Digital Servo Amplifier

SERVOSTAR® 400

Assembly, Installation, Setup

Edition 07/03

File sr400_d.xxx

Order No.: 102530

Page 2: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

Previous editions

Edition Comments

10/01 First edition

02/02 new layout

07/03 new layout, technical data adapted to new hardware, equipment matching removed

PC-AT is a registered trademark of International Business Machines Corp.

MS-DOS is a registered trademark of Microsoft Corp.

WINDOWS is a registered trademark of Microsoft Corp.

HIPERFACE is a registered trademark of Max Stegmann GmbH

EnDat is a registered trademark of Dr.Johannes Heidenhain GmbH

SERVOSTAR is a registered trademark of Kollmorgen Corporation

Technical changes to improve the performance of the equipment may be made without notice !

Printed in the Federal Republic of Germany

All rights reserved. No part of this work may be reproduced in any form (by printing, photocopying, microfilm or any other

method) or processed, copied or distributed by electronic means without the written permission of Danaher Motion.

Page 3: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

SERVOSTAR®

400 Installation manual 3

Kollmorgen 07/03 Contents

1 General1.1 About this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

1.2 Use as directed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

1.3 Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

1.4 Equipment description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

1.4.1 Package as supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

1.4.2 Digital servo amplifiers in the series SERVOSTAR 400 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

1.4.3 Operation directly from the supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

1.4.4 Digital servo amplifier concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

1.5 Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

1.6 Components of a servo system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

1.7 Technical data for SERVOSTAR 400 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

1.7.1 External fusing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

1.7.2 Permissible ambient conditions, ventilation, mounting position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

1.7.3 Conductor cross-sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

1.7.4 Recommended tightening torques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

1.7.5 LED display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

1.8 Grounding system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

1.9 Motor holding brake conrol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

1.10 Regen circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

1.11 Switch-on/-off behaviour . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

1.11.1 Stop function as per EN 60204 (VDE 0113) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

1.11.2 Emergency stop methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

2 Installation2.1 Important notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

2.2 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

2.2.1 Dimensions SERVOSTAR 400 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

2.3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

2.3.1 Wiring diagram SERVOSTAR 400M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

2.3.2 Wiring diagram SERVOSTAR 400A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

2.3.3 Example of connections for multi-axis system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

2.3.4 Connector assignments SERVOSTAR 400 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

2.3.5 Connection techniques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

2.3.5.1 Shield connection on the front panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

2.3.5.2 Technical data of connecting cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

2.4 Setup software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

2.4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

2.4.1.1 Use as directed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

2.4.1.2 Software description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

2.4.1.3 Hardware requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

2.4.1.4 Operating systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

2.4.2 Installation under WINDOWS 95 / 98 / 2000 / ME / NT / XP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Page

Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

European Directives and Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

-Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Abbreviations and Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Page 4: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

4 SERVOSTAR®

400 Installation manual

Contents 07/03 Kollmorgen

3 Interfaces3.1 Supply voltage (master only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

3.1.1 Supply connection (X0) for 3-phase supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

3.1.2 Supply connection (X0) for single-phase supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

3.1.3 24V auxiliary voltage (X0) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

3.1.4 DC-link/DC-bus (X0) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

3.2 Motor connection with brake (X6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

3.3 External ballast resistor (X0)(master only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

3.4 Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

3.4.1 Resolver connection (X5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

3.4.2 Encoder connection (X2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

3.5 Control and monitoring signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

3.5.1 Analog setpoint input (X3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

3.5.2 Digital control inputs (X3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

3.5.3 Digital control outputs (X3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

3.5.4 Digital control signals on the PSU (X1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

3.6 Encoder emulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

3.6.1 Incremntal encoder interface (X4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

3.6.2 SSI interface (X4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

3.7 RS232 interface, PC connection (X8)(master only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

3.8 Interface for stepper motor controls (pulse/direction) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

3.8.1 Connection of stepper motor controls with 5V signal level (X4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

3.8.2 Connection of stepper motor controls with 24V signal level (X3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

3.9 Interface for master-slave operation, encoder control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

3.9.1 Connection to SERVOSTAR 400 master, 5V level (X4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

3.9.2 Connection to encoder with 24V signal level (X3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

3.9.3 Connection for Sin/Cos encoder (X2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

3.10 Fieldbus connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

3.10.1 CANopen interface (X7) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

3.10.2 PROFIBUS interface (X7)(option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

3.10.3 SERCOS interface (X7)(option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

3.10.3.1 Light emitting diodes (LEDs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

3.10.3.2 Connection diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

4 Commissioning4.1 Important notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

4.2 Parameterization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

4.2.1 Multi-axis systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

4.2.2 Key pad controls and status displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

4.2.2.1 Operating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

4.2.2.2 Status display on the axis module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

4.2.2.3 Status display on the master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

4.3 Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

4.4 Warning messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

5 Accessories5.1 External PSU 24V DC / 5A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

5.2 External PSU 24V DC / 20A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

5.3 External ballast resistor BARxxx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

5.4 Add-on fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

6 Appendix6.1 Transport, storage, maintenace, disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

6.2 Fault-finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

6.3 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

6.4 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Page

Page 5: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

Safety Instructions

� Only properly qualified personnel are permitted to carry out activities such

as transport, installation, commissioning and maintenance. Properly

qualified persons are those who are familiar with the transport, assembly,

installation, commissioning and operation of the product, and who have the

appropriate qualifications for their job. The qualified personnel must know

and observe the following standards and regulations:

IEC 364 and CENELEC HD 384 or DIN VDE 0100

IEC Report 664 or DIN VDE 0110

national accident prevention regulations or BGV A2

� Read this documentation before carrying out the installation and

commissioning. Incorrect handling of the servo amplifier can lead to

personal injury or material damage. It is vital that you keep to the technical

data and information on connection requirements (nameplate and

documentation).

� The manufacturer of the machine must produce a hazard analysis for the

machine and take appropriate measures to ensure that unforeseen

movements do not result in personal injury or material damage.

� The servo amplifiers contain electrostatically sensitive components which

may be damaged by incorrect handling. Discharge your body before

touching the servo amplifier. Avoid contact with highly insulating materials

(artificial fabrics, plastic film etc.). Place the servo amplifier on a conductive

surface.

� Do not open the equipment. Keep all covers and cabinet doors closed during

operation. Otherwise, there are deadly hazards, with the possibility of death,

severe injury or material damage.

� During operation, servo amplifiers may have uncovered live components,

depending on their level of enclosure protection. Control and power

connections may be live, even though the motor is not rotating.

� Servo amplifiers may have hot surfaces during operation. Since the front

panel is used for cooling, it can reach temperatures above 80°C.

� Never undo any electrical connections to the servo amplifier while it is live.

There is a danger of electrical arcing with damage to contacts and personal

injury.

� Wait at least five minutes after disconnecting the servo amplifier from the

main supply power before touching potentially live sections of the

equipment (e.g. contacts) or undoing any connections. Capacitors can still

have dangerous voltages present up to five minutes after switching off the

supply power. To be sure, measure the voltage in the DC-link circuit and wait

until it has fallen below 40V.

SERVOSTAR®

400 Installation manual 5

Kollmorgen 07/03 Safety Instructions

Page 6: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

European Directives and Standards

Servo amplifiers are components that are intended to be incorporated into electrical plant and machines for in-

dustrial use.

When the servoamplifiers are built into machines or plant, the intended operation of the amplifier is forbidden

until it has been established that the machine or plant fulfills the requirements of the EC Machinery Directive

98/37/EG and the EC Directive on EMC (89/336/EEC).

To fulfill the EC Machinery directive (98/37/EG), the following standards have to be applied:

EN 60204-1 (Safety and electrical equipment of machines)

EN 292 (Safety of machines)

The manufacturer of the machine must produce a hazard analysis for the machine and take appropria-

te measures to ensure that unforeseen movements do not result in personal injury or material dama-

ge.

To fulfill the Low Voltage Directive 73/23/EEC, the following standards have to be applied:

EN 60204-1 (Safety and electrical equipment of machines)

EN 50178 (Equipment of high voltage plant with electronic devices)

EN 60439-1 (Low-voltage switchgear and controlgear assemblies)

To fulfill the EC EMC regulations (89/336/EEC), the following standards have to be applied:

EN 61000-6-1 or EN 61000-6-2 (noise immunity within the domestic range/industrial range)

EN 61000-6-3 or EN 61000-6-4 (noise emission within the domestic range/industrial range)

The manufacturer of the machine or plant is responsible for ensuring that they meet the limits required by the

EMC regulations. Advice on the correct installation for EMC – such as shielding, grounding, arrangement of

connectors and cable routing – can be found in this documentation.

The machine / plant manufacturer must examine whether with its machine / plant still further or other

standards or EEC guidelines are to be used.

Conformity

Conformity with the EC Directive on EMC 89/336/EEC and the Low Voltage Directive 73/23/EEC is mandatory

for servoamplifiers supplied within the European Union.

To fulfill the EMC directive, the standard EN 61800-3 is applied.

In the reference to noise immunity the servoamplifier fulfills the requirement to the category second environ-

ment (industrial environment).

For the range of the noise emission the rvo amplifier fulfills the requirement to a product of the category redu-

ced availability.

Warning!

This is a product with reduced availability according to IEC 61800-3. This product can cause in-

terferences within domestic range; if required you must accomplish appropriate measures.

The servo amplifiers have been tested by an authorized testing laboratory in a defined configuration with the

system components which are described in this documentation. Any divergence from the configuration and in-

stallation described in this documentation means that you will be responsible for carrying out new measure-

ments to ensure that the regulatory requirements are fulfilled.

To fulfill the Low Voltage Directive, the standard EN 50178 has to be applied.

6 SERVOSTAR®

400 Installation manual

Directives and Standards 07/03 Kollmorgen

Page 7: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

UL and cUL- Conformance

In preparation

SERVOSTAR®

400 Installation manual 7

Kollmorgen 07/03 UL and cUL- Conformance

Page 8: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

Abbreviations used in this Manual

The abbreviations used in this manual are explained in the table below.

Symbols used in this Manual

danger to personnel

from electricity

and its effects

general warning

general instructions

mechanical hazard

� p. see Page (cross-reference) � special emphasis

Keys on the master:

� press once : move up one menu item, increase number by one

press twice in rapid succession : increase number by ten

press once : move down one menu item, decrease number by one

press twice in rapid succession : decrease number by ten

hold right key pressed, and then press left key as well :

to enter number, Return function

8 SERVOSTAR®

400 Installation manual

Abbreviations and Symbols 07/03 Kollmorgen

Abbrev. Meaning

AGND Analog ground

BTB/RTO Ready to operate

CAN Fieldbus (CANopen)

CE Communité Europeenne (=EC)

CLK Clock signal

COM Serial interface for a PC-AT

DGND Digital ground

DIN Deutsches Institut für Normung

Disk Magnetic storage (diskette, hard disk)

EEPROM Electrically erasable memory

EMC Electromagnetic compatibility

EMI Elektromagnetic interference

EN European standard

ESD Electrostatic discharge

IEC International Electrotechnical Commission

IGBT Insulated gate bipolar transistor

INC Incremental Interface

ISO International Standardization Organization

LED Light-emitting diode

MB Megabyte

MS-DOS Operating system for PC-AT

Abbrev. Meaning

NI Zero pulse

NSTOP Limit-switch input, rot. dir. CCW (left)

PC-AT Personal Computer with 80x86 processor

PELV Protected low voltage

PLC Programmable logic controller

PSTOP Limit-switch input, rot. dir. CW (right)

PWM Pulse-width modulation

RAM Volatile memory

RBallast Ballast (regen) resistor

RBext External ballast (regen) resistor

RBint Internal ballast (regen) resistor

RES Resolver

ROD 426 A quad B Encoder

SRAM Static RAM

SSI Synchronous serial interface

SW/SETP. Setpoint

UL Underwriter Laboratory

V AC AC voltage

V DC DC voltage

VDE Verein deutscher Elektrotechniker

Page 9: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

1 General

1.1 About this manual

This manual describes the digital servo amplifiers of the SERVOSTAR 400 series.

