Page 1: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—2020

Digital switchgear concepts for MV applicationsTake full advantage of IEC 61850 and IoT and enable digital switchgear

Page 2: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Learning objectives

August 6, 2020 Slide 2

– Introduction to digital switchgear

– Governing standards

– Key digital switchgear components

• Current and voltage sensors• Protection and control relays with LEA inputs

– Value of digital switchgear

• Examples

– Asset health monitoring

– Reference projects– Appendices

Page 3: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—What is digital switchgear?

August 6, 2020 Slide 3

Definition

Switchgear where device status information, current and voltage measurements and commands are reliably transferred on a common communication bus. Alternatively, or as part of this, the switchgear and its equipment condition monitoring and diagnostic information is also digitally available for advanced analysis

Page 4: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—ANSI MV digital switchgear

August 6, 2020 Slide 4

Scope

Base product –ReliaGear ND, Advance, Advance 27, SafeGear,

SafeGear HD

Coming in H2 2020

Base product

With digital solutions –ReliaGear ND Digital, Advance Digital, Advance 27 Digital,

SafeGear Digital, SafeGear HD Digital

Automation and control

61850 Bus communication

Future option: centralized protection

Current and voltage sensors

SCADA (Local/remote)

Monitoring and diagnostics

(On-premise)

Asset health –SwitchgearMD™ with

SWICOM

Future option: energy management

EL common platform (Cloud)

ABB Edge/Cloud gateway

Energy management

Asset managementMV SWG

—ABB Ability™

Page 5: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Digital switchgear is the next phase in the evolution of switchgear

August 6, 2020 Slide 5

SAFETY and SIMPLICITY are the most significant benefits, but there are many more

Sensor technology and common communication bus are essential to realize the full benefits of digital switchgear

Digital switchgear is a proven technology embedded with new products and is UL certified

Communicationstandard

802.3 EthernetCat 5E or Better

Protocol standards

Asset health sensors

Protective relayvoltage sensorcurrent sensor

Page 6: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Governing standards

Page 7: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Do switchgear standards permit the use of sensors?

August 6, 2020 Slide 7

– The latest version of the metal-clad switchgear standard, IEEE C37.20.2-2015, addresses the use of sensors in Annex D

– Additionally, the use of sensors is also referenced in IEEE C37.20.3-2013 for metal-enclosed switchgear and IEEE C37.20.9-2019 for gas insulated switchgear

– UL347 6th Ed. for MV Motor Control Centers addresses the use of sensors in Annex E

Page 8: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—What standards are applicable to sensors?

August 6, 2020 Slide 8

Background

Instrument transformers are primarily covered by IEEE C57.13-2016; this standard does not cover sensors

IEEE standards/guides for current and voltage sensors

– No specific standard exists today

– IEEE PSIM formed new Sensor Subcommittee in January 2020 to organize sensor activities

– IEEE PSIM Working Group formed to work on an IEEE Guide that will be focused on testing of end-to-end sensor systems and Task Force focused on Sensors Accuracy Testing Paper

– IEEE C37.235-2007 - Guide for the Application of Rogowski Coils used for Protective Relaying Purposes

– IEEE C37.92-2005 - Standard for Analog Inputs to Protective Relays From Electronic Voltage and Current Transducers

However, this should not limit your applications

– IEC standards 60044 and 61869 cover sensors

• IEC 61869-10 (2017): Additional requirements for low-power passive current transformers

• IEC 61869-11 (2017): Additional requirements for low power passive voltage transformers

Current sensors – IEC 60044-8 (2002)– IEC 61869-10 (2017) - active

Voltage sensors – IEC 60044-7 (1999)– IEC 61869-11 (2017) - active

Page 9: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Key digital switchgear components

Page 10: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Key digital switchgear components

August 6, 2020 Slide 10

Levels of digitalization

Description Main value

Level 0 Simply replace CTs and PTs with current and voltage sensors

Add additional sensor packages (e.g., temperature) as needed

1. Reduced weight2. Space saving (primarily due to elimination of PT compartment)3. Eliminates problems of saturation and ferroresonance4. Safety – no possibility of unsafe voltages from open CT secondary circuits5. Equipment condition for switchgear and circuit breakers

Level 1 Above + IEC61850-8-1 and GOOSE messaging– Ethernet cabling between Protective Relays

Above +5. Significant reduction in wiring between frames6. Late customization7. Increased flexibility in protection and control scheme development

Level 2 Above + Process bus (61850-9-2LE)– Requires use of Merging Units (MUs), time synchronization devices and

Ethernet switches– Fiber optic connection from bay (switchgear) to substation

Above +8. Improved flexibility – changes in protection only require IED level changes.

Page 11: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Is digital switchgear constructed differently?

August 6, 2020 Slide 11

Form factor permits switchgear space savings

Voltage sensors

More flexibility in placement of voltage sensors compared to PTs and major space savings possible.

