direct drive products 11-1-2011
TRANSCRIPT
Direct Drive Products
Magic AireMagic Aire
Air Handling Products Air Handling Products
Direct Drive – Vertical (DV)
Product Overview
DV Series (Direct Drive)
• 1 – 2.5 Tons
• Front Access
• 3-Speed PSC Motor
• 5-Speed ECM-VE Motor
• 2 & 4 Pipe CW/HW/DX
• Electric Heat (Access.)
• 4 - Row Cooling Coil
• 2 - Row HW Coil (Access.)
DVW / DVX Series
DV NOTESSIZE RANGE - TONS 1.0 - 2.5
SIZE RANGE - CFM 400 - 1000
ESP RANGE .10 - .50
AIR FLOW Vertical up flow - down flow optional
VOLTAGES 120/1 208- 240/1 277/1 No options
CW COIL ROWS/STD HAND 4 row - right hand no other options
~OPTIONAL HAND left hand
HW COIL ROWS/STD HND 2 row - right hand hot water coils are mounted in a seperate cabinet; and shipped separately;
~OPTIONAL HAND left hand assembly must be field mounted to discharge side of unit ( 2 sizes to select from)
DX COIL ROWS/STD HAND 4 row - right hand supplied with TXV (Chatleff threaded connection)
~OPTIONAL HAND left
~OTHER OPTIONS R410a refrigerant supplied with TXV (Chatleff threaded connection)
STEAM COIL Not Available
ELECTRIC HEAT Available - pricing and part number available on "by job" supplied as separate component to be field mounted - primary power brought to heater separately
basis currently KW range 1.0 - 10.0 depending on size of unit
HEATING COIL POSITION reheat only
FILTER TYPE 1" Throwaway
~OPTIONAL None
DRAIN PAN Galvanized
~OPTIONAL Stainless Steel
GAUGE OF CONSTRUCTION 20
STD INSULATION 3/4" Tuff skin I I - yellow fg w/black scrim coating
~OPTIONAL none
CONTROLS STD J - box mounting position follows the hand of the coil
~OPTIONAL None "XT w/fan relay; contactor" shown in current catalog is incorrect
ACCESSORIES 3 speed fan control switch, wall mount or unit mount Switch is field mount - shipped loose
Leg Kit - 4"
Direct Drive – Horizontal (DH)
Product Overview
DH Series
DH Series (Direct Drive)
• 1 – 2.5 Tons
• Bottom Access
• 3-Speed PSC Motor
• 5-Speed ECM-VE Motor
• 2 & 4 Pipe CW/HW/DX
• Electric Heat (field acc.)
• 4 or 6 - Row Cooling Coil
• 2 - Row HW Coil
DH NOTESSIZE RANGE - TONS 1.0 - 2.5
SIZE RANGE - CFM 400 - 1000
ESP RANGE .10 - .50
AIR FLOW Horizontal
VOLTAGES 120/1 208- 240/1 277/1 No options
CW COIL ROWS/STD HAND 4 row - right hand no other options
OPTIONAL HAND left hand
HW COIL ROWS/STD HAND 2 row - right hand hot water coils are mounted in a seperate cabinet and shipped separately;
OPTIONAL HAND left hand assembly must be field mounted to discharge side of unit ( 4 sizes to select from)
DX COIL ROWS/STD HAND 4 row - right hand supplied with TXV (Chatleff threaded connection)
OPTIONAL HAND left
OTHER OPTIONS R410a refrigerant supplied with TXV (Chatleff threaded connection)
STEAM COIL Not Available
ELECTRIC HEAT Available - pricing and part number available on "by job" supplied as separate component to be field mounted
basis currently KW range 1.0 - 10.0 depending on size of unit
HEATING COIL POSITION reheat only
FILTER TYPE 1" Throwaway
OPTIONAL None
DRAIN PAN Galvanized
OPTIONAL Stainless Steel
GAUGE OF CONSTRUCTION 20
STD INSULATION 3/4" Tuff skin I I - yellow fg w/black scrim coating
OPTIONAL None
CONTROLS STD J - box mounting position follows the hand of the coil
OPTIONAL None "XT w/fan relay; contactor" shown in current catalog is incorrect
ACCESSORIES 3 speed fan control switch, wall mount or unit mount Switch is field mount - shipped loose
Leg Kit - 4"
Direct Drive – Universal (DU)
Vertical – Horizontal Fan coil units 1 to 5 tons.
