dijagram reduktora pritiska

4
Data sheet 700003 englisch (english) ARI-PREDU ® Sizing diagram for water Edition 12/07 - Data subject to alteration Volumetric flow Differential pressure Δp Example: Volumetric flow = 24 m 3 /h ∆p = 4 bar ----------------------------------------------- 24 m 3 /h x Factor 1,25 = 30 m 3 /h choosen DN40

Upload: darko-kocic

Post on 15-Nov-2015

213 views

Category:

Documents


1 download

DESCRIPTION

dIJAGRAM REDUKTORA PRITISKA

TRANSCRIPT

  • Data sheet 700003 englisch (english)

    ARI-PREDU Sizing diagram for water

    Edition 12/07 - Data subject to alteration

    Volu

    met

    ric fl

    ow

    Differential pressure p

    Example:Volumetric flow = 24 m3/hp = 4 bar ----------------------------------------------- 24 m3/h x Factor 1,25 = 30 m3/hchoosen DN40

  • 2ARI-PREDUSizing diagram for saturated steam

    Edition 12/07 - Data subject to alteration

    Downstream pressure

    Example:Steam flow = 1200 kg/hUpstream pressure = 10bar / Downstream pressure = 8bar ---------------------------------------------------------------- 1200 kg/h x Factor 1,25 = 1500 kg/h choosen DN40

    Stea

    m fl

    owIn

    let p

    ress

    .

  • ARI-PREDUPipe sizing for saturated steam

    Edition 12/07 - Data subject to alteration

    Stea

    m fl

    ow at

    25 m

    /s (8

    2ft/s

    ) ste

    am ve

    locit

    y

    Diam

    eter

    of t

    he st

    eam

    pip

    e

    Steam pressure (barg)

    Example:Steam upstream pressure = 10 bar(g) Steam downstream pressure = 4 bar(g) Steam flow = 5000 kg/h choosen upstream pipe = DN125 choosen downstream pipe = DN200

  • 4Technology for the Future. G E R M A N Q U A L I T Y V A L V E S

    ARI-Armaturen Albert Richter GmbH & Co. KG, D-33756 Schlo Holte-Stukenbrock, Tel. +49 52 07 / 994-0, Telefax +49 52 07 / 994-158 or 159 Internet: http://www.ari-armaturen.com E-mail: [email protected]

    ARI-PREDUFlow velocity in pipelines

    Edition 12/07 - Data subject to alteration

    Max. Flow velocity:Liquids 5 m/s (16 ft/s)Gases and saturated steam 25 m/s (82 ft/s)Superheated steam 50 m/s (162 ft/s)

    Volu

    met

    ric fl

    ow q

    v

    Speed

    ARI-PREDU Sizing diagramSizing diagram for waterSizing diagram for saturated steamPipe sizing for saturated steam

    ARI-PREDU Pressure reducing valveARI-PREDU-ANSI Pressure reducing valve