Current sensors

Put in the same location as CTs

MV sensors Standards

Current sensors

– IEEE 802.3ae and 802.3an– IEEE C37.20.2-2015Paragraph 5.9: Rogowski coils– IEC 60044-8Electronic current transformers– UL/UR/cUR certified

Voltage sensors

– IEEE 802.3ae and 802.3an– IEC 60044-7Electronic voltage transformers– UL certified

Page 12: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Digital switchgear

August 6, 2020 Slide 12

Circuit breaker compartment

Current sensors

Cat 5E or better cable

Page 13: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Digital switchgear

August 6, 2020 Slide 13

Cable compartment

Voltage sensors

Cat 5E or better cable

Page 14: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Sensors – ideal for critical applications

August 6, 2020 Slide 14

Concerns better addressed by sensors

– 20+ year old technology in switchgear

– Use solid state components and little or no ferromagnetic material in circuit

– Lack of magnetic core - very low energy output – cannot typically transfer power to secondary

– Current Sensors @ 60Hz have a 0-180mv output

– Voltage Sensors @ 60Hz have a 0-10V output

– Increased safety

– Reduced footprint– More linear response

– Simplified installations – less wiring, smaller footprint, lighter weight

– Reduced energy use, esp. in tight compartments

Page 15: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

150

100

50

0

-50

-100

-150

0,3

0,2

0,1

0,0

-0,1

-0,2

-0,3Time

Prim

ary

curr

ent,

Ip (A

)

Seco

ndar

y vo

ltage

, Us(

V)

ipus

Current sensors

August 6, 2020 Slide 15

Current sensors are safer than conventional CTs

Digital switchgear

Rogowski coil sensor

– Us=150 mV for 50 Hz - 80 A Primary

– Us=180 mV for 60 Hz - 80 A Primary

Rogowski coil sensor– Output voltage is proportional to the derivative of primary current

– Output voltage is integrated by protective relay

No saturation (air core)

Open CT hazard eliminated

Low power CT, output is voltage rather than currentFOCS (fiber optic current sensor) mainly used in high voltage applications due to higher cost

dttdi

Mtu ps

)()( =

𝑈𝑠(𝑡) = 𝑀𝑑𝑖 𝑝(𝑡)𝑑𝑡

No saturation (air core)

Open CT hazard eliminated

Rated short-time thermal current: up to 85KA/3s

Page 16: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Current sensors

August 6, 2020 Slide 16

Increased performance in differential protection

Rogowski Coil

– Improved sensitivity for “in zone” faults

– Speed of response – reaches steady state of output faster vs. a Conventional CT

– High security for “out of zone” faults– Multiple slopes not required (transformer)

– No need to keep the secondary closed, therefore no need for shorting terminals – connect/disconnect from the relay at any time

I_DIFF

OPERATE REGION

NON-OPERATE REGION

Standard CT

ABB Sensor

I_BIAS

Secondaryoutput

Saturationlevel

10A 100A 1000A 10 000A Primary current

Standard CT

iS

ABB sensor

US

Page 17: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Current sensors

August 6, 2020 Slide 17

Combined accuracy class 0.5/5P630 (5P400)

– Current sensors, thanks to their linear characteristic, guarantee wide range of primary current

– The sensor standard defines accuracy characteristic as combination of metering and protection class into one

– Thus, current sensors transmit currents from couple of Amps up to short circuit, therefore accuracy class is defined as 5P630, where 630 is not an error but a real number calculated out of maximal current to be transmitted via sensor to secondary side

Accuracy of sensor is ensured by utilizing correction factors in the protection relays

≈ ≈

ε [%]+5%

+1.5%

+0.75%

+0.5%

-0.5%

-0.75%

-1.5%

5%

Metering accuracy limit class 0.5

Protection accuracy limit class 5P630 (5P400)

4 A 16 A 80 A 4000 A 50 (31.5) kA 85 kA

Ith IpIcthIpr100 %20%5%

Page 18: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Voltage sensors

August 6, 2020 Slide 18

Voltage sensors are safer than conventional PTs

Voltage sensors

Resistive voltage divider sensor

– Passive element

– No fuses required

Non-saturable and linear over the whole measuring rangeNo ferro resonance (non-inductive)

10,000:1 transformation ratio

Accuracy up to class 0.5

Gas insulated switchgear (GIS) uses capacitive voltage divider (CVD) sensors

No ferro-resonance (non-inductive)

Us=R2

R1+R2Up

40

30

20

10

0

-10

-20

-30

-40

8

6

4

2

0

-2

-4

-6

-8Time (ms)

Prim

ary

volta

ge, U

p (k

V)

Seco

ndar

y vo

ltage

,Us (

V)

up (kV)us (V)

0 10 20 4030

Page 19: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Voltage sensors

August 6, 2020 Slide 19

Combined accuracy class 0.5/3P

– For voltage sensors, the sensor standard defines the accuracy class combining metering and protection class into one

– Thus voltage sensors have accuracy class of 0.5 Protection accuracy limit class 3P

