dirana application guide - measuring and analyzing power transformers

Upload: deal-achmad-fadeal

Post on 01-Mar-2018

676 views

Category:

Documents


114 download

TRANSCRIPT

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    1/33

    DIRANA

    Application Guide

    Measuring and Analyzing the Dielectric

    Response of a Power Transformer

    This application guide informs how to measure and

    analyze the dielectric response of power

    transformers in order to reliably assess the moisture

    content of the paper and pressboard insulation.

    June 2008

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    2/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 2/33

    OMICRON electronics 2008. All rights reserved.

    This Application Guide is a publication of OMICRON electronics GmbH. All rights including

    translation reserved. Reproduction of any kind, e.g., photocopying, microfilming or storage in

    electronic data processing systems, requires the explicit consent of OMICRON electronics.Reprinting, wholly or in part, is not permitted. This Application Note represents the technical status

    at the time of printing. The product information, specifications, and all technical data contained

    within this Application Note are not contractually binding. OMICRON electronics reserves the right to

    make changes at any time to the technology and/or configuration without announcement.

    OMICRON electronics is not to be held liable for statements and declarations given in this

    Application Note. The user is responsible for every application described in this Application Note

    and its results. OMICRON electronics explicitly exonerates itself from all liability for mistakes in this

    document.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    3/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 3/33

    Contents

    1 Using This Document ............................................................................................................ 5

    1.1 Operator Qualifications and Safety Standards ...................................................................5

    1.2 Safety Measures................................................................................................................5

    1.3 Related Documents ........................................................................................................... 5

    2 Preparing the Transformer....................................................................................................6

    2.1 Disconnection from the Network ........................................................................................ 6

    2.2 Gathering Transformer Data..............................................................................................6

    2.2.1 Insulation Temperature.................................................................................................6

    2.2.2 Nameplate Data ........................................................................................................... 7

    2.2.3 Oil Tests....................................................................................................................... 8

    2.2.4 Environmental Conditions.............................................................................................9

    2.2.5 Other Information ......................................................................................................... 9

    3 Connecting DIRANA to the Transformer..............................................................................9

    3.1 Basic Measurement Circuit Guarding Principle ............................................................... 9

    3.2 General Procedure .......................................................................................................... 10

    3.3 Wiring Diagram for Various Winding Set-Ups ..................................................................12

    3.3.1 Two Winding Transformer .......................................................................................... 12

    3.3.2 Three Winding Transformer........................................................................................12

    3.3.3 Autotransformer.......................................................................................................... 13

    3.3.4 Shunt Reactor ............................................................................................................ 13

    3.4 Which HV Devices Can Be Left Connected? ...................................................................14

    4 Setting Up the Software....................................................................................................... 16

    5 Performing the Measurement.............................................................................................. 18

    5.1 Development of the Dissipation Factor Curve .................................................................. 18

    5.2 Measurement Errors ........................................................................................................19

    6 Interpreting the Dielectric Response in Frequency Domain ............................................. 21

    7 Moisture Analysis Using DIRANA....................................................................................... 24

    7.1 Principle of Moisture Analysis .......................................................................................... 24

    7.2 Step by Step Guide for Moisture Analysis........................................................................ 25

    7.3 Analysis of a Measurement with Limited Frequency Range............................................. 27

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    4/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 4/33

    8 Assessing the Analysis Results ......................................................................................... 28

    8.1 Assessment According to IEC 60422............................................................................... 28

    8.2 Transformer Drying..........................................................................................................29

    8.3 Accuracy of Analysis Results........................................................................................... 30

    8.4 Comparison to Other Moisture Measurement Techniques ............................................... 31

    9 Literature .............................................................................................................................. 32

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    5/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 5/33

    1 Using This Document

    This application guide provides detailed information on how to measure and to analyze the

    dielectric response of an oil-paper-insulated power transformer using OMICRON DIRANA. Please

    refer to national and international safety regulations relevant to working with DIRANA. The

    regulation EN 50191 "The Erection and Operation of Electrical Test Equipment" as well as all the

    applicable regulations for accident prevention in the country and at the site of operation has to be

    fulfilled.

    1.1 Operator Qualifications and Safety Standards

    Working on HV devices is extremely dangerous. The measurements described in this Application

    Guide must be carried out only by qualified, skilled and authorized personnel. Before starting to

    work, clearly establish the responsibilities. Personnel receiving training, instructions, directions, oreducation on the measurement setup must be under constant supervision of an experienced

    operator while working with the equipment. The measurement must comply with the relevant

    national and international safety standards listed below:

    EN 50191 (VDE 0104) "Erection and Operation of Electrical Equipment"

    EN 50110-1 (VDE 0105 Part 100) "Operation of Electrical Installations"

    IEEE 510 "Recommended Practices for Safety in High-Voltage and High-Power Testing"

    LAPG 1710.6 NASA "Electrical Safety"

    Moreover, additional relevant laws and internal safety standards have to be followed.

    1.2 Safety Measures

    Before starting a measurement, read the safety rules in the DIRANA User Manual and observe the

    application specific safety instructions in this Application Note when performing measurements to

    protect yourself from high-voltage hazards.

    1.3 Related Documents

    Title Description

    DIRANA User Manual Contains information on how to use the DIRANA

    test system and relevant safety instructions.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    6/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 6/33

    2 Preparing the Transformer

    2.1 Disconnection from the Network

    For a dielectric response measurement, the transformer needs to be switched off and then

    disconnected from the network. All connections to the HV, MV and LV bushings should be

    removed in a similar as to conventional dissipation factor tests. If complete disconnection is

    impossible, please refer to p. 14.

    After switching off it is not necessary to wait for a cool down period or for moisture equilibrium.

    However, in order to avoid rapid temperature changes, the cooling system should be off during the

    measurement.