In this manual you can find information about:

� Technical data of the servo amplifiers Chapter I

� Assembly / installation of the servo amplifiers Chapter II

� Interfaces Chapter III

� Commissioning the servo amplifiers Chapter IV

� Accessories for the servo amplifiers Chapter V

� Transport, storage, maintenance, disposal Chapter VI

A more detailed description of the field bus interfaces and the digital connection to automation sys-

tems can be found on the accompanying CD-ROM in PDF format (system requirements: WIND-

OWS 95 or higher, Internet browser, Acrobat Reader 4.0 or higher) in English, German, French and

Italian versions.

You can print out this documentation on any standard printer. A printed copy of the documentation

is available from us at extra cost.

This manual makes the following demands on qualified personnel :

Transport: only by personnel with knowledge of handling electrostatically

sensitive components.

Installation: only by electrically qualified personnel

Commissioning: only by qualified personnel with extensive knowledge of electrical

engineering / drive technology

SERVOSTAR®

400 Installation manual 9

Kollmorgen 07/03 General

Page 10: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

1.2 Use as directed

The servo amplifiers are components which are built into electrical equipment or machines, and can

only be commissioned as integral components of such equipment.

The manufacturer of the machine must produce a hazard analysis for the machine and

take appropriate measures to ensure that unforeseen movements do not result in perso-

nal injury or material damage.

Use the servo amplifiers only on the following types of supply:

1 x 115V AC (only SERVOSTAR 40xM, unearthed operation is permissible)

3 x 115V AC (only SERVOSTAR 40xM, unearthed operation is permissible)

1 x 230V AC (only SERVOSTAR 40xM, unearthed operation is permissible)

3 x 230V AC (all types, unearthed operation is permissible)

3 x 400V AC (only SERVOSTAR 44xM, TN-system or TT-system with earthed

neutral point, max. 5000A symmetrical rated current)

If the servo amplifiers are used in residential areas, or in business or commercial premises, then

additional filter measures must be implemented by the user.

The SERVOSTAR 400 family of servo amplifiers is only intended to drive specific brushless syn-

chronous servomotors with closed-loop control of torque, speed and/or position. The rated voltage

of the motors must be at least as high as the DC-link voltage of the servo amplifier.

The servo amplifiers may only be operated in a closed switchgear cabinet, taking into account the

ambient conditions defined on Page 18. Ventilation or cooling measures may be required to keep

the temperature below 45°C.

Use only copper-cored cables for wiring. The conductor cross-sections can be taken from the Euro-

pean standard EN 60204 (or Table 310-16 of NEC for 60°C or 75°C in the column for AWG

cross-sections).

We can only guarantee that the system will conform to the standards cited on Page 6 if the compo-

nents used are exclusively those supplied by us (servo amplifier, motor, cables etc.).

10 SERVOSTAR®

400 Installation manual

General 07/03 Kollmorgen

Page 11: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

1.3 Nameplate

The nameplate depicted below is attached to the side of the servo amplifier.

The information described below is printed in the individual fields.

1.4 Equipment description

1.4.1 Package as supplied

If you order a SERVOSTAR 400 series amplifier from us, you will receive:

— SERVOSTAR 4xxM (master)

— Mating connectors for X0, X1, X3

— Protective cover for the axis-side (required only once per system)

— Assembly and Installation Instructions

— Setup software DRIVE.EXE and online documentation on CD-ROM

alternatively

— SERVOSTAR 4xxA (axis module)

— Mating connector for X3

— Short-form instructions

The mating SubD connectors are not part of the package supplied!

Accessories: (must be ordered separately if required)

— Electrical add-on fan (for max. 2 axes, required for SERVOSTAR 4x6)

— Synchronous servomotor (linear or rotary)

— Motor lead (pre-assembled), or motor cable as cut-off length + loose connectors

(motor- and amplifier-side)

— Feedback cable (pre-assembled, see also App. Report “Cables & Connectors”) or

Both feedback connectors, loose with feedback cable as cut-off length

— External regen resistor (� p.65)

— Communication cable to PC(� p.45) for parameterizing the master and any

attached axis modules

— Power cable, control cables, fieldbus cables (as lengths)

SERVOSTAR®

400 Installation manual 11

Kollmorgen 07/03 General

Typenbezeichnung

Spannungsversorgung

Model Number

Power Supply

Ser. Nr

Nennstrom

Ser. No.

Nom. Current

Bemerkung

Schutzart

Comment

Encl.Rating

Danaher Motion GmbH & Co. KGWacholderstr. 40-42D-40489 Düsseldorfwww.DanaherMotion.de

Customer ServiceEurope Tel. +49 (0)203 / 99790Italy 3 36 594260North America 1 80 777-3786

Tel. + 9 (0) 2 /Tel. + ( 0)

Instrument codeSerial numberServo amplifier type

Electrical supply,

installed loadOutput current

in S1 operationEnclosure rating

Page 12: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

1.4.2 Digital servo amplifiers in the series SERVOSTAR 400

Standard version

� 2 supply voltage versions: SERVOSTAR 40xM up to 3x230VAC and

SERVOSTAR 44xM up to 3x400VAC

� one size for the master and axis modules each, see Page 25

� shield connection directly on the servo amplifier

� analog input

� fieldbus interface is integrated

(standard: CANopen for integration into CAN bus systems)

� RS232 is integrated

� pulse-direction interface is integrated

Options

� PROFIBUS DP interface instead of CANopen, see page 53

� SERCOS interface instead of CANopen, see page 54

Open architecture

� open hardware and software architecture

� macro language and compiler are integrated

1.4.3 Operation directly from the supply

Supply power (master only)

� operation directly from electrical supply:

1 x 115V AC (SERVOSTAR 40xM only, unearthed operation is permitted)

3 x 115V AC (SERVOSTAR 40xM only, unearthed operation is permitted)

1 x 230V AC (SERVOSTAR 40xM only, unearthed operation is permissible)

3 x 230V AC (all types, unearthed operation is permissible)

3 x 400V AC (SERVOSTAR 44xM only, TN-system or TT-system with

earthed neutral point, max. 5000A sym. rated current)

� fusing (e.g. fusible cutout) provided by the user

Auxiliary voltage 24V DC

� electrically isolated via an external 24V DC PSU, e.g. with isolating transformer

Power input filter

� interference suppression filter for the supply input (for reduced availability according to

EN61800-3) is integrated

� interference suppression filter for the 24V auxiliary supply (for general availability according

to EN 61800-3) is integrated

12 SERVOSTAR®

400 Installation manual

General 07/03 Kollmorgen

Page 13: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

1.4.4 Digital servo amplifier concept

Operation and parameter setting

� with the comfortable setup software, via the serial interface of a PC to a single connection for

all axes in a system

� station address setting through two keys and a 3-digit LED status display on the master

� fully programmable via RS232 interface

Power section

� power supply B6 rectifier bridge, directly off electrical supply

input, integral power input filter and inrush circuit

� all shielding connections directly on the amplifier

� output stage IGBT module with isolated current measurement

Clock frequency can be switched from 8 to 16 kHz with

ASCII command (with power reduction, please contact

our customer support)

� regen (ballast) circuit internal regen resistor as standard,

external regen resistor if required

� DC-link voltage 160...310V DC for SERVOSTAR 40xM

310...560V DC for SERVOSTAR 44xM

160...560V DC for SERVOSTAR 4xxA

Completely digital control

� digital current controller (space vector pulse-width modulation, 62.5 µs)

� freely programmable digital speed controller (62.5 µs or 250 µs)

� integral position controller, with adaptation possibilities for every application (250 µs)

� integrated pulse direction interface, for connection of a servomotor to a stepper-motor con-

trol

� evaluation of the resolver signals or sine/cosine signals from a high-resolution encoder

� encoder emulation (incremental ROD 426-compatible or SSI)

SERVOSTAR®

400 Installation manual 13

Kollmorgen 07/03 General

Page 14: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

Comfort functions

� adjustable setpoint ramps

� 4 programmable digital inputs

(two are normally defined as limit-switch inputs)

� 2 programmable digital outputs

� freely programmable combinations of all digital signals

Integrated safety

� safe electrical separation to EN 50178 between the power input / motor connections and the

signal electronics, provided by appropriate creepage distances and complete electrical isola-

tion

� Soft-start, overvoltage detection, short-circuit protection, phase-failure monitoring

� temperature monitoring of servo amplifier and motor (when using our motors with our pre-as-

sembled cables)

Minimum complexity

� up to 8 axes in a single system

� only one power supply feed and one auxiliary voltage supply per system

� all axes in a system can be parameterized through a single interface

� Strongly reduced wiring expenditure by modular structure

� Simple mechanical structure on DIN rails

14 SERVOSTAR®

400 Installation manual

General 07/03 Kollmorgen

Page 15: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

1.5 Block diagram

SERVOSTAR®

400 Installation manual 15

Kollmorgen 07/03 General

Page 16: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

1.6 Components of a servo system

16 SERVOSTAR®

400 Installation manual

General 07/03 Kollmorgen

24V supply

fuses

drive contactor

terminals

motor

SERVOSTAR 400

PC

Controls / PLC

Page 17: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

1.7 Technical data for SERVOSTAR 400

max. 230VAC max. 400VAC

SERVOSTAR SERVOSTAR

Rated data DIM 403M 406M 403A 406A 443M 446M 403A 406A

Rated supply voltage V~

1 x 115V-10%

to

3 x 230V+10%

3 x 230V-10%

to

3 x 400V+10%

Max. installed load for S1 operation

(in a multi-axis system)kVA 7 — 12 —

Rated DC-link voltage V= 160 - 310 310 - 560

Rated output current (rms value, � 3%, @ 8kHz) Arms 3 6* 3 6* 3 6* 3 6*

Peak output current (max. ca. 5s, � 3%, @ 8kHz) Arms 9 12* 9 12* 9 12* 9 12*

Clock frequency of output stage kHz 8 (can be switched to 16, see page 13)

Technical data of regen circuit — � p.20 — � p.20 —

Overvoltage switch-off threshold V 450 — 750 —

maximum load inductance mH 75 40 75 40 75 40 75 40

minimum load inductance mH 12 7,5 12 7,5 12 7,5 12 7,5

Form factor of the output current

(rated conditions and min. load inductance)— 1.01 1.01

Bandwidth of subordinate current controller kHz > 1.2 > 1.2

Residual voltage drop at rated current V < 5 < 5

Quiescent dissipation, output stage disabled W 12 15 12 15 12 15 12 15

Dissipation at rated current

(without regen dissipation)W 35 60 30 40 35 60 30 40

Internal fusing (for external fusing � p.18)

Auxiliary supply 24V — int. 20 AM—

int. 20 AM—

Regen resistor — electronic electronic

Inputs/outputs

Analog input, 14-bit resolution V �10 �10

common-mode voltage max. V �10 �10

input resistance k� 20 20

Digital control inputs low 0...7 / high 11...30V, 7mA low 0...7 / high 11...30V, 7mA

Digital control outputs, open emitter max. 30V, 10mA max. 30V, 10mA

BTB/RTO output, relay contactsV

DC max. 30,

AC max 42 —

DC max. 30,

AC max 42 —

mA 500 500

Auxiliary supply, electrically isolated,

without brake, without fan

V 20...30—

20...30—

A 0.5 0.5

Auxiliary supply, electrically isolated,

with brake or fan (check voltage drop !)