Metering accuracy limit class 0.5

Continuous voltage measurement

ε [%]+6%

+3%

+0.5%

-0.5%

-3%

-6%

≈ ≈Upn Upn Upn0.02∗ 0.8∗ Upn1.2∗ Upn1.9∗ Up

Page 20: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Current and voltage sensor connections to IED

August 6, 2020 Slide 20

Point-to-point wiring eliminated and test set-up simplified

Almost no analog wiring in the switchgear – increases reliability

Protective relays must have LEA (low energy analog) inputs compatible with the Rogowski coil and RVD sensors

Protection relayFT Switch Digital per 3 Phase

Sensors

L1

Shielded cable with Cat 5E (min)Adapter

FT-14 Switch Digital

FT-14 Test Plug

Test set

Page 21: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Innovation workshop

August 6, 2020 Slide 21

MV sensors – easy to test and verify

Required tests Available primary injection test set

1. Primary injection test/ratio test

2. Polarity test

3. Secondary winding resistance test

4. Secondary circuit insulation resistance test5. Magnetization curves test

– Omicron CPC 100

Page 22: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Relays for digital switchgear

August 6, 2020 Slide 22

Future proof solution based on IEC 61850 and IEEE 802.3 standards

– Based on worldwide accepted IEC 61850 standard ensuring long-term sustainability

– Ready to be connected to remote control (SCADA) systems

– GOOSE messaging configured with software setting– Available IEC 61850-9-2LE (Edition 2) features:

• Vertical communication

• Horizontal GOOSE communication

• Process bus

– LEA (Low Energy Analog) inputs with IEEE 802.3 (Cat 5E or better cables)

61850

Page 23: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—IEC 61850-9-2LE process bus and GOOSE messaging

August 6, 2020 Slide 23

One line diagram

Common EthernetStation bus (IEC 61850-8-1), process bus (IEC 61850-9-2 LE) and IEEE 1588 v2 time synchronization

Anal

og m

easu

rem

ents

Digi

tal d

ata

Voltage sensor

IED

Current sensor

GOO

SE

SMV

GOO

SE

SMV

GOO

SE

SMV

GOO

SE

SMV

GOO

SE

SMV

GOO

SE

SMV

GOO

SE

SMV

Page 24: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Benefits of digital switchgear

Page 25: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Value of digital switchgear

Safety Savings

Speed Simplicity Sustainability

August 6, 2020 Slide 25

Increased safety by eliminating access to both the dangerous CT secondary signals and PT ferro-resonance. Switchgear condition monitoring technologies reduce personnel exposure due to less unplanned maintenance.

Lower cost of ownership with increased maintenance intervals, lower inventory costs and energy savings. Digital design offers space and weight savings leading to lower switchgear housing costs and freight costs.

Flexibility in engineering and design with the ability to compress order to delivery time and to accommodate late changes.

Reduction in hardware and wiring creating a simpler design to install and maintain. Current and voltage sensors provide greater reliability with a wide and linear range

Enables future system expansion and provides flexibility in protection and control scheme designs. Less material usage and reduction in lifetime energy consumption within the switchgear.

Page 26: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Digital switchgear benefits

August 6, 2020 Slide 26

Reference project: ANSI switchgear at a US industrial user

521200A 521200A 521200A522000A

522000A

5 kV, 2000A, 40 kA

LINESIDE

PT

PTBUSSIDE

A01.04Main

A01.05Feeder

A01.06Feeder

A01.07Feeder

PLENUM DUCTWITH VENT

INST COMPT

2000A

PLENUM DUCT

INST COMPT

1200A

PT COMPT

INSTCOMPT

PLENUM DUCT

INST COMPT

1200A

PT COMPT

INSTCOMPT

PLENUM DUCT

INST COMPT

1200A

INSTCOMPT

1200A

B03.0152-1

B03.0252-2

B03.0452-3

B03.0552-4_52-5

Page 27: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Digital switchgear benefits

August 6, 2020 Slide 27

Reference project: ANSI switchgear at a US industrial user

PLENUM DUCTWITH VENT

INST COMPT

2000A

PLENUM DUCT

INST COMPT

1200A

PT COMPT

INSTCOMPT

PLENUM DUCT

INST COMPT

1200A

PT COMPT

INSTCOMPT

B03.0152-1

B03.0252-2

B03.0452-3

Footprint: -25%, costs: -8.9%

LINESIDE

BUSSIDE

B03.0152-1

B03.0252-2

B03.0452-3

Page 28: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Digital switchgear benefits

August 6, 2020 Slide 28

Reference project: ANSI switchgear at a US industrial user

PLENUM DUCTWITH VENT

INST COMPT

2000A

PLENUM DUCT

INST COMPT

1200A

PT COMPT

INSTCOMPT

PLENUM DUCT

INST COMPT

1200A

PT COMPT

INSTCOMPT

B03.0152-1

B03.0252-2

B03.0452-3

Footprint: -25%, costs: -8.9%

52 52 52522000A

522000A

5 kV, 2000A, 40 kAPT

PT

A01.04Main

A01.05Feeder

A01.06Feeder

A01.07Feeder

LINESIDE

BUSSIDE

1200A 1200A 1200A

Page 29: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Benefits of digital medium voltage switchgear

