direct emission measurements on cast iron pipe

21
Direct Emission Measurements on Cast Iron Pipe Lillian L. Woolley, P.E. DTE Energy October 25, 2007

Upload: others

Post on 20-Feb-2022

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Direct Emission Measurements on Cast Iron Pipe

Direct Emission Measurements on Cast Iron Pipe

Lillian L. Woolley, P.E. DTE Energy

October 25, 2007

Page 2: Direct Emission Measurements on Cast Iron Pipe

OVERVIEW

• Background • Use of Hi-Flow Gas

Sampler • Second Study • Going Forward

2

Page 3: Direct Emission Measurements on Cast Iron Pipe

DTE Energy - MichCon

• DTE Energy is one of the nation’s largest diversified energy companies.

• Its largest operating units are Detroit Edison, an electric utility serving 2.2 million customers in SE Michigan, and MichCon, a natural gas utility serving 1.3 million customers in Michigan.

• MichCon, founded in 1849, is the fifth largest natural gas utility.

• MichCon is able to store 130 billion cubic feet of gas in naturally occurring underground rock formations.

3

Page 4: Direct Emission Measurements on Cast Iron Pipe

What is the issue?

• Cast Iron Pipe Replacement Program – 2500 Miles in 50 Years

• Increased Focus on GHG – Should we use emissions to help us prioritize?

• Little Emissions Data is available on Underground Pipe

• GRI/EPA study dated June, 1996 • MichCon Needs Better Quality Data!

4

Page 5: Direct Emission Measurements on Cast Iron Pipe

Why does cast iron pipe leak?

• Bell-and-spigot joints that connect pipe sections together tend to leak as pipe ages.

• Corrosion of pipe may also be an issue.

5

Page 6: Direct Emission Measurements on Cast Iron Pipe

Factors Affecting Leak Rate -GRI/EPA Study

• Stratifying variables were identified as:– Pipe use (service versus mains) – Pipe materials – Pipe age

6

Page 7: Direct Emission Measurements on Cast Iron Pipe

Factors Affecting Leak Rate -GRI/EPA Study

• Additional Factors: – System leak detection and repair programs – Pipe operating pressures – Distribution soil characteristics – Pipe diameter

7

Page 8: Direct Emission Measurements on Cast Iron Pipe

•EPA/GRI Test Procedure

• Leak was identified • Segment to be tested was capped off at the service-to-main

connection • A short segment of main (20 feet long) with a detectable leak

was isolated or • A longer segment with multiple leaks was isolated • Cast iron pipe was slightly different as many sections have

undetected leaks • Gas was metered to the section and the gas flow rate required to

maintain pressure was recorded • Separate work was completed on the oxidation of methane in

soil

8

Page 9: Direct Emission Measurements on Cast Iron Pipe

MichCon Emissions Study

• MichCon worked with Heath Consultants to establish a protocol for measuring leaks in underground pipe using a high-flow sampler.

• The study included: – Selection of several sites with different

characteristics (similar to the GRI/EPA study)

– Use of three different methods of enclosing leaks

9

Page 10: Direct Emission Measurements on Cast Iron Pipe

Funnel Method

10

Page 11: Direct Emission Measurements on Cast Iron Pipe

Issues associated with sampling

Funnel Method – • Many did not produce any measured sample

• May have been issues with the seal to the ground

• May have been venting over a wider range – even at the curb

• Cannot be used on city streets • Sampling could be improved with a much

larger funnel

11

Page 12: Direct Emission Measurements on Cast Iron Pipe

3-Hole Sampling Method

12

Page 13: Direct Emission Measurements on Cast Iron Pipe

Issued associated with sampling

Direct Measurement – 3-Hose Sampling Method

• Produced results – but still not sure entire leak was captured

• Even with this method, not sure steady-state was reached and pooled gas was not being measured

• MichCon employees felt maybe gas was being pulled out of pipe

13

Page 14: Direct Emission Measurements on Cast Iron Pipe

Tarp Enclosure Method

14

Page 15: Direct Emission Measurements on Cast Iron Pipe

Issues Associated with Sampling

Tarp Enclosure Method – • Need to test outside of tarp area to ensure all gas was

captured • Problems in areas between the curb and sidewalk • Issues with seal to the ground • Need a larger sample to adequately determine

effectiveness

15

Page 16: Direct Emission Measurements on Cast Iron Pipe

Leak Rate from Funnel Measurements

Leak Rate (cf/hr)

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

Leak

Rat

e (c

f/hr)

16

Page 17: Direct Emission Measurements on Cast Iron Pipe

Cast Iron Pipe Emissions Data

• GRI/EPA – 238 Mcf/mile

• DTE – 21,595 Mcf/mile

17

Page 18: Direct Emission Measurements on Cast Iron Pipe

Emissions Study

• As main services were renewed, service was transferred to the new main

• Meter was installed between the soon-to-be abandoned main and the existing system

• Gas to the isolated system was measured for 1.5 weeks to determine the leak rate

• One system – 0 gas leaks (580 feet)

• Second system – 16.7 cf/hr (1150 feet)

• Similar repair histories, etc.

18

Page 19: Direct Emission Measurements on Cast Iron Pipe

Going Forward

• Additional main renewal emissions collection

• Better Repair HistoryTracking

• Additional Information on Leaks Collected

• Newer Technologies?

19

Page 20: Direct Emission Measurements on Cast Iron Pipe

Any Questions?

20

Page 21: Direct Emission Measurements on Cast Iron Pipe

21