Product Overview
Vertical & Horizontal DX Fan Coil - 1.5 to 5 Tons
• 600 – 2,000 CFM
• 2 & 4 Pipe CW/HW
• 2, 3, or 4 Row HW Coil
• Electric Heat to 20KW
• 3 or 4 - Row CW or DX Coil
• 3 - Speed PSC Motors
• R-410A is 13 SEER Tested
DU Series
Vertical – Horizontal Fan coil units 1 to 5 tons.
Product Overview
Additional Features
• Threaded TXV’s for flexibility (and “NMD” option) – no brazing.
• Plug-in electric heat. Includes power switch.
• 5-Speed ECM-VE motor option – coming soon.
• “Vertical-only RH” drainpan standard.
DU Series
DU Series
DU NOTESSIZE RANGE - TONS 1.5 - 5.0
SIZE RANGE - CFM 600 - 2000
ESP RANGE .10 - .50
AIR FLOW Vertical/horizontal - field convertible
VOLTAGES 120/1 208/1 240/1 No options
208/1 units wired as 240/1 at the factory - XT wire connections must be changed in field
CW COIL ROWS 3 row or 4 row, slab type no other options; draw through
HW COIL ROWS 2, 3, or 4 row, slab type 2 row HW coils available on sizes 06 through 12 only; blow through
reheat position only; top connections
DX COIL ROWS/STD HAND 4 row, slab type supplied with TXV (Chatleff threaded connection)
~OTHER OPTIONS R410a refrigerant supplied with TXV (Chatleff threaded connection)
no metering device construction allows for field selection of refrigerant type - uses Chatleff threaded connection
STEAM COIL Not Available
ELECTRIC HEAT 3.0 - 20.0 KW depending on unit size reheat position only
electric heaters include circuit breaker style power switch - 15 & 20 KW have 2 circuits
power switch is a service switch - NEC requires branch service protection in addition
HEATING COIL POSITI ON reheat only
FI LTER TYPE 1" Throwaway
~OPTIONAL None
DRAIN PAN Galvanized, vertical with RH drain connections only
~OPTIONAL Stainless steel, vertical with RH drain connections only
Universal/horizontal type - galvanized
Universal/horizontal type - stainless steel
GAUGE OF CONSTRUCTI ON 20
STD I NSULATION 3/4" Tuff skin I I - yellow fg w/black scrim coating
~OPTIONAL none
CONTROLS STD 24 volt Multi- function controller Includes transformer, fan relay, terminal block w/ground lug - for chilled water cooling
Includes transformer, 2 fan relays, terminal block w/ground lug, and timer - for DX cooling
~OPTIONAL Multi- function controller w/hot water heat- low limit
Multi- function controller w/aquastat
M- F controller w/hot water heat- low limit & aquastat
ACCESSORIES Cabinet option for return air - right return bottom return is included as a standard construction feature
Cabinet option for return air - left return
Horizontal - Exposed (CE)
MagicAire Commercial Products.
CE Series Ceiling Exposed FCU s
• 200 – 1,200 CFM
• 2 & 4 Pipe CW/HW
• Electric Heat
• 3, 4, & 5 Row CW Coil
•1 & 2 Row HW Coil
• SS Drain Pan Option
• 3 - Speed PSC Motors
• 3 Speed Switch (field acc.)
• OA Damper Option
Product Overview
CE Series
CE (CA SED) NOTESSIZE RANGE - TONS .50 - 3.0
SIZE RANGE - CFM 200 - 1200
ESP RANGE .10 - .30 (for standard motors)
.20 - .60 (for high static motors)
AIR FLOW Horizontal
VOLTAGES 120/1 208- 240/1 277/1 No 277/1 for high static motors
CW COIL ROWS/STD HAND 3,4, & 5 row - right hand no other options
~OPTIONAL HAND left hand opposite hand configuration available for 4 pipe arrangement
( 3 & 4 row can be used as heating on 2 pipe systems) heating capacity ratings provided
HW COIL ROWS/STD HAND 1 & 2 row - right hand
~OPTIONAL HAND left hand opposite hand configuration available for 4 pipe arrangement
NOTE: ALL UNITS REQUIRE A MINIMUM OF 3 ROWS OF COIL WHEN SELECTED.