August 6, 2020 Slide 29

Increased safety

Safer switchgear operation

Sensor technology for current and voltage measurement ensuresa safer working environment for personnel

– When testing current and voltage signal secondary circuits, personnel is not exposed to high-voltage

– Sensors are easier to work with compared to conventional

– Less material exposed to high-voltage electrical stress, decreasing risk of failure

Page 30: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Benefits of digital medium voltage switchgear

August 6, 2020 Slide 30

Energy efficient and climate-friendly

Reduced environmental impact

Energy loss is minimized with the use of sensors

Reduced resource consumption in manufacturing

– Saving potential of up to 250 MWh over 30 years (sample switchgear with 14 frames and 42 CTs or Sensors)

– Saves up to 150 tons of CO2

– Reduced inventory requirements

8900 x

Page 31: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Benefits of digital medium voltage switchgear

August 6, 2020 Data table from: Paper 0103, CIRED 2013, Stockholm – “Application of IEC 61850-9-2 in MV Switchgear with Sensors Use”Slide 31

Energy savings

Feeder CTs Number of panels

Number of CTs

Powerconsumption

Energy consumption in 30 years

Incoming 1000:1/1A 2 6 140 VA 36 698 kWh

Outgoing 1 200:1/1A 8 24 448 VA 117 776 kWh

Outgoing 2 100:1/1A 4 12 102 VA 26 724 kWh

Total - 14 42 690 VA 181 198 kWh

Incoming 2 6 0.0000 VA 0.000 01 kWh

Outgoing 1 8 24 0.0000 VA 0.000 04 kWh

Outgoing 2 4 12 0.0000 VA 0.000 02 kWh

Total - 14 42 0.0000 VA 0.000 07 kWh

Sens

or

Incoming 1000:5/5A 2 6 172 VA 45 244 kWh

Outgoing 1 200:5/5A 8 24 629 VA 165 208 kWh

Outgoing 2 100:5/5A 4 12 179 VA 47 124 kWh

Total - 14 42 980 VA 257 576 kWhCT w

/5A

rate

d se

cond

ary

curr

ent

CT w

/1A

rate

d se

cond

ary

curr

ent Calculation for switchgear

with 14 frames:

– 2 incoming feeders with CTs 1000:x/x A

– 8 outgoing feeders with CTs 200:x/x A – 4 outgoing feeders with CTs 100:x/x A

Page 32: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Benefits of digital medium voltage switchgear

August 6, 2020 Slide 32

Increased flexibility

Adapt easily when requirements change

You can adapt the switchgear as the requirements in your network change, e.g. feeder current

– Digital switchgear can be adapted even at the final stage of the manufacturing process

– Changes can be applied via updating parameters or logics in a protection relay, no need to replace components

– IEC 61850 is future-proof standard, which ensures efficient future updates

Increased flexibility

Page 33: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Benefits of digital medium voltage switchgear

August 6, 2020 Slide 33

Reduced footprint

Reduced space requirement

– Minimized switchgear footprint as potential transformer compartments can be completely eliminated, as voltage sensors can be mounted in the cable compartment tapped to main bus

– New generation of sensors are perfect fit in switchgear requiring less space and weigh significantly less

LPT

BPT

INSTRUMENT

1200A

1200A

INSTRUMENT

1200A

1200A

INSTRUMENT

1200A

INSTRUMENT

1200A

INSTRUMENT

1200A

INSTRUMENT

1200A

LPT

BPT

INSTRUMENT

1200A

1200A

INSTRUMENT

1200A

1200A

INSTRUMENT

1200A

1200A

INST COMPT

1200A

1200A

INST COMPT

1200A

INST COMPT

1200A

INST COMPT

1200A

INST COMPT

1200A

1200A

INST COMPT

1200A

1200A

INST COMPT

1200A

1200A

INST COMPT

1200A

Page 34: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Benefits of digital medium voltage switchgear

August 6, 2020 Slide 34

Optimized weight

Reduced switchgear weight

Lowered impact on site

– Bus PT or Line PT compartments are not required

– Sensors are small and weigh less compared to conventional current transformers (CT) and voltage transformers (VT)

– CTs and VTs weigh in the range of 40 - 60lbs while sensors weigh only 1.1 -4.5lbs.