    2.2 Gathering Transformer Data

    2.2.1 Insulation Temperature

    Various data provide useful information in order to reliably assess the condition of a transformer.

    The temperature of the insulation is of essential importance for moisture analysis and, therefore,

    should be carefully noted. To measure this value, the oil temperature may be used. As an

    example, Figure 1 depicts the temperature distribution in a large power transformer with ONAN

    cooling. The top oil temperature best correlates with the average insulation temperature.

    Ambient

    20C

    72C98C

    Average

    winding

    83C

    63C

    54C

    Cooling

    system

    74C

    92C

    Bottom oil Bottom winding

    Top oilHot spot

    Top winding

    Average

    oil

    Figure 1: Exemple of

    temperature distribution in

    a large power transformer

    with ONAN cooling

    according to IEC 60354

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    7/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 7/33

    Temperature from Oil Sample

    The most accurate way to determine the top oil temperature is to take an oil sample and measure

    the temperature directly on-site of that oil. After opening the valve, colder oil trapped in the valve

    will flow out at first, thus, wait for sufficient time in order to get a representative reading.

    Temperature from Build-In Temperature Gauge

    If direct sampling of the oil is not possible, the temperature of the built-in temperature gauge may

    be used. This, however, may display inaccurate readings depending on the place, where the

    temperature probe is located. Figure 2 depicts a build-in temperature gauge of a transformer.

    Taking photographs helps for later data analysis and documentation.

    Figure 2: Built-in temperature gauge displaying the top oil

    temperature; in this case 42C

    Temperature from Contact ThermometersAnother way to determine the top oil temperature is to place a contact thermometer on top of the

    transformer tank.

    Temperature from Winding Resistance Measurement

    The winding temperature may also be calculated using winding resistance measurement. From the

    difference between the winding resistance during the dielectric response measurement and that in

    the workshop at ambient temperature the winding temperature may be calculated.

    Temperature Change during Measurement

    If the transformer has been switched off prior to the measurement, the temperature will slowly

    decrease. Typical temperature time constants for power transformers are 1-2 Kelvin/h. Since a

    dielectric response measurement takes typically less then 1 h, in maximum 3 h, the decrease in

    temperature will be of minor importance. However, the cooling systems must be turned off.

    2.2.2 Nameplate Data

    The transformer nameplate displays the winding configuration which is essential information for

    making correct connect of the DIRANA instrument. Beside this, the year of manufacture and the

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    8/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 8/33

    voltage ratio help to check the consistency of the subsequent moisture analysis. Taking a

    photograph of the nameplate, again, helps in the documentation process.

    2.2.3 Oil Tests

    The Operators of power transformers depend heavily on the periodic sampling of the oil. The

    screening consists of several parameters that are of particular interest with regard to the dielectric

    response measurement:

    Acidity

    High acidity reflects paper and oil aging and often increases the oil conductivity. It takes a

    certain quantity of an alkaline material to neutralize these acids. A standard method that is

    used to find this quantity neutralization number, is to mix potassium hydroxide (KOH) with

    the acid/oil until it is neutralized, and is measured in milligrams of KOH per gram of oil.

    [ASTM D974, D664, D1534]. New oils have an acidity below 0.05 mg KOH / g oil. It

    increases with aging to 0.5 and above. The conductivity of oil is influenced by acids and

    given in Siemens per meter, that is S / m or 1/ / m. New oils have around 0.05 pS/m and a

    conductivity of above 20 pS/m at ambient temperature points on a progressed aging state.

    Water in oil

    Since the water content in oil in ppm strictly depends on temperature, no levels of permitted

    moisture concentration based on ppm can be given. By applying the water content in oil

    (ppm) and the sampling temperature (C) to a moisture equilibrium diagram (Figure 3) a

    very rough estimation of moisture content in paper can be made. Since aging of oil and

    paper shifts the equilibrium curves, this method overestimates moisture in paper. This

    especially applies if the acidity and / or oil conductivity are high. To overcome the influence

    of oil aging, water saturation in oil (%) instead of water content in oil (ppm) can be used [3].

    0

    1

    3

    4

    5

    0 10 20 30 40 50

    Moisture in oil / ppm

    Moistureincellulose/%

    2

    Solubility in oil / ppm20 50 80 120

    260

    500

    880

    0C 20C 30C 40C

    60C

    80C

    100C

    Figure 3: Moisture equilibrium

    curves based on moisture

    content in oil in ppm (redrawn

    according to the original source

    [1]). Note, that these diagrams

    usually overestimate moisture

    content in paper.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    9/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 9/33

    Moistureinagedpressboard/%

    Moisture relative to saturation / %

    0

    1

    2

    3

    4

    5

    6

    0 10 20 30 40

    21C

    40C60C

    80C

    Figure 4: Moisture equilibrium

    diagram based on moisture

    saturation in oil [2]

    2.2.4 Environmental Conditions

    In case the transformer was out of service, the ambient temperature helps to judge about the

    accuracy of the build-in temperature gauge.

    The relative humidity in the air and possible rain should be noted. Wet bushings increase the guard

    current and may lead to a negative dissipation factor. This is especially important, if an insulation

    system to ground is measured (CLor CH).

    2.2.5 Other Information

    If available, take note of the setup of the main insulation (number and diameter of barriers and

    spacers). Since the position of the tap changer may influence the high frequency portion of the

    dissipation factor trace, note the tap changer position.

    3 Connecting DIRANA to the Transformer

    3.1 Basic Measurement Circuit Guarding Principle

    A dielectric response measurement is a three terminal measurement that includes the output

    voltage, the measured current and a guard. Generally, the output voltage should be connected to

    the bushing, which is mostly exposed to electromagnetic disturbances. Guarding is required to

    prevent disturbances due to unwanted current paths as caused by dirty bushings and unwanted

    electromagnetic fields.

