diris a40/a41 - socomec a40/a41 - ref.: 536 181 b gb 3 preliminary operations _____4 general...

28
DIRIS A40/A41 ETHERNET ® Operating instructions F GB D I NL E P

Upload: doancong

Post on 29-Jul-2018

244 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41ETHERNET®

Operating instructions

F GB D I NL E P

Page 2: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

2 DIRIS A40/A41 - Ref.: 536 181 B GB

Page 3: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

3DIRIS A40/A41 - Ref.: 536 181 B GB

PRELIMINARY OPERATIONS _________________________________________________________ 4 GENERAL INFORMATION _________________________________________________________ 4 INSTALLATION __________________________________________________________________________ 5 CONNECTION _____________________________________________________________________ 5 VISUAL DIAGNOSTIC _____________________________________________________________ 6PROGRAMMING ________________________________________________________________________ 7 ETHERNET CONFIGURATION ON DIRIS A40/A41 _______________________________ 7 IP ADDRESS _______________________________________________________________________ 8 MASK _____________________________________________________________________________11 GATEWAY _________________________________________________________________________11 DHCP _____________________________________________________________________________12 WEBSERVER _____________________________________________________________________13 ENVIRONMENTAL CONDITIONS AND TYPE OF TEST _________________________14 INTERFACE SPECIFICATIONS: SUPPLY ________________________________________14 RS485 _____________________________________________________________________________14 ETHERNET ________________________________________________________________________14COMMUNICATION _____________________________________________________________________15A : NEW COMMUNICATION TABLE FROM 01/2009 __________________________ 15 1 > TABLE C550 Hex : Main measurements allocated from current transformer

and voltage transformer values __________________________________________ 15 2 > TABLE C650 Hex : Energy monitoring _____________________________________ 16 3 > TABLE C750 Hex : Additional measurements allocated from current transformer and voltage transformer values __________________________________________ 16 4 > TABLE C850 Hex : Main measurements not allocated from current transformer

and voltage transformer values __________________________________________ 17 5 > TABLE C900Hex : Temperature measurements ______________________________ 18 6 > TABLE C950Hex : Harmonics ___________________________________________ 18 7>TABLEE000Hex:Primaryconfiguration ___________________________________ 24 8>TABLEE110Hex:Ethernetconfiguration __________________________________ 24 9>TABLEE200Hex:Ethernetconfiguration __________________________________ 26

Con

tent

s

GB

Page 4: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

4 DIRIS A40/A41 - Ref.: 536 181 B GB

PRELIMINARY OPERATIONS

•ETHERNET MODULE WITH MODBUS RTU GATEWAY – Ref. 48250204:

> MODBUS master gateway with RS485 3-point link with TCP.

> MODBUS TCP and MODBUS RTU protocols.>WEB-serverforproductconfiguration,displaying

the values and the diagnostics.

The gateway in this version enables the module to be used as a master gateway for a Jbus/Modbus network onRS485withamaximumof246slaves.Todothis,a Jbus/Modbus address other than 255 needs to be configured.

For personnel and product safety please read the contents of these operating instructions carefully before connecting.Check the following points as soon as you receive the DIRIS A40/A41 package:•thepackingisingoodcondition,

•theproducthasnotbeendamagedduringtransit,•the product reference number conforms to yourorder,

•thepackagecontainstheproductandtheoperatinginstructions.

FunctionsThe optional Ethernet module is linked to the DIRIS A40/A41(ref.48250201,48250202,48250207,48251201,48251202,4825U201,48250211,48250213,48250214)andenablesconnectionstobemadetoa10BaseTor 100BaseT type network. It also enables the DIRIS measurement units to be used and monitored from a PC or an API.

GENERAL INFORMATION

The module is available in 2 versions:•ETHERNET MODULE – Ref. 48250203:> Link to an RJ45 connection.> MODBUS TCP or MODBUS RTU Protocol with TCP.>WEB-serverforproductconfiguration,displayingthe

values and diagnostics.

TCP/IPEthernet Module

DIRIS A40/41@1

(maximum of 4 clients)Client 1

PC

Client 2

API

(maximum of 4 clients)

TCP/IP(RJ45)

MODBUS(RS485)

Ethernet Module

DIRIS A40/41@1

Client 1

PC

Client 2

API

ModuleRS485

DIRIS A40/41@2

ModuleRS485

DIRIS A40/41@3

Maximum of 246 slaves

Page 5: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

5DIRIS A40/A41 - Ref.: 536 181 B GB

GB

INSTALLATION

CONNECTION

4 Follow indications when connecting the termi-nal. Switch on voltage supply.

The DIRIS A40/A41 must be switched off

DIR

IS 3

42 A

1

DIR

IS 3

43 A

2 Fix the module in one of the four positions.

DIR

IS 3

47 A

3

ThemoduleisfittedontothebackoftheDIRIS A40/A41 in one of the 4 positions provided.

DIR

IS 3

47 A

Page 6: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

6 DIRIS A40/A41 - Ref.: 536 181 B GB

VISUAL DIAGNOSTIC

INSTALLATION

LED Colour Status Description

SYS - NOT LIT No internal electrical supplyFirmware is re-initialisingHardware is faulty

Yellow LIT Loadingphaseofthesoftware,waiting to start

FLASHING AT 1Hz Error during the start-up phase

Green LIT Operating system functioning

COM Red NOT LIT No errors

FLASHING Not used

LIT Internal JBUS error

Green NOT LIT See red LED

FLASHING JBUS external error

LIT Noerror,fullyfunctional

Link Green NOT LIT No connection to the Ethernet network

LIT Ethernet Network connected

Activity Yellow FLASHING Sending/receiving Ethernet frames

> LED indicators

Page 7: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

7DIRIS A40/A41 - Ref.: 536 181 B GB

GB

PROGRAMMING

ETHERNET CONFIGURATION ON DIRIS A40/A41

This involves setting up the IP parameters for the DIRIS connected to the gateway