– Average weight reduction of up to 28lbs per vertical section, depending on the application

– Elimination of entire frames can reduce weight by thousands of pounds– Support structures and room layout can be adapted to lower weight

requirements

Optimized weight

reduction

Digital switchgear

Page 35: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Benefits of digital medium voltage switchgear

August 6, 2020 Slide 35

Faster installation and commissioning

Reduced time spent on installation and commissioning

Reduced time for on site installation and commissioning activities, thanks to:

− Fewer panels to be installed

− Less inter-panel cabling

− Fewer components to test in the low voltage compartment• Switchgear delivered pre-tested, which minimizes amount of time

needed for commissioning

− Late modifications in the commissioning phase can be quickly re-configured in the protection relays, with minimal or no hardware changes

Reduction in installation,

commissioning and maintenance

Conventional Digital

Page 36: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Benefits of digital medium voltage switchgear

August 6, 2020 Slide 36

Faster delivery time

Improved delivery

Shorter time from ordering to operation

– Digital switchgear can be delivered faster thanks to

• One size fits all with sensor technology and is faster than engineering CTs/PTs

• Wider range of operability for medium voltage applications

• Sensors available in stock

• Need for configuration in hardware wiring is minimized, as changes can be made using the software logic in the protection relays Improved

delivery

Page 37: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Benefits of digital medium voltage switchgear

August 6, 2020 Slide 37

Inventory reduction

Voltage transformers

Current transformers

Voltage sensors

Current sensors

Full range: up to 4000 A, 63 kA at 15kV; 2000A, 25 kA at 27 kV

Variants

10’s

100’s

2

2

Page 38: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Benefits of digital medium voltage switchgear

August 6, 2020 Slide 38

Increased switchgear reliability

Increased equipment reliability

Digital switchgear is based on well-proven switchgear platform, but uses sensors

– With sensors, less human interaction is required, which leads to reduced risk of malfunction

– Sensors are smaller, reduce the risk of isolation degradation in the switchgear

– Sensors are immune against grid disturbances, such as ferro-resonance phenomenon

Digital communication– Permanent active supervision of wiring and signal transfer

with IEC 61850 digital communication to enable fast and precise actions in case of failures

Digital switchgear

IEC 61850

Increased reliability

Page 39: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Benefits of digital medium voltage switchgear

August 6, 2020 Slide 39

Increased system reliability

Benefits of IEC 61850 communication

Fast and reliable communication with IEC 61850, the global standard for communications in substations

− Complex control transfer schemes can be configured using the IEC 61850 compliant relays

− Flexibility to adapt and change the switchgear, without costly and time-consuming physical re-wiring

− Using the programmable logic in the protection relays, changes can be done easily and faster

− GOOSE communication between the substation equipment for improved speed and reduced switchgear cabling

− Fewer wires reduces risk of failures

Conventional approach– Wiring between devices must be done

individually per signal

Horizontal GOOSE communication– Number of interconnections is equal to

number of devices

Communication Network (Ethernet)

Page 40: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—IEC 61850-9-2LE process bus and GOOSE messaging in digital switchgear

August 6, 2020 Slide 40

Replacing copper with Ethernet

No cable tray

Single conduitto carry fiber

Before After

Digital substation reduces wiring complexity and resulting risks for operations and maintenance personnel

Page 41: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Asset health monitoringSwitchgearMD™

Page 42: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Asset health monitoring

August 6, 2020 Slide 42

Temperature monitoring: non-intrusive methods

IR cameras Fiber optic sensors Wireless active (battery powered) sensors

IR sensors Wireless passive sensors

– Periodic measurement

– Require a pre-installed transparent window

– Requires line of sight through the window thus limiting monitoring locations

– A good IR camera can be expensive

– Require a technician to get close to the gear

– Require direct surface contact

– Real-time monitoring

– Added installation costs of wiring

– Limits on mounting locations

– In dusty and humid environments the FO cable can create a conductive ground path

– Require direct surface contact

– Real-time monitoring

– Can monitor any location inside the switchgear

– Batteries have limited life-span and this introduces additional maintenance headaches

– Proper sensor and antenna location is essential

– Line of sight required by the sensor thus limiting monitoring locations

– Real-time monitoring

– Added installation costs of wiring

– Accuracy affected by emissivity and reflectivity of adjacent surfaces

– Sensor susceptible to misalignment due to vibration and shock

– Require direct surface contact

– Real-time monitoring

– Can monitor any location inside the switchgear

– Proper sensor and antenna location is essential

Page 43: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Asset health monitoring

August 6, 2020 Slide 43

Partial discharge monitoring

IEC 60270:2000+AMD1:2015 partial discharge measurements

IEC 62478:2016 high-voltage test techniques – measurement of partial discharge by electromagnetic and acoustic methods

Instruments use indirect analytical measurements to obtain a relative signature of PD pulses that can indicate trends

TEV (transient earth voltage) measurement

– Measure EM emissions conducted to ground (typical values 0.1mV to 1V each)

– Cannot always monitor faults between phases

High frequency (HF) and VHF measurements

– Operate 3-300 MHz and use large antennas (not suited for switchgear) and HFCTs or coupled sensors (coupling impairs safety)

Acoustic measurements

– Use a microphone or acoustic sensor to monitor between 10 Hz and 300 KHz

– Wireless method

– Limited detection range due to sound damping within dielectric materials

UHF measurements

– Monitor transient EM waves in 300MHz to 3 GHz range.