    Figure 11 illustrates the principle of guarding. Without guarding, the ammeter measures the current

    through the insulation volume Ivolandthe unwanted current over the insulation surface Isur. After

    applying a guard wire, the unwanted current Isurwill bypass the ammeter and flow directly to the

    voltage source.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    10/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 10/33

    Insulationunder test

    ~

    A

    IVolISur

    IVol + ISur

    Insulation

    under test~

    A

    IVolISur

    IVol

    ISur

    Figure 5: A dielectric response measurement without guarding (left) and with guarding (right)

    Figure 6 illustrates the guarding principle for a power transformer. Here the currents over dirty

    bushings will not be measured by the instrument. Additionally, the transformer tank and the

    shielded measurement cables will prevent electromagnetic field coupling.

    Guard

    CHLCL

    LV HV

    A

    Voltage source

    Current sense 1AInstrum

    ent

    CH

    =

    IVol

    ISur

    IVol

    ISur

    Figure 6: Guarding principle applied to a

    power transformer

    3.2 General Procedure

    This section gives illustrated introductions how to connect the DIRANA to a power transformer.

    Please refer also to the user manual.

    1. In order to have the same reference potential, connect the grounding cable to the ground

    terminal on the rear panel of the DIRANA, and clamp its other end to the transformer tank.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    11/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 11/33

    2. Next, connect all HV bushings to each other. Do the same for all LV bushings.

    3. After this, connect the cable for the voltage output (yellow) to the HV bushings and the

    cable for the input channel (red) to the LV bushings.

    4. Connect the guard of bothmeasurement cables to the transformer tank. Insure a good

    connection, avoid lacquered surfaces or corroded metal.

    5. Finally, plug the measurement cables into the DIRANA instrument.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    12/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 12/33

    3.3 Wiring Diagram for Various Winding Set-Ups

    3.3.1 Two Winding Transformer

    To determine the water content of the main insulation, the capacitance between HV and LV

    winding CHL provides the most valuable information. The wiring diagram is the same for three

    phase transformer as for single phase (Figure 7).

    A

    A

    V

    Output

    CH1

    CH2

    single channel mode

    CH1: UST-A CHL - Measurement of the main insulation (LV - HV)

    CHL

    CL CH

    Figure 7: Typical measurement set-up for a two winding transformer

    3.3.2 Three Winding Transformer

    For a three winding transformer with HV, MV and LV winding (or tertiary winding), both current

    measurement channels can be used simultaneously. Figure 8 depicts this connection. The

    measurement voltage is applied to the winding which is located in between the other two windings.

    Capacitance measurements help to identify the location of the windings.

    CHT

    CLT CHL

    CT CL CH

    A

    A

    V

    Output

    CH1

    CH2

    dual channel modeCH1: UST-A CHL - Measurement of the insulation LV- HV

    CH2: UST-B CLT - Measurement of the insulation LV- TV

    Figure 8: Typical measurement set-up for a three winding transformer

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    13/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 13/33

    3.3.3 Autotransformer

    For an autotransformer, the measurement voltage should be connected to the (internally

    connected) HV and LV winding and the input channel to the tertiary winding. In case, the tertiary

    winding cannot be reached, use the same connection as for the shunt reactor, p. 13.

    single channel modeCH1: UST-A CHT - Measurement of the insulation HV- TV

    A

    A

    V

    Output

    CH1

    CH2

    CHT

    CT CH

    Figure 9: Measurement set-up for an autotransformer with tertiary winding

    3.3.4 Shunt Reactor

    A shunt reactor contains only one single winding per phase, not two, as for normal power

    transformers. Instead of measuring the capacitance between windings CHL, the capacitance of thesingle winding to ground CHwill be measured. Therefore, the guarding technique (voltage to HV,

    current from LV and guard to tank) cannot be used. Since the capacitance of the bushings to tank

    will not be guarded, the measured losses will be higher than the losses of the internal capacitance

    CHonly. Depending on the condition of the bushing (surface wetness, dirt), this will result in an

    overestimation of moisture content. A typical overestimation compared to the "true" moisture

    content (m.c.) is 15 %; that means for example 2 % m.c. + 15 % = 2.3 % m.c.. Figure 10 displays

    the corresponding wiring diagram. In order to minimize disturbances, the voltage here is applied to

    the tank and the current is measured at the bushings. Depending upon the on-site conditions, theconnection with fewer disturbances might also be to apply the voltage to the bushings and

    measure the current at the tank.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    14/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 14/33

    CH

    single channel mode

    CH1: GST-A CH - Measurement of the insulation HV - Tank/Core

    A

    A

    V

    Output

    CH1

    CH2

    Figure 10: Measurement set-up for a shunt reactor or an autotransformer without tertiary winding

    3.4 Which HV Devices Can Be Left Connected?

    It is the best practice to completely disconnect the transformer from the network. However, if a

    complete disconnection is impossible, it must be distinguished between CHL and CH/CL

    measurements. The capacitance between the windings CHLprovides most valuable information for

    subsequent moisture determination. The high and low voltage winding capacitances to ground (CHand CL) are only useful if a measurement of CHLis impossible.

    Effect of Remaining HV Devices on Guarded CHL- Measurements

    While measuring the capacitance between windings CHL (voltage output to HV-winding, current

    input to LV or MV winding, guard to tank), the guarding technique prevents disturbing influences by

    still-connected devices. However, the following requirements must be fulfilled:

    Disconnect voltage transformers and neutral point impedances as they cause a short circuit

    to ground.

    Avoid overloading of the instrument due to high currents, e.g. long cables.

    The still-connected devices should have low capacitances and losses compared to the

    transformer insulation; otherwise high guard currents may cause a negative dissipation

    factor (p. 19).