IF YOU HAVE A HEATING ONLY REQUIREMENT, YOU MUST USE A 3 ROW
COOLING COIL ON HEAT
DX COIL not available
STEAM COIL Not Available
ELECTRIC HEAT 1.5 - 2.5 KW @ 120/1 only only available in pre- heat arrangement; actual KW range for unit depends on size of unit
3.0 - 10.0 KW @ 240/1 able to be used with 5 row water coils
2.3 - 7.5 KW @ 208/1 (derated from 240v)
1.1 - 7.5 KW @ 208 volt
HEATING COIL POSITION preheat or reheat preheat only for electric heat units
FILTER TYPE 1" Throwaway
~OPTIONAL None
DRAIN PAN Galvanized
~OPTIONAL Stainless Steel
GAUGE OF CONSTRUCTION 18 - cabinet enclosure bottom return on cabinet is standard
~Other Options:
bottom return with rear outside air intake, no actuator
bottom return with rear outside air intake, with actuator
bottom return with top outside air intake, no actuator
bottom return with top outside air intake, with actuator
rear return only
STD INSULATION 1/2" Tuff skin I I - yellow fg w/black scrim coating
~OPTIONAL None
CONTROLS STD J - box
~OPTIONAL Hi static motor
ACCESSORIES 3 speed fan control switch, wall mount or unit mount Switch is field mount - shipped loose
outside air damper
~OTHER OPTIONS fan control with service disconnect not available on electric heat equipped units
service disconnect only not available on electric heat equipped units
24v control and timer
24v control, timer, and disconnect
Horizontal – Hideaway (CH)
MagicAire Commercial Products.
CH Series Hideaway FCU s
• 200 – 1,200 CFM
• 2 & 4 Pipe CW/HW/DX
• Electric Heat
• 3, 4, & 5 Row CW Coil
• 4 Row DX (600-1200cfm)
• 1 & 2 Row HW Coil
• SS Drain Pan Option
• 3 - Speed PSC Motors
• 3 Speed Switch (field acc.)
• Return Plenum option
Product Overview
CHW / CHX Series
CH (UN-CA SED) NOTESSIZE RANGE - TONS .50 - 3.0
SIZE RANGE - CFM 200 - 1200
ESP RANGE .10 - .30 (for standard motors)
.20 - .60 (for high static motors)
AIR FLOW Horizontal
VOLTAGES 120/1 208- 240/1 277/1 No 277/1 for high static motors
CW COIL ROWS/STD HAND 3,4, & 5 row - right hand no other options
~OPTIONAL HAND left hand opposite hand configuration available for 4 pipe arrangement
( 3 & 4 row can be used as heating on 2 pipe systems) heating capacity ratings provided
DX COIL 4- row right or left hand less TXV available for field- supplied TXV
HW COIL ROWS/STD HAND 1 & 2 row - right hand
~OPTIONAL HAND left hand opposite hand configuration available for 4 pipe arrangement
NOTE: ALL UNITS REQUIRE A MINIMUM OF 3 ROWS OF COIL WHEN SELECTED.
IF YOU HAVE A HEATING ONLY REQUIREMENT, YOU MUST USE A 3 ROW
COOLING COIL ON HEAT
DX COIL not available
STEAM COIL Not Available
ELECTRIC HEAT 1.5 - 2.5 KW @ 120/1 only only available in pre- heat arrangement; actual KW range for unit depends on size of unit
3.0 - 10.0 KW @ 240/1 able to be used with 5 row water coils
2.3 - 7.5 KW @ 208/1 (derated from 240v)
1.1 - 7.5 KW @ 208 volt
HEATING COIL POSITION preheat or reheat preheat only for electric heat units
FILTER TYPE 1" Throwaway
~OPTIONAL None
DRAIN PAN Galvanized
~OPTIONAL Stainless Steel
GAUGE OF CONSTRUCTION 18 - cabinet enclosure bottom return on cabinet is standard
~Other Options:
bottom return with rear outside air intake, no actuator
bottom return with rear outside air intake, with actuator
bottom return with top outside air intake, no actuator
bottom return with top outside air intake, with actuator
rear return only
STD INSULATION 1/2" Tuff skin I I - yellow fg w/ black scrim coating
~OPTIONAL None
CONTROLS STD J - box
~OPTIONAL Hi static motor
ACCESSORIES 3 speed fan control switch, wall mount or unit mount Switch is field mount - shipped loose
~OTHER OPTIONS fan control with service disconnect not available on electric heat equipped units
service disconnect only not available on electric heat equipped units
24v control and timer
24v control, timer, and disconnect
Magic Aire Commercial Products Competitive Cross Reference Chart May 15, 2008
MAGIC DUNHAM FIRSTAIRE IEC ETI AIRTHERM CARRIER BUSH CO. MCQUAY TRANE WILLIAMS YORK** TITUS
DV VEY CDV ? 42DDA CR-VC MB TSF ? HC-C DEVY VHC
DH HLY CDH(?) ? 42DAA CR-HB SHW SCD ? HHB, HHR DCY HHP
DU N/A ? CR-VC N/A N/A ? DCY(?) HHP, HHC
HB HBC H AHW 42BHC SH/WH CZC BCHC AHAHV DBY HAB
BV VBY V* AVW SV BCVC ? ? VAB
CH CHY HLF CC 42CAA CR-CB HBC THC FCCB HLB YHBC HBC
CE CXB HLE CB 42CGA CR-CC CHBC TSC FCDB CH/HLD YCHBC HBE
BM N/A HM/VM N/A 42BV CW(?) N/A N/A N/A MAB
BR N/A N/A N/A N/A N/A N/A N/A N/A RAB
FF FXY, FSY VF F, FP 42VBA VCB CR-FC FCBB LV-D YFA VBVFBVSB
* Also have models VB & VR** Nomenclature changing after purchase of ETI
NOTE: The above information is supplied as a guide as is not represented being accurate. No responsibility is implied or assumed regarding the information contained.