V24

(-0% +15%) —

24

(-0% +15%) —

A 2.5 2.5

Max. output current for brake A 2 2

Connections

Control signals — Combicon spring terminal

Power supply —Power

Combicon—

Power

Combicon—

Motor — Combicon Combicon

Resolver input — SubD 9-pin (socket) SubD 9-pin (socket)

Incremental encoder input — SubD 15-pin (socket) SubD 15-pin (socket)

PC interface — SubD 9-pin (plug) SubD 9-pin (plug)

Encoder emulation, ROD/SSI — SubD 9-pin (plug) SubD 9-pin (plug)

Mechanical

Weight kg 3 1.7 3 1.7

Height, without connectors mm 230 267* 230 267* 230 267* 230 267*

Width mm 100 50 100 50

Depth, without connectors mm 240 240 240 240

* with add-on ventilation

SERVOSTAR®

400 Installation manual 17

Kollmorgen 07/03 General

Page 18: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

1.7.1 External fusing

Fusible cutouts or similar

AC feed FN1/2/3 16 A slow

24V feed FH1/2 16 A slow

regen resistor FB1/2 6 A slow

1.7.2 Permissible ambient conditions, ventilation, mounting position

Storage temp. / humidity / duration � p.65

Transport temperature / humidity � p.65

Supply voltage tolerances

main power

SERVOSTAR 40xM

SERVOSTAR 44xM

auxiliary supply

w/o brake, w/o fan

with brake or fan

min 1x115V-10% AC / max 1x230V+10%

, 50/60 Hz

min 3x115V-10% AC / max 3x230V+10%

, 50/60 Hz

min 3x230V-10% AC / max 3x400V+10%

, 50/60 Hz

20 VDC ... 30 VDC

24 VDC (-0% +15%)

Ambient temperature in operation0...+45

oC at rated conditions

+45...+55°C with power derating 2.5% / K

Humidity in operation rel. humidity 85%, no condensation

Site altitude

up to 1000m amsl without restrictions

1000...2500m amsl with derating

1.5% / 100m

Pollution level Pollution level 2 as per EN 60204 / EN 50178

Enclosure rating IP 20

Mounting position normally vertical � p.24

Ventilationfree convection for SERVOSTAR4x3,

add-on fan (� p.66) required for SERVOSTAR4x6

Make sure that there is adequate forced ventilation within the closed switchgear cabinet.

1.7.3 Conductor cross-sections

Following EN 60204-1, we recommend for single-axis systems:

AC connection 4 mm², depending on the system fusing

Motor cables 1 mm², shielded, capacitance <150pF/m, max. 25m

Resolver, motor thermostat4x2x0.25 mm², twisted pairs, shielded, max.100m,

capacitance <120pF/m

Encoder, motor thermostat7x2x0.25 mm², twisted pairs, shielded, max. 50m,

capacitance <120pF/m

Analog signals 0.25 mm² , twisted pairs, shielded

Control signals, BTB, DGND 0.5 mm²

Holding brake (motor) 0.75 mm², shielded, check voltage drop

+24 V / XGND max. 2.5 mm², check voltage drop

Technical data for connecting cables � p.33. Please note our Application Report “Cables & Connectors”.

1.7.4 Recommended tightening torques

Connector Tightening torque

X1, X3, X6 0.3 Nm

X0 1.3 Nm

Earthing bolts 3.5 Nm

lower mounting bolt 3,5 Nm

18 SERVOSTAR®

400 Installation manual

General 07/03 Kollmorgen

Page 19: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

1.7.5 LED display

A 3-digit LED display indicates the amplifier status after switching on the 24V supply

(� p.59). The address can be read out while it is being set on the master by using the keys.

1.8 Grounding system

AGND – ground reference for analog signals, internal analog ground

DGND – ground reference for digital signals and auxiliary supply voltage, optically isolated

The electrical isolation is indicated in the block diagram (� p.15).

1.9 Motor holding brake conrol

A motor holding brake (24V / max.1,5A) can be controlled directly by the servo amplifier. This

function does not ensure personnel safety! The brake function must be enabled through the

BRAKE parameter (on the screen page for Motor): the setting is WITH. In the diagram below you

can see the timing and functional relationships between the ENABLE signal, speed setpoint, speed

and braking force.

During the internal ENABLE delay time of 100ms the speed setpoint of the servo amplifier is inter-

nally driven down a 10ms ramp to 0V. The brake output is switched on when 3% of the final speed

is reached, at the latest after 1 second.

The rise (fbrH) and fall (fbrL) times of the holding brakes that are built into the motors vary for the dif-

ferent types of motor (see motor manual).

A description of the interface can be found on Page 38.

Personnel-safe operation of the holding brake requires an additional “make” contact in the brake cir-

cuit and a spark suppressor device (e.g. a varistor) in the recommended brake circuit:

SERVOSTAR®

400 Installation manual 19

Kollmorgen 07/03 General

SERVOSTAR

Page 20: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

1.10 Regen circuit

During braking with the aid of the motor, energy is fed back to the servo amplifier. This energy is

converted into heat in the regen resistor (ballast resistor). The regen resistor is switched in and out

by the regen circuit. The switching thresholds for the regen circuit are adjusted to suit the supply

voltage with the aid of the setup software.

Our customer support can help you with the calculation of the regen power which is required. A des-

cription of the interface can be found on Page 39 .

Internal regen resistor 33 �

External regen resistor 33 �

Functional description

The regen circuit starts to respond when the DC-link voltage reaches the set value.

If the energy which is fed back from the motor, as an average over time or as a

peak value, is higher than the preset regen power, then the servo amplifier will

output the status regen power exceeded and the circuit will be switched off.

At the next internal check of the DC-link voltage (after a few milliseconds) an

overvoltage will be detected and the servo amplifier will be switched off, with the

error message overvoltage (� p.60).

The BTB/RTO contact (terminals X1/1,2) will be opened simultaneously (� p.44).

Technical data: regen circuit

Supply voltage Rated data DIM Value

3 x 230 V

Upper switch-on threshold for regen circuit V 400

Switch-off threshold for regen circuit V 380

Continuous int. power in regen circuit (RBint) W 55

Continuous ext. power in circuit (RBext) max. kW 0,4

Pulse power, internal (RBint max. 1s) kW 4.8

Pulse power, external (RBext max. 1s) kW 4.8

External regen resistor � 33

3 x 400 V

Upper switch-on threshold for regen circuit V 720

Switch-off threshold for regen circuit V 680

Continuous int. power in regen circuit (RBint) W 80

Continuous ext. power in circuit (RBext) max. kW 0,6

Pulse power, internal (RBint max. 1s) kW 16

Pulse power, external (RBext max. 1s) kW 16

External regen resistor � 33

20 SERVOSTAR®

400 Installation manual

General 07/03 Kollmorgen

Page 21: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

1.11 Switch-on/-off behaviour

The diagram below illustrates the correct functional sequence for switching the servo amplifier on

and off.

1.11.1 Stop function as per EN 60204 (VDE 0113)

If a fault occurs (� p.60), the output stage of the servo amplifier is switched off and the BTB/RTO

contact is opened. In addition, a global error signal can be given out at one of the digital outputs

(terminals X3/8 and X3/9) (see the Online help in the setup software, or the manual for the setup

software). These signals can be used by the higher-level control to terminate the current PLC cycle

or to shut down the drive (through an additional brake or similar means).

Instruments with a selected Brake function use a special sequence for switching off the output stage

(� p.19).

The Stop functions are defined in EN 60204 (VDE 0113), Paras. 9.2.2 and 9.2.5.3.

There are three categories of Stop functions:

Category 0: Shut down by immediate switch-off of the supply of energy to the

drive machinery (i.e. an uncontrolled shut-down)

Category 1: A controlled shut-down, during which the supply of energy to the

drive machinery is maintained to perform the shut-down, and where

the supply is only interrupted when standstill has been reached

Category 2: A controlled shut-down, where the supply of energy to the drive

machinery is maintained

Every machine must be equipped with a Stop function to Category 0.

Categories 1 and/or 2 must be provided if the safety or functional requirements of the machine

make this necessary.

SERVOSTAR®

400 Installation manual 21

Kollmorgen 07/03 General

Page 22: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

1.11.2 Emergency stop methods

The Emergency Stop function is defined in EN 60204 (VDE 0113), Para. 9.2.5.4.

Implementation of the Emergency Stop function :

You can find wiring recommendations in our application note

“Stop and Emergency Stop functions with SERVOSTAR”

Category 0:

The amplifier is disabled, the electrical supply is disconnected.

The drive must be held by an electromagnetical clamping device (brake).

In multi-axis systems (several SERVOSTAR 400-systems or combinations of

SERVOSTAR 400 and SERVOSTAR 600) using a coupled DC-link (= DC bus) the motor

cable must also be disconnected by a changeover switch (a contactor, such as Siemens

type 3RT1516-1BB40) and short-circuited by resistors wired in a star configuration.

Category 1:

If hazardous conditions can result from an Emergency Stop disconnection,

because of an unbraked run-down, then the drive can be switched off by a

controlled shut-down.

Stop Category 1 permits electromotive braking with a switch-off when zero

speed has been reached.

Safe shut-down can be achieved if the disappearance of the supply power is not

evaluated as a fault, but the control system takes on the task of disabling the

amplifier.

In the normal situation only the main supply power is switched off in a safe

manner. The 24V auxiliary supply remains switched on.

22 SERVOSTAR®

400 Installation manual

General 07/03 Kollmorgen

Page 23: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

2 Installation

2.1 Important notes

� Protect the servo amplifier from impermissible stresses. In particular, do not let any compo-

nents become bent or any insulation distances altered during transport and handling. Avoid

contact with electronic components and contacts.

� Check the combination of servo amplifier and motor (� p.72). Compare the rated voltage

and current of the units. Carry out the wiring according to the instructions on Page 26.

� Make sure that the maximum permissible rated voltage at the terminals for L1, L2, L3 and

+RBext, –DC is not exceeded by more than 10%, even in the most unfavourable conditions

(see EN 60204-1 Section 4.3.1). An excessive voltage on these terminals can lead to de-

struction of the regen circuit and the servo amplifier.

Use the SERVOSTAR 44x only on an earthed 3-phase supply system. Use the amplifier only

to drive a synchronous servomotor.

� The fusing of the AC supply input and the 24V supply is installed by the user (� p.18).

� Take care that the servo amplifier and motor are properly earthed. Do not use painted

(non-conductive) mounting plates.

� Route power and control cables separately. We recommend a separation of at least 20 cm.

This improves the interference immunity required by EMC regulations. If a motor power ca-

ble is used which includes cores for brake control, the brake control cores must be sepa-

rately shielded.

Earth the shielding at both ends (� p.28).

� Install all heavy-current cables with an adequate cross-section, as per EN 60204-1

(� p.18).

� Wire the BTB/RTO contact in series into the safety circuit of the installation.

Only in this way is the monitoring of the servo amplifier assured.

� Install all shielding with large area (low impedance) connections, with metallised connector

housings or shield connection clamps where possible.

Notes on connection techniques can be found on Page 32 and the Application Note “Cables

& Connectors”.

� Ensure that there is an adequate flow of cool, filtered air into the bottom of the switchgear

cabinet. Note the conditions on Page 18 .

� It is permissible to alter the servo amplifier settings by using the operator software.

Any other alterations will invalidate the warranty.

Caution

Never disconnect the electrical connections to the servo amplifier while it is live.

In unfavourable circumstances this could result in destruction of the electronics.

Residual charges in the capacitors can have dangerous levels up to 300 seconds after

switching off the mains supply voltage. Measure the voltage in the DC-link

(+RBext/-DC) and wait until the voltage has fallen below 40V.

Control and power connections can still be live, even when the motor is not rotating.

SERVOSTAR®

400 Installation manual 23

Kollmorgen 07/03 Installation

Page 24: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

2.2 Mounting

Material: 2 mounting rails to EN60715, min. length = system width + 40mm,

make sure there is a conductive connection to the mounting plate

Mount the protective cover (7mm) on the left side of the system.

Tools required: Screwdriver with approx. 5 mm blade width

24 SERVOSTAR®

400 Installation manual

Installation 07/03 Kollmorgen

SERVOSTAR 400

60715

Page 25: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

2.2.1 Dimensions SERVOSTAR 400

SERVOSTAR®

400 Installation manual 25

Kollmorgen 07/03 Installation

SERVOSTAR 400M

SERVOSTAR 400A

Page 26: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

2.3 Wiring

Only professional staff who are qualified in electrical engineering are allowed to install the

servo amplifier.