    Avoid electromagnetic field coupling since the still-connected devices might act as

    antennas.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    15/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 15/33

    If these requirements are fulfilled, the instrument can attain the same accuracy as that of a

    complete disconnection. Figure 11 illustrates the effect of a still connected HV device C Extwhich is

    connected to ground / guard.

    ACurrent input

    Guard/Ground

    CLT CHLCT

    MVLV HV

    ~

    Voltage source

    CExtCH

    ACurrent input

    Guard/Ground

    CLT CHLCT

    MVLV HV

    ~

    Voltage source

    CExtCH

    Figure 11: Wiring diagram for a

    three winding transformer

    having an external device CExt

    still connected

    Effect of Remaining HV Devices on Not Guarded CH/CL- Measurements

    For CHand CLmeasurements (voltage output to HV/LV-winding, current sense to tank, guard to LV

    or MV winding if available) the still-connected HV devices will increase the losses and thus lead to

    an overestimation of moisture. This is especially ture for insulations having losses or impedances

    in the range of the transformer insulation.

    ~

    Current sense

    Guard

    Ground

    CLT CHLCT

    MVLV HV

    A

    Voltage source

    CExtCH

    Figure 12: Wiring diagram for CH

    - measurement having an

    external device CExtstill

    connected

    A measurement is of little value or impossible in case of

    Wet or dirty bushings

    Cables with paper / oil insulation

    Voltage transformers

    Whereas the following devices will have a minor influence:

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    16/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 16/33

    Short PE cables

    Short bus bars with high resistance to ground

    Other devices having low losses compared to the transformer insulation

    4 Setting Up the Software

    1. Connect DIRANA to one USB port of your laptop and start the DIRANA software. The

    status field in the lower right corner of the main window indicates that the connection is

    established.

    2. Press the button "Configure Measurement".

    3. By clicking the drop-down-list, choose the configuration that fits to your measurement

    specimen. You may also refer to the corresponding wiring diagram in order to connectDIRANA to the transformer.

    4. Click the settings tab and then enter 100 Hz as stop frequency. The section below will

    explain the required frequency ranges.

    5. After this, close the dialog field "Configure Measurement" by clicking on "OK".

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    17/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 17/33

    Required Stop Frequency for Subsequent Moisture Analysis

    For moisture analysis, the very low frequencies of the dissipation factor curve are required. The

    dissipation factor plotted over frequency shows a typical s-shaped curve (Figure 13). With

    increasing moisture content, temperature, or aging, the curve shifts towards higher frequencies.

    Moisture particularly influences the low frequency part. A change in the high frequency part occurs

    only for high water content. The middle part of the curve with the steep gradient reflects oil

    conductivity. Insulation geometry determines the local maximum or "hump" on the left-hand side of

    the steep gradient. In order to determine the moisture content of the insulation, the measurement

    should provide the point of inflection on the left-hand side of the area dominated by insulation

    geometry. There, the properties of the cellulose insulation and its water content dominate.

    high

    low

    oil

    conductivity

    moisture and aging

    of cellulose

    high

    high

    low

    low

    0,001 0,01 1 100

    0,001

    0,01

    0,1

    1

    1000

    Frequency [Hz]

    Dissipationfactor

    insulationgeometry high

    low

    oil

    conductivity

    moisture and aging

    of cellulose

    high

    high

    low

    low

    0,001 0,01 1 100

    0,001

    0,01

    0,1

    1

    1000

    Frequency [Hz]

    Dissipationfactor

    insulationgeometry

    Figure 13: Interpretation scheme of a dissipation

    factor curve providing discrimination between

    the influences of moisture, aging, oil

    conductivity and insulation geometry

    The position of the area influenced by moisture in cellulose and, consequently, the frequency

    range required for the specific insulation depends on the condition of the insulation. Dry or cold

    insulations require measuring down to very low frequencies, i.e. 100 Hz. For hot or highly

    conductive insulations, the stop frequency can be much higher; e.g. 0.1 Hz.

    As the condition of the transformer to be measured is unknown in most cases, set the stop

    frequency to the lowest value, i.e. 100 Hz. Then, observe the dissipation factor curve during the

    measurement and stop the measurement when the "hump" and the point of inflexion on its left-

    hand side appear. See also the measurement example below.

    Note that for elevated temperatures the "hump" will not be as distinct as in Figure 13. The

    dissipation factor trace does not show such a clear local maximum, but rather, a slight point of

    inflexion (Figure 24).

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    18/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 18/33

    5 Performing the Measurement

    5.1 Development of the Dissipation Factor Curve

    After setting up the software and checking the measurement cables, press the "Send Configuration

    to Device and Start Measurement" button . During the running measurement do not move the

    cables since the piezoelectric effect may cause disturbing charges. The dissipation factor curve will

    appear, starting at the high frequencies, and developing toward the low frequencies.

    Figure 14: Dissipation factor curve starting at the

    high frequencies. The table at the top displays the

    values for the curser position, currently for power

    frequency.

    Figure 15: Dissipation factor curve after transition

    from time to frequency domain at 0.1 Hz.

    Figure 16: Complete dissipation factor curve.

    Sufficient data for subsequent moisture analysis

    were already available at 0.0005 Hz, corresponding

    to 40 minutes measurement time. The

    measurement could have been stopped at this

    point.

    During the measurement, DIRANA can be disconnected from the computer and the measurement

    will continue offline. After reconnection to the computer, the measurement results are loaded into

    the DIRANA software and displayed in the graphical view pane.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    19/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 19/33

    The measurement can be stopped when the "hump" and the point of inflexion on its left-hand side

    are measured; please refer to the explanations for Figure 13.

    5.2 Measurement Errors

    Voltage Source Overload

    If the instrument is not able to reach the desired voltage, an error message will indicate the

    instrument overload.

    To solve the problem:

    Check whether the measurement setup has resulted in a short-circuit.