– Selective, banded UHF monitoring allows noise rejection

– Band-pass UHF PD detection

• Emission frequencies in 400-800MHz range often found in MV switchgear centered on cavity resonance

Direct measurement of current and voltage spikes using high-frequency CTs and HV capacitive couplers

Can analyze pulse shapes and plot discharge events relative to the phase of the power line waveform

– Expensive and require trained technicians to analyze the data

– Coupling detectors require a ground reference and this exposes a potential failure mode and safety issue

PD dielectric breakdown causes a small, but sudden, rise in current accompanied by a current pulse, as well as electromagnetic, acoustic and ozone emissions

Page 44: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Asset health monitoring

August 6, 2020 Slide 44

Circuit breaker monitoring

Measurements are retrieved with no additional sensors

Data retrieved from relays

– Circuit breaker opening time

– Circuit breaker closing time

– Spring charging time (for spring mech breakers)

– I2t (per phase)– Number of operations

– Days of inactivity

– Trip coil supervision (Binary)

– Gas pressure (Binary) – for SF6 breakers

Page 45: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Asset health monitoring

August 6, 2020 Slide 45

Sensor positioning

Sensors

Data concentrator

Power Supply Unit

Local HMI (current)

Cable compartmentControl compartment

(LV)

Ventilation chamber

Main bus compartment

Breaker compartment

Page 46: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Asset health monitoring

August 6, 2020 Slide 46

Application recommendations

– Aging equipment that may be susceptible to primary cable failures

– Remote or isolated equipment that is difficult for personnel to access

– Critical power equipment that serve processes that would be costly to shut down

– Equipment used in unusual operating or environmental conditions that might decrease the life of the switchgear, especially those in caustic environments

– Any new equipment where the end user wants to reduce the total cost of ownership

– Any new equipment where the end user wants to reduce the risks associated with performing bus inspections or taking bus temperature readings

Page 47: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Reference projects

Page 48: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Digital switchgear

August 6, 2020 Slide 48

Global references

ABB has supplied >1500 digital switchgear panels in over 30 countries in Europe, Asia, Africa and the Americas

Page 49: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Digital switchgear

August 6, 2020 Slide 49

Reference examples in Oil, Gas & Chemical/F&B

UniGear Digital Switchgear (IEC) launched in Q4 2013ANSI MV Digital Switchgear introduced in Q1 2018 and market launch in Q3 2020

Food & Bev, US

– Number of frames: 4

– Voltage level: 4.16 kV

– Commissioned: 03/2019

– Main challenge: Modernize old existing switchgear

Major downstream company, ZA

– Number of frames: 21

– Voltage level: 3,3/6,6/11 kV

– Commissioned: 08/2015

– Main challenge: Substation usable on various voltage levels and easily movable at site

Chemical company, UK

– Number of frames: 20

– Voltage level: 11 kV

– Commissioned: 04/2016

– Main challenge: Substation usable on various voltage levels and easily movable at site

Page 50: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors
Page 51: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Appendix A IEC 61850 Basics for digital switchgear

Page 52: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—MV digital switchgear connection and protocol standards

August 6, 2020 Slide 52

Background of improvements

Institute of Electrical

and Electronics Engineers

International

Electrotechnical Commission

Ethernet 802.3 Connection Standards

1990: IEEE 802.3i – 10 Mbps

1998: IEEE 802.3z – 1 Gbps

2002: IEEE 802.3ae – 10 Gbps (Cat 6)2006: IEEE 802.3an – 10 Gbps (Cat 6)

2010: IEEE 802.3ba – 100 Gbps

IEC/IEEE 61850 Protocol Standards

2003: IEC 61850-2 Glossary

2009: IEC 61850-6 Configuration to IEDs

2011: IEC 61850-8-1 Manufacturing Message Specification (GOOSE) 2011: IEC 61850-9-2 Sampled Values

2012: IEC 61850-10 Conformance testing

2016: IEC/IEEE 61850-9-3 - Precision Time Protocol for Power Utility Automation

Page 53: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Introduction to IEC 61850

August 6, 2020 Slide 53

Station and process bus: physical allocation

Overview

Station bus

Serial connection between station level devices

– E.g., station computer, network gateway, bay level IEDs like protection and control IEDs

Process bus

Serial connection between bay level IEDs and process interfaces at the primary apparatus

– E.g., voltage and current sensors– Disconnectors, earthing switches, circuit breakers

NCIT: non-conventional instrument transformer

I/OI/O MU MU

Station bus IEC 61850

Process bus IEC 61850

NCIT

Page 54: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

I/OI/O MU MU

Station bus IEC 61850

Process bus IEC 61850

NCIT

Introduction to IEC 61850

August 6, 2020 Slide 54

IEC 61850 services on station bus

NCIT: non-conventional instrument transformer

Overview

Station bus

Data is transferred according IEC 61850-8-1 for:

– Control service

• Commands– Report Service

• Indications to IEC 61850 clients

– GOOSE service

• Indication and information exchange between bay level IEDs

– File transfer service• Transmission of disturbance records

Page 55: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

I/OI/O MU MU

Station bus IEC 61850

Process bus IEC 61850

NCIT

Introduction to IEC 61850

August 6, 2020 Slide 55

IEC 61850 services on process bus

NCIT: non-conventional instrument transformer

Overview

Process bus

Data is transferred according IEC 61850-8-1 for:

– GOOSE service

• Binary states like switch/CB positions• Trips

• Commands

Data is transferred according IEC 61850-9-2 for:

– Sampled value service• Sampled current and voltage measurements

Page 56: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

8-1 GOOSE 9-2 SV

Characteristics Event driven Streaming

Information transmitted Binary, Enum Analog

Update rate On data change Repetitive

ContinuousSampling rate

Update intervals 1ms…1s 200-250us

Protocol characteristics

August 6, 2020 Slide 56

GOOSE vs sampled measured values (SMV)

Page 57: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Appendix BBus protection applications

Page 58: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Bus protection

August 6, 2020 Slide 58

Principle of operation (internal bus fault)

Bus protection

– Bus fault occurs

– At least one reverse direction (REV) element is detected

– Not any forward direction (FWD) element is pending

– The “master” relay trips and block-closes all contributing breaker via GOOSE

67-1P/N

67-2P/N

REV

Source #1

67-1P/N

67-2P/N

REV

Source #2

67-1P/N

67-2P/N

REV

Feeder #1

REV

Feeder #2

67-2P/N

67-1P/N

Ethernet Switch

(Master)(Backup)

Page 59: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Bus protection

August 6, 2020 Slide 59

Principle of operation (external through fault)

Bus protection

– An external/through fault occurs, i.e., on Feeder #2

– Feeder #2 relay FWD detected

– The rest of relays either see REV or not FWD

– ONLY Feeder #2 breaker trips

67-1P/N

67-2P/N

REV

Source #1

67-1P/N

67-2P/N

REV

Source #2

67-1P/N

67-2P/N

REV

Feeder #1

FWD

Feeder #2

67-2P/N

67-1P/N

Ethernet Switch

(Master)(Backup)

Page 60: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Bus protection

August 6, 2020 Slide 60

Scheme validation testing results

Trials Processing time (ms) Processing time (cy)

1 50.50 3.03

2 51.00 3.06

3 49.70 2.98

4 55.30 3.32

5 51.50 3.09

6 51.80 3.11

7 52.10 3.13

8 55.20 3.31

9 56.60 3.40

10 54.20 3.25

Average 52.79 3.17

Operating times for internal bus fault Operating times for external through fault

Trials Processing time (ms) Processing time (cy)

1 50.10 3.01

2 53.20 3.19

3 53.20 3.19

4 50.90 3.05

5 51.20 3.07

6 51.60 3.10

7 56.10 3.37

8 51.20 3.07

9 53.30 3.20

10 55.50 3.33

Average 52.63 3.16

Page 61: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Bus protection

August 6, 2020 Slide 61

Novel method using GOOSE messaging

Bus protection

– Utilization of directional overcurrent elements of feeder protection relays

– Dedicated bus protection relay and associated current transformers are not required (reduces footprint)

– Reliable: operates only upon a fault on the protected bus

• All contributing breakers are tripped and block-closed• Acceptable operating speed ~3.16 cycles (50.5 ms)

– Secure: able to distinguish between internal and external (through) faults

• Allows the individual breaker to trip first to maximize system reliability

Page 62: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Bus protection

August 6, 2020 Slide 62

Communication redundancy

– IEC 61850 Ethernet Redundancy – HSR High-availability Seamless Redundancy (self-healing ring)

– IEC 61850 Ethernet Redundancy – PRP Parallel Redundancy Protocol (double star network)

– Supports IEEE 1588 V2 precision time protocol (PTP) high-accuracy time sync of 1µs

67-1P/N

67-2P/N

Source #1

67-1P/N

67-2P/N

Source #2

67-1P/N

67-2P/N

Feeder #1 Feeder #2

67-2P/N

67-1P/N

Ethernet Switch

(Master)(Backup)

Ethernet Switch

Page 63: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Appendix CApplication areas from components to solutions

Page 64: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Single-line diagram applications

August 6, 2020 Slide 64

MTM Configuration

Loads – 500HP motor, long feeder, secondary selective substations/ low voltage switchgear

Without digital switchgear - extensive wiring of I/O for controls, PT wiring between cubicles for bus voltage monitoring