IP address (Rth Adr IP) : [CLASS A].[CLASS B].[CLASS C].[CLASS D]Subnet mask (Eth MASH) : [CLASS A].[CLASS B].[CLASS C].[CLASS D]Gateway (Eth GATE) : [CLASS A].[CLASS B].[CLASS C].[CLASS D]DHCP activation (Eth DHCP) : Yes/ No

The factory setting is:

• IP address: 192.168.1.1• Subnet mask: 255.255.255.0• Gateway: 0.0.0.0• DHCP activation: NO

x 4

x 4

x 4

x 1

Page 8: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

8 DIRIS A40/A41 - Ref.: 536 181 B GB

PROGRAMMING

ADRESSE IP :

> For example: Programming the address 191.158.1.7 CLASS A = 191

x 1

x 3

x 1

Page 9: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

9DIRIS A40/A41 - Ref.: 536 181 B GB

GB

ADRESSE IP :

> For example: Programming the address 191.158.1.7 CLASS D = 158

PROGRAMMING

x 2

x 1

x 1

Page 10: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

10 DIRIS A40/A41 - Ref.: 536 181 B GB

PROGRAMMING

ADRESSE IP :

> For example: Programming the address 191.158.1.7 CLASS C = 1

x 6

> For example: Programming the address 191.158.1.7 CLASS C = 7

x 3

x 3

x 1

Page 11: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

11DIRIS A40/A41 - Ref.: 536 181 B GB

GB

PROGRAMMING

MASQUE:

> For example: 255.255.255.0 The principle is the same as for the IP address

x 4

x 4

GATEWAY:

> For example: 0.0.0.0 The principle is the same as for the IP address

Page 12: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

12 DIRIS A40/A41 - Ref.: 536 181 B GB

PROGRAMMING

DHCP :

> WARNING: The DHCP function is not recommended. Contact your IT networks administrator.

x 1

x 1

x 1

Page 13: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

13DIRIS A40/A41 - Ref.: 536 181 B GB

GB

PROGRAMMING

WEBSERVER

> The Webserver can be accessed by entering the product’s IP address into your internet browser.

For example:IP address of the DIRIS : 192.168.1.0URL address: http://192.168.1.0/index.htm

The Web server makes the following available:- The main DIRIS database parameters.- The main instant and average meter readings.

Page 14: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

14 DIRIS A40/A41 - Ref.: 536 181 B GB

ENVIRONMENTAL CONDITIONS AND TYPE OF TEST

Description Standard Level

Electrostatic discharge IEC 61000-4-2 4 kV contact8 kV air

Modulated A electromagnetic radiation

IEC 61000-4-3 10V/m(80MHz–1GHz)3V/m(1,4GHz–2GHz)1V/m(2,0GHz–2,7GHz)

Magneticfields frequency factor

IEC 61000-4-8 50 Hz / 60 Hz30 A/m

Rapid transients in bursts IEC 61000-4-4 1 kV

Impulsewaves(lightning) IEC 61000-4-5 1 kV

Injection of HF current IEC 61000-4-6 150 KHz – 80 MHz80%AM,1KHzsinusoidalwave1,5x10E-3decade/s3 V

> Electromagnetic compatibility:

Operational temperature -25 to +70°C

Storage temperature -40 to +70°C

> Environmental:

Supply voltage (from the DIRIS) + 9 VDC

Consumption Between 1.3 and 1.7 W

INTERFACE SPECIFICATIONS: SUPPLY

Electricalspecification RJ45 Norme IEE3-wire

Transmission speed 10MBits/s or 100MBits/s

Protocol Modbus/TCP or Jbus/Modbus RTU with TCP

ETHERNET

Electricalspecification RS485 EIA3-wire half duplex

Transmission speed 38,4kBit/s

Stop bit 2

Parity without

Maximum number of slaves 246

RS485

PROGRAMMING

UL-CSA APPROVAL

Standard UL 61010-1 CSA-C22.2 No. 61010-1

Certificate ULfileNo:E257746

Page 15: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

15DIRIS A40/A41 - Ref.: 536 181 B GB

GB

COMMUNICATION

A : NEW COMMUNICATION TABLE FROM 01/2009These new tables are available for all new Socomec products on sale from January 2009. The aim is to have common tables for common values, irrespective of the Socomec product. We recommend that you use these new tables whe-never possible for developing your applications.

1 > TABLE C550 Hex : Main measurements allocated from CT (current transformer) and VT (voltage transformer) values

Decimal Hex. No. of Description Unit JBUS function address address words available

50512 C550 2 hour meter 1/100 h 350514 C552 2 phase to phase voltage U12 V/100 350516 C554 2 phase to phase voltage U23 V/100 350518 C556 2 phase to phase voltage U31 V/100 350520 C558 2 phase to neutral voltage phase 1 V/100 350522 C55A 2 phase to neutral voltage phase 2 V/100 350524 C55C 2 phase to neutral voltage phase 3 V/100 350526 C55E 2 frequency Hz/100 350528 C560 2 phase current 1 mA 350530 C562 2 phase current 2 mA 350532 C564 2 phase current 3 mA 350534 C566 2 neutral current mA 350536 C568 2 Σ active power +/- kW/100 350538 C56A 2 Σ reactive power +/- kvar/100 350540 C56C 2 Σ apparent power kVA/100 350542 C56E 2 Σpowerfactor-:leadingand+:lagging 0,001 350544 C570 2 active power phase 1 +/- kW/100 350546 C572 2 active power phase 2 +/- kW/100 350548 C574 2 active power phase 3 +/- kW/100 350550 C576 2 reactive power phase 1 +/- kvar/100 350552 C578 2 reactive power phase 2 +/- kvar/100 350554 C57A 2 reactive power phase 3 +/- kvar/100 350556 C57C 2 apparent power phase 1 kVA/100 350558 C57E 2 apparent power phase 2 kVA/100 350560 C580 2 apparent power phase 3 kVA/100 350562 C582 2 powerfactorphase1-:leadingand+:lagging 0,001 350564 C584 2 powerfactorphase2-:leadingand+:lagging 0,001 350566 C586 2 powerfactorphase3-:leadingand+:lagging 0,001 350568 C588 2 Reserved for manufacturer - 350570 C58A 2 Reserved for manufacturer - 350572 C58C 2 Reserved for manufacturer - 3