    If capacitive currents cause an overload (typical for long cables), decrease the output

    voltage or start the measurement at lower frequencies than 1000 Hz; i.e. at 100 Hz.

    Input Overflow

    In case the software displays an input overflow error, check that the transformer and the DIRANA

    have the same reference potential. Usually this error appears when the transformer tank is on a

    floating potential. Connect the transformer tank to the ground terminal on the rear panel of the

    DIRANA (p. 10).

    Negative Dissipation Factor

    The dissipation factor curve may turn negative at high frequencies, see Figure 17. Reasons for this

    problem may be at first a high guard impedance, at second a small measured capacitance in

    conjunction with a large guard capacitance, at third high guard currents (dirty bushings) and at

    fourth the inductivity of coils.

    CHL

    f/Hz0.001 0.010 0.100 1.000 10.000

    DF

    0.0050.0100

    0.0500.100

    0.5001.000

    Figure 17: Dielectric measurement with negative

    dissipation factor

    To solve the problem:

    Connect all guards of measurement cables and if possible an additional wire from the

    triaxial connectors at the DIRANA front plate to the transformer tank.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    20/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 20/33

    Try to decrease the guard currents (clean bushings, disconnect all devices which are

    possibly still connected to the transformer).

    Check ratio of capacitances (measure adjacent windings only).

    Ensure a proper connection of the DIRANA housing to the reference potential, usually the

    transformer tank.

    Dip at the Transition from Time to Frequency Domain

    At the transition from time domain (PDC) to frequency domain (FDS) a dip may appear. Two

    reasons for this are possible: first a remaining polarization of the dielectric and second

    disturbances at in the time domain measurement.

    Figure 18 illustrates a dip caused by a remaining polarization. For this transformer, the resistance

    of the dielectric was tested with 5 kV DC prior to the dielectric response measurement using

    DIRANA. The remaining polarization shifts the time domain current and, consequently, the

    dissipation factor as displayed in frequency domain.

    f/Hz0.0010 0.0100 0.1000 1.0000 10.0000 100.0000

    DF

    0.007

    0.010

    0.020

    0.030

    0.050

    0.070

    0.100

    0.200

    0.0001

    Figure 18: Dip at the transition from

    frequency domain (FDS) to time

    domain (PDC)

    To solve this problem,

    Depolarize the dielectric by connecting the terminals of the HV and the LV bushings to each

    over and to the transformer tank. The depolarization time should be at least as long as the

    polarization time (duration, for which the voltage was applied), however this also depends

    on the applied voltage. After this, the DIRANA measurement can be repeated.

    Measure the dielectric response using DIRANA at first prior to the resistance test of the

    dielectric.

    Disturbances during Time Domain Measurement

    Disturbances in the time domain current are transformed into the frequency domain and affect the

    results displayed in frequency domain (e.g. dissipation factor). Figure 19 shows disturbances on

    the time domain current for 600-1100 s measurement time as an example. They cause

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    21/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 21/33

    disturbances in dissipation factor for the low frequencies. Generally, the disturbances in time

    domain will appear in frequency domain depending on their frequency spectrum.

    f/Hz0.0010 0.0100 0.1000 1.0000 10.0000

    DF

    0.020

    0.050

    0.100

    0.200

    0.500

    1.000

    2.000

    t/s2 5 10 20 50 100 200 500 1000

    I/A

    0.0000005

    0.0000007

    0.0000010

    0.0000020

    0.0000030HV+LV to tank HV+LV to tank

    Figure 19: Time domain current with disturbances at around 1000 s (left) and its transformation in

    frequency domain with disturbances at the low frequencies (right). The reason for the disturbances was

    that guarding was not applicable for this CL-measurement.

    To solve this problem,

    Use a guarded measurement set-up

    Apply all guards of the measurement cables

    Increase measurement voltage

    Try to minimize disturbances by e.g. using an electrostatic shield Perform the measurement in frequency domain only

    In the dialog field "Configure Measurement", click on the "Show Advanced Settings" button.

    Set the "Switch Frequency" to the same value as the "Stop Frequency", e.g. 100 Hz. Note

    that this increases the time duration for the measurement substantially.

    6 Interpreting the Dielectric Response in Frequency Domain

    The dielectric response of oil-paper-insulated power transformers consists of three components:The dielectric response of the cellulose insulation (paper, pressboard), the dielectric response of

    the oil and the interfacial polarization effect. The superposition of these three components follows

    in the dielectric response.

    Moisture, temperature, insulation geometry, oil conductivity and conductive aging by-products

    influence the dielectric response. The discrimination of moisture from other effects is a key quality

    feature for the analysis of dielectric measurements.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    22/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 22/33

    Superposition of Dielectric Properties

    Figure 20 displays the dissipation factor of only pressboard with a moisture content of 1, 2 and 3 %

    measured at 20C.

    f/Hz0.001 0.01 0.1 1.0 10.0 100

    DF

    0.005

    0.010

    0.020

    0.050

    0.100

    0.200

    0.500

    1.000

    3%

    2%

    1%

    Figure 20: Dissipation factor of pressboard only

    having moisture content of 1, 2 and 3 %

    Figure 21 shows the dissipation factor of only oil with a conductivity of 1 pS/m measured at 20C.