The installation procedure is described as an example. A different procedure may be appropriate or

necessary, depending on the application of the equipment.

We provide further know-how through training courses (on request).

Caution !

Only install and wire up the equipment when it is not live, i.e. when neither the mains

power supply nor the 24 V auxiliary voltage nor the operating voltages of any other

connected equipment is switched on.

Take care that the cabinet is safely disconnected (with a lock-out, warning signs etc.).

The individual voltages will be switched on for the first time during commissioning.

Note !

The ground symbol�, which you will find in all the wiring diagrams, indicates that

you must take care to provide an electrically conductive connection with the largest

possible area between the unit indicated and the mounting plate in the switchgear cabi-

net. This connection is for the effective grounding of HF interference, and must not be

confused with the PE symbol � (protective earth to EN 60204).

Use the following wiring and connection diagrams :

— Power and control connections : Page 28

— Multiaxis systems : Page 30

— Resolver : Page 39

— High-resolution encoder : Page 40

— Encoder emulation ROD : Page 45

— Encoder emulation SSI : Page 46

— RS232 / PC : Page 45

— Pulse/direction interface : Page 48

— Master/slave interface : Page 50

— CAN interface : Page 52

— PROFIBUS interface : Page 53

— SERCOS interface : Page 54

26 SERVOSTAR®

400 Installation manual

Installation 07/03 Kollmorgen

Page 27: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

The following notes should assist you to carry out the installation in a sensible sequence, without

overlooking anything important.

In a closed switchgear cabinet. Observe Page 18 .

The site must be free from conductive or corrosive materials.

For the mounting position within the cabinet� p.24

Check that the ventilation of the servo amplifier is unimpeded and keep

within the permitted ambient temperature� p.18 .

Keep the required space clear above and below the servo amplifier

� p.24.

Mount the servo amplifier on mounting rails (DIN-rails) on the conduc-

tive, earthed mounting plate in the cabinet.

Select cables according to EN 60204-1,� p.18

EMC-conform shielding and grounding (� p.28)

Earth the mounting plate, motor housing and CNC-GND of the con-

trols.Notes on connection techniques are on Page 32

— Route power leads separately from control cables

— Wire the BTB/RTO contact in series into the safety loop of the

installation

— Connect the digital control inputs to the servo amplifier

— Connect up AGND

— Connect the analog setpoint, if required

— Connect the feedback unit (resolver or encoder)

— If required, connect the encoder emulation

— If required, connect the fieldbus

— Connect the motor cable

— Connect shielding to EMC connectors at the motor end, and the

— shielding lug at the amplifier end

— Connect motor-holding brake, with shielding to EMC connector at

— the motor end, and to shielding lug at the amplifier end

— If required, connect the external regen resistor (with fusing)

— Connect the auxiliary supply

— (maximum permissible voltages� p.18)

— Connect main power supply

— (maximum permissible voltages� p.18)

— Connect PC (� p.45).

Make a final check of the wiring carried out against the wiring diagrams

that have been used

SERVOSTAR®

400 Installation manual 27

Kollmorgen 07/03 Installation

Site

Ventilation

Mounting

Grounding,

Shielding

Cable selection

Check

Wiring

Page 28: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

2.3.1 Wiring diagram SERVOSTAR 400M

28 SERVOSTAR®

400 Installation manual

Installation 07/03 Kollmorgen

� p.37

� p.52

� p.45

� p.50

� p.38

� p.40

� p.39

� p.41

� p.42

� p.43

� p.44

� p.38

� p.39

SERVOSTAR 400MFollow the safety instructions (� p.5)

and the use as directed (� p.10) !

Page 29: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

2.3.2 Wiring diagram SERVOSTAR 400A

SERVOSTAR®

400 Installation manual 29

Kollmorgen 07/03 Installation

� p.52

� p.50

� p.38

� p.40

� p.39

� p.41

� p.42

� p.43

SERVOSTAR 400AFollow the safety instructions (� p.5)

and the use as directed (� p.10) !

Page 30: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

2.3.3 Example of connections for multi-axis system

30 SERVOSTAR®

400 Installation manual

Installation 07/03 Kollmorgen

SERVOSTAR 400A

SERVOSTAR 400A

SERVOSTAR 400M

MM

M

Follow the safety instructions (� p.5)

and the use as directed (� p.10) !

Page 31: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

2.3.4 Connector assignments SERVOSTAR 400

SERVOSTAR®

400 Installation manual 31

Kollmorgen 07/03 Installation

Page 32: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

2.3.5 Connection techniques

Please consult our application note “Cables & Connectors”.

2.3.5.1 Shield connection on the front panel

32 SERVOSTAR®

400 Installation manual

Installation 07/03 Kollmorgen

The pre-assembled cables for

SERVOSTAR 400 are provided

with an overall metal ferrule at the

amplifier end that is electrically

connected to the shielding.

Thread a cable tie through each slot

in the shielding strip (front panel) of

the servo amplifier.

Tighten up the cable ties so that the

shielding ferrule and the sheathing

of the cable is pressed down tightly

against the shielding strip.

SERVOSTAR400

SERVOSTAR400

Page 33: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

2.3.5.2 Technical data of connecting cables

Further information on the chemical, mechanical and electrical characteristics of the cables can be

obtained from our customer support.

Insulation material

Sheathing PUR (polyurethane, code 11Y)

Core insulation PETP (polyesteraphthalate, code 12Y)

Capacitance

Motor cable less than 150 pF/m

RES/encoder cable less than 120 pF/m

Technical data

— The brackets in the cable designation indicate the shielding.

— All cables are suitable for use as trailing cables.

— The technical data refer to the use as moveable cables.

operating life : 1 million bending cycles

— The permissible operating temperature range is from -30°C to +80°C.

— All cables are colour-coded according to IEC 757.

Cores

[mm²]

External diameter

[mm]

Bending radius

[mm]Remarks

(4x1.0) 10 100 Motor cable

(4x1.0+(2x0.75)) 10.5 100Motor cable with extra cores

for controls

(4x2x0.25) 6.9 60

twisted pairs(7x2x0.25) 9.9 80

(10x2x0.14) 8.8 80

SERVOSTAR®

400 Installation manual 33

Kollmorgen 07/03 Installation

Page 34: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

This page has been deliberately left blank.

34 SERVOSTAR®

400 Installation manual

Installation 07/03 Kollmorgen

Page 35: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

2.4 Setup software

2.4.1 General

This chapter describes the installation of the setup software DRIVE.EXE for the SERVOSTAR 400

digital servo amplifiers.

We offer training and familiarization courses on request.

2.4.1.1 Use as directed

The operator software is intended to be used for altering and storing the operating parameters for

the SERVOSTAR 400 series of servo amplifiers. The attached servo amplifier is commissioned with

the assistance of the software - during this process the drive can be controlled directly by the ser-

vice functions.

Only professional personnel who have the relevant expertise described on Page 9 are

permitted to carry out online parameter setting for a drive which is running.

Sets of data which are stored on data media are not safe against unintended alteration

by other persons. After loading a set of data you must therefore check all parameters

thoroughly before enabling the servo amplifier.

2.4.1.2 Software description

The servo amplifiers must be adapted to the requirements of your installation. Usually you will not

have to carry out this parameter setting yourself on the amplifier, but on a PC, with the assistance of

the operator software. The PC is connected to the servo amplifier by a null-modem (serial) cable.

The setup software provides the communication between the PC and SERVOSTAR 400.

You will find the setup software on the accompanying CD-ROM and in the download section of the

Danaher Motion web appearance.

With very little effort you can alter parameters and immediately observe the effect on the drive,

since there is a continuous (online) connection to the amplifier. At the same time, important actual

values are read out from the amplifier and displayed on the PC monitor (oscilloscope function).

Any interface modules which may be built into the amplifier are automatically recognized, and the

additional parameters which are required for position control or motion-block definition are made

available.

Sets of data can be stored on data media (archived) and loaded again. You can also print out the

data sets.

We provide you with motor-specific default sets of data for all the reasonable combinations of servo

amplifier and motor. In most applications you will be able to use these default values to get your

drive running without any problems.

SERVOSTAR®

400 Installation manual 35

Kollmorgen 07/03 Installation

Page 36: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

2.4.1.3 Hardware requirements

The PC interface (X6, RS232) of the master is connected to a serial interface on the PC by a

null-modem cable (not a null-modem link cable !) (� p.45).

Connect / disconnect the interface cable only when the supply is switched off for both

the PC and the servo amplifier.

The interface in the servo amplifier is electrically isolated by an optocoupler, and is at the same

potential as the CANopen interface.

Minimum requirements for the PC:

Processor : 80486 or higher

Operating system : WINDOWS 95(c) / 98 /2000 / ME, WINDOWS NT4.0 / XP

Graphica adapter : Windows compatible, color

Drives : Diskette drive 3.5"

Hard disk (5 MB free space)

CD-ROM drive

Main memory : at least 8MB

Interface : one free serial interface (COM1:, 2:, 3: or 4:)

2.4.1.4 Operating systems

WINDOWS 95(c) / WINDOWS 98 / WINDOWS 2000 / WINDOWS ME / WINDOWS NT / XP

DRIVE.EXE can run under WINDOWS 95c / 98 / 2000 / ME / XP or WINDOWS NT 4.0.

The help system can not be used under Windows 95a and 95b.

WINDOWS FOR WORKGROUPS 3.xx, DOS, OS2, Unix, Linux

DRIVE.EXE does not run under WINDOWS 3.xx, DOS, OS2, Unix and Linux.

Emergency operation is possible with an ASCII terminal-emulation (without user interface).

Interface setting: 9600 bps, no parity, no handshake

2.4.2 Installation under WINDOWS 95 / 98 / 2000 / ME / NT / XP

The CD-ROM includes an installation program called SETUP.EXE that makes it easier to install the

setup software on your PC.

Connection to the serial interface of the PC:

Connect the interface cable to a serial interface on your PC and the PC interfaces (X8) of the

SERVOSTAR 400 (� p.45).

Switch-on:

Switch on your PC-AT and the monitor.

After the start phase (boot-up) is finished, the Windows user-interface appears on the screen.

Installation:

Click on START (task bar), then on Run.

Enter the program call x:\setup.exe (where x= is the drive letter for the CD drive).

Click on OK and follow the instructions.

Setting up the graphics card (font size)

Click on the desktop with the right mouse button. The dialogue window “Properties” will appear.

Select the file card “Settings”. Set the Font size to “Small Fonts”. Follow the instructions provided

by the system.

36 SERVOSTAR®

400 Installation manual

Installation 07/03 Kollmorgen

Page 37: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3 Interfaces

This chapter presents all the important interfaces, divided between master and axis module. The

precise location of the connectors and terminals can be seen on Page 31.

3.1 Supply voltage, master only

3.1.1 Supply connection (X0) for 3-phase supplies

Directly to earthed supply, filter is integrated, fusing (e.g. fusible cut-outs) to be provided by the user

� p.18

3.1.2 Supply connection (X0) for single-phase supplies

Directly to supply, filter is integrated, fusing (e.g. fusible cut-outs) to be provided by the user� p.18

SERVOSTAR®

400 Installation manual 37

Kollmorgen 07/03 Interfaces

SERVOSTAR 400

SERVOSTAR 400

for SERVOSTAR40xM

for SERVOSTAR44xM

for SERVOSTAR40xM

Page 38: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.1.3 24V auxiliary voltage (X0)

— Electrically isolated supply from an external 24V DC PSU, e.g. with isolating transformer

— Required current rating� p.17

— Integrated EMC filter for the 24V auxiliary supply

3.1.4 DC-link/DC-bus (X0)

Can be connected in parallel with further, identical masters (via terminals -DC and RBext).

3.2 Motor connection with brake (X6)

Max. admisible length of the motor cable is 25 m.

38 SERVOSTAR®

400 Installation manual

Interfaces 07/03 Kollmorgen

SERVOSTAR 400

SERVOSTAR 400

Page 39: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.3 External ballast resistor (X0), master only

Remove the plug-on link between terminals X0/5 (-RB) and X0/4 (+Rbint).