Page 16: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

16 DIRIS A40/A41 - Ref.: 536 181 B GB

COMMUNICATION

A : NEW COMMUNICATION TABLE FROM 01/20092 > TABLE C650 Hex : Energy monitoring

Decimal Hex. No. of Description Unit JBUS function address address words available

50768 C650 2 hour meter 1/100 h 350770 C652 2 Reserved for manufacturer - 350772 C654 2 Reserved for manufacturer - 350774 C656 2 Reserved for manufacturer - 350776 C658 2 Reserved for manufacturer - 350778 C65A 2 Reserved for manufacturer - 350770 C652 2 active energy + kWh 350772 C654 2 reactive energy + kvarh 350774 C656 2 apparent apparente kVAh 350776 C658 2 active energy - kWh 350778 C65A 2 active energy + kWh 350780 C65C 2 No. Compteurs d’Impulsions - 350782 C65E 2 pulse meter 1 - 350784 C660 2 pulse meter 2 - 350786 C662 2 pulse meter 3 - 350788 C664 2 pulse meter 4 - 350790 C666 2 pulse meter 5 - 350792 C668 2 pulse meter 6 - 350794 C66A 2 Reserved for manufacturer - 350796 C66C 2 Reserved for manufacturer - 350798 C66E 2 Reserved for manufacturer - 350800 C670 2 Reserved for manufacturer - 350802 C672 2 S Predicted active power kW/100 350804 C674 2 S Predicted reactive power kvar/100 350806 C676 2 S Predicted apparent power kVA/100 350808 C678 2 Ea+ between2tops 0,1Ws 350810 C67A 2 Ea- between2tops 0,1Ws 350812 C67C 2 Er+ between2tops 0,1vars 350814 C67E 2 Er- between2tops 0,1vars 350816 C680 2 Reserved for manufacturer - 350816 C680 1 Reserved for manufacturer - 350817 C681 1 Reserved for manufacturer - 3

3 > TABLE C750 Hex : Additional measurements allocated from CT values (current transformer) and VT (voltage transformer) values

Decimal Hex. No. of Description Unit JBUS function address address words available

51024 C750 2 avg U12 V/100 351026 C752 2 avg U23 V/100 351028 C754 2 avg U31 V/100 351030 C756 2 avg V1 V/100 351032 C758 2 avg V2 V/100 351034 C75A 2 avg V3 V/100 351036 C75C 2 avg F Hz/100 351038 C75E 2 avg I1 mA 351040 C760 2 avg I2 mA 351042 C762 2 avg I3 mA 351044 C764 2 avg In mA 351046 C766 2 avg Σ active power + kW/100 351048 C768 2 avg Σ active power - kW/100 351050 C76A 2 avg Σ reactive power + kvar/100 351052 C76C 2 avg Σ reactive power - kvar/100 351054 C76E 2 avg Σ apparent power kVA/100 351056 C770 2 max/avg U12 V/100 3

Page 17: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

17DIRIS A40/A41 - Ref.: 536 181 B GB

GB

COMMUNICATION

Decimal Hex. No. of Description Unit JBUS function address address words available

51058 C772 2 max/avg U23 V/100 351060 C774 2 max/avg U31 V/100 351062 C776 2 max/avg V1 V/100 351064 C778 2 max/avg V2 V/100 351066 C77A 2 max/avg V3 V/100 351068 C77C 2 max/avg F Hz/100 351070 C77E 2 max/avg I1 mA 351072 C780 2 max/avg I2 mA 351074 C782 2 max/avg I3 mA 351076 C784 2 max/avg In mA 351078 C786 2 max/avg Σ active power + kW/100 351080 C788 2 max/avg Σ active power - kW/100 351082 C78A 2 max/avg Σ reactive power + kvar/100 351084 C78C 2 max/avg Σ reactive power - kvar/100 351086 C78E 2 max/avg Σ apparent power kVA/100 351088 C790 1 Reserved for manufacturer - 351089 C791 1 Reserved for manufacturer - 351090 C792 1 Reserved for manufacturer - 351091 C793 1 Reserved for manufacturer - 351092 C794 1 Reserved for manufacturer - 351093 C795 1 Reserved for manufacturer - 3

A : NEW COMMUNICATION TABLE FROM 01/20093 > TABLE C750 Hex (continued)

Decimal Hex. No. of Description Unit JBUS function address address words available

51280 C850 1 hour meter h 351281 C851 1 phase to phase voltage U12 V/100 351282 C852 1 phase to phase voltage U23 V/100 351283 C853 1 phase to phase voltage U31 V/100 351284 C854 1 phase to neutral voltage 1 V/100 351285 C855 1 phase to neutral voltage 2 V/100 351286 C856 1 phase to neutral voltage 3 V/100 351287 C857 1 frequency Hz/100 351288 C858 1 phase current 1 mA 351289 C859 1 phase current 3 mA 351291 C85B 1 neutral current mA 351292 C85C 1 Σ active power +/- kW/100 351293 C85D 1 Σ reactive power +/- kvar/100 351294 C85E 1 Σ apparent power +/- kVA/100 351295 C85F 1 Σ power factor L/C -:

leadingand+:lagging 0,001 351296 C860 1 phase active power 1 +/- kW/100 351297 C861 1 phase active power 2 +/- kW/100 351298 C862 1 phase active power 3 +/- kW/100 351299 C863 1 phase reactive power 1 +/- kvar/100 351300 C864 1 phase reactive power 2 +/- kvar/100 351301 C865 1 phase reactive power 3 +/- kvar/100 351302 C866 1 phase apparent power 1 kVA/100 351303 C867 1 phase apparent power 2 kVA/100 351304 C868 1 phase apparent power 3 kVA/100 3

4 > TABLE C850 Hex : Main measurements not allocated from CT values (current transformer) and VT (voltage transformer) valuesCAUTION : using this table involves multiplying values by transformation ratios.