    Note, that the losses are much higher as for pressboard and that the dissipation factor is just a line

    with a slope of 20 dB / decade.

    f/Hz0.001 0.010 0.100 1.00 10.00 100.00

    DF

    0.0001

    0.001

    0.01

    0.10

    1.00

    10.0

    Figure 21: Dissipation factor of oil only having a

    conductivity of 1 pS/m at 20C

    The dielectric properties of pressboard and oil are superimposed together with interfacial

    polarization. Interfacial polarization is typical for non-homogeneous dielectrics with different

    permittivity or conductivity. Here charge carriers such as ions accumulate at the interfaces, forming

    clouds with a dipole-like behavior. This kind of polarization is effective only somewhere below ten

    Hertz.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    23/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 23/33

    f/Hz0.001 0.010 0.100 1.000 10.000 100.000

    DF

    0.01

    0.03

    0.10

    0.30

    Pressboard

    Insulation

    Geometry

    Oil

    conductivity

    Pressboard

    Figure 22: Dissipation factor of pressboard and

    oil together with the interfacial polarization effect

    (insulation geometry)

    Figure 22 displays the dissipation factor of pressboard having 1 % moisture content and oil

    togetherwith the interfacial polarization effect (insulation geometry). The insulation geometry (ratio

    of oil to pressboard) determines the interfacial polarization effect. The frequency range of 1000-

    10 Hz is dominated by the pressboard. Oil conductivity causes the steep slope at 1-0.01 Hz. Theinterfacial polarization (insulation geometry) determines the local maximum or "hump" at 0.003 Hz.

    Finally, the properties of pressboard appear again at the frequencies below 0.0005 Hz. The

    frequency limits correspond to Figure 22, but will vary in a wide range with moisture, oil

    conductivity, temperature and amount of conductive aging by-products.

    Moisture especially increases the losses in the low frequency range of the dielectric response of

    pressboard. Thus, data on the left-hand side of the area dominated by interfacial polarization

    (insulation geometry) are required for a reliable moisture determination. The point of inflexion onthe left hand side of the area dominated by insulation geometry must be reached.

    Since pressboard also dominates the high frequency area above 10 Hz in Figure 22, it might

    appear that it is sufficient to measure this frequency range. However, moisture especially affects

    the low frequency branch of the dissipation factor curve. Figure 20 illustrates, that the high

    frequency part of the dissipation factor curve is very similar for different moisture contents, but the

    low frequency part differs. Consequently, if the measurement range is restricted to the high

    frequencies, the accuracy of water determination will be very low allowing only for a rough

    discrimination between wet and dry.

    If geometry data of the transformer are known, it is not necessary to measure down to these low

    frequencies. For example, for Figure 22, the measurement could be stopped at 0.001 Hz.

    Influence of Moisture and Temperature

    For increasing moisture content and oil conductivity, the curve shifts toward higher frequencies, but

    the shape remains similar. Figure 23 depicts the dissipation factor over frequency for 3 % moisture

    content and 10 pS/m oil conductivity. Figure 24 illustrates the influence of temperature on the same

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    24/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 24/33

    insulation system. At 50C the losses of pressboard along with the oil conductivity increase while

    the shape of the curve remains similar.

    f/Hz0.001 0.010 0.100 1.000 10.000 100.00

    DF

    0.01

    0.02

    0.10

    0.20

    1.00

    Figure 23: Dissipation factor of an oil-paper-

    insulation with pressboard having 3 % moisture

    content and oil with a conductivity of 10 pS/m

    f/Hz0.001 0.010 0.100 1.000 10.00 100.00

    DF

    0.01

    0.05

    0.10

    0.50

    1.00

    5.00

    10.00

    Figure 24: Dissipation factor at 50C of an oil-

    paper-insulation with pressboard having 3 %

    moisture content and oil with a conductivity of

    43 pS/m

    For the measurement as shown in Figure 23, sufficient data for subsequent moisture analysis wasavailable at 0.0021 Hz, corresponding to a measurement time of 14 minutes. At this frequency the

    only properties of pressboard appear, which is the prerequisite for accurate moisture analysis.

    Finally, for the elevated temperature of 50C of Figure 24, the measurement could have been

    stopped at 0.01 Hz.

    7 Moisture Analysis Using DIRANA

    7.1 Principle of Moisture Analysis

    Moisture determination is based upon a comparison of the transformer's dielectric response to a

    modelled dielectric response. A so-called XY model combines the dielectric response of

    pressboard as taken from a database with that of oil with regard to the insulation temperature. A

    fitting algorithm rearranges the modelled dielectric response and delivers moisture content and oil

    conductivity. The software will automatically compensate for the influence of conductive aging by-

    products. Figure 25 depicts the programming flowchart of the analysis algorithm.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    25/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 25/33

    Measurement Data base

    Temperature

    Oil XY-model

    moisture content,

    oil conductivity

    Comparison

    44C Model Curve

    f/Hz0.01 0.10 1.00 10.00 100.0

    DF

    0.005

    0.01

    0.02

    0.05

    0.10

    0.20

    0.50

    1.00

    Figure 25: Programming flowchart of the analysis algorithm

    7.2 Step by Step Guide for Moisture Analysis

    1. Select the Measurement

    Select the desired measurement in the measurement

    collection, and open the moisture assessment window by

    clicking on the Assessment button.

    2. Enter Variables

    For temperature compensation, type the insulation

    temperature into the corresponding field. For this

    measurement, it was 44C.

    The fields barriers (X - ratio of barriers to oil) and spacers

    (Y - ratio of spacers to oil) determine the insulation

    geometry. If data with a sufficient frequency depth were

    measured (3-5 points on the left hand side of the hump),

    the software would automatically calculate these values.

    Therefore, no numbers have to be entered.

    The oil conductivity will also be calculated automatically. If the oil conductivity is known, it can be

    entered taking into account the measurement temperature. Using the "Enter Conductivity at

    Different Temp." button, the conductivity can be recalculated to the insulation temperature.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    26/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 26/33

    All parameters with a check mark will be calculated automatically by the DIRANA software. The

    only parameter that is absolutely necessary is the insulation temperature.

    3. Automatic Assessment

    Press the "Start Assessment" button. The fitting algorithm arranges the parameters of the model

    (barriers X, spacers Y, oil conductivity, moisture content) in order to obtain the best fit between themodel curve and the measurement curve. Figure 26 displays the result of the automatic curve

    fitting.

