______________________________________________________________

} Switch 16 _______________________________________________________________

One to One Connection via flat cable

One of four digout units on ISSMB1-4IO

Jxx / ISSMB1-4IO (xx = 12,15,18,21)

8 switches supplied by pins 1 + 2 of power connector Jxx /ISSMB1-4IO

8 switches supplied by pins 3 + 4 of power connector Jxx /ISSMB1-4IO

Flow fluid sensor in

Cable connector adapter

Ground Ground for 5 VDC or 24 VDC 5 or 24 VDC

1 Power supply for flow fluid sensor

InputNPN 2 Sensor input 5VDC or 24 VDC ( minimum 4mA)

InputPNP 2 Sensor input 5VDC or 24 VDC ( minimum 4mA)

1 5VDC = On Aqua-PiggyBack: R6 is open, R7 is shorted 24VDC = On Aqua-PiggyBack: R6 is shorted, R7 is open

2 NPN = On Aqua-PiggyBack: R8 is shorted PNP = On Aqua-PiggyBack: R8 is open

CAVEAT: Only one sensor (NPN or PNP) is allowed to be connected to Digout-Aqua-PWM1A/16-Aqua