Page 18: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

18 DIRIS A40/A41 - Ref.: 536 181 B GB

COMMUNICATION

A : NEW COMMUNICATION TABLE FROM 01/20094 > TABLE C850 Hex (continued)

Decimal Hex. No. of Description Unit JBUS function address address words available

51305 C869 1 phase power factor 1 -: leadingand+:lagging 0,001 3

51306 C86A 1 phase power factor 2 -: leadingand+:lagging 0,001 3

51307 C86B 1 phase power factor 3 -: leadingand+:lagging 0,001 3

51308 C86C 1 Reserved for manufacturer - 351309 C86D 1 Reserved for manufacturer - 351310 C86E 1 Reserved for manufacturer - 351311 C86F 1 Ea+ MWh 351312 C870 1 Reserved for manufacturer - 351313 C871 1 ER+ MWh 3

5 > TABLE C900Hex : Temperature measurements

Decimal Hex. No. of Description Unit JBUS function address address words available

51456 C900 1 Internal temperature sensor present 0 : no - 1 : yes - 351457 C901 1 Temperature module °C 351458 C902 1 Externaltemperaturesensors(1to5max) - 351459 C903 1 extern temperature 1 °C 351460 C904 1 extern temperature 2 °C 351461 C905 1 extern temperature 3 °C 351462 C906 1 Reserved for manufacturer - 351463 C907 1 Reserved for manufacturer - 3

6 > TABLE C950Hex : Harmonics

Decimal Hex. No. of Description Unit JBUS function address address words available

THD 51536 C950 1 thdU12 0,001 351537 C951 1 thdU23 0,001 351538 C952 1 thdU31 0,001 351539 C953 1 thdV1 0,001 351540 C954 1 thdV2 0,001 351541 C955 1 thdV3 0,001 351542 C956 1 thdI1 0,001 351543 C957 1 thdI2 0,001 351544 C958 1 thdI3 0,001 351545 C959 1 thdIn 0,001 3 Current 51546 C95A 1 Max rank 351547 C95B 1 HarmonicI1row3 0,001 351548 C95C 1 HarmonicI2row3 0,001 351549 C95D 1 HarmonicI3row3 0,001 351550 C95E 1 HarmonicINrow3 0,001 351551 C95F 1 HarmonicI1row5 0,001 351552 C960 1 HarmonicI2row5 0,001 351553 C961 1 HarmonicI3row5 0,001 351554 C962 1 HarmonicINrow5 0,001 351555 C963 1 HarmonicI1row7 0,001 3

Page 19: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

19DIRIS A40/A41 - Ref.: 536 181 B GB

GB

COMMUNICATION

Decimal Hex. No. of Description Unit JBUS function address address words available51556 C964 1 HarmonicI2row7 0,001 351557 C965 1 HarmonicI3row7 0,001 351558 C966 1 HarmonicINrow7 0,001 351559 C967 1 HarmonicI1row9 0,001 351560 C968 1 HarmonicI2row9 0,001 351561 C969 1 HarmonicI3row9 0,001 351562 C96A 1 HarmonicINrow9 0,001 351563 C96B 1 HarmonicI1row11 0,001 351564 C96C 1 HarmonicI2row11 0,001 351565 C96D 1 HarmonicI3row11 0,001 351566 C96E 1 HarmonicINrow11 0,001 351567 C96F 1 HarmonicI1row13 0,001 351568 C970 1 HarmonicI2row13 0,001 351569 C971 1 HarmonicI3row13 0,001 351570 C972 1 HarmonicINrow13 0,001 351571 C973 1 HarmonicI1row15 0,001 351572 C974 1 HarmonicI2row15 0,001 351573 C975 1 HarmonicI3row15 0,001 351574 C976 1 HarmonicINrow15 0,001 351575 C977 1 HarmonicI1row17 0,001 351576 C978 1 HarmonicI2row17 0,001 351577 C979 1 HarmonicI3row17 0,001 351578 C97A 1 HarmonicINrow17 0,001 351579 C97B 1 HarmonicI1row19 0,001 351580 C97C 1 HarmonicI2row19 0,001 351581 C97D 1 HarmonicI3row19 0,001 351582 C97E 1 HarmonicINrow19 0,001 351583 C97F 1 HarmonicI1row21 0,001 351584 C980 1 HarmonicI2row21 0,001 351585 C981 1 HarmonicI3row21 0,001 351586 C982 1 HarmonicINrow21 0,001 351587 C983 1 HarmonicI1row23 0,001 351588 C984 1 HarmonicI2row23 0,001 351589 C985 1 HarmonicI3row23 0,001 351590 C986 1 HarmonicINrow23 0,001 351591 C987 1 HarmonicI1row25 0,001 351592 C988 1 HarmonicI2row25 0,001 351593 C989 1 HarmonicI3row25 0,001 351594 C98A 1 HarmonicINrow25 0,001 351595 C98B 1 HarmonicI1row27 0,001 351596 C98C 1 HarmonicI2row27 0,001 351597 C98D 1 HarmonicI3row27 0,001 351598 C98E 1 HarmonicINrow27 0,001 351599 C98F 1 HarmonicI1row29 0,001 351600 C990 1 HarmonicI2row29 0,001 351601 C991 1 HarmonicI3row29 0,001 351602 C992 1 HarmonicINrow29 0,001 351603 C993 1 HarmonicI1row31 0,001 351604 C994 1 HarmonicI2row31 0,001 351605 C995 1 HarmonicI3row31 0,001 351606 C996 1 HarmonicINrow31 0,001 351607 C997 1 HarmonicI1row33 0,001 351608 C998 1 HarmonicI2row33 0,001 351609 C999 1 HarmonicI3row33 0,001 3