    Figure 26: Assessment screen

    after automatic curve fitting

    In this example, the automatic curve fitting gives the result of 1.7 % moisture content, 9.3 pS/m oilconductivity, 20 % barriers and 14 % spacers.

    4. Optimizing the Moisture Analysis by Hand

    As the low frequencies on the left-hand side of the "hump" reflect moisture, a good fitting of this

    area should be observed. In this respect, Figure 26 leaves some room for improvements. Since

    insulation geometry causes the hump, decreasing the amount of barriers to 12 % gives a better

    fitting of this area. Consequently, the moisture content must be adjusted to 1.5 %.

    The automatic assessment gave a different result than the optimization by hand because the lower

    limit for barriers was set to 20 %. By setting the limit for barriers to 10 % in the "Advanced Limits

    for Automatic Assessment" tab, the automatic assessment comes to the same result as the

    optimization by hand.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    27/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 27/33

    Figure 27: Assessment screen

    after optimization by hand

    7.3 Analysis of a Measurement with Limited Frequency Range

    The moisture analysis reaches a high accuracy, if data of the low frequencies dominated by

    pressboard are available (Figure 22). Figure 28 depicts an example with a limited frequency range

    where the measurement was stopped too early; the low frequency properties of pressboard are

    invisible.

    f/Hz0.01 0.10 1.00 10.0 100.0

    DF

    0.005

    0.010

    0.020

    0.050

    0.100

    0.200

    0.500

    Figure 28: Dissipation factor curve without

    information on the left hand side of the "hump"

    To analyze such a measurement, some estimation of the geometric conditions will help. Set the

    geometry condition to fixed values of X = 30 % and Y = 20 %. The amount of barriers to oil X

    typically ranges from 15 to 55 % and of spacers Y from 13 to 24 %. Usually, older transformers

    contain a higher ratio of pressboard to oil (Figure 29). To estimate the ratio of solid to liquid

    insulation, one may also look at the high frequencies of 100-1000 Hz.

    After this, perform the automatic assessment and, if necessary, some optimization by hand as

    described above. For the example of Figure 28, the assessment result is then depicted in Figure

    30.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    28/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 28/33

    0

    10

    20

    30

    40

    50

    60

    70

    1960 1970 1980 1990 2000 2010

    Year of manufacture

    BarriersXin% 22 kV 65 kV

    110 kV 220 kV

    400 kV 500 kV

    autotransformer

    Figure 29: Ratio of barriers to

    oil X for various transformers

    depending on year of

    manufacture.

    Figure 30: Assessment result

    for a measurement with limited

    frequency range

    8 Assessing the Analysis Results

    8.1 Assessment According to IEC 60422

    The DIRANA software assesses the moisture concentration based on the classifications given in

    the IEC 60422 "Mineral insulating oils in electrical equipment Supervision and maintenanceguidance". The categories are:

    Category Moisture content in % Color

    Dry below 2,2

    Moderately wet 2,2-3,7

    Wet 3,7-4,8

    Extremely wet above 4,8

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    29/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 29/33

    IEC 60422 provides categories for moisture contamination of power transformers based on

    moisture saturation. Moisture saturation can be converted into moisture content using sorption

    isotherms (Figure 31). The IEC rates moisture saturations of more than 6 % as "moderately wet",

    which is equivalent to a moisture content of approximately 2.2 %. In this area the water molecules

    become more and more active, increasing the dangerous effects of water. At this level,

    maintenance actions such as drying should be considered, taking into account the importance and

    future operation of the transformer. Figure 31 shows the relationship between moisture content and

    moisture saturation and illustrates the categories of IEC 60422 in order to assess the results

    analyzed by DIRANA.

    Moistureco

    ntent[%]

    Moisture saturation [%]

    0

    1

    2

    3

    4

    5

    10 20 30

    21C

    80C

    Moderately

    wet

    Dry

    Wet,

    > 30 %extremelywet

    Moisture

    conta

    minatio

    n

    Figure 31: Moisture sorption isotherm for a

    cellulose material relating moisture saturation to

    moisture content with categories according to

    IEC 60422

    8.2 Transformer Drying

    Basically there are three approaches for the drying of power transformers: off-site oven drying, on-

    site drying and on-line drying.

    Off-Site Oven Drying

    Off-site oven drying is the traditional drying technique used for new transformers in the factory.

    High temperature applied together with low pressure dry the insulation. However, for an already

    installed transformer, the transportation to a workshop can be very expensive. Additionally, the

    transformer will be off-line for a considerable length of time.

    On-Site Drying

    For on-site drying techniques, the transformer will be left in the substation. Low frequency heating

    of the winding in combination with vacuum is one common on-site drying technique. A second

    technique uses hot oil spray together with vacuum. Both techniques are very effective but have the

    disadvantage that the transformer will be out of service during the maintenance action.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    30/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 30/33

    On-Line Drying

    Here on-line drying systems dry the oil through continuous circulation. The transformer can be left

    in service and the oil will regain its dielectric withstand strength very quickly. As the oil contains

    only a very small amount of water, typically half of 1 % of all the water in the transformer, this

    method of drying the solid insulation will take the long time of months up to years. Additionally,

    there is a risk that the inhibitors in the oil may be inadvertently removed.

    DIRANA can validate the efficiency of drying methods. Drying methods will at first affect the outer

    layers of the cellulose insulation and thus cause an inhomogeneous moisture distribution. In order

    to obtain a more realistic moisture distribution for moisture analysis by DIRANA, the transformer

    should be in operation and reach at least a top oil temperature of 50C. This procedure causes a

    homogenous moisture distribution and a reliable moisture analysis result.