3.4 Feedback

3.4.1 Resolver connection (X5)

Our rotary servomotors have 2-pole hollow-shaft resolvers built in as a standard.

It is possible to connect 2- to 32-pole resolvers to SERVOSTAR 400.

If lead lengths of more than 25m are planned, please consult our customer support.

The thermostat contact in the motor is connected via the resolver cable to the SERVOSTAR 400

and evaluated there.

SERVOSTAR®

400 Installation manual 39

Kollmorgen 07/03 Interfaces

SERVOSTAR 400

SERVOSTAR 400SubD9 12-pin round

Page 40: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.4.2 Encoder connection (X2)

As an option, the motors can be fitted with a single-turn or multiturn sine-cosine encoder. Preferred

types are the ECN1313 and EQN1325 encoders.

The encoder is used by the SERVOSTAR 400 as a feedback device for drive tasks that require

highly precise positioning or extremely smooth running.

If lead lengths of more than 25m are planned, please consult our customer support.

The thermostat contact in the motor is connected via the encoder cable to the SERVOSTAR 400

and evaluated there.

40 SERVOSTAR®

400 Installation manual

Interfaces 07/03 Kollmorgen

SERVOSTAR 400 SubD15 17-pin round

Page 41: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.5 Control signals

3.5.1 Analog setpoint input (X3)

The servo amplifier has a programmable input for analog setpoints.

AGND (X3/1) must always be joined to the CNC-GND of the controls to provide a ground reference.

Technical data

— Input voltage max. ± 10 V

— Resolution 1.25 mV

— Ground reference AGND, terminal X3/1

— Input resistance 20 k�

— Common mode voltage range for both inputs ± 10 V supplementary

Analog input (terminals X3/2-3)

Input voltage max. ± 10 V, 14-bit resolution, scalable

Standard setting speed setpoint

Fixing the direction of rotation

Standard setting clockwise rotation of the motor shaft (looking at shaft end)

with positive voltage on terminal X3/3 (+ ) against X3/2 ( - )

To reverse the direction of rotation you can swap the connections to terminals X3/2-3 or change the

DIRECTION parameter in the SPEED screen.

SERVOSTAR®

400 Installation manual 41

Kollmorgen 07/03 Interfaces

SERVOSTAR 400

Page 42: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.5.2 Digital control inputs (X3)

All digital inputs are electrically isolated through optocouplers.

Technical data

— Reference ground is digital-GND (DGND, terminal X1/4,5 on the master)

— The logic is dimensioned for +24V / 7mA (PLC-compatible)

— H-level from +12...36V / 7mA, L-level from 0...7V / 0 mA

You can use the digital inputs PSTOP / NSTOP / DIGITAL-IN1 and DIGITAL-IN2 to initiate pre-pro-

grammed functions that are stored in the servo amplifier.

You will find a list of the pre-programmed functions in the Online Help.

If an input has to be re-assigned to a pre-programmed function, then the data set must be stored in

the EEPROM of the servo amplifier, and the 24V auxiliary supply for the servo amplifier must be

switched off and then on again (to reset the amplifier software).

Limit-switches PSTOP / NSTOP

Terminals X3/6 and X3/7 are normally programmed for the connection of limit switches.

If these inputs are not needed for the connection of limit switches, then they can be used for other

input functions.

Limit-switch positive/negative (PSTOP / NSTOP, terminals X3/6 and X3/7), high level in normal

operation (fail-safe for cable break).

A low signal (open) inhibits the corresponding direction of rotation, the ramp functions remain

effective.

DIGITAL-IN 1 / DIGITAL-IN 2

You can link the digital inputs at terminals X3/4 (DIGITAL-IN 1) and X3/5 (DIGITAL-IN2) with a

pre-programmed function.

42 SERVOSTAR®

400 Installation manual

Interfaces 07/03 Kollmorgen

SERVOSTAR 400

Page 43: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.5.3 Digital control outputs (X3)

Technical characteristics

— Ground reference is Digital-GND (DGND, terminal X1/4,5 on the master)

— Alle digital outputs are floating

— DIGITAL-OUT1 and 2 : Open-collector, max. 30V DC, 10mA

Programmable digital outputs DIGITAL-OUT 1 / 2:

You can use the digital outputs DIGITAL-OUT1 (terminal X3/8) and DIGITAL-OUT2

(terminal X3/9) to output messages from pre-programmed functions that are stored in the servo

amplifier.

A list of the pre-programmed functions can be found in the Online Help.

If an input is freshly assigned to a pre-programmed function, then the data set must be stored in the

EEPROM of the servo amplifier, and the 24V auxiliary supply of the servo amplifier must be swit-

ched off and on again (to reset the amplifier software).

SERVOSTAR®

400 Installation manual 43

Kollmorgen 07/03 Interfaces

SERVOSTAR 400

Page 44: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.5.4 Digital control signals on the PSU (X1)

Technical characteristics

— Ground reference is Digital-GND (DGND, terminal X1/4,5)

— The logic is dimensioned for +24V / 7mA (PLC-compatible)

— H-level from +12...36V / 7mA, L-level from 0...7V / 0 mA

BTB/RTO: Relay output, max. 30V DC or 42V AC, 0.5A

ENABLE input

The output stage of the servo amplifier is activated by the enable signal

(terminal X1/3, input 24V, active-high).

In the inhibited state (low signal) the motor which is attached does not have any torque.

Ready-to-operate contact BTB/RTO

Operational readiness (terminals X1/1 and X1/2 ) is signalled via a floating relay contact.

The contact is closed when all servo amplifiers in the system are ready for operation. This signal is

not influenced by the enable signal, the I²t- limit, or the regen threshold.

All faults cause the BTB/RTO contact to open and the output stage to switch off

A list of the error messages can be found on Page 60.

44 SERVOSTAR®

400 Installation manual

Interfaces 07/03 Kollmorgen

SERVOSTAR 400

Page 45: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.6 Encoder emulations

3.6.1 Incremental encoder interface (X4)

The incremental-encoder interface is part of the package supplied.

Select the encoder function ROD (screen page Encoder).

In the servo amplifier, the position of the motor shaft is calculated from the cyclic-absolute signals of

the resolver or encoder.

This information is used to generate incremental-encoder compatible pulses.

Pulses are output on the SubD-connector X4 as two signals, A and B, with 90° phase difference

and a zero pulse.

The resolution can be changed with the ENCOUT parameter:

32/64/128/256/512/1024 pulses per turn for Feedback=Resolver

2048/4096 pulses per turn for Feedback=EnDat or HIPERFACE

8192 pulses per turn for Feedback=EnDat or HIPERFACE up to 3000 rpm

16384 pulses per turn for Feedback=EnDat or HIPERFACE up to 1500 rpm

You can also adjust and store the position of the zero pulse within one mechanical turn

(parameter NI-OFFSET). Because of the compatibility with normal commercial pulse encoders, you

can only set the zero pulse when A=B=1.

The ground reference for the interface is AGND.

This must always be connected to the ground for the control input signals.

Connections and signal description for the incremental-encoder interface :

SERVOSTAR®

400 Installation manual 45

Kollmorgen 07/03 Interfaces

SERVOSTAR 400

Page 46: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.6.2 SSI interface (X4)

The SSI interface (synchronous serial absolute-encoder emulation) is part of the package delivered.

Select the encoder function SSI (screen page Encoder).

In the servo amplifier, the position of the motor shaft is calculated from the cyclic-absolute signals of

the resolver or encoder. The information is used to generate a position output compatible with the

data format of normal commercial SSI absolute encoders. This synchronous-serial, cyclic-absolute

12-bit information is output on the SubD-Connector X4.

24 bits are transmitted. The upper 12 bits are fixed at ZERO, the lower 12 bits contain the position

information.

The interface must be read in as a multi-turn encoder, but delivers valid single-turn data. The signal

sequence can be output in Gray code (standard) or in binary code (parameter SSI-CODE).

A serial signal is read out from the control, with a synchronous clock frequency of max. 1.5 MHz.

The servo amplifier can be adjusted to the clock frequency of your SSI-evaluation with the

SSI-CLOCK parameter (200 kHz or 1.5MHz and inverted).

The ground reference for the interface is AGND.

This must always be connected to the ground for the control input signals.

Connections and signal description for the SSI interface :

The count direction for the SSI interface is upwards when the motor shaft is rotating clockwise (loo-

king at the shaft end).

46 SERVOSTAR®

400 Installation manual

Interfaces 07/03 Kollmorgen

SERVOSTAR 400

Page 47: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.7 RS232 interface, PC connection (X8), master only

The setting of the operating, position control, and motion-block parameters, can be carried out by

using the setup software on an ordinary commercial PC.

Connect the PC interface (X8) of the servo amplifier while the supply to the equipment is swit-

ched off via a null-modem cable to a serial interface on the PC (do not use a null-modem link

cable!).

The interface has the same potential as the internal logic, and uses AGND as the ground reference.

The interface is selected and set up in the setup software.

Further notes can be found on Page 35 .

Interface cable between the PC and servo amplifiers of the SERVOSTAR 400 series:

(View: front view of the built-in SubD connectors, this corresponds to looking at the solder side of

the SubD connector on the cable.)

SERVOSTAR®

400 Installation manual 47

Kollmorgen 07/03 Interfaces

SERVOSTAR 400

Page 48: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.8 Interface for stepper motor controls (pulse/direction)

This interface can be used to connect the servo amplifier to a third-party stepper-motor controller.

The parameters for the servo amplifier are set up with the aid of the setup software (electrical gea-

ring). The number of steps can be adjusted, so that the servo amplifier can be adjusted to the

pulse/direction signals of any stepper-motor controller. Various monitoring signals can be output.

The analog input is inactive.

AGND (terminal X3/1) must be connected to the ground of the control system! Observe the

limit frequency!

Speed profile and signal diagram

Note:

Encoder Input A quad B offers more EMI supression.

48 SERVOSTAR®

400 Installation manual

Interfaces 07/03 Kollmorgen

Page 49: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.8.1 Connection of stepper motor controls with 5V signal level (X4)

You can use this interface to connect the servo amplifier to a stepper motor control with a 5V signal

level. The SubD connector X4 is used for this purpose.

Limit frequency: 1 MHz

AGND (terminal X3/1) must be connected to the ground of the control system!

3.8.2 Connection of stepper motor controls with 24V signal level (X3)

You can use this interface to connect the servo amplifier to a stepper motor control with a 24V sig-

nal level. The digital inputs DIGITAL-IN 1 and 2 on connector X3 are used for this purpose.

Limit frequency: 100 kHz

AGND (terminal X3/1) must be connected to the ground of the control system!

SERVOSTAR®

400 Installation manual 49

Kollmorgen 07/03 Interfaces

SERVOSTAR 400

SERVOSTAR 400

Page 50: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.9 Interface for master-slave operation, encoder control

This interface can be used to link several SERVOSTAR 400 amplifiers in master-slave operation.

The parameters for the slave amplifier are set up with the aid of the setup software (electrical gea-

ring). The resolution (no. of pulses/turn) can be adjusted. The analog setpoint input is inactive.

AGND (terminal X3/1) must be connected to the ground of the control system! Observe the

limit frequency!

Please contact our customer support for information on connecting external SSI encoders.

Signal diagram (for encoders with RS422 or 24V outputs)

3.9.1 Connection to SERVOSTAR 400 master, 5V level (X4)

This interface can be used to link several SERVOSTAR 400 amplifiers in master-slave operation.

Up to 16 slave amplifiers can be controller by the master via the encoder output. The SubD connec-

tor X4 is used for this purpose.

Limit frequency: 1 MHz, transition speed tv � 0.1µsec

AGND (terminal X3/1) must be connected to the ground of the control system!

50 SERVOSTAR®

400 Installation manual

Interfaces 07/03 Kollmorgen

SERVOSTAR 400 SERVOSTAR 400

Page 51: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.9.2 Connection to encoder with 24V signal level (X3)

You can use this interface to set up the SERVOSTAR 400 as a slave following an encoder with a

24V signal level (master-slave operation). This application uses the digital inputs DIGITAL-IN 1 and

2 on connector X3.