A : NEW COMMUNICATION TABLE FROM 01/20096 > TABLE C950Hex (continued)

Page 20: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

20 DIRIS A40/A41 - Ref.: 536 181 B GB

COMMUNICATION

A : NEW COMMUNICATION TABLE FROM 01/20096 > TABLE C950Hex (continued)

Decimal Hex. No. of Description Unit JBUS function address address words available51610 C99A 1 HarmonicINrow33 0,001 351611 C99B 1 HarmonicI1row35 0,001 351612 C99C 1 HarmonicI2row35 0,001 351613 C99D 1 HarmonicI3row35 0,001 351614 C99E 1 HarmonicINrow35 0,001 351615 C99F 1 HarmonicI1row37 0,001 351616 C9A0 1 HarmonicI2row37 0,001 351617 C9A1 1 HarmonicI3row37 0,001 351618 C9A2 1 HarmonicINrow37 0,001 351619 C9A3 1 HarmonicI1row39 0,001 351620 C9A4 1 HarmonicI2row39 0,001 351621 C9A5 1 HarmonicI3row39 0,001 351622 C9A6 1 HarmonicINrow39 0,001 351623 C9A7 1 HarmonicI1row41 0,001 351624 C9A8 1 HarmonicI2row41 0,001 351625 C9A9 1 HarmonicI3row41 0,001 351626 C9AA 1 HarmonicINrow41 0,001 351627 C9AB 1 HarmonicI1row43 0,001 351628 C9AC 1 HarmonicI2row43 0,001 351629 C9AD 1 HarmonicI3row43 0,001 351630 C9AE 1 HarmonicINrow43 0,001 351631 C9AF 1 HarmonicI1row45 0,001 351632 C9B0 1 HarmonicI2row45 0,001 351633 C9B1 1 HarmonicI3row45 0,001 351634 C9B2 1 HarmonicINrow45 0,001 351635 C9B3 1 HarmonicI1row47 0,001 351636 C9B4 1 HarmonicI2row47 0,001 351637 C9B5 1 HarmonicI3row47 0,001 351638 C9B6 1 HarmonicINrow47 0,001 351639 C9B7 1 HarmonicI1row49 0,001 351640 C9B8 1 HarmonicI2row49 0,001 351641 C9B9 1 HarmonicI3row49 0,001 351642 C9BA 1 HarmonicINrow49 0,001 351643 C9BB 1 HarmonicI1row51 0,001 351644 C9BC 1 HarmonicI2row51 0,001 351645 C9BD 1 HarmonicI3row51 0,001 351646 C9BE 1 HarmonicINrow51 0,001 351647 C9BF 1 HarmonicI1row53 0,001 351648 C9C0 1 HarmonicI2row53 0,001 351649 C9C1 1 HarmonicI3row53 0,001 351650 C9C2 1 HarmonicINrow53 0,001 351651 C9C3 1 HarmonicI1row55 0,001 351652 C9C4 1 HarmonicI2row55 0,001 351653 C9C5 1 HarmonicI3row55 0,001 351654 C9C6 1 HarmonicINrow55 0,001 351655 C9C7 1 HarmonicI1row57 0,001 351656 C9C8 1 HarmonicI2row57 0,001 351657 C9C9 1 HarmonicI3row57 0,001 351658 C9CA 1 HarmonicINrow57 0,001 351659 C9CB 1 HarmonicI1row59 0,001 351660 C9CC 1 HarmonicI2row59 0,001 351661 C9CD 1 HarmonicI3row59 0,001 351662 C9CE 1 HarmonicINrow59 0,001 351663 C9CF 1 HarmonicI1row61 0,001 3

Page 21: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

21DIRIS A40/A41 - Ref.: 536 181 B GB

GB

COMMUNICATION

Decimal Hex. No. of Description Unit JBUS function address address words available51664 C9D0 1 HarmonicI2row61 0,001 351665 C9D1 1 HarmonicI3row61 0,001 351666 C9D2 1 HarmonicINrow61 0,001 351667 C9D3 1 HarmonicI1row63 0,001 351668 C9D4 1 HarmonicI2row63 0,001 351669 C9D5 1 HarmonicI3row63 0,001 351670 C9D6 1 HarmonicINrow63 0,001 3 Phase to phase voltage51671 C9D7 1 Max rank 351672 C9D8 1 HarmonicU12row3 0,001 351673 C9D9 1 HarmonicU23row3 0,001 351674 C9DA 1 HarmonicU31row3 0,001 351675 C9DB 1 HarmonicU12row5 0,001 351676 C9DC 1 HarmonicU23row5 0,001 351677 C9DD 1 HarmonicU31row5 0,001 351678 C9DE 1 HarmonicU12row7 0,001 351679 C9DF 1 HarmonicU23row7 0,001 351680 C9E0 1 HarmonicU31row7 0,001 351681 C9E1 1 HarmonicU12row9 0,001 351682 C9E2 1 HarmonicU23row9 0,001 351683 C9E3 1 HarmonicU31row9 0,001 351684 C9E4 1 HarmonicU12row11 0,001 351685 C9E5 1 HarmonicU23row11 0,001 351686 C9E6 1 HarmonicU31row11 0,001 351687 C9E7 1 HarmonicU12row13 0,001 351688 C9E8 1 HarmonicU23row13 0,001 351689 C9E9 1 HarmonicU31row13 0,001 351690 C9EA 1 HarmonicU12row15 0,001 351691 C9EB 1 HarmonicU23row15 0,001 351692 C9EC 1 HarmonicU31row15 0,001 351693 C9ED 1 HarmonicU12row17 0,001 351694 C9EE 1 HarmonicU23row17 0,001 351695 C9EF 1 HarmonicU31row17 0,001 351696 C9F0 1 HarmonicU12row19 0,001 351697 C9F1 1 HarmonicU23row19 0,001 351698 C9F2 1 HarmonicU31row19 0,001 351699 C9F3 1 HarmonicU12row21 0,001 351700 C9F4 1 HarmonicU23row21 0,001 351701 C9F5 1 HarmonicU31row21 0,001 351702 C9F6 1 HarmonicU12row23 0,001 351703 C9F7 1 HarmonicU23row23 0,001 351704 C9F8 1 HarmonicU31row23 0,001 351705 C9F9 1 HarmonicU12row25 0,001 351706 C9FA 1 HarmonicU23row25 0,001 351707 C9FB 1 HarmonicU31row25 0,001 351708 C9FC 1 HarmonicU12row27 0,001 351709 C9FD 1 HarmonicU23row27 0,001 351710 C9FE 1 HarmonicU31row27 0,001 351711 C9FF 1 HarmonicU12row29 0,001 351712 CA00 1 HarmonicU23row29 0,001 351713 CA01 1 HarmonicU31row29 0,001 351714 CA02 1 HarmonicU12row31 0,001 351715 CA03 1 HarmonicU23row31 0,001 351716 CA04 1 HarmonicU31row31 0,001 3