    8.3 Accuracy of Analysis Results

    The analysis software will reliably calculate moisture content if the following conditions are fulfilled:

    Materials consist of oil and oil-impregnated paper/pressboard. An analysis of transformers

    without oil is possible as well; however the cellulose materials must be oil-impregnated.

    Measurement data on the left-hand side of the "hump" are available (Figure 22). This

    makes the analysis independent from the geometric setup and the oil conductivity of the

    specific insulation. The software will calculate the insulation geometry; the user doesn'thave to enter the data.

    No "direct" oil connection between the windings, at least one winding must be fully covered

    with paper/pressboard. This condition is surely fulfilled at voltages above 20 kV. In the other

    case the large influence of the oil gap might hide the properties of pressboard and paper. If

    this occurs, the dissipation factor curve will not have the specific shape of Figure 22.

    The following conditions influence the accuracy of moisture analysis:

    Very high temperature:

    Cellulose materials have different temperature dependent behavior. The temperature

    compensation of the software will perfectly compensate the influence of temperature if the

    materials inside the transformer are the same as in the data base. As this is rarely the case,

    an increase in temperature of 30 K can lead to an underestimation of moisture content of

    0.5 %. For example, the moisture analysis indicated 2.5 % moisture content for a

    transformer measured at 50C. Here the "true" moisture content may range from 2.5-3 %

    depending on the temperature characteristic of the material used.

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    31/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 31/33

    Low temperature:

    Temperatures below 10C involve the problems of a reliable temperature measurement and

    of the temperature dependent behavior of the cellulose materials used in the particular

    transformer.

    High oil conductivityAn oil conductivity of more then 20 pS/m at ambient temperature points on conductive

    aging by-products. These by-products increase the dielectric losses in a similar way as

    water and may lead to an overestimation of moisture. Without compensation the

    overestimation can be up to 1.5 % moisture content. DIRANA compensates for this

    influence, however an overestimation of moisture of up to 0.3 % may occur.

    8.4 Comparison to Other Moisture Measurement Techniques

    Oil Sampling with Equilibrium Diagrams

    By applying the water content in oil (ppm) and the sampling temperature (C) to a moisture

    equilibrium diagram only a very rough estimation of moisture content in paper can be made. Since

    aging of oil and paper shifts the equilibrium curves, this method essentially overestimatesmoisture

    content in paper . This especially applies if the acidity and / or oil conductivity are high.

    Dielectric Response Methods

    For the recovery voltage method RVM, the CIGR task force 15.01.09 stated: "For the RVM

    technique, the old interpretation based only on simple relationship between the dominant time

    constant of the polarization spectrum and the water content in cellulose is not correct" [4].

    The newer methods of polarization and depolarization currents (PDC) and frequency domain

    spectroscopy (FDS) are based on a comparison of the measured dielectric response to a modeled

    dielectric response. As the data base of the modeled dielectric response was scaled with different

    Karl Fischer titration techniques, the moisture contents as analyzed by these methods may differ

    as well.

    Paper Samples and Karl Fischer Titration

    Taking paper samples offers a good opportunity to validate dielectric response methods. On the

    other hand, three restrictions apply:

    Sampling procedure

    During paper sampling and transportation to the laboratory, moisture from the atmosphere

    easily increases the moisture content of the sample. A few minutes of exposure to air

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    32/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    OMICRONelectronics GmbH 32/33

    makes the test useless. Therefore the sampling conditions may lead to an overestimation of

    moisture content.

    Comparability of Karl Fischer titration

    Karl Fischer titration suffers from a poor comparability between different instruments and

    laboratories [5]. The laboratory measuring the water content of paper samples may use adifferent instrument and procedure as the one used to scale the DIRANA data base.

    Consequently, the indicated moisture content might differ to a certain extend.

    Sample position

    The temperature distribution inside a power transformer causes a moisture distribution. The

    cold insulation structures (construction elements) accumulate water and the hot structures

    (winding paper) are drier. DIRANA will indicate an average moisture content of the barriers

    and spacers operated at oil temperature and the winding paper.

    Contact Technical Support

    In case of further questions, please contact OMICRON's technical support:

    Europe/Middle East/Africa [email protected]

    Phone: +43 5523-507-333

    Fax: +43 5523-507-7333

    North and South America [email protected]

    Phone: +1 713 830-4660 or 1 800 OMICRON

    Fax: +1 713 830+4661

    Asia/Pacific [email protected]

    Phone: +852 2634 0377

    Fax: +852 2634 0390

    9 Literature

    [1] T. V. Oommen: Moisture Equilibrium Charts for Transformer Insulation Drying Practice

    IEEE Transaction on Power Apparatus and Systems,Vol. PAS-103, No. 10, Oct. 1984, pp.

    3063-3067.

    [2] M. Koch, S. Tenbohlen, D. Giselbrecht, C. Homagk, T. Leibfried: Onsite, Online and Post

    Mortem Insulation Diagnostics at Power Transformers, Cigr SC A2 & D1 Colloquium,

    Brugge, Belgium 2007

  • 7/25/2019 DIRANA Application Guide - Measuring and Analyzing Power Transformers

    33/33

    DIRANA Application Guide Measuring and Analyzing the Dielectric Response of a Power Transformer

    [3] M. Koch, M. Krger: Moisture Determination by Improved On-Site Diagnostics, TechCon

    Asia Pacific,Sydney 2008, download at www.omicron.at

    [4] S. M. Gubanski et al.: Dielectric Response Methods for Diagnostics of Power

    Transformers CIGR Task Force 15.01.09, Technical Brochure 254,Paris, 2004

    [5] M. Koch, S. Tenbohlen, J. Blennow, I. Hoehlein: Reliability and Improvements of Water

    Titration by the Karl Fischer Technique Proceedings of the XVth International Symposium

    on High Voltage Engineering, ISH, Ljubljana, Slovenia, 2007