Limit frequency: 100 kHz, transition speed tv � 0.1µsec

AGND (terminal X3/1) must be connected to the ground of the control system!

3.9.3 Connection for Sin/Cos encoder (X2)

You can use this interface to set up the SERVOSTAR 400 as a slave following a sine/ cosine enco-

der (master-slave operation). This application uses the SubD connector X2.

Limit frequency: 250 kHz

AGND (terminal X3/1) must be connected to the ground of the control system!

SERVOSTAR®

400 Installation manual 51

Kollmorgen 07/03 Interfaces

SERVOSTAR 400

SERVOSTAR 400

Page 52: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.10 Fieldbus connection

3.10.1 CANopen interface (X7)

The interface for connection to the CAN bus (default: 500 kbps). The integrated profile is based on

the communication profile CANopen DS301 and the drive profile DSP402.

The following functions are available in connection with the integrated position controller:

Jogging with variable speed, homing, start motion task, start direct task, digital setpoint provision,

data transmission functions and many others.

Detailed information can be found in the CANopen manual.

The interface is at the same potential as the internal logic, and uses AGND as the ground refer-

ence. The analog input can still be used.

Even if the analog input is not used, AGND must nevertheless be joined to the control sys-

tem ground!

CAN bus cable

To meet ISO 11898 you should use a bus cable with a 120 � characteristic impedance. The maxi-

mum usable cable length for reliable communication decreases with increasing transmission speed.

As a guide, you can use the following values which we have measured, but they must not be assu-

med to be limits:

Cable data: Characteristic impedance 100-120 �

Cable capacitance max. 60 nF/km

Conductor loop resistance 159.8 �/km

Cable length, depending on the transmission rate

Transmission rate / kbps max. cable length / m

1000 20

500 70

250 115

Lower cable capacitance (max. 30 nF/km) and lower lead resistance (loop: 115 �/km) make it pos-

sible to transmit over longer distances.

(Characteristic impedance 150 ± 5� � terminating resistance 150 ± 5�).

For EMC reasons, the SubD connector housing must fulfil the following conditions:

— metal or metallized housing

— provision for connecting the cable shielding within the housing,

large-area connections

The master is fitted with a CAN input. All axis modules in the system are connected to this through

the internal bus. The last axis module has a CAN output, where the CAN bus either continues to

other bus participants or is terminated by a termination resistor.

52 SERVOSTAR®

400 Installation manual

Interfaces 07/03 Kollmorgen

SERVOSTAR 400

Page 53: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.10.2 PROFIBUS interface (X7), option

This section describes the PROFIBUS interface for SERVOSTAR 400.

Information on the range of functions and the software protocol can be found in the description

“Communication profile PROFIBUS-DP”.

The selection of cables, cable routing, shielding, bus connectors, bus termination and propagation

times are described in the “Setup guidelines for PROFIBUS-DP/FMS” from PNO, the PROFIBUS

User Organization, Order No. 2.111.

SERVOSTAR®

400 Installation manual 53

Kollmorgen 07/03 Interfaces

SERVOSTAR 400

Page 54: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

3.10.3 SERCOS interface (X7), option

This section describes the SERCOS interface of the SERVOSTAR 400.

Information on the range of functions and the software protocol can be found in the manual “IDN

Reference Guide SERCOS”.

For the optical fibre (LWL) connection, only use SERCOS components to the SERCOS Standard

IEC 61491.

3.10.3.1 Light emitting diodes (LEDs)

RT: indicates whether SERCOS telegrams are being correctly received. In the final

Communication Phase 4 this LED should flicker, since cyclical telegrams are being received.

TT: indicates that SERCOS telegrams are being transmitted. In the final Communication Phase

4 this LED should flicker, since cyclical telegrams are being transmitted.

Check the stations addresses for the controls and the servo amplifier if:

- the LED never lights up in SERCOS Phase 1 or

- the axis cannot be operated, although the RT LED is lighting up cyclically.

Err: indicates that SERCOS communication is faulty or suffering from interference.

If this LED is very bright, then communication is suffering strong interference, or is

non-existent.

Check the SERCOS transmission speed for the controls and the servo amplifier

(BAUDRATE) and the fibre-optic connection.

If this LED flickers, this indicates a low level of interference for Sercos communication, or the

optical transmitting power is not correctly adjusted to suit the length of cable.

Check the transmitting power of the (physically) previous SERCOS station.

The transmitting power of the servo amplifier can be adjusted in the setup software

DRIVE.EXE on the SERCOS screen page, by altering the LWL length parameter for the

cable length.

3.10.3.2 Connection diagram

Layout of the SERCOS bus system in ring topology, with optical fibre cables (schematic).

54 SERVOSTAR®

400 Installation manual

Interfaces 07/03 Kollmorgen

Page 55: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

4 Commissioning

4.1 Important notes

Only professional personnel with extensive knowledge in the fields of electrical engineering

and drive technology are allowed to commission the servo amplifier.

The procedure for commissioning is described as an example. Depending on the application, a dif-

ferent procedure may be appropriate or necessary.

In multi-axis systems, commission each servo amplifier individually.

Before commissioning, the manufacturer of the machine must produce a hazard analy-

sis for the machine and take appropriate measures to ensure that unforeseen move-

ments do not result in personal injury or material damage.

Caution !

Check that all live connecting elements are protected from accidental contact.

Deadly voltages can be present, up to 800V.

Never disconnect any of the electrical connections to the servo amplifier while it is live.

Capacitors can still have residual charges with dangerous levels up to 300 seconds af-

ter switching off the supply power.

Heat sinks and front panels of the amplifier can reach a temperature of up to 80°C in

operation. Check (measure) the heat sink temperature. Wait until the heat sink has

cooled down below 40°C before touching it.

Warning !

If the servo amplifier has been stored for longer than 1 year, then the DC-link capaci-

tors will have to be re-formed.

To do this, disconnect all the electrical connections.

Supply the servo amplifier for about 30 min. from single-phase 230V AC to the termi-

nals L1 / L2. This will re-form the capacitors.

Further information on commissioning:

The adaptation of parameters and their effects on the control loop behaviour are des-

cribed in the manual for the setup software.

The commissioning of the fieldbus interface is described in the corresponding manual.

We can provide further know-how through training courses (on request).

SERVOSTAR®

400 Installation manual 55

Kollmorgen 07/03 Commissioning

Page 56: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

The following instructions should help you to carry out the commissioning in a sensible order, wit-

hout any hazards to people or machinery.

See Chapter 2. Disconnect the servo amplifier from the supply.

0V on terminal X1/3 (Enable)

24V DC on terminal 0/1, ground on terminal X0/2

After the initialization procedure (about 0.5 sec.) the status is

shown in the LED display (� p.58)

Select the interface to which the servo amplifier is connected.

The parameters which are stored in the SRAM of the servo

amplifier are transferred to the PC.

Caution !

Check the parameters described below especially carefully.

If you ignore these basic data, system components may be

damaged or destroyed.

Supply voltage : set to the actual mains supply voltage

(observe supply voltage limits,� p.17)

Rated motor voltage : at least as high as the DC-link voltage of the amplifier

Motor pole-no. : must match the motor (see motor manual)

Feedback : must match the feedback unit in the motor

IRMS : maximum is the motor standstill current I0 (as on nameplate)

IPEAK : maximum is 4 x motor standstill current I0Limit speed : maximum is the rated motor speed (as on nameplate)

Regen power : maximum is the rated dissipation for the regen resistor

Station address : unique address on the master

Caution !

Make sure that any unintended movement of the drive

cannot cause danger to machinery or personnel.

through the ON/OFF button of the contactor control

apply 0V to terminals X3/2-3

(500 msec after switching on the supply power) 24V DC on

terminal X1/3 (Enable), motor is at rest with standstill torque M0

apply a small analog setpoint (about 0.5V is recommended) to

terminals X3/2-3

If the motor oscillates, the Kp parameter in the screen page

Speed controller must be reduced – the motor is in danger !

optimize the speed, current and position controllers

see commissioning instructions in the corresponding

manual on the CD-ROM

56 SERVOSTAR®

400 Installation manual

Commissioning 07/03 Kollmorgen

Check installation

Negate enable signal

Switch on 24V

aux. supply

Switch on PC, start

setup S/W

Check the displayed

parameters, and

correct them if

necessary

Check safety devices

Switch on power

Apply 0V setpoint

Enable amplifier

Optimization

Commission fieldbus

Setpoint

Page 57: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

4.2 Parameterization

A default parameter set is loaded into your servo amplifier at the factory. This contains valid and

safe parameters for the current and speed controllers.

A database for motor parameters is stored in the servo amplifier. During commissioning you must

select the data set for the motor that is connected and store it in the servo amplifier. For most appli-

cations these settings will already provide good to very good control loop characteristics.

An exact description of all parameters and the options for optimizing the control loop characteristics

can be found in the manual “Setup Software DRIVE.EXE”.

4.2.1 Multi-axis systems

All the axes in a system can be parameterized through the RS232 interface in the master. To do

this, there is an internal connection between the master and the axis modules. The PC cable only

has to be connected to the master.

The internal address assignment is carried out automatically, so that it is only necessary to set up

the basic station address for the master.

After changing the station address it is necessary to turn off the 24V auxiliary

supply, and then turn it on again.

Starting at the master, descending addresses are assigned automatically to the axis modules. The

following table shows an example with one master and three axis modules:

Axis Address Remark

Master 10 Master address, set by user

Axis module 3 9

assigned automaticallyAxis module 2 8

Axis module 1 7

The highest permitted master address is 128. When choosing the master address, please

consider that at least address 1 will be assigned to the last (leftmost) axis module.

In CAN and PROFIBUS field bus systems the automatically assigned addresses must

not match the address of other nodes.

SERVOSTAR®

400 Installation manual 57

Kollmorgen 07/03 Commissioning

PC

COMx

RS232

X8

PC

Axismodule

1

MasterAxis

module2

Axismodule

3

Page 58: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

4.2.2 Key pad controls and status displays

Two keys are fitted in the operating panel of the master. Here you can enter the basic address for

the system and call up status information on all the axes that are connected.

4.2.2.1 Operating

The two keys can be used to perform the following functions:

Key symbol Functions

� press once : go up one menu item, increase number by one

press twice in rapid succession : increase number by ten

press once : go down one menu item, decrease number by one

press twice in rapid succession : decrease number by ten

press and hold right key, then press left key as well :

enters a number, return function

4.2.2.2 Status display on the axis module

Each axis module is fitted with 2 LEDs that provide a quick indication of the instrument status.

LED

red green Interpretation

lit off axis is not ready for operation (fault)

blinking off a warning has been generated

off lit axis is ready for operation, and enabled

off blinking axis is ready for operation, but not enabled

blinking blinking axis is selected for editing by the master

A detailed display of the warnings and faults can be called up in the display on the master (� p.59).

58 SERVOSTAR®

400 Installation manual

Commissioning 07/03 Kollmorgen

Page 59: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

4.2.2.3 Status display on the master

SERVOSTAR®

400 Installation manual 59

Kollmorgen 07/03 Commissioning

Page 60: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

4.3 Error messages

Any errors that occur are shown in coded form by an error number in the LED display on the front

panel. All error messages result in the BTB/RTO contact being opened, and the output stage of the

amplifier being switched off (motor loses all torque). The motor-holding brake is activated.