A : NEW COMMUNICATION TABLE FROM 01/20096 > TABLE C950Hex (continued)

Page 22: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

22 DIRIS A40/A41 - Ref.: 536 181 B GB

COMMUNICATION

A : NEW COMMUNICATION TABLE FROM 01/20096 > TABLE C950Hex (continued)

Decimal Hex. No. of Description Unit JBUS function address address words available51717 CA05 1 HarmonicU12row33 0,001 351718 CA06 1 HarmonicU23row33 0,001 351719 CA07 1 HarmonicU31row33 0,001 351720 CA08 1 HarmonicU12row35 0,001 351721 CA09 1 HarmonicU23row35 0,001 351722 CA0A 1 HarmonicU31row35 0,001 351723 CA0B 1 HarmonicU12row37 0,001 351724 CA0C 1 HarmonicU23row37 0,001 351725 CA0D 1 HarmonicU31row37 0,001 351726 CA0E 1 HarmonicU12row39 0,001 351727 CA0F 1 HarmonicU23row39 0,001 351728 CA10 1 HarmonicU31row39 0,001 351729 CA11 1 HarmonicU12row41 0,001 351730 CA12 1 HarmonicU23row41 0,001 351731 CA13 1 HarmonicU31row41 0,001 351732 CA14 1 HarmonicU12row43 0,001 351733 CA15 1 HarmonicU23row43 0,001 351734 CA16 1 HarmonicU31row43 0,001 351735 CA17 1 HarmonicU12row45 0,001 351736 CA18 1 HarmonicU23row45 0,001 351737 CA19 1 HarmonicU31row45 0,001 351738 CA1A 1 HarmonicU12row47 0,001 351739 CA1B 1 HarmonicU23row47 0,001 351740 CA1C 1 HarmonicU31row47 0,001 351741 CA1D 1 HarmonicU12row49 0,001 351742 CA1E 1 HarmonicU23row49 0,001 351743 CA1F 1 HarmonicU31row49 0,001 351744 CA20 1 HarmonicU12row51 0,001 351745 CA21 1 HarmonicU23row51 0,001 351746 CA22 1 HarmonicU31row51 0,001 351747 CA23 1 HarmonicU12row53 0,001 351748 CA24 1 HarmonicU23row53 0,001 351749 CA25 1 HarmonicU31row53 0,001 351750 CA26 1 HarmonicU12row55 0,001 351751 CA27 1 HarmonicU23row55 0,001 351752 CA28 1 HarmonicU31row55 0,001 351753 CA29 1 HarmonicU12row57 0,001 351754 CA2A 1 HarmonicU23row57 0,001 351755 CA2B 1 HarmonicU31row57 0,001 351756 CA2C 1 HarmonicU12row59 0,001 351757 CA2D 1 HarmonicU23row59 0,001 351758 CA2E 1 HarmonicU31row59 0,001 351759 CA2F 1 HarmonicU12row61 0,001 351760 CA30 1 HarmonicU23row61 0,001 351761 CA31 1 HarmonicU31row61 0,001 351762 CA32 1 HarmonicU12row63 0,001 351763 CA33 1 HarmonicU23row63 0,001 351764 CA34 1 HarmonicU31row63 0,001 3 Phase to neutral voltage51765 CA35 1 Max rank 351766 CA36 1 HarmonicV1row3 0,001 351767 CA37 1 HarmonicV2row3 0,001 351768 CA38 1 HarmonicV3row3 0,001 351769 CA39 1 HarmonicV1row5 0,001 3