Magic Aire Commercial Products Competitive Cross Reference Chart 10/10/2005
MAGIC DUNHAM FIRST WILLIAMSAIRE IEC ETI AIRTHERM CARRIER BUSH CO. MCQUAY TRANE (LANCO) YORK TITUS
CHW CHY HLF CC 42CAA CR-CB HBC (1) (1) LH-B YHBC HBCCHW w/PL CPY HLP CA, CC w/PL 42CEA CR-CBP PHBC TSH FCCB LH-R YPHBC HBPN/A CBY N/A CR 42CKA CR-CT RHBC TSC FCEB LH-F YRHBC HBRCEW CXB HLE CB 42CGA CR-CC CHBC TSC FCDB LH-D YCHBC HBE
CHW w/HSM BHY N/A CC w/M24 MTR 42CFA CR-CBH HHS (1) (1) ON REQ. CCHY(4) HBC w/HSMCHW w/HSM BPY N/A CC w/PL M24 MTR 42CFA w/PL CR-CBHP HBC TSH w/HS MTR FCCB w/HS MTR ON REQ. CCHP(4) HBC w/HSM
FHW FHY VFC CF 42VAA CR-FB VCA TSB FCHB/FCAB LV-B YCA VBCFFW FXY VFE F, FP 42VBA CR-FC VFA TSF FCBB LV-D YFA VBFFSW FSY VFS SF 42VFA CR-FCS VSA TSF w/SLOPE FCIB LV-S YSA VBA
N/A LHA N/A (1) 42VCA CR-LFB N/A N/A FCKB (1) LCY(4) N/AN/A LXA N/A (1) 42VEA CR-LFC N/A N/A FCLB (1) LEY(4) VBL
N/A STY N/A PCF 42VGA SD N/A N/A N/A STW (2) N/A
DHW/DUW HHY CDH (1) 42DAA CR-HB HYB SHD N/A HH-B DCY(4) HHCDHW/DUW HPY CDH (1) 42DCA CR-HBP (1) SHD w/PL N/A HH-R DCPY(4) HHPN/A HXY N/A (1) 42DEA CR-HG (1) SCD N/A HH-C DEY(4) HHEN/A HLY N/A (1) 42DFA CR-HE (1) SCD N/A HH-D DELY(4) N/A
DVW/DUW VEY CDW (1) 42DDA CR-VC MH/MHE AVD N/A HC-C DEVY VHC
N/A MXY N/A N/A 42SHA SP-C N/A N/A N/A ER-D N/A N/AN/A MPY VHC GO 42SGA SP-B N/A HSB/HKD VHRA ER-B N/A VSR
N/A MAY/MBY VHA/VHB N/A 42SJA SP-DB N/A N/A N/A (1) N/A N/AN/A MMY/MSY VHM/VHS GM/GS 42SGA (M/S) SP-B (M/S) N/A HSB (TWIN) VHRA (2) N/A VSM/VSS
HBA HBC H/MQL AHW 42BHC N/A CHW (3)SCB/SHB BCHC AHAHV DBY HABBVW N/A VB/VR AVW N/A N/A N/A N/A BCVC N/A N/A VABBRW N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A RABBMW VBY MQL N/A 42BV N/A CVW N/A N/A N/A N/A MAB
Information contained in this chart is latest available.1. No information, may or may not be available.2. Available, no model information. 3. SHB has no cabinet - only base, blower, motor & coil.4. Not available after Sept. 30, 1996.