Number Designation Explanation

F00 no error no error in the selected axis module

F01* heat sink temperatureheat sink temperature too high

limit is set by manufacturer to 80°C

F02* overvoltageovervoltage in DC-link

limit depends on the mains supply voltage

F03* contouring error message from the position controller

F04 feedback cable break, short circuit, short to ground

F05* undervoltageundervoltage in DC-link

limit is set by manufacturer to 100V

F06 motor temperaturemotor temperature too high (or temp. sensor defect)

limit is set by manufacturer to145°C

F07 aux. voltage internal aux. voltage not OK

F08* overspeed motor runs away, speed is too high

F09 EEPROM checksum error

F10 Flash-EPROM checksum error

F11 brake cable break, short circuit, short to ground

F12 motor phase motor phase missing (cable break or similar)

F13* internal temperature internal temperature too high

F14 output stage fault in the output stage

F15 I²t max. I²t max value exceeded

F16* supply BTB/RTO 2 or 3 phases missing in the supply feed

F17 A/D converter error in the analog-digital conversion

F18 regen regen circuit faulty or incorrect setting

F19* supply phase a phase is missing in the supply power feed

F20 slot error slot error

F21 handling error software error on the expansion card

F22 earth/ground fault only for 40/70 A instruments: earth fault

F23 CAN bus off severe CAN bus communication error

F24 warning warning display is evaluated as fault

F25 commutation error commutation error

F26 limit-switch homing error (drove onto hardware limit-switch)

F27 AS-optionoperational error with -AS- option (control signal for -AS- option ap-

pears simultaneously with the ENABLE signal)

F28 reserve reserve

F29 Sercos error only in SERCOS systems

F30 SERCOS timeout Sercos timeout, leads to emergency stop

F31 reserve reserve

F32 system error system software nor responding correctly

* = these error messages can be cleared without a reset, by using the ASCII command CLRFAULT.

If only one of these errors is present and the RESET button or the I/O RESET function is used, only the

CLRFAULT command will be executed.

60 SERVOSTAR®

400 Installation manual

Commissioning 07/03 Kollmorgen

Page 61: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

4.4 Warning messages

Faults which occur, but which do not cause a switch-off of the amplifier output stage (BTB/RTO con-

tact remains closed), are indicated in the LED display on the front panel by a coded warning num-

ber.

Number Designation Explanation

n01 I²t I²t threshold exceeded

n02 regen power reached preset regen power limit

n03* S_fault exceeded preset contouring error limit

n04* response monitoring response monitoring (fieldbus) has been activated

n05 supply phase supply phase missing

n06* Sw limit-switch 1 passed software limit-switch 1

n07* Sw limit-switch 2 passed software limit-switch 2

n08 motion task error a faulty motion task was started

n09 no reference point no reference point set at start of motion task

n10* PSTOP PSTOP limit-switch activated

n11* NSTOP NSTOP limit-switch activated

n12 default values only for HIPERFACE®

: motor default values loaded

n13* expansion card expansion card not operating correctly

n14 SinCos feedback SinCos commutation failure

n15 table fault fault as per speed/current table INXMODE 35

n16-n31 reserve reserve

n32 firmware beta version firmware version has not been released

* = these warning messages result in a controller shut-down of the drive (braking by emergency stop ramp)

SERVOSTAR®

400 Installation manual 61

Kollmorgen 07/03 Commissioning

Page 62: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

This page has been deliberately left blank.

62 SERVOSTAR®

400 Installation manual

Commissioning 07/03 Kollmorgen

Page 63: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

5 Accessories

5.1 External PSU 24V DC / 5A

Technical data

Input voltage 120 / 230V

Input current 0.9 / 0.6A

Frequency 50/60Hz

Primary fusing 3.15AT

Output voltage 24V ± 1%

Max. output current 5A

Residual ripple <150mVss

Switching peaks <240mVss

Output fusing short-circuit proof

Temperature range 0 to +60°C

Mounting methodDIN-rail, vertical mounting

50mm free space required above and below the instrument

Weight 0.75kg

Order No. 83034

SERVOSTAR®

400 Installation manual 63

Kollmorgen 07/03 Accessories

Page 64: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

5.2 External PSU 24V DC / 20A

64 SERVOSTAR®

400 Installation manual

Accessories 07/03 Kollmorgen

Technical data

Input voltage 3 x 400V AC ± 10%

Input current approx. 1.1A

Frequency 50/60Hz

Primary fusing none

Output voltage 24V ± 1%

Max. output current 20A

Residual ripple <0.1%

Output fusing short-circuit proof

Test voltage to VDE 0550

Temperature range -20 to +60°C

Mounting methodon mounting plate (supplied)

Keep space free

Weight 3.5kg

Order No. 81279

Page 65: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

5.3 External ballast resistor BARxxx

Caution:

Surface temperature may exceed 200°C.

Observe the requested free space.

Do not mount to combustible surface

SERVOSTAR®

400 Installation manual 65

Kollmorgen 07/03 Accessories

Page 66: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

5.4 Add-on fan

Electrical add-on fan for two axes to achieve rated power even under unfavourable ambient condi-

tions, required for SERVOSTAR4x6.

To mount the fan, just hook it in the designated slots at the bottom of the SERVOSTAR and screw

the fixing bolt into the thread in the housing

The electrical connection takes place automatically when mounting the fan.

Please consider that a mounted fan increases the required space underneath the ampli-

fier! (� p. 24)

The drawing below shows, how the fan should be mounted.

With an odd number of axes (master included), the fan must also cover the power supply unit at the

master.

66 SERVOSTAR®

400 Installation manual

Accessories 07/03 Kollmorgen

Single master Master with 2 Axis modulesMaster with 1 Axis module

Page 67: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

6 Appendix

6.1 Transport, storage, maintenace, disposal

Transport: — only by qualified personnel

— only in the manufacturer’s original recyclable packaging

— avoid shocks

— temperature -25 to +70°C, max. rate of change 20°C/hour

— humidity max. 95% relative humidity, no condensation

— the servo amplifiers contain electrostatically sensitive components

— which can be damaged by incorrect handling. Discharge yourself

— before touching the servo amplifier. Avoid contact with highly

— insulating materials (artificial fabrics, plastic films etc.).

— Place the servo amplifier on a conductive surface.

— if the packaging is damaged, check the unit for visible damage.

— In such a case, inform the shipper and the manufacturer.

Packaging: — recyclable cardboard with inserts

— dimensions SERVOSTAR 4xxA (HxWxD) 100x300x270 mm

SERVOSTAR 4xxM (HxWxD) 150x300x270 mm

— labelling instrument label on outside of box

Storage : — only in the manufacturer’s original recyclable packaging

— the servo amplifiers contain electrostatically sensitive components

— which can be damaged by incorrect handling. Discharge yourself

— before touching the servo amplifier. Avoid contact with highly

— insulating materials (artificial fabrics, plastic films etc.).

— Place the servo amplifier on a conductive surface.

— max. stacking height: 8 cartons

— storage temp. –25 to +55°C, max. rate of change 20°C/hr

— humidity relative humidity max. 95%, no condensation

— storage duration < 1 year without restriction

> 1 year: capacitors must be re-formed before

the servo amplifier is commissioned.

To do this, remove all electrical connections and

supply the servo amplifier for about 30 min. from

230V AC, single-phase, on terminals L2 / L3.

Maintenance: — the instruments do not require any maintenance

— opening the instruments invalidates the warranty

Cleaning : — if the casing is dirty : cleaning with Isopropanol or similar

do not immerse or spray

— if there is dirt inside the unit: to be cleaned by the manufacturer

— dirty protective grill (fan) : clean with a dry brush

Disposal : — you can dismantle the servo amplifier into its principal components

— by screwing it apart (aluminium heat sink, steel housing sections,

— electronics boards)

— disposal should be carried out by a certified disposal company.

— We can give you suitable addresses on request.

SERVOSTAR®

400 Installation manual 67

Kollmorgen 07/03 Appendix

Page 68: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

6.2 Fault-finding

The table below should be regarded as a “First-aid” box.

Depending on the conditions in your installation, there may be a wide variety of reasons for the

fault. In multi-axis systems there may be further hidden causes of a fault.

Our customer support can give you further assistance with problems.

Fault possible causesMeasures to remove the cause of

the fault

HMI message:

communication

fault

— wrong cable used

— cable plugged into wrong position

in servo amplifier or PC

— wrong PC interface selected

— use null-modem cable

— plug cable into the correct sockets

on the servo amplifier and PC

— select correct interface

F01 message:

heat sink

temperature

— permissible heat sink temperature

exceeded

— improve ventilation

F02 message:

overvoltage

— regen power is insufficient. regen power

limit was reached and the regen resistor

was switched off. This causes excessive

voltage in the DC-link circuit.

— supply voltage too high

— shorten the braking time RAMP or

use an external regen resistor

with a higher power rating and

adjust the regen power parameter

— use mains transformer

F04 message:

feedback unit

— feedback connector not properly inserted

— feedback cable is broken, crushed or

otherwise damaged

— check connector

— check cable

F05 message:

undervoltage

— supply voltage not present or too low

when servo amplifier is enabled

— only enable the servo amplifier

when the mains supply voltage has

been switched on delay > 500 ms

F06 message:

motor temperature

— motor thermostat has been activated

— feedback connector is loose or break in

feedback cable

— wait until motor has cooled down,

then check why it became so hot

— tighten connector or use

new feedback cable

F07 message:

aux. voltage

— the aux. voltage produced by the servo

amplifier is incorrect

— return the servo amplifier to the

manufacturer for repair

F08 message:

motor runs away

(overspeed)

— motor phases swapped

— feedback set up incorrectly

— faulty connection to feedback unit

— correct motor phase sequence

— set up correct offset angle

— check connector

F11 message:

brake

— short-circuit in the supply cable for the

motor-holding brake

— motor-holding brake is faulty

— fault in brake cable

— no brake connected, although the

brake parameter is set to "WITH"

— remove short-circuit

— replace motor

— check shielding of brake cable

— brake parameter set to "WITHOUT"

F13 message:

internal tempera-

ture

— permissible internal temperature exceeded — improve ventilation

F14 message:

output stage fault

— motor cable has short-circuit/ground short

— motor has short-circuit / ground short

— output module is overheated

— output stage is faulty

— short-circuit / short to ground in the

external regen resistor

— replace cable

— replace motor

— improve ventilation

— return the servo amplifier to the

manufacturer for repair

— remove short-circuit / ground short

F16 message:

mains BTB/RTO

— enable was applied, although the

supply voltage was not present.

— at least 2 supply phases are missing

— only enable the servo amplifier

when the mains supply voltage

has been switched on

— check electrical supply

F17 message:

A/D converter

— error in the analog-digital conversion,

usually caused by excessive EMI

— reduce EMI,

check screening and grounding

68 SERVOSTAR®

400 Installation manual

Appendix 07/03 Kollmorgen

Page 69: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

Fault possible causesmeasures to remove the cause of

the fault

F25 message:

Commutation error

— wrong cable

— wrong phasing

— check wiring

— check resolver poles (RESPOLES)

check motor poles (MPOLES)

check offset (MPHASE)

F27 message:

error AS-option

— -AS-24V relay AND hardware enable AND

software enable are active

— check PLC programming and

wiring

motor does not rotate

— servo amplifier not enabled

— break in setpoint cable

— motor phases swapped

— brake not released

— drive is mechanically blocked

— no. of motor poles set incorrectly

— feedback set up incorrectly

— apply enable signal

— check setpoint cable

— correct motor phase sequence

— check brake control

— check mechanism

— set no. of motor poles

— set up feedback correctly

motor oscillates

— gain too high (speed controller)

— shielding in feedback cable has a break

— AGND not wired up

— reduce Kp (speed controller)

— replace feedback cable

— join AGND to CNC-GND

drive reports

following error

— Irms or Ipeak is set to low

— setpoint ramp is too long

— increase Irms or Ipeak

(keep within motor data !)

— shorten setpoint ramp +/-

motor overheating — Irms/Ipeak set too high — reduce Irms/Ipeak

drive too soft

— Kp (speed controller) too low

— Tn (speed controller) too high

— PID-T2 too high

— T-Tacho too high

— increase Kp (speed controller)

— use motor default value for

Tn (speed controller)

— reduce PID-T2

— reduce T-Tacho

drive runs

roughly

— Kp (speed controller) too high

— Tn (speed controller) too low

— PID-T2 too low

— T-Tacho too low

— reduce Kp (speed controller)

— use motor default value for

Tn (speed controller)

— increase PID-T2

— increase T-Tacho

axis drifts at

setpoint = 0V

— offset not correctly adjusted for analog

setpoint provision

— AGND not joined to the CNC-GND of the

controls

— adjust setpoint-offset (analog I/O)

— join AGND and CNC-GND

n12 message:

Motor default values

loaded

— Motor number stored in sine encoders

EEPROM different than what drive is

configured for

— If n12 is displayed, default values

for the motor are loaded.