Ferro resonance on PT’s, CT saturation studies

REF615 Conf N

67P/51P/50P50BF67G/51G/50G2727R25AFD

Y

Y ∆or

3

52

3

REF615 Conf N

67P/51P/50P50BF67G/51G/50G2727R25AFD

52

Y

Y ∆or

3

3

REF615 Conf B

51P/50P50BF49M51LR/6627/27PS59RTDAFD

3

M

52

3

REF615 Conf F

51P/50P50BF67/51G/50GAFD

3

3

REF615 Conf D

51P/50P50BF67/51G/50GAFD87L

3

52

REF615 Conf F

51P/50P50BF67/51G/50GAFD

3

52

1 1

52

52Y ∆or 3

500HPLong

Feeder

Y ∆or

3 3REF615 Conf P

67P/51P/50P50BF67N/51N/50N2727R25AFD

Page 65: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Bus protection application

August 6, 2020 Slide 65

Relays that support IEC 61850-9-2LE provide real-time sharing of information accurate enough for protection and control

In this example, voltage samples are shared at rate of 80 samples per cycle for protectionBus-bar protection can be achieved using Zone Selective Interlocking (ZSI) scheme through GOOSE messaging

Sensors are immune to CT saturation and ferro resonance

REF615 Conf L

67P/51P/50P50BF67G/51G/50G2727R via IEC 61850-9-2LE25 via IEC 61850-9-2LEAFD

REF615 Conf L

67P/51P/50P50BF67G/51G/50G2727R via IEC 61850-9-2LE

25 via IEC 61850-9-2LE

AFD

Y

Va, Vb, Vc

52

31

52

Y

M

52

REF615 Conf L

51P/50P50BF67/51G/50GAFD52

REF615 Conf L

51P/50P50BF67/51G/50GAFD5252

52

500HPLong

Feeder

Va, Vb, Vc

31

31 31 31 31REF615 Conf D

51P/50P50BF27R46R66/51 LRS49MAFDRTD – via RI 0600

REF615 Conf E

51P/50P50BF67/51G/50GAFD87L

REF615 Conf L

67P/51P/50P50BF67N/51N/50N2727R via IEC 61850-9-2LE

25 via IEC 61850-9-2LE

AFD

Va, Vb, Vc Va, Vb, Vc

31

IEC 61850 9-2LE (SV), GOOSE

GFCT

Voltage Sensors

Current Sensors31

Va, Vb, Vc

Page 66: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Line protection application

August 6, 2020 Slide 66

REF615 Conf L

67P/51P/50P50BF67G/51G/50G2727R via IEC 61850-9-2LE

25 via IEC 61850-9-2LEAFD

REF615 Conf L

67P/51P/50P50BF67G/51G/50G2727R via IEC 61850-9-2LE

25 via IEC 61850-9-2LEAFD

Y

Va, Vb, Vc

52

31

52

Y

M

52

REF615 Conf L

51P/50P50BF67/51G/50GAFD

52

REF615 Conf L

51P/50P50BF67/51G/50GAFD5252

52

500HP

Long Feeder

Va, Vb, Vc

31

31 31 31 31REF615 Conf D

51P/50P50BF27R46R66/51 LRS49MAFDRTD – via RI 0600

REF615 Conf E

51P/50P50BF67/51G/50GAFD87L

REF615 Conf L

67P/51P/50P50BF67N/51N/50N2727R via IEC 61850-9-2LE

25 via IEC 61850-9-2LE

AFD

Va, Vb, Vc Va, Vb, Vc

31

Y

3

REF615 Conf D

51P/50P50BF67/51G/50GAFD87L52

M M

87L

SSC600Centralized Protection, Control

– Voltage Protection– Current Protection– FrequencyProtection– Line Differential– Line Distance

IEC 61850 9-2LE (SV), GOOSE

GFCT

Voltage Sensors

Current Sensors31

Va, Vb, Vc

Page 67: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Appendix DSmart substation control and protection

Page 68: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Smart substation control and protection

August 6, 2020 Slide 68

– Centralized, protection and control in one single device at a Substation level for reduced network complexity

– Ease of adding additional functions, changing protection philosophy after commissioning of apparatus

– Back-up protection provided by individual merging unit relay in switchgear

– Lower total cost of ownership of “protection and control system”

– Fully modular software for maximum flexibility during the entire lifetime of the substation

– Parallel Redundancy Protocol (PRP) provides additional redundancy in communication and protection scheme

Control Center

COM600Gateway

Primary IEEE 1588 v2GPS master clock

SMU615 MU as backupIEEE 1588 v2 master

SSC600

Page 69: Digital switchgear concepts for MV applications · Digital switchgear concepts for MV applications ... Digital switchgear is based on well-proven switchgear platform, but uses sensors

—Smart substation control and protection

August 6, 2020 Slide 69

Base protection functionality

Feeder/line protection

Power transformer protection Machine protection Power quality measurements

Interconnection protection On-load tap changer control Arc protection option

– Protection against arc flash– Light sensing in merging units

– Position indication– Voltage regulation– Line drop compensation

– Protection of interconnection points of distributed generation units

– Extensive earth-fault protection– Fault locator– Distance protection

– Overcurrent– Earthfault– Fault recorder– Switchgear control– Voltage– Frequency

– Protection for two winding power transformers

– Protection of asynchronous machines

– Current and voltage distortions– Voltage variation– Voltage unbalance