Page 23: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

23DIRIS A40/A41 - Ref.: 536 181 B GB

GB

COMMUNICATION

Decimal Hex. No. of Description Unit JBUS function address address words available51770 CA3A 1 HarmonicV2row5 0,001 351771 CA3B 1 HarmonicV3row5 0,001 351772 CA3C 1 HarmonicV1row7 0,001 351773 CA3D 1 HarmonicV2row7 0,001 351774 CA3E 1 HarmonicV3row7 0,001 351775 CA3F 1 HarmonicV1row9 0,001 351776 CA40 1 HarmonicV2row9 0,001 351777 CA41 1 HarmonicV3row9 0,001 351778 CA42 1 HarmonicV1row11 0,001 351779 CA43 1 HarmonicV2row11 0,001 351780 CA44 1 HarmonicV3row11 0,001 351781 CA45 1 HarmonicV1row13 0,001 351782 CA46 1 HarmonicV2row13 0,001 351783 CA47 1 HarmonicV3row13 0,001 351784 CA48 1 HarmonicV1row15 0,001 351785 CA49 1 HarmonicV2row15 0,001 351786 CA4A 1 HarmonicV3row15 0,001 351787 CA4B 1 HarmonicV1row17 0,001 351788 CA4C 1 HarmonicV2row17 0,001 351789 CA4D 1 HarmonicV3row17 0,001 351790 CA4E 1 HarmonicV1row19 0,001 351791 CA4F 1 HarmonicV2row19 0,001 351792 CA50 1 HarmonicV3row19 0,001 351793 CA51 1 HarmonicV1row21 0,001 351794 CA52 1 HarmonicV2row21 0,001 351795 CA53 1 HarmonicV3row21 0,001 351796 CA54 1 HarmonicV1row23 0,001 351797 CA55 1 HarmonicV2row23 0,001 351798 CA56 1 HarmonicV3row23 0,001 351799 CA57 1 HarmonicV1row25 0,001 351800 CA58 1 HarmonicV2row25 0,001 351801 CA59 1 HarmonicV3row25 0,001 351802 CA5A 1 HarmonicV1row27 0,001 351803 CA5B 1 HarmonicV2row27 0,001 351804 CA5C 1 HarmonicV3row27 0,001 351805 CA5D 1 HarmonicV1row29 0,001 351806 CA5E 1 HarmonicV2row29 0,001 351807 CA5F 1 HarmonicV3row29 0,001 351808 CA60 1 HarmonicV1row31 0,001 351809 CA61 1 HarmonicV2row31 0,001 351810 CA62 1 HarmonicV3row31 0,001 351811 CA63 1 HarmonicV1row33 0,001 351812 CA64 1 HarmonicV2row33 0,001 351813 CA65 1 HarmonicV3row33 0,001 351814 CA66 1 HarmonicV1row35 0,001 351815 CA67 1 HarmonicV2row35 0,001 351816 CA68 1 HarmonicV3row35 0,001 351817 CA69 1 HarmonicV1row37 0,001 351818 CA6A 1 HarmonicV2row37 0,001 351819 CA6B 1 HarmonicV3row37 0,001 351820 CA6C 1 HarmonicV1row39 0,001 351821 CA6D 1 HarmonicV2row39 0,001 351822 CA6E 1 HarmonicV3row39 0,001 351823 CA6F 1 HarmonicV1row41 0,001 3

A : NEW COMMUNICATION TABLE FROM 01/20096 > TABLE C950Hex (continued)

Page 24: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

24 DIRIS A40/A41 - Ref.: 536 181 B GB

COMMUNICATION

A : NEW COMMUNICATION TABLE FROM 01/20096 > TABLE C950Hex (continued)

Decimal Hex. No. of Description Unit JBUS function address address words available51824 CA70 1 HarmonicV2row41 0,001 351825 CA71 1 HarmonicV3row41 0,001 351826 CA72 1 HarmonicV1row43 0,001 351827 CA73 1 HarmonicV2row43 0,001 351828 CA74 1 HarmonicV3row43 0,001 351829 CA75 1 HarmonicV1row45 0,001 351830 CA76 1 HarmonicV2row45 0,001 351831 CA77 1 HarmonicV3row45 0,001 351832 CA78 1 HarmonicV1row47 0,001 351833 CA79 1 HarmonicV2row47 0,001 351834 CA7A 1 HarmonicV3row47 0,001 351835 CA7B 1 HarmonicV1row49 0,001 351836 CA7C 1 HarmonicV2row49 0,001 351837 CA7D 1 HarmonicV3row49 0,001 351838 CA7E 1 HarmonicV1row51 0,001 351839 CA7F 1 HarmonicV2row51 0,001 351840 CA80 1 HarmonicV3row51 0,001 351841 CA81 1 HarmonicV1row53 0,001 351842 CA82 1 HarmonicV2row53 0,001 351843 CA83 1 HarmonicV3row53 0,001 351844 CA84 1 HarmonicV1row55 0,001 351845 CA85 1 HarmonicV2row55 0,001 351846 CA86 1 HarmonicV3row55 0,001 351847 CA87 1 HarmonicV1row57 0,001 351848 CA88 1 HarmonicV2row57 0,001 351849 CA89 1 HarmonicV3row57 0,001 351850 CA8A 1 HarmonicV1row59 0,001 351851 CA8B 1 HarmonicV2row59 0,001 351852 CA8C 1 HarmonicV3row59 0,001 351853 CA8D 1 HarmonicV1row61 0,001 351854 CA8E 1 HarmonicV2row61 0,001 351855 CA8F 1 HarmonicV3row61 0,001 351856 CA90 1 HarmonicV1row63 0,001 351857 CA91 1 HarmonicV2row63 0,001 351858 CA92 1 HarmonicV3row63 0,001 3

7 > TABLE E000 Hex : Primary configuration

Decimal Hex. No. of Description Unit JBUS function address address words available

57344 E000 1 Network type : 0 : 1BL 1 : 2BL 2 : 3BL 3 : 3NBL 4 : 4BL 5 : 4NBL – 3; 6; 1657345 E001 1 CT secondary : 1: 1 A 5: 5 A A 3; 6; 1657346 E002 1 CT primary A 3; 6; 1657347 E003 1 Neutral current input on CT : 0 : No 1: Yes – 3; 6; 1657348 E004 1 CTN secondary : 1: 1 A 5: 5 A A 3; 6; 1657349 E005 1 CTN primary A 3; 6; 1657350 E006 1 Voltage input on TP : 0 : No 1: Yes – 3; 6; 16

Page 25: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

25DIRIS A40/A41 - Ref.: 536 181 B GB

GB

COMMUNICATION

Decimal Hex. No. of Description Unit JBUS function address address words available

57351 E007 1 TP secondary : 60 : 60 V 100 : 100 V 110 : 110 V 115 : 115 V 120 : 120 V 173 : 173 V 190 : 190 V V 3; 6; 1657352 E008 2 TP primary V 3; 6; 1657354 E00A 1 Synchronisation start 0 : internal - 1 : external – 3; 6; 1657355 E00B 1 Internal synchronisation of mean powers P+/- Q+/- : 300 : 5mn - 480 : 8mn - 600 : 10mn 900 : 15mn - 1200 : 20mn - 1800 : 30mn s 3; 6; 16

A : NEW COMMUNICATION TABLE FROM 01/20097 > TABLE E000 Hex (continued)