Motor number will be automatically

stored in EEPROM with SAVE.

n14 message:

Wake & shake active— Wake & shake not executed — Enable the drive

SERVOSTAR®

400 Installation manual 69

Kollmorgen 07/03 Appendix

Page 70: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

6.3 Glossary

C clock Clock signal

common-mode voltage The maximum amplitude of a disturbance (on both

inputs) which a differential input can eliminate

continuous power of regen circuit Mean power which can be dissipated in the regen circuit

counts Internal count pulses, 1 pulse = 1/220

turn-1

current controller Regulates the difference between the current setpoint

and the actual value to 0

Output : power output voltage

D DC-link Rectified and smoothed power voltage

disable Removal of the enable signal (0V or open)

E earth short electrical connection between a phase and

the protective earth (PE)

enable Enable signal for the servo amplifier (+24V)

F fieldbus interface CANopen, PROFIBUS, SERCOS

free convection Free movement of air for cooling

G GRAY-code Special format for representing binary numbers

H holding brake Brake in the motor, which should only be used when the

motor is at standstill

I I²t threshold Monitoring of the r.m.s. current that is actually required

incremental encoder interface Position signalling by 2 signals with 90° phase

difference, not an absolute position output

input drift Temperature and age-dependent alteration of an

analog input

Ipeak, peak current The effective value of the peak current

Irms, effective current The r.m.s. value of the continuous current

K Kp, P-gain Proportional gain of a control loop

L limit speed Maximum value for speed normalization at ±10V

limit-switch Switch limiting the traverse path of the machine;

implemented as n.c. (break) contact

M machine The complete assembly of all connected parts or

devices, of which at least one is movable

motion-block Set of all the position control parameters

which are required for a motion task

multi-axis system Machine with several driven axes

N natural convection Free movement of air for cooling

O optocoupler Optical connection between two electrically

independent systems

70 SERVOSTAR®

400 Installation manual

Appendix 07/03 Kollmorgen

Page 71: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

P P-controller Control loop with purely proportional behaviour

phase shift Compensation for the lag between the electromagnetic

and magnetic fields in the motor

PID-controller Control loop with proportional, integral and

differential behaviour

PID-T2 Filter time constant for the speed controller output

position controller Regulates the difference between the position setpoint

and the actual position to 0

Output : speed setpoint

potential isolation electrically decoupled

power contactor System protection device with phase monitoring

pulse power of the regen circuit Maximum power which can be dissipated in the

regen circuit

R regen circuit Converts superfluous energy, which is fed back

during braking, into heat in the regen resistor

reset New start of the microprocessor

reversing mode Operation with a periodic change of direction

ring core Ferrite rings for interference suppression

ROD-interface Incremental position output

S servo amplifier Control device for regulating the speed, torque

and position of a servomotor

setpoint ramps Limits for the rate of change of the speed setpoint SW

short-circuit here: electrically conductive connection between

two phases

speed controller Regulates the difference between the speed setpoint

and the actual value to 0

Output : current setpoint

SSI-interface Cyclic-absolute, serial position output

supply filter Device to divert interference on the power supply

cables to PE

T T-tacho, tachometer time constant Filter time constant in the speed feedback of

the control loop

tachometer voltage Voltage proportional to the actual speed

thermostat Temperature-sensitive switch built into the

motor winding

Tn, I-integration time Integral section of a control loop

Z zero pulse Output once per turn from incremental encoders,

used to zero the machine

SERVOSTAR®

400 Installation manual 71

Kollmorgen 07/03 Appendix

Page 72: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

6.4 Index

72 SERVOSTAR®

400 Installation manual

Appendix 07/03 Kollmorgen

! 24V aux. supply, interface . . . . . . . . . . . 38

A Abbreviations . . . . . . . . . . . . . . . . . . 7

Accessories . . . . . . . . . . . . . . . . . . 63

AGND . . . . . . . . . . . . . . . . . . . . . 19

ambient conditions . . . . . . . . . . . . . . . 18

ambient temperature . . . . . . . . . . . . . . 18

B Block diagram . . . . . . . . . . . . . . . . . 15

brake . . . . . . . . . . . . . . . . . . . . . . 19

BTB/RTO. . . . . . . . . . . . . . . . . . . . 44

C CANopen interface . . . . . . . . . . . . . . . 52

CE conformity . . . . . . . . . . . . . . . . . . 6

commissioning . . . . . . . . . . . . . . . . . 55

conductor cross-sections. . . . . . . . . . . . 18

Connection cables . . . . . . . . . . . . . . . 33

Connection techniques. . . . . . . . . . . . . 32

connector assignments . . . . . . . . . . . . 31

contents . . . . . . . . . . . . . . . . . . . . . 3

Control signals . . . . . . . . . . . . . . . . . 41

D DC-link, interface. . . . . . . . . . . . . . . . 38

DGND . . . . . . . . . . . . . . . . . . . . . 19

Dimensions. . . . . . . . . . . . . . . . . . . 25

display . . . . . . . . . . . . . . . . . . . . . 19

disposal . . . . . . . . . . . . . . . . . . . . 67

E earthing

installation . . . . . . . . . . . . . . . . . 27

wiring diagram . . . . . . . . . . . . . . . 28

EMC . . . . . . . . . . . . . . . . . . . . . . 23

Emergency Stop methods . . . . . . . . . . . 22

enclosure rating . . . . . . . . . . . . . . . . 18

encoder

interface . . . . . . . . . . . . . . . . . . 40

master-slave interface . . . . . . . . . . . 50

encoder emulations . . . . . . . . . . . . . . 45

Equipment description . . . . . . . . . . . . . 11

error messages . . . . . . . . . . . . . . . . 60

external fusing . . . . . . . . . . . . . . . . . 18

F Fault-finding . . . . . . . . . . . . . . . . . . 68

Fieldbus interface . . . . . . . . . . . . . . . 52

forming . . . . . . . . . . . . . . . . . . . . . 55

G Glossary . . . . . . . . . . . . . . . . . . . . 70

ground symbol . . . . . . . . . . . . . . . . . 26

Grounding system . . . . . . . . . . . . . . . 19

H hardware requirements. . . . . . . . . . . . . 36

humidity . . . . . . . . . . . . . . . . . . . . 67

I inputs

analog setpoint. . . . . . . . . . . . . . . 41

DIGI-IN 1/2 . . . . . . . . . . . . . . . . . 42

Enable . . . . . . . . . . . . . . . . . . . 44

NSTOP. . . . . . . . . . . . . . . . . . . 42

PSTOP. . . . . . . . . . . . . . . . . . . 42

installation

hardware . . . . . . . . . . . . . . . . . . 26

software . . . . . . . . . . . . . . . . . . 36

Interfaces. . . . . . . . . . . . . . . . . . . . 37

K key operation. . . . . . . . . . . . . . . . . . 58

L LED display . . . . . . . . . . . . . . . . . . 58

limit-switch inputs . . . . . . . . . . . . . . . 42

M maintenance . . . . . . . . . . . . . . . . . . 67

master-slave . . . . . . . . . . . . . . . . . . 50

motor

interface . . . . . . . . . . . . . . . . . . 38

motor choke, connection example . . . . . . . 30

mounting . . . . . . . . . . . . . . . . . . . . 24

mounting position . . . . . . . . . . . . . . . 18

multi-axis system, connection example . . . . 30

N nameplate . . . . . . . . . . . . . . . . . . . 11

NSTOP, interface . . . . . . . . . . . . . . . 42

O Operating systems . . . . . . . . . . . . . . . 36

options . . . . . . . . . . . . . . . . . . . . . 12

outputs

BTB/RTO. . . . . . . . . . . . . . . . . . 44

DIGI-OUT 1/2 . . . . . . . . . . . . . . . 43

P package supplied . . . . . . . . . . . . . . . 11

packaging . . . . . . . . . . . . . . . . . . . 67

parameterization . . . . . . . . . . . . . . . . 57

PC connection . . . . . . . . . . . . . . . . . 47

PC interface cable . . . . . . . . . . . . . . . 47

pollution level. . . . . . . . . . . . . . . . . . 18

PROFIBUS interface . . . . . . . . . . . . . . 53

PSTOP, interface . . . . . . . . . . . . . . . 42

PSU 24V

20A. . . . . . . . . . . . . . . . . . . . . 64

5A . . . . . . . . . . . . . . . . . . . . . 63

pulse/direction, interface . . . . . . . . . . . . 48

R regen circuit . . . . . . . . . . . . . . . . . . 20

regen resistor

dimensions. . . . . . . . . . . . . . . . . 65

external interface. . . . . . . . . . . . . . 39

techn. data . . . . . . . . . . . . . . . . . 20

resolver

interface . . . . . . . . . . . . . . . . . . 39

ROD, interface . . . . . . . . . . . . . . . . . 45

RS232/PC, interface . . . . . . . . . . . . . . 47

S safety instructions . . . . . . . . . . . . . . . . 5

SERCOS interface . . . . . . . . . . . . . . . 54

setpoint inputs . . . . . . . . . . . . . . . . . 41

Setup software . . . . . . . . . . . . . . . . . 35

SETUP.EXE . . . . . . . . . . . . . . . . . . 36

Shield connection . . . . . . . . . . . . . . . 32

shielding

installation . . . . . . . . . . . . . . . . . 27

wiring diagram . . . . . . . . . . . . . . . 28

site . . . . . . . . . . . . . . . . . . . . . . . 27

site altitude . . . . . . . . . . . . . . . . . . . 18

SSI, interface. . . . . . . . . . . . . . . . . . 46

stacking height . . . . . . . . . . . . . . . . . 67

Standards . . . . . . . . . . . . . . . . . . . . 6

Status display . . . . . . . . . . . . . . . . . 58

storage . . . . . . . . . . . . . . . . . . . . . 67

storage duration . . . . . . . . . . . . . . . . 67

storage temperature . . . . . . . . . . . . . . 67

supply connection, interface . . . . . . . . . . 37

supply voltage . . . . . . . . . . . . . . . . . 18

Switch on/off behaviour . . . . . . . . . . . . 21

Symbols . . . . . . . . . . . . . . . . . . . . . 7

system components, summary. . . . . . . . . 16

T technical data . . . . . . . . . . . . . . . . . 17

tightening torques, connectors . . . . . . . . . 18

transport . . . . . . . . . . . . . . . . . . . . 67

Transport temperature . . . . . . . . . . . . . 18

U use as directed . . . . . . . . . . . . . . . . . 9

servo amplifier . . . . . . . . . . . . . . . 10

setup software . . . . . . . . . . . . . . . 35

V ventilation

installation . . . . . . . . . . . . . . . . . 27

techn. data . . . . . . . . . . . . . . . . . 18

W warning messages . . . . . . . . . . . . . . . 61

wiring . . . . . . . . . . . . . . . . . . . . . . 27

wiring diagram . . . . . . . . . . . . . . . . . 28

Page 73: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

This page has been deliberately left blank.

SERVOSTAR®

400 Installation manual 73

Kollmorgen 07/03 Appendix

Page 74: Digital Servo Amplifier - tgdrives.cz · movements do not result in personal injury ... until it has been established that the machine or plant fulfills the ... NI Zero pulse NSTOP

Sales and Service

Visit the European Danaher Motion web site at www.DanaherMotion.de for Setup Software upgrades,application notes, technical publications and the most recent version of our product manuals.

Danaher Motion Customer Support - Europe

Internet www.DanaherMotion.deE-Mail [email protected]: +49(0)203 - 99 79 - 0Fax: +49(0)203 - 99 79 - 155

Europe

North America

Visit the North American Danaher Motion web site at www.DanaherMotion.com for Setup Softwareupgrades, application notes, technical publications and the most recent version of our product manuals.