Decimal Hex. No. of Description Unit JBUS function address address words available57616 E110 1 EthernetAdressIPClassA(0-255) – 3;6;1657617 E111 1 EthernetAdressIPClassB(0-255) – 3;6;1657618 E112 1 EthernetAdressIPClassC(0-255) – 3;6;1657619 E113 1 EthernetAdressIPClassD(0-255) – 3;6;1657620 E114 1 EthernetGATEClassA(0-255) – 3;6;1657621 E115 1 EthernetGATEClassB(0-255) – 3;6;1657622 E116 1 EthernetGATEClassC(0-255) – 3;6;1657623 E117 1 EthernetGATEClassD(0-255) – 3;6;1657624 E118 1 EthernetMASKClassA(0-255) – 3;6;1657625 E119 1 EthernetMASKClassB(0-255) – 3;6;1657626 E11A 1 EthernetMASKClassC(0-255) – 3;6;1657627 E11B 1 EthernetMASKClassD(0-255) – 3;6;1657628 E11C 1 Use of DHCP

0 : No - 1 : Yes – 3; 6; 1657629 E11D 1 Reserved for manufacturer – 3; 6; 1657630 E11E 1 JBUS RTU over Ethernet 0 : No - 1 ; Yes – 3; 6; 1657631 E11F 1 JBUS/MODBUS gateway speed > Ethernet 0 = 2400 bps - 1 = 4800 bps - 2 = 9600 bps

3 = 19200 bps - 4 = 38400 bps – 3; 6; 1657632 E120 1 JBUS/MODBUS gateway parity > Ethernet 0 = none 0 = none

1 = even 1 = even 2 = odd 2 = odd

57633 E121 1 JBUS/MODBUS gateway stop bits > Ethernet - 3; 6; 1657634 E122 1 Time out Jbus / Modbus > Ethernet 500 ms 3; 6; 1657635 E123 1 JBUSslaveaddress(RS485&RTUoverEthernet) 1-247 3;6;16

8 > TABLE E110 Hex : Ethernet configuration

Page 26: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

26 DIRIS A40/A41 - Ref.: 536 181 B GB

COMMUNICATION

A : NEW COMMUNICATION TABLE FROM 01/20099 > TABLE E200 Hex : Ethernet configuration

Decimal Hex. No. of Description Unit JBUS function address address words available

57856 E200 1 Action : 0xA1:Eeprombackupconfiguration 0xB2 : Product Reset - 6; 16

Page 27: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

DIRIS A40/A41 - RS485 - ETHERNET®

27DIRIS A40/A41 - Ref.: 536 181 B GB

GB

NOTES

Page 28: DIRIS A40/A41 - Socomec A40/A41 - Ref.: 536 181 B GB 3 PRELIMINARY OPERATIONS _____4 GENERAL INFORMATION ... ETHERNET CONFIGURATION ON DIRIS A40/A41 This involves setting up the IP

SOCOMEC - Ref.: 536 181 B GB - 06 / 12

DIR

IS 3

45 A

/ Q

UA

T N

OT

3i

VALID FOR FRANCE

www.socomec.com

hEAD OFFICE

SOCOMEC GROUPS.A. SOCOMEC capital 10 951 300 €R.C.S. Strasbourg B 548 500 149B.P. 60010 - 1, rue de Westhouse F-67235 Benfeld Cedex - FRANCE

InTERnATIOnAL SALES DEPARTMEnT

SOCOMEC1, rue de Westhouse - B.P. 60010 F - 67235 Benfeld Cedex - FRANCETel. +33 (0)3 88 57 41 41 Fax +33 (0)3 88 74 08 [email protected]

Socomec worldwide

In EUROPE

BELGIUMB - 1190 Brussel Tel. +32 (0)2 340 02 30 [email protected]

FRANCEF - 94132 Fontenay-sous-Bois Cedex Tel. +33 (0)1 45 14 63 30 [email protected]

GERMANYD - 76275 Ettlingen Tel. +49 (0)7243 65 29 2 0 [email protected]

ITALYI - 20098 San Giuliano Milanese (MI) Tel. +39 02 9849821 [email protected]

POLAND01-625 Warszawa Tel. +48 91 442 64 11 [email protected]

SLOVENIASI - 1000 Ljubljana Tel. +386 1 5807 860 [email protected]

SPAINE - 08310 Argentona (Barcelona) Tel. +34 93 741 60 67 [email protected]

ThE NEThERLANDSNL - 3991 CD Houten Tel. +31 (0)30 760 0901 [email protected]

TURKEY34775 Istanbul Tel. +90 (0) 216 540 71 20 [email protected]

In MIDDLE EAST

UNITED ARAB EMIRATESDubai, U.A.E. Tel. +971 (0) 4 29 98 441 [email protected]

non

con

trac

tual

doc

umen

t. ©

201

2, S

ocom

ec S

A. A

ll rig

hts

rese

rved

.

To h

elp

prot

ect t

he e

nviro

nmen

t, th

is d

ocum

ent h

as b

een

prin

ted

on P

EFC

pap

er (P

rogr

amm

e fo

r th

e E

ndor

sem

ent o

f For

est C

ertif

icat

ion)

ThE UnITED KInGDOM

SOCOMEC Ltd UK - Knowl Piece - Wilbury Way Hitchin Hertfordshire SG4 0TY Tel. 01462 440033 Fax 01462 431143 [email protected]

YOUR DISTRIBUTOR

In ASIA

NORTh EAST ASIAP.R.C 200052 Shanghai - China Tel. +86 (0)21 5298 9555 [email protected]

SOUTh EAST ASIA & PACIFICUBI TECHPARK - 408569 Singapore Tel. +65 65 07 94 90 [email protected]

SOUTh ASIA122001 Gurgaon, Haryana - India Tel. +91 124 4562 700 [email protected]

In nORTh AMERICA

USA, CANADA & MEXICOCambridge, MA 02142 USA Tel. +1 617 245 0447 [email protected]

• 4e_couv_SCP_2012_25092012.indd 7 12/